HomeMy WebLinkAboutEnlarged Refrigeration Electrical Plan - RE1.1J J
J
J
J
J J J J
JJJ
J J J
J
KE2-RE2-40(BS08 GLY)KE2-RE2-40(BS09 GLY)J
J
J
J
J
J J
J J
JJ
J
CF
J
CF
C
J
J
J
2
BASR3.2
1 2 3 4 5
C
D
E
BS05a GLY BS05b GLY BS05c GLY BS06a GLY BS06b GLY
BS01a GLY BS01b GLY BS01c GLY BS02a GLY BS02b GLY
BS03a GLY BS03b GLY BS03c GLY BS04a GLY BS04b GLY
BS04c GLYBS07a GLYBS07b GLYBS20 GLYBS19b GLYBS19a GLY
BS18 GLY BS17 GLYBS08 GLY
BS09 GLYCU5a TCO2 CU5b TCO2 CU5c TCO2CU5d TCO2L2D3-81
CHB2-33
L2D1-81COORDINATE BOSS
GATEWAY RECEPTACLE
LOCATION WITH
REFRIGERATION BAS
INSTALLER
CHB2-27
CHB2-25 16.145
16.145
CHB1-14
CHB1-12 16.145
16.145
CHA2-25
CHA2-23 16.145
16.145
CHA2-35
CHA2-33 16.145
16.145
CHA2-14 16.145
CHA2-19
CHA2-17 16.145
16.145
SPARE OUT EXISTING CIRCUIT
CHA2-21 SINCE NEW CASE DOES
NOT HAVE ANTI-SWEAT
CHB2-11
CHB2-9 16.145
16.145 CHB2-15
CHB2-13 16.145
16.145
CHB2-3
CHB2-1 16.145
16.145 CHB2-7
CHB2-5 16.145
16.145
CHB2-21
CHB2-23 16.145
16.145CHB2-17
CHB2-19 16.145
16.145
16.710
2
RE1.3TYP
16.711
TYP
3
RE1.3TYP
3
RE1.3 TYP
3
RE1.3 TYP
4
RE1.3TYP
CHB2-29
CHB2-31
L2D1-79CIRCUIT FOR DEVICES ON NEW
BAS BACKBOARD IN EDC2
22 (CF)
22 (CF)
WP, WR, GFCI CONVENIENCE
RECEPTACLE FOR GLYCOL AND
TCO2 CHARGING STATION.
1 2
G
H
BS14a GLYBS14b GLYBS14 GLYCHB2-16
CHB2-14 16.145
16.145
5
RE1.3
TYP
3
RE1.3
2
RE1.3
SHEET:
DRAWN BY:
CHECKED BY:
PROTO CYCLE:
DOCUMENT DATE:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.P (407) 661-9100F (407) 661-9101c-p.comFlorida Corporate Certificate #AA C0005262600 Maitland Center ParkwaySuite #200Maitland, FL 32751CUSHING TERRELL306 W. RAIL ROAD SUITE 104MISSOULA, MT 59802Phone: (406)728-9522Fax: (406)728-8287EXISTING CONDITIONS WERE TAKEN FROM
ORIGINAL DRAWINGS AND MAY NOT REFLECT
EXACT "AS-BUILT" CONDITIONS. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS
PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR
SHALL CAREFULLY COORDINATE NEW WORK AND
DEMOLITION WITH ALL OTHER DISCIPLINES AND
EXISTING CONDITIONS.
EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING
A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND
SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE
TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES
NOT RELIEVE THE RESPONSIBILITY OF PERFORMING
THE WORK PROPERLY. NO ADDITIONAL
COMPENSATION SHALL BE ALLOWED BECAUSE OF
CONDITIONS THAT OCCUR DUE TO FAILURE TO
FAMILIARIZE WORKERS WITH THIS KNOWLEDGE.
DOCUMENTS WITHOUT
SIGNATURE AND REQUIRED
SEAL OF AOR/EOR ARE NOT
FOR CONSTRUCTION
RE1.1
ENLARGED
REFRIGERATION
ELECTRICAL
PLANS
DM20240347BOYNTON BEACH, FL11/07/2511/07/25STORE NO: 5911-2769006/27/25BOYNTON BEACH, FLSP3625 S FEDERAL HWY.1. COORDINATE ALL WORK WITH REFRIGERATION
CONTRACTOR (R.C.) PRIOR TO INSTALLATION.
2. REFRIGERATED CASES: E.C. SHALL PROVIDE CONDUIT
AND WIRE FOR REFRIGERATED CASE FANS, LIGHTS
AND ANTI-SWEAT HEATERS, AND (IF APPLICABLE)
ELECTRICAL DEFROST. PROVIDE ADEQUATE
CONDUCTOR LENGTH TO ALLOW TERMINATION.
NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND
LABEL EACH CIRCUIT WITH BRANCH CIRCUIT
DESIGNATION AND REFRIGERATION SYSTEM NUMBER
FOR FINAL TERMINATION AT CASE BY R.C. REF CASE
CONNECTION WIRING DETAIL.
3. IF NEW CASES ARE PROVIDED WITH A FACTORY
INSTALLED TERMINAL STRIP AND JUMPERS FOR
CONNECTION TO A SINGLE CIRCUIT FOR 120V CASE
LOADS. RC SHALL REMOVE FACTORY INSTALLED
JUMPERS AS REQUIRED TO UTILIZE EXISTING
SEPARATE 120V FAN/LIGHT/ANTI-SWEAT CIRCUITS AS
INDICATED ON PLANS AND/OR PANELBOARD
SCHEDULES. ANY EXISTING ANTI-SWEAT CONTROL
(SWEATMISER) SHALL BE BY-PASSED. CASES UTILIZING
ELECTRICAL DEFROST WILL BE PROVIDED WITH
SEPARATE 208V TERMINATIONS AT THE TERMINAL
STRIP FOR CONNECTION TO THE 208V ELECTRIC
DEFROST CIRCUIT. RC SHALL MAKE FINAL
TERMINATIONS OF 120V AND 208V POWER CIRCUIT(S)
AT CASE TERMINAL STRIP. REFER TO CASE
CONNECTION SCHEMATIC ON REFRIGERATION
SHEETS.
4. WALK-IN UNITS: PROVIDE CONDUIT AND WIRE FOR
EVAPORATOR COIL FANS (CF) AND (IF APPLICABLE)
ELECTRIC DEFROST (ED). PROVIDE ADEQUATE
CONDUCTOR LENGTH TO ALLOW TERMINATION.
NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND
LABEL EACH CIRCUIT WITH BRANCH CIRCUIT
DESIGNATION AND REFRIGERATION SYSTEM NUMBER
FOR FINAL TERMINATION AT COIL BY R.C. REF
EVAPORATOR COIL WIRING DETAIL.
5. ROUTE REFRIGERATED CASE AND WALK-IN UNIT COIL
FAN, LIGHTS, ANTI-SWEAT AND DEFROST BRANCH
CIRCUITS TO WIREWAYS PROVIDED AT
REFRIGERATION EQUIPMENT AND/OR PANELBOARDS
AS REQUIRED.
6. REFRIGERATED CASE WIRING COMPARTMENT
REPRESENTED ON DRAWING BY JUNCTION BOX.
7. KEEP PENETRATIONS THROUGH WALK-IN UNITS
TO A MINIMUM. ROUTE ALL CONDUITS SERVING
FREEZERS AND COOLERS ON INSIDE OF BOX.
8. ALL CONDUITS INSTALLED ON TOP OF WALK-IN UNITS
SHALL BE A MINIMUM OF 6" FROM ANY EDGE TO ALLOW
SPACE FOR EDGE PROTECTION NETTING. DO NOT
ROUTE CONDUITS ABOVE THE CEILING GRID ACCESS
UNLESS CONDUITS ARE INSTALLED IN JOIST SPACE,
REF ARCH.
9. UNDERSLAB CIRCUITS SHALL NOT BE ROUTED UNDER
WALK-IN FREEZERS AND SHALL BE ROUTED ABOVE
REFRIGERANT LINES WHERE THEY CROSS.
10. CIRCUITS FOR REFRIGERATED CASES SERVED BY
UNDERSLAB REFRIGERATION PIPING ARE TO BE
ROUTED UNDERSLAB AND EXTENDED TO THE FIRST
CASE IN EACH SYSTEM. WIRING AND CONDUIT FOR
SLAVE WIRING BETWEEN CASES SHALL BE PROVIDED
BY R.C. REFER TO UNDERSLAB CASE CONNECTION
WIRING DETAIL.
11. ALL UNDERSLAB CONDUITS SHALL BE 3/4" MIN.
12. CIRCUITS FOR REFRIGERATED CASES SERVED BY
OVERHEAD REFRIGERATION PIPING ARE TO BE
ROUTED DOWN FROM STRUCTURE AT THE SAME
LOCATION AS THE REFRIGERATION PIPING AND
EXTENDED TO THE FIRST CASE IN EACH SYSTEM. WIRE
AND CONDUIT FOR SLAVE WIRING BETWEEN CASES
SHALL BE PROVIDED BY THE R.C. REFER TO
OVERHEAD CASE CONNECTION WIRING DETAIL.
13. ON GROUPS OF THREE OR MORE REFRIGERATED
CASES WITH ELECTRIC DEFROST, R.C. SHALL
CONNECT CASES TO CREATE A THREE-PHASE HEATER
CIRCUIT. HEATER LOADS SHALL BE BALANCED
BETWEEN PHASES AS EVENLY AS POSSIBLE. REF
CASE DEFROST WIRING DETAIL.
14. PROVIDE A SEPARATE NEUTRAL FOR EACH NEW
BRANCH CIRCUIT SERVING REFRIGERATED CASES OR
WALK-IN UNITS.
15. PROVIDE CIRCUIT BREAKER LOCKING DEVICE (LOCK-
OFF FOR MAINTENANCE) ON NEW AND/OR EXISTING
CIRCUIT BREAKERS SERVING REFRIGERATED CASES.
16. REFERENCE ARCHITECTURAL DEMOLITION PLANS FOR
FULL EXTENT OF DEMOLITION WORK REQUIRED.
GENERAL REFRIGERATION
ELECTRICAL NOTES
08.28.20
1/8" = 1'-0"1 FRONT REFRIGERATION ELECTRICAL PLAN (NOVAR)
KEYNOTES
16.145 CONNECT CIRCUIT(S) TO EXISTING BRANCH CIRCUITRY.
MINIMUM WIRE SIZE AND PANELBOARD CIRCUIT ARE
NOTED. VERIFY SIZE, RATING AND CONDITION OF
EXISTING BRANCH CIRCUIT CONDUIT AND WIRE PRIOR
TO USE TO ENSURE THAT THEY MEET REQUIRED SIZE,
AND ALL U.L. RATINGS AND REPLACE AS REQUIRED.
16.710 BUILDING AUTOMATION CONDUITS: PROVIDE 1" (UNLESS
NOTED OTHERWISE) CONDUIT (WITH PULL WIRE)
ROUTED FROM 6" ABOVE BOTTOM OF BAR JOIST IN
SALES FLOOR ACCESSIBLE CEILING SPACE THROUGH
PVC CHASE.
16.711 POINT OF TRANSITION FROM EMT TO FLEX. PROVIDE
CONDUIT AND BRANCH CIRCUITS FOR REFRIGERATED
CASE FANS, LIGHTS, ANTI-SWEAT HEATERS, AND
ELECTRICAL DEFROST (IF REQUIRED). TERMINATION TO
REFRIGERATED CASE ELECTRICAL CONNECTION POINT
BY R.C. REFER TO CASE CONNECTION WIRING DETAIL.
1/8" = 1'-0"3 REAR REFRIGERATION ELECTRICAL PLAN (NOVAR)
FEEDER OR GROUND SIZE
ALL CONDUIT AND CONDUCTOR SIZES ARE BASED ON EMT WITH 40%
FILL, 75ºC RATED TERMINATIONS AND TYPE THHN/THWN-2 INSULATION.
FOR NON-EMT CONDUIT OR TERMINATIONS OR INSULATION TYPES
RATED LESS THAN 75ºC, MODIFY SIZES ACCORDING TO NEC.
FEEDER SCHEDULE
22 (2)#12, (1)#12 G, 1/2" C
ISSUE BLOCKVOID