DRAWINGS
DESIGN AREA #A-1
1ST FLOOR OUTSIDE DWELLING UNIT
DESIGN PER NFPA 13R,
SECTION 7.2
22
123123
FT.FT.
S20S21
.15DENSITY @7PSI.15DENSITY @7PSI
22
123123
FT.FT.
S22S23
.15DENSITY @7PSI.15DENSITY @7PSI
DENSITY.15
R00948N
DOMESTIC DEMAND - GPM
131
CORTINA
OLD BOYNTON ROAD
BOYNTON BEACH, FLORIDA
MORGAN GROUP
316 NE 4TH STREET, SUITE 4
FT. LAUDERDALE, FL 33301
BLDG 1 - TYPE I FIRST FLOOR
STEVEN A ZWALLY
573
AUGUST 30, 2018
CITY OF BOYNTON BEACH
91653
ISSUE FOR CONSTRUCTION 06/11/2019
IIIB
R2, S2
FP2
CORTINA
OLD BOYNTON ROAD
BOYNTON BEACH, FLORIDA
MORGAN GROUP
316 NE 4TH STREET, SUITE 4
FT. LAUDERDALE, FL 33301
BLDG 1 - TYPE I SECOND & THIRD FLOOR
STEVEN A ZWALLY
573
AUGUST 30, 2018
CITY OF BOYNTON BEACH
91653
IIIB
ISSUE FOR CONSTRUCTION 06/11/2019
R2, S2
FP3
DESIGN AREA #3
FLOOR UNIT C2 BEDROOM
COMPARTMENT DESIGN PER NFPA 13R,
SECTION 7.1.1
18' X 18'SPACING
S44
17GPM @12.0PSI
SINGLE SPRINKLER PROOF CALCULATION
R00943N
DOMESTIC DEMAND - GPM
131
DESIGN AREA #4
DESIGN AREA #2
4TH FLOOR OUTSIDE DWELLING UNIT
FLOOR UNIT C1 COMMON AREA
4TH
DESIGN PER NFPA 13R,
COMPARTMENT DESIGN PER NFPA 13R,
SECTION 7.2
SECTION 7.1.1
22
8383
FT.FT.
16' X 16'SPACING 16'w X 16't SPACING
S45S47
S40S42
.10DENSITY @7PSI.10DENSITY @7PSI
13GPM @7PSI14GPM @12.3PSI
22
8342
FT.FT.
16' X 16'SPACING 16' X 16'SPACING
S46S48
S41S43
.10DENSITY @7PSI.10DENSITY @7PSI
13GPM @7PSI13GPM @7PSI
DENSITY.10
DENSITY.05
R00948N
DOMESTIC DEMAND - GPM
131
R00946N
DOMESTIC DEMAND - GPM 131
CORTINA
OLD BOYNTON ROAD
BOYNTON BEACH, FLORIDA
MORGAN GROUP
316 NE 4TH STREET, SUITE 4
FT. LAUDERDALE, FL 33301
BLDG 1 - TYPE I FOURTH FLOOR
STEVEN A ZWALLY
573
AUGUST 30, 2018
CITY OF BOYNTON BEACH
91653
IIIB
ISSUE FOR CONSTRUCTION 06/11/2019
FP4
R2, S2