PERMIT DOCUMENTS DF-61010:A The Fire-Lite SD365(A), SD365T(A), and SD365R(A) Series addressable plug-in photoelectric smoke detectors are designed for both performance and aesthetics. A new modern, sleek, contempo- rary design and enhanced optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources in accordance with more stringent code standards. panels, the SD365(A) Series point ID capability allows each detec- ing exact detector location for emergency personnel to quickly locate a fire during its early stages, potentially saving precious rescue time while also reducing property damage. Two LEDs on each sensor light to provide a local, visible sensor indication. The SD365(A) Series also offers 135°F (57°C) fixed temperature thermal sensing on the SD365T(A) and a remote test capable detec- tor on the SD365R(A) for use with DNR(A)/DNRW duct smoke detector housings. SD365 SD365(A) series plug-in detectors use a detachable mounting base to simplify installation, service and maintenance. Mount base (all base types) on an electrical backbox which is at least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes, see to a broad range of fires. Each SD365(A) Series detector uses one possible addresses on the Fire-liteSignaling Line Circuit (SLC). It responds to regular polls sistant feature. from the system and reports its type and status. cleaning. Each detector can have its sensitivity tested (required per NFPA 72, Chapter 14 on ) when installed/ connected to an ES-50X or ES-200X addressable fire alarm control old level. panel. The results of the sensitivity test can be printed off the for record keeping. with the fire panel) and latches on in alarm. Voltage range: Standby current: 200 A @ 24 VDC. Max current: octagonal box, or 4.0" (10.16 cm) square electrical box Air velocity: 4,000 ft./min. (20 m/sec.) maximum. Sensitivity: UL Applications: 0.5% to 4.0% per foot obscuration Size: 2.0" (5.3 cm) high; base determines diameter. B300-6: 6.1" (15.6 cm) diameter. B501: 4" (10.2 cm) diameter. For a complete list of detector bases see . Shipping weight: 3.4 oz. (95 g). B224BI-IV: Ivory detector base. ( Operating temperature range: B224BIA-WH: White, detector base, ULC listing. B224BIA-IV: Ivory detector base, ULC listing. A)/DNRW -20°C to 70°C (-4°F to 158°F). B200S-WH: White, Intelligent addressable sounder base capable of Relative humidity: 10%-93%, non-condensing. producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and custom tone. Uses FlashScan protocol. B200S-IV: Ivory, Intelligent addressable sounder base capable of Listings and approvals below apply to the SD365 Series detectors. producing sound output in high or low volume with ANSI Temporal 3, In some cases, certain detectors may not be listed by certain ANSI Temporal 4, continuous tone, marching tone, and custom tone. approval agencies, or listing may be in process. Consult factory for Uses FlashScan protocol. latest listing status. B200SA-WH: Same as B200S-WH, ULC listing. B200SA-IV: Same as B200S-IV, ULC listing. B200SCOA-WH: White, Intelligent, programmable sounder base in English/French (required in Canada for ULC applications with CO Series detector applications. B200SCOA-IV: Ivory Intelligent, programmable sounder base in English/French (required in Canada for ULC applications with CO Series detector applications, ULC listing. B200S-LF-WH: White, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- SD365(A): White, Addressable photoelectric detector; B300-6 base 10% with a square wave or its equivalent; designed to meet the included. LiteSpeed only. NFPA 72 sleeping space requirement. ( SD365(A)-IV: Ivory, Addressable photoelectric detector; B300-6 base included. B200S-LF-IV: Ivory, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- SD365T(A): White, Same as SD365 but with thermal element; 10% with a square wave or its equivalent; designed to meet the B300-6 base included. LiteSpeed only. NFPA 72 sleeping space requirement. ( SD365T(A)-IV: Ivory, Same as SD365 but with thermal element; B300-6 base included. B200SR-WH: White, Intelligent sounder base capable of producing SD365R(A): White, Remote test capable addressable photoelectric sound output with ANSI Temporal 3 or continuous tone. Intended for detector for use with DNR(A)/DNRW. LiteSpeed only. retrofit applications. SD365R(A)-IV: Ivory, Remote test capable addressable photoelec- B200SR-IV: Ivory, Intelligent sounder base capable of producing tric detector; for use with DNR(A)/DNRW. sound output with ANSI Temporal 3 or continuous tone. Intended for retrofit applications. B200SRA-WH: Same as B200SR-WH with, ULC listing. B200SRA-IV: Same as B200SR-IV in Ivory color, ULC listing. B300-6: B200SR-LF-WH: White, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- B300-6-IV: 10% with a square wave or its equivalent; designed to meet the base. NFPA 72 sleeping space requirement. Intended for retrofit applica- B300A-6: Same as B300-6, ULC listed. tions. ( B300A-6-IV: B200SR-LF-IV: Ivory, Low Frequency Intelligent, programmable ULC listed. sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the B300-6-BP: Bulk pack of B300-6, package contains 10 NFPA 72 sleeping space requirement. Intended for retrofit applica- B501-WHITE: tions. ( base. UL/ULC listed. B501-BL: UL/ULC listed. TR300: White, replacement flange for B210LP(A) base. B501-IV: TR300-IV: Ivory, replacement flange for B210LP(A) base. base. UL/ULC listed. RA100Z(A): B501-WHITE-BP: Bulk pack of B501-WHITE contains 10. U.S. single-gang electrical box. For use with B501(A) and B300- 6(A). B224RB-WH: White, relay base. ( M02-04-00: Test magnet. B224RB-IV: Ivory, relay base. ( M02-09-00: Test magnet with telescoping handle. B224RBA-WH: White, relay base, ULC listing. CK300: Color Kit (includes cover and trim ring), white, 10-pack. B224RBA-IV: Ivory, relay base, ULC listing. CK300-IV: Color Kit (includes cover and trim ring), ivory, 10-pack. B224BI-WH: White, detector base. ( CK300-BL: Color Kit (includes cover and trim ring), black, 10-pack. FireLite® Alarms is a registered trademark of Honeywell International Inc. ©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. www.firelite.com DTK-2LVLPF is specifically designed to protect 24V SLC loops on fire alarm control panels where a current limiting feature is required. Its low-current fusing prevents induced surges from damaging sensitive (and expensive) control boards. Technical Specifications Service Voltage: 24V MCOV: 38V Product Features Clamping Voltage: 47V Series connection, parallel function adds no Protection Modes: Line-Ground (All) resistance to loop circuits Surge Current Rating: 2,000 Amps per pair Protects up to 2 pairs of SLC wire Max. Continuous Current: 200 mA Mechanical Characteristics Applications Connection Method: #22-#10 AWG screw terminals Alarm Panel SLC Circuits Housing: ABS 4-20 mA Current Loops Operating Temperature: -40°F - 158°F (-40°C - 70°C) Maximum Humidity: 95% non-condensing Accessories 3.0L x 1.6W x 1.6H DIN Rail Kit part number DTK-DRK Dimensions: (76mm x 41mm x 41mm) Weight: 2.65oz (75g) Wiring Example: Quality, Standards & Approval Agency Approvals: UL497B Warranty: Ten Year Limited Warranty intelligent control panels to suit a variety of applications. Moni- tor modules are used to supervise a circuit of dry-contact input devices, such as conventional heat detectors and pull stations, or monitor and power a circuit of two-wire smoke detectors (MMF-302(A)). MMF-300(A) is a standard-sized module (typically mounts to a 4" \[10.16 cm\] square box) that supervises either a Style D (Class A) or Style B (Class B) circuit of dry-contact input devices. MMF-301(A) is a miniature monitor module a mere 1.3" (3.302 cm) H x 2.75" (6.985 cm) W x 0.65" (1.651 cm) D that super- vises a Style B (Class B) circuit of dry-contact input devices. Its compact design allows the MMF-301(A) to be mounted in a single-gang box behind the device it monitors. MMF-302(A) is a standard-sized module used to monitor and 6999cov.jpg supervise compatible two-wire, 24 volt, smoke detectors on a Style D (Class A) or Style B (Class B) circuit. MMF-300(A) (TypeH) MDF-300(A) is a standard-sized dual monitor module used to monitor and supervise two independent two-wire Style B (Class B) dry-contact initiating device circuits (IDCs) at two supervisory indication at the control panel. Monitored circuit separate, consecutive addresses in intelligent, two-wire sys- may be wired as an NFPA Style B (Class B) or Style D (Class tems. A) Initiating Device Circuit. A 47K Ohm End-of-Line Resistor (provided) terminates the Style B circuit. No resistor is required for supervision of the Style D circuit. munication between analog intelligent devices. Intelligent MMF-300(A) O PERATION devices communicate in a grouped fashion. If one of the Each MMF-300(A) uses one of the available module devices within the group has new information, the panel CPU addresses on an SLC loop. It responds to regular polls from stops the group poll and concentrates on single points. The the control panel and reports its type and the status (open/nor- net effect is response speed greater than five times that of mal/short) of its Initiating Device Circuit (IDC). A flashing LED other communication protocols. indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop). MMF-300(A) S PECIFICATIONS as a monitor module to the control panel. Nominal operating voltage: 15 to 32 VDC. power required. Maximum current draw: 5.0 mA (LED on). Average operating current: 375 µA (LED flashing), 1 com- munication every 5 seconds, 47k EOL. Maximum IDC wiring resistance: 1500 Ohms. Maximum IDC Voltage: 11 Volts. EOL resistance: 47K Ohms. to indicate alarm. The MMF-300(A) Monitor Module is intended for use in intelli- Temperature range: 32°F to 120°F (0°C to 49°C). gent, two-wire systems, where the individual address of each Humidity range: 10% to 93% noncondensing. module is selected using the built-in rotary switches. It pro- Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x vides either a two-wire or four-wire fault-tolerant Initiating 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x Device Circuit (IDC) for normally-open-contact fire alarm and 2.125" (5.398 cm) deep box. supervisory devices. The module has a panel-controlled LED indicator. The MMF-300(A) can be used to replace M300(A) modules in existing systems. MMF-300(A) A PPLICATIONS as a monitor module to the panel. Use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally- power required. open dry-contact alarm activation devices. May also be used to monitor normally-open supervisory devices with special source. 6720m101.wmf control panel. The MMF-302(A) Interface Module is intended for use in intelli- gent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two- wire conventional smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two-wire detectors being monitored must be UL compatible with the module. The MMF-302(A) can be used to replace M302(A) modules in existing systems. MMF-302 (A) A PPLICATIONS Use the MMF-302(A) to monitor a zone of two-wire smoke The MMF-301(A) Mini Monitor Module can be installed in a detectors. The monitored circuit may be wired as an NFPA single-gang junction directly behind the monitored unit. Its Style B (Class B) or Style D (Class A) Initiating Device Circuit. small size and light weight allow it to be installed without rigid A 3.9 K Ohm End-of-Line Resistor (provided) terminates the mounting. The MMF-301(A) is intended for use in intelligent, end of the Style B or D (class B or A) circuit (maximum IDC two-wire systems where the individual address of each module loop resistance is 25 Ohms). Install ELR across terminals 8 is selected using rotary switches. It provides a two-wire initiat- and 9 for Style D application. ing device circuit for normally-open-contact fire alarm devices. MMF-302(A) O PERATION The MMF-301(A) can be used to replace M301(A) modules in existing systems. Each MMF-302(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from MMF-301(A) A PPLICATIONS the control panel and reports its type and the status (open/nor- Use to monitor a single device or a zone of four-wire smoke mal/short) of its Initiating Device Circuit (IDC). A flashing LED detectors, manual fire alarm pull stations, waterflow devices, indicates that the module is in communication with the control or other normally-open dry-contact devices. May also be used panel. The LED latches steady on alarm (subject to current to monitor normally-open supervisory devices with special limitations on the loop). supervisory indication at the control panel. Monitored circuit/ MMF-302(A) S PECIFICATIONS device is wired as an NFPA Style B (Class B) Initiating Device Circuit. A 47K Ohm End-of-Line Resistor (provided) terminates Nominal operating voltage: 15 to 32 VDC. the circuit. Maximum current draw: 5.1 mA (LED on). MMF-301(A) O PERATION Maximum IDC wiring resistance: 25 Ohms. Each MMF-301(A) uses one of the available module Average operating current: 270 µA, 1 communication and 1 addresses on an SLC loop. It responds to regular polls from LED flash every 5 seconds, 3.9k eol. the control panel and reports its type and the status (open/nor- EOL resistance: 3.9K Ohms. mal/short) of its Initiating Device Circuit (IDC). External supply voltage (between Terminals T10 and T11): MMF-301(A) S PECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Average operating current: 350 µA, 1 communication every 5 seconds, 47k EOL; 600 µA Max. (Communicating, IDC Temperature range: 32°F to 120°F (0°C to 49°C). Shorted). Humidity range: 10% to 93% noncondensing. Maximum IDC wiring resistance: 1500 Ohms. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x Maximum IDC Voltage: 11 Volts. 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x Maximum IDC Current: 450 µA. 2.125" (5.398 cm) deep box. EOL resistance: 47K Ohms. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. The MDF-300(A) Dual Monitor Module is intended for use in intelligent, two-wire systems. It provides two independent two- Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x wire initiating device circuits (IDCs) at two separate, consecutive 0.65" (1.651 cm) deep. addresses. It is capable of monitoring normally open contact fire Wire length: 6" (15.24 cm) minimum. alarm and supervisory devices. The module has a single panel- controlled LED. NOTE: The MDF-300(A) provides two Style B (Class B) IDC cir- MDF-300(A): Monitor module, dual, two independent Class B cuits ONLY. Style D (Class A) IDC circuits are NOT supported in circuits. any application. SMB500: Optional surface-mount backbox. MDF-300(A) S PECIFICATIONS NOTE: See installation instructions and refer to the SLC Wiring Manual, PN 51309. Normal operating voltage range: 15 to 32 VDC. Maximum current draw: 6.4 mA (LED on). Average operating current: 750 µA (LED flashing). Specifications of these devices and all FireLite products are Maximum IDC wiring resistance: 1,500 Ohms. available from FireLite. Maximum IDC Voltage: 11 Volts. Maximum IDC Current: 240 µA EOL resistance: 47K Ohms. Temperature range: 32° to 120°F (0° to 49°C). Humidity range: 10% to 93% (non-condensing). Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box. MDF-300(A) A UTOMATIC A DDRESSING The MDF-300(A) automatically assigns itself to two address- able points, starting with the original address. For example, if NOTE: only. Terminals 6 and 7 use the first address, and terminals 8 and 9 use the second address. CAUTION: Avoid duplicating addresses on the system. MMF-300(A), MMF-302(A), and MDF-300(A) modules mount directly to a standard 4" (10.16 cm) square, 2.125" (5.398 cm) deep, electrical box. They may also be mounted to the SMB500 surface-mount box. Mounting hardware and installa- tion instructions are provided with each module. All wiring must conform to applicable local codes, ordinances, and regu- lations. These modules are intended for power-limited wiring only. The MMF-301(A) module is intended to be wired and mounted without rigid connections inside a standard electrical box. All wiring must conform to applicable local codes, ordinances, and regulations. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. UL: S2424. ULC: S2424. CSFM: 7300-0075:0185. MEA: 72-01-E. NOTE: MMF-300(A): Monitor module. MMF-301(A): Monitor module, miniature. MMF-302(A): Monitor module, two-wire detectors. trademarks of Honeywell International Inc. ©2015 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. www.firelite.com DF-60957:C The ES-200X is the latest intelligent addressable Fire Alarm Control the MS-9200UDLS. The ES-200X comes with a pre-installed com- municator and supports up to 198 addressable devices (99 detec- tors and 99 modules). With an extensive list of powerful features, the yet fits into applications previously served only by conventional pan- els. The pre-installed IPOTS-COM is a dual technology (POTS and IP) communicator. The POTS transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone alarm signals over the Internet saving the monthly cost of two dedi- cated business telephone lines. Although not required, the second- ary telephone line may be retained providing backup communication over the public switched telephone line. Optional cellular reporting is available using the CELL-MOD or CELL-CAB-FL. Remote and local programming of the control panel is possible using the FS-Tools Upload/Download utility. Programming databases can or via an ethernet connection using the IPOTS-COM communicator. The USB port also allows for the download or upload of the entire program, history file, walk-test data, current status and system volt- ages by means of a USB flash drive. The power supply and all electronics are contained on a circuit tion is excessive board supported on a new quick install chassis and housed in a metal cabinet. Available accessories include local and remote printout upload/download software, remote annunciators, and reverse polar- ity/city box transmitter (4XTMF). 72 compliant) IP and POTS (Plain Old Tele- addressable modules or remote annunciator phone Service) Central Station Communicator over AlarmNet Tools Programming Utility Communicator over AlarmNet® SLC COMMUNICATION LOOP Center twisted, unshielded wire reduces installation time. Reports two devices set to the same address Class A requirements Style Y (Class B) NAC circuits 99 modules) and Gentex devices SLC Wiring Manual) NOTIFICATION APPLIANCE CIRCUITS (NACS) configured for the following outputs: (Class B) (Class A) response circuit board NACs with two-stage capability NOTE: Maximum or total 24VDC system power shared between all NAC circuits and the ANN-BUS is 2.7A PROGRAMMING AND SOFTWARE PRN Series: UL listed compatible event printer. Uses tractor-fed paper. OPTIONAL MODULES selected from an internal library file 4XTMF Reverse Polarity Transmitter Module: Provides a super- vised output for local energy municipal box transmitter, alarm and trouble. Includes a disable switch and disable trouble LED. PWRMOD24 Power Expander Module: Optional power module. Increases alarm power output to 6 amps. to any zone or input point COMPATIBLE ANNUNCIATORS OFFLINE PROGRAMMING: Create the entire program in your ANN-80: Remote LCD annunciator mimics the information dis- office using FS-Tools, a Windows®-based software package, and played on the FACP LCD display. Recommended wire type is un- upload/download system programming locally. Offline program- shielded. ming requires an ethernet connection. FS-Tools is available on ANN-100: Remote LCD annunciator mimics the information dis- www.firelite.com. played on the FACP LCD display. Recommended wire type is un- shielded. For use in FM applications only. ANN-I/O: LED Driver Module provides connections to a user sup- LED INDICATORS plied graphic annunciator. (See DF-52430.) ANN-LED: Annunciator Module provides three LEDs for each zone: Alarm, Trouble, and Supervisory. Ships with red enclosure. (See DF- 60241.) ANN-RLED: Provides alarm (red) indicators for up to 30 input zones or addressable points. (See DF-60241.) ANN-RLY: Relay Module provides 10 programmable Form-C relays. Can be mounted inside the cabinet. (See DF-52431.) ANN-S/PG: Serial/Parallel Printer Gateway module provides a con- nection for a serial or parallel printer. (See DF-52429.) ADDRESSABLE DEVICES All feature a polling LED and rotary switches for addressing. SD365: Addressable low-profile photoelectric smoke detector. Lite- Speed only. SD365-IV: Addressable low-profile photoelectric smoke detector. KEYPAD Ivory. LiteSpeed and CLIP mode. SD365T: Addressable low-profile photoelectric smoke detector with thermal sensor. LiteSpeed only. SD365T-IV: Addressable low-profile photoelectric smoke detector with thermal sensor. Ivory. LiteSpeed and CLIP mode. SD365R: Remote test capable addressable photoelectric smoke detector for use with DNR(W) duct detector housing. LiteSpeed only. SD365R-IV: Remote test capable addressable photoelectric smoke PRODUCT LINE INFORMATION detector for use with DNR(W) duct detector housing. Ivory. Lite- ES-200X: Addressable Fire Alarm Control Panel with one SLC loop. Speed and CLIP mode. Includes main circuit board with display, pre-installed communicator, H365: Low-profile 135°F fixed thermal sensor. LiteSpeed only. chassis with transformer, backbox with door, plastic bag containing H365-IV: Low-profile 135°F fixed thermal sensor. Ivory. LiteSpeed screws, cables, key, etc. (For ES-200XC, refer to DF-60958.) and CLIP mode. FS-Tools: Programming software for Windows®-based PC com- puter. Available for download at www.firelite.com. H365R: Low-profile, intelligent, rate-of-rise thermal sensor. Lite- Speed only. CELL-CAB-FL/CELL-MOD: Optional GSM communicators. IPOTS-COM: Dual technology (POTS and IP) communicator.H365R-IV: Low-profile, intelligent, rate-of-rise thermal sensor. Ivory. (replacement board)LiteSpeed and CLIP mode. DP-ES-R: Optional dress panel for the ES-200X. H365HT: Low-profile intelligent 190°F/88°C fixed thermal sensor. LiteSpeed only. TR-CE: Optional trim ring for semi-flush mounting. BB-2F: Optional cabinet for one or two modules. H365HT-IV: Low-profile intelligent 190°F/88°C fixed thermal sensor. Ivory. LiteSpeed and CLIP mode. BB-6F: Optional cabinet for up to six modules mounted on CHS-6 chassis. BB-26: Battery backbox, holds up to two 25 AH batteries and CHG- CP355: Addressable low-profile ionization smoke detector. 75. SD355: Addressable low-profile photoelectric smoke detector. BB-55F: Battery box, houses two 55 AH batteries SD355T: Addressable low-profile photoelectric smoke detector with CHS-6: Chassis, mounts up to six multi-modules in a BB-6F cabinet. thermal sensor. CHG-75: Battery charger for lead-acid batteries with a rating of 25 to SD355R: Remote test capable addressable photoelectric smoke 75 AH. detector for use with DNR(W) duct detector housing. CHG-120F: Remote battery charging system for lead-acid batteries SD355CO: Addressable, low-profile device that provides fire, heat, with a rating of 55 to 120 AH. Requires additional BB-55F for mount- and carbon monoxide (CO) detection. ing. H355: Fast-response, low-profile heat detector. BAT Series: Batteries, see data sheet DF-52397. H355R: Fast-response, low-profile heat detector with rate-of-rise option. H355HT: Fast-response, low-profile heat detector that activates at 190°F/88°C. AD355: Low-profile, intelligent, (B350LP base included). W-H355: LiteSpeed intelligent wireless fixed-temperature (135°) B200SR: Addressable sounder base. heat detector. W-MMF: LiteSpeed Intelligent wireless monitor module. BEAM355: Intelligent beam smoke detector. W-CRF: LiteSpeed Intelligent wireless relay module. BEAM355S: Intelligent beam smoke detector with integral sensitiv- ity test. W-BG12LX: LiteSpeed Intelligent wireless pull station. D355PL: InnovairFlex low-flow non-relay duct-detector housing; WAV-RL, WAV-WL,WAV-CRL,WAV-CWL: LiteSpeed Intelligent AV includes SD355R. bases. W-USB: Wireless USB radio/antenna dongle that plugs into the DNR: InnovairFlex low-flow non-relay duct-detector housing. (Order USB port of a PC running SWIFT Tools. SD355R/SD365R separately.) SWIFT Tools: Programming and diagnostic utility for the Wireless DNRW: InnovairFlex low-flow non-relay duct-detector housing, with Gateway and devices. Available for download from firelite.com. NEMA-4 rating. Watertight. (Order SD355R/SD365R separately.) NOTE: For more information on Compatible Addressable Devices for use with the ES-200X, see the following data sheets (document num- MMF-300: Addressable Monitor Module for one zone of normally- bers): SD365 Series (DF-61010), H365 Series (DF-61011), AD355 open dry-contact initiating devices. Mounts in standard 4.0" (10.16 (DF-52386), BG-12LX (DF-52013), CMF-300-6 (DF-52365), CRF-300-6 cm.) box. Includes plastic cover plate and end-of-line resistor. Mod- (DF-52374), CMF/CRF Series (DF-52130), CP355 (DF-52383), H355 ule may be configured for either a Style B (Class B) or Style D (Class Series(DF-52385), I300 (DF-52389), ISO-6 (DF-60485), MMF-300 A)IDC. Series/MDF-300 (DF-52121), MMF-300-10 (DF-52347), MMF-302-6 (DF-52356), SD355/SD355T (DF-52384), and SLC Wiring Manual MDF-300: Dual Monitor Module. Same as MMF-300 except it pro- (51309). vides two Style B (Class B) only IDCs. NOTE: Legacy 300 Series detection devices such as the CP300/CP350, MMF-301: Miniature version of MMF-300. Excludes LED and Style SD300(T)/SD350(T) and older modules such as the M300, M301, M302, D option. Connects with wire pigtails. May mount in device backbox. C304, and BG-10LX are not compatible with LiteSpeed polling. If the MMF-302: Similar to MMF-300. Addressable Monitor Module for one SLC contains one of these devices, polling must be set for standard zone of conventional two-wire detectors. Requires resettable 24 CLIP protocol. Please consult factory for further information on previous VDC power. Refer to the Device Compatibility Document for listed 300 Series devices. compatible devices and quantity limitation. ADDRESSABLE DEVICE ACCESSORIES CMF-300: Addressable Control Module for one Style Y/Z (Class B/ End-of-Line Resistor Assembly (R-47K and R-3.9K): The A)zone of supervised polarized Notification Appliances. Mounts 47kohm assembly supervises the MMF-300, MDF-300, MMF-301, directly to a 4.0" (10.16 cm.) electrical box. NAC option requires and CMF-300 module circuits. The 3.9kohm assembly supervises external 24 VDC to power notification appliances. the MMF-302 module circuit. These resistors are included with each CRF-300: Addressable relay module containing two isolated sets of module. Form-C contacts, which operate as a DPDT switch. Mounts directly Power Supervision Relay: Supervises the power to 4-wire smoke to a 4.0" (10.16 cm.) box, surface mount using the SMB500. detectors and notification appliances. BG-12LX: Addressable manual pull station with interface module mounted inside. I300: This module isolates the SLC loop from short circuit conditions While shielded wire is not required, it is recommended that all SLC (required for Style 6 or 7 operation). wiring be twisted-pair to minimize the effects of electrical interfer- ISO-6: Six-fault isolator module. Mount one or two modules in a ence. Refer to the panel manual for wiring details. BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassisin a BB-6F cabinet. SMB500: Used to mount all modules except the MMF-301 and M301. MMF-300-10: Ten-input monitor module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. MMF-302-6: Six-zone interface module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. CMF-300-6: Six-circuit supervised control module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. CRF-300-6: Six-relay control module (Form-C relays). Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. SYSTEM SPECIFICATIONS 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in 80°F. AC Power: 120240 VAC, 50/60 Hz, 3.25A . Wire size: minimum 14AWG (2.00 mm2) with 600 V insulation. Nonpower-limited, supervised. The ES-200X complies with the following NFPA 72 Fire Alarm Sys- Battery: Two 12 V 18AH lead-acid batteries. Battery Charger tems requirements: Capacity: 7-18AH (ES-200X cabinet holds maximum of two 18AH batteries.) (Automatic, Manual, Waterflow and Sprinkler Supervi- sory). Communication Loop: Supervised and power-limited. (Automatic, Manual and Waterflow) (requires Notification Appliance Circuits: Terminal Block provides connec- 4XTMF). tions for four NACs, Style Y (Class B) or Style Z (Class A). Special (Automatic, Manual and Waterflow) Application power. Power-limited, supervised circuitry. Maximum (Where a DACT is not accepted, the alarm, trouble and supervi- signaling current per circuit: 2.5amps special application, 250mA sory relays may be connected to UL 864 listed transmitters. For regulated. End-of-Line Resistor: 4.7kohm, ½ watt (P/N 71252 UL reverse polarity signaling of alarm and trouble, 4XTMF is listed) for Style Y (Class B) NAC; system capable of 1.9 k - 22k required.) ELR range. Refer to the for (Automatic, Manual and Waterflow). listed compatible devices. (Automatic, Manual and Waterflow, and Two Programmable Relays and One Fixed Trouble Relay: Con- Sprinkler Supervised). tact rating: 2.0A @ 30 VDC (resistive), 0.5A @ 30 VAC (resistive). Form-C relays, non-power-limited, non-supervised. (Other Technologies, Packet-switched Data Net- work) (Seismic). (Seismic) Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x 0.72" (1.82 cm.) deep. Backbox: 19.00" (48.26 cm.) high x 16.65" (42.29 cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring (TR-CE): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide. The listings and approvals below apply to the basic ES-200X control panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. Weight: 26.9 lbs. (12.20 kg.) Dimensions: 2080 cm.) high wide x deep. UL: S624 FM approved CSFM: 7165-0075:500 FDNY: COA #6261 NOTE: See DF-60958 for ULC-listed model. AlarmNet®, Fire-Lite® Alarms, SWIFT®, and System Sensor® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. ©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Country of Origin: USA www.firelite.com DTK-HW Series of surge protective devicesare designed and manufactured to meet thestandards of the life safety industry. These compact,parallel-available for 120V, 240V and 120/240V systems; andare widely used to protect fire alarm panels and other dedicated branch circuit loads.Their small footprint enables installation in a variety of locations. Technical Specifications Part Number:DTK-120HWDTK-240HWDTK-120/240HW Single SingleSplit Service Voltage: (2W+G), (2W+G), (3W+G), ProductFeatures 120VAC240VAC120/240VAC Approved for 20A circuit breakers MCOV: 150V320V150/320V NEMA 4X Weatherproof enclosureallows Protection Modes: L-G, L-N, N-GL-G, L-N, N-GL-G, L-L, L-N, N-G for use in harsh environments 700V L-G1,200V L-G,700V L-G, L-N Voltage Protection Diagnostic LED indicates ground presence, 700VL-N1,200V L-N1,500V L-L, Rating: 1,500V N-G2,000V N-G1,500V N-G system power and SPD function Surge Current Complies with ANSI/IEEE C62.41 and 50,000A50,000A100,000A Rating: C62.45 Category B standards SCCR:10kA Nominal Discharge Applications 10kA Current Rating (I n): Fire Alarm Control Panels Mechanical Characteristics Equipment Panels Connection Method:Parallel Wired Dedicated BranchCircuits Housing:NEMA 4X Pumps,MotorsandLift Pump Stations Temperature Range:-31°F-176°F (-35°C-80°C) Maximum Humidity: 95% non-condensing Accessories 3.584 Dimensions: (88.9mm x 48.3mm x 86.4mm) DIN Rail Mounting Kit DTK-DRK Weight:0.55lb. (0.25 kg) Dimensions Quality, Standards & Approval th Agency Approvals: UL 14494Edition, cUL SPD Type:Type 1SPD Warranty:Ten Year Limited DTK-2MHLPB series of signal, data and loop circuit surge protectors provide robust protection in a compact package. This series was designed for ease of installation, with convenient field-replaceable modules and a Snap-Track base system, allowing the installer to protect multiple circuits while utilizing a common ground point. Technical Specifications DTK-2MHLP 5B 12B 24B 36B 48B 75B Product Features Service Voltage: 5V 12V 24V 36V 48V 75V MCOV: 6V 18V 33V 48V 64V 90V Protects two pairs per module Clamping Voltage: 6.8V 21.6V 39V 57V 76V 108V Multi-stage, SAD technology, hybrid design, provides the best possible protection Protection Modes: Line-Ground (All) Field replaceable, modular edge card connection Surge Current design with a single point ground for fast 20,000 Amps Rating: installation, saves time Max Continuous Six voltage levels available to protect all types of 5 Amps Current: voice/data applications Data Rate: 200kbps to 2Mbps Hard-wired multi-base mounting system allows you to protect up to ten pairs with a common ground. See next page for base part numbers Mechanical Characteristics Suitable for use on both AC and DC circuits Base Connection 10AWG max screw terminals Method: Module Connection Edge card into mounting base Applications Method: Fire Alarm Panel NAC, SLC, PIV and IDC Circuits Housing: ABS Burglar Alarm Panels NAC and IDC Circuits Operating -40°F - 158°F (-40°C - 70°C) 70V Speakers and Audio Equipment Temperature: Low-Voltage Landscape Lighting and Lighting Maximum Humidity: 95% non-condensing Control Circuits Module Module with Base 4-20mA Current Loops Dimensions: Weight: 1.2 oz (34g) 2.8 oz (79g) Accessories Quality, Standards & Approval part number Agency Approvals: UL497B Test Module Kit Part Number DTK-2MHLPTM Warranty: Ten Year Limited Warranty DIN Rail Mounting Kit Part Number DTK-DRK DTK-MB10 2 DTK-2MB 4 DTK-3MB 6 DTK- 4MB 8 DTK- 5MB 10 DTK-MB10 DTK-3MB DTK-2MB DTK-5MB DTK-4MB The CMF-300(A) Addressable Control Module provides Appliances (horns, strobes, etc.). Addressability allows the CMF-300(A) to be activated through panel programming, on a select (zone or area of coverage) basis. munication between analog intelligent devices. Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new information, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other designs. devices to the control panel. The CMF-300(A) module requires power (for horns,CMF-300(A) strobes, etc.). received from the control panel and turns on steady red external power supply is always relay-isolated from the com- when activated. munication loop so that a trouble condition on the external power supply will never interfere with the rest of the system. Rotary switches set a unique address for each module. The power. address may be set before or after mounting. The built-in TYPE CODE (not settable) will identify the module to the con- trol panel, so as to differentiate between a module and a sen- sor address. Normal operating voltage: 15 to 32 VDC. Maximum SLC current draw: 6.5 mA (LED on). The CMF-300(A) is used to switch 24 VDC audible/visual power. Average operating current: 350 A direct poll (CLIP mode), 375 A group poll (LiteSpeed mode) with LED flashing. External supply voltage: maximum 80 volts (RMS or DC). Drain on external supply: 2 mA maximum (using internal EOL relay). address setting. EOL resistance: 47K ohms. Temperature range: 32°F to 120°F (0°C to 49°C). or Class A (Style Z) Notification Appliance Circuit. Humidity range: 10% to 93% non-condensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x Each CMF-300(A) uses one of the module addresses on a 2.125" (5.398 cm) deep box. SLC loop. It responds to regular polls from the control panel and reports its type and status, including the open/normal/ short status of its Notification Appliance Circuit (NAC). The LED blinks with each poll received. On command, it activates In some cases, certain modules may not be listed by certain its internal relay. The CMF-300(A) supervises Class B (Style approval agencies, or listing may be in process. Consult fac- Y) or Class A (Style Z) notification or control circuits. tory for latest listing status. Upon code command from the panel, the CMF-300(A) will dis- ULC: S2424 connect the supervision and connect the external power sup- ply in the proper polarity across the load device. The disconnection of the supervision provides a positive indication to the panel that the control relay actually turned ON. The CMF-300: Intelligent addressable control module. CMF-300A: Canadian intelligent addressable control module. SMB500: Optional surface-mount backbox. CB500: Optional control module barrier, required by UL for separating power-limited and non-power-limited wiring in the same junction box as CMF-300(A). of Honeywell International Inc. ©2010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Made in the U.S. A. www.firelite.com The Fire·Lite BG-12LX is a state-of-the-art, dual-action (i.e., requires two motions to activate the station) pull station that includes an addressable interface (mounted inside) for Because the BG-12LX is addressable, the control panel can display the exact location of the activated manual station. This leads fire personnel quickly to the location of the alarm. address setting without causing an alarm condition. the station, flashes in normal operation and latches steady red when in alarm. appears to clearly indicate the station has been operated. SLC loop (accepts up to 12 AWG/3.25 mm² wire). flush mounted. Semi-flush mount to a standard single- gang, double-gang, or 4" (10.16 cm) square electrical box. lines (Section 4.1.3\[13\]); meets ADA requirement for 5 lb. maximum activation force. usually needed for semi-flush mounting with 4" (10.16 cm) or double-gang boxes (not with single-gang boxes). Pushing in, then pulling down on the handle causes it to latch Boxes. while a portion of the handle protrudes from the bottom of the station. To reset the station, simply unlock the station with the key and pull the door open. This action resets the handle; clos- ing the door automatically resets the switch. Shell, door, and handle are molded of durable polycarbonate Each manual station, on command from the control panel, material with a textured finish. sends data to the panel representing the state of the manual switch. Two rotary decimal switches allow address settings Shipping Weight: 9.6 oz. (272.15 g) Normal operating voltage: 24 VDC. Maximum SLC loop voltage: 28.0 VDC. Maximum SLC standby current: 375 A. Maximum SLC alarm current: 5 mA. Manual Fire Alarm Stations shall be non-coded, with a key- operated reset lock in order that they may be tested, and so Temperature Range: 32°F to 120°F (0°C to 49°C) designed that after actual Emergency Operation, they cannot Relative Humidity: 10% to 93% (noncondensing) be restored to normal except by use of a key. An operated sta- For use indoors in a dry location tion shall automatically condition itself so as to be visually detected as activated. Manual stations shall be constructed of red-colored polycarbonate material with clearly visible operat- ing instructions provided on the cover. The word FIRE shall The BG-12LX will mount semi-flush into a single-gang, double- appear on the front of the stations in white letters, 1.00 inches gang, or standard 4" (10.16 cm) square electrical outlet box, or (2.54 cm) or larger. Stations shall be suitable for surface will surface mount to the model SB-10 or SB-I/O surface back- mounting on matching backbox SB-10 or SB-I/O; or semi-flush box. If the BG-12LX is being semi-flush mounted, then the mounting on a standard single-gang, double-gang, or optional trim ring (BG12TR) may be used. The BG12TR is 4"(10.16 cm) square electrical box, and shall be installed within the limits defined by the Americans with Disabilities Act (ADA) or per national/local requirements. Manual Stations shall be Underwriters Laboratories listed. Manual stations shall connect with two wires to one of the con- trol panel SLC loops. The manual station shall, on command from the control panel, send data to the panel representing the state of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches. BG-12LX: Dual-action addressable pull station. Includes key locking feature. (Listed for Canadian and non-Canadian appli- cations.) SB-10: Surface backbox; metal. SB-I/O: Surface backbox; plastic. BG12TR: Optional trim ring. 17003: Keys, set of two. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in pro- cess. Consult factory for latest listing status. UL/ULC Listed: S711 (listed for Canadian and non-Cana- dian applications). MEA: 67-02-E. 7150-0075:0184. Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772; 6,632,108. FireLite® Alarms® is a registered trademark of Honeywell International Inc. ©2012 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Made in the U.S. A. www.firelite.com The ANN-80 annunciator is a compact, backlit, 80-character LCD fire annunciator that mimics the Fire Alarm Control Panel (FACP) display. It provides system status indicators for AC Power, Alarm, Trouble, Supervisory, and Alarm Silenced condi- tions. The ANN-80 and the FACP communicate over a two-wire serial interface employing the ANN-BUS communication format. Connected devices are powered, via two additional wires, by either the host FACP or a remote UL-listed, filtered power supply. ANN-80 is red; for white, order ANN-80-W. The ANN-80 displays English-language text of system point information including device type, zone, independent point alarm, trouble or supervisory status, as well as any custom alpha labels programmed into the control panel. It includes con- trol switches for remote control of critical system functions. (A keyswitch prevents unauthorized operation of the control switches.) Up to eight ANN-80s may be connected to the ANN-BUS of 52417cov.jpg each FACP. No programming is required, which saves time dur- ing system commissioning. Drill, and Reset. Operating voltage range: 18 VDC to 28 VDC. at the FACP. Current consumption @ 24 VDC nominal (filtered and non- resettable): 40 mA maximum. cally locks annunciator enclosure Ambient temperature: 32°F to 120°F (0°C to 49°C). Relative humidity: 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). sory, and Alarm Silence. (3.49 cm.) deep. requires minimal panel programming. ble, supervisory, zone, and custom alpha labels. The listings and approvals below apply to the ANN-80. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest square electrical box. listing status. UL: S2424 box. Use ANN-SB80KIT for angled view mounting. CSFM: 7120-0075:211 panel. MEA: 442-06-E but will turn back on if an alarm condition occurs. power supply (requires 24 VDC). The ANN-BUS can be powered by an auxiliary power supply when the maximum number of ANN-BUS devices exceeds the ANN-BUS power requirements. See the FACP manual for more information. After calculating the total worst case current draw, the following table specifies the maximum distance the modules can be Each ANN-BUS device requires a unique address (ID Number) located from the FACP on a single wire run. The table ensures in order to communicate with the FACP. A maximum of 8 devices 6.0 volts of line drop maximum. In general, the wire length is lim- can be connected to the FACP ANN-BUS communication circuit. ited by resistance, but for heavier wire gauges, capacitance is See the FACP manual for more information. the limiting factor. These cases are marked in the chart with an asterisk (*). Maxi- mum length can never be more than 6,000 feet (1,800 m), The ANN-80 connects to the FACP ANN-BUS communications regardless of gauge used. See table below. circuit. To determine the type of wire and the maximum wiring distance that can be used with FACP ANN-BUS accessory mod- ules, it is necessary to calculate the total worst case current 2 ) wire for 24 VDC power cir- draw for all modules on a single 4-conductor bus. The total worst cuit is acceptable. Power wire distance limitation is set by 1.2 case current draw is calculated by adding the individual worst volt maximum line drop form source to end of circuit. case currents for each module. this circuit. Communication Pair Wiring Distance: FACP to Last ANN-BUS Module Total Worst Case 22 Gauge18 Gauge16 Gauge14 Gauge Current Draw (amps) 0.1001,852 ft.4,688 ft.* 6,000 ft.*6,000 ft. 0.200926 ft.2,344 ft.3,731 ft.5,906 ft. 0.300617 ft.1,563 ft.2,488 ft.3,937 ft. 0.400463 ft.1,172 ft.1,866 ft.2,953 ft. 0.500370 ft.938 ft.1,493 ft.2,362 ft. 0.600309 ft.781 ft.1,244 ft.1,969 ft. 0.700265 ft.670 ft.1,066 ft.1,687 ft. 0.800231 ft.586 ft.933 ft.1,476 ft. 0.900206 ft.521 ft.829 ft.1,312 ft. 1.000 (max.)185 ft.469 ft.746 ft.1,181 ft. The following figure illustrates the wiring between the FACP and ANN-80: Red 80 character LCD Annunciator. ANN-BUS devices. ANN-80-W: White, 80 character LCD Annunciator. ANN-BUS and power ANN-SB80KIT-R: Red surface mount backbox with angled wiring are supervised wedge. and power-limited. ANN-SB80KIT-W: White surface mount backbox with angled wedge. ANN-BUS Device MS-9050UD FACP Wiring to ANN-BUS Device FireLite® Alarms is a registered trademark of Honeywell International Inc. ©2009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Made in the U.S. A. www.firelite.com