17-2095DEMOLITION & CONSTRUCTION NOTES: CONTRACTORS AND SUBCONTRACTORS SHALL PERFORM ALL WORK TO MEET CODES, REGULATIONS, AND MASONRY 1. DESIGN OF MASONRY IS BASED ON "BUILDING CODE REQUIREMENTS AND SPECIFICATION FOR MASONRY STRUCTURES", (TMS 402-08/ACI 530-08/ASCE 5-08). 2. PROVIDE CLEAN—OUT/ INSPECTION BLOCKOUT AT BASE OF ALL VERTICAL FILLED CELLS. VERTICAL REINFORCING SHALL BE SECURED TO FOUNDATION DOWELS AND BEAM REINFORCING TO PREVENT DISPLACEMENT DURING HIGH LIFT GROUTING OPERATIONS. RESTRICTIONS, HAVING JURISDICTION. CONCRETE REINFORCING AT LEAST 1. CONCRETE AND REINFORCING SHALL BE PLACED ALL DIMENSIONS SHALL BE VERIFIED PRIOR TO ACCORDING TO ACI -318 AND MINIMUM CONCRETE COVER CONSTRUCTION BY CONTRACTOR AND/OR SHALL BE: SUBCONTRACTORS. THE CONTRACTOR AND/OR BEAM AND COLUMNS — 1-1/2" SUBCONTRACTOR SHALL NOTIFY THE ARCHITECT OR SLAB — 3/4" ENGINEER AND PROJECT MANAGER OF ANY EXPOSED UNPROTECTED CONCRETE — 1-1/2" DISCREPANCIES PRIOR TO COMMENCING CONSTRUCTION. IF FORMED CONCRETE BELOW GRADE — 2" CONTRACTOR AND/OR SUBCONTRACTOR FAILS TO NOTIFY UNFORMED CONCRETE BELOW GRADE — 3" THE ARCHITECT OR ENGINEER OR PROJECT MANAGER, THE 2. ALL REINFORCING STEEL SHALL BE NEW BILLET STEEL CONTRACTOR AND/OR SUBCONTRACTOR SHALL BEAR ALL CONFORMING TO ASTM A615—GRADE 60. ALL DETAILING EXPENSE FOR CORRECTION. AND ACCESSORIES SHALL CONFORM TO TYPICAL DETAILS SHOWN IN THE "MANUAL OF STANDARD PRACTICE FOR ADEQUATE VERTICAL AND HORIZONTAL SHORING SHALL DETAILING REINFORCED CONC STRUCTURES ACI 315, --BE PROVIDED TO SAFELY' SUPPORTALL CONSTRUCTION LATEST EDITION". LOADS. 3. ALL CONTINUOUS VERTICAL OR HORIZONTAL BARS IN ADEQUATE BARRIERS SHALL BE PROVIDED TO PROTECT FOOTINGS, FOUNDATIONS, WALLS, SLABS AND OTHER PUBLIC AND ADJOINING PROPERTY CONC SHALL BE LAP—SPLICED 48 BAR DIAM. OR 2'-0" ' MINIMUM WHICHEVER IS GREATER (EXCEPT AS NOTED BY ALL WORK SHALL CONFORM TO AT LEAST THE MINIMUM DRAWINGS). ALL BARS AT END OF CONT. FTGS, BEAMS STANDARDS OF THE 2014 5th ED. FBC STANDARD OR CONT. HORIZ. ELEMENTS SHALL BE CONTINUED TO FAR BUILDING CODE AND SUBSEQUENT AMENDMENTS. SIDES OF INTERSECTING ELEMENTS. SPLICES OF HORIZONTAL REINFORCING SHALL OCCUR ONLY AT TO THE BEST OF THE ENGINEERS KNOWLEDGE, THESE REINFORCED MASONRY COLUMNS. PLANS AND SPECIFICATIONS COMPLY WITH THE 4. DETAILS OF CONCRETE REINFORCEMENT SHALL BE IN APPLICABLE MINIMUM BUILDING CODES. ACCORDANCE WITH "THE MANUAL OF STANDARD PRACTICE FOR REINFORCED CONCRETE CONSTRUCTION", AS PUBLISHED BY THE CONCRETE REINFORCING STEEL CONCRETE INSTITUTE, UNLESS OTHERWISE NOTED. 1. STRUCTURAL CONCRETE SHALL CONFORM TO THE 5. REINFORCEMENT SHALL BE CAREFULLY PLACED, REQUIREMENTS OF ACI 301 AND SHALL ATTAIN A RIGIDLY SUPPORTED, AND WELL TIED WITH BAR SUPPORTS MINIMUM COMPRESSIVE STRENGTH IN 28 DAYS OF 3000 AND SPACERS. 6. ADEQUATE VERTICAL AND HORIZONTAL SHORING PSI. UNLESS NOTED OTHERWISE ON PLAN OR IN SHALL BE PROVIDED TO SAFELY SUPPORT ALL SPECIFICATIONS CONSTRUCTION LOADS. Z. CONCRETE, WHEN PLACED, SHALL HAVE A SLUMP OF 2 INCHES PLUS OR MINUS ONE INCH. 3. CONSTRUCTION JOINTS DESIGN AND LOCATION SHALL CONFORM STRICTLY TO THE REQUIREMENTS OF THE PLANS AND SPECIFICATIONS. ANY CONSTRUCTION OR CONTROL JOINTS DESIRED OR PREFERRED BY THE CONTRACTOR SHALL BE APPROVED BY THE ENGINEER PRIOR TO CONSTRUCTION OF THOSE AREAS INVOLVED. 4. CHECK ALL DRAWINGS AND APPLICABLE MANUFACTURER'S SHOP DRAWINGS FOR LOCATION OF ALL EMBEDDED ITEMS, SUCH AS PIPE SLEEVES, ANCHOR BOLTS, ETC. PRIOR TO PLACING CONC. •00 1. ALL FRAMING LUMBER SHALL BE STRESS GRADE LUMBER (SOUTHERN YELLOW PINE) WITH MIN. fb = 1500 PSF, #2 SPF AND MOISTURE CONTENT NOT TO EXCEED 197.. ALL LUMBER IN CONTACT WITH CONCRETE, MASONRY, EARTH, OR STEEL SHALL BE PRESSURE TREATED. PLYWOOD SHALL BE EXTERIOR GRADE 5/8" CDX. 2. SUPPORT FOR ANY ROOF TOP OR CEILING HUNG EQUIPMENT, PARTITIONS, OR ITEM SHALL BE PROVIDED AND COORDINATED BY THE GENERAL CONTRACTOR. ALL WORK SHALL CONFORM TO AT LEAST THE MINIMUM STANDARDS OF THE 5th ED. (2014) FBC STANDARD BUILDING CODE AND SUBSEQUENT AMENDMENTS THIS BUILDING HAS BEEN DESIGN LOADS: WIND VELOCITY, RISK CAT. EXPOSURE ENCLOSED DESIGNED FOR AT LEAST THE FOLLOWING MINIMUM Vult= 170 MPH Vosd = 132 MPH 11 D INT. PRESSURE COEFF. +/— 0.18 GENERAL NOTES NO SCALE Aak 60.00' ^ /i N SITE PLAN SCALE: 1/8"=V-0" wa LLI 0 0 � v) Of 4; O - z 0 Wwcwa2� ZLu z~Qa- o <00,Zl,o w o >-Zi�-:2 C) W F � Z < 0-0 0 c oat w 0 M inV)aw .� owz�= Of �a_>-CF_ =Xzwl� f-wao_0 0 z W� C) o Q E-4wruCCoC\20 rc\t p' Q124 Co 0 °' o 0 Cd I = -� Ww 0'0Coa) aim $ W a�ow�b w El0 z �D W m a m a` a a E ii Q W � U O W � ^ O <C W 0 111 �Wzm W < O 0 a z (fiLI-I r O n a`a v ) n m Wr 14, 4 s', rt -VY •bit :, f"^rry�'�... o °±r'tiidl`�t a Scale: AS NOTED Date 11-23-16 Sheet X11 OF 7 i EXISTING FLOOR PLAN Z -n, no PLAN SCALE: 1/4"=V-0" w5 W Sheet 1,2 Z wC)Z OF 7 U -, F-wow O o V) 0 W —Z —wcafr- � C) ZwV) Z a'uj n-*, ^ O Q2 OOZ,J� d w--:2 >-ZI~--:2 O <C W c.� w ZCr-wO�Z U Q O �Wzm V1 OQ = �~w CO m O •(/} owEw= Q z O a C � 1 O O F-w¢Ofo Z > Z X11 W Sheet 1,2 ry OF 7 U -, O z � W n-*, ^ O o_ O <C W c.� w �Wzm Q z O a O Z > W L �— o v� n � m a X11 :, ��sgfPflRt�t��t Scale: AS NOTED Date 11-23-16 Sheet 1,2 OF 7 �r -, :, ��sgfPflRt�t��t Scale: AS NOTED Date 11-23-16 Sheet 1,2 OF 7 8'-0' TOP OF WALL 0'-0' TOP OF SLAB 8'-0' TOP OF WALL 0'4' TOP OF SLAB DESIGN PR RES: + 35.3 PSF - 38.2 PSF 0 NORTH SOUTH ELEVATIONS 0 t m.j mr - 38.2 PSF 5/8" CDX PLYWOOD SHEATHING (SEE NAILING SCHEDULE) W/ SEE 12 30# BASE & SHINGLES PER PLAN PRODUCT APPROVAL MIN 30R INSULATION TRUSS ANCHOR SEE PLAN 5/8 DRYWALL TRUSS BRG. \,.F�8'-0» FLASHING PRE-ENGINEERED WOOD 2X4XCONT PT TRUSSES @ 2'-0" O.C. SUB FASCIA BOND BEAM PROVIDE CONT. P.T. BLOCKING 1X6XCONT SEE PLAN BETWEEN TRUSSES PT FASCIA STUCCO Z'-0" TV / L R-5 (MIN) INSUL HI RIB LATH 8" CMU a 1x FURRING & STUCCO W/ #5 1/2" DRYWALL SOFFIT 48" OC 3 SOFFIT & FINISH DETAIL. 3/4 V-0, 12 13 8'-Q' TOP OF WALL 1 _ SCALE: 1/4"=l' -O" 0'-0' TOP OF SLAB EAST 12 3(— — 6 -Cr TOP OF WALL ❑ ❑ DESM PRESSURES: b + 35.3 PSF 5 - 38.2 PSF #-0' TOP OF SCABA., DESiGN PRESSURES: + 35.3 PSF - 38.2 PSF WEST tr >- Date 11-23-16 Sheet 1,3 w n - OU OF 7 w 0 ZO 0 W �LLLIOV)w ry V)0w-z — wCDQf o 0 zwcn zQ°-o z � W r ^ (L'C:>ULLJ Ld o= 0 w0 Fr z O v W v, z�o�o w 0 ulU)(L�m z ao 'rn Ld 0ui Ld owe-= �l­_ Cr Of z 6 = X Z W E—w<Cof0 z W a a E -i-1 cr) CC12 CQ rn C\2 M v 0 w 4co I� I w C) Co �- v•�,��roZ*z Q W CoM Lo� W H Z c� 0 Z �N � Scale: AS NOTED Date 11-23-16 Sheet 1,3 Q OF 7 0 W ry C� O z � W r ^ � o= O Q W CD w � W z ao m �W�QO z c 0 Ez z Ln O o co � � m o_ Scale: AS NOTED Date 11-23-16 Sheet 1,3 OF 7 0 N Cu Cu 0 lrUTaov FOOTING SCHEDULE F'c=2500 psi MARK 11'-8' SIZE 11'-4` 16'-0' gpT7, LONG BOTT.SHORT TOP LONG TOP SHORT T.O.F. NOTE TE -18 P-6" 2'-0"xCONT. 2-#5 CONT. --- 1-#5 CONT. --- 0'-0" O I 1 00 • • w o>-z�-:2 �Wzm `— TE -1 8 I L4 ----------------1 Qn0 � ® $ W I w , \ o I I I � E I 0 UJ ofry z �w I n,r-- I 0 I I z I s -2.t EDGE OF 1 ° EXISTING I 1 SLAB i I s -2.t I I , • I 1-1/2" RECESS ( I • W/#5 EMBEDED DOWELS AT 48" O.C. TO MATCH MASONRY REINF., I TYP. UN0. INFILL _._-- EXISTING I OPENING ° 00 �I I 4" THICK CONC. SLAB, 2500 PSI, W W/ 6X6 W2XW2 WWF ON VAPOR I— BARRIER OVER CLEAN, WELL I I COMPACTED POISON TREATED SOIL • I EMBEDED DOWELS AT 48" Q.C. TO I 1 I MATCH MASONRY REINF., TYP. INFILL r EXISTING OPENING I I BREAK EXISTING SLAB AS REQUIRED TO PROVIDE NEW FOOTING AND DOWELS INTO EXISTING SLAB. REFER I TO SECTION 2 • ----TE-18 • ° • : ° • I I • COI I I00 I ( I L- -----J TE -18 . • / • • 14'-3' 13'-9' 39'_0.. FOOTING SCHEDULE F'c=2500 psi MARK DEPTH SIZE REINFORCING gpT7, LONG BOTT.SHORT TOP LONG TOP SHORT T.O.F. NOTE TE -18 P-6" 2'-0"xCONT. 2-#5 CONT. --- 1-#5 CONT. --- 0'-0" cu PREENGINEERED PREMANUFACTURED MT'L OR WD. TRUSSES @ 24" OC TYPICAL (PROVIDE FL. ENGR SEALED SHOP DRAWINGS)TYP. TRUSS BRG. _s– SEE SEE PLAN r— _ EXISTING SLAB TO 1-1/2 )1 RECESS AS REQUIRED \ 12 RE: ARCH. r' s' s' TRUSS ANCHOR SEE PLAN CDX PLYWOOD SHEATHING SEE ROOF FRAMING NOTES 8"X8" BOND BM. GROUTED W/ 2—#5 CONT. REINF'D W/ #4 @ 48" O.C. IN GROUTED CELLS PROVIDE MATCHING DOWELS * DUR—O—WAL HOR. REINF. @ 16" O.C. W. W. F. CONC. FLOOR SLAB WELL COMPACTED CLEAN FILL 1 SECTION AT WALL NEW 4" SLAB ICKENED EDGE SEE SCHEDULE FOR SIZE & REINF. DRILL DOWELS W/4" MIN. EMBED TO EXISTING SLAB @ 24" O.C. SECTION AT SLAB EDGE (1)-#5 CONT. DOWEL 0 48" TO MATCH MASONRY REINF. 1-1 /2" RECESS AS REQUIRED \ I 0 I 0 I 0 r TE -18 3 SEE TYPICAL 8" X CONT. CONC. CURB 0 H SEE FOUNDATION PLAN FOR SIZE AND REINF. REF. FIN. FLR. 4 SECTION AT UTILITY SCALE: 3/4" = 1'-0" TYP QO I i`0 L_ N REINF'D W/ #4 i 0 48" O.C. IN GROUTED CELLS - PROVIDE MATCHING DOWELS I & DUR-O-WAL HOR. REINF. * 16" O.C. W.W.F.NEW CONC. FLOOR SLAB L - REF. FIN. FLR. �» I SEE PLAN CUT BACK EXISTING SLAB TO POUR NEW FOOTING WELL COMPACTED CLEAN FILL SECTION AT WALL w0 ry wczno O �wopu)w a Wo-Za - � uiow 01zui n zi-Qa.o O ao� uj W 0 w o>-z�-:2 �Wzm 0W0�z N Qn0 � ® $ W cn O a - w p z w 0 Z \ o M U- N a- w E .Ln 0 UJ ofry z �w a v / n,r-- m 0 =xzwLL_ rw¢cro z W� a o o � twU E.1 P41-6 Cr) C\2 rn Ir --j i Wwc) Cr) Q)ai a OOm o Q W ° z a to Ew ►�� z �D E Xx 0 m E 0 z W ry U O z � W � O c W 0 W �Wzm ® $ W QO z 0 Z E z a v / n,r-- m Scale: AS NaTED Date 11-23-16 Sheet 2 i 1 OF 7 114 t 23'-0' U=1683 rA U=1683 /� F1=106 (�I F1=106 I`1 F2=626 F2=626 TYP. BOTH TYP. BOTH SIDES SIDES 39'-0" 11'-4' 16'-0' U=1683 F1=106 F2=626 A TYP. BOTH SIDES DIA. OTY LENGTH THREAD HOOK PROD LENGTH Y IH D O NU TB 1 CONNECTOR ALLOWABLE m FL PRODUCT REMARKS TYPE 13F UPLIFT CONNECTOR LOAD VALUES 1'-6' 4' $ 0 N j v UPLIFT LATERAL LATERAL TB -._1 C13tlNECTI13N FORCE +8'-3" --- U=1683 F1=106 F2=62 A TYP. BOTH SIDES .N ,4 # CMU BOND BEAM # F1 F2 (QTY) a SIZE HIP GIRDER 2-#5 #3 ® 8 -OC (MA)O (# OF CONNECTORS)PARALLEL ¢0Z)W0 PERPEND. m p�0 w YPRE-ENGINEERED TRUSSES @ 2'-0" O.C. cza a_ 0 m TO BEAM TO BEAM W It � 2otf TRUSS GIRDER PRE—ENGINERED TRUSSES @ 2' _ p:� 0. B— w o CD = � E TO RAFTER TO WALL/ BEAM SXZWLL_ F-wQW'O MARK UPLIFT C#) -� W In L i JZI ISTI USS FORCE o (u N MASONRY GABLE END 895 SIMPS❑N HETA16 1810 340 725 (9)-10dX1 1/2' EMBED 4' G P S- @12 E—E — GINE " 0. RED . SIMPSON MGT 3965 - - (22)-10d (1) 5/8' BOLT FL11470 PI TRUSSES GYB CK E 7 OR NOTE ■ m 1503 (2) SIMPSON HETA16 2035 1225 1520 (10)-10dX1 1/2' EMBED 4' FL11473 AT 1 PLY D 649 SIMPSON H10 995 590 285 (8)-BdXl 1/2' (8)-SdXl 1/2' FL10456 E 418 SIMPSON LUS26 1165 GRAVITY LOAD (4)-IOdXl 1/2' (6) 10d FL10655 CONN. RAFTER Pa = 1070 TO LEDGER M U=168 TYP. BOTH F1=106 SIDES 2=626 A HIP GIRDER =1683 1=106 TYP. BOTH 2=62 SIDES A m I- TB 14F m F- 11'-0' BEARING WALL BELOW @ 8'0" elev. U=1683 F1=106 f�1 F2=626 TYP. BOTH SIDES 14'-3' 39'-0' ROOD FRAMING PLAN PRE—ENGINEERED TRUSSES @ 2'-0" O.C. 13'-9" SCALE: 1/4"=l'—O" CONNECTOR SCHEDULE DIA. OTY LENGTH THREAD HOOK PROD LENGTH Y IH D O NU 1/2' CONNECTOR ALLOWABLE FASTENER FL PRODUCT REMARKS TYPE 13F UPLIFT CONNECTOR LOAD VALUES 1'-6' 4' $ APPROVAL # 2-#5 UPLIFT LATERAL LATERAL 9-1 4' 2'-0' 4' 4' C13tlNECTI13N FORCE +8'-3" --- 1-#5 --- # CMU BOND BEAM # F1 F2 (QTY) a SIZE --- 2-#5 #3 ® 8 -OC (MA)O (# OF CONNECTORS)PARALLEL ¢0Z)W0 PERPEND. PER CONNECTOR p�0 w o cza a_ 0 m TO BEAM TO BEAM W It � 2otf TRUSS TRUSS � E TO RAFTER TO WALL/ BEAM SXZWLL_ F-wQW'O MARK UPLIFT C#) -� W In L i JZI Na FORCE A 895 SIMPS❑N HETA16 1810 340 725 (9)-10dX1 1/2' EMBED 4' FL11473 B 3137 SIMPSON MGT 3965 - - (22)-10d (1) 5/8' BOLT FL11470 SEE ANCt13R SCHEDULE OR NOTE ■ C 1503 (2) SIMPSON HETA16 2035 1225 1520 (10)-10dX1 1/2' EMBED 4' FL11473 AT 1 PLY D 649 SIMPSON H10 995 590 285 (8)-BdXl 1/2' (8)-SdXl 1/2' FL10456 E 418 SIMPSON LUS26 1165 GRAVITY LOAD (4)-IOdXl 1/2' (6) 10d FL10655 CONN. RAFTER Pa = 1070 TO LEDGER NOTEi 538 SIMPSON HCP2 645 300 - (6)-IUa x t6) 1/4'xe- 1/4' FL10447 USE AT CORNER HIP 1 1/2' TITEN (SINGLE PLY) X NDTE. S/8' THREADED R❑D WITH SET EPDXY-TIE ADHESIVE W/ 12' EMBED, MAY BE USED IN LIEU OF EMBEDDED ANCHOR ANCHOR BOLT DETAIL DIA. OTY LENGTH THREAD HOOK PROD LENGTH Y IH D O NU 1/2' W -s' 2~ 2' 1 -1/2 - 511r 1'-o' 3' 3' 2' 3/4' 1'-3' 3' 3' 2-3/4' 1'-6' 4' $ 3-1/2- 2-#5 --- 4' 3-1/27 9-1 4' 2'-0' 4' 4' 3-1/2" BEAM SCHEDULE MARK SIZE (wxd) TOP ELEV. REINFORCING TOP MID. BOTT. CLOSED TIES REMARKS TB -1 8"x12" +8'-3" 2-#5 --- 2-#5 - TIE BEAM BB -1 8"x8" +8'-3" --- 1-#5 --- - CMU BOND BEAM B-2 8"x12" +8'-3" 2-#5 --- 2-#5 #3 ® 8 -OC CIP BEAM m GABLE > 7 deg. N ROOF SHEATHING NAILING NTS ROOF SHEATHING: Z=3' 19/32" OR GREATER IL: W 8d RING SHANK ZPNE 1 & 2: 4 O.C. EDGE AND 6_ O.C. INTERMEDIATE ZPNE 3: 4 O.C. EDGE AND 4' O.C. INTERMEDIATE NET ROOF PRESSURES: ZONE 1: -40.8 PSF ZONE 2: -70.9 PSF ZONE 3: -104.9 PSF ROOF FRAMING NOTES 2. TRUSS MANUFACTURER SHALL SUBMIT PLANS AND ENGINEERING DRAWINGS FOR PERMIT,WHICH SHALL BE CERTIFIED BY AN ENGINEER REGISTERED IN THE STATE OF FLORIDA. 3. DESIGN LIVE LOAD FLOOR 40 PSF ROOF 30 PSF WIND LOAD 170 MPH. 4. ALL MEMBERS SHALL BE SO FRAMED, ANCHORED, TIED AND BRACED THAT THEY HAVE THE REQUIRED STRENGTH AND RIGIDITY. 5. GENERALLY WALL SIZES INDICATED ARE BASED ON NOMINAL LUMBER SIZES. CARE SHOULD BE TAKEN DURING LAYOUT TO HOLD ALL EXTERIOR DIMENSIONS AND WORK INTERIOR DIMENSIONS TO THE CENTER LINE OF WALLS. 6. ALL CONNECTIONS SHALL BE AS SPECIFIED IN THE 5TH ED. (2014) FLORIDA BUILDING CODE AND LOCAL AMENDMENTS 7. ALL PLYWOOD SHALL BE IDENTIFIED WITH THE APPROPRIATE GRADE/TRADEMARK OF THE AMERICAN PLYWOOD ASSOCIATION. 8. ALL PLYWOOD EXPOSED TO THE WEATHER SHALL BE EXTERIOR TYPE. 9. ALL CONNECTORS HAVE BEEN SELECTED TO RESIST LATERAL LOADS. 5 INFILL MASONRY DETAIL 1/2' = 1'-0' W d W Luo 0 u Wo U) W O U)0W—Z p ui 0 Ix- omZLLI ) � z�QIZo S .cc O U W p w Q W pW��z CD W ¢0Z)W0 p�0 w o cza a_ 0 m '0) W It � 2otf � a N�}CN � E SXZWLL_ F-wQW'O z z -� W In L i JZI w C:) o EmC\20 � Q � CQ M Ww � I U,oCo� Q) r.- v', �-� 4 �Go co w WCCC) IL-4 ate, Ex-ico z0 E A� a m Scale: AS NOTED Date 11-23-16 Sheet I OF 7 W ry u O W � 0 Q W CD W �Wzm �z Q0 � a z � E z z -� W In >- 0 Ln. I.r� � a m Scale: AS NOTED Date 11-23-16 Sheet I OF 7 V.T.R. 2' V.T.R. 2" I ( � VENT �STUDOR 1/2' WASH _ SINK 2" I IAV. /7-' 2 i V CAP EXISTING - - -OLD SINK 2" B NC 11E TO EXISTING 3� PLUMBING RISER SCALE: N.T.S. ELECTRICAL LEGEND * CLG. MOUNTED LIGHT 0 WALL MOUNTED LIGHT WOa RECESS HI HAT wzOO SWITCH O SWITCH 3 WAY CEILING FAN w/LIGHT CEILING FAN g ELECTRIC METER SECURI zhln- 9i O. ;; [11111 ' a pi DISC( NOTE: ALL NEW CIRCUITS & FIXTURES TO BE COORDI(` W/ ELECTRICAL CONTRACTOR AND OWNER. ELECTRICAL NOTES: 1. -ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF THE NEC, & NFPA-70 AND ALL OTHER PERTAINING CODES AND REGULATIONS ESTABLISHED BY AUTHORITIES HAVING JURISDICTION, AND SHALL MEET THE REQUIREMENTS OF OTHER RECOGNIZED STANDARDS AS THE ASTM, IEEE, NFPA AND NEMA,WHERE THE REQUIREMENTS OF SUCH STANDARDS ARE MORE STRINGENT THAN THOSE CITED ABOVE. 2. -ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS MANNER, FULLY OPERATIVE, AND TO THE ACCEPTANCE OF THE OWNER AND THE ENGINEER. 3. -ALL ELECTRICAL MATERIALS AND EQUIPMENT SHALL BE APPROVED BY U.L.AND SHALL BEAR THE U.L.LABEL, 4. -THE PLANS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL COORDINATE HIS WORK WITH THE WORK OF OTHER TRADES SO THAT INTERFERENCE BETWEEN CONDUITS PIPING AND STRUCTURAL WORK WILL BE AVOIDED. 5. -THE CONTRACTOR SHALL HAVE VISITED THE JOB SITE BEFORE BIDDING AND ASCERTAINED ALL EXISTING CONDITIONS WHICH WILLAFFECT HIS WORK. FAILURE TO DO SO WILL NOT BE ACCEPTED AS A REASON FOR REQUESTING EXTRA PAY IN THE EVENT THAT THE EXISTING CONDITIONS RESULT IN EXTRA MATERIALS OR LABOR. 6. -ANY EXISTING, CONDITION FOUND BY THE CONTRACTOR WHICH WILL ADVERSELY AFFECT THE WORK SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE OWNER APED/OR THE ENGINEER. 7. -AFTER THE SYSTEM IS INSTALLED CONTRACTOR SHALL CONDUCT AN OPERATIVE TE5� T FOR APPROVAL AND ACCEPTANCE BY THE OWNER. EQUIPMENT SHALL BE GUARANTEED FOR A PERIOD OF 1 YEAR FROM THE DATE OF FINAL ACCEPTANCE THEREOF AGAINST DEFECTIVE MATERIALS AND WORKMANSHIP. 8. -ALL CONDUCTORS SHALL BE SOFT COPPER WITH THW/THWN 600 VOLT INSULATION CONDUIT SHALL BE RGS OR IMC FOR EXTERIOR RUNS, EMT FOR CONCEALED AND INTERIOR RUNS NOT EXPOSED TO WEATHER OR MECHANICAL DAMAGE MAY BE USED UNDERGROUND WHERE BURIED 18" AND PROVIDED WITH A GROUND WIRE AS PER NEC 250. 9. -GROUNDING SHALL COMPLY WITH NEC 250 AND SHALL CONSIST OF COPPER CONDUCTORS IN CONDUIT WITH BOLTED OR BRAZED CONNECTIONS TO COLD WATER PIPE RODS, AND ALL AVAILABLE ELECTRODES. (NEC: 250.50). ALL METALLIC RACEWAYS SHALL BE GROUNTED. 10.-MECHANICALEQUIPMENT DISCONNECT SWITCHES SHALL BE PROVIDED WITH DUAL ELEMENT FUSES SIZED AS NOTED PER MANUFACTURER'S RECOMMENDATION VERIFY BEFORE INSTALLATION. 15. -SMOKE AND CARBON MONOXIDE ALARM SHALL BE INSTALLED WITHIN 10 FEET OF EACH SLEEPING AREA. A BATTERY BACK-UP POWER SUPPLY IS ALSO REQUIRED INTERCONNECTED AND ON IFCI. L 1 #6 SOLID CU GROUND TO 5/8"X io' CU. ROD L MAIN DISC METE 200 AMPS (3) #2/0 THW-CU PMEL (1) #6 GRD 40 CIRCUIT IN 2" RIGID (3) #4/0 IN 2-1/2" RIGID (FPL) ELECTRIC RISER SCALE: 1/4"=l' -O" Ill E W FLOOR PLAN SCALE: 1/4"=V-0" C2 i W 12- EXHAUST FAN OF 7 RECEPTACLE wzOO GROUND FAULT INDIC O SMOKE ALARM SECURI zhln- 9i O. ;; [11111 ' a pi DISC( NOTE: ALL NEW CIRCUITS & FIXTURES TO BE COORDI(` W/ ELECTRICAL CONTRACTOR AND OWNER. ELECTRICAL NOTES: 1. -ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF THE NEC, & NFPA-70 AND ALL OTHER PERTAINING CODES AND REGULATIONS ESTABLISHED BY AUTHORITIES HAVING JURISDICTION, AND SHALL MEET THE REQUIREMENTS OF OTHER RECOGNIZED STANDARDS AS THE ASTM, IEEE, NFPA AND NEMA,WHERE THE REQUIREMENTS OF SUCH STANDARDS ARE MORE STRINGENT THAN THOSE CITED ABOVE. 2. -ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS MANNER, FULLY OPERATIVE, AND TO THE ACCEPTANCE OF THE OWNER AND THE ENGINEER. 3. -ALL ELECTRICAL MATERIALS AND EQUIPMENT SHALL BE APPROVED BY U.L.AND SHALL BEAR THE U.L.LABEL, 4. -THE PLANS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL COORDINATE HIS WORK WITH THE WORK OF OTHER TRADES SO THAT INTERFERENCE BETWEEN CONDUITS PIPING AND STRUCTURAL WORK WILL BE AVOIDED. 5. -THE CONTRACTOR SHALL HAVE VISITED THE JOB SITE BEFORE BIDDING AND ASCERTAINED ALL EXISTING CONDITIONS WHICH WILLAFFECT HIS WORK. FAILURE TO DO SO WILL NOT BE ACCEPTED AS A REASON FOR REQUESTING EXTRA PAY IN THE EVENT THAT THE EXISTING CONDITIONS RESULT IN EXTRA MATERIALS OR LABOR. 6. -ANY EXISTING, CONDITION FOUND BY THE CONTRACTOR WHICH WILL ADVERSELY AFFECT THE WORK SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE OWNER APED/OR THE ENGINEER. 7. -AFTER THE SYSTEM IS INSTALLED CONTRACTOR SHALL CONDUCT AN OPERATIVE TE5� T FOR APPROVAL AND ACCEPTANCE BY THE OWNER. EQUIPMENT SHALL BE GUARANTEED FOR A PERIOD OF 1 YEAR FROM THE DATE OF FINAL ACCEPTANCE THEREOF AGAINST DEFECTIVE MATERIALS AND WORKMANSHIP. 8. -ALL CONDUCTORS SHALL BE SOFT COPPER WITH THW/THWN 600 VOLT INSULATION CONDUIT SHALL BE RGS OR IMC FOR EXTERIOR RUNS, EMT FOR CONCEALED AND INTERIOR RUNS NOT EXPOSED TO WEATHER OR MECHANICAL DAMAGE MAY BE USED UNDERGROUND WHERE BURIED 18" AND PROVIDED WITH A GROUND WIRE AS PER NEC 250. 9. -GROUNDING SHALL COMPLY WITH NEC 250 AND SHALL CONSIST OF COPPER CONDUCTORS IN CONDUIT WITH BOLTED OR BRAZED CONNECTIONS TO COLD WATER PIPE RODS, AND ALL AVAILABLE ELECTRODES. (NEC: 250.50). ALL METALLIC RACEWAYS SHALL BE GROUNTED. 10.-MECHANICALEQUIPMENT DISCONNECT SWITCHES SHALL BE PROVIDED WITH DUAL ELEMENT FUSES SIZED AS NOTED PER MANUFACTURER'S RECOMMENDATION VERIFY BEFORE INSTALLATION. 15. -SMOKE AND CARBON MONOXIDE ALARM SHALL BE INSTALLED WITHIN 10 FEET OF EACH SLEEPING AREA. A BATTERY BACK-UP POWER SUPPLY IS ALSO REQUIRED INTERCONNECTED AND ON IFCI. L 1 #6 SOLID CU GROUND TO 5/8"X io' CU. ROD L MAIN DISC METE 200 AMPS (3) #2/0 THW-CU PMEL (1) #6 GRD 40 CIRCUIT IN 2" RIGID (3) #4/0 IN 2-1/2" RIGID (FPL) ELECTRIC RISER SCALE: 1/4"=l' -O" Ill E W FLOOR PLAN SCALE: 1/4"=V-0" C2 i W 12- W OF 7 wzOO U �W0V)W a a Z (n W :2 CD W __j LL - U ()f - ZPQCLd 'Ld r ^ ao0,Zo ry W D Z H :2 O< ry Z Z W(1) (1)Qa-C) v1 op =Z p \ O C90-O~w M •m ouj LLI Wryry= � (n0 ->-Q~ Z O -� �-- E =xzWLL- I Z W W a--3 C) o 1'T W U'b �, a, �- co copq � w co0 z E W ii m c 0 ID E 0 z V) Scale: AS NOTED Date 11-23-116 Sheet 3,1 W OF 7 � U a z __j LL - W r ^ O< m W W�`0 � 0 Z O -� �-- E I --J W I no � m CL V) Scale: AS NOTED Date 11-23-116 Sheet 3,1 OF 7 DocuSign Envelope ID: EEB3876A-80CC-4767-BE6B-2BOAD3D190FC SYS # TONS I MANUS UNIT MODEL 1 2.0 GOODMAN GSX160241F* LF G END >4 10x10 SUPPLY GRILLE 6x6 SUPPLY GRILLE GSM 1-0 50 CFM EXHAUST FAN (V.T.O.) RETURN AIR DUCT SUPPLY AIR DUCT 4" QCT FLEX DUCT ------------------ 3/4" PVC DRAIN LINE WALL CONNECTION FROM AHU TO RIGID DUCT NOTE: AIR HANDLER SHALL WAVE A MW. CLEARANCE OF 3" ALONG THE SIDES, BACK t TOP WITH THE TOTAL WIDTH OF THE ENCLOSING SPACE BEING AT LEAST 12" WIDER THAN THE AIR HANDLER OPT. VIBRATION ISOLATORS CEA. CORNED SOFFIT VENT U 4" EXI- 50 cm RETURN MCA/ UNIT # A.H.0 CFM MOCP UNIT MODEL TOTAL MFG 1 ASPT29B14A* 800 CEILING 0 L E-SCERANT SECONDARY BRAN PAN WITH FLOAT SWITCH-- / STEEL FRAME PLENUM/STAND t CONDENSATE DRAIN TYP. AHU MOUNTING DETAIL W/ VERT RETURN NTS BATH EXHAUST DETAIL NTS SEER 16 MIN 39'-00 Ili -e# 1 11`4" UTILm E 1 1 ,- COOL BTUH HEAT KW AHRI CERT SUC &LIQ LINE SIZE DRAWINGS AND AS SPECIFIED. 2. MECHANICAL EQUIPMENT & FITTINGS SHALL BE PROVIDED AS SHOWN ON THE DRAWINGS. WORK SHALL INCLUDE TRIM AND RELATED CONSTRUCTION AS REQUIRED. 13. K.G. ENERGY PROVIDE EXPERIENCED, WELL TRAINED WORKERS COMPETENT TO COMPLETE THE WORK AS SPECIFIED. DESIGN, LLG 23600 5 8242076 7/8"& 3/8" 4. UNLESS APPROVED BY THE DESIGNER, PROVIDE RELATED PRODUCTS AND ACCESSORIES FROM ONE MANUFACTURER. 5. ALL WORK SHALL COIF -PLY W/ MANUFACTURER'S SPECIFICATIONS. 6. } SUB -CONTRACTOR SHALL PROVIDE COPIES OF MANUFACTURERS INSTALLATION, MAINTENANCE & WARRANTY INFORMATION. efficiency b y design' 7. DELIVER, STORE & TRANSPORT MATERIALS TO AVOID DAMAGE TO THE PRODUCT AND OTHER WORK. REJECT ANY DAMAGED PRODUCTS DELIVERED TO JOB SITE. __---- REF LINES ON EXTERIOR OF BUILDING WALL IN fWDTECTIVE 8. VERIFY LAYOUT AND C.F.M. REQUIREMENTS SHOWN ON DRAWINGS AND NOTIFY DESIGNER OF DISCREPANCIES. KAREN OLIVER 1470 NORTH CONGRESS AVE METAL LINE CHASE, PANT TO 9. EXAMINE AND VERIFY THAT JOB CONDITIONS ARE SATISFACTORY FOR ACCEPTABLE WORK. WEST PALM BEACH, FL, 33409 561.327.7272 FAX 561.333.0775 MATCH WALL 10. MAINTAIN AND USE UP-TO-DATE TRADE STANDARDS AND MANUFACTURERS INSTRUCTIONS. FLORIDA STATE LICENSE #CACA15692 NOTE THERE CAN Be NO OVERHANG OR 11. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES. OBSTRUCTION TO AIR FLOW 12. DUCTWORK SHALL BE R-6 MINIMUM (3 POUNDS PER CUBIC FOOT DENSITY FIBERGLASS WITH VAPOR BARRIER) IN ACCORDANCE WITH ASHRAE AND SMACNA STANDARDS. DIRECTLY A50VE CONDENSING UNIT DUCTWORK AND COMPONENTS SHALL BE CLASS 1 IN ACCORDANCE WITH 181 TESTS. 13. FLEXIBLE DUCT SHALL BE CLASS A IN ACCORDANCE WITH NAFPA STANDARDS 90A OR 90B INSTALLED STRICTLY AS DIRECTED BY MANUFACTURER, WITHOUT SAGS OR KINKS. wwwKoEnergyDesig oom 14. REFRIGERANT PIPING SHALL BE COPPER, HAND DRAWN TYPE L ACR TYP, DEHYDRATED AND SEALED JOINTS TO BE HIGH TEMPERATURE BRAZING ALLOY NOT LESS THAN 5% SILVER. INSULATION NOT LESS TI -LAN 1/2" "ARMAFLEX" 'TYPE. LIQUID AND SUCTION LINES TO BE SIZED ACCORDING TO MANUFACTURER'S SPECIFICATIONS. (S) FLIT EQ TIE DOWN CLIPS 15. PROVIDE TURNING VANES FOR PROPER AIR BALANCING. - 411xi° G90 39K,SI QALY. STEEL Wf't1-! 16. PROVIDE GASKETS AT ALL GRILLS AND DIFFUSERS. - SCREW THRU UNIT M PLACES AND #" TAPcoN I" EMi3ED INTO 17. DRYER VENT SHALL BE MIN. 25 GAUGE METAL PIPE WITH SMOOTH INTERIOR SURFACE OR APPROVED METAL MATERIAL AND INSTALLED AND UTILIZED IN ACCORDANCE DRAWINGS FOR: CON 1141STT WITH MANUFACTURER'S RECOMMENDATIONS. MINIMUM SIZE OF EXHAUST DUCT SHALL BE 4" INTERIOR DIMENSIONS. MAXIMUM LENGTH SHALL NOT EXCEED 25' FROM DRYER EA R ¢" FROM CORNER TYP. LOCATION TO WALL, ROOFCAP OR ENGINEERED EXHAUST SYSTEM. THE _iol 18. BALANCED AIR RETURN - RETURN AIR SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL AREA (SQ INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM ITS SERVING & THE 0 DOOR HAVING UNRESTRICTED 1" UNDERCUT. ALL SUPPLY AIR INTO THE MASTER SUITE SHALL BE INCLUDED. SYLNE a a` 19. SIZING FOR THRU THE WALL TRANSFER GRILLES SHALL USE 50 SQUARE INCHES TO 100 CFM OF SUPPLY AIR WITH UNRESTRICTED 1" DOOR UNDERCUT. RESIDENCE 20. DUCTS SHALL NOT BE INSTALLED IN OR WITHIN 6" OF THE GROUND. 4 CONCRETE SLA5 3 ABOVE 21. DRYER VENT -MIN. 4" GALVANIZED ADJOINING DJ SING FINISHED ° i3GRADE UNIT METAL DUCT TO BE LISTED AND UL LABEL AND CONSTRUCTED AS PER FMC 504.6 AND VENTED TO THE EXTERIOR WITH BACK DRAFT DAMPER AS 504.4&5 ON ALL SIDES' 22. AC SHALL BE IN COMPLIANCE WITH FBC RESIDENTLAL 5TH(2014) EDITION NOTE: A/C COND. UNIT A ANCHORAGE SHALL IBE CAPA5LE 23. AHU UNITS SHALL HAVE A DRAIN PAN WITH OVERFLOW SHUT OFF SWITCH 135 FLAMINGO DRIVE OF SUSTAINING Ii0 MPH WIND LOAD AS PER FBc 16202 24. MECHANICAL EQUIPMENT AND APPLIANCES SHALL BE LOCATED AT OR ABOVE THE ELEVATION REQUIRED BY SECTION 1612.4 Q BOYNTON BEACH FLORIDA 25. CONDENSATE DRAIN LINES SHALL DISCHARGE AT LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, WHETHER BY UNDERGROUND PIPING, TAIL ' EQUIPMENT SCHEDULE & LEGEND Q EXTENSIONS OR SPLASH BLOCKS. AS PER 2014 FBC-8318.5 26. ALL ENVIRONMENTAL AIR EXHAUST SHALL TERMINATE NOT LESS THAN 3 FEET FROM OPERAL OPENINGS AS PER 2014 FMC 501.2.1. r� GENERAL HVAC NOTES 39'-00 Ili -e# 1 11`4" UTILm .wbd uvu t IMPACT RESIST 3707 SH NT IMPACT RESISTANT 000 D . SIN - - OW �. 3/4"0 PVC Iro5 Q GOND. DRAIN OF Q 3TANT I , 'TING -SLA , i� o MIRRO I 4 L 1211 cu @I W 8 V) CD ! �� Q 1 ��!. 41 - mg I 30" PDAET DOOR 4110 a 12 , REPLACE 4110 Q f EXISTING � WINDOW \A/ A Sj (JBL 3740 SSI EGRESS IMPACT REiSTANT 3� Is"xls° U LL H G T. NTNG e EXISTING 2 OPENING REMOVE EXISTING P'AN RNTIT10r INFILL EXISTING A OPENINGI LIVING �1 9,11 RESISTANT -1110 000, 12"x121. R.TJG_ 16/-0& 110--0 "x10" R.T.G. -7"0 FIRST FLOOR HVAC PLAN Scale: 1/4" = V-0" DRAWING INFO DATE 9/16/2016 SCALE VARIES JOB # XXXX DRAWN BY D. MOYER REVISIONS OWNERSHIP AND USE OF THESE DOCUMENTS & SPECIFICATIONS AS INSTRUMENTS OF SERVICE ARE AND SHALL REMAIN THE PROPERTY OF THE K.O. ENERGY DESIGN, LLC. WHETHER THE PROJECT THEY ARE MADE FOR IS EXECUTED OR NOT. THEY SHALL NOT BE USED BY THE OWNER OR OTHERS ON OTHER PROJECTS OR FOR ADDITIONS TO THIS PROJECT BY OTHERS, EXCEPT BY AGREEMENT IN WRITING FROM K.O. ENERGY DESIGN, LLC. DocuSigned by: 561477A05D2941 E... KAREN OLIVER 9/19/2016 FLORIDA STATE LICENSE #CACA15692 SHEET Mel