DRAWINGSBQQSPWFE
GJSF
dmjofl!1901603132
Johnson Controls
1830 Park Lane South
BQQSPWFE
Jupiter FL. 33458
FMFDUSJD
cbmvzpun!1901703132
INSTALLING CONTRACTOR:
R
CONTACT INFORMATION:
Fire Alarm System
BUILDING INFORMATION
Scope of work
General notes:
Occupancy Type: A2
Add Sole Path cellular communicator to existing system
1.All fire alarm devices are to be installed according the the requirements of NFPA 72 and the
Sprinkler System: NO
manufactures instructions.
Total Area 5320 sq ft
2.All fire alarm devices are to be mounted on back boxes.
Occupancy Load 266 (+/-)
3.All fire alarm devices are to be UL Listed and compatible.
Number of Stories 1
4.All wire is to be in conduit from the device back box to above the false ceiling or to the bar
Construction Type VB
joists. Wire may be run exposed horizontally but must be attached to the building structure
Egress Doors NO
or supported by approved hangers.
Door Holders NO
5.All wire is to be Power Limited, Type FPLP unless otherwise noted. All wiring is to be
Number of AHU 3
installed in accordance with the adapted NFPA 70 (NEC Section 760), NFPA 72 and all
local codes.
SHEET INDEX
6.Control panels and power supplies are to be mounted in the manager's office unless the
FA1.1 = Cover Page & Notes
AHJ requires otherwise. They are to be mounted no more that 72 inches above the floor to
FA1.2 = Fire Alarm Initiation Layout
the top of the cabinet.
FA1.3 = Fire Alarm Notification Layout
7.Annunciator/Keypads are to be mounted at 54 inches above the floor to the top of the unit
FA1.4 = Riser Diagram & Battery Calculations
unless the AHJ requires otherwise.
8.Manual pull stations are to be mounted at 48 inches above the floor to the center of the box
unless the AHJ requires otherwise.
9.Wall mounted horns and strobes shall be mounted at 80 inches to the bottom of the box
Issue Date:
06.17.2020
above the finished floor.The candela rating is noted near the device on the drawings.
10.Ceiling mounted horns and strobes will be noted with a "C".The candela rating is noted near
REVISION INFORMATION
the device on the drawings.
Added Cell Communicator
11.The Darden electrical contractor is to supply all required 120VAC to the fire alarm control
panel and all power supplies on dedicated Circuit(s). The circuit(s) are to be locked and
label "fire alarm do not turn off".
12.The Darden electrical contractor is to supply all conduit stub ups, back boxes, power supply
inter connection conduit required and any under ground conduit and wiring to outside
devices. The under ground wire is to be THHW or equal.
13.The Darden sprinkler contractor is to supply, install and adjust all sprinkler system
supervisory switches.
is to Supply the Mechanical contractor with addressble duct smoke detectors, &
14.Tyco
sampling tubes. The mechanical contractor is to install the duct detectors, & sampling tubes.
is to wire the duct smokes for proper monitoring, & connect the control relay to the fan
Tyco
shutdown points provided by the mechanical contractor.
15.Upon fire alarm activation the music system must be automatically disabled by the fire alarm
Restaurant #:
5050
system. Tyco & music system contractor must coordinate and test shutdown feature.
16.Upon completion of the installation 2 sets of plans shall be marked up for as built. one set is
LONGHORN
to be left on site in a locked cabinet at the fire alarm control panel. The other set is to be
returned to Tyco.
17.Tyco shall provide a point of connection only to the existing duct detectors. Detectors were
501 N Congress Ave
installed by others at an earlier time.
Boynton Beach, FL 33426
Boynton Beach, FL
FIRE ALARM
COVER
PAGE
Tyco
FA1.1
BQQSPWFE
GJSF
dmjofl!1901603132
FIRE ALARM LEGEND
**NOT ALL DEVICES ON LEGEND APPEAR ON
DRAWINGS**
Johnson Controls
Symbol
Description
1830 Park Lane South
BQQSPWFE
Jupiter FL. 33458
FMFDUSJD
Fire Alarm Control
FACP
cbmvzpun!1901703132
Panel
Fire Alarm Annunciator
FSA
Alpha Keypad
Sole Path Cell
CELL
Communicator
Addressable Monitor
AIM
INSTALLING CONTRACTOR:
Module
Addressable Control
AOM
Module
P
Manual Pull Station
P
Smoke Detector
P
Photo Electric
Heat Detector R of R
R
135 deg or indicated
Duct Smoke Detector
Photo Electric
Remote indicator
Test/Reset
RTS
CONTACT INFORMATION:
KHS
Water Flow Switch
POC
Sprinkler Valve Tamper
Switch
Ceiling Horn Strobe
Candella Indicated
C
Ceiling Strobe Candella
C
Indicated
Wall Horn Strobe
Candella Indicated
Wall Strobe Candella
Indicated
Outdoor Horn Strobe
Candella Indicated
WP
LOW VOLTAGE WIRING LEGEND
**SEE GENERAL WIRING NOTES FOR EACH SYSTEM**
Description
Line Type
AWGCONDSHIELDCLASS
P
Security System
184NOCMP
Data loop / Device
Wiring
Fire Alarm System
18NOFPLP
4
Device Wiring
Fire Alarm System
186NOFPLP
Remote Test Switch
Wiring
Fire Alarm System
162NOFPLP
Data Loop Wiring
Fire Alarm System
2NOFPLP
14
Notification Device
Wiring
Security System
16NOCMP
4
Device Power Wiring
Issue Date:
xx.xx.xx
REVISION INFORMATION
P
Restaurant #:
xxxx
LONGHORN
P
501 N Congress Ave
Boynton Beach, FL 33426
Boynton Beach, FL
FIRE ALARM
INITIATION
LAYOUT
Tyco
FA1.2
BQQSPWFE
GJSF
dmjofl!1901603132
Johnson Controls
BQQSPWFE
1830 Park Lane South
FMFDUSJD
Jupiter FL. 33458
cbmvzpun!1901703132
FIRE ALARM LEGEND
**NOT ALL DEVICES ON LEGEND APPEAR ON
DRAWINGS**
SymbolDescription
Fire Alarm Control
FACP
Panel
Fire Alarm Annunciator
FSA
Alpha Keypad
INSTALLING CONTRACTOR:
Sole Path Cell
CELL
Communicator
Addressable Monitor
AIM
Module
Addressable Control
AOM
Module
Manual Pull Station
P
Smoke Detector
P
Photo Electric
Heat Detector R of R
15CD
R
135 deg or indicated
Duct Smoke Detector
Photo Electric
Remote indicator
C
Test/Reset
RTS
Water Flow Switch
Sprinkler Valve Tamper
Switch
CONTACT INFORMATION:
Ceiling Horn Strobe
Candella Indicated
C
Ceiling Strobe Candella
C
Indicated
Wall Horn Strobe
Candella Indicated
Wall Strobe Candella
Indicated
Outdoor Horn Strobe
Candella Indicated
WP
15CD15CD
LOW VOLTAGE WIRING LEGEND
**SEE GENERAL WIRING NOTES FOR EACH SYSTEM**
Description
Line Type
AWGCONDSHIELDCLASS
Security System
18NOCMP
4
Data loop / Device
Wiring
Fire Alarm System
184NOFPLP
Device Wiring
Fire Alarm System
186NOFPLP
Remote Test Switch
Wiring
Fire Alarm System
162NOFPLP
Data Loop Wiring
Fire Alarm System
2NOFPLP
14
Notification Device
Wiring
Security System
16NOCMP
4
Device Power Wiring
Issue Date:
xx.xx.xx
REVISION INFORMATION
Restaurant #:
xxxx
LONGHORN
501 N Congress Ave
Boynton Beach, FL 33426
Boynton Beach, FL
FIRE ALARM
NOTIFICATION
LAYOUT
Tyco
FA1.3
BQQSPWFEBQQSPWFE
GJSF
dmjofl!1901603132
BQQSPWFE
FMFDUSJD
Johnson Controls
cbmvzpun!1901703132
1830 Park Lane South
Jupiter FL. 33458
FPLP
INSTALLING CONTRACTOR:
FPLP
RJ-
CELL
PHONE LINE - 1
U.L. LISTED CENTRAL STATION
31X
UNIT
CONTACT INFORMATION:
JOHNSON CONTROLS
14200 EXPOSITION AVE.
RJ-
PHONE LINE - 2
AURORA, CO. 80012
31X
1-800-428-7124
DEDICATED 120 VAC
20 AMP CIRCUIT(LOCKED)
4" (0.1m)
CEILINGCEILINGCEILINGCEILING
4" (0.1m)
MINIMUM
MINIMUM
CONDUIT PENETRATION U.L. C-AJ-1045
IF TOTAL HEIGHT IS LESS THAN
ACCEPTABLE HERE
1 OR 2 HOUR RATED CONCRETE
IF TOTAL HEIGHT IS LESS THAN3M FIRE BARRIER
NEVER HERE
90", MOUNT 6" FROM CEILING
BLOCK WALL ASSEMBLY
96", MOUNT 6" FROM CEILINGCP 25WB+ CAULK
OR EQUAL
BACKBOX
BACKBOX
BACKBOX
12" (0.3m)
FIRE
INSTALL HORN AT NFPA
MAXIMUM
72 7.4.7.1 STANDARD
TOP OF DETECTOR
(ACCEPTABLE HERE)
PACKING
CONDUIT
MATERIAL
NOTES:
STROBE WITH BACKBOX
PULL STATION
NOT
HORN WITH BACKBOX
WITH BACKBOX
GREATER
1.CONDUIT SHALL BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY.
THAN 96"INSTALL MANUAL PULL
2.THE ANNULAR SPACE BETWEEN CONDUIT AND PERIPHERY OF OPENING SHALL BE 0 TO 1-3/8
NOT LESS
AFFSTATION 48" AFF TO THE
NOT LESS
INCHES.
SIDEWALL
THAN 80"
OPERABLE PART
THAN 90"
3.MAXIMUM OF (1) CONDUIT PER FIRESTOP SYSTEM.
AFF
AFF
4.PACKING MATERIAL - MINIMUM 4 INCH THICKNESS OF MINIMUM 8 PCF MINERAL WOOL BATT
INSULATION SHALL BE FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING
MATERIAL SHALL BE RECESSED FROM BOTH SURFACES OF WALL AS REQUIRED TO
Issue Date:
xx.xx.xx
ACCOMMODATE THE REQUIRED THICKNESS OF CAULK MATERIAL.
FINISHED FLOORFINISHED FLOORFINISHED FLOORFINISHED FLOOR
5.CAULK MATERIAL - MINIMUM 1/2 INCH THICKNESS OF FILL MATERIAL SHALL BE APPLIED
WITHIN THE ANNULUS, FLUSH WITH BOTH SURFACES OF THE WALL.
NOTES:NOTES:
NOTES:NOTES:
REVISION INFORMATION
H
FIRE RATED CONCRETE BLOCK WALL
1. IF THE CEILING HEIGHTS ALLOW, AND UNLESS OTHERWISE1. WALL MOUNTED APPLIANCES SHALL BE MOUNTED SUCH THAT1.THE OPERABLE PART OF EACH MANUAL FIRE ALARM BOX SHALL1.FOR CEILINGS WITH
BEAM DEPTHS OF LESS THAN 10% OF THE
PERMITTED BY (7.4.7.2.) THROUGH (7.4.7.5.) WALL-MOUNTEDTHE ENTIRE LENS IS NOT LESS THAN 80" AND NOT GREATER THANBE NOT LESS THAN 3'-6" AND NOT MORE THAN 4'-6" ABOVE FLOORCEILING HEIGHT(0.1
H), SMOOTH CEILING SPACING SHALL BE
Scale:NTS
APPLIANCES SHALL HAVE THEIR TOPS ABOVE THE FINISHED96" ABOVE FINISHED FLOOR OR AT THE MOUNTING HEIGHTLEVELPERMITTED.
FA
2.PER NFPA 72 (5.13.4)2.FOR CEILINGS WITH BEAM DEPTHS EQUAL TO OR GREATER THAN
FLOORS AT HEIGHTS OF NOT LESS THAN 90" AND BELOW THESPECIFIED USING THE PERFORMANCE-BASED ALTERNATIVE OF
NFPA 72 (7.5.4.5.).10% OF THE CEILING HEIGHT (0.1 H) AND BEAM SPACING EQUAL
FINISHED CEILINGS AT DISTANCES OF NOT LESS THAN 6".
TO OR GREATER THAN 40 % OF THE CEILING HEIGHT (0.4 H),
SPOT-TYPE DETECTORS SHALL BE LOCATED ON THE CEILING IN
EACH BEAM POCKET.
3.MEASUREMENTS SHOWN ARE TO THE CLOSEST EDGE OF THE
CONDUIT PENETRATION U.L. W-L-1001
DETECTOR.
1 OR 2 HOUR RATED GYP.
3M FIRE BARRIER
ABCD
WALLBOARD ASSEMBLY
HORN ONLY DETAILSTROBE OR STROBE/HORN DETAILPULL STATION MOUNTING DETAILDETECTOR MOUNTING DETAIL
CP 25WB+ CAULK
OR EQUAL
Scale:NTSScale:NTSScale:NTSScale:NTS
FAFAFAFA
FIRE ALARM PANEL
CONDUIT
NOTES:
1.CONDUIT SHALL BE INSTALLED AT CENTER OF STUD CAVITY WIDTH AND SHALL BE RIGIDLY
SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY.
2.CAULK FILL MATERIAL SHALL COMPLETELY FILL ANNULAR SPACE BETWEEN CONDUIT AND
CONDUIT
WALL; AND WITH A WIDTH OF 1/4 INCH DIAMETER BEAD OF CAULK APPLIED TO PERIMETER OF
CONDUIT AT ITS EGRESS OF THE WALL. FOR CONDUIT 1" DIAMETER AND SMALLER, ANNULAR
DMARC
SPACE SHALL BE 0 TO 3/16". FOR CONDUIT 4" DIAMETER AND SMALLER, ANNULAR SPACE
LINE
SHALL BE 0 TO 1-1/2".
3.MAXIMUM OF (1) CONDUIT PER FIRESTOP SYSTEM.
DISTRIBUTION PANEL
4.CONSULT CURRENT U.L. FIRE RESISTANCE DIRECTORY FOR DETAILS.
DEDICATED LOCKED
TELCO
CIRCUIT BREAKER
LINES
I
FIRE RATED GYPSUM WALLBOARD
LINE
TO PHONES
Scale:NTS
FA
FIRE ALARM WIRE
FIRE ALARM WIRE
PRIMARY LINE
CABLE PENETRATION U.L. W-L-3149
FIRE ALARM WIRE
OR
SECONDARY LINE
1 OR 2 HOUR RATED GYP.
3M FIRE BARRIER
WALLBOARD ASSEMBLY
Restaurant #:
FD-150+ CAULK
xxxx
CONDUIT
OR EQUAL
PRIMARY PORT
PRIMARY PORT
BURGLAR
FIRE ALARM PANEL
SECONDARY PORT
CABLE OR
PANEL
LONGHORN
CABLE BUNDLE
FIRE PANEL
NOTES:
CONDUIT
1.CABLES SHALL BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY.
NOTES:
NOTES:
2.THE ANNULAR SPACE BETWEEN CABLE/CABLE BUNDLE AND PERIPHERY OF OPENING SHALL
BE 0 TO 1 INCH.
FIRE ALARM DISCONNECT
1.CONDUIT SHALL BE USED FOR ALL EXPOSED FIRE ALARM CABLING INSTALLED
1.THE FIRE PANEL WILL NEVER SEE A LINE FAULT IF IT WIRED BEFORE
3.MAXIMUM OF A 1 INCH DIAMETER CABLE BUNDLE PER FIRESTOP SYSTEM.
BELOW JOISTS AND BEAMS.
THE BA PANEL
4.CAULK MATERIAL - MINIMUM 5/8 INCH THICKNESS OF FILL MATERIAL APPLIED WITHIN
TO DEDICATED LOCKED BRANCH
2.CONDUIT SHALL BE A MINIMUM. OF 3/4 INCHES
2.THE BA PANEL WILL NEVER SEE A LINE FAULT IF IT IS WIRED TO THE
ANNULUS, FLUSH WITH BOTH SURFACES OF THE WALL. MINIMUM 1/2 INCH DIAMETER BEAD
CIRCUIT 120VAC/20AMP SOURCE
FIRE SECONDARY LINE.
OF CAULK APPLIED AT THE CABLE/WALLBOARD INTERFACE AT POINT CONTACT LOCATION ON
3.BA PANEL WILL SEE LINE FAULT IF UNIMODE SEIZES SECONDARY LINE
501 N Congress Ave
BOTH SIDES OF WALL.
FOR MORE THAN ABOUT TWO MINUTES, WHICH IS OK.
5.CONSULT CURRENT U.L. FIRE RESISTANCE DIRECTORY FOR DETAILS.
Boynton Beach, FL 33426
EFGJ
PHONE CONNECTION DETAILPOWER DISCONNECTCEILING TO WALL TRANSITION AND FIRE ALARM OPEN WIRINGFIRE RATED GYPSUM WALLBOARD
Scale:NTSScale:NTSScale:NTSScale:NTS
FAFAFAFA
Boynton Beach, FL
FIRE RATED CABLE
OR CONDUIT
FIRE RATED CABLE
BREAK WIRE
OR CONDUIT
STROBEHORN/STROBE
DONT LOOP
EOL RESISTOR
EOL RESISTOR
AT LAST DEVICE
AT LAST DEVICE
PRECEDING STROBE
OR
FROM LAST
POWER SUPPLY
DEVICE
FIRE ALARM
SQUARE JUNCTION BOX
OCTAGON JUNCTION BOX
K
L
DEVICE WIRING
STROBE - HORN/STROBE WIRING
RISER
Scale:NTS
Scale:NTS
FA
FA
PAGE
N.1N.2
J-BOX DETAILS ON DROP CEILINGJ-BOX DETAILS ON DROP CEILING
Scale:NTSScale:NTS
FAFA
Tyco
FA1.4