16-2923ABOVE FACP
NAC#1 current is within the limitations of the circuit.`
NAC#2 current is within the limitations of the circuit.
NAC#3 current is within the limitations of the circuit.
NAC#4 current is within the limitations of the circuit.
MS 92000DLS Control Panel:
The output current is within the panel's limitations.
120 VAC 3#12 AWG THHN
ON HOUSE ELECTRICAL PANEL
WITH 20 AMP MAX CKT. BKR.
BREAKER WILL BE FOR
FIRE ALARM USE ONLY WITH
BREAKER LOCK.
ALARM PANELS
AND EQUIPMENT SHALL BE
GROUNDED IN ACCORDANCE
WITH M.E.C. ARTICLE 250
FIRE ALARM WIRE LEGEND
SYMBOL
DESCRIPTION
WIRE
D
DATA CIRCUIT
18/2 AWG FPL, FPLP OR THHN
H
HORN CIRCUIT
14/2 AWG FPL, FPLP OR THHN
P
POWER 24V
14/2 AWG FPL, FPLP OR THHN
C
COMMUNICATION CIRCUIT
18/2 AWG FPL, FPLP OR THHN
FIRE ALARM DEVICE LEGEND
TY
YMBO
PART #
PART NAME
MFG.
1
FACP
MS-920OUDLS
FIRE ALARM CONTROL PANEL
FIRELITE
I
RADIO
STARLINK SLe-GSM
FACP COMMUNICATION RADIO
NAPCO
FIRE ALARM SYSTEM - ELECTRICAL LAYOUT
N.T.S.
MAP OF LOCATION
N.T.S.
ID NUMBERS:
IDENTIFICATION NUMBERS (ID NUMBERS) HAVE BEEN ATTACHED TO ALL INITIATION
AND NOTIFICATION DEVICES ON THESE SET OF PLANS FOR IDENTIFICATION AND
CROSS REFERENCING PURPOSE. THE ELECTRONIC ADDRESS OF THE INTELLIGENT
DEVICE MAY DIFFER FROM THE ID NUMBER AND WILL BE SELECTED AT THE TIME
OF INSTALLATION.
SCOPE OF WORK:
1. SCOPE OF WORK IS TO ENERGIZE 4. ALL CONTROL FUNCTIONS
FIRE ALARM PANEL(S) AND SHALL BE TESTED FOR PROPER
RETEST ALL EXISTING DEVICES OPERATION.
2. SYSTEM SHALL BE RESTORED TO
FUNCTIONAL OPERATION IF
NEEDED.
i
3. NEW TEST AND INSPECTION
FORMS SHALL BE PROVIDED
AND NEW INSPECTION TAG'
PLACED ON THE FACP.
? (q y
v
VISI®NS
GENERAL NOTES (ALL MAY NOT APPLY):
FIRE ALARM SYSTEM NOTES:
1. FIRE ALARM IS MONITORED BY A CENTRAL STATION..
1. INSTALL NEW POWER LIMITED, LOW VOLTAGE, UL LISTED
2. THIS IS A POWER LIMITED SYSTEM
FOR FIRE ALARM USE.
3. THE RISER DIAGRAM MAY NOT BE EXACT ROUTE OF ALL WIRES.
4. ALL DEVICES SHALL.BE COMPATIBLE WITH EACH OTHER
2. THE FIRE ALARM SYSTEM SHALL COMPLY WITH THE FLORIDA
5. INSTALLATION SHALL COMPLY WITH NFPA 1, 2012, APPLICABLE CHAPTERS.
FIRE PREVENTION CODE 5TH EDITION (LIFESAFETY CODE -
6. INSTALLATION SHALL COMPLY WITH NFPA 72, 2010, APPLICABLE CHAPTERS
NFPA - 101) AND NFPA-1 UNIFORM FIRE CODE. STATE 69A-48.
7. INSTALLATION SHALL COMPLY WITH NFPA 101, 2012, APPLICABLE CHAPTERS.
8. INSTALLATION SHALL COMPLY NEC 2008.
3. THE FIRE ALARM SYSTEM SHALL BE PROVIDED WITH A
9. RACEWAYS TO BE EMT, WIREMOLD, PVC & FREEZEWIRE (FISHED) WHERE CODE
SUPERVISED BATTERY BACK UP AND BUILT IN CHARGER.
PERMITS. MINIMUM RACEWAY 2", 40% CONDUIT FILL MAXIMUM.
Z
BATTERY SHALL BE CALCULATED AT 24HR STANDBY AND
10. SYSTEM SHALL BE GROUNDED PER MANUFACTURES SPECIFICATIONS.
15MIN OF ALARM MINIMUM.
11. NAC CIRCUITS TO BE #14 AWG, FPL CABLE STYLE Y (CLASS B). SLC CIRCUITS TO BE
O
# 18 AWG, FPL STYLE CABLE STYLE B.
�
4. THE FIRE ALARM SYSTEM SHALL BE ON A DEDICATED
12. WIRE RUNS ON PLANS ARE NOT EXACT ROUTE OF CONDUIT OR FREEWIRE.
BRANCH CIRCUIT OF FROM THE BUILDINGS "HOUSE
13. ALL SPACES SHALL MEET THE AUDIBLE CHARACTERISTICS OF NFPA72 AND
EMERGENCY PANEL". THE FIRE ALARM CIRCUIT BREAKER
NFPA101.
SHALL BE PROTECTED BY A LOCKED CABINET DOOR OR
14. SMOKE DETECTORS SHALL NOT BE LOCATED WITHIN 3' OF A/C DIFFUSERS, KITCHEN
DEDICATED BREAKER LOCK. CIRCUIT BREAKER SHALL BE
OR BATHROOM DOORS.
4S
MARKED WITH "FA" NEXT TO THE BREAKER, NOTED ON THE
15. CEILING MOUNTED DEVICES SHALL BE LOCATED AT A HEIGHT OF 10' +/- ON
_
PANEL SCHEDULE AND NOTED ON THE FRONT OF THE
SMOOTH FLAT CEILINGS UNLESS OTHERWISE NOTED.
ELECTRICAL PANEL DOOR OR COVER.
16. THIS PANEL SUPPORTS UP TO 99 ADDRESSABLE DETECTORS AND 99 MODULES. SEE
FLOORS PLANS FOR QUANTITIES & TYPES OF DEVICES.
5. FIRE ALARM CONDUITS SHALL BE INSTALLED PER NFPA-70
17. THIS IS A BATTERY BACKED UP SYSTEM, WITH 24 HOURS OF BACKUP AND 5
(NEC). FIRE ALARM WIRES SHALL BE MULTI -CONDUCTOR
MINUTES ALARM, SHOULD LOSS OF NORMAL 120 VAC OPERATION POWER OCCUR,
CABLE PLENUM TYPE AND SHALL BE RUM "FREE WIRE"
THE FACP WILL AUTOMATICALLY TRANSFER TO STANDBY BATTERY.
WHERE ABOVE 7'. WIRES SHALL BE INSTALLED PER ARTICLE
18. FIRE ALARM PANEL & ANY ASSOCIATED FIRE ALARM TRANSPONDERS SHALL BE
Q�
}, no u_ r -
760 FOR LOW VOLTAGE, POWER LIMITED FIRE ALARM
FED BY A 120 VAC, SINGLE SYSTEM AND SHALL BE MONITORED FOR INTEGRITY PER
CIRCUITS.
NFPA 72.
2- CO CO
19. RACKS, SHELVES AND EQUIPMENT ARE ALL LOWER THAN 80" ABOVE FINISHED
6. ALL FIRE ALARM AUDIBLE NOTIFICATION DEVICES WITHIN
FLOOR UNLESS OTHERWISE INDICATED
"-
J LL
cv coo uj 0 LL
EACH AREA / FLOOR USED FOR EVACUATION SHALL BE
20. THE DESIGN INSTALLATION COMPLIES WITH F.B.C. 11-4.28.3
TEMPORAL AND SYNCHRONIZED PER NFPA.
21. ALL EQUIPMENT TO BE U.L. LISTED
22. ALL FIRE CAULK TO BE U.L. LISTED.
7. ALL FIRE ALARM VISUAL NOTIFICATION DEVICES USED FOR
23. THIS IS A FULLY SPRINKLERED BUILDING
EVACUATION SHALL BE OF THE XENON STROBE TYPE AND
24. THIS IS A 4 STORIES FACILITY
SHALL BE A MINIMUM OF 75CD. ALL VISUAL DEVICES WITHIN
25. ROOM CONTAINING FACP IS MECHANICALLY VENTILATED
EACH AREA / FLOOR SHALL BE SYNCHRONIZED.
26. POWER UP AND POWER DOWN OF THE FIRE ALARM PANEL MUST BE DONE IN THE
DATE: 11/21/2016
SCALE: AS NOTED
PROPER SEQUENCE:
CHECKED BY: JS
8. WALL MOUNTED STROBE LIGHTS SHALL BE MOUNTED AT 80"
POWER DOWN: DISCONNECT BATTERY AND TURN OFF THE AC POWER AT THE
AFF TO THE BOTTOM OF THE DEVICE.
BREAKER
9. PULL STATIONS SHALL BE MOUNTED AT 48"AFF PER ADA
POWER UP: TURN ON THE AC POWER AT THE BREAKER AND THEN CONNECT
REQUIREMENTS.
THE BATTERY.
NOTE: DO NOT DISCONNECT THE AC POWER FEED FROM THE TERMINAL
10. A SMOKE DETECTOR SHALL BE INSTALLED ABOVE THE FIRE
TO DISCONNECT':POWER.
ALARM CONTROL PANEL.
27. THE 120 VAC PRIMARY POWER SHALL CONFORM TO NFPA 72 2007 EDITION SECTION
4.4.1.4:
11. FIRE ALARM CONTROL PANEL TO BE INSTALLED INTO AN
4.4.1.4.2._MECHANICAL PROTECTION
F
EXTSTING NEMA ENCLOSURE
4.4:1.4.2.1. THE DEDICATED -BRANCH CIRCUITS AND CONNECTIONS SHALL -
__.__ CIRCUIT(S)
MECHANICALLY -PROTECTED.
4.4.1.4.2.2._CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING AND
SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT".
4.4.1.4.2.3._THE LOCATION OF THE DISCONNECTING MEANS SHALL BE
PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT.
28. THE CONTROL (RELAY) MODULE FOR AHU SHUTDOWN SHALL BE LOCATED WITHIN
THREE (3) FEET OF THE DEVICE BEING CONTROLLED PER NFPA 101. THE CONTROL
MODULE SHALL BE LOCATED SUCH THAT THE FRONT MOUNTED LED IS VISIBLE
UPON ENTRY INTO MECHANICAL ROOM. SHOULD THE DUCT DETECTORS BE
LOCATED ABOVE CEILING, THE CONTROL MODULES SHALL BE LOCATED IN THE
CEILING DIRECTLY BELOW THE DUCT DETECTOR, SO THE LED IS CLEARLY VISIBLE.
THE RELAY CONTACTS HAVE A MAXIMUM CAPABILITY OF 1.0 AMPS @ 24V AND 0.3
AMPS @120 VAC. CONTRACTOR MUST VERIFY THAT THE SHUTDOWN CIRCUIT DOES
NOT EXCEED THESE MAXIMUM CURRENT RATINGS.
29. 75 DBA SHALL BE ACHIEVED FOR ALL SLEEPING AREAS BY NFPA 72.7.4.4.
MAP OF LOCATION
N.T.S.
ID NUMBERS:
IDENTIFICATION NUMBERS (ID NUMBERS) HAVE BEEN ATTACHED TO ALL INITIATION
AND NOTIFICATION DEVICES ON THESE SET OF PLANS FOR IDENTIFICATION AND
CROSS REFERENCING PURPOSE. THE ELECTRONIC ADDRESS OF THE INTELLIGENT
DEVICE MAY DIFFER FROM THE ID NUMBER AND WILL BE SELECTED AT THE TIME
OF INSTALLATION.
SCOPE OF WORK:
1. SCOPE OF WORK IS TO ENERGIZE 4. ALL CONTROL FUNCTIONS
FIRE ALARM PANEL(S) AND SHALL BE TESTED FOR PROPER
RETEST ALL EXISTING DEVICES OPERATION.
2. SYSTEM SHALL BE RESTORED TO
FUNCTIONAL OPERATION IF
NEEDED.
i
3. NEW TEST AND INSPECTION
FORMS SHALL BE PROVIDED
AND NEW INSPECTION TAG'
PLACED ON THE FACP.
? (q y
v
Im
VISI®NS
M
Z
O
NQ
�
W �
W
.t
4S
��
72
ul
AA
so,
5
-i-+
co
co>co
Q�
}, no u_ r -
co
NQ? � ' `� '
4-. 0) 0 0
t� M
2- CO CO
0
v 6.
`�
"-
J LL
cv coo uj 0 LL
FIRE ALARM SYSTEM
SHEET FA -1
DATE: 11/21/2016
SCALE: AS NOTED
DRAWN BY: BD
CHECKED BY: JS
Im