PERMIT APPLICATIONBP200101
CITY OF BOYNTON BEACH
Application Inquiry
ii/i8/02
15:37:34
Application number ..... : 02 00001300
Application status, date : CERTIFICATE OF COMPLETION 11/14/02
Property .......... : 4735 NW 7TH CT
PCN ............. : 08-43-45-08-04-004-0010
Lot Number ......... :
Zoning ........... : PUD PLANNED ZONED DISTRICT
Application type ...... : RM RE-MODELING
Application date ...... : 4/10/02
Tenant nbr, name ...... : CAFETERIA BLDG. RENOVATE
Master plan nbr, revwd by : JP
Estimated valuation .... : 1500000
Total square footage .... : 0
Public building ...... : NO
Work description, qty . . . :
Pin number ......... : 4398
Press Enter to continue.
F3=Exit F5=Land inq
F10=Fees F11=Receipts
F7=Appl names
F12=Cancel
F8=Tracking inq
F13=Val calcs
F9=Bond inquiry
F24=More keys
C)
DEPARTMENT OF DEVELOPMENT
BUILDING DIVISION
BUILDING PERM~ APPLICA TION~- -
02-1300
Original Permit # =2.-/
Project Name: /VE~A~7-
Project Address: ,/735 ~v.~. ~ ~,~/
Contractor's Name:
Date:
Master Permit #
Value of Work: $
Total Estimated Value of this Revision $
Description of Work: (Please specify in detail what is being revised from o#ginal permit.)
Electrical: /'~z~.~--~'Z~¢,¢~/_
Fire Sprinkler:
Value of Work: $
Value of Work: $
Irrigation:
Value of Work: $
Value of Work:
Value of Work: $
Roofing:
Value of Work: $
Sign:
r=I E. tVED Value of Work: $
JUN
Site Lighting: ~//~ _?..Fl~c~i;~,.
Clearing & Grubbing: W//~
Value of Work: $
Value of Work: $
Paving/Drainage:
Value of Work: $
Fill/Excavation:
Value of Work: $
Landscaping:
Value of Work: $
t wish to revise the above referenced permit to pedorm the work described herein. I certify that all work will be constructed in conformance with all
laws, cedes, regulations, rules, etc. governing Boynton Beach, and I certify that the above information is true and correct.
STATE OF FLORIDA, COUNTY OF PALM BEACH'~ ~'\ /
As identification and'~fio did
/ho is
es prnd~ced ~,~ M~Com mission Con~ _'~. /7~
take an oath ~ /
. ._ '- °%~,.,~,.,' Expires December08.2003 / ~ (~ /
~AnaLt)ure of person taking acknowledgement
Name of officer taking acknowledgement ty, p~l, p'M~ted or sta~np~
T ,e a.k ..--'"-?.-'p/'/ Number,
~.,~e~nit Officer ~ c___------
ISSUANCE OF THIS PERMIT DOES NOT AUTHORIZE VIOLATION OF DEED RESTRICTIONS
FEES ARE NOT REFUNDABLE
Odginal Permit #
PCN
(For Office Use Only)
Application Accepted By:
Master Permit #
(Palm Beach County Property Control #)
Type of Construction
Occupancy Type
Fence Type
Roof Type
Flood Zone
Base Flood Elevation
Finish Floor Elev. (Proposed)
Number of Units
Parking Spaces Required
Parking Spaces Provided
Area Square Feat (Gross)
Area Square Feat (Net)
Number of Stodes
Number of Bedrooms
Remarks:
Compl~ed by Date r~cmcls
Completed by.
Parks
Forester Dev Depl
Date records
Date entered into Pe~nit Log Initials
Date called for comments Initials
ADDITIONAL FEE(S)
BCAIF
Parks Fea
Penalty Fee
Public Building Fee
Radon Fea
Road Impact Fea
Schod Fea
Sewer Fea
Water Fea
Fire Deparlment Fee
Overtime Fee
Sub-Total
Clearing & Grubbing v ~ ,~_.-
Drainage
Electrical
Excavation
Fill
Fire Sprinkler
Irrigation
Landscaping
Mechanical
Paving
Plumbing
Roofing
Sign
Site Lighting
TOTAL AMOUNT DUE
Date Permit Issued
Review F H
Date to P&Z records
Date records
Forester Dev. Dept
Date entered into Permit Log
Date called for comments
Initials
Initials
DEPARTMENT OF DEVELOPMENT
BUILDING DIVISION
BUILDING PERMIT APPLICATION
PCN#
Master Permit #
08-43-45-08-04-004-0000
Senior Lifestyle Newport, L.P.
111 E Wacker Drive. Suite 2450
Fee Simple Title Holder's Name
Fee Simple Title Holder's Address
City/State/Zip
IL
Permit #
' 2-1 00
(Palm Beach County Property Control
;Zip'Code? 60601
(If other than owner's)
(If other than owner's)
City/State/Zip
Orlando, ~g 32824
Inc c°mPany Ph°ne# 407-g57-3510
40/468-2194
Pager/Fax~ 407-857-8094
Newport Fiace Main
4735 North West Seventh Court
Boynton ~ach, FL 3342b
Zoned
Bonding Company
Bonding Company Address
City/State/Zip
Architect/Engineer's Name
Architect/Engineer's Address
City/State/Zip
Mortgage Lender's Name
Mortgage Lender's Address
City/State/Zip
(Check one below)
Single Family
Duplex Multi-Family
/V/A
Hotel Retail Office Industrial
& replacement of existing RTU'S & Associated ductwork
(Check Reviewer Required below)
Electrical Mechanical X Plumbing Structural Fire Other
Application is hereby required to obtain a permit to do work and installations as indicated. I certify that no work or installation has commenced prior
to the issuance of a permit and that all work will be performed to meet the standards of all codes, laws, rules and regulations governing
construction in this jurisdiction. I understand that a separate permit must be secured for. ELECTRICAL, PLUMBING, SIGNS, WELLS, POOLS,
FURNACES, BOILERS, HEATERS, TANKS and AIR CONDITIONING WORK, ETC.
ENCEMENT MAY RESULT IN
OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all
applicable codes, laws, rules and regulations governing construction and zoning.
Property Owner's or Agent's Signature
STATE OF FLORIDA, COUNTY OF PALM BEACH
The foregoing instrument was
acknowledged before me this
Who is personally known to me or who
has produced
(SEAL)
Signature of person taking acknowledgement
~ //~ (date) by ~ /,,~
/,,r.. /
As identification and who did (did not) take an oath.
Serial Number, if any N / ~
Name of officer taking acknowledgement typed, printed or
Title or rank ... j j
Contractor's Signature Date
STATE OF FLORIDA, COUNTY OF PALM ~EACH
The foregoing instrument was
a~nowledged before me this 2~ ~z cE ~y 2002 (date) by ~d ~. ~o~e
Who is personally known to me or who
has pr~SiNm N F~ pers~azzy ~ As identification and who did (did not) take an oath.
Signa'~persont~ga~wledgemont ~ ''~~ > _ ,
Name of officer~king ackno~edgement typed,~inted or stamped
Tiaa or rank ~es~d~E Serial Number, if any
(Cedifi~te of Competency Holder)
Contractor's State Ce~ification of Registration No. ~O
Liabili~lnsurance Expiration Date 2/[/03 ~~ Workers' Compensation~~Expiration Date 2/[/03
Application Approved by ~--- (Permit Officer) Date
~y ~aage in buitding ~s ff s~dfica{ions ~st be re~rd~ ~ ~is office, Any ~rk not covered above ~sl have a mild ~r~l pri~ lo sluing. In c~sideration o~ grants ~is pe~t. Ihe
~ner and building agree Io erst this structure in full co~liance with lhe Building and Zoning Codes of the City of Boynton Beach.
N~TE: This ~rmit VOID a~er 180 DAYS UNLESS the work which it covers has commen~d. All Contractors must have valid State CeAifi~tion or County Competency
plus County and City ~cupational Li~nses prior to obtaining permit.
ISSUANCE OF THIS PERMIT DOES NOT AUTHORIZE VIOLATION OF DEED RESTRICTIONS
FEES ARE NOT REFUNDABLE
S:\DEVELOPMENT~FORMS&TEMPLATES\BUILDING PERMIT APPLICATION-Icl. Rev 6/18/97, 11/4/97, 12/98, 6/99, 8/99, 5/00, 8/00, 9/00, 10/01
Application Accepted By:
Application #
Type of Construction
Occupancy Type
Fence Type
Roof Type
Flood Zone
Base Flood Elevation
Finish Floor Elev. (Proposed)
Number of Units
Parking Spaces Required
Parking Spaces Provided
Area Square Feet (Gross)
Area Square Feet (Net)
Number of Stories
Number of Bedrooms
Remarks:
IF THIS BOX IS NOT COMPLETED, THIS PERMIT IS
SUBJECT TO A FINAL INSPECTION ONLY.
AUTHORIZED for CERTIFICATE OF OCCUPANCY:
Date
AUTHORIZED for CERTIFICATE OF COMPLETION:
Date
ADDITIONAL FEE(S)
BCAIF
Parks Fee
Penalty Fee
Public Building Fee
Radon Fee
Road Impact Fee
School Fee
Sewer Fee
Water Fee
Fire Depadment Fee
Overtime Fee
Sub-Total
SINGLE FEE
Building
__ Clearing & Grubbing
Drainage
Electrical
Excavation
Fill
__ Fire Sprinkler
Irrigation
Landscaping
Mechanical
__ Paving
Plumbing
Roofing
Sign
Site Lighting
Sub-Total
TOTAL
Less Plan Filing Fee
Receipt Number
Check/Credit Card Number
Cash
Received from:
Accepted by: (Initials)
BALANCE DUE
Receipt Number
Check/Credit Card Number
Cash
Received from:
Accepted by: (Initials)
VALUE FEE
S:\DEVELOPMENT~FORMS&TEMPLATES\BUILDING PERMIT APPLICATION-Igl. Rev 6/18/97, 11/4/97, 12/98, 6/99, 8/99, 5/00, 8/00, 9/00, 10/01
DEPARTMENT OF DEVELOPMENT
BUILDING DIVISION 0 2 - :l 3 0 0
BUILDING PERMIT APPLICATION
City/State/Zip
Job Name
Job Address
City/State/Zip
Legal Description
Bonding Company
Please print. All lines MUST be completed. If not applicable, write N/A.
Date: ~' , ~l/ ("~-- Master Permit # ~ ~C~L%~.)(.~ (~C'~O Permit#
PCN~
Owner's Addrees ~'"~ '2--'7 ~/~,'~ ~ ~/,~,,~J
Fee Simple Title Holder's Name /
Fee Simple Title Holder's Address
City/State/Zip
Contact pemon & emergency phone # d*~/~ ,~//~--o ~
Company Address /(.~,.0-:7,4., ,"~//c/1. ~-c:./,,e ,/~2,~4..470 /~(~:~/
!
Bonding Company Address
C~ylStateFZip
Amhitect/Enginee~s Name
ArchitectJEngineer's Address
City/state/Zip
Mortgage Lender's Name
Mortgage Lender's Address
City/State/Zip
(Check one below)
Single Family Duplex
Eslimated Value of Construction $
Detailed D_,~c___-ription of Work
(Palm Beach County Property Control #)
Owner's Phone#
~code bo~
(If other than o~vner's)
(If other than owner's)
Zoned
Multi-Family Hotel Retail
Office ~ Industrial
(Check Reviewer Requked below)
Electrical Mechanical ~ Plumbing Structural ~ Fire Other
Application is hereby required to obtain a permit to do work and installations as indicated. I certify that no work or installation has commenced prior
to the issuance of a pmmit and that all work will be performed to meet the standards ~ all codes, laws, rules and regulations governing
construction in this jurisdiction. I understand that a separate permit must be securecl for ELECTRICAL, PLUMBING, SIGNS, WELLS, POOLS,
FURNACES, BOILERS, HEATERS, TANKS and AIR CONDITIONING WORK, ETC.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR PAYING
TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR
LENDER OR AN A'rrORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT.
OWNER'S AFFIDAVIT: I certify ~at all the foregoing information is accurate and that all work will be done in compliance with all
applicable codes, laws, rules and regulations governing construction and zoning.
Property Owner's or Agent's Signature Date
STATE OF FLORIDA, COUNTY OF PALM BEACH
The foregoing instrument was
acknowledged before me this (date) by
Who is personally known to me or who
has produced As identification and who did (did not) take an oath.
(SEAL)
Signature of person taking acknowledgement
Name of officar taking acknowledgement typed, ~rinted or stamped
Title or rank
:(date) by
STATE OF FLORIDA, COUNTY OF
The foregoing instrument was
acknowledged before me this ~
Who is personally known to me or ~
has produced
(SEAL)
Signature of person taking acknowledgement
Serial Number, if any
As ideotif'v-..ation and who did (did not) take an oath.
Name of officer taking acknowledgement typed, pdnted or stamped
Title or rank Serial Number, if any
(Certifm. ate of Competency Holder)
Co~tractor's State Certification of Registration No. ~ F - CO --z. I c/-7 ~j
Liability lnsurance Expiration Date _t~/. (.~/ , ~ Workers' Compensation Expiration Date /~)/, (~)1 o
Application Approved by (Perm/t Of~ed Date
Any change in building pla~s or specil'icaPOns must be recorded with ttis o~fice. Any work not covered al3ove must have a valid permit Ixx)r to staling. In oonaldemtk3n al t~-~;~ ti'is permit, the
owne~ and building agree to erect this structure in full c,~mppance with the Building and Zoning Codes of tfm City of Boynton Beach.
NOTE: This permit VOID after 180 DAYS UNLESS the wofl< which it covers has commenced. All Contractors must have valid State Certificatio~ or County Competency
plus County and City Occupational Licenses prior to obtaining permit.
ISSUANCE OF THIS PERMIT DOES NOT AUTHORIZE VIOLATION OF DEED RESTRICTIONS
FEE8 ARE NOT REFUNDABLE
F[]] Hr-
(For Office Use Only)
Application Accepted By:
Application #
Type of Construction
Occupancy Type
Fence Type
Roof Type
Flood Zone
Base Flood Elevation
Finish Floor Elev. (Proposed)
Number of Units
Parking Spaces Required
Parking Spaces Provided
Area Square Feet (Gross)
Area Square Feet (Net)
Number of Stodes
Number of Bedrooms
Remarks:
IF THIS BOX IS NOT COMPLETED, THIS PERMIT IS
SUBJECT TO A FINAL INSPECTION ONLY.
AUTHORIZED for CERTIFICATE OF OCCUPANCY:
Date
AUTHORIZED for CERTIFICATE OF COMPLETION:
Date
ADDITIONAL FEE(S)
BCAIF
Parks Fee
Penalty Fee
Public Building Fee
Radon Fee
Road Impact Fee
School Fee
Sewer Fee
Water Fee
Fire Depa, i~.ent Fee
Overtime Fee
Sub-Total
SINGLE FEE
Building
Cleadng & Grubbing
__ Drainage
Electrical
Excavation
Fill
Fire Sprinkler
Irrigation
Mechanical
Paving
__ Plumbing
__ Roofing
Sign
__ Site Lighting
Sub-Total
TOTAL
Less Plan Filing Fee
Receipt Number
CheckJCredit Card Number
Cash
Received from:
Accepted by: (Initials)
BALANCE DUE
Receipt Number
Check/Credit Card Number
Cash
Received from:
VALUE
FEE
Accepted by: (Initials)
DEPARTMENT OF DEVELOPMENT
BUILDING DIVISION
BUILDING PERMIT APPLICATION
Date:
PCN#
Master Permit #
Fee Simple Title Holder's Name
Fee Simple Title Holder's Address
City/State/Zip
Company Address
City/State/Zip
state
Bonding Compan
permit#
(Palm Beach County Property Control #)
(If other than owner's)
(if other than owner's)
~Company phone #
Pager/Fax#
Zoned
Bonding Company
City/State/Zip
ArchitectJEng
Architect/Engi
City/State/Zip
Mortgage Lender's
Mortgag
City/State/Zip
(Check one below)
Single Family Duplex .Multi-Family_'/b' Hotel Retail Office Industrial
/...~- x~,/Z~,~/'
(Check Reviewer Required below) '
Electrical X Mechanical . ~. Plumbing ~ Structural ~Z Fire ,/~ Other ~-/- ~
Application is hereby required to obtain a permit to do work and installations as indicated. I certify that no work or installation has commenced prior
to the issuance of a permit and that all work will be performed to meet the standards of all codes, laws, rules and regulations governing
construction in this jurisdiction. I understand that a separate permit must be secured for.. ELECTRICAL, PLUMBING, SIGNS, WELLS, POOLS,
FURNACES, BOILERS, HEATERS, TANKS and AIR CONDITIONING WORK, ETC.
;OMMENCEMI
OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all
applicable codes, laws, rules and regulations governing ,¢~nstruction_~,-~d/[oning.
Property Owner's.or Agent's Si~lnature ~ ~,_j~ ~~~ Date '~ / ! ~3/~._.-
· The foregoing instrument was
acknowledged before me this ~ 113 2-_ (d 0 ~C~.~t I~) ~r~
Who is persoqa~own t'~ me or who
Signature of person taking acknowledgement
Name of officer taking acknowledgement typed, printed or stamped _ _ _
Title or rank Serial Number, if ~ - - -
Contractor's Signature~~ ~.~.,~ Date
The foregoing instrument was
acknowledged before me this ~ ~ (d~y ~~ ~ ~ ~O~l~
Who is personally known to me or who - ~ ...... , ~
~ ........... _~'~'~ 3Z~- [%- V-/' ~>Z-- 0 As identifi~fion and who did (did not) ~ke an oath.
Name q ~ ~~~rinted or *~mped'
Title or ~' ~--- Serial Number, if any
(Cedifl~te of Competency Holder)
Contractor's State Ce~ification of Registration No.
Uabi, ,surance E pira t o ke s' Co p ,sation xp tio,
Appli~tion Approv~~'~~ (Permit Officer)
Any change in building plan fi~tions ~rded ~th ~is ~ce. Any wo~ not covered above ~t have a valid ~r~t ~ to sta~n9. In c~sid~ati~ of grants this ~L the
o~er and building agree to ~d this s~dure in ~ c~ian~ ~th the Building and Zo~ng C~ of the City of B~nton Beach,
NOTE: This permit VOiD after 180 DAYS UNLESS the wo~ ~ich it covers has ~mmen~d. Ali Contractors must have valid State Ce~ifi~tion or County Competency
31us County and Ci[y O~upational Licenses prior to obtaining permit.
ISSUANCE OF THIS PERMIT DOES NOT AUTHORIZE VIOLATION OF DEED RESTRICTIONS
FEES ARE NOT REFUNDABLE
Date
MEN'I~FORMS&TEMPLATES\BUILDiNG PERMIT APPLICATION-Igl. Rev 6/18/97, 1114/97, 12/98, 6/99, 8/99, 5/00, 8/00, 9/00, 10/01
F[--I HI--]
Application Accepted By: Application #
Type of Construction
Occupancy Type
Fence Type
Roof Type
Flood Zone
Base Flood Elevation
Finish Floor Elev. (Proposed)
Number of Units
Parking Spaces Required
Parking Spaces Provided
Area Square Feet (Gross)
Area Square Feet (Net).
Number of Stories
Number of Bedrooms
Remarks:
IF THIS BOX IS NOT COMPLETED, THIS PERMIT IS
SUBJECT TO A FINAL INSPECTION ONLY.
AUTHORIZED for CERTIFICATE OF OCCUPANCY:
Date
ADDITIONAL FEE(S)
BCAIF
Parks Fee
Penalty Fee
Public Building Fee
Radon Fee
Road Impact,Fee
School Fee
Sewer Fee
Waker Fee
Fire Department Fee
Overtime Fee
Sub-Total
SINGLE FEE
Building
Clearing & Grubbing
Drainage
Electrical
Excavation
Fill
Fire Sprinkler
Irrigation
Landscaping
Mechanical
Paving
Plumbing
Roofing
Sign
Site Lighting
Sub-Total
TOTAL
VALUE
Less Plan Filing Fee
Receipt Nam ber ~-(.~ ( (,~.~C~,~
FEE
0
Check/Credit Card Number
Cash
Received from:
Accepted by: (Initials)
BALANCE DUE
Receipt Number
Check/Credit Card Number
Cash
Received from:
Accepted by: (Initials)
S:\DEVELOPMEN~FORMS&TEMPLATES\BUILDING PERMIT APPLICATION-Igl. Rev 6/16/97, 11/4/97, 12/98, 6/99, 6/99, 5/00, 8/00, 9/00, 10/01
Page 1~ Master Permit # ~_~_,___(~.00 Perm,# _ 0
DEPARTMENT OF DEVELOPMENT
BUILDING DIVISION
BUILDING PERMIT APPLICATION
Please print. All lines MUST be completed. If not applicable, write NIA.
Date: ~"
Permit #
Master Permit
PCN#
Owner's Name ~.mFE51".tL.E ,/~IE~Po~..~' ~'T',.~
Owner's/~ddress ~'~2.-7' // ~l~rz,5~N ,~
City (~'N Id,4(.,o ' State
Fee Simple Title Holder's Name
Fee Simple Title Holder's Address
(Palm Beach County Property Control #)
Owner's Phone #
Zip Code ¢~<~)
(If other than owner's)
(If other than owner's)
City/State/Zip
Contractor's Company ~T~-.,~--~/~¢41~'£.,¢ D~-/VT Company Phone
Contact person & emergency phone #
Company Address
City/State/Zip ~/~ ~ l.
Job Name -. / ,
Job Address ~/~ /¢/,~) 7t%-/~ ~_.;'~
City/State/Zip
Legal Description
Pager/Fax#
Zoned
Bonding Company
Bonding Company Address
City/State/Zip
Architect/Engineer's Name
Architect/Engineer's Address
City/State/Zip
Mortgage Lender's Name
Mortgage Lender's Address
City/State/Zip
(Check one below)
Single Family Duplex Multi-Family
Estimated Value of Construction.~ /
Detailed Descr, iPtion of Work
/
(Check Rev. i~er Required below)
Electrical v Mechanical Plumbing
Hotel Retail Office Industrial
Structural Fire Other
Application is hereby required to obtain a permit to do work and installations as indicated. I certify that no work or installation has
commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all codes, laws, rules and
regulations governing construction in this jurisdiction. I understand that a separate permit must be secured for ELECTRICAL,
PLUMBING, SIGNS, WELLS, POOLS, FURNACES, BOILERS, HEATERS, TANKS and AIR CONDITIONING WORK, ETC.
OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done
in compliance with all applicable codes, laws, rules and regulations governing construction and zoning.
S:\DEVELOPMENT\FORMS&TEMPLATES\BUILDING PERMIT APPLICATION- Revised 6/18/97, 1114197, 12~98, 6/99, 8/99, 5/00, 8/00, 9/00, 10/01
Master Permit # 02-/~00 Permit
Page 2 of 2
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT
IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN
FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR
NOTICE OF COMMENCEMENT.
Property Owner's or Agent's Signature
Date
STATE OF FLORIDA, COUNTY OF PALM BEACH
The foregoing instrument was
acknowledged before me this
Who is personally known to me
or who has produced
take an oath.
(date) by
As identification and who did (did not)
(SEAL)
Signature of person taking acknowledgement
Name of officer taking acknowledgement typed, printed or stamped
Title or rank Serial Number, if any
STATE OF FLORpdA, tbOUNTY OF PALM BEACH
The foregoing instrument was '"~.., [ ~'~'"~/~ ~"~
acknowledged before me this ~_~)~. ~ ~, ~,
Who is personally known to me
or who has produced ~' As identification and who did (did not)
take an oath.
(SEAL)
Signature of person taking acknowledgement ~_,
Name of officerJ~king acknowledgement typed, pri~ or stamped -
Title or rank",)~ ~ Serial Number, if any
(Certificate of Competency Holder) ,, ........
Contractor's State Certification of Registration No.
Liability Insurance Expiration Date
Grace S. ¢ompisl
MY COMMISSION # CC816406 EXPlRE~
3uly 10, 2005
I~OND~D THRU ~OY FAiN INS UI~ANC~ INC
Workers' Compensation Expiration Date
Application Approved by Date
Permit Officer
Any change in building plans or specifications must be recorded with this office. Any work not covered above must
have a valid permit prior to starting. In consideration of grants this permit, the owner and building agree to erect this
structure in full compliance with the Building and Zoning Codes of the City of Boynton Beach.
NOTE: This permit VOID after 180 DAYS UNLESS the work which it covers has commenced. All Contractors must
have valid State Certification or County Competency plus County and City Occupational Licenses prior to obtaining
permit.
ISSUANCE OF THIS PERMIT DOES NOT AUTHORIZE VIOLATION OF DEED RESTRICTIONS
FEES ARE NOT REFUNDABLE
S:\DEVELOPMENTtFORMS&TEMPLATES\BUILDING PERMIT APPLICATION- Revised 6118197, 11/4/97, 12198, 6199, 8~99, 5/00, 8/00, 9/00, 10/01
05/0~/0~ 17:47 FAX 850 6585579 KIB~O$
M I A M I'OADE
FRuuut. I c. urn i ~ob NOTICE OF ACCEPTA[~CE
Kawneer Company, Inc.
555 Guthridge Court
Norc~s ,GA 30092
OUIL, OIpIG CODE COMPLI^IVCI: OFFICE.
MhqT(O-D^DI: I:L^GI.I~R LIUILDL'cG
I {0 WEST FLAGLER STREi,.'r. SUITE 16o3
MiAMi. Fi.GRiD^ il i }~ i.%3
CON'J'IL4,(.'FOII I.IC'EIVSING S£C'I'ION
(~]05) 375-2S27
CONTIL&(YI'OR I~NFOltCERlt:,ngr DIVISION
(305) 375.29(,6 FAX {305) ]75-2~S
t'IiOI}UCT CO,'gfROL OIVL,;IOS'
005) 375-2902 FAX (30~) 372-6~)e
You r application for Noclc~ of Acce0canc¢. (NOA)' of: ..
Seri~ IR 500 Aluminum Glazed (w/Virdeon ${ormGuard) Winsdow wall system-Impact
under Chapter g'o[the Pode of' Minmi-D'ade'County gnvemin~ the use o£Altemate Materials and Types of
This NOA shall not be valid after the expiration date stated below. BCCO reserves fl~c right to secure this
product or materiai at any time from a jobsite or manu£acmrcr's plant for quality control ic=ii,g. I~ ~
product or material fails to perform in the approved manner, ~g~o may revoke, modify, or suspend &c
use o£ such product or material immediately. BCCO reserves the nglmt to revoke this approval, if it is
determined by BCCO that this product or material fails to meet the requirements of the Soutt~ Florida
Building Code.
THIS IS THE COVERSHEET~ SEE ADDITIONAL PAGES FOR SPECIFIC AND GENERAL
t-'t-~l~rt TTIt'IIM~
This application for Product Approval has been reviewed by thc BCCO and approved by thc Building
Code ~d Produ~! ~_e~[ew Con~mi,~. tn he u~e~ in M~nmi-D~e County, Florida under the condidons set
[17_.
Francisco 1. Qu;ntana, R.~.
05/02/02 17:47 F.AX 850 6685679 KINKOS ~003
Kanweer Company Inc.
ACCEPTANCE No.:
02-1300
00-1il4.07
APPROVED
: Aorii 12~ 2001
EXPIRES
:.April2, 2006
NOT.ICE OF ACCEPTANC_ E:. SPECIFIC CONDITIONS
SCOPE
This approves an aluminum window wall system, as described in Sec:ion 2 of' this Notice of
Acceptance, designed to comply with the South Florida Building Code (SFBC), 1994 Edition for
Miami-Dad¢ County: for the locations where the pressure requirements, as determined by SFBC
Chnpter ~_3. da nat exceed the Design Pressure Rating values indicated in the approved drawings.
PRODUCT DESCRIPTION
following d~mcms: D~ng No. T57~$0i, ti~i~ "Kawneer iR 5~ - imp~" Shes i through 7
of-/, d~ OSiZS/~ ~d last revised on 0i-i~0i, prepar~ by manufacturer, bca~ng ~he biiami-
Dade County Product Control appro~ stamp wire the Notice of Acc~tan~ numO~ and approval
date by the Miami-Dade County Produ~ Control Division. These documents shall h~ema~er be
referred to as the approved dra~ngs.
LIMITATIONS
This approval applies to multiple unit applications of an aluminum window wall system, limited
4. INSTALLATION
4.1 i ne aiuminum window waii system anci its componems shaii be installed in strict " ....... ""
~11t [J I liil 1~,~.
the approved drawings. .-'.
4.2 Humcanc protection system (,shutters): the instailatlon of this unit will not requLr.e, a hurricane
protection sy-.tem.
5. LABELING
5. I Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and
BUILDING PERMIT REQUIREMENTS
6.1.1 Thi~ Nuti~
Accepta~e, cieariy marked to s~w the core.neats selected for thc pro~s~ ink. Ii.ilo..
6.1.3 Any otn~ documcn~ r~uir~ by thc ~uiiaing Ot~ciai or the Souti~ Florida ~uiiding Code
(5FBC) in order ~o ~opedy ~aluate thc installation of th~s ~stem.
'; I~ ~ ishaa I.'Chanaa. P.E. Pm~uc, Control Examiner
~' '" ' P?od~ct Control Division
05/02/02 17~¢~ F~685679
~os ~oo4
~, anweer Company Inc.
e
ACCEPTANCE No.:
02-130
00-I 114.07
APPROVED
: Anrill2.2001
EXPIRES
: Apcil 121 2006
NOTIC~OF ACCEPTA~, CE; .STANDARD CONDITIONS
Renewal ofthis Acceptance (approval) shall be considered after a renewal application has been filed
and thc original submitted documentation, including test supporting data, engineering documents, arc
no older than eight (8) years.
Any and all approved products shall be permanently labeled with the manufacturer's name, city, state,
and the following statement: "M~ami-Dade County Product Control Approved", or as specifically
stated in the specific conditions of this Acceptance.
Renewals of Acceptance will not be considered if~
a) There has been a change in thc South Florida Building Code affecting the evaluation of this
product and the product is not in compliance with the code changes;
b) The product is no longer the same produ~ (10critical) a_s the nne originally approved;
-~ ........... V ........................... $-
automatically be cause for icrminatlon o£thi$ Acccp[ancc, unless prior written approval ha~ bccn
requested (through ~he 5ling ora revision appiicadon with appropriate fee) aM grante~ by this office.
Any of the following shall also be grounds for removal of this Acceptance:
a) Unsatisfactory performance of'this product or process.
b) Misuse of this Acceptance as an endorsement of'any product, for sales, advectising or ari~ other
purpose.
Thc Notice of Acceptance number preceded by the words Miami-Dadc County, Florida, and followed
by thc expiration.date may be displayed in advertising literature. It' any portion of the Notice of
Acceotance is displayed, then it shall bc done in its entirety.
7. A copy of this Acceptance as well as approved drawings and other documents, where it applies, shall
be provided to the user by the manufacturer or its distributors a,xd shall be available for inspectionat'
thc job site at all time. Thc engineer need nm re.~eal the cnpie~
8, Failure to comply with any section of this Acceptance shall be cause for termination and removaI Of
This Notice of Acceptance consists of pages 1, :2 and this last page 3.
.06/02/02
17:48 FAX 850 66856?9 KIl~0$
~oo$
02"1300
ATL Report # II0~.01-99 DC Note # ATL 99016., _
Pa~e I of 9
DaIe:
ATL C~d~c~on # 9g=0213.05
Test Dates:
11/3, 11/4~ 11/lS/99,
111"} 111"'~ 911~!0.13
Test Requested By- Iame~ Evans, Kawneer Coml~may. In~., 555 ~e C6u~
Geeq~a 3OO92. :l'honc (??0) 449-~5s5, ~'ax (~-/o)
Confguration - Tttvee pa~d~ wide with 4 fixed litcs.
,, 05/02/'02 17:49 FAX 850 66856"/9
I ,,..~ - :. ,,'. . . · -:
:.;:~'-.: ., :..:' .-.,..: ... ..... _. . .:.,, .... ,,..,. . . .
KINKO$ ~ 006
ATI~F # 1103.01-99
Page 2 0£9
thicknesiY Thejambs'consisted of a solid section (part # $75-001) f2.500' x 5" x 0.090" _typk~l*wall
!hlaknp..~S)_ _On_ ~m2~...i.m_ ens ~ snd ~ the head consisted of a sohd se~ticm (.Dart # 575-012) (2.$00' x
s~me stops. T~ tiffin h~ad, center and right siii consisr~ of a tub~ar section (part. ii 575-003) (2.500"
4.952" x 0.090" typical wall thickness) with same stops. 'f~e interm~iat¢ horizontal murfion consisted ora
double tubular section (part # 575-011) (2.500" x 4.952" x 0.090" typical wall thiclmess) wath the same
~;0_6i'as b~ed at the head and sill_ On' specimens'B;'D and'F the intermediate horizontal mullion~ras ....
located on th6 left fixed lite and on spechnen H was located on the right fixixt Utc. Au ~arudcd aluminum
~L" flashing (part # 575-03T) (2~594" x 5.250" x 0,080" typical wall thickness) ran coatilmous under the
_~;1_!,I ,nd ..v~_s o!os.e~l, off at e~eh ~nd of th~ frame with an aluminum extruded enct dam (part ii 575-114)
{6.434'> x 0.S5'~; x 0.250;' typicai waii thickn~s x 4'-: in length at the jambs ami_h¢~i_' ex_ .c~n, _X~o~,~e. on~$ on
~h ski= of the imermedi~te vertacai muiiions which are s~; in length) to fasten ncaa ann la~, ~e test
buck. (7) atrap anchors pcrjamb, locat~xl (1) at 6" fi'om head then (6) at 14-5/8" oc. (_12k~ct~s, at
thc head, located (1) at 6" from jamb, (2)- at 16-7/16" oc, 18-7/16", 10..3/4", 17-9/16",~,k~/l~g'i
10-1/2".. 18-7/16", (2~ at 16-7/16" oc. Spec/mens "'B" aaa "D' use a strap aachor (~N'~'/~I~6) (6.434"
x o_SST' x 0.250" t~."cal wall thickness'X 4" in length) to fasten the iambs to the wobd t~uc~ted
Giszing B'Iate~ - 9/16" Storm~m laminated glass by Viracon: 1/4" HS out'board lite / 0.1
Sailex~ HP int~n4ayer (by Sohnia) / 1/4" HS inboard lite.
Gtazine Method - Extmior flush glaz~l with an EPDM (push-in _type) gasket (pai~ #'27~ on thc
e~nr perimeter rrfthe infill and a 1/4" deen x 1/2" high bead of Dow Corning_ 983 Or 995 siliCOne with
elida_in ~t,.,-~r £nsr~ ii 19'/_$11 9~ £1 la" x~d~ x ~/1 g" de~n~ an the int0~rlnr perimeter of the infill The .typical
DavUvht Ouenin~ -
center panel:
LeR panel'. Top
Bottom lite
wide x 94~3/4" high).
MGe X 5u~..514" mgn).
'wide x 4b-l/S:; high').
wide x 46-I/8" high) .
· 05/02/02 17:49 FAX 650 6685679 EINKO$
..:. ,~-.-~ -, - . ';~r. 4' ~. ':'?-.,-), ...~,'- . .
* ' A~ ~ 1103,01-99
~1007
0 ,"1300
Page 3 of 9
Westher-striDDiul - Hone
Hardware: 'None
Weepholes, r None
lrduiitifii" ' N/A ........................
R. ein~. orc.ement-' Stc~l l=inforcem{~ (part # 575-110) (4.282" x I.OOty' x 0.13s" typical wall thiclmc,$),
,,-nv,, .n,,',el'm'~n','~e '~ ~.,,'~nh ;,r,+~,~.~,,,~l.~,+~,,,a,,r+h'..~l rn'nllln'n~ ~tt~nh~l 'tu'~'h ii 19. ~ %IR" ~ n~'n ht,,.-~rl ~G'ilIip$ .~"n.~. '2-
Seal~nt ~ The kd~ior ami .exterior perimeter joints, upturned Icg of the flashing ami all frame com~ectio~s
Additional Dcscrij)tlon_ -_
Dow ~ng ~ ~.
Spc~.H ~ ~~ ~ ~ ~em bi~ ~ fi~t j~, ~ ~ i~ j~b, s~dd ~n~ ~,~
/ 203 - ~. Sp~ B m~ Dow ~g 983 ~ne.
~ r~kem~ of~C~ ~ml PA 202 - 94. S~mea ~ m~ Dow ~ng
Sill: 6
the "La flashing to the wood test ~9k.
ii 14 x T' SS pan head .-wood screws
Ccnte~. 14 at 6' from fight jamb, O) at l6-T/16~ oc, (2) at 2' oo, 6z3/4~, (2) a~ 2~ oc, O) at l5-
and ~ight sill: PI16'; (:2) ~.Z" oc_
Rip. hr 6e.,~- 6 at 6" from right jamb, O)at 16-7/~6" oc._ (2)-aI 2"
05/02/0~ 1'/:50 F~ 850 66656?9
" .... :. :i~" .' .... :.? · ~ .' xJ' ~-:.:' ' ,'-,~.
'-; ~. '~ -. .::='.' ' 7-..::?.:-..~.:~i: '
KINK0$
Page 6 of 9
Static Tests were conducted in accordance with DCBCCD PA 202 - 94
+ 90.0 psi', - 90.0 pst. Speebneu F
· Posidve loads ~ime (~:.)
Test 30
U~Ioad oerm. set~kn,~b, le O.a%
135.0
O.OIT' 0.235"
.......... ~-O~g' ........ '0'.399" ....................
.~ 0
*N¢_~ive loa,~ time
'L'~'t jo
p__si'load l~rm. set alloi~tblo 0.4%'
I~$.0
029Cr~ 0.39~TM
0.002'~
IMPACT TESTS - LARGE MTSb-'I~E
rmnnet t~cs were c~nducted in accordance with DCBCCD PA 201 - 94
(~_,~l;___~g AS .._'J:~_ ~. 1RRf~.O9 and SI~CCI SSTD 12-99
i I'
I I
I I
I I
I I
I , ,!
I '*--' I
I I
1 I.
I
!
I
I
, I I
i 1
!
II
It
I1
r"-'*-, I !
12111
--'* ! 1
I I
I!
II
II
Il
!1
il
!1
I!
!1.
SP~;:~r~ I~/S~C
1). 5o.1 2). so.1 :q..
Succhnen D
,~ ~ 1! ' il
II II !1 il
!1 !! !1 11
I! Il Ii !i
!1 ~ .!1 ~ ~ II
I t-----!_~ t--II I~! !~1 II
I~ II
~009
': ..... 02.-1 00
I! !1 II 11
II Il ~ll II
il II I~ ill Il_
Il II ~ ~11 11
11 Ii -{~ ' ,~
?a$c ? of S
II II
Il II
!1~ 11
Iii~1 II
__l l: ' !!
{1 ii
SPEB~ Fl/SEC
1). 50.8 2). 50.8 3). 50.9 4). 50.7
# 2 Southern Yellow Pine 2,x4, 'Length approx= 92-11/16" & 9-1/2 l_J:,.
05/02/02
17:50 FAX 850 6685679 KINKOS
~OlO
0 .'t800
The first impact was made in thc center of the middlc pan& The second impact' was made in the
lower left corner or'tim middie panel. The thizd ~u~a~ w~ ~o ~ --~, ~, .................
~ertiead _mnllion_ The fourth impact was made at the ........ ':-'- '-: ..... ~ --"':""
Cycle t~'ts were concluaed in ac~ordan~ with DCBCCD PA, 203-94
o,,.~_lj_~ina ASTM E 1886-99 and SBCCI SSTD 12-99
- Sp_,x. lm~s a,. I)
ttnn~e of test
Positive lc;ads
+ .2 - .5
+ .0 - .6
+ _$ - .g
4-.3- ! .('1
actual load psf
t$ 45'
0 54
45 72
27 90
27 90
~ ~ '7O
# of cycles cycledmin
~ D
300 Z3 ~
600 46 ~
100 2_6 25
so 25 25
!OSO 47 31
~n 9~ ~5
Design Loads
+ $9.0 psf and - 89.0 psi'
Range of test
· actual load psf
ii of cycles
Positive loads
+ .5 - .a
-~ .3 - i_0
- .3 - 1.0
· '- .2 -' .5
53
"71
~ 89
45 71
0 53
lg 45
3500 39
goo 33
6OO 30
50 25
3350 ~
9000 qr¢l~ ¢omp~,,.~i
05/02/02 17:51 FAX 850
· -.~ ~. ' : ~',..~,~..-,-, - ..-.---~',,-~... ..... ,".!-~ ~
..-...'-(,;...;:.'. .,
~- mill polyothylenc film was used on'~he oycle tests and it is the opinion of
~he undersigned that they had no ir~luence on the results of these ~ests.
Observers- 11/3. 11/4,11118/99, l/l~ 1/13, ~/18/2000
............ ~';'o:;~.~' ~.~-~.~' T.~<, ~1~ ~'A~.~ '"
Bob Fi~--
The PA 201-94,'PA 202-94 and PA. 203-94 ~ reported have been imrformed in full ac, cordan~ to lira
~ements ofl)ad¢ Count,/, with no deviaicms.
Not pre, eat
/.Ketth ~__. ~sistam Direcior
"--Amcricag~est Lab oi South ~iorida
All Tcs~ Cer~ficd a~ud Wire. ed t~.
6795 N_ W. 17 Av~ue
F~ ~d~e, ~ 33309
)
[\\\ l .V
/q\ \v Nkk
05/02/02 17:~1 FAX 850 6685679 KINKO$ !~]012
05/02/02 17:52 FiX 850 6685679 KINKOS ~013
I
05/02/02 17:52 FAX 85__0 6585679 KI~0$ ~014
- I /'x~ - r-.,.,,,~.
J~, ~,,,,..,
- - ......... ;' ......... ~-'-~ ........................ il
.... _ ................................... Jq
~o15
I
Zl
o_1
...I ~1
, ,~1 ~1
u~l ~1
,~1
;41 I
u-I , .--fi,1
~.1 i-711
J,.ql I11t -"1 ~1
CITY OF BOYNTON BEACH
DEVELOPMENT DEPARTMENT
100 East Boynton Beach Blvd.
P. O. Box 310
Boynton Beach, Florida 33425-0310
PLAN REVIEW COMMENTS
- 1;:IU U
PLEASE NOTE THAT THE EFFICIENCY BY WHICH YOU RECEIVE YOUR PERMIT
DEPENDS ON YOUR RESPONSE TO THE CONTENTS OF THIS DOCUMENT. IT IS
RECOMMENDED THAT YOU CAREFULLY READ AND CORRECTLY RESPOND TO
ALL ASPECTS OF THIS DOCUMENT.
COMMENTS:
For permit application number / review: 02-1300 STRUCT I ST REVIEW
Project Name or Address: NEWPORT PLACE
REVIEWED BY:
Department and/or Division: Building Division
Name of Reviewer: Bob Donovan
Trade: Structual
Phone # (561) 742-6375 ext.
Fax # . (561) 742-6357
Review Date: 4/19/02
Type of Review: STRUCT
COMMENT DISTRIBUTION:
Person identified on the application to receive comments:
Name ABI COMPANIES
Phone # (area code:561) 586-6455 ext.
Fax # (area code:561) ,;.,
Date(s) reviewer called:
Person who received the call
THE FOLLOWING AREA SHALL BE FILLED-IN IN THE PRESENCE OF A BUILDING DIVISION
STAFF MEMBER:
COMMENTS/PLANS PICKED UP:
Comment(s) recd. by print name and date' ; -"
OR
Plans/Comments recd. by print name and date:
_. 05/02/02 17:$~ F/~ $$0 66856?9
KINI(O$
1~017
, I1-
U
o
i !.;.;.'.~
I
/
/
/1
I~,t
U
..... o$/o~/o2_ 17:$~ F~ $$0 66556?9
~015
05/02/02 17:54 FiL]~ 850 6685679
'~:,,i .. :::~:- -.,- ..:...,... ....... ,~ .~ .~ ..~ .... ,..-~ ~.
KINKO$
# !_2. x 1-1/~2: pan head ~hillips sins
Sill: 6 ~t 3-1/4"= 46~1/4": 26-1/2~ 34-1/4": 26-1~2". 46-1/2' from left jamb. Us~I lo fasten
th~ -r :' fl. ~hing tn t~he_ vnmd teat buck
Ccnter: 14.
anti fight sill:
at 6" from.right jamb, (3) at 16-7/16" oc, (2) at 2" oc, 6-3/4", t2) at 2" oc, O) at i5-
9116", (.2) al 2' oc. _
.
Air Infiltration Tests were conducted in aooordance with DCBCCD PA 202 - 94
R?o~imen F 0.02 CFM/SO. FT. 0.37 CFI~SQ. FT_ . - '"
Air at 62.4 psi'
Mea.mred
Allowable
ox? a~sq_ FT.
05/02/02 17:54 FAX 850 6685679 KINKO$
STATIC AI~ PRY.5~UI~ TEST~
02-1300
Page 5 ot'9
Qualifying ASTM E 330
!1 I~ Ii
II I1 11
I1 II !!
!1 II I1
II
II
II.
II
Il
II
II II
Il,, II
Icl II
Il Il
Il I
,
II
IL
II
II
Il
II
!l
I ~
D~ign Loads
+ 90.0 pst, - 9o.0 psf. Specimen F
Positive loads time (sec.) psfload - ma~z d~-fa~ ~A~
1/2 Test 30 67.5
Design 30 90.0 0.09(F'
max. deft: at 'B"
0.360"
No w.~e~ pe~-,,ilon over sill
':/:.
Page 2 of 2
Plan Review Comments for Permit Application # 02-1300 STRUCT lS ~ 0 0
Your permit application and supporting documentation do not comply with the City of
Boynton Beach Code of Ordinances. Prior to receiving a permit to construct or install
the requested improvements the plans and documents shall be amended to show
compliance with the below listed comments. For questions regarding my review please
contact me at the number listed above. If a conference is necessary, please schedule
an appointment. Phone calls and appointments are received and scheduled during
work days Monday through Friday 9:30 to 10:30 AM and 1:45 to 2:45 PM. Please note
that additional comments may be generated following staff review of the amended
plans. Timely approval of your project is dependent upon your prompt and correct
response to the information provided in this document.
1. AS PER SECTION 104.2 2001 FLORIDA BUILDING CODE NEED PRODUCT
APPROVAL SHEETS FOR THE NEW WINDOWS. ( NOTE MUST MEET IMPACT OR
NEED HURRICANE SHUTTERS,) ~,~ (,~..~
2. AS PER SECTION 104.2 2001 FLORIDA BUILDING CODE NEED
CONCONSTRUCTION DETAILS FOR NEW RAMP SHOWN ON PAGE A-1.0 OF
PLANS.
CITY OF BOYNTON BEACH
FIRE AND LIFE SAFETY DIVISION
100 East Boynton Beach Blvd.
P. O. Box 310
Boynton Beach, Florida 33425-0310
PLAN REVIEW COMMENTS
PLEASE NOTE THAT THE EFFICIENCY BY WHICH YOU RECEIVE YOUR PERMIT
DEPENDS ON YOUR RESPONSE TO THE CONTENTS OF THIS DOCUMENT. IT IS
RECOMMENDED THAT YOU CAREFULLY READ AND CORRECTLY RESPOND TO
ALL ASPECTS OF THIS DOCUMENT.
COMMENTS:
For permit application number / review: 02-1300/1st review fire-RWK
Project Name or Address: Newport Place
REVIEWED BY:
Department: Fire Rescue Department
Name of Reviewer: Rodger Kemmer, Plans Examiner/Fire Inspector
Phone # (561) 742-6753
Fax # (561) 364-7382
Review Date: 04/19/02
Type of Review: Fire & Life Safety
COMMENT DISTRIBUTION:
Person identified on the application to receive comments:
Name ABI Companies
Phone # (area code:561 ) 586-6455
Fax # (area code:)
Date(s) reviewer called:
Person who received the call
THE FOLLOWING AREA SHALL BE FILLED-IN IN THE PRESENCE OF A BUILDING DIVISION
STAFF MEMBER:
COMMENTS/PLANS PICKED UP: ,J/~.z./o
Comment(s) recd. by print name and dated~~ ~ 7"d~/~/,/t2~'~
OR
Plans/Comments recd. by print name and date:
Page 2 of 2 Plan Review Comments for Permit Application # 02-1300
02-180
Your permit application and supporting documentation do not comply with the City of Boynton Beach
Code of Ordinances, or lack sufficient detail to provide a comprehensive review. Prior to receiving a
permit to construct or install the requested improvements the plans and documents shall be amended to
show compliance with the comments listed below. For questions regarding my review please contact me
at the number listed above. If a conference is necessary, please schedule an appointment. Phone calls
are received and appointments scheduled during work days Monday through Friday 8:00 to 12:00 AM
and 1:00 to 5:00 PM. Please note that additional comments may be generated following staff review of
the amended plans. Corrected or revised plans must be submitted to the Building Department. Timely
approval of your project is dependent upon your prompt and correct response to the information provided
in this document.
Will this work require any modifications or impairments to the fire sprinkler system?
If so, provide details.
Provide ramp detail.
Are cooking appliances located in the Hobby & Crafts room used for any purpose
that would generate smoke or grease laden vapors?
Where an approved fire alarm system is installed in a building, HVAC duct detectors
shall be connected to the fire alarm system. They are not required to activate the
building evacuation alarm. NFPA 90A (1999) Section 4-4.4.2.
Smoke detectors for use in air distribution systems shall be located downstream of
the air filters and ahead of any branch connections in the air supply systems having
a capacity greater than 2000 cfm. (NFPA 90^, 1999, Section 4-4.2)
Reference Note #5 on dwg. MO.3, a hood exhaust fan(s) shall continue to operate
after the extinguishing system has been activated, unless fan shutdown is required
by a listed component of the ventilation system or by the design of the extinguishing
system. (NFPA 96, 1996, Section 5-2.3)
CITY OF BOYNTON BEACH
DEVELOPMENT DEPARTMENT
100 East Boynton Beach Blvd.
P. O. Box 310
Boynton Beach, Florida 33425-0310
02-1300
FILE COPY
PLAN REVIEW COMMENTS
PLEASE NOTE THAT THE EFFICIENCY BY WHICH YOU RECEIVE YOUR PERMIT
DEPENDS ON YOUR RESPONSE TO THE CONTENTS OF THIS DOCUMENT. IT IS
RECOMMENDED THAT YOU CAREFULLY READ AND CORRECTLY RESPOND TO
ALL ASPECTS OF THIS DOCUMENT.
COMMENTS:
For permit application number/review: 02-1300 1ST REVIEW
Project Name or Address: ABI COMPANIES
REVIEWED BY:
Department and/or Division: Building Division
Name of Reviewer: Bill Erskine
Trade:
Phone #
Fax #
Review Date:
Type of Review:
Mechanical - Plumbing
(561) 742-6755 ext.
(561) 742-6357
4/17/02
PLUMBING/MECHANICAL
COMMENT DISTRIBUTION:
Person identified on the application to receive comments:
Name TONY HUDZIK
Phone # (area code:813) 927-2977
Fax # (area code:561 )
Date(s) reviewer called:
Person who received the call
ext.
THE FOLLOWING AREA SHALL BE FILLED-IN IN THE PRESENCE OF A BUILDING DIVISION
STAFF MEMBER:
COMMENTS/PLANS PICKED UP:
Comment(s) recd. by print name and date:~.. ~
OR
Plans/Comments recd, by print name and date:
Page 2 of 2 Plan Review Comments for Permit Application # 02-1300 1 ST REVIEW ,
02-1800
Your permit application and supporting documentation do not comply with the City of
Boynton Beach Code of Ordinances. Pdor to receiving a permit to construct or install
the requested improvements the plans and documents shall be amended to show
compliance with the below listed comments. For questions re§ardin§ my review please
contact me at the number listed above. If a conference is necessary, please schedule
an appointment. Phone calls and appointments are received and scheduled dudn§
work days Monday through Friday 9:30 to 10:30 AM and 1:45 to 2:45 PM. Please note
that additional comments may be generated following staff review of the amended
plans. Timely approval of your project is dependent upon your prompt and correct
response to the information provided in this document.
1. SECTION 606.2.1 FMC 01- PROVIDE SMOKE DETECTORS FOR ALL THE
A/C UNITS.
2. SECTION 608.16.1 FPC 01- PROVIDE BACKFLOW PROTECTION ST THE
BEVERAGE DISPENSER.
3. SECTION 104.2 FMC 01- THE ENERGY CALCULATIONS SHOW A MAXIMUM
PER SYSTEM OF 46 TONS WITH 1 ZONE, WHILE THE PLANS SHOW 65.5
TONS IN RTU'S ALONE AND MANY ZONES, PLEASE CLARIFY.
4. SECTION 1002.4 FPC 01- PROVIDR TRAP PRIMERS ON ALL FLOOR
DRAI NS.
FIGURE 404.4.3(e) FPC 01- COMPLY WITH THIS SECTION, THE MINIMUM
WIDTH OF AN ACCESSIBLE TOILET STALL IN A TOILET ROOM IS 84.5",
WITH THE CENTER OF THE LAVATORY BEING 15"T TO CENTER FROM A
SIDE WALL.
02-1300
CITY OF BOYNTON BEACH
DEVELOPMENT DEPARTMENT
100 East Boynton Beach Blvd.
P. O. Box 310
Boynton Beach, Florida 33425-0310
PLAN REVIEW COMMENTS
PLEASE NOTE THAT THE EFFICIENCY BY WHICH YOU RECEIVE YOUR PERMIT
DEPENDS ON YOUR RESPONSE TO THE CONTENTS OF THIS DOCUMENT. IT IS
RECOMMENDED THAT YOU CAREFULLY READ AND CORRECTLY RESPOND TO
ALL ASPECTS OF THIS DOCUMENT.
COMMENTS:
For permit application number / review: 02-1300 1sT REVIEW
Project Name or Address: AB! COMPANIES
REVIEWED BY:
Department and/or Division: Building Division
Name of Reviewer: Bill Erskine
Trade: Mechanical - Plumbing
Phone # (561) 742-6755 ext.
Fax # (561) 742-6357
Review Date: 4/17/02
Type of Review: PLUMBING/MECHANICAL
COMMENT DISTRIBUTION:
Person identified on the application to receive comments:
Name TONY HUDZlK
Phone # (area code:813) 927-2977 ext.
Fax # .(area code:561)
Date(s) reviewer called:
Person who received the call
THE FOLLOWING AREA SHALL BE FILLED-IN IN THE PRESENCE OF A BUILDING DIVISION
STAFF MEMBER:
COMMENTS/PLANS PICKED UP:
Comment(s) recd. by print name and date:
OR
Plans/Comments recd. by pdnt name and date:
Page 2 of 2
Plan Review Comments for Permit Application # 02-1300 1sT REVIEW
0
Your permit application and supporting documentation do not comply with the City of
Boynton Beach Code of Ordinances. Prior to receiving a permit to construct or install
the requested improvements the plans and documents shall be amended to show
compliance with the below listed comments. For questions regarding my review please
contact me at the number listed above. If a conference is necessary, please schedule
an appointment. Phone calls and appointments are received and scheduled during
work days Monday through Friday 9:30 to 10:30 AM and 1:45 to 2:45 PM. Please note
that additional comments may be generated following staff review of the amended
plans. Timely approval of your project is dependent upon your prompt and correct
response to the information provided in this document.
1. SECTION 606.2.1 FMC 01- PROVIDE SMOKE DETECTORS FOR ALL THE
NC UNITS.
2. SECTION 608.16.1 FPC 01- PROVIDE BACKFLOW PROTECTION ST THE
BEVERAGE DISPENSER.
3. SECTION 104.2 FMC 01- THE ENERGY CALCULATIONS SHOW A MAXIMUM
PER SYSTEM OF 46 TONS WITH 1 ZONE, WHILE THE PLANS SHOW 65.5
TONS IN RTU'S ALONE AND MANY ZONES, PLEASE CLARIFY.
· 4. SECTION 1002.4 FPC 01- PROVIDR TRAP PRIMERS ON ALL FLOOR
DRAINS.
FIGURE 404.4.3(e) FPC 01- COMPLY WITH THIS SECTION, THE MINIMUM
WIDTH OF AN ACCESSIBLE TOILET STALL IN A TOILET ROOM IS 84.5",
WITH THE CENTER OF THE LAVATORY BEING 15'% TO CENTER FROM A
SIDE WALL.
May 7, 2002
02-1300
ABI Companies, Inc.
4301 Anchor Plaza Parkway
Tampa, FL 33634
Attn:
Re:
Mr. Robert Brikas
Newport Place Cafeteria Building
PEI Project No. 02053
City of Boynton Beach Plan Review Comment
Dear Bob,
Peninsula Engineering, Inc. has completed our review of the Plan Review Comments from the
City of Boynton Beach on the above referenced project. A number of their comments are the
result of the engineering design being based on the old building code and the plan review was
based on the new Florida Mechanical Code.
The following is listing of the city's comments and Peninsula Engineering's response.
BUILDING DMSION
COMMENT NO. 1
Section 606.2.1 FMC 01 - Provide smoke detectorS for all the A/C Units:
RESPONSE
Duct smoke detectors have been provided in all new or replace air conditioning units
having a capacity greater than 2000 cfm or combination of MC units serving a common
area having a combined capacity greater than 2000 cfm.
The drawings have been revised to locate the duct smoke detectors in the supply air duct
in lieu of the return air duct in accordance with FMC01.
'"
SELECTED 1998 ENGINEERING FIRM OF THE YEAR BY FLORID/~ ENeINEERlr ,~~
2016 AMen Road Orlando, Florida 32803 407.246.1688 FAX 4 ~ o~, "7 .... ' '-'- ( poi peifla.com
center from a side wall.
Mr. Robert Brikas
COMMENT NO. 4
May 7, 2002
02- $00
Where an approved fire alarm system is installed in a building, HVAC duct detectors
shall be connected to the fire alarm system. They are not required to activate the building
evacuation alarm. NFPA 90A (1999) Section 4-4.4.2.
RESPONSE
The building does have a fire alarm system. The fire alarm contractor to provide
drawings and details to connect HVAC duet smoke detectors to the system.
COMMENT NO. 5
Smoke detectors for use in air distribution systems shall be located downstream of the air
filters and ahead of any branch connections in the air supply systems having a capacity
greater than 2000 cfm. (NFPA 90A, 1999, Section 4-4.2)
RESPONSE
The HVAC drawings have been revised to indicate location of duct smoke detectors in
the supply air duct from A/C unit with having 2000 cfm or greater per NFPA 90A and
FIVIC01.
COMMENT NO. 6
Reference Note #5 on dwg. MO.3, a hood exhaust fan(s) shall continue to operate after
the extinguishing system has been activated, unless fan shutdown is required by a listed
component of the ventilation system or by the design of the extinguishing system.
(NFPA 96, 1996, Section 5-2.3)
RESPONSE
Note No. 5 on drawing MO.3 has been revised to indicate hood exhaust fan to continue to
operate a_tier extinguishing system activation. The hood's make-up air fan will shut down
upon extinguishing system activation.
Peninsula Engineering, Inc. has revised the mechanical and plumbing drawings to incorporate
Mr. Robert Brikas May '/, 2002
02-1300
Please review the comments and drawings and let us know fi]you have any comments or require
additional information.
Sincerely,
Albert Marques, P.E.
Mechanical Engineer
Florida Registration #37313
BS:jnp
CITY OF BOYNTON BEACH
FIRE AND LIFE SAFETY DIVISION
100 East Boynton Beach Blvd.
P. O. Box 310
Boynton Beach, Florida 33425-0310
, II I I ! .... I .... IIII I I I I ,,, I ................ I, , I I I I I , I I .... I,[ I
0P,"1800
PLAN REVIEW COMMENTS
PLEASE NOTE THAT THE EFFICIENCY BY WHICH YOU RECEIVE YOUR PERMIT
DEPENDS ON YOUR RESPONSE TO THE CONTENTS OF THIS DOCUMENT. IT IS
RECOMMENDED THAT YOU CAREFULLY READ AND CORRECTLY RESPOND TO
ALL ASPECTS OF THIS DOCUMENT.
COMMENTS:
For permit application number / review: 02-1300/1st review fire-RWK
Project Name or Address: Newport Place
REVIEWED BY:
Department: Fire Rescue Department
Name of Reviewer: , R0dger Kemmer, Plans Examiner/Fire Inspector
Phone # (561) 742-6753
Fax # (561) 364-7382
Review Date: 04/19/02
Type of Review: Fire & Life Safety
COMMENT DISTRIBUTION:
Person identified on the application to receive comments:
Name ABI Companies
Phone # (area code:561 ) 586-6455
Fax # (area code:)
Date(s) reviewer called:
Person who received the call
THE FOLLOWING AREA SHALL BE FILLED-IN IN THE PRESENCE OF A BUILDING DIVISION
STAFF MEMBER:
· ,ii
COMMENTS/PLANS PICKED UP:
Comment(s) recd. by print name and date:
OR
Plans/Comments recd. by print name and date:
Page 2 of 2
Plan Review Comments for Permit Application # 02-1300
O2
'1800
Your permit application and supporting documentation do not comply with the City of Boynton Beach
Code of Ordinances, or lack sufficient detail to provide a comprehensive review. Pdor to receiving a
permit to construct or install the requested improvements the plans and documents shall be amended to
show compliance with the comments listed below. For questions regarding my review please contact me
at the number listed above. If a conference is necessary, please schedule an appointment. Phone calls
are received and appointments scheduled during work days Monday through Friday 8:00 to 12:00 AM
and 1:00 to 5:00 PM. Please note that additional comments may be generated following staff review of
the amended plans. Corrected or revised plans must be submitted to the Building Department. Timely
approval of your project is dependent upon your prompt and correct response to the information provided
in this document.
Will this work require any modifications or impairments to the fire sprinkler system?
If so, provide details.
Provide ramp detail.
Are cooking appliances located in the Hobby & Crafts room used for any purpose
that would generate smoke or grease laden vapors?
Where an approved fire alarm system is installed in a building, HVAC duct detectors
shall be connected to the fire alarm system. They are not required to activate the
building evacuation alarm. NFPA 90A (1999) Section 4-4.4.2.
Smoke detectors for use in air distribution systems shall be located downstream of
the air filters and ahead of any branch connections in the air supply systems having
a capacity greater than 2000 cfm. (NFPA 90A, 1999, Section 4-4.2)
Reference Note #5 on dwg. MO.3, a hood exhaust fan(s) shall continue to operate
after the extinguishing system has been activated, unless fan shutdown is required
by a listed component of the ventilation system or by the design of the extinguishing
system. (NFPA 96, 1996, Section 5-2.3)
NEWPOI PLACE
-11t0
0
May 9, 2002
City of Boynton Beach
Fire Rescue Department
Roger Kemmer, Plans Examiner/Fire Inspector
Re: Newport Place, 4735 N.W. 7th Court, Boynton Beach, Fl. 33426
To Whom It May Concern:
Staff or residents do not use the cooking appliances located in the Arts &
Crafts room. These appliances are for aesthetic purposes only.
If you have any questions, please do not hesitate to call me.
Sincerely,
Lori Okeon
Executive Director
~I~,~A HoalzoN BaY S£Nioa COMMUNITY
4735 N.W. SEVENTH COUR'r BOYNTON BEACH, FL 33426
561-586-6455 FAx 561-586-0828 . WWW.HOmZOrqBA¥.COM
May 7, 2002
02-1300--
ABI Companies, Inc.
4301 Anchor Plaza Parkway
Tampa, FL 33634
Attn:
Re:
Mr. Robert Brikas
Newport Place Cafeteria Building
PEI Project No. 02053
City of Boynton Beach Plan Review Comment
Dear Bob,
Peninsula Engineering, Inc. has completed our review of the Plan Review Comments from the
City of Boynton Beach on the above referenced project. A number of their comments are the
result of the engineering design being based on the old building code and the plan review was
based on the new Florida Mechanical Code.
The following is listing of the city's comments and Peninsula Engineering's response.
BUILDING DMSION
COMMENT NO. 1
Section 606.2.1 FMC 01 - Provide smoke detectors for all the A/C units.
RESPONSE
Duct smoke detectors have been provided in all new or replace air conditioning units
having a capacity greater than 2000 cfm or combination of A/C units serving a common
area having a combined capacity greater than 2000 cfm.
The drawings have been revised to locate the duct smoke detectors in the supply air duct
in lieu of the return air duct in accordance with FMCO1. ~ .......................
SELECTED 1998 ENGINEERING FIRM OF THE YEAR BY FLORIDA ENGINEERING SOCIETY
2016 Alden Road Orlando, Florida 32803 407.246.1688 FAX 407.246.1664 :: E-Mail pei@peifla.com
Mr. Robert Brikas May 7, 2002
COMMENT NO. 2
::' 0 -1 00
Section 608.16.1 FPC 01 - Provide backflow protection at the beverage dispenser.
RESPONSE
The plumbing drawings have been revised to provide a double check type backflow
preventer in the water line to the beverage dispensers.
COMMENT NO. 3
Section 104.2 FMC 01 - The energy calculations show a maximum per system of 46 tons
with 1 zone, while the plans show 65.5 tons in RTU's alone and many zones, please
clarify.
RESPONSE
Per Daniel Young, (Peninsula Engineering, Inc.), phone conversation with Mr. Bill
Erskine (Plan Reviewer, City of Boynton Beach) the submitted Florida Energy Code was
to cover the 2na floor of the dining building. The tonnage for the 2nd floor is
approximately 46 tons as indicated on the energy code.
The A.C. and RTU schedule indicate all the A/C units for the project. The other
scheduled units are for direct replacement of defective units in the 1~t floor of the dining
building, administration building and the two residenance towers.
COMMENTS NO. 4
Section 1002.4 FPC 01 - Provide trap primers on all floor drains.
RESPONSE
Tap primers are being provided on all floor drains per Note No. 3 on Drawing P2.2.
COMMENT NO. 5
Figure 404.4.3(e) FPC 0 1 - Comply with this section, the minimum width of an
accessible toilet stall in a toilet room is 84.5", with the center of the lavatory being 15" to
center from a side wall.
Mr. Robert Brikas May 7, 2002
RESPONSE -' 0 2 - 1 3 0 0
Architect needs to verify room and stall dimensions and fixture placement to comply with
FPCO 1.
FIRE RESCUE DEPARTMENT
COMMENT NO. 1
Will this work require any modifications or impairments to the fire sprinkler system? If
so, provide details.
RESPONSE
Yes, the sprinkler system will require modifications to accommodate the new layout of
the 2na floor of the dining building. The sprinkler contractor to provide sprinkler layout
drawings as required.
COMMENT NO. 2
Provide ramp detail
RESPONSE
Architect needs to provide ramps details.
COMMENT NO. 3
Are cooking appliances located in the Hobby and Crat'ts room used for any purpose that
would generate smoke or grease laden vapors?
RESPONSE
According to staff, the cooking appliances in the Hobby and Crafts room are used for
crafts and to boil water, not cooking. Owner should verify usage..
Mr. Robert Brikas May 7, 2002
COMMENT NO. 4
02-1300
Where an approved fire alarm system is installed in a building, HVAC duct detectors
shall be connected to the fire alarm system. They are not required to activate the building
evacuation alarm. NFPA 90A (1999) Section 4-4.4.2.
RESPONSE
The building does have a fire alarm system. The fire alarm contractor to provide
drawings and details to connect HVAC duct smoke detectors to the system.
COMMENT NO. 5
Smoke detectors for use in air distribution systems shall be located downstream of the air
filters and ahead of any branch connections in the air supply systems having a capacity
greater than 2000 cfm. (NFPA 90A, 1999, Section 4-4.2)
RESPONSE
The HVAC drawings have been revised to indicate location of duct smoke detectors in
the supply air duct from A/C unit with having 2000 cfm or greater per NFPA 90A and
FMC01.
COMMENT NO. 6
Reference Note #5 on dwg. MO.3, a hood exhaust fan(s) shall continue to operate at~er
the extinguishing system has been activated, unless fan shutdown is required by a listed
component of the ventilation system or by the design of the extinguishing system.
(NFPA 96, 1996, Section 5-2.3)
RESPONSE
Note No. 5 on drawing MO.3 has been revised to indicate hood exhaust fan to continue to
operate after extinguishing system activation. The hood's make-up air fan will shut down
upon extinguishing system activation.
Peninsula Engineering, Inc. has revised the mechanical and plumbing drawings to incorporate
the City's comments.
Mr. Robert Brikas May 7, 2002
Please review the comments and drawings and let us know if you have any comments or require
additional information.
- 02-1300
Sincerely,
Albert Marques, P.E.
Mechanical Engineer
Florida Registration #37313
BS:jnp
CITY OF BOYNTON BEACH
FIRE AND LIFE SAFETY DIVISION
100 East Boynton Beach Blvd.
P. O. Box 310
Boynton Beach, Florida 33425-0310
02-1300
PLAN REVIEW COMMENTS
PLEASE NOTE THAT THE EFFICIENCY BY WHICH YOU RECEIVE YOUR PERMIT
DEPENDS ON YOUR RESPONSE TO THE CONTENTS OF THIS DOCUMENT. IT IS
RECOMMENDED THAT YOU CAREFULLY READ AND CORRECTLY RESPOND TO
ALL ASPECTS OF THIS DOCUMENT.
COMMENTS:
For permit application number / review: 02-1300/2nd review fire-RWK
Project Name or Address: Newport Place
REVIEWED BY:
Department: Fire Rescue Department
Name of Reviewer: Rodger Kemmer, Plans Examiner/Fire Inspector
Phone # (56'1) 742-6753
Fax # (56'1) 364-7382
Review Date: 05/10/02
Type of Review: Fire & Life Safety
COMMENT DISTRIBUTION:
Person identified on the application to receive comments:
Name ABI Companies
Phone # (area code:561) 586-6455
Fax # (area code:)
Date(s) reviewer called:
Person who received the call
THE FOLLOWING AREA SHALL BE FILLED-IN IN THE PRESENCE OF A BUILDING DIVISION
STAFF MEMBER:
COMMENTS/PLANS PICKED UP:
Comment(s) recd. by print name and date:
OR
Plans/Comments recd. by print name and date:
Page 2 of 2
Plan Review Comments for Permit Application # 02-1300
0 '1800
Your permit application and supporting documentation do not comply with the City of Boynton Beach
Code of Ordinances, or lack sufficient detail to provide a comprehensive review. Prior to receiving a
permit to construct or install the requested improvements the plans and documents shall be amended to
show compliance with the comments listed below. For questions regarding my review please contact me
at the number listed above. If a conference is necessary, please schedule an appointment. Phone calls
are received and appointments scheduled during work days Monday through Friday 8:00 to 12:00 AM
and 1:00 to 5:00 PM. Please note that additional comments may be generated following staff review of
the amended plans. Corrected or revised plans must be submitted to the Building Department. Timely
approval of your project is dependent upon your prompt and correct response to the information provided
in this document.
Provide ramp detail. (Not addressed from 1st review)
CITY OF BOYNTON BEACH
FIRE AND LIFE SAFETY DIVISION
100 East Boynton Beach Blvd.
P. O. Box 310
Boynton Beach, Florida 33425-0310
'1 00
PLAN REVIEW COMMENTS
PLEASE NOTE THAT THE EFFICIENCY BY WHICH YOU RECEIVE YOUR PERMIT
DEPENDS ON YOUR RESPONSE TO THE CONTENTS OF THIS DOCUMENT. IT IS
RECOMMENDED THAT YOU CAREFULLY READ AND CORRECTLY RESPOND TO
ALL ASPECTS OF THIS DOCUMENT.
COMMENTS:
For permit application number / review: 02-1300/2nd review fire-RWK
Project Name or Address: Newport Place
REVIEWED BY:
Department: Fire Rescue Department
Name of Reviewer: Rodger Kemmer, Plans Examiner/Fire Inspector
Phone # (561) 742-6753
Fax # (561) 364-7382
Review Date: 05/10/02
Type of Review: Fire & Life Safety
COMMENT DISTRIBUTION:
Person identified on the application to receive comments:
Name ABI Companies
Phone # (area code:561) 586-6455
Fax # (area code:)
Date(s) reviewer called:
Person who received the call
THE FOLLOWING AREA SHALL BE FILLED-IN IN THE PRESENCE OF A BUILDING DIVISION
STAFF MEMBER:
COMMENTS/PLANS PICKED UP:
Comment(s) recd. by print name and date:
OR
Plans/Comments recd. by print name and date:
Page 2 of 2 Plan Review Conunents for Permit Application # 02-1300
Your permit application and supporting documentation do not comply with the City of Boynton Beach
Code of Ordinances, or lack sufficient detail to provide a comprehensive review. Prior to receiving a
permit to construct or install the requested improvements the plans and documents shall be amended to
show compliance with the comments listed below. For questions regarding my review please contact me
at the number listed above. If a conference is necessary, please schedule an appointment. Phone calls
are received and appointments scheduled during work days Monday through Friday 8:00 to 12:00 AM
and 1:00 to 5:00 PM. Please note that additional comments may be generated following staff review of
the amended plans. Corrected or revised plans must be submitted to the Building Department. Timely
approval of your project is dependent upon your prompt and correct response to the information provided
in this document.
Provide ramp detail. (Not addressed from 1st review)
2
CITY OF BOYNTON BEACH
FIRE AND LIFE SAFETY OlVlSlON
100 East Boynton Beach Blvd.
P. O. Box 310
Boynton Beach, Florida 33425-0310
02-1300
PLAN REVIEW COMMENTS
PLEASE NOTE THAT THE EFFICIENCY BY WHICH YOU RECEIVE YOUR PERMIT
DEPENDS ON YOUR RESPONSE TO THE CONTENTS OF THIS DOCUMENT. IT IS
RECOMMENDED THAT YOU CAREFULLY READ AND CORRECTLY RESPOND TO
ALL ASPECTS OF THIS DOCUMENT.
COMMENTS:
For permit application number / review: 02-1300/1st review fire-RWK
Project Name or Address: Newport Place
REVIEWED BY:
Department: Fire Rescue Department
Name of Reviewer. Rodger Kemmer~, Plans Examiner/Fire Inspector
Phone # (561) 742-6753
Fax # (561) 364-7382
Review Date: 04/19/02
Type of Review: Fire & Life Safety
COMMENT DISTRIBUTION:
Person identified on the application to receive comments:
Name ABI Companies
Phone # (area code:561) 586-6455
Fax # . (area code:)
Date(s) reviewer called:
Person who received the call
THE FOLLOWING AREA SHALL BE FILLED-IN IN THE PRESENCE OF A BUILDING DIVISION
STAFF MEMBER:
COMMENTS/PLANS PICKED UP:
Comment(s) recd. by print name and date:
OR
Plans/Comments recd. by pdnt name and date:
Page 2 of 2
Plan Review Comments for Permit Application # 02-1300
02-1300
Your permit application and supporting documentation do not comply with the City of Boynton Beach
Code of Ordinances, or lack sufficient detail to provide a comprehensive review. Prior to receiving a
permit to construct or install the requested improvements the plans and documents shall be amended to
show compliance with the comments listed below. For questions regarding my review please contact me
at the number listed above. If a conference is necessary, please schedule an appointment. Phone calls
are received and appointments scheduled during work days Monday through Friday 8:00 to 12:00 AM
and 1:00 to 5:00 PM. Please note that additional comments may be generated following staff review of
the amended plans. Corrected or revised plans must be submitted to the Building Department. Timely
approval of your project is dependent upon your prompt and correct response to the information provided
in this document.
Will this work require any modifications or impairments to the fire sprinkler system?
If so, provide details.
Provide ramp detail.
Are cooking appliances located in the Hobby & Crafts room used for any purpose
that would generate smoke or grease laden vapors?
Where an approved fire alarm system is installed in a building, HVAC duct detectors
shall be connected to the fire alarm system. They are not required to activate the
building evacuation alarm. NFPA 90A (1999) Section 4-4.4.2.
Smoke detectors for use in air distribution systems shall be located downstream of
the air filters and ahead of any branch connections in the air supply systems having
a capacity greater than 2000 cfm. (NFPA 90A, 1999, Section 4-4.2)
Reference Note #5 on dwg. MO.3, a hood exhaust fan(s) shall continue to operate
after the extinguishing system has been activated, unless fan shutdown is required
by a listed component of the ventilation system or by the design of the extinguishing
system. (NFPA 96, 1996, Section 5-2.3)
NEWPOR PLACE
02-1300
May 9, 2002
City of Boynton Beach
Fire Rescue Department
Roger Kemmer, Plans Examiner/Fire Inspector
Re: Newport Place, 4735 N.W. 7th Court, Boynton Beach, Fl. 33426
To Whom It May Concern:
Staff or residents do not use the cooking appliances located in the Arts &
Crafts room. These appliances are for aesthetic purposes only.
If you have any questions, please do not hesitate to call me.
Sincerely,
Lori Okeon
Executive Director
'~--~ A HORIZON BAY SENIOR COMMUNITY
4735 N.W. SEVENTH COURT BOYNTON BEACH, FL 33426
561-586-6455 FAX 561-586-0828 WWW.HORIZONBAY.COM
02-1800
May 7, 2002
ABI Companies, Inc.
4301 Anchor Plaza Parkway
Tampa, FL 33634
Attn:
Re:
Mr. Robert Brikas
Newport Place Cafeteria Building
PEI Project No. 02053
City of Boynton Beach Plan Review Comment
Dear Bob,
Peninsula Engineering, Inc. has completed our review of the Plan Review Comments from the
City of Boynton Beach on the above referenced project. A number of their comments are the
result of the engineering design being based on the old building code and the plan review was
based on the new Florida Mechanical Code.
The following is listing of the city's comments and Peninsula Engineering's response.
BUILDING DIVISION
COMMENT NO. 1
Section 606.2.1 FMC 01 - Provide smoke detectors for all the A/C units.
RESPONSE
Duct smoke detectors have been provided in all new or replace air conditioning units
having a capacity greater than 2000 cfm or combination of A/C units serving a common
area having a combined capacity greater than 2000 cfm.
The drawings have been revised to locate the duct smoke detectors in the supply air duct
in lieu of the return air duct in accordance with FMC01 .! ~. '~i.' ~" :~:-.~ ;.?: .~i~ ~ -.~-~ '
SELEGTED ~998 ENGINEERING FI~M OF THE YEA~ EY FLORIDA ENGINEERING SOCIETY
~0~ ~1~ ~o~ Orl~o, Florida 3~80~ 407.~4&~ FAX 407.~4~A6~4 E-mail ~oi~oodl~.~om
Mr. Robert Brikas May 7, 2002
COMMENT NO. 2 "
- 018-1300
Section 608.16.1 FPC 01 - Provide backflow protection at the beverage dispenser.
RESPONSE
The plumbing drawings have been revised to provide a double check type backflow
preventer in the water line to the beverage dispensers.
COMMENT NO. 3
Section 104.2 FMC 01 - The energy calculations show a maximum per system of 46 tons
with 1 zone, while the plans show 65.5 tons in RTU's alone and many zones, please
clarify.
RESPONSE
Per Daniel Young, (Peninsula Engineering, Inc.), phone conversation with Mr. Bill
Erskine (Plan Reviewer, City of Boynton Beach) the submitted Florida Energy Code was
to cover the 2na floor of the dining building. The tonnage for the 2na floor is
approximately 46 tons as indicated on the energy code.
The A.C. and RTU schedule indicate all the A/C units for the project. The other
scheduled units are for direct replacement of defective units in the 1~t floor of the dining
building, administration building and the two residenance towers.
COMMENTS NO. 4
Section 1002.4 FPC 01 - Provide trap primers on all floor drains.
RESPONSE
Tap primers are being provided on all floor drains per Note No. 3 on Drawing P2.2.
COMMENT NO. 5
Figure 404.4.3(e) FPC 0 1 - Comply with this section, the minimum width of an
accessible toilet stall in a toilet room is 84.5", with the center of the lavatory being 15" to
center from a side wall.
Mr. Robert Brikas May 7, 2002
RESPONSE -~ 0 2 ' 1 3 0 0
Architect needs to verify room and stall dimensions and fixture placement to comply with
FPC01.
FIRE RESCUE DEPARTMENT
COMMENT NO. 1
Will this work require any modifications or impairments to the fire sprinkler system? If
so, provide details.
RESPONSE
Yes, the sprinkler system will require modifications to accommodate the new layout of
the 2na floor of the dining building. The sprinkler contractor to provide sprinkler layout
drawings as required.
COMMENT NO. 2
Provide ramp detail
RESPONSE
Architect needs to provide ramps details.
COMMENT NO. 3
Are cooking appliances located in the Hobby and Crafts room used for any purpose that
would generate smoke or grease laden vapors7
RESPONSE
According to staff, the cooking appliances in the Hobby and Crafts room are used for
crafts and to boil water, not cooking. Owner should verify usage.
Mr. Robert Brikas
COMMENT NO. 4
May 7, 2002
0 ,-1300
Where an approved fire alarm system is installed in a building, HVAC duct detectors
shall be connected to the fire alarm system. They are not required to activate the building
evacuation alarm. NFPA 90A (1999) Section 4-4.4.2.
RESPONSE
The building does have a fire alarm system. The fire alarm contractor to provide
drawings and details to connect HVAC duct smoke detectors to the system.
COMMENT NO. 5
Smoke detectors for use in air distribution systems shall be located downstream of the air
filters and ahead of any branch connections in the air supply systems having a capacity
greater than 2000 cfm. (NFPA 90A, 1999, Section 4-4.2)
RESPONSE
The HVAC drawings have been revised to indicate location of duct smoke detectors in
the supply air duct from A/C unit with having 2000 cfm or greater per NFPA 90A and
FMCO1.
COMME~ NO. 6
Reference Note #5 on dwg. MO.3, a hood exhaust fan(s) shall continue to operate after
the extinguishing system has been activated, unless fan shutdown is required by a listed
component of the ventilation system or by the design of the extinguishing system.
(NFPA 96, 1996, Section 5-2.3)
RESPONSE
Note No. 5 on drawing MO.3 has been revised to indicate hood exhaust fan to continue to
operate after extinguishing system activation. The hood's make-up air fan will shut down
upon extinguishing system activation.
Peninsula Engineering, Inc. has revised the mechanical and plumbingidra, wi_ggs:to ,.'mco~gr .ale
the City's comments.
= 0B-1300
Mr. Robert Brikas
May 7, 2002
Please review the comments and drawings and let us know if you have any comments or require
additional information.
Sincerely,
Albert Marques, P.E.
Mechanical Engineer
Florida Registration #37313
BS:jnp
02-1300
CITY OF BOYNTON BEACH
DEVELOPMENT DEPARTMENT
100 East Boynton Beach Blvd.
P. O. Box 310
Boynton Beach, Fiodda 33425-0310
PLAN REVIEW COMMENTS
PLEASE NOTE THAT THE EFFICIENCY BY WHICH YOU RECEIVE YOUR PERMIT
DEPENDS ON YOUR RESPONSE TO THE CONTENTS OF THIS DOCUMENT. IT IS
RECOMMENDED THAT YOU CAREFULLY READ AND CORRECTLY RESPOND TO
ALL ASPECTS OF THIS DOCUMENT.
COMMENTS:
For permit application number/review: 02-1300 1ST REVIEW
Project Name or Address: ABI COMPANIES
REVIEWED BY:
Department and/or Division: Building Division
Name of Reviewer: Bill Erskine
Trade: MechanicaI - plumbing
Phone # (561) 742-6755 ext.
Fax # (561) 742-6357
Review Date: 4/17/02
Type of Review: PLUMBING/MECHANICAL
COMMENT DISTRIBUTION:
Person identified on the application to receive comments:
Name TONY HUDZIK
Phone # (area code:813). 927-2977 ext.
Fax # (area code:561 )
Date(s) reviewer called:
Person who received the call
THE FOLLOWING AREA SHALL BE FILLED-IN IN THE PRESENCE OF A BUILDING DIVISION
STAFF MEMBER:
COMMENTS/PLANS PICKED UP:
Comment(s) recd, by print name and date:
OR
Plans/Comments recd. by pdnt name and date:
Page 2 of 2
Plan Review Comments for Permit Application # 02-1300 1 ST REVIEW '~
02-130
Your permit application and supporting documentation do not comply with the City of
Boynton Beach Code of Ordinances. Pdor to receiving a permit to construct or install
the requested improvements the plans and documents shall be amended to show
compliance with the below listed comments. For questions regarding my review please
contact me at the number listed above. If a conference is necessary, please schedule
an appointment. Phone calls and appointments are received and scheduled during
work days Monday through Friday 9:30 to 10:30 AM and 1:45 to 2:45 PM. Please note
that additional comments may be generated following staff review of the amended
plans. Timely approval of your project is dependent upon your prompt and correct
response to the information provided in this document.
1. SECTION 606.2.1 FMC 01- PROVIDE SMOKE DETECTORS FOR ALL THE
NC UNITS.
2. SECTION 608.16.1 FPC 01- PROVIDE BACKFLOW PROTECTION ST THE
BEVERAGE DISPENSER.
3. SECTION 104.2 FMC 01- THE ENERGY CALCULATIONS SHOW A MAXIMUM
PER SYSTEM OF 46 TONS WITH 1 ZONE, WHILE THE PLANS SHOW 65.5
TONS IN RTU'S ALONE AND MANY ZONES, PLEASE CLARIFY.
· 4. SECTION 1002.4 FPC 01- PROVIDR TRAP PRIMERS ON ALL FLOOR
DRAINS.
,~.FIGURE 404.4.3(e) FPC 01- COMPLY WITH THIS SECTION, THE MINIMUM
WIDTH OF AN ACCESSIBLE TOILET STALL IN A TOILET ROOM IS 84.5",
WITH THE CENTER OF THE LAVATORY BEING 15"T TO CENTER FROM ^
SIDE WALL.
0
May 7, 2002
ABI Companies, Inc.
4301 Anchor Plaza Parkway
Tampa, FL 33634
Attn:
Re:
Mr. Robert Brikas
Newport Place Cafeteria Building
PEI Project No. 02053
City of Boynton Beach Plan Review Comment
Dear Bob,
Peninsula Engineering, Inc. has completed our review of the Plan Review Comments from the
City of Boynton Beach on the above referenced project. A number of their comments are the
result of the engineering design being based on the old building code and the plan review was
based on the new Florida Mechanical Code.
The following is listing of the city's comments and Peninsula Engineering's response.
BUILDING DIVISION
COMMENT NO. 1
Section 606.2.1 FMC 01 - Provide smoke detectors for all the A/C units.
RESPONSE
Duct smoke detectors have been provided in all new or replace air conditioning units
having a capacity greater than 2000 cfm or combination of A/C units serving a common
area having a combined capacity greater than 2000 cfm.
The drawings have been revised to locate the duct smoke detectors i.n the supply air duct
in lieu of the return air duct in accordance with FMCO1.
'~_,,..._¢_,,~t. Or , ,. ;;,,;,,;!...
SELECTED 1998 ENGINEERING FIRM OF THE YEAR BY FLORIDA ENGINEERING SOCIETY
2016 Alden Road Orlando, Florida 32803 407.246.1688 FAX 407.246.1664 ~' E-Mail pei@peifla.com
Mr. Robert Brikas May 7, 2002
COMMENT NO. 2 ~ 02 ' 1 80 0
Section 608.16.1 FPC 01 - Provide backflow protection at the beverage dispenser.
RESPONSE
The plumbing drawings have been revised to provide a double check type backflow
preventer in the water line to the beverage dispensers.
COMMENT NO. 3
Section 104.2 FMC 01 - The energy calculations show a maximum per system of 46 tons
with 1 zone, while the plans show 65.5 tons in RTU's alone and many zones, please
clarify.
RESPONSE
Per Daniel Young, (Peninsula Engineering, Inc.), phone conversation with Mr. Bill
Erskine (Plan Reviewer, City of Boynton Beach) the submitted Florida Energy Code was
to cover the 2na floor of the dining building. The tonnage for the 2~a floor is
approximately 46 tons as indicated on the energy code.
The A.C. and RTU schedule indicate all the A/C units for the project. The other
scheduled units are for direct replacement of defective units in the 1~t floor of the dining
building, administration building and the two residenance towers.
COMMENTS NO. 4
Section 1002.4 FPC 01 - Provide trap primers on all floor drains.
RESPONSE
Tap primers are being provided on all floor drains per Note No. 3 on Drawing P2.2.
COMMENT NO. 5
Figure 404.4.3(e) FPC 0 1 - Comply with this section, the minimum width of an
accessible toilet stall in a toilet room is 84.5", with the center of the lavatory being 15" to
center from a side wall. ~ - . ...............
Mr. Robert Brikas
02-1300
May 7, 2002
RESPONSE
Architect needs to vefi~y room and stall dimensions and fixture placement to comply with
FPC01.
FIRE RESCUE DEPARTMENT
COMMENT NO. 1
Will this work require any modifications or impairments to the fire sprinkler system? If
so, provide details.
RESPONSE
Yes, the sprinkler system will require modifications to accommodate the new layout of
the 2~d floor of the dining building. The sprinkler contractor to provide sprinkler layout
drawings as required.
COMMENT NO. 2
Provide ramp detail
RESPONSE
Architect needs to provide ramps details.
COMMENT NO. 3
Are cooking appliances located in the Hobby and Crax~s room used for any purpose that
would generate smoke or grease laden vapors?
RESPONSE
According to staff', the cooking appliances in the Hobby and CraRs room are used for
cra~s and to boil water, not cooking. Owner should veri~y usage.
02-1300
Mr. Robert Brikas
May 7, 2002
COMMENT NO. 4
Where an approved fire alarm system is installed in a building, HVAC duct detectors
shall be connected to the fire alarm system. They are not required to activate the building
evacuation alarm. NFPA 90A (1999) Section 4-4.4.2.
RESPONSE
The building does have a fire alarm system. The fire alarm contractor to provide
drawings and details to connect HVAC duct smoke detectors to the system.
COMMENT NO. 5
Smoke detectors for use in air distribution systems shall be located downstream of the air
filters and ahead of any branch connections in the air supply systems having a capacity
greater than 2000 cfm. (NFPA 90A, 1999, Section 4-4.2)
RESPONSE
The HVAC drawings have been revised to indicate location of duct smoke detectors in
the supply air duct from 3dC unit with having 2000 cfm or greater per NFPA 90A and
FMCO1.
COMMENT NO. 6
Reference Note #5 on dwg. MO.3, a hood exhaust fan(s) shall continue to operate after
the extinguishing system has been activated, unless fan shutdown is required by a listed
component of the ventilation system or by the design of the extinguishing system.
0NFPA 96, 1996, Section 5-2.3)
RESPONSE
Note No. 5 on drawing MO.3 has been revised to indicate hood exhaust fan to continue to
operate after extinguishing system activation. The hood's make-up air fan will shut down
upon extinguishing system activation.
Peninsula Engineering, Inc. has revised the mechanical and plumbing drawings to incorporate
City .........
the 's comments. , ~ , -~ : ; ~-
Mr. Robert Brikas May 7, 2002
02-1300
Please review the comments and drawings and let us know if you have any comments or require
additional information.
Sincerely,
Albert Marques, P.E.
Mechanical Engineer
Florida Registration #3 7313
BS:jnp
CITY OF BOYNTON BEACH
DEVELOPMENT DEPARTMENT
Be~)ch
100 East Boynton Blvd.
1, 00
P. O. Box31
Boynton Beach, Florida 33425-0310~-~i,
PLAN REVIEW COMMENTS
PLEASE NOTE THAT THE EFFICIENCY BY WHICH YOU RECEIVE YOUR PERMIT
DEPENDS ON YOUR RESPONSE TO THE CONTENTS OF THIS DOCUMENT. IT IS
RECOMMENDED THAT YOU CAREFULLY READ AND CORRECTLY RESPOND TO
ALL ASPECTS OF THIS DOCUMENT.
COMMENTS:
For permit application number / review: 02-1300 STRUCT 1ST REVIEW
Project Name or Address: NEWPORT PLACE
REVIEWED BY.'
Department and/or Division: Building Division
Name of Reviewer: Bob Donovan
Trade: Structual
Phone # (561) 742-6375 ext.
Fax # (561) 742-6357
Review Date: 4/19/02
Type of Review: STRUCT
COMMENT DISTRIBUTION:
Person identified on the application to receive comments:
Name ABI COMPANIES
Phone # (area code:561) 586-6455 ext.
Fax # (area code:561)
Date(s) reviewer called: ¢_.~.~_~_ ~ r,?~b_'' (,~
Person who received the call ~,J(_')~ ~_ ~ O,
THE FOLLOWING AREA SHALL BE FILLED-IN IN THE PRESENCE OF A BUILDING DIVISION
STAFF MEMBER:
COMMENTS/PLANS PICKED UP;
Comment(s) recd. by print name and date: _~_~'~¢~ OR
Plans/Comments recd. by print name and date:
~ Page 2. of 2
02-1 00
Plan Review Comments for Permit Application # 02-1300 STRUCT 1 ST REVIEW
Your permit application and supporting documentation do not comply with the City of
Boynton Beach Code of Ordinances. Prior to receiving a permit to construct or install
the requested improvements the plans and documents shall be amended to show
compliance with the below listed comments. For questions regarding my review please
contact me at the number listed above. If a conference is necessary, please schedule
an appointment. Phone calls and appointments are received and scheduled during
work days Monday through Friday 9:30 to 10:30 AM and 1:45 to 2:45 PM. Please note
that additional comments may be generated following staff review of the amended
plans. Timely approval of your project is dependent upon your prompt and correct
response to the information provided in this document.
1. AS PER SECTION 104.2 2001 FLORIDA BUILDING CODE NEED PRODUCT
APPROVAL SHEETS FOR THE NEW WINDOWS. ( NOTE MUST MEET IMPACT OR
NEED HURRICANE SHUTTERS.)
2. AS PER SECTION 104.2 2001 FLORIDA BUILDING CODE NEED
CONCONSTRUCTION DETAILS FOR NEW RAMP SHOWN ON PAGE A-1.0 OF
PLANS.
I I I
CITY OF BOYNTON BEACH
DEVELOPMENT DEPARTMENT
100 East Boynton Beach Blvd.
P. O. Box 310
Boynton Beach, Florida 33425-0310
02-1300
PLAN REVIEW COMMENTS
PLEASE NOTE THAT THE EFFICIENCY BY WHICH YOU RECEIVE YOUR PERMIT
DEPENDS ON YOUR RESPONSE TO THE CONTENTS OF THIS DOCUMENT. IT IS
RECOMMENDED THAT YOU CAREFULLY READ AND CORRECTLY RESPOND TO
ALL ASPECTS OF THIS DOCUMENT.
COMMENTS:
For permit application number / review: 02-1300 STRUCT 1 ST REVIEW
Project Name or Address: NEWPORT PLACE
REVIEWED BY:
Department and/or Division: Building Division
Name of Reviewer: Bob Donovan
Trade: Structual
Phone # (561) 742-6375 ext.
Fax # (56!) 742-6357
Review Date: 4/19/02
Type of Review: STRUCT
COMMENT DISTRIBUTION:
Person identified on the application to receive comments:
Name ABI COMPANIES
Phone # (area code:561) 586-6455 ext.
Fax # (area code:561 )
Date(s) reviewer called:
Person who received the call
THE FOLLOWING AREA SHALL BE FILLED-IN IN THE PRESENCE OF A BUILDING DIVISION
STAFF MEMBER:
COMMENTS/PLANS PICKED UP:
Comment(s) recd. by print name and date'
OR' --"
Plans/Comments recd. by print name and date:
Page 2 of 2
01'1800
Plan Review Comments for Permit Application # 02-1300 STRUGT ~ ST REVIEW
Your permit application and supporting documentation do not comply with the City of
Boynton Beach Code of Ordinances. Pdor to receiving a permit to construct or install
the requested improvements the plans and documents shall be amended to show
compliance with the below listed comments. For questions regarding my review please
contact me at the number listed above. If a conference is necessary, please schedule
an appointment. Phone calls and appointments are received and scheduled dudng
work days Monday through Fdday 9:30 to 10:30 AM and 1:45 to 2:45 PM. Please note
that additional comments may be generated following staff review of the amended
plans. Timely approval of your project is dependent upon your prompt and correct
response to the information provided in this document.
1. AS PER SECTION 104.2 2001 FLORIDA BUILDING CODE NEED PRODUCT
APPROVAL SHEETS FOR THE NEW WINDOWS. ( NOTE MUST MEET IMPACT OR
NEED HURRICANE SHUTTERS.)
2. AS PER SECTION 104.2 2001 FLORIDA BUILDING CODE NEED
CONCONSTRUCTION DETAILS FOR NEW RAMP SHOWN ON PAGE A-1.0 OF
PLANS.
PREPARED 5/21/02, 13:07:33
CITY OF BOYNTON BEACH
PAYMENTS DUE RECEIPT
PROGRAM BP820L
APPLICATION NUMBER: 02-00001300 4735 NW 7TH CT
FEE DESCRIPTION AMOUNT DUE
FIRE AND LIFE SAFETY FEES
BUILDING PERMIT
TOTAL DUE
273.47 x
1~8oo. oo 0 ~ - 1 ~ 0 0
17073 .47
Please present this receipt to the cashier with full payment.
Oper: H~YOD
Date: 5/22/82 ~
Total te~ered
Total 0a~ent
Receipt no: ~IB~
$17873.47
$17873.47
PREPARED 4/10/02, 11:23:25 PAYMENTS DUE RECEIPT
CITY OF BOYNTON BEACH PROGRAM BP820L
APPLICATION NUMBER: 02-00001300 4735 NW 7TH CT
FEE DESCRIPTION AMOUNT DUE
...........................................................................
PLAN CHECK FEE
7200.00
TOTAL DUE 7200.00
Please present this receipt to the cashier with full payment.
· Building
DEPARTlvENT OF DEVELOPlvlENT
PLANNING AND ZONING DIVlS ION
· Planning & Zoning · Occupational Licenses · Community Redevelopment
April 17, 2002
Mr. Tony Hudzik, Superintendent
ABI Companies, Inc.
4301 Anchor Plaza Parkway, Suite 400
Tampa, Florida 33634
Re:
Newport Place - Interior Renovations
MMSP 02-025
Dear Mr. Hudzik:
In response to your request for the administrative review and approval of the modifications proposed to
the above-referenced, approved site plan, please be informed that the changes as shown on the site plan
date stamped 04/04/02 are "minor", as defined within the Land Development Regulations, Chapter 4-
Site Plan Review.
This project provided 22 on-site parking spaces, including two (2) handicap accessible spaces. This
increase of four (4) units does not impact parking requirements as total parking requirements were met
as part of the original master plan approval. A parking surplus remains to offset this increase in
dwelling units.
This project may continue to be processed by the Building Division as a permit application. Be advised that
the proposed changes may require a modification to the building permit. Please contact me at (561) 742-
6260 if you have additional questions.
Sincerely,
Michael Rumpf
Planning and Zoning Director
Cc:
Lusia Galav, Principal Planner
Jose Alfaro, Planner
Maxime Ducoste-A., Planner
J:\SHRDATAXPlanning~SHARED\WI'\PROJECTS~,Newport Place\MMSP 02-025-Interior Renovations~Approval Letter. doe
City of Boynton Beach · 100 East Boynton Beach Blvd., P.O. Box 310 · Boynton Beach, Florida 33425-0310
Phone: (561) 742-6350 · www. ci.boynton-beach.fl.us
PREPARED 6/17/02, 13:19:46 PAYMENTS DUE RECEIPT
CITY OF BOYNTON BEACH PROGRAM BP820L
APPLICATION NUMBER: 02-00001300 4735 NW 7TH CT
FEE DESCRIPTION AMOUNT DUE
PLAN CHECK FEE
38.80
TOTAL DUE 38.80
02"1800
Please present this receipt to the cashier with full payment.
O~r: ALLEH~
Date: 6/18/~
Total tendered
Total oa¥eent
Receipt no: 289629
$38.88
$38.88
CITY OF BOYNTON BEACH
DEVELOPMENT DEPARTMENT
100 East Boynton Beach Blvd.
P.O. Box 310
Boynton l~ach, Flork~,, 334~10
__ I1! I I I II I ~ ~11 I ........... I I II !
02-1300
PLAN REVIEW COMMENTS
PLEASE NOTE THAT THE EFFICIENCY BY WHICH YOU RECEIVE YOUR PERMIT
DEPENDS ON YOUR RESPONSE TO THE CONTENTS OF THIS DOCUMENT. IT IS
RECOMMENDED THAT YOU CAREFULLY READ AND CORRECTLY RESPOND TO
ALL ,aSPECTS OF THIS DOCUMENT.
For permit application nurr~er t review:. 02-1300 REV. 1 1st REVIEW WE
Project Name or Address: ABI CO.
REVIEWED BY:
Review Date:
Type of Review:
COMMENT DISTRIBUTION:
Department and/or Division:
Narr,~ of Reviewer;. Bill Enddne
Trade: Mechank~d - Plumbing
Phone # (56t) 742'-67~5 ext. ....... .
Fax # (~1) ,~42..6a57
6t18/02
MECHANICAL
Building Dlvisb:m
Person identified on the application to receive, c~-nments:
Name ABI CO.
Fax # .(area c...o~:..60.1)
Date(s) reviewer called;
Person who receive(l the call
THE FOLLOWING AREA SHALL BE FILLED-IN IN THE PRESENCE OF A BUff. DING DIVISION
STAFF MEMBER:
Comment(s) recd. by print name and date:
OR ~ d-./ ....
Plans/Comments rec~l, by print name and date: .....
RECEIVED
JUN 2 8 2002
BUILDING DIVISION
CORRECTED
Palle 2 of 2
Review C(,,a,,,~t, f~ ~ Applica~ioa # 02-1300 REV. 1 I ST REVIEW WE
02- 30 0
Your permit application and supporting documentation do not comply with the City of
aoynton Beach Code of Ordinances. Prior to receiving a permit to construct or install
the requested improvements the plans and documents shall be amended to show
compliance with the below listed comments: For questions regarding my review please
contact me at the number listed above. If a conference is necessa~j, please schedule
an appointment. Phone calls and appointments are received and scheduled during
work days Monday through Friday 9:30 to t0:30 AM and 1:45 to 2:45 PM. Please note
that additional comments may be generated following staff review of the amended
plans. Timely approval of your project is dependent upon your prompt and correct
response to the information provided in this dormant.
SECTION 606.2.2 FMC 01-PROVIDE SMOKE DETECTORS FOR RTU-~, OR
FIRE DAMPERS WHERE THE SUPPLY AND RETURN DUCTS CROSSES
THE EGRESS HALL, AS THIS UNIT IS LINKED TO RTU-19, RTU-8, AND
RTU-7.
RECEIVED
JUN 2 8 2002
BUILDING DIVISION
CORRECTED
CITY OF BOYNTON BEACH
DEVELOPI~NT DEPARTMEHT
~00 East Boynton Beech Blvd.
P. O. Box 310 .T
Boynton Beach. Florida 33425-0310
02-1300
PLAN REVIEW COMMENTS
PLEASE NOTE THAT THE EFFICIENCY BY WHICH YOU RECEIVE YOUR PERMIT
DEPENDS ON YOUR RESPONSE TO THE CONTENTS OF THIS DOCUMENT. IT IS
RECOMMENDED THAT YOU CAREFULLY READ AND CORRECTLY RESPOND TO
ALL ASPECTS OF THIS DOCUMENT.
For permil application number I review:. 02-1300 REV. 1 1ST R_EV~ VVE
Project Name or Address: AB! CO.
REVIEWED BY:
Depa~ and/or Division:
Name of Reviewer;. .B,.ill Enddne
Trade: Mm;hank=al .. Plumbing
Phone # (56't) 742.67SS ext. ~
Fax# ~ (se'i) 742.;3s7
Review Date: 6/18/02
Type of Review: MECHANICAL
COMMENT DISTRIBUTION:
Person identified on the applicalion to receive, comments:
Name ABI CO.
Fax # (area cod, ~.~l) ,,
Date(s) reviewer called;
Person who received the call
' THE FOLLOWING AREA SHALL BE: FILLED-IN IN THE PREsENcE OF .~ BUILDING DIVISION
STAFF MEMBER:
COMMENTS/PLANS PICKED UP: ~~~_~
Comment(s) recd. by print name and date:
OR
Plans/Comments recd. by print name and date: ,,
RECEIVED
JUN 2 8 2002
~FILE cOPYe
~UILDING D~VIS~ON
CORR£C'T£O
CITY OF BOYNTON BEACH
DEVELOPMENT DEPARTMENT
100 East Boynton Beach Blvd.
P. O. Box 310
Boynton Beach, Florida 33425-0310
- 02
FILE
PLAN REVIEW COMMENTS
PLEASE NOTE THAT THE EFFICIENCY BY WHICH YOU RECEIVE YOUR PERMIT
DEPENDS ON YOUR RESPONSE TO THE CONTENTS OF THIS DOCUMENT. IT IS
RECOMMENDED THAT YOU CAREFULLY READ AND CORRECTLY RESPOND TO
ALL ASPECTS OF THIS DOCUMENT.
COMMENTS:
For permit application number / review: 02-1300 REV. 1 1ST REVIEW WE
Project Name or Address: ABI CO.
REVIEWED BY:
Trade:
Phone #
Fax #
Review Date:
Type of Review:
Department and/or Division:
Name of Reviewer: Bill Erskine
Mechanical - Plumbing
(56'1) 742-6755 ext.
(56'1) 742-6357
6/18/02
MECHANICAL
Building Division
COMMENT DISTRIBUTION:
Person identified on the application to receive comments:
Name ABI CO.
Phone # (area code:561) 547-9886 ext.
Fax# (area code:561) ~--~'-'~
Date(s) reviewer called: ~' ~---I~ '~;l(~ '
Person who received the call -'"~--(~'~('-1
~J
THE FOLLOWING AREA SHALL BE FILLED-IN IN THE PRESENCE
STAFF MEMBER:
COMMENTS/PLANS PICKED UP:
Comment(s) recd. by print name and date:
OR
Plans/Comments recd. by print name and date:
OF A BUILDING DIVISION
Page 2 of 2 Plan Review Comments for Permit Application # 02-1300 REV. 1 1 ST REVIEW WE
'
Your permit application and supportin9 documentation do not comply with the
Boynton Beach Code of Ordinances. Prior to receiving a permit to construct or install
the requested improvements the plans and documents shall be amended to show
compliance with the below listed comments. For questions regarding my review please
contact me at the number listed above. If a conference is necessary, please schedule
an appointment. Phone calls and appointments are received and scheduled during
work days Monday throu§h Friday 9:30 to 10:30 AM and 1:45 to 2:45 PM. Please note
that additional comments may be generated following staff review of the amended
plans. Timely approval of your project is dependent upon your prompt and correct
response to the information provided in this document.
SECTION 606.2.2 FMC 01-PROVIDE SMOKE DETECTORS FOR RTU-8, OR
FIRE DAMPERS WHERE THE SUPPLY AND RETURN DUCTS CROSSES
THE EGRESS HALL, AS THIS UNIT IS LINKED TO RTU-19, RTU-6, AND
RTUo7.
2
CITY OF BOYNTON BEACH
DEVELOPMENT DEPARTMENT
100 East Boynton Beach Blvd.
P. O. Box 310
Boynton Beach, Florida 33425-0310
02-1300
PLAN REVIEW COMMENTS
PLEASE NOTE THAT THE EFFICIENCY BY WHICH YOU RECEIVE YOUR PERMIT
DEPENDS ON YOUR RESPONSE TO THE CONTENTS OF THIS DOCUMENT. IT IS
RECOMMENDED THAT YOU CAREFULLY READ AND CORRECTLY RESPOND TO
ALL ASPECTS OF THIS DOCUMENT.
COMMENTS:
For permit application number / review: 02-1300 REV. 1 1sT REVIEW WE
Project Name or Address: ABI CO.
REVIEWED BY:
Department and/or Division: Building Division
Name of Reviewer: Bill Erskine
Trade: Mechanical - Plumbing
Phone # (561) 742-6755 ext.
Fax # (561) 742-6357
Review Date: 6/18/02
Type of Review: MECHANICAL
COMMENT DISTRIBUTION:
Person identified on the application to receive comments:
Name ABI CO.
Phone # (area code:561) 547-9886 ext.
Fax # (area code:561)
Date(s) reviewer called:
Person who received the call
THE FOLLOWING AREA SHALL BE FILLED-IN IN THE PRESENCE OF A BUILDING DIVISION
STAFF MEMBER:
COMMENTS/PLANS PICKED UP:
Comment(s) recd. by print name and date:
OR
Plans/Comments recd. by print name and date:
Page 2 of 2
02'1300
Plan Review Comments for Permit Application # 02-1300 REV. 1 1 ST REVIEW WE
Your permit application and supporting documentation do not comply with the City of
Boynton Beach Code of Ordinances. Prior to receiving a permit to construct or install
the requested improvements the plans and documents shall be amended to show
compliance with the below listed comments. For questions regarding my review please
contact me at the number listed above. If a conference is necessary, please schedule
an appointment. Phone calls and appointments are received and scheduled during
work days Monday through Friday 9:30 to 10:30 AM and 1:45 to 2:45 PM. Please note
that additional comments may be generated following staff review of the amended
plans. Timely approval of your project is dependent upon your prompt and correct
response to the information provided in this document.
SECTION 606.2.2 FMC 01-PROVIDE SMOKE DETECTORS FOR RTU-8, OR
FIRE DAMPERS WHERE THE SUPPLY AND RETURN DUCTS CROSSES
THE EGRESS HALL, AS THIS UNIT IS LINKED TO RTU-19, RTU-6, AND
RTU-7.
TIME
N~ME
FAX
TEL
02-1 00
86/24/2882 14:0S
CITY OF BOYNTON BLDG
§617426S57
DATE,TIME
FAX NO./NAME
DURATION
PAGE(S)
RESULT
MODE
08:00:44
0S
OK
STANDARD
EOM
Building Division
FACSIMILE
02-1300
CITY OF BOYNTON BEACH
Department of Development
City Hail, West Wing
100 E. Boynton Beach Blvd.
P.O. Box 310
Boynton Beach, Florida 33425
(561) 742-6350
(561) 742-6357 Fax
TO:
FROM:
DATE:
NUMBER OF PAGES: (Including cover)
If you receive this fax in error, or experience trouble with transmission, please notify our office
immediately, at (561) 742-6350. Thank you.
06/24/2002 14:02 5617426357 CITY OF ~3VNTON 8LDG PAGE 02
CITY OF BOYNTON BEACH
DEVELOPMENT DEPARTMENT
100 East Boynton I~each g~.
p, o. Box 3~ 0
B F~oriCa 33425.0310
oynton IBeac~,. ,,,' ,~ ..... ,,,.
02-1300
PLAN REVIEW COMMENTS
PLEASE NOTE THAT THE EFFICIENCY I~Y WHICH YOU RECEIVE YOUR PERMIT
DEPENDS ON YOUR RESPONSE TO THE CONTENTS OF THiS DOCUMENT. IT IS
RECOMMENDED THAT YOU CAREFULLY RE. AD AN[:) CORRECTLY RESPOND TO
ALL ASPECTS OF THIS DOCUMENT.
COMMENTS:
For permit aCplication number / review;
Project Name or Address: ABI CO,
REVIEWED BY:
Department and/or Division: Building Dlviston
Name of Reviewer: Bill Emkine
Trade: Mechanical - Plumbing
Fax ~ (561} 742-6357
Review Date: 6/18/02
Ty~e of Rewew; MECHANICAL
COMMENT DISTRIBUTION:
Person identified on ~e applic~on to receive, comments:
Name ABI CO,
Phone # _.(area.code_;_5_6..1_}.547-9886 ext.
Fax # _(ar_e_a code:5~. 1
Date(s) revlewor called:
Pemon who receive<3 the call
"THE FOLLOWING AREA SHALL BE FILLED-IN IN THE PRESENCE OF A BUILDING DIVISION
02-1300 REV. 1 Isr REVIE'W WE
STAFF MEMBER:
COMMENTS/PLANS PICKED UP: /'7'?~,-vv' /--/'u,'/,;~//~- .
OR
Plans/Comments recd. by print name and date:
I'd [qEtS-L~,g-Igg zen:~.[apoa R,~e9 d/..O:E~O ~O t,E unc
DEPARTMENT OF DEVELOPMENT
BUILDING DIVISION
MEMORANDUM NO. 02-287
SCANNED
TO: Diane Reese, Finance Director
DEC 2 7 ZOO2
FROM: Don Johnson, Building Official BUILDING DIVISION
DATE: December 11, 2002
RE: RETURN OF CASH BOND - NEWPORT PLACE - 4735 N.W. 7Tu COURT
On October 14, 2002, we sent you a memo (copy attached) regarding a cash bond of $6,600.00 for the
completion of the permitted work at the above address. The work has been completed and the final Certificate
of Occupancy has been issued. Therefore, please return the bond to ABI Companies, Inc. Attached are a
Direct Payment Requisition and an Agenda Item Request form.
DJ:rs
Attachments
XC: Timothy K. Large, Building Code Administrator
Permit File # 02-1300
S:'ff)evelopment',BUILDING'~Building Div',DocumentsLMemos in Word\Cash Bonds - 2002hRetum Cash Bond - Newport Place 02-1300.doc
DIRECT PAYMENT REQUISITION
PLEASE RETURN CHECK TO RUTH IN THE BUILDING DIV.
Please issue a check in the amount of $
To:
ABI Companies, Inc.
6,600.00
SCANNED
BUILDINg, r'}l'tzm rrv,,~
4301 Anchor Plaza Parkway, Suite 400
Tampa, FL 33634
For: Return of cash bond for the completion of permitted work at Newport Place located at
4735 N.W. 7tn Court.
Requested by
Department of Development
Date December 12, 2002
Approvals:
Section Admin. &~~
'E~on John~.~ '
Finance Dept.
City Manager
001 0000 220 99 00 6,600.0C
6,600.00
rs
Attachments\Memo # 02-229, 02-287 and Agenda Item Request Form
XC: Permit File # 02-1300
S:\Development\BUILDING~Building Div\Documents\121 Forms\Cash Bond Return-NeVl0ort Place.doc
Requested City Commission
Meetimz Dates
[] December 3, 2002
[] December 17, 2002
[] January 7, 2003
[] January 21, 2003
CITY OF BOYNTON BEACH
AGENDA ITEM REQUEST FORM
Date Final Form Must be Turned
in to (;ity Clerk's Office
November 18, 2002 (Noon)
December 2, 2002 (Noon)
December 16, 2002 (Noon)
January 6, 2003 (Noon.)
Requested City Commission
Meetinc, Dates
[] February 4, 2003
[] February 18, 2003
[] March 4, 2003
[] March 18,. 2003
SCANNED
7 200
BUILDING DIVISION
Date Final Form Must be Turned
in to CiW Clerk's Office
January 21, 2003 (Noon)
February 3, 2003 ~qoon)
February I8, 2003 (Noon)
March 3, 2003 (Noon)
NATIYRE OF
AGENDA ITEM
[] Adminis~xative [] Development Plans
[] Consent Agenda [] New Business
[] Public Hearing [] Legal
[] Bids [] Unfinished Business
[] Announcement [] Presentation
[] City Manager's Report
RECOMMENDATION:
Resolution authorizing the release of a cash bond of $6,600.00 to ABI Companies, Inc. for the project known as Newport
Place.
EXPLANATION:
On October 14, 2002, the Building Division sent to thc Finance Department a cash bond of $6,600.00 for the completion of
the permitted work. at Newport Place (4735 N.W. 7z Court). The work has been completed and the Certificate of Occupancy
has been issued.
PROGRAM IMPACT: None
FISCAL IMPACT: None
ALTERNATIVE/~None
· Quin~l~.'Or~l~n~, I~e-v~lo~-ment Director City Manager's Signature
Development Department
Depaxtanent Name
City Attorney / Finance / Human Resources
S:~BULLETrNkFORMSkAGENDA ITEM REQUEST FORM.DOC
11/25/2882 18:14 8132896628
I~~-~:" ", ..
,....~, Providing Construction $olutlor~
-,
November 25, 200:2
P~GE 82/82
BUILDING DIVISION
City of Boynton Beach Planning & Development
100 E. Boynton Beach Blvd.
Boyaton Beach, FL 33435
RE: PERI, gIT #02-1300 CO
To Whom It May Concern:
Thc final inspections for permit #02-1300 were completed and approved on 11/13/02 by
City Inspirers. Ou,r office was notified that the Certificate of Completion was issued
November 14, 2002.
As all work has been completed and signed off, ABI Companies is requesting thc retmxi
o£ th.eir Surety Check in thc amount of $6,000.00 given to the City o f Boynton Beach·
Planning & Development on October 11,2002 for the issuance of a Temporary
Certificate of Completion.
If you have any questions I can be reached at 813-289-8808.
Sr. Project Manager
KB/ar
cc: Jeff Herndon, Vice President
ABI Cornpan~t, Inc.
p '
4301 Anchor laza Parkway, Suite 400, Tarrca, Florida 33634
T~Jepha~, ...' 813.289,8808 * Fox: 8T3,289.6628
www. abiin¢.~m · abirnaiJ@ab~inc.com
EXHIBIT "A"
TO:
FROM:
DATE:
SUBJ'ECT:
DEPARTMENT OF DEVELOPMENT
BUILDING DIVISION
MEMORANDUM NO. 02-229
Diane Reese, Finance Director
Don Johnson, Building Official ~F
October 14, 2002
CASH BOND - NE~,VPORT PLACE - 4735 N.}V. 7TM COURT
SCANNED
BUILDING DIVISION
Attached is a cashier's check for 56,600.00 from ABI Companies, Inc. This is a cash surety for Newport
'Place and is to be held until ali outstanding issues of their temporary Certificate of Occupancy are
completed. This should occur within 30 days. ..
Upon completion of the deficiencies'of the permit and the issuance of the final Certificate of Occupancy,
the surety will be returned.
DJ':rs
Attachments/letter from William H.'Booth m' and check
XC:
Timothy K. Large, Building Code Administrator
Permit File # 02-1300
S:\Development~SUILDING~guiid£ng Div~DocumentshMcmos in Word, Cash Bonds - 2002\Cash Bond - Newport Place. doc.
EXHIBIT "B"
SCANNED.
Bankofg.'i.', .. ,ca. ~- Cashier's' Chee¢UILDING DIVISION:':-"-':-'-' ..... '""-"':-2'~'~"L~"--i ....
- " No. 2363728
: ,..' ~,~
'"
=
The
/
.' · · '
.
I
CITY OF BOYNTON BEACH
Boynton Beach, Florida
"25352
2o~.~..
DOLLARS
EXHIBIT "C"
EXHIBIT "D"