HomeMy WebLinkAboutRefrigeration Details Glycol - R3.2SUPPLY AND RETURN AS SPECIFIED IN PIPING SCHEDULE SPACE AT 4' INTERVALS TYP 1" EXPANDED POLYSTYRENE OR EQUAL 6" MINIMUM WIDTH. LENGTH AS REQUIRED TYP ROUTE SUPPLY AND RETURN HEADERS ON TOP OF CASES SUPPLY AND RETURN SHUT- OFF VALVES FURNISHED AND INSTALLED BY REFRIGERATION CONTRACTOR. ADJUST LOCATION OF DROPS AS REQUIRED. IF ROUTED IN WALL, EXIT WALL 6" ABOVE TOP OF CASE HEIGHT TYP PROVIDE TEMPERATURE/PRESSURE TEST WELLS AT LAST CASE IN LINEUP. REFRIGERATION CASE MANUFACTURER TO FURNISH AND INSTALL TOP FED CASES WITH FACTORY INSTALLED SHUT-OFF VALVES, SUPPLY SOLENOID VALVES, AND RETURN AUTOFLOW BALANCE VALVES FOR EACH CASE. REF SPECIFICATIONS REAR HALF OF REFRIGERATED CASE DESIGNATED FOR PIPING AND VALVES. FRONT HALF OF REFRIGERATED CASE DESIGNATED FOR ELECTRICAL AND BAS COMPONENTS. RETURN SUB-LOOP BRANCH SUPPLY SUB-LOOP BRANCH PROVIDE SUPPLY AND RETURN SUB-LOOP SHUT-OFF VALVES . REFER TO PLANS FOR LOCATIONS. CONTINUES TO ADDITIONAL CIRCUITS ON SUB-LOOP MAIN SUPPLY AND RETURN BRANCH PIPING SUPPLY AND RETURN LINES FOR SECOND CIRCUIT ON SUB-LOOP CONTINUES TO SECONDARY PUMP SKID REFER TO SPECIFICATION SECTION 15181 FOR PIPE LABELING REQUIREMENTS. (TYP OF ALL SECONDARY GLYCOL SUPPLY AND RETURN PIPING) TEMPORARY U-BEND BYPASS TO BE REMOVED BEFORE FINAL CONNECTION. REFER TO U- BEND BYPASS DETAIL. SUPPLY AND RETURN AS SPECIFIED IN PIPING SCHEDULE SPACE AT 4' INTERVALS TYP 1" EXPANDED POLYSTYRENE OR EQUAL 6" MINIMUM WIDTH. LENGTH AS REQUIRED TYP ROUTE SUPPLY AND RETURN HEADERS ON TOP OF CASES SUPPLY AND RETURN SHUT-OFF VALVES FURNISHED AND INSTALLED BY REFRIGERATION CONTRACTOR. ADJUST LOCATION OF DROPS AS REQUIRED. IF ROUTED IN WALL, EXIT WALL 6" ABOVE TOP OF CASE HEIGHT TYP PROVIDE TEMPERATURE/PRESSURE TEST WELLS AT LAST CASE IN LINEUP. REFRIGERATION CASE MANUFACTURER TO FURNISH AND INSTALL TOP FED CASES WITH FACTORY INSTALLED SHUT-OFF VALVES, SUPPLY SOLENOID VALVES, AND RETURN AUTOFLOW BALANCE VALVES FOR EACH CASE. REF SPECIFICATIONS REAR HALF OF REFRIGERATED CASE DESIGNATED FOR PIPING AND VALVES. FRONT HALF OF REFRIGERATED CASE DESIGNATED FOR ELECTRICAL AND BAS COMPONENTS. RETURN SUB-LOOP BRANCH SUPPLY SUB-LOOP BRANCH PROVIDE SUPPLY AND RETURN SUB-LOOP SHUT-OFF VALVES . REFER TO PLANS FOR LOCATIONS. CONTINUES TO ADDITIONAL CIRCUITS ON SUB-LOOP MAIN SUPPLY AND RETURN BRANCH PIPING SUPPLY AND RETURN LINES FOR SECOND CIRCUIT ON SUB-LOOP CONTINUES TO SECONDARY PUMP SKID REFER TO SPECIFICATION SECTION 15181 FOR PIPE LABELING REQUIREMENTS. (TYP OF ALL SECONDARY GLYCOL SUPPLY AND RETURN PIPING) APPROXIMATELY 2' ABOVE TOP OF CASE TYP TEMPORARY U-BEND BYPASS TO BE REMOVED BEFORE FINAL CONNECTION. REFERENCE U- BEND BYPASS DETAIL. FULLY INSULATE PIPING BEFORE PHASING. SUPPLY LINE FROM RACK PROVIDE NORMALLY OPEN GLYCOL ISOLATION VALVES IN AN ACCESSIBLE LOCATION. REFER TO SPECIFICATIONS. INSULATION RETURN LINE TO RACK CONTRACTOR PROVIDED BLIND FLANGE CONNECTION. (TYP) PROVIDED ISOLATION VALVE FIELD INSTALLED. (TYP BOTH SUPPLY AND RETURN) EMERGENCY CHILLER CONNECTION TO PUMP SKID. MATCH MAIN SUPPLY AND RETURN PIPE SIZE. SUPPLY FROM PUMP SKID RETURN TO PUMP SKID SUPPLY TO CASES/COILS RETURN FROM CASES/COILS SUPPORT EMERGENCY CHILLER CONNECTION. REFER TO REFRIGERATION PIPING SUPPORT DETAIL. (TYP) GLYCOL RETURN GLYCOL SUPPLY INSTALL BYPASS VALVE IN LOCATION SHOWN ON PIPING PLANS. CONNECT BYPASS LINE TO MAIN PIPING; MAIN PIPING TO BE SAME SIZE OR LARGER THAN BYPASS VALVE SIZE. BYPASS LINE SIZE TO MATCH BYPASS VALVE SIZE INSTALL OWNER FURNISHED SECONDARY GLYCOL BYPASS VALVE, SEE REFRIGERATION SECONDARY PUMP SKID SCHEDULE FOR SIZE. ENSURE VALVE DIRECTION ALLOWS FLOW FROM SUPPLY TO RETURN. LABEL GLYCOL PIPING PER SPECIFICATION SECTION 15181 REFRIGERATION CONTRACTOR SHALL FURNISH AND INSTALL FULL PORT ISOLATION BALL VALVES ON BOTH SIDES OF BYPASS VALVE. REFER TO GLYCOL REFRIGERATION ISOLATION VALVES DETAIL. FLOW DIRECTION BYPASS LINE MAIN CLOSE VALVES DURING INITIAL SYSTEM FLUSH, OPEN DURING NORMAL OPERATION. VENT & DRAIN 1.PROVIDE 1/2" VENT VALVES AT ALL HIGH POINTS OF THE PIPING TO REMOVE AIR DURING INSTALLATION AND MAINTENANCE. HIGH POINTS ARE ANY PLACE ON A REFRIGERATION LINE THAT AIR POCKETS COULD FORM. PROVIDE DROP- DOWN LINE FOR CONVENIENT ACCESS TO THE VALVE AS REQUIRED. 2.PROVIDE 3/4" DRAIN VALVES AT ALL LOW POINTS IN MAINS, RISERS, AND BRANCH LINES. LOW POINTS ARE DEFINED AS ANY PLACE ON A REFRIGERATION LINE THAT CAN POOL GLYCOL AS SYSTEM IS DRAINED. 3.THE VENT AND DRAIN VALVES TO HAVE THREADED CONNECTIONS FOR HOSES OR PIPES. THEY SHALL REMAIN CAPPED DURING NORMAL OPERATION. 4.AVOID CHANGE IN ELEVATION FOR THE PIPE RUN. 5.REFERENCE SPECIFICATION SECTION 15181. MINIMUM 1/2" TEE INSULATION AND VAPOR BARRIER PER SPECIFICATIONS INSTALL VENT AT HIGHEST POINT OF PIPING 1/2 " MANUAL AIR VENT WITH THREADED NIPPLE AND CAP. NORMALLY CLOSED. OBSTRUCTIONS (TYP) MAINTAIN INSULATION AROUND NIPPLE (TYP) INSULATION PER SPECIFICATIONS MINIMUM 3/4" TEE FITTING. 3/4" DRAIN VALVE WITH THREADED NIPPLE AND CAP. NORMALLY CLOSED INSTALL DRAIN PER SPECIFICATION 15181. CIRCUIT LEVEL SUPPLY AND RETURN ISOLATION VALVES. SUPPLY FROM PUMP SKID RETURN TO PUMP SKID LEAVE SUFFICIENT SPACE TO ALLOW REMOVAL OF U-BEND AND EXTENSION OF PIPING DURING PHASING OF FINAL CONNECTION. REFERENCE SPEC 15181 FOR U-BEND BYPASS REQUIREMENTS AND USAGE. FULLY INSULATE PIPING AND VALVES PRIOR TO FILLING SYSTEM. 12" FROM TOP OF CASE INSTALL 1/4" MANUAL AIR VENT WITH NIPPLE AND CAP. REFER TO SPECIFICATION 15181. VALVES SHALL BE FULLY INSULATED AND HAVE EXTENDED STEM/BONNET SUITABLE FOR INSULATION THICKNESS. TOP OF CASE 24" MAX SUPPORT PIPING WITHIN 1 FOOT OF RISER. REFER TO HORIZONTAL REFRIGERANT LINE SUPPORT DETAIL. ROOF OPENING MAY CONTAIN MULTIPLE PIPING AND CONDUIT TYPES, SEE PLANS. MINIMUM 2" GAP BETWEEN ADJACENT PIPES OR CONDUITS. OWNER PROVIDED MANUFACTURED CURB, SEE ARCHITECTURAL DETAILS FOR SIZE, INSULATION, ASSEMBLY, AND SEALING REQUIREMENTS SUPPORT PIPING WITHIN 1 FOOT OF RISER USING KLO-SHURE, SEE ROOF SUPPORT DETAIL. 2'-0" WIDE, 18 GAUGE SHEET METAL DRAIN PAN WITH INTERNAL MASTIC COATING SUPPORT ROD (TYP) PROVIDE A 3/4" PVC DRAIN FOR ANY PENETRATION WHOSE WIDTH IS 16" -24". PROVIDE A 1' PVC DRAIN FOR ANY PENETRATION WHOSE WIDTH IS 30" -36", AND PROVIDE A 1 1/2" PVC DRAIN FOR ANY PENETRATIONS WHOSE WIDTH IS GREATER THAN 36". SLOPE PVC DRAIN LINE 1/8" PER 12" AND TERMINATE OVER DRAIN WITH 2" AIR GAP. DO NOT TRAP AT BOTTOM OF GLYCOL RISER. INSTALL DRAIN VALVE AT ALL LOW POINTS. REMOVABLE HOOD PROVIDED WITH CURB. INVERTED TRAP ALLOWED BUT NOT REQUIRED FOR GLYCOL PIPING. INSTALL AIR VENT ON ALL HIGH POINTS. SECURE PIPING TO UNISTRUT AT TOP OF CURB WITH KLO-SHURE CLAMP 5" CENTER OF PIPE TO TOP OF CURB. AIR VENT AT HIGH POINT IN ACCESSIBLE LOCATION. LABEL PIPING PER SPECIFICATION SECTION 15181. 1' MAX 1' MAX GLYCOL FAN/ COIL UNIT TOP OF BOX BOX WALL MOUNT COIL ACCORDING TO MANUFACTURER'S RECOMMENDATIONS (TYP). COIL DRAIN AND ISOLATION VALVE, LOCATED AT LOWER CONNECTION OF COIL PROVIDE COIL SUPPLY SHUTOFF VALVE, ONE PER CIRCUIT. INSTALL REFRIGERATION EQUIPMENT SUPPLIER-FURNISHED COIL AUTOFLOW BALANCING VALVE, ONE PER COIL. PROVIDE CIRCUIT RETURN SHUTOFF VALVE, ONE PER CIRCUIT. SUPPORT EVAPORATORS WITH BOLTS THRU CEILING PANEL TO 1 5/8" X 1 5/8" X 10 FT. LONG 14 GAUGE. GALVANIZED UNISTRUT SPANNING THREE COOLER/FREEZER CEILING PANELS. PROVIDE DOUBLE NUTS ON EACH BOLT. SEAL AROUND BOLT PENETRATIONS THRU COOLER/FREEZER BOX WALLS OR CEILINGS WITH BACKER ROD AND SEALANT. TYP SUPPLY RETURN FOAM TOPS OF BOLT PENETRATIONS. TYP DRILL HOLE IN COOLER/FREEZER BOX WALLS, CENTER PIPE IN OPENING, AND SEAL WITH EXPANDING FOAM. AFTER FOAM CURES, TRIM FLUSH TO PANEL. BUTT INSULATION TO THE BOUNDARY OF BOX PENETRATION. SEAL WHERE INSULATION BUTTS AGAINST THE PANEL AND AROUND PERIMETER OF INSULATION TO CREATE VAPOR BARRIER. TYP OF ALL PIPE PENETRATIONS THROUGH BOX WALL. INSULATED WALL SILICONE SEALANT HOLE DIAMETER 1" GREATER THAN PIPE SECONDARY OR CONDENSATE PIPE PIPE INSULATION EXPANDING FOAM MOUNT REFRIGERATION CONTROL VALVES NEAR EDGE OF WALK-IN FOR SERVICE ACCESS FROM LADDERS. COORDINATE WITH EDGE PROTECTION NET SYSTEM. REF ARCHITECTURAL COPPER TO PVC CONNECTION OUTSIDE OF WALL AS REQUIRED. INSULATE COPPER PIPE OUTSIDE COOLER WALL PER SPECIFICATIONS PVC DRAIN TRAP OUTSIDE DRAIN PAN UNION PVC TERMINATE CONDENSATE DRAIN OVER HUB DRAIN OR SERVICE SINK WITH AIR GAP. PROVIDE RUNNING TRAP FOR INTERIOR CONDENSATE HEADERS RUNNING BETWEEN MULTIPLE WALK-INS OPERATING AT TEMPERATURES ABOVE FREEZING. TEMPORARY U-BEND BYPASS TO BE REMOVED BEFORE FINAL CONNECTION. REFERENCE U-BEND BYPASS DETAIL. PROVIDE SOLENOID VALVE, ONE PER COIL. PROVIDE COPPER CONDENSATE DRAIN PIPING FULL SIZE OF COIL DRAIN PAN CONNECTION AND SLOPE 1/8" PER 1'-0" TOWARD DRAIN. REFRIGERATION CONTRACTOR FURNISHED FIELD INSTALLED 1" ISOLATION BALL VALVE (TYP) PIPE SUPPORT. REFER TO HORIZONTAL REFRIGERANT LINE SUPPORT DETAIL ROOF OPENING TO ACCOMMODATE BOTH REFRIGERATION PIPING AND ELECTRICAL CONDUIT. REFER TO ARCH AND REFRIG PLANS. REFER TO ARCHITECTURAL DETAIL FOR INSTALLATION OF MANUFACTURED METAL CURB, INSULATION, AND SHEET METAL ENCLOSURE SUPPORT PIPING ON ROOF. REFER TO REFRIGERATION PIPING SUPPORT DETAIL. 3/4" CHARGING HOSE. CAP WITH CHAIN WHEN NOT IN USE. PROVIDE 3/4" MALE CONNECTION. MOUNT 60" AFF. PROVIDE CAP WITH CHAIN AND CAP WHEN NOT IN USE. CONNECTION SHALL TERMINATE OUTWARD, AWAY FROM WALL. ALL CHARGING STATION EQUIPMENT FURNISHED AND INSTALLED BY REFRIGERATION CONTRACTOR. PROVIDE 3/4" HOSE CONNECTION. PROVIDE 1" COPPER PIPING FROM GLYCOL FEEDER STATION TO PUMP SKID. PROVIDE SPARE STUB AND CAP END FOR FUTURE USE. (TYP) REFERENCE UNISTRUT PIPING SUPPORT DETAIL. PROVIDE TAG INDICATING SKID SERVED. REFER TO SPEC 15181 FOR PIPE LABELING REQUIREMENTS. TYPICAL OF EACH CHARGING LINE TO PUMP SKID. 6" PROVIDE PIPE LABELS AT EACH CONNECTION PER SPECIFICATION SECTION 15181. LABEL GLYCOL CHARGING LINE ON ROOF AS "GLYCOL CHARGING". REFER TO SPEC 15181 FOR LABELING REQUIREMENTS. BOLLARD. REFER TO ARCH. (TYP) SIDE VIEW VERTICAL PIPING SUPPORT. REFER TO VERTICAL REFRIGERANT LINE SUPPORT DETAIL ROUTE PIPING THROUGH NEW OR EXISTING WALL PENETRATIONS. REFER TO ARCH AND STRUCTURAL. SHEET: DRAWN BY: CHECKED BY: PROTO CYCLE: DOCUMENT DATE:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.P (407) 661-9100F (407) 661-9101c-p.comFlorida Corporate Certificate #AA C0005262600 Maitland Center ParkwaySuite #200Maitland, FL 32751CUSHING TERRELL306 W. RAIL ROAD SUITE 104MISSOULA, MT 59802Phone: (406)728-9522Fax: (406)728-8287EXISTING CONDITIONS WERE TAKEN FROM ORIGINAL DRAWINGS AND MAY NOT REFLECT EXACT "AS-BUILT" CONDITIONS. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR SHALL CAREFULLY COORDINATE NEW WORK AND DEMOLITION WITH ALL OTHER DISCIPLINES AND EXISTING CONDITIONS. EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES NOT RELIEVE THE RESPONSIBILITY OF PERFORMING THE WORK PROPERLY. NO ADDITIONAL COMPENSATION SHALL BE ALLOWED BECAUSE OF CONDITIONS THAT OCCUR DUE TO FAILURE TO FAMILIARIZE WORKERS WITH THIS KNOWLEDGE. DOCUMENTS WITHOUT SIGNATURE AND REQUIRED SEAL OF AOR/EOR ARE NOT FOR CONSTRUCTION R3.2 REFRIGERATION DETAILS GLYCOL DM20240347BOYNTON BEACH, FL11/07/2511/07/25STORE NO: 5911-2769006/27/25BOYNTON BEACH, FLSP3625 S FEDERAL HWY.NTS1CASE PIPING (HORIZONTAL OPTION) (GLYCOL) NTS2CASE PIPING (VERTICAL OPTION) (GLYCOL) NTS4ISOLATION VALVES (GLYCOL) NTS7 REMOTE EMERGENCY CHILLER CONNECTION (GLYCOL) NTS5END-OF-LOOP BYPASS VALVE (GLYCOL) NTS3PIPING VENT AND DRAIN INSTALLATION (GLYCOL) NTS9TEMPORARY U-BEND BYPASS (GLYCOL) NTS10CHARGING STATION (GLYCOL)NTS8ROOF PENETRATION (GLYCOL) NTS6FAN-COIL UNIT (GLYCOL) ISSUE BLOCK FLORI D No. 63660 L A STATE OFM YICHAE L J AMES AM E S TOPRROF ESSIONAL E N G INEEEICENSVOID