HomeMy WebLinkAboutOverall Refrigeration Electrical Plan - RE12 3 4 5 C D E F G H I NEW CU5 TCO2 (ON ROOF) NEW DTB GLY (ON ROOF) ROOF PENETRATION FOR CONDUIT ETR DTB DX RACK ETR DTA DX RACK EXISTING ROOF MOUNTED COMPRESSOR HOUSES REFRIGERATED CASES EVAP COILS DELI COOLER 1 2 3 4 D E F G H I BAKERY COOLERTYP 16.492 TYP 16.492 REFRIGERATED CASES TYP 16.492 REFRIGERATED CASES TYP 16.492 EXISTING ROOFTOP SPLIT SUCTION HYBRID HOUSE DTB EXISTING ROOFTOP SPLIT SUCTION HYBRID HOUSE DTA COORDINATE DEMOLITION OF EXISTING OGP CASE ELECTRICAL CIRCUITS WITH WALMART CONSTRUCTION MANAGER. SHEET: DRAWN BY: CHECKED BY: PROTO CYCLE: DOCUMENT DATE:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.P (407) 661-9100F (407) 661-9101c-p.comFlorida Corporate Certificate #AA C0005262600 Maitland Center ParkwaySuite #200Maitland, FL 32751CUSHING TERRELL306 W. RAIL ROAD SUITE 104MISSOULA, MT 59802Phone: (406)728-9522Fax: (406)728-8287EXISTING CONDITIONS WERE TAKEN FROM ORIGINAL DRAWINGS AND MAY NOT REFLECT EXACT "AS-BUILT" CONDITIONS. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR SHALL CAREFULLY COORDINATE NEW WORK AND DEMOLITION WITH ALL OTHER DISCIPLINES AND EXISTING CONDITIONS. EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES NOT RELIEVE THE RESPONSIBILITY OF PERFORMING THE WORK PROPERLY. NO ADDITIONAL COMPENSATION SHALL BE ALLOWED BECAUSE OF CONDITIONS THAT OCCUR DUE TO FAILURE TO FAMILIARIZE WORKERS WITH THIS KNOWLEDGE. DOCUMENTS WITHOUT SIGNATURE AND REQUIRED SEAL OF AOR/EOR ARE NOT FOR CONSTRUCTION RE1 OVERALL REFRIGERATION ELECTRICAL PLAN DM20240347BOYNTON BEACH, FL11/07/2511/07/25STORE NO: 5911-2769006/27/25BOYNTON BEACH, FLSP3625 S FEDERAL HWY.KEYNOTES 16.492 E.C. SHALL COORDINATE WITH GENERAL CONTRACTOR AND ARCHITECTURAL DEMOLITION PLANS THE EXTENT OF ELECTRICAL DEMOLITION. REMOVE UNUSED DEVICES, BOXES, CONDUITS, AND WIRING BACK TO ORIGINATING JUNCTION BOXES OR PANELBOARDS. REFERENCE POWER PLANS FOR CIRCUITRY TO BE REUSED. DEMOLITION SHALL NOT AFFECT ACTIVE CIRCUITS. IF CIRCUIT IS DEMOLISHED ALL THE WAY TO PANELBOARD, REMOVE CIRCUIT BREAKER AND REPLACE WITH FILLER PLATE. UPDATE TYPEWRITTEN CIRCUIT DIRECTORY IDENTIFYING CIRCUIT AS "SPACE". COORDINATE EXACT REQUIREMENTS WITH EXISTING CONDITIONS PRIOR TO BID. 1. COORDINATE ALL WORK WITH REFRIGERATION CONTRACTOR (R.C.) PRIOR TO INSTALLATION. 2. REFRIGERATED CASES: E.C. SHALL PROVIDE CONDUIT AND WIRE FOR REFRIGERATED CASE FANS, LIGHTS AND ANTI-SWEAT HEATERS, AND (IF APPLICABLE) ELECTRICAL DEFROST. PROVIDE ADEQUATE CONDUCTOR LENGTH TO ALLOW TERMINATION. NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND LABEL EACH CIRCUIT WITH BRANCH CIRCUIT DESIGNATION AND REFRIGERATION SYSTEM NUMBER FOR FINAL TERMINATION AT CASE BY R.C. REF CASE CONNECTION WIRING DETAIL. 3. IF NEW CASES ARE PROVIDED WITH A FACTORY INSTALLED TERMINAL STRIP AND JUMPERS FOR CONNECTION TO A SINGLE CIRCUIT FOR 120V CASE LOADS. RC SHALL REMOVE FACTORY INSTALLED JUMPERS AS REQUIRED TO UTILIZE EXISTING SEPARATE 120V FAN/LIGHT/ANTI-SWEAT CIRCUITS AS INDICATED ON PLANS AND/OR PANELBOARD SCHEDULES. ANY EXISTING ANTI-SWEAT CONTROL (SWEATMISER) SHALL BE BY-PASSED. CASES UTILIZING ELECTRICAL DEFROST WILL BE PROVIDED WITH SEPARATE 208V TERMINATIONS AT THE TERMINAL STRIP FOR CONNECTION TO THE 208V ELECTRIC DEFROST CIRCUIT. RC SHALL MAKE FINAL TERMINATIONS OF 120V AND 208V POWER CIRCUIT(S) AT CASE TERMINAL STRIP. REFER TO CASE CONNECTION SCHEMATIC ON REFRIGERATION SHEETS. 4. WALK-IN UNITS: PROVIDE CONDUIT AND WIRE FOR EVAPORATOR COIL FANS (CF) AND (IF APPLICABLE) ELECTRIC DEFROST (ED). PROVIDE ADEQUATE CONDUCTOR LENGTH TO ALLOW TERMINATION. NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND LABEL EACH CIRCUIT WITH BRANCH CIRCUIT DESIGNATION AND REFRIGERATION SYSTEM NUMBER FOR FINAL TERMINATION AT COIL BY R.C. REF EVAPORATOR COIL WIRING DETAIL. 5. ROUTE REFRIGERATED CASE AND WALK-IN UNIT COIL FAN, LIGHTS, ANTI-SWEAT AND DEFROST BRANCH CIRCUITS TO WIREWAYS PROVIDED AT REFRIGERATION EQUIPMENT AND/OR PANELBOARDS AS REQUIRED. 6. REFRIGERATED CASE WIRING COMPARTMENT REPRESENTED ON DRAWING BY JUNCTION BOX. 7. KEEP PENETRATIONS THROUGH WALK-IN UNITS TO A MINIMUM. ROUTE ALL CONDUITS SERVING FREEZERS AND COOLERS ON INSIDE OF BOX. 8. ALL CONDUITS INSTALLED ON TOP OF WALK-IN UNITS SHALL BE A MINIMUM OF 6" FROM ANY EDGE TO ALLOW SPACE FOR EDGE PROTECTION NETTING. DO NOT ROUTE CONDUITS ABOVE THE CEILING GRID ACCESS UNLESS CONDUITS ARE INSTALLED IN JOIST SPACE, REF ARCH. 9. UNDERSLAB CIRCUITS SHALL NOT BE ROUTED UNDER WALK-IN FREEZERS AND SHALL BE ROUTED ABOVE REFRIGERANT LINES WHERE THEY CROSS. 10. CIRCUITS FOR REFRIGERATED CASES SERVED BY UNDERSLAB REFRIGERATION PIPING ARE TO BE ROUTED UNDERSLAB AND EXTENDED TO THE FIRST CASE IN EACH SYSTEM. WIRING AND CONDUIT FOR SLAVE WIRING BETWEEN CASES SHALL BE PROVIDED BY R.C. REFER TO UNDERSLAB CASE CONNECTION WIRING DETAIL. 11. ALL UNDERSLAB CONDUITS SHALL BE 3/4" MIN. 12. CIRCUITS FOR REFRIGERATED CASES SERVED BY OVERHEAD REFRIGERATION PIPING ARE TO BE ROUTED DOWN FROM STRUCTURE AT THE SAME LOCATION AS THE REFRIGERATION PIPING AND EXTENDED TO THE FIRST CASE IN EACH SYSTEM. WIRE AND CONDUIT FOR SLAVE WIRING BETWEEN CASES SHALL BE PROVIDED BY THE R.C. REFER TO OVERHEAD CASE CONNECTION WIRING DETAIL. 13. ON GROUPS OF THREE OR MORE REFRIGERATED CASES WITH ELECTRIC DEFROST, R.C. SHALL CONNECT CASES TO CREATE A THREE-PHASE HEATER CIRCUIT. HEATER LOADS SHALL BE BALANCED BETWEEN PHASES AS EVENLY AS POSSIBLE. REF CASE DEFROST WIRING DETAIL. 14. PROVIDE A SEPARATE NEUTRAL FOR EACH NEW BRANCH CIRCUIT SERVING REFRIGERATED CASES OR WALK-IN UNITS. 15. PROVIDE CIRCUIT BREAKER LOCKING DEVICE (LOCK- OFF FOR MAINTENANCE) ON NEW AND/OR EXISTING CIRCUIT BREAKERS SERVING REFRIGERATED CASES. 16. REFERENCE ARCHITECTURAL DEMOLITION PLANS FOR FULL EXTENT OF DEMOLITION WORK REQUIRED. GENERAL REFRIGERATION ELECTRICAL NOTES 08.28.20 FOR LOCKOUT TAG OUT PROCEDURES REFER TO SPECIFICATION SECTION 01351 AND THE MASTER CONSTRUCTION AGREEMENT FOR WALMART GLOBAL ETHICS AND COMPLIANCE, "COMPLIANCE PERFORMANCE STANDARD FOR CONSTRUCTION." A R S OS B DH J SS OS2S OSS 3S 4S DS MS VSS KS S SINGLE POLE SWITCH CIRCUIT, CONCEALED IN WALLS OR CEILING, E INDICATES EXISTING WIRING SMOKE DETECTOR SAIL SWITCH JUNCTION BOX HORN / STROBE ABBREVIATIONS BUZZER CIRCUIT, CONCEALED IN SLAB FLOOR, E INDICATES EXISTING WIRING CONDUIT SLEEVE SURFACE MOUNTED PANELBOARD FLUSH MOUNTED PANELBOARD CIRCUIT, EXPOSED, E INDICATES EXISTING WIRING LOW VOLTAGE WIRING TELEPOWER POLE TELEPHONE / DATA BOX FOR ISD TELEPHONE, FLUSH FLOOR PUSH BUTTON MOTOR ALARM JUNCTION BOX, FOR REMOTE TEST/RESET (WALL MOUNTED/CEILING MOUNTED) EQUIPMENT CONNECTION POINT (PROVIDED WITH EQUIPMENT) NON-FUSED DISCONNECT RECEPTACLE, PLUG-MOLD RECEPTACLE, SIMPLEX RECEPTACLE, SPECIAL JUNCTION BOX (WALL MOUNTED/CEILING MOUNTED) ALARM JUNCTION BOX, (WALL MOUNTED/CEILING MOUNTED) RECEPTACLE, DOUBLE DUPLEX, ISOLATED GROUND FUSED DISCONNECT 4-WAY SWITCH RECEPTACLE, DUPLEX ISOLATED GROUND FLUSH FLOOR RECEPTACLE, DOUBLE DUPLEX RECEPTACLE, DUPLEX FLUSH FLOOR VARIABLE SPEED SWITCH KEYED SWITCH DIMMER SWITCH RECEPTACLE, DUPLEX, MOUNTED HORIZONTALLY RECEPTACLE, DUPLEX MANUAL MOTOR SWITCH 3-WAY SWITCH RECEPTACLE, DUPLEX ISOLATED GROUND LIGHT FIXTURE, NIGHT LIGHT VOLUMETRIC LIGHT FIXTURE LIGHT FIXTURE (WALL MOUNTED/CEILING MOUNTED) LIGHT FIXTURE (SYMBOLS APPLY ONLY WHEN USED ON DRAWINGS) SYMBOL DESCRIPTION RECEPTACLE, DUPLEX TWIST LOCK, ISOLATED GROUND, L5-15R, UNO SINGLE POLE OCCUPANCY SENSOR SWITCH LOW VOLTAGE CABLE BOX FOR OTHER DOOR HOLD OPEN RECEPTACLE, DUPLEX TWIST LOCK, L5-15R, UNO RECEPTACLE, SIMPLEX TWIST LOCK, ISOLATED GROUND, L5-15R, UNO RECEPTACLE, SIMPLEX TWIST LOCK, L5-15R, UNO OCCUPANCY SENSOR SWITCH, ONE-DIRECTION SENSING RECEPTACLE, GFI DOUBLE POLE OCCUPANCY SENSOR SWITCH T THERMOSTAT (WALL MOUNTED/CEILING MOUNTED) EXIT FIXTURE (WALL MOUNTED/CEILING MOUNTED) EMERGENCY LIGHT (WALL MOUNTED/CEILING MOUNTED) EMERGENCY LIGHT REMOTE HEADS (WALL MOUNTED/CEILING MOUNTED) a, b, c LOWER CASE LETTERS INDICATE SWITCHING CONFIGURATION AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE C CONDUIT CCT CIRCUIT CF CEILING FAN CW CASH WRAP EC ELECTRICAL CONTRACTOR EF EXHAUST FAN ETR EXISTING TO REMAIN EWC ELECTRIC WATER COOLER G GROUND GC GENERAL CONTRACTOR GFEP GROUND FAULT EQUIPMENT PROTECTION GFI GROUND FAULT CIRCUIT INTERRUPTER HD HAND DRYER IG ISOLATED GROUND LCU LIGHTING CONTROL UNIT NL NIGHT LIGHT NTS NOT TO SCALE REC REFRIGERATION ELECTRICAL CONTRACTOR RC REFRIGERATION CONTRACTOR RH RADIANT HEATER SC SECURITY CAMERA TR TAMPER RESISTANT TYP TYPICAL UH UNIT HEATER UNO UNLESS NOTED OTHERWISE WH WATER HEATER WP WEATHER PROOF WR WEATHER RESISTANT ELECTRICAL SYMBOLS LEGEND TIME CLOCKTC TRACK LIGHTING 12.17.21 OS OCCUPANCY SENSOR SWITCH, FOUR-DIRECTION SENSING 1" = 20'-0"2 OVERALL REFRIGERATION ELECTRICAL PLAN 1" = 20'-0"1 REFRIGERATION ELECTRICAL DEMO PLAN ARC FLASH HAZARD WARNING LABELING REQUIREMENTS PER NEC ARE PROVIDED BY OWNER UNDER SEPARATE CONTRACT. ARC FLASH CONTRACTOR TO VERIFY THE FEEDER ORIGINATION POINT SOURCE OF POWER FOR ALL DISTRIBUTION BOARDS, PANELBOARDS, AND BUSWAY AFFECTED BY THE REMODEL SCOPE OF WORK. PROVIDE A LAMINATED PLASTIC NAMEPLATE PER SPECIFICATIONS INDICATING THIS INFORMATION. EXAMPLES: H1A FED FROM MSWB L1D FED FROM H1B VIA T1D SOURCE OF SUPPLY NOTE COORDINATE ALL WORK THAT REQUIRES POWER INTERRUPTIONS TO THE STORE WITH THE STORE MANAGER AND THE WALMART CONSTRUCTION MANAGER A MINIMUM OF 48 HOURS IN ADVANCE OF ALL STORE POWER INTERRUPTIONS. IN ADDITION, IF THE MAIN ELECTRICAL SWITCHGEAR REQUIRES WORK AND DOES NOT HAVE A MAIN SERVICE DISCONNECTING MEANS, COORDINATE WITH THE UTILITY COMPANY A MINIMUM OF TWO WEEKS IN ADVANCE OF THE STORE POWER INTERRUPTION. IF STORE IS NOT OPEN 24 HOURS PER DAY, ALL STORE POWER INTERRUPTIONS ARE TO BE ACCOMPLISHED AFTER NORMAL STORE BUSINESS HOURS. PROVIDE TEMPORARY POWER AS REQUIRED PER SPECIFICATIONS. INSTALLATION OF NEW EQUIPMENT SHALL BE COMPLETED AND THE POWER SYSTEM TESTED AND RE-ENERGIZED PRIOR TO THE TIME ESTABLISHED BY THE STORE MANAGER AND THE WALMART CONSTRUCTION MANAGER. POWER INTERRUPTION NOTE 11.30.18 ISSUE BLOCK VOID