4 5
D L2B-32,34,36NEW
CU5 TCO2
PROVIDE 3/4"C FROM LOW VOLTAGE
WIRING COMPARTMENT TO ACCESSIBLE
INTERIOR JOIST SPACE AND TERMINATE
WITH BUSHING. (TYP)WR,WP 100A/3/NF,
NEMA 3R
MOUNT TO FRAMING OR NON-
REMOVABLE ACCESS PANEL
TO NEAREST RTU MAINTENANCE
RECEPTACLE CIRCUIT 16.250103
2 3
F
NEW
DTB GLY H1A-25,27,2916.250
16.258
EXISTING ROOF MOUNTED SPLIT
SUCTION HYBRID HOUSES
ETR
DTA DX
ETR
DTB DX
1
RE1.3
ROOF
PENETRATIONBAS CONTROL
TRANSFORMER INSTALLED
INSIDE PUMP SKID
ELECTRICAL CABINET BY
BASR CONTRACTOR.
FACTORY
INSTALLED,
WP/WR, GFCI
RCPT.
PANELS CHA1 AND
CHA2 STACKED
PANELS CHB1 AND
CHB2 STACKED
33
SHEET:
DRAWN BY:
CHECKED BY:
PROTO CYCLE:
DOCUMENT DATE:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.P (407) 661-9100F (407) 661-9101c-p.comFlorida Corporate Certificate #AA C0005262600 Maitland Center ParkwaySuite #200Maitland, FL 32751CUSHING TERRELL306 W. RAIL ROAD SUITE 104MISSOULA, MT 59802Phone: (406)728-9522Fax: (406)728-8287EXISTING CONDITIONS WERE TAKEN FROM
ORIGINAL DRAWINGS AND MAY NOT REFLECT
EXACT "AS-BUILT" CONDITIONS. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS
PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR
SHALL CAREFULLY COORDINATE NEW WORK AND
DEMOLITION WITH ALL OTHER DISCIPLINES AND
EXISTING CONDITIONS.
EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING
A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND
SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE
TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES
NOT RELIEVE THE RESPONSIBILITY OF PERFORMING
THE WORK PROPERLY. NO ADDITIONAL
COMPENSATION SHALL BE ALLOWED BECAUSE OF
CONDITIONS THAT OCCUR DUE TO FAILURE TO
FAMILIARIZE WORKERS WITH THIS KNOWLEDGE.
DOCUMENTS WITHOUT
SIGNATURE AND REQUIRED
SEAL OF AOR/EOR ARE NOT
FOR CONSTRUCTION
RE1.2
ENLARGED
REFRIGERATION
ELECTRICAL
PLANS
DM20240347BOYNTON BEACH, FL11/07/2511/07/25STORE NO: 5911-2769006/27/25BOYNTON BEACH, FLSP3625 S FEDERAL HWY.1/8" = 1'-0"1 REFRIGERATION ELECTRICAL ROOF PLAN (FRONT)
1/8" = 1'-0"2 REFRIGERATION ELECTRICAL ROOF PLAN (REAR)
1. COORDINATE ALL WORK WITH REFRIGERATION
CONTRACTOR (R.C.) PRIOR TO INSTALLATION.
2. REFRIGERATED CASES: E.C. SHALL PROVIDE CONDUIT
AND WIRE FOR REFRIGERATED CASE FANS, LIGHTS
AND ANTI-SWEAT HEATERS, AND (IF APPLICABLE)
ELECTRICAL DEFROST. PROVIDE ADEQUATE
CONDUCTOR LENGTH TO ALLOW TERMINATION.
NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND
LABEL EACH CIRCUIT WITH BRANCH CIRCUIT
DESIGNATION AND REFRIGERATION SYSTEM NUMBER
FOR FINAL TERMINATION AT CASE BY R.C. REF CASE
CONNECTION WIRING DETAIL.
3. IF NEW CASES ARE PROVIDED WITH A FACTORY
INSTALLED TERMINAL STRIP AND JUMPERS FOR
CONNECTION TO A SINGLE CIRCUIT FOR 120V CASE
LOADS. RC SHALL REMOVE FACTORY INSTALLED
JUMPERS AS REQUIRED TO UTILIZE EXISTING
SEPARATE 120V FAN/LIGHT/ANTI-SWEAT CIRCUITS AS
INDICATED ON PLANS AND/OR PANELBOARD
SCHEDULES. ANY EXISTING ANTI-SWEAT CONTROL
(SWEATMISER) SHALL BE BY-PASSED. CASES UTILIZING
ELECTRICAL DEFROST WILL BE PROVIDED WITH
SEPARATE 208V TERMINATIONS AT THE TERMINAL
STRIP FOR CONNECTION TO THE 208V ELECTRIC
DEFROST CIRCUIT. RC SHALL MAKE FINAL
TERMINATIONS OF 120V AND 208V POWER CIRCUIT(S)
AT CASE TERMINAL STRIP. REFER TO CASE
CONNECTION SCHEMATIC ON REFRIGERATION
SHEETS.
4. WALK-IN UNITS: PROVIDE CONDUIT AND WIRE FOR
EVAPORATOR COIL FANS (CF) AND (IF APPLICABLE)
ELECTRIC DEFROST (ED). PROVIDE ADEQUATE
CONDUCTOR LENGTH TO ALLOW TERMINATION.
NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND
LABEL EACH CIRCUIT WITH BRANCH CIRCUIT
DESIGNATION AND REFRIGERATION SYSTEM NUMBER
FOR FINAL TERMINATION AT COIL BY R.C. REF
EVAPORATOR COIL WIRING DETAIL.
5. ROUTE REFRIGERATED CASE AND WALK-IN UNIT COIL
FAN, LIGHTS, ANTI-SWEAT AND DEFROST BRANCH
CIRCUITS TO WIREWAYS PROVIDED AT
REFRIGERATION EQUIPMENT AND/OR PANELBOARDS
AS REQUIRED.
6. REFRIGERATED CASE WIRING COMPARTMENT
REPRESENTED ON DRAWING BY JUNCTION BOX.
7. KEEP PENETRATIONS THROUGH WALK-IN UNITS
TO A MINIMUM. ROUTE ALL CONDUITS SERVING
FREEZERS AND COOLERS ON INSIDE OF BOX.
8. ALL CONDUITS INSTALLED ON TOP OF WALK-IN UNITS
SHALL BE A MINIMUM OF 6" FROM ANY EDGE TO ALLOW
SPACE FOR EDGE PROTECTION NETTING. DO NOT
ROUTE CONDUITS ABOVE THE CEILING GRID ACCESS
UNLESS CONDUITS ARE INSTALLED IN JOIST SPACE,
REF ARCH.
9. UNDERSLAB CIRCUITS SHALL NOT BE ROUTED UNDER
WALK-IN FREEZERS AND SHALL BE ROUTED ABOVE
REFRIGERANT LINES WHERE THEY CROSS.
10. CIRCUITS FOR REFRIGERATED CASES SERVED BY
UNDERSLAB REFRIGERATION PIPING ARE TO BE
ROUTED UNDERSLAB AND EXTENDED TO THE FIRST
CASE IN EACH SYSTEM. WIRING AND CONDUIT FOR
SLAVE WIRING BETWEEN CASES SHALL BE PROVIDED
BY R.C. REFER TO UNDERSLAB CASE CONNECTION
WIRING DETAIL.
11. ALL UNDERSLAB CONDUITS SHALL BE 3/4" MIN.
12. CIRCUITS FOR REFRIGERATED CASES SERVED BY
OVERHEAD REFRIGERATION PIPING ARE TO BE
ROUTED DOWN FROM STRUCTURE AT THE SAME
LOCATION AS THE REFRIGERATION PIPING AND
EXTENDED TO THE FIRST CASE IN EACH SYSTEM. WIRE
AND CONDUIT FOR SLAVE WIRING BETWEEN CASES
SHALL BE PROVIDED BY THE R.C. REFER TO
OVERHEAD CASE CONNECTION WIRING DETAIL.
13. ON GROUPS OF THREE OR MORE REFRIGERATED
CASES WITH ELECTRIC DEFROST, R.C. SHALL
CONNECT CASES TO CREATE A THREE-PHASE HEATER
CIRCUIT. HEATER LOADS SHALL BE BALANCED
BETWEEN PHASES AS EVENLY AS POSSIBLE. REF
CASE DEFROST WIRING DETAIL.
14. PROVIDE A SEPARATE NEUTRAL FOR EACH NEW
BRANCH CIRCUIT SERVING REFRIGERATED CASES OR
WALK-IN UNITS.
15. PROVIDE CIRCUIT BREAKER LOCKING DEVICE (LOCK-
OFF FOR MAINTENANCE) ON NEW AND/OR EXISTING
CIRCUIT BREAKERS SERVING REFRIGERATED CASES.
16. REFERENCE ARCHITECTURAL DEMOLITION PLANS FOR
FULL EXTENT OF DEMOLITION WORK REQUIRED.
GENERAL REFRIGERATION
ELECTRICAL NOTES
08.28.20
KEYNOTES
16.250 CONNECT CIRCUITRY TO FACTORY PROVIDED
MAINTENANCE RECEPTACLE. ROUTE CIRCUIT TO
NEAREST RTU OR AHU MAINTENANCE RECEPTACLE
CIRCUIT.
16.258 CONNECT CIRCUITRY TO FACTORY PROVIDED
DISCONNECT SWITCH.
FEEDER OR GROUND SIZE
ALL CONDUIT AND CONDUCTOR SIZES ARE BASED ON EMT WITH 40%
FILL, 75ºC RATED TERMINATIONS AND TYPE THHN/THWN-2 INSULATION.
FOR NON-EMT CONDUIT OR TERMINATIONS OR INSULATION TYPES
RATED LESS THAN 75ºC, MODIFY SIZES ACCORDING TO NEC.
FEEDER SCHEDULE
33 (3)#10, (1)#10 G, 1/2” C
103 (3)#3, (1)#8 G, 1" C
ISSUE BLOCKVOID