HomeMy WebLinkAboutRefrigeration Electrical Panel Schedules and Details - RE1.3SUPPORT CONDUIT FROM TOP
OR BOTTOM OF STRUCTURE
ONLY. DO NOT INSTALL
CONDUIT BELOW STRUCTURE.
ROOF OPENING MAY CONTAIN
MULTIPLE CONDUIT TYPES, SEE
ELECTRICAL AND BASR PLANS.
MINIMUM 2" GAP BETWEEN ADJACENT
CONDUITS.
OWNER PROVIDED
MANUFACTURED CURB, SEE
ARCHITECTURAL DETAILS FOR
SIZE, INSULATION, ASSEMBLY,
AND SEALING REQUIREMENTS
SUPPORT CONDUIT PER
SPECIFICATIONS, SEE ROOF SUPPORT
DETAIL.
REMOVABLE HOOD
PROVIDED WITH CURB.
DROP CONDUIT NEAR HOOD TO ALIGN WITH
ROOF SUPPORT HEIGHT IF NEEDED.
SECURE CONDUIT TO
UNISTRUT AT TOP OF
CURB
5" CENTER OF CONDUIT TO TOP OF CURB.
PAINT CONDUIT TO
MATCH ADJACENT
CEILING COLOR
TYPICAL REFRIGERATED CASE SYSTEM
12" WIRE PIGTAILS (TYP)
5' FLEX CONDUIT (TYP)
ROUTE EMT CONDUITS (UNDER CASES, ABOVE
SLAB) TO POINT OF TRANSITION TO FLEX
PROVIDE TRANSITION FROM EMT TO FLEX
BRANCH CIRCUIT AND EMS CONDUITS TO OTHER
REFRIGERATED CASE SYSTEMS (TYP)
BRACKET CONDUIT TO FLOOR
AS REQUIRED BY CODE (TYP)
ROUTE CONDUIT FOR BRANCH CIRCUITS FROM OVERHEAD
THRU CHASE, ALONG WITH REFRIGERATION PIPING (TYP)
PROVIDE (2) CONDUITS AND BRANCH CIRCUITS PER REFRIGERATED
CASE SYSTEM. ONE CONDUIT WILL SERVE 120V CASE FANS, LIGHTS
AND ANTI-SWEAT CIRCUITS; ONE CONDUIT WILL SERVE 208V CASE
ELECTRIC DEFROST CIRCUIT. ON SYSTEMS WITHOUT ELECTRIC
DEFROST, ONLY PROVIDE ONE CONDUIT
PROVIDE 5' LENGTH OF FLEX CONDUIT WITH 12" PIGTAIL STUBBED
FROM END OF EACH FLEX CONDUIT.
PVC CHASE
EMS CONDUIT: PROVIDE CONDUIT (WITH PULL WIRE) ROUTED 6"
ABOVE BOTTOM OF BAR JOIST IN SALES FLOOR ACCESSIBLE CEILING
SPACE THROUGH PVC CHASE. CONDUIT WILL BE SIZED 1" FOR (4) OR
FEWER EMS CABLES AND 1-1/4" FOR (5) OR MORE EMS CABLES.REAR HALF OF
REFRIGERATED CASE
DESIGNATED FOR
PIPING AND VALVES
FRONT HALF OF
REFRIGERATED CASE
DESIGNATED FOR
ELECTRICAL AND
BAS COMPONENTS
REFRIGERATED CASE CONTROLLER
REFER TO BASR PLANS FOR CASE
CONTROLLER TYPE, WIRING DETAILS,
AND CONTROLLER TERMINATION
POINTS, TYP
CONDUITS FOR REFRIGERATED CASE POWER. ONE CONDUIT WILL SERVE
120V FANS, LIGHTS, AND ANTI-SWEAT HEATERS CIRCUITS. ONE CONDUIT
WILL SERVE 208V ELECTRIC DEFROST CIRCUIT. REFER TO REFRIGERATION
ELECTRICAL PLANS IF ELECTRIC DEFROST IS REQUIRED AND FOR FEEDER
AND CONDUIT SIZES.
CONDUIT FOR DAISY CHAINED BASR CABLING. FROM PREVIOUS
BASR CONTROLLER OR MASTER CONTROLLER. REFER TO BASR
PLANS AND ONE-LINE DIAGRAM.
TO NEXT BASR CONTROLLER IN DAISY CHAIN
OR MASTER CONTROLLER. REFER TO BASR
PLANS AND ONE-LINE DIAGRAM.
CASE JUNCTION BOX FOR TRANSITION
FROM EMT TO FLEX CONDUIT, TYP.
FLEX CONDUITS FROM CASE JUNCTION BOX
TO CASE CONTROLLER, TYP. ONE CONDUIT FOR
120V CASE FANS, LIGHTS, AND ANTI-SWEAT
HEATERS CIRCUIT. ONE CONDUIT FOR
208V ELECTRIC DEFROST CIRCUIT.
REFRIGERATED CASE, TYP. REFER TO PLANS
FOR QUANTITY OF CASES ON CASE LINEUP.
ROUTE CONDUITS WITH REFRIGERATION
PIPING TO ACCESSIBLE JOIST SPACE.
REFER TO REFRIGERATION PLANS FOR
CHASE ROUTING DETAILS, IF REQUIRED.
EMT CONDUIT BETWEEN
CASE JUNCTION BOXES, TYP
PROVIDE CEILING MOUNTED MANUAL SWITCH 'HUBBELL' CLASS
HBLDS3 OR ‘EATON’CLASS AHDS30. IF OVER 30 AMPS PROVIDE
‘HUBBEL’CLASS HBLDS6 OR ‘EATON’AHDS60. WITH NEMA 4X
WATERTIGHT NON-METALLIC ENCLOSURE FOR CONNECTION
OF EVAPORATOR COIL FANS (CF) AND/OR ELECTRIC DEFROST
(ED), (WHERE SHOWN ON DRAWINGS). PROVIDE PLACARD ON
CEILING DETAILING PURPOSE OF EACH MANUAL SWITCH AND
THE ELECTRICAL SOURCE (PANEL AND CIRCUIT NUMBER).
NOTE: DO NOT LOCATE WP JUNCTION BOX DIRECTLY IN FRONT OF DISCHARGE FAN, OFFSET TO SIDE.
TYPICAL COIL
EMT CONDUIT AND WIRING TO NEXT
COIL POWER JUNCTION BOX ON SAME
SYSTEM WHEN MULTIPLE COILS ARE IN
SAME COOLER/FREEZER BOX. POWER
CONDUIT AND WIRING SAME SIZE AND
QUANTITY AS WIRING TO PANEL.
1" EMT CONDUIT
PENETRATION SEALED
WITH SILICONE SEALANT.
NOTE: TAP DEFROST CIRCUIT IN
JUNCTION BOX WITH #10 AWG FOR
CONNECTION TO UNIT. MAXIMUM
LENGTH OF TAP CONDUCTOR 18"
CONDULET AT CEILING PENETRATION
FILLED WITH SILICONE
COIL FAN/DEFROST POWER EMT CONDUIT
AND WIRING TO DESIGNATED PANEL VIA
WALK-IN FAN/DEFROST CONTROL DEVICE.
FINAL CONNECTION BY RC.
COOLER/FREEZER BOX CEILING
CEILING MOUNTED WP JUNCTION BOX WITH THREADED HUBS
AND GASKETED COVERPLATE. SEAL TOP OF JUNCTION BOX
TO COOLER/FREEZER CEILING WITH SILICONE SEALANT.
1" LIQUID-TIGHT FLEXIBLE METAL CONDUIT
TO KNOCKOUT ON UNIT. FINAL
CONNECTION TO COIL BY RC.
Ø
Ø
Ø
PROVIDE 208/3Ø HOME RUN TO DESIGNATED PANEL
BOARD . FINAL CONNECTION AT CASE BY R.C.
CALCULATION OF 3Ø UNBALANCED LOAD
B LOAD = (12.6 A + 12.6 A) x .866 = 21.8 A (HIGH LEG)
A LOAD = (12.6 A + 9.9 A) x .866 = 19.5 A
B LOAD = (12.6 A + 12.6 A) x .866 = 21.8 A (HIGH LEG)
C LOAD = (12.6 A + 9.9 A) x .866 = 19.5 A
NOTES:
ON SYSTEMS WITH UNEQUAL LOADS, REC
(REFRIGERATION ELECTRICAL CONTRACTOR) SHALL
ARRANGE CONNECTIONS FOR MAXIMUM BALANCE
A CCBBA
C
B
A
12.6 A 9.9 A12.6 A
4 DOOR CASE5 DOOR CASE5 DOOR CASE
TYPICAL REFRIGERATED CASE SYSTEM
NTS1ROOF PENETRATION (CONDUIT)
NTS2CASE CONNECTION WIRING (PVC CHASE)
NTS3CASE CONDUIT ROUTING
NTS4EVAPORATOR COIL WIRING
NTS5CASE DEFROST WIRING
SHEET:
DRAWN BY:
CHECKED BY:
PROTO CYCLE:
DOCUMENT DATE:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.P (407) 661-9100F (407) 661-9101c-p.comFlorida Corporate Certificate #AA C0005262600 Maitland Center ParkwaySuite #200Maitland, FL 32751CUSHING TERRELL306 W. RAIL ROAD SUITE 104MISSOULA, MT 59802Phone: (406)728-9522Fax: (406)728-8287EXISTING CONDITIONS WERE TAKEN FROM
ORIGINAL DRAWINGS AND MAY NOT REFLECT
EXACT "AS-BUILT" CONDITIONS. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS
PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR
SHALL CAREFULLY COORDINATE NEW WORK AND
DEMOLITION WITH ALL OTHER DISCIPLINES AND
EXISTING CONDITIONS.
EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING
A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND
SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE
TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES
NOT RELIEVE THE RESPONSIBILITY OF PERFORMING
THE WORK PROPERLY. NO ADDITIONAL
COMPENSATION SHALL BE ALLOWED BECAUSE OF
CONDITIONS THAT OCCUR DUE TO FAILURE TO
FAMILIARIZE WORKERS WITH THIS KNOWLEDGE.
DOCUMENTS WITHOUT
SIGNATURE AND REQUIRED
SEAL OF AOR/EOR ARE NOT
FOR CONSTRUCTION
RE1.3
REFRIGERATION
ELECTRICAL
PANEL
SCHEDULES
AND DETAILS
DM20240347BOYNTON BEACH, FL11/07/2511/07/25STORE NO: 5911-2769006/27/25BOYNTON BEACH, FLSP3625 S FEDERAL HWY.A. LEGEND: (N) NEW, (E ) EXISTING, (M) MODIFY, B. CONTROLLED VIA 100A-3P CONTACTOR
CIRCUIT NOTES:
MISCELLANEOUS 0.4 PER NEC 210.20(A) 0.5
WATER HEAT 0.0 100% 0.0
ELECTRIC HEAT 0.0 100% 0.0 DEMAND AMPS 33.9
KITCHEN EQUIPMENT 0.0 PER NEC 220.56 0.0 DEMAND LOAD (kVA):12.2
MOTORS 4.4 PER NEC 430.24 4.7
CONVENIENCE OUTLETS 1.6 PER NEC 220.44 1.6 CONNECTED AMPS:29.9
LIGHTING 4.4 PER NEC 210.20(A) 5.5 CONNECTED LOAD(kVA):10.8
LOAD CLASSIFICATION CONNECTED LOAD(kVA) FACTOR DEMAND LOAD PANEL TOTALS
30.8 31.7 27.2 TOTAL CONNECTED PHASE AMPS
3700 3800 3260 TOTAL CONNECTED PHASE VA
SPARE E 1 20 41 42 20 1 E SPACE
AS12 CASE LIGHTS (11) E 1 20 39 280 40 20 1 E SPACE
AS12 CASE FANS E 1 20 37 150 38 20 1 E SPACE
BS20 GLY CASE LIGHTS (11) M 1 20 35 60 36 20 1 E SPACE
BS20 GLY CASE FANS M 1 20 33 40 34 20 1 E SPACE
AS08 CASE FANS E 1 20 31 1100 32 20 1 E SPACE
AS07 CASE LIGHTS (11) E 1 20 29 1260 30 20 1 E SPARE
AS07 CASE FANS E 1 20 27 420 28 20 1 E SPARE
BS18 GLY CASE LIGHTS (11) M 1 20 25 50 26 20 1 E SPARE
BS18 GLY CASE FANS M 1 20 23 110 24 20 1 E SPARE
SPARE M 1 20 21 180 22 20 1 E AS11 EMS CONTROLLER
BS17 GLY CASE LIGHTS (11) M 1 20 19 90 180 20 20 1 E AS10 EMS CONTROLLER
BS17 GLY CASE FANS M 1 20 17 150 180 18 20 1 E AS08 CASE RECEPTACLE
AS04 CASE LIGHTS (11) E 1 20 15 590 180 16 20 1 E AS08 CASE RECEPTACLE
AS04 CASE FANS E 1 20 13 770 180 14 20 1 M BS17 GLY CASE RECEPTACLE
AS03 CASE LIGHTS (11) E 1 20 11 590 180 12 20 1 E AS04 CASE RECEPTACLE
AS03 CASE FANS E 1 20 9 770 180 10 20 1 E AS04 CASE RECEPTACLE
AS02 CASE LIGHTS (11) E 1 20 7 460 180 8 20 1 E AS03 CASE RECEPTACLE
AS02 CASE FANS E 1 20 5 550 180 6 20 1 E AS03 CASE RECEPTACLE
AS01 CASE LIGHTS (11) E 1 20 3 980 180 4 20 1 E AS02 CASE RECEPTACLE
AS01 CASE FANS E 1 20 1 360 180 2 20 1 E AS02 CASE RECEPTACLE
NOTES POLE AMP NO NO AMP POLE NOTESLOAD NAME
CKT BRK CKT PHASE A
LOAD (VA)
PHASE B
LOAD (VA)
PHASE C
LOAD (VA)
CKT BRK CKT
LOAD NAME
MODEL TYPE:EXISTING WIRES:4
MANUFACTURER:EXISTING PHASE:3 NOTES:YES
TYPE OF MAIN:100A MLO VOLTAGE:208Y/120 MOUNTING TYPE:EXISTING
LOCATION:HYBRID HOUSE DTA AMPS:100 MINIMUM AIC RATING:10,000
EXISTING PANEL: (E)CHA2
A. LEGEND: (N) NEW, (E ) EXISTING, (M) MODIFY, B. CONTROLLED VIA 100A-3P CONTACTOR
CIRCUIT NOTES:
MISCELLANEOUS 0.2 PER NEC 210.20(A) 0.2
WATER HEAT 0.0 100% 0.0
ELECTRIC HEAT 10.4 100% 10.4 DEMAND AMPS 47.6
KITCHEN EQUIPMENT 0.0 PER NEC 220.56 0.0 DEMAND LOAD (kVA):17.1
MOTORS 2.0 PER NEC 430.24 2.1
CONVENIENCE OUTLETS 0.7 PER NEC 220.44 0.7 CONNECTED AMPS:45.2
LIGHTING 3.0 PER NEC 210.20(A) 3.7 CONNECTED LOAD(kVA):16.3
LOAD CLASSIFICATION CONNECTED LOAD(kVA) FACTOR DEMAND LOAD PANEL TOTALS
44.2 41.6 49.8 TOTAL CONNECTED PHASE AMPS
5300 4990 5970 TOTAL CONNECTED PHASE VA
SPARE E 1 20 41 42 20 1 E SPACE
B06 CASE LIGHTS (11) E 1 20 39 460 40 20 1 E SPACE
B06 CASE A/S HTRS E 1 20 37 1670 38 20 1 E SPACE
B06 CASE FANS E 1 20 35 300 36 20 1 E SPACE
B05 CASE LIGHTS (11) E 1 20 33 550 34 20 1 E SPACE
B05 CASE A/S HTRS E 1 20 31 930 32 20 1 E SPACE
B05 CASE A/S HTRS E 1 20 29 1040 30 20 1 E SPACE
B05 CASE FANS E 1 20 27 350 28 20 1 E SPACE
B04 CASE LIGHTS (11) E 1 20 25 430 26 20 1 E SPACE
B04 CASE A/S HTRS (6) E 1 20 23 1560 24 20 1 E SPACE
B04 CASE FANS E 1 20 21 280 22 20 1 E SPACE
B03 CASE LIGHTS (11) E 1 20 19 430 20 20 1 E SPACE
B03 CASE A/S HTRS E 1 20 17 1560 18 20 1 E SPACE
B03 CASE FANS E 1 20 15 280 16 20 1 E SPACE
B02 CASE LIGHTS (11) E 1 20 13 460 120 14 20 1 M BS19 GLY CASE FANS
B02 CASE FANS E 1 20 11 300 100 12 20 1 M BS19 GLY CASE LIGHTS
B02 CASE A/S HTRS E 1 20 9 1670 180 10 20 1 E B07 EMS CONTROLLER
B01 CASE LIGHTS (11) E 1 20 7 550 180 8 20 1 E B06 CASE RECEPTACLE
B01 CASE A/S HTRS E 1 20 5 930 180 6 20 1 E B04 CASE RECEPTACLE
B01 CASE A/S HTRS E 1 20 3 1040 180 4 20 1 E B03 CASE RECEPTACLE
B01 CASE FANS E 1 20 1 350 180 2 20 1 E B02 CASE RECEPTACLE
NOTES POLE AMP NO NO AMP POLE NOTESLOAD NAME
CKT BRK CKT PHASE A
LOAD (VA)
PHASE B
LOAD (VA)
PHASE C
LOAD (VA)
CKT BRK CKT
LOAD NAME
MODEL TYPE:EXISTING WIRES:4
MANUFACTURER:EXISTING PHASE:3 NOTES:YES
TYPE OF MAIN:100A MLO VOLTAGE:208Y/120 MOUNTING TYPE:EXISTING
LOCATION:HYBRID HOUSE DTB AMPS:100 MINIMUM AIC RATING:10,000
EXISTING PANEL: (E)CHB1
A. LEGEND: (N) NEW, (E ) EXISTING, (M) MODIFY
CIRCUIT NOTES:
MISCELLANEOUS 1.1 PER NEC 210.20(A) 1.4
WATER HEAT 0.0 100% 0.0
ELECTRIC HEAT 1.1 100% 1.1 DEMAND AMPS 29.4
KITCHEN EQUIPMENT 0.0 PER NEC 220.56 0.0 DEMAND LOAD (kVA):10.6
MOTORS 5.0 PER NEC 430.24 5.2
CONVENIENCE OUTLETS 0.0 PER NEC 220.44 0.0 CONNECTED AMPS:26.3
LIGHTING 2.3 PER NEC 210.20(A) 2.9 CONNECTED LOAD(kVA):9.5
LOAD CLASSIFICATION CONNECTED LOAD(kVA) FACTOR DEMAND LOAD PANEL TOTALS
24.4 29.2 25.1 TOTAL CONNECTED PHASE AMPS
2930 3505 3015 TOTAL CONNECTED PHASE VA
SPARE E 1 20 41 42 20 1 E SPACE
SPARE E 1 20 39 40 20 1 E SPACE
SPARE E 1 20 37 38 20 1 E SPACE
SPARE E 1 20 35 36 20 1 E SPACE
CU5 CASE FANS & LTS N 1 20 33 1110 34 20 1 E SPACE
BS09 GLY COIL FANS M 1 20 31 220 32 20 1 E SPACE
BS08 GLY COIL FANS M 1 20 29 305 30 20 1 E SPACE
BS07 GLY CASE LIGHTS (11) M 1 20 27 140 28 20 1 E SPACE
BS07 GLY CASE FANS M 1 20 25 145 26 20 1 E SPACE
BS06 GLY CASE LIGHTS (11) M 1 20 23 190 24 20 1 E SPACE
BS06 GLY CASE FANS M 1 20 21 325 22 20 1 E SPACE
BS05 GLY CASE LIGHTS (11) M 1 20 19 250 20 20 1 E SPACE
BS05 GLY CASE FANS M 1 20 17 410 18 20 1 E SPACE
BS04 GLY CASE LIGHTS (11) M 1 20 15 195 245 16 20 1 M BS14 GLY CASE LIGHTS (11)
BS04 GLY CASE FANS M 1 20 13 135 205 14 20 1 M BS14 GLY CASE FANS
BS03 GLY CASE LIGHTS (11) M 1 20 11 245 650 12 20 1 E BS13 COIL FANS
BS03 GLY CASE FANS M 1 20 9 210 430 10 20 1 E BS12 COIL FANS
BS02 GLY CASE LIGHTS (11) M 1 20 7 165 540 8 20 1 E BS11 COIL FANS
BS02 GLY CASE FANS M 1 20 5 135 1080 6 20 1 E BS10 COIL FANS
BS01 GLY CASE LIGHTS (11) M 1 20 3 220 630 4 20 1 E DAIRY COOLER DOOR LTS (11)
BS01 GLY CASE FANS M 1 20 1 170 1100 2 20 1 E DAIRY COOLER DOOR HTRS
NOTES POLE AMP NO NO AMP POLE NOTESLOAD NAME
CKT BRK CKT PHASE A
LOAD (VA)
PHASE B
LOAD (VA)
PHASE C
LOAD (VA)
CKT BRK CKT
LOAD NAME
MODEL TYPE:EXISTING WIRES:4
MANUFACTURER:EXISTING PHASE:3 NOTES:YES
TYPE OF MAIN:100A MLO VOLTAGE:208Y/120 MOUNTING TYPE:EXISTING
LOCATION:HYBRID HOUSE DTB AMPS:100 MINIMUM AIC RATING:10,000
EXISTING PANEL: (E)CHB2