REF PLAN
NOTE #2
7
S2
EXIST ROOFSLOPE DOWNREF PLAN
NOTE #1
6
S2
TYP
DTB GLY
(2796 LBS)
REF PLAN
NOTE #1
EXISTING
SKYLIGHT, TYP
RACK ETR (FIELD VERIFY SPACING)EXISTING STEEL JOISTS AT 5'-8" ± OC, TYP5
C
D EXISTING JOIST GIRDER, TYPNEW ROOFTOP
CONDENSING UNIT ON
CAPPED CURB, REF ARCH
& REFRIGERATION5
S2
4
S2
TYP
CU5
(1400 LBS)
LOCATE CL OF
SUPPORT CHANNEL
3" MAX FROM CL
BEAM GIRDER
EXIST ROOFSLOPE DOWNEXISTING CMU WALL
REF PLAN
NOTE #1
EXISTING
BEAM GIRDER 5' - 5" ±(FIELD VERIFY SPACING)EXISTING STEEL JOISTS AT 5'-1"± OC, TYPEXISTING ROOF
DECK TO REMAIN
ATTACH CURB TO
CHANNEL WITH
#12 TEK SCREWS AT
12" OC, TYP 2 SIDES
1/8 1
1/8 1
CHANNEL TO
JST THROUGH
DECK, TYP
C6x8.2 CONT
INSTALLED OVER
EXISTING ROOF DECK
FIELD ADJUSTABLE
CAPPED CURB PER
CURB SUPPLIER
EXISTING JOIST
TO REMAIN
PROVIDE FIELD STRUT
PER 10-S2 AS REQD
CONDENSING UNIT, REF
REFRIGERATION
NOTE:
ATTACH UNIT TO UNISTRUT
WITH STAINLESS STEEL BOLTS.
REF UNIT SUPPLIER FOR BOLT
QUANTITY, SIZE AND LAYOUT.
4" TYP
EXISTING JOIST
TO REMAIN, TYP
C6x8.2 CONT INSTALLED
OVER EXISTING ROOF DECK
EXISTING ROOF
DECK TO REMAIN
PROVIDE FIELD STRUT
PER 10-S2 AS REQD
NOTE:
REF 4-S2 FOR INFORMATION
SHOWN BUT NOT NOTED.
EXISTING ROOF
DECK TO REMAIN
ATTACH CURB TO CHANNEL
WITH #14 TEK SCREWS AT
12" OC, TYP 2 SIDES
1/8 1
1/8 1
CHANNEL TO
JST THROUGH
DECK, TYP
C6x13 CONT INSTALLED
OVER EXISTING ROOF DECK
CAPPED CURB BY
CURB SUPPLIER
EXISTING JOIST
TO REMAIN
PROVIDE FIELD STRUT
PER 8-S2 OR
10-S2 AS REQD
REFRIGERATION
EQUIP, REF
REFRIGERATION
FASTEN EA SIDE OF SKID TO EA
CURB SUPPORT RAIL WITH 5/8" DIA
ASTM F593 TYPE 304 BOLTS AT 3/4"
MOUNTING HOLES AND 1/2" DIA
BOLTS AT 5/8" MOUNTING HOLES
CAPPED CURB
SUPPORT RAIL
4" TYP
EXISTING JOIST
TO REMAIN, TYP
NEW STL CHANNEL
INSTALLED OVER EXISTING
ROOF DECK; REF 2-S2
EXISTING ROOF
DECK TO REMAIN
PROVIDE FIELD
STRUT PER 8-S2 OR
10-S2 AS REQD
NOTE:
REF 6-S2 FOR INFORMATION
SHOWN BUT NOT NOTED.
CAPPED CURB
SUPPORT RAIL
REF 6-S2 FOR EQUIPMENT
TO CURB SUPPORT RAIL
CONNECTION
ATTACH CURB TO
DECKING WITH #12
TEK SCREWS AT 6" OC
EXISTING
ROOF DECK
L3x3x3/16, TYP
ATTACH ROOF DECK
TO ANGLE WITH #12
TEK SCREWS AT 6" OC
NON-STRUCTURAL
ROOF CURB
ATTACH CURB TO
DECKING WITH #12
TEK SCREWS AT 6" OC
ATTACH ROOF DECK
TO ANGLE WITH #12
TEK SCREWS AT 6" OC
L3x3x3/16, TYP
EXISTING
ROOF DECK
CL OF JOIST
3/16 2
3/16 2
1/8 1
1/8 1 TYP
SECTION A SECTION B
NON-STRUCTURAL
ROOF CURB
EXISTING JOIST
TOP CHORD
3/16 2
3/16 2
CL OF
EXISTING JOIST
VERIFYFIELDVERIFY
FIELDVERIFYFIELD CL OF
EXISTING JOIST
PLAN VIEW
CONCENTRATED
LOAD, REF NOTE
GREATER
3" OR
CONCENTRATED
LOAD, REF NOTE
GREATER
3" OR
GENERAL CONTRACTOR TO PROVIDE AND INSTALL
FIELD STRUT (L2x2x3/16) EACH SIDE OF JOIST AT ALL
LOCATIONS WHERE CONCENTRATED LOAD DOES
NOT OCCUR WITHIN 3" OF A PANEL POINT. INSTALL
ANGLE WITH ONE END AT LOCATION OF LOAD AND
OTHER END AT A PANEL POINT ON THE OPPOSITE
CHORD, TYP. ANGLES SHALL BE INSTALLED PRIOR
TO NEW LOAD BEING APPLIED TO THE JOIST
TYP EACH
END EACH
ANGLE1/8 1
1/8 1
TOP CHORD PANEL
BOTTOM CHORD PANELNOTE:
PROVIDE JOIST REINF IN ACCORDANCE WITH THIS DETAIL
FOR ALL CONCENTRATED LOADS IN EXCESS OF 100 LBS.
WHERE MORE THAN ONE CONCENTRATED LOAD EXISTS
WITHIN A CHORD PANEL AND THE SUM OF THOSE LOADS
EXCEEDS 100 LBS, PROVIDE JOIST REINFORCEMENT AS
DETAILED SUCH THAT THE SUM OF THE LOADS WITHIN
THE REMAINING UNSUPPORTED CHORD LENGTH DOES
NOT EXCEED 100 LBS.
JOIST TOP
CHORD
JOIST BOTTOM
CHORD
CONCENTRATED
LOAD
PROVIDE AND INSTALL VERTICAL WEB
REINFORCEMENT PER 6-S2 AT ANY
LOCATIONS WHERE A NEW
CONCENTRATED LOAD OCCURS
WITHIN 3" OF THE VERTICAL WEB
JOIST TOP
CHORD
JOIST BOTTOM
CHORD
NOTE:
VERTICAL WEB REINF IS ONLY
REQUIRED IF EXISTING JOIST
HAS VERTICAL WEB MEMBERS.
3" OR LESS
1. REF 9-S2 FOR SUPPORT FRAMING AT PIPE PENETRATION; FRAMING NOT REQUIRED
FOR OPENINGS LESS THAN 10"x10"; FIELD VERIFY LOCATION ONCE UNIT HAS BEEN
INSTALLED. REF REFRIG FOR EXACT SIZE AND LOCATION OF PENETRATION.
2. NEW DTA GLY ON CAPPED CURB, REF REFRIG; ALIGN ONE SIDE OF CURB WITH
EXISTING JOIST GIRDER BELOW.
ROOF FRAMING PLAN NOTES
NOTE:
1. CONTRACTOR SHALL FIELD LOCATE ALL VERTICAL
WALL REINFORCEMENT PRIOR TO CUTTING WALL.
PER ORIGINAL CONSTRUCTION DOCUMENTS
EXISTING REINFORCEMENT SHOULD BE (2) #6 BAR
AT 24" OC AT SIM. IF FIELD CONDITIONS PROHIBIT
INSTALLATION AS SHOWN, CONTACT WALMART
CONSTRUCTION MANAGER IMMEDIATELY.
NOTE:
DO NOT CUT OPENING
WITHIN 2'-0" OF EXISTING
CONTROL JOINT
REF ARCH (FIELD VERIFY
TO OPENING EL)
EXISTING VERT
REINF REF NOTE #1
TYP
EXISTING VERT
REINF REF NOTE #1
PRE-DRILL ANGLES
FOR 1/4" x 1" TAPCON
SCEWS AT 16" OC, TYP
FOR OPENING
REF ARCH8"
EXISTING
REINF CELL LOCATE EXISTING WALL REINF
(REF NOTE #1) AND LOCATE
EDGE OF OPENING SHOWNSECTIONNOTE:
CAULK ALL ANGLE
EDGES AND PAINT
TO MATCH.
NOTE:
NO REINFORCEMENT
SHALL BE CUT
SECTION A -12" CMU
AT SIM8"EXISTING 12"
CMU WALL
GRIND CORNERS OF CMU
WALL AS REQUIRED TO ALLOW
BOTH LEGS OF ANGLE TO BE
TIGHT AGAINST CMU, TYP
L4x4x1/4; MITER
CORNERS P (407) 661-9100F (407) 661-9101c-p.comFlorida Corporate Certificate #AA C0005262600 Maitland Center ParkwaySuite #200Maitland, FL 32751ENGINEER OF RECORD:
BENJAMIN BRYAN BAILEY, P.E.
930 CENTRAL ST.
KANSAS CITY, MO 64105
FL LICENSE #88408JOHNSTONBAURKHOLDERSSOCIATESc o n s u l t i n g s t r u c t u r a l e n g i n e e r s930 C 816.421.4200 ·· K C MO ENTRAL ANSASITY,64105 WWW.JBAENGR.COMSHEET:
DRAWN BY:
CHECKED BY:
PROTO CYCLE:
DOCUMENT DATE:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.JBA NO. 25350059111/6/2026 2:34:12 PMS2
ROOFTOP
EQUIPMENT
PLANS AND
DETAILS
POI20240347BOYNTON BEACH, FL11/07/2511/07/25STORE NO: 05911 - 2769006/27/25BOYNTON BEACH, FLJSH3625 S FEDERAL HWY1/8" = 1'-0"2 ROOF FRAMING PLAN - PUMP SKID SUPPORT FRAMING
1/8" = 1'-0"3 ROOF FRAMING PLAN - RCU SUPPORT FRAMING
3/4" = 1'-0"4
REMOTE CONDENSER
ROOF CURB SUPPORT
3/4" = 1'-0"5
REMOTE CONDENSER
ROOF CURB SUPPORT
3/4" = 1'-0"6 REFRIGERATION EQUIPMENT SUPPORT
3/4" = 1'-0"7 REFRIGERATION EQUIPMENT SUPPORT
NTS9PIPE PENETRATION SUPPORT FRAMING
6.0-23/4" = 1'-0"10 JOIST REINFORCING AT CONCENTRATED LOAD
5.0-2 3/4" = 1'-0"8 JOIST VERTICAL WEB REINFORCING AT REFRIG EQUIP
1/2" = 1'-0"1 NEW OPENING IN EXISTING WALL
S3-X1