HomeMy WebLinkAboutOverall Refrigeration Electrical Plan - RE12 3 4 5
C
D
E
F
G
H
I
NEW
CU5 TCO2
(ON ROOF)
NEW
DTB GLY
(ON ROOF)
ROOF
PENETRATION
FOR CONDUIT
ETR
DTB DX
RACK
ETR
DTA DX
RACK
EXISTING ROOF
MOUNTED
COMPRESSOR
HOUSES
REFRIGERATED
CASES
EVAP COILS
DELI
COOLER
1 2 3 4
D
E
F
G
H
I
BAKERY
COOLERTYP
16.492
TYP
16.492
REFRIGERATED
CASES
TYP
16.492
REFRIGERATED
CASES
TYP
16.492
EXISTING
ROOFTOP SPLIT
SUCTION HYBRID
HOUSE DTB
EXISTING
ROOFTOP SPLIT
SUCTION HYBRID
HOUSE DTA
COORDINATE DEMOLITION OF
EXISTING OGP CASE ELECTRICAL
CIRCUITS WITH WALMART
CONSTRUCTION MANAGER.
SHEET:
DRAWN BY:
CHECKED BY:
PROTO CYCLE:
DOCUMENT DATE:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.P (407) 661-9100F (407) 661-9101c-p.comFlorida Corporate Certificate #AA C0005262600 Maitland Center ParkwaySuite #200Maitland, FL 32751CUSHING TERRELL306 W. RAIL ROAD SUITE 104MISSOULA, MT 59802Phone: (406)728-9522Fax: (406)728-8287EXISTING CONDITIONS WERE TAKEN FROM
ORIGINAL DRAWINGS AND MAY NOT REFLECT
EXACT "AS-BUILT" CONDITIONS. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS
PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR
SHALL CAREFULLY COORDINATE NEW WORK AND
DEMOLITION WITH ALL OTHER DISCIPLINES AND
EXISTING CONDITIONS.
EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING
A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND
SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE
TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES
NOT RELIEVE THE RESPONSIBILITY OF PERFORMING
THE WORK PROPERLY. NO ADDITIONAL
COMPENSATION SHALL BE ALLOWED BECAUSE OF
CONDITIONS THAT OCCUR DUE TO FAILURE TO
FAMILIARIZE WORKERS WITH THIS KNOWLEDGE.
DOCUMENTS WITHOUT
SIGNATURE AND REQUIRED
SEAL OF AOR/EOR ARE NOT
FOR CONSTRUCTION
RE1
OVERALL
REFRIGERATION
ELECTRICAL
PLAN
DM20240347BOYNTON BEACH, FL11/07/2511/07/25STORE NO: 5911-2769006/27/25BOYNTON BEACH, FLSP3625 S FEDERAL HWY.KEYNOTES
16.492 E.C. SHALL COORDINATE WITH GENERAL
CONTRACTOR AND ARCHITECTURAL
DEMOLITION PLANS THE EXTENT OF ELECTRICAL
DEMOLITION. REMOVE UNUSED DEVICES,
BOXES, CONDUITS, AND WIRING BACK TO
ORIGINATING JUNCTION BOXES OR
PANELBOARDS. REFERENCE POWER PLANS FOR
CIRCUITRY TO BE REUSED. DEMOLITION SHALL
NOT AFFECT ACTIVE CIRCUITS. IF CIRCUIT IS
DEMOLISHED ALL THE WAY TO PANELBOARD,
REMOVE CIRCUIT BREAKER AND REPLACE WITH
FILLER PLATE. UPDATE TYPEWRITTEN CIRCUIT
DIRECTORY IDENTIFYING CIRCUIT AS "SPACE".
COORDINATE EXACT REQUIREMENTS WITH
EXISTING CONDITIONS PRIOR TO BID.
1. COORDINATE ALL WORK WITH REFRIGERATION
CONTRACTOR (R.C.) PRIOR TO INSTALLATION.
2. REFRIGERATED CASES: E.C. SHALL PROVIDE CONDUIT
AND WIRE FOR REFRIGERATED CASE FANS, LIGHTS
AND ANTI-SWEAT HEATERS, AND (IF APPLICABLE)
ELECTRICAL DEFROST. PROVIDE ADEQUATE
CONDUCTOR LENGTH TO ALLOW TERMINATION.
NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND
LABEL EACH CIRCUIT WITH BRANCH CIRCUIT
DESIGNATION AND REFRIGERATION SYSTEM NUMBER
FOR FINAL TERMINATION AT CASE BY R.C. REF CASE
CONNECTION WIRING DETAIL.
3. IF NEW CASES ARE PROVIDED WITH A FACTORY
INSTALLED TERMINAL STRIP AND JUMPERS FOR
CONNECTION TO A SINGLE CIRCUIT FOR 120V CASE
LOADS. RC SHALL REMOVE FACTORY INSTALLED
JUMPERS AS REQUIRED TO UTILIZE EXISTING
SEPARATE 120V FAN/LIGHT/ANTI-SWEAT CIRCUITS AS
INDICATED ON PLANS AND/OR PANELBOARD
SCHEDULES. ANY EXISTING ANTI-SWEAT CONTROL
(SWEATMISER) SHALL BE BY-PASSED. CASES UTILIZING
ELECTRICAL DEFROST WILL BE PROVIDED WITH
SEPARATE 208V TERMINATIONS AT THE TERMINAL
STRIP FOR CONNECTION TO THE 208V ELECTRIC
DEFROST CIRCUIT. RC SHALL MAKE FINAL
TERMINATIONS OF 120V AND 208V POWER CIRCUIT(S)
AT CASE TERMINAL STRIP. REFER TO CASE
CONNECTION SCHEMATIC ON REFRIGERATION
SHEETS.
4. WALK-IN UNITS: PROVIDE CONDUIT AND WIRE FOR
EVAPORATOR COIL FANS (CF) AND (IF APPLICABLE)
ELECTRIC DEFROST (ED). PROVIDE ADEQUATE
CONDUCTOR LENGTH TO ALLOW TERMINATION.
NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND
LABEL EACH CIRCUIT WITH BRANCH CIRCUIT
DESIGNATION AND REFRIGERATION SYSTEM NUMBER
FOR FINAL TERMINATION AT COIL BY R.C. REF
EVAPORATOR COIL WIRING DETAIL.
5. ROUTE REFRIGERATED CASE AND WALK-IN UNIT COIL
FAN, LIGHTS, ANTI-SWEAT AND DEFROST BRANCH
CIRCUITS TO WIREWAYS PROVIDED AT
REFRIGERATION EQUIPMENT AND/OR PANELBOARDS
AS REQUIRED.
6. REFRIGERATED CASE WIRING COMPARTMENT
REPRESENTED ON DRAWING BY JUNCTION BOX.
7. KEEP PENETRATIONS THROUGH WALK-IN UNITS
TO A MINIMUM. ROUTE ALL CONDUITS SERVING
FREEZERS AND COOLERS ON INSIDE OF BOX.
8. ALL CONDUITS INSTALLED ON TOP OF WALK-IN UNITS
SHALL BE A MINIMUM OF 6" FROM ANY EDGE TO ALLOW
SPACE FOR EDGE PROTECTION NETTING. DO NOT
ROUTE CONDUITS ABOVE THE CEILING GRID ACCESS
UNLESS CONDUITS ARE INSTALLED IN JOIST SPACE,
REF ARCH.
9. UNDERSLAB CIRCUITS SHALL NOT BE ROUTED UNDER
WALK-IN FREEZERS AND SHALL BE ROUTED ABOVE
REFRIGERANT LINES WHERE THEY CROSS.
10. CIRCUITS FOR REFRIGERATED CASES SERVED BY
UNDERSLAB REFRIGERATION PIPING ARE TO BE
ROUTED UNDERSLAB AND EXTENDED TO THE FIRST
CASE IN EACH SYSTEM. WIRING AND CONDUIT FOR
SLAVE WIRING BETWEEN CASES SHALL BE PROVIDED
BY R.C. REFER TO UNDERSLAB CASE CONNECTION
WIRING DETAIL.
11. ALL UNDERSLAB CONDUITS SHALL BE 3/4" MIN.
12. CIRCUITS FOR REFRIGERATED CASES SERVED BY
OVERHEAD REFRIGERATION PIPING ARE TO BE
ROUTED DOWN FROM STRUCTURE AT THE SAME
LOCATION AS THE REFRIGERATION PIPING AND
EXTENDED TO THE FIRST CASE IN EACH SYSTEM. WIRE
AND CONDUIT FOR SLAVE WIRING BETWEEN CASES
SHALL BE PROVIDED BY THE R.C. REFER TO
OVERHEAD CASE CONNECTION WIRING DETAIL.
13. ON GROUPS OF THREE OR MORE REFRIGERATED
CASES WITH ELECTRIC DEFROST, R.C. SHALL
CONNECT CASES TO CREATE A THREE-PHASE HEATER
CIRCUIT. HEATER LOADS SHALL BE BALANCED
BETWEEN PHASES AS EVENLY AS POSSIBLE. REF
CASE DEFROST WIRING DETAIL.
14. PROVIDE A SEPARATE NEUTRAL FOR EACH NEW
BRANCH CIRCUIT SERVING REFRIGERATED CASES OR
WALK-IN UNITS.
15. PROVIDE CIRCUIT BREAKER LOCKING DEVICE (LOCK-
OFF FOR MAINTENANCE) ON NEW AND/OR EXISTING
CIRCUIT BREAKERS SERVING REFRIGERATED CASES.
16. REFERENCE ARCHITECTURAL DEMOLITION PLANS FOR
FULL EXTENT OF DEMOLITION WORK REQUIRED.
GENERAL REFRIGERATION
ELECTRICAL NOTES
08.28.20
FOR LOCKOUT TAG OUT PROCEDURES REFER TO
SPECIFICATION SECTION 01351 AND THE MASTER
CONSTRUCTION AGREEMENT FOR WALMART
GLOBAL ETHICS AND COMPLIANCE, "COMPLIANCE
PERFORMANCE STANDARD FOR CONSTRUCTION."
A
R
S
OS
B
DH
J
SS
OS2S
OSS
3S
4S
DS
MS
VSS
KS
S SINGLE POLE SWITCH
CIRCUIT, CONCEALED IN WALLS OR
CEILING, E INDICATES EXISTING WIRING
SMOKE DETECTOR
SAIL SWITCH
JUNCTION BOX
HORN / STROBE
ABBREVIATIONS
BUZZER
CIRCUIT, CONCEALED IN SLAB FLOOR,
E INDICATES EXISTING WIRING
CONDUIT SLEEVE
SURFACE MOUNTED PANELBOARD
FLUSH MOUNTED PANELBOARD
CIRCUIT, EXPOSED,
E INDICATES EXISTING WIRING
LOW VOLTAGE WIRING
TELEPOWER POLE
TELEPHONE / DATA BOX FOR ISD
TELEPHONE, FLUSH FLOOR
PUSH BUTTON
MOTOR
ALARM JUNCTION BOX,
FOR REMOTE TEST/RESET
(WALL MOUNTED/CEILING MOUNTED)
EQUIPMENT CONNECTION POINT
(PROVIDED WITH EQUIPMENT)
NON-FUSED DISCONNECT
RECEPTACLE, PLUG-MOLD
RECEPTACLE, SIMPLEX
RECEPTACLE, SPECIAL
JUNCTION BOX
(WALL MOUNTED/CEILING MOUNTED)
ALARM JUNCTION BOX,
(WALL MOUNTED/CEILING MOUNTED)
RECEPTACLE, DOUBLE DUPLEX,
ISOLATED GROUND
FUSED DISCONNECT
4-WAY SWITCH
RECEPTACLE, DUPLEX ISOLATED
GROUND FLUSH FLOOR
RECEPTACLE, DOUBLE DUPLEX
RECEPTACLE, DUPLEX FLUSH FLOOR
VARIABLE SPEED SWITCH
KEYED SWITCH
DIMMER SWITCH
RECEPTACLE, DUPLEX,
MOUNTED HORIZONTALLY
RECEPTACLE, DUPLEX
MANUAL MOTOR SWITCH
3-WAY SWITCH
RECEPTACLE, DUPLEX
ISOLATED GROUND
LIGHT FIXTURE,
NIGHT LIGHT
VOLUMETRIC LIGHT FIXTURE
LIGHT FIXTURE
(WALL MOUNTED/CEILING MOUNTED)
LIGHT FIXTURE
(SYMBOLS APPLY ONLY WHEN USED ON DRAWINGS)
SYMBOL DESCRIPTION
RECEPTACLE, DUPLEX TWIST LOCK,
ISOLATED GROUND, L5-15R, UNO
SINGLE POLE OCCUPANCY
SENSOR SWITCH
LOW VOLTAGE CABLE
BOX FOR OTHER
DOOR HOLD OPEN
RECEPTACLE, DUPLEX TWIST LOCK,
L5-15R, UNO
RECEPTACLE, SIMPLEX TWIST LOCK,
ISOLATED GROUND, L5-15R, UNO
RECEPTACLE, SIMPLEX TWIST LOCK,
L5-15R, UNO
OCCUPANCY SENSOR SWITCH,
ONE-DIRECTION SENSING
RECEPTACLE, GFI
DOUBLE POLE OCCUPANCY
SENSOR SWITCH
T THERMOSTAT
(WALL MOUNTED/CEILING MOUNTED)
EXIT FIXTURE
(WALL MOUNTED/CEILING MOUNTED)
EMERGENCY LIGHT
(WALL MOUNTED/CEILING MOUNTED)
EMERGENCY LIGHT REMOTE HEADS
(WALL MOUNTED/CEILING MOUNTED)
a, b, c LOWER CASE LETTERS INDICATE
SWITCHING CONFIGURATION
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
C CONDUIT
CCT CIRCUIT
CF CEILING FAN
CW CASH WRAP
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
G GROUND
GC GENERAL CONTRACTOR
GFEP GROUND FAULT EQUIPMENT PROTECTION
GFI GROUND FAULT CIRCUIT INTERRUPTER
HD HAND DRYER
IG ISOLATED GROUND
LCU LIGHTING CONTROL UNIT
NL NIGHT LIGHT
NTS NOT TO SCALE
REC REFRIGERATION ELECTRICAL CONTRACTOR
RC REFRIGERATION CONTRACTOR
RH RADIANT HEATER
SC SECURITY CAMERA
TR TAMPER RESISTANT
TYP TYPICAL
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
WH WATER HEATER
WP WEATHER PROOF
WR WEATHER RESISTANT
ELECTRICAL SYMBOLS
LEGEND
TIME CLOCKTC
TRACK LIGHTING
12.17.21
OS OCCUPANCY SENSOR SWITCH,
FOUR-DIRECTION SENSING
1" = 20'-0"2 OVERALL REFRIGERATION ELECTRICAL PLAN
1" = 20'-0"1 REFRIGERATION ELECTRICAL DEMO PLAN
ARC FLASH HAZARD WARNING LABELING REQUIREMENTS
PER NEC ARE PROVIDED BY OWNER UNDER SEPARATE
CONTRACT.
ARC FLASH
CONTRACTOR TO VERIFY THE FEEDER ORIGINATION
POINT SOURCE OF POWER FOR ALL DISTRIBUTION
BOARDS, PANELBOARDS, AND BUSWAY AFFECTED BY
THE REMODEL SCOPE OF WORK. PROVIDE A
LAMINATED PLASTIC NAMEPLATE PER SPECIFICATIONS
INDICATING THIS INFORMATION.
EXAMPLES:
H1A FED FROM MSWB
L1D FED FROM H1B VIA T1D
SOURCE OF SUPPLY NOTE
COORDINATE ALL WORK THAT REQUIRES POWER
INTERRUPTIONS TO THE STORE WITH THE STORE
MANAGER AND THE WALMART CONSTRUCTION MANAGER
A MINIMUM OF 48 HOURS IN ADVANCE OF ALL STORE
POWER INTERRUPTIONS. IN ADDITION, IF THE MAIN
ELECTRICAL SWITCHGEAR REQUIRES WORK AND DOES
NOT HAVE A MAIN SERVICE DISCONNECTING MEANS,
COORDINATE WITH THE UTILITY COMPANY A MINIMUM OF
TWO WEEKS IN ADVANCE OF THE STORE POWER
INTERRUPTION. IF STORE IS NOT OPEN 24 HOURS PER
DAY, ALL STORE POWER INTERRUPTIONS ARE TO BE
ACCOMPLISHED AFTER NORMAL STORE BUSINESS
HOURS. PROVIDE TEMPORARY POWER AS REQUIRED
PER SPECIFICATIONS. INSTALLATION OF NEW EQUIPMENT
SHALL BE COMPLETED AND THE POWER SYSTEM TESTED
AND RE-ENERGIZED PRIOR TO THE TIME ESTABLISHED BY
THE STORE MANAGER AND THE WALMART
CONSTRUCTION MANAGER.
POWER INTERRUPTION NOTE
11.30.18
ISSUE BLOCK
VOID