HomeMy WebLinkAboutRefrigeration Electrical Plans - RE1, RE1.1, RE1.2, RE1.32 3 4 5
C
D
E
F
G
H
I
NEW
CU5 TCO2
(ON ROOF)
NEW
DTB GLY
(ON ROOF)
ROOF
PENETRATION
FOR CONDUIT
ETR
DTB DX
RACK
ETR
DTA DX
RACK
EXISTING ROOF
MOUNTED
COMPRESSOR
HOUSES
REFRIGERATED
CASES
EVAP COILS
DELI
COOLER
1 2 3 4
D
E
F
G
H
I
BAKERY
COOLERTYP
16.492
TYP
16.492
REFRIGERATED
CASES
TYP
16.492
REFRIGERATED
CASES
TYP
16.492
EXISTING
ROOFTOP SPLIT
SUCTION HYBRID
HOUSE DTB
EXISTING
ROOFTOP SPLIT
SUCTION HYBRID
HOUSE DTA
COORDINATE DEMOLITION OF
EXISTING OGP CASE ELECTRICAL
CIRCUITS WITH WALMART
CONSTRUCTION MANAGER.
SHEET:
DRAWN BY:
CHECKED BY:
PROTO CYCLE:
DOCUMENT DATE:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.P (407) 661-9100F (407) 661-9101c-p.comFlorida Corporate Certificate #AA C0005262600 Maitland Center ParkwaySuite #200Maitland, FL 32751CUSHING TERRELL306 W. RAIL ROAD SUITE 104MISSOULA, MT 59802Phone: (406)728-9522Fax: (406)728-8287EXISTING CONDITIONS WERE TAKEN FROM
ORIGINAL DRAWINGS AND MAY NOT REFLECT
EXACT "AS-BUILT" CONDITIONS. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS
PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR
SHALL CAREFULLY COORDINATE NEW WORK AND
DEMOLITION WITH ALL OTHER DISCIPLINES AND
EXISTING CONDITIONS.
EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING
A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND
SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE
TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES
NOT RELIEVE THE RESPONSIBILITY OF PERFORMING
THE WORK PROPERLY. NO ADDITIONAL
COMPENSATION SHALL BE ALLOWED BECAUSE OF
CONDITIONS THAT OCCUR DUE TO FAILURE TO
FAMILIARIZE WORKERS WITH THIS KNOWLEDGE.
DOCUMENTS WITHOUT
SIGNATURE AND REQUIRED
SEAL OF AOR/EOR ARE NOT
FOR CONSTRUCTION
RE1
OVERALL
REFRIGERATION
ELECTRICAL
PLAN
DM20240347BOYNTON BEACH, FL11/07/2511/07/25STORE NO: 5911-2769006/27/25BOYNTON BEACH, FLSP3625 S FEDERAL HWY.KEYNOTES
16.492 E.C. SHALL COORDINATE WITH GENERAL
CONTRACTOR AND ARCHITECTURAL
DEMOLITION PLANS THE EXTENT OF ELECTRICAL
DEMOLITION. REMOVE UNUSED DEVICES,
BOXES, CONDUITS, AND WIRING BACK TO
ORIGINATING JUNCTION BOXES OR
PANELBOARDS. REFERENCE POWER PLANS FOR
CIRCUITRY TO BE REUSED. DEMOLITION SHALL
NOT AFFECT ACTIVE CIRCUITS. IF CIRCUIT IS
DEMOLISHED ALL THE WAY TO PANELBOARD,
REMOVE CIRCUIT BREAKER AND REPLACE WITH
FILLER PLATE. UPDATE TYPEWRITTEN CIRCUIT
DIRECTORY IDENTIFYING CIRCUIT AS "SPACE".
COORDINATE EXACT REQUIREMENTS WITH
EXISTING CONDITIONS PRIOR TO BID.
1. COORDINATE ALL WORK WITH REFRIGERATION
CONTRACTOR (R.C.) PRIOR TO INSTALLATION.
2. REFRIGERATED CASES: E.C. SHALL PROVIDE CONDUIT
AND WIRE FOR REFRIGERATED CASE FANS, LIGHTS
AND ANTI-SWEAT HEATERS, AND (IF APPLICABLE)
ELECTRICAL DEFROST. PROVIDE ADEQUATE
CONDUCTOR LENGTH TO ALLOW TERMINATION.
NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND
LABEL EACH CIRCUIT WITH BRANCH CIRCUIT
DESIGNATION AND REFRIGERATION SYSTEM NUMBER
FOR FINAL TERMINATION AT CASE BY R.C. REF CASE
CONNECTION WIRING DETAIL.
3. IF NEW CASES ARE PROVIDED WITH A FACTORY
INSTALLED TERMINAL STRIP AND JUMPERS FOR
CONNECTION TO A SINGLE CIRCUIT FOR 120V CASE
LOADS. RC SHALL REMOVE FACTORY INSTALLED
JUMPERS AS REQUIRED TO UTILIZE EXISTING
SEPARATE 120V FAN/LIGHT/ANTI-SWEAT CIRCUITS AS
INDICATED ON PLANS AND/OR PANELBOARD
SCHEDULES. ANY EXISTING ANTI-SWEAT CONTROL
(SWEATMISER) SHALL BE BY-PASSED. CASES UTILIZING
ELECTRICAL DEFROST WILL BE PROVIDED WITH
SEPARATE 208V TERMINATIONS AT THE TERMINAL
STRIP FOR CONNECTION TO THE 208V ELECTRIC
DEFROST CIRCUIT. RC SHALL MAKE FINAL
TERMINATIONS OF 120V AND 208V POWER CIRCUIT(S)
AT CASE TERMINAL STRIP. REFER TO CASE
CONNECTION SCHEMATIC ON REFRIGERATION
SHEETS.
4. WALK-IN UNITS: PROVIDE CONDUIT AND WIRE FOR
EVAPORATOR COIL FANS (CF) AND (IF APPLICABLE)
ELECTRIC DEFROST (ED). PROVIDE ADEQUATE
CONDUCTOR LENGTH TO ALLOW TERMINATION.
NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND
LABEL EACH CIRCUIT WITH BRANCH CIRCUIT
DESIGNATION AND REFRIGERATION SYSTEM NUMBER
FOR FINAL TERMINATION AT COIL BY R.C. REF
EVAPORATOR COIL WIRING DETAIL.
5. ROUTE REFRIGERATED CASE AND WALK-IN UNIT COIL
FAN, LIGHTS, ANTI-SWEAT AND DEFROST BRANCH
CIRCUITS TO WIREWAYS PROVIDED AT
REFRIGERATION EQUIPMENT AND/OR PANELBOARDS
AS REQUIRED.
6. REFRIGERATED CASE WIRING COMPARTMENT
REPRESENTED ON DRAWING BY JUNCTION BOX.
7. KEEP PENETRATIONS THROUGH WALK-IN UNITS
TO A MINIMUM. ROUTE ALL CONDUITS SERVING
FREEZERS AND COOLERS ON INSIDE OF BOX.
8. ALL CONDUITS INSTALLED ON TOP OF WALK-IN UNITS
SHALL BE A MINIMUM OF 6" FROM ANY EDGE TO ALLOW
SPACE FOR EDGE PROTECTION NETTING. DO NOT
ROUTE CONDUITS ABOVE THE CEILING GRID ACCESS
UNLESS CONDUITS ARE INSTALLED IN JOIST SPACE,
REF ARCH.
9. UNDERSLAB CIRCUITS SHALL NOT BE ROUTED UNDER
WALK-IN FREEZERS AND SHALL BE ROUTED ABOVE
REFRIGERANT LINES WHERE THEY CROSS.
10. CIRCUITS FOR REFRIGERATED CASES SERVED BY
UNDERSLAB REFRIGERATION PIPING ARE TO BE
ROUTED UNDERSLAB AND EXTENDED TO THE FIRST
CASE IN EACH SYSTEM. WIRING AND CONDUIT FOR
SLAVE WIRING BETWEEN CASES SHALL BE PROVIDED
BY R.C. REFER TO UNDERSLAB CASE CONNECTION
WIRING DETAIL.
11. ALL UNDERSLAB CONDUITS SHALL BE 3/4" MIN.
12. CIRCUITS FOR REFRIGERATED CASES SERVED BY
OVERHEAD REFRIGERATION PIPING ARE TO BE
ROUTED DOWN FROM STRUCTURE AT THE SAME
LOCATION AS THE REFRIGERATION PIPING AND
EXTENDED TO THE FIRST CASE IN EACH SYSTEM. WIRE
AND CONDUIT FOR SLAVE WIRING BETWEEN CASES
SHALL BE PROVIDED BY THE R.C. REFER TO
OVERHEAD CASE CONNECTION WIRING DETAIL.
13. ON GROUPS OF THREE OR MORE REFRIGERATED
CASES WITH ELECTRIC DEFROST, R.C. SHALL
CONNECT CASES TO CREATE A THREE-PHASE HEATER
CIRCUIT. HEATER LOADS SHALL BE BALANCED
BETWEEN PHASES AS EVENLY AS POSSIBLE. REF
CASE DEFROST WIRING DETAIL.
14. PROVIDE A SEPARATE NEUTRAL FOR EACH NEW
BRANCH CIRCUIT SERVING REFRIGERATED CASES OR
WALK-IN UNITS.
15. PROVIDE CIRCUIT BREAKER LOCKING DEVICE (LOCK-
OFF FOR MAINTENANCE) ON NEW AND/OR EXISTING
CIRCUIT BREAKERS SERVING REFRIGERATED CASES.
16. REFERENCE ARCHITECTURAL DEMOLITION PLANS FOR
FULL EXTENT OF DEMOLITION WORK REQUIRED.
GENERAL REFRIGERATION
ELECTRICAL NOTES
08.28.20
FOR LOCKOUT TAG OUT PROCEDURES REFER TO
SPECIFICATION SECTION 01351 AND THE MASTER
CONSTRUCTION AGREEMENT FOR WALMART
GLOBAL ETHICS AND COMPLIANCE, "COMPLIANCE
PERFORMANCE STANDARD FOR CONSTRUCTION."
A
R
S
OS
B
DH
J
SS
OS2S
OSS
3S
4S
DS
MS
VSS
KS
S SINGLE POLE SWITCH
CIRCUIT, CONCEALED IN WALLS OR
CEILING, E INDICATES EXISTING WIRING
SMOKE DETECTOR
SAIL SWITCH
JUNCTION BOX
HORN / STROBE
ABBREVIATIONS
BUZZER
CIRCUIT, CONCEALED IN SLAB FLOOR,
E INDICATES EXISTING WIRING
CONDUIT SLEEVE
SURFACE MOUNTED PANELBOARD
FLUSH MOUNTED PANELBOARD
CIRCUIT, EXPOSED,
E INDICATES EXISTING WIRING
LOW VOLTAGE WIRING
TELEPOWER POLE
TELEPHONE / DATA BOX FOR ISD
TELEPHONE, FLUSH FLOOR
PUSH BUTTON
MOTOR
ALARM JUNCTION BOX,
FOR REMOTE TEST/RESET
(WALL MOUNTED/CEILING MOUNTED)
EQUIPMENT CONNECTION POINT
(PROVIDED WITH EQUIPMENT)
NON-FUSED DISCONNECT
RECEPTACLE, PLUG-MOLD
RECEPTACLE, SIMPLEX
RECEPTACLE, SPECIAL
JUNCTION BOX
(WALL MOUNTED/CEILING MOUNTED)
ALARM JUNCTION BOX,
(WALL MOUNTED/CEILING MOUNTED)
RECEPTACLE, DOUBLE DUPLEX,
ISOLATED GROUND
FUSED DISCONNECT
4-WAY SWITCH
RECEPTACLE, DUPLEX ISOLATED
GROUND FLUSH FLOOR
RECEPTACLE, DOUBLE DUPLEX
RECEPTACLE, DUPLEX FLUSH FLOOR
VARIABLE SPEED SWITCH
KEYED SWITCH
DIMMER SWITCH
RECEPTACLE, DUPLEX,
MOUNTED HORIZONTALLY
RECEPTACLE, DUPLEX
MANUAL MOTOR SWITCH
3-WAY SWITCH
RECEPTACLE, DUPLEX
ISOLATED GROUND
LIGHT FIXTURE,
NIGHT LIGHT
VOLUMETRIC LIGHT FIXTURE
LIGHT FIXTURE
(WALL MOUNTED/CEILING MOUNTED)
LIGHT FIXTURE
(SYMBOLS APPLY ONLY WHEN USED ON DRAWINGS)
SYMBOL DESCRIPTION
RECEPTACLE, DUPLEX TWIST LOCK,
ISOLATED GROUND, L5-15R, UNO
SINGLE POLE OCCUPANCY
SENSOR SWITCH
LOW VOLTAGE CABLE
BOX FOR OTHER
DOOR HOLD OPEN
RECEPTACLE, DUPLEX TWIST LOCK,
L5-15R, UNO
RECEPTACLE, SIMPLEX TWIST LOCK,
ISOLATED GROUND, L5-15R, UNO
RECEPTACLE, SIMPLEX TWIST LOCK,
L5-15R, UNO
OCCUPANCY SENSOR SWITCH,
ONE-DIRECTION SENSING
RECEPTACLE, GFI
DOUBLE POLE OCCUPANCY
SENSOR SWITCH
T THERMOSTAT
(WALL MOUNTED/CEILING MOUNTED)
EXIT FIXTURE
(WALL MOUNTED/CEILING MOUNTED)
EMERGENCY LIGHT
(WALL MOUNTED/CEILING MOUNTED)
EMERGENCY LIGHT REMOTE HEADS
(WALL MOUNTED/CEILING MOUNTED)
a, b, c LOWER CASE LETTERS INDICATE
SWITCHING CONFIGURATION
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
C CONDUIT
CCT CIRCUIT
CF CEILING FAN
CW CASH WRAP
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
G GROUND
GC GENERAL CONTRACTOR
GFEP GROUND FAULT EQUIPMENT PROTECTION
GFI GROUND FAULT CIRCUIT INTERRUPTER
HD HAND DRYER
IG ISOLATED GROUND
LCU LIGHTING CONTROL UNIT
NL NIGHT LIGHT
NTS NOT TO SCALE
REC REFRIGERATION ELECTRICAL CONTRACTOR
RC REFRIGERATION CONTRACTOR
RH RADIANT HEATER
SC SECURITY CAMERA
TR TAMPER RESISTANT
TYP TYPICAL
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
WH WATER HEATER
WP WEATHER PROOF
WR WEATHER RESISTANT
ELECTRICAL SYMBOLS
LEGEND
TIME CLOCKTC
TRACK LIGHTING
12.17.21
OS OCCUPANCY SENSOR SWITCH,
FOUR-DIRECTION SENSING
1" = 20'-0"2 OVERALL REFRIGERATION ELECTRICAL PLAN
1" = 20'-0"1 REFRIGERATION ELECTRICAL DEMO PLAN
ARC FLASH HAZARD WARNING LABELING REQUIREMENTS
PER NEC ARE PROVIDED BY OWNER UNDER SEPARATE
CONTRACT.
ARC FLASH
CONTRACTOR TO VERIFY THE FEEDER ORIGINATION
POINT SOURCE OF POWER FOR ALL DISTRIBUTION
BOARDS, PANELBOARDS, AND BUSWAY AFFECTED BY
THE REMODEL SCOPE OF WORK. PROVIDE A
LAMINATED PLASTIC NAMEPLATE PER SPECIFICATIONS
INDICATING THIS INFORMATION.
EXAMPLES:
H1A FED FROM MSWB
L1D FED FROM H1B VIA T1D
SOURCE OF SUPPLY NOTE
COORDINATE ALL WORK THAT REQUIRES POWER
INTERRUPTIONS TO THE STORE WITH THE STORE
MANAGER AND THE WALMART CONSTRUCTION MANAGER
A MINIMUM OF 48 HOURS IN ADVANCE OF ALL STORE
POWER INTERRUPTIONS. IN ADDITION, IF THE MAIN
ELECTRICAL SWITCHGEAR REQUIRES WORK AND DOES
NOT HAVE A MAIN SERVICE DISCONNECTING MEANS,
COORDINATE WITH THE UTILITY COMPANY A MINIMUM OF
TWO WEEKS IN ADVANCE OF THE STORE POWER
INTERRUPTION. IF STORE IS NOT OPEN 24 HOURS PER
DAY, ALL STORE POWER INTERRUPTIONS ARE TO BE
ACCOMPLISHED AFTER NORMAL STORE BUSINESS
HOURS. PROVIDE TEMPORARY POWER AS REQUIRED
PER SPECIFICATIONS. INSTALLATION OF NEW EQUIPMENT
SHALL BE COMPLETED AND THE POWER SYSTEM TESTED
AND RE-ENERGIZED PRIOR TO THE TIME ESTABLISHED BY
THE STORE MANAGER AND THE WALMART
CONSTRUCTION MANAGER.
POWER INTERRUPTION NOTE
11.30.18
ISSUE BLOCK
Not part of this application. A
permit application shall be
submitted for interior remodeling.
J J
J
J
J
J J J J
JJJ
J J J
J
KE2-RE2-40(BS08 GLY)KE2-RE2-40(BS09 GLY)J
J
J
J
J
J J
J J
JJ
J
CF
J
CF
C
J
J
J
2
BASR3.2
1 2 3 4 5
C
D
E
BS05a GLY BS05b GLY BS05c GLY BS06a GLY BS06b GLY
BS01a GLY BS01b GLY BS01c GLY BS02a GLY BS02b GLY
BS03a GLY BS03b GLY BS03c GLY BS04a GLY BS04b GLY
BS04c GLYBS07a GLYBS07b GLYBS20 GLYBS19b GLYBS19a GLY
BS18 GLY BS17 GLYBS08 GLY
BS09 GLYCU5a TCO2 CU5b TCO2 CU5c TCO2CU5d TCO2L2D3-81
CHB2-33
L2D1-81COORDINATE BOSS
GATEWAY RECEPTACLE
LOCATION WITH
REFRIGERATION BAS
INSTALLER
CHB2-27
CHB2-25 16.145
16.145
CHB1-14
CHB1-12 16.145
16.145
CHA2-25
CHA2-23 16.145
16.145
CHA2-35
CHA2-33 16.145
16.145
CHA2-14 16.145
CHA2-19
CHA2-17 16.145
16.145
SPARE OUT EXISTING CIRCUIT
CHA2-21 SINCE NEW CASE DOES
NOT HAVE ANTI-SWEAT
CHB2-11
CHB2-9 16.145
16.145 CHB2-15
CHB2-13 16.145
16.145
CHB2-3
CHB2-1 16.145
16.145 CHB2-7
CHB2-5 16.145
16.145
CHB2-21
CHB2-23 16.145
16.145CHB2-17
CHB2-19 16.145
16.145
16.710
2
RE1.3TYP
16.711
TYP
3
RE1.3TYP
3
RE1.3 TYP
3
RE1.3 TYP
4
RE1.3TYP
CHB2-29
CHB2-31
L2D1-79CIRCUIT FOR DEVICES ON NEW
BAS BACKBOARD IN EDC2
22 (CF)
22 (CF)
WP, WR, GFCI CONVENIENCE
RECEPTACLE FOR GLYCOL AND
TCO2 CHARGING STATION.
1 2
G
H
BS14a GLYBS14b GLYBS14 GLYCHB2-16
CHB2-14 16.145
16.145
5
RE1.3
TYP
3
RE1.3
2
RE1.3
SHEET:
DRAWN BY:
CHECKED BY:
PROTO CYCLE:
DOCUMENT DATE:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.P (407) 661-9100F (407) 661-9101c-p.comFlorida Corporate Certificate #AA C0005262600 Maitland Center ParkwaySuite #200Maitland, FL 32751CUSHING TERRELL306 W. RAIL ROAD SUITE 104MISSOULA, MT 59802Phone: (406)728-9522Fax: (406)728-8287EXISTING CONDITIONS WERE TAKEN FROM
ORIGINAL DRAWINGS AND MAY NOT REFLECT
EXACT "AS-BUILT" CONDITIONS. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS
PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR
SHALL CAREFULLY COORDINATE NEW WORK AND
DEMOLITION WITH ALL OTHER DISCIPLINES AND
EXISTING CONDITIONS.
EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING
A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND
SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE
TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES
NOT RELIEVE THE RESPONSIBILITY OF PERFORMING
THE WORK PROPERLY. NO ADDITIONAL
COMPENSATION SHALL BE ALLOWED BECAUSE OF
CONDITIONS THAT OCCUR DUE TO FAILURE TO
FAMILIARIZE WORKERS WITH THIS KNOWLEDGE.
DOCUMENTS WITHOUT
SIGNATURE AND REQUIRED
SEAL OF AOR/EOR ARE NOT
FOR CONSTRUCTION
RE1.1
ENLARGED
REFRIGERATION
ELECTRICAL
PLANS
DM20240347BOYNTON BEACH, FL11/07/2511/07/25STORE NO: 5911-2769006/27/25BOYNTON BEACH, FLSP3625 S FEDERAL HWY.1. COORDINATE ALL WORK WITH REFRIGERATION
CONTRACTOR (R.C.) PRIOR TO INSTALLATION.
2. REFRIGERATED CASES: E.C. SHALL PROVIDE CONDUIT
AND WIRE FOR REFRIGERATED CASE FANS, LIGHTS
AND ANTI-SWEAT HEATERS, AND (IF APPLICABLE)
ELECTRICAL DEFROST. PROVIDE ADEQUATE
CONDUCTOR LENGTH TO ALLOW TERMINATION.
NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND
LABEL EACH CIRCUIT WITH BRANCH CIRCUIT
DESIGNATION AND REFRIGERATION SYSTEM NUMBER
FOR FINAL TERMINATION AT CASE BY R.C. REF CASE
CONNECTION WIRING DETAIL.
3. IF NEW CASES ARE PROVIDED WITH A FACTORY
INSTALLED TERMINAL STRIP AND JUMPERS FOR
CONNECTION TO A SINGLE CIRCUIT FOR 120V CASE
LOADS. RC SHALL REMOVE FACTORY INSTALLED
JUMPERS AS REQUIRED TO UTILIZE EXISTING
SEPARATE 120V FAN/LIGHT/ANTI-SWEAT CIRCUITS AS
INDICATED ON PLANS AND/OR PANELBOARD
SCHEDULES. ANY EXISTING ANTI-SWEAT CONTROL
(SWEATMISER) SHALL BE BY-PASSED. CASES UTILIZING
ELECTRICAL DEFROST WILL BE PROVIDED WITH
SEPARATE 208V TERMINATIONS AT THE TERMINAL
STRIP FOR CONNECTION TO THE 208V ELECTRIC
DEFROST CIRCUIT. RC SHALL MAKE FINAL
TERMINATIONS OF 120V AND 208V POWER CIRCUIT(S)
AT CASE TERMINAL STRIP. REFER TO CASE
CONNECTION SCHEMATIC ON REFRIGERATION
SHEETS.
4. WALK-IN UNITS: PROVIDE CONDUIT AND WIRE FOR
EVAPORATOR COIL FANS (CF) AND (IF APPLICABLE)
ELECTRIC DEFROST (ED). PROVIDE ADEQUATE
CONDUCTOR LENGTH TO ALLOW TERMINATION.
NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND
LABEL EACH CIRCUIT WITH BRANCH CIRCUIT
DESIGNATION AND REFRIGERATION SYSTEM NUMBER
FOR FINAL TERMINATION AT COIL BY R.C. REF
EVAPORATOR COIL WIRING DETAIL.
5. ROUTE REFRIGERATED CASE AND WALK-IN UNIT COIL
FAN, LIGHTS, ANTI-SWEAT AND DEFROST BRANCH
CIRCUITS TO WIREWAYS PROVIDED AT
REFRIGERATION EQUIPMENT AND/OR PANELBOARDS
AS REQUIRED.
6. REFRIGERATED CASE WIRING COMPARTMENT
REPRESENTED ON DRAWING BY JUNCTION BOX.
7. KEEP PENETRATIONS THROUGH WALK-IN UNITS
TO A MINIMUM. ROUTE ALL CONDUITS SERVING
FREEZERS AND COOLERS ON INSIDE OF BOX.
8. ALL CONDUITS INSTALLED ON TOP OF WALK-IN UNITS
SHALL BE A MINIMUM OF 6" FROM ANY EDGE TO ALLOW
SPACE FOR EDGE PROTECTION NETTING. DO NOT
ROUTE CONDUITS ABOVE THE CEILING GRID ACCESS
UNLESS CONDUITS ARE INSTALLED IN JOIST SPACE,
REF ARCH.
9. UNDERSLAB CIRCUITS SHALL NOT BE ROUTED UNDER
WALK-IN FREEZERS AND SHALL BE ROUTED ABOVE
REFRIGERANT LINES WHERE THEY CROSS.
10. CIRCUITS FOR REFRIGERATED CASES SERVED BY
UNDERSLAB REFRIGERATION PIPING ARE TO BE
ROUTED UNDERSLAB AND EXTENDED TO THE FIRST
CASE IN EACH SYSTEM. WIRING AND CONDUIT FOR
SLAVE WIRING BETWEEN CASES SHALL BE PROVIDED
BY R.C. REFER TO UNDERSLAB CASE CONNECTION
WIRING DETAIL.
11. ALL UNDERSLAB CONDUITS SHALL BE 3/4" MIN.
12. CIRCUITS FOR REFRIGERATED CASES SERVED BY
OVERHEAD REFRIGERATION PIPING ARE TO BE
ROUTED DOWN FROM STRUCTURE AT THE SAME
LOCATION AS THE REFRIGERATION PIPING AND
EXTENDED TO THE FIRST CASE IN EACH SYSTEM. WIRE
AND CONDUIT FOR SLAVE WIRING BETWEEN CASES
SHALL BE PROVIDED BY THE R.C. REFER TO
OVERHEAD CASE CONNECTION WIRING DETAIL.
13. ON GROUPS OF THREE OR MORE REFRIGERATED
CASES WITH ELECTRIC DEFROST, R.C. SHALL
CONNECT CASES TO CREATE A THREE-PHASE HEATER
CIRCUIT. HEATER LOADS SHALL BE BALANCED
BETWEEN PHASES AS EVENLY AS POSSIBLE. REF
CASE DEFROST WIRING DETAIL.
14. PROVIDE A SEPARATE NEUTRAL FOR EACH NEW
BRANCH CIRCUIT SERVING REFRIGERATED CASES OR
WALK-IN UNITS.
15. PROVIDE CIRCUIT BREAKER LOCKING DEVICE (LOCK-
OFF FOR MAINTENANCE) ON NEW AND/OR EXISTING
CIRCUIT BREAKERS SERVING REFRIGERATED CASES.
16. REFERENCE ARCHITECTURAL DEMOLITION PLANS FOR
FULL EXTENT OF DEMOLITION WORK REQUIRED.
GENERAL REFRIGERATION
ELECTRICAL NOTES
08.28.20
1/8" = 1'-0"1 FRONT REFRIGERATION ELECTRICAL PLAN (NOVAR)
KEYNOTES
16.145 CONNECT CIRCUIT(S) TO EXISTING BRANCH CIRCUITRY.
MINIMUM WIRE SIZE AND PANELBOARD CIRCUIT ARE
NOTED. VERIFY SIZE, RATING AND CONDITION OF
EXISTING BRANCH CIRCUIT CONDUIT AND WIRE PRIOR
TO USE TO ENSURE THAT THEY MEET REQUIRED SIZE,
AND ALL U.L. RATINGS AND REPLACE AS REQUIRED.
16.710 BUILDING AUTOMATION CONDUITS: PROVIDE 1" (UNLESS
NOTED OTHERWISE) CONDUIT (WITH PULL WIRE)
ROUTED FROM 6" ABOVE BOTTOM OF BAR JOIST IN
SALES FLOOR ACCESSIBLE CEILING SPACE THROUGH
PVC CHASE.
16.711 POINT OF TRANSITION FROM EMT TO FLEX. PROVIDE
CONDUIT AND BRANCH CIRCUITS FOR REFRIGERATED
CASE FANS, LIGHTS, ANTI-SWEAT HEATERS, AND
ELECTRICAL DEFROST (IF REQUIRED). TERMINATION TO
REFRIGERATED CASE ELECTRICAL CONNECTION POINT
BY R.C. REFER TO CASE CONNECTION WIRING DETAIL.
1/8" = 1'-0"3 REAR REFRIGERATION ELECTRICAL PLAN (NOVAR)
FEEDER OR GROUND SIZE
ALL CONDUIT AND CONDUCTOR SIZES ARE BASED ON EMT WITH 40%
FILL, 75ºC RATED TERMINATIONS AND TYPE THHN/THWN-2 INSULATION.
FOR NON-EMT CONDUIT OR TERMINATIONS OR INSULATION TYPES
RATED LESS THAN 75ºC, MODIFY SIZES ACCORDING TO NEC.
FEEDER SCHEDULE
22 (2)#12, (1)#12 G, 1/2" C
ISSUE BLOCK
Not part of this application. A
permit application shall be
submitted for interior remodeling.
C
4 5
D L2B-32,34,36NEW
CU5 TCO2
PROVIDE 3/4"C FROM LOW VOLTAGE
WIRING COMPARTMENT TO ACCESSIBLE
INTERIOR JOIST SPACE AND TERMINATE
WITH BUSHING. (TYP)WR,WP 100A/3/NF,
NEMA 3R
MOUNT TO FRAMING OR NON-
REMOVABLE ACCESS PANEL
TO NEAREST RTU MAINTENANCE
RECEPTACLE CIRCUIT 16.250103
2 3
F
NEW
DTB GLY H1A-25,27,2916.250
16.258
EXISTING ROOF MOUNTED SPLIT
SUCTION HYBRID HOUSES
ETR
DTA DX
ETR
DTB DX
1
RE1.3
ROOF
PENETRATIONBAS CONTROL
TRANSFORMER INSTALLED
INSIDE PUMP SKID
ELECTRICAL CABINET BY
BASR CONTRACTOR.
FACTORY
INSTALLED,
WP/WR, GFCI
RCPT.
PANELS CHA1 AND
CHA2 STACKED
PANELS CHB1 AND
CHB2 STACKED
33
SHEET:
DRAWN BY:
CHECKED BY:
PROTO CYCLE:
DOCUMENT DATE:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.P (407) 661-9100F (407) 661-9101c-p.comFlorida Corporate Certificate #AA C0005262600 Maitland Center ParkwaySuite #200Maitland, FL 32751CUSHING TERRELL306 W. RAIL ROAD SUITE 104MISSOULA, MT 59802Phone: (406)728-9522Fax: (406)728-8287EXISTING CONDITIONS WERE TAKEN FROM
ORIGINAL DRAWINGS AND MAY NOT REFLECT
EXACT "AS-BUILT" CONDITIONS. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS
PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR
SHALL CAREFULLY COORDINATE NEW WORK AND
DEMOLITION WITH ALL OTHER DISCIPLINES AND
EXISTING CONDITIONS.
EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING
A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND
SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE
TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES
NOT RELIEVE THE RESPONSIBILITY OF PERFORMING
THE WORK PROPERLY. NO ADDITIONAL
COMPENSATION SHALL BE ALLOWED BECAUSE OF
CONDITIONS THAT OCCUR DUE TO FAILURE TO
FAMILIARIZE WORKERS WITH THIS KNOWLEDGE.
DOCUMENTS WITHOUT
SIGNATURE AND REQUIRED
SEAL OF AOR/EOR ARE NOT
FOR CONSTRUCTION
RE1.2
ENLARGED
REFRIGERATION
ELECTRICAL
PLANS
DM20240347BOYNTON BEACH, FL11/07/2511/07/25STORE NO: 5911-2769006/27/25BOYNTON BEACH, FLSP3625 S FEDERAL HWY.1/8" = 1'-0"1 REFRIGERATION ELECTRICAL ROOF PLAN (FRONT)
1/8" = 1'-0"2 REFRIGERATION ELECTRICAL ROOF PLAN (REAR)
1. COORDINATE ALL WORK WITH REFRIGERATION
CONTRACTOR (R.C.) PRIOR TO INSTALLATION.
2. REFRIGERATED CASES: E.C. SHALL PROVIDE CONDUIT
AND WIRE FOR REFRIGERATED CASE FANS, LIGHTS
AND ANTI-SWEAT HEATERS, AND (IF APPLICABLE)
ELECTRICAL DEFROST. PROVIDE ADEQUATE
CONDUCTOR LENGTH TO ALLOW TERMINATION.
NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND
LABEL EACH CIRCUIT WITH BRANCH CIRCUIT
DESIGNATION AND REFRIGERATION SYSTEM NUMBER
FOR FINAL TERMINATION AT CASE BY R.C. REF CASE
CONNECTION WIRING DETAIL.
3. IF NEW CASES ARE PROVIDED WITH A FACTORY
INSTALLED TERMINAL STRIP AND JUMPERS FOR
CONNECTION TO A SINGLE CIRCUIT FOR 120V CASE
LOADS. RC SHALL REMOVE FACTORY INSTALLED
JUMPERS AS REQUIRED TO UTILIZE EXISTING
SEPARATE 120V FAN/LIGHT/ANTI-SWEAT CIRCUITS AS
INDICATED ON PLANS AND/OR PANELBOARD
SCHEDULES. ANY EXISTING ANTI-SWEAT CONTROL
(SWEATMISER) SHALL BE BY-PASSED. CASES UTILIZING
ELECTRICAL DEFROST WILL BE PROVIDED WITH
SEPARATE 208V TERMINATIONS AT THE TERMINAL
STRIP FOR CONNECTION TO THE 208V ELECTRIC
DEFROST CIRCUIT. RC SHALL MAKE FINAL
TERMINATIONS OF 120V AND 208V POWER CIRCUIT(S)
AT CASE TERMINAL STRIP. REFER TO CASE
CONNECTION SCHEMATIC ON REFRIGERATION
SHEETS.
4. WALK-IN UNITS: PROVIDE CONDUIT AND WIRE FOR
EVAPORATOR COIL FANS (CF) AND (IF APPLICABLE)
ELECTRIC DEFROST (ED). PROVIDE ADEQUATE
CONDUCTOR LENGTH TO ALLOW TERMINATION.
NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND
LABEL EACH CIRCUIT WITH BRANCH CIRCUIT
DESIGNATION AND REFRIGERATION SYSTEM NUMBER
FOR FINAL TERMINATION AT COIL BY R.C. REF
EVAPORATOR COIL WIRING DETAIL.
5. ROUTE REFRIGERATED CASE AND WALK-IN UNIT COIL
FAN, LIGHTS, ANTI-SWEAT AND DEFROST BRANCH
CIRCUITS TO WIREWAYS PROVIDED AT
REFRIGERATION EQUIPMENT AND/OR PANELBOARDS
AS REQUIRED.
6. REFRIGERATED CASE WIRING COMPARTMENT
REPRESENTED ON DRAWING BY JUNCTION BOX.
7. KEEP PENETRATIONS THROUGH WALK-IN UNITS
TO A MINIMUM. ROUTE ALL CONDUITS SERVING
FREEZERS AND COOLERS ON INSIDE OF BOX.
8. ALL CONDUITS INSTALLED ON TOP OF WALK-IN UNITS
SHALL BE A MINIMUM OF 6" FROM ANY EDGE TO ALLOW
SPACE FOR EDGE PROTECTION NETTING. DO NOT
ROUTE CONDUITS ABOVE THE CEILING GRID ACCESS
UNLESS CONDUITS ARE INSTALLED IN JOIST SPACE,
REF ARCH.
9. UNDERSLAB CIRCUITS SHALL NOT BE ROUTED UNDER
WALK-IN FREEZERS AND SHALL BE ROUTED ABOVE
REFRIGERANT LINES WHERE THEY CROSS.
10. CIRCUITS FOR REFRIGERATED CASES SERVED BY
UNDERSLAB REFRIGERATION PIPING ARE TO BE
ROUTED UNDERSLAB AND EXTENDED TO THE FIRST
CASE IN EACH SYSTEM. WIRING AND CONDUIT FOR
SLAVE WIRING BETWEEN CASES SHALL BE PROVIDED
BY R.C. REFER TO UNDERSLAB CASE CONNECTION
WIRING DETAIL.
11. ALL UNDERSLAB CONDUITS SHALL BE 3/4" MIN.
12. CIRCUITS FOR REFRIGERATED CASES SERVED BY
OVERHEAD REFRIGERATION PIPING ARE TO BE
ROUTED DOWN FROM STRUCTURE AT THE SAME
LOCATION AS THE REFRIGERATION PIPING AND
EXTENDED TO THE FIRST CASE IN EACH SYSTEM. WIRE
AND CONDUIT FOR SLAVE WIRING BETWEEN CASES
SHALL BE PROVIDED BY THE R.C. REFER TO
OVERHEAD CASE CONNECTION WIRING DETAIL.
13. ON GROUPS OF THREE OR MORE REFRIGERATED
CASES WITH ELECTRIC DEFROST, R.C. SHALL
CONNECT CASES TO CREATE A THREE-PHASE HEATER
CIRCUIT. HEATER LOADS SHALL BE BALANCED
BETWEEN PHASES AS EVENLY AS POSSIBLE. REF
CASE DEFROST WIRING DETAIL.
14. PROVIDE A SEPARATE NEUTRAL FOR EACH NEW
BRANCH CIRCUIT SERVING REFRIGERATED CASES OR
WALK-IN UNITS.
15. PROVIDE CIRCUIT BREAKER LOCKING DEVICE (LOCK-
OFF FOR MAINTENANCE) ON NEW AND/OR EXISTING
CIRCUIT BREAKERS SERVING REFRIGERATED CASES.
16. REFERENCE ARCHITECTURAL DEMOLITION PLANS FOR
FULL EXTENT OF DEMOLITION WORK REQUIRED.
GENERAL REFRIGERATION
ELECTRICAL NOTES
08.28.20
KEYNOTES
16.250 CONNECT CIRCUITRY TO FACTORY PROVIDED
MAINTENANCE RECEPTACLE. ROUTE CIRCUIT TO
NEAREST RTU OR AHU MAINTENANCE RECEPTACLE
CIRCUIT.
16.258 CONNECT CIRCUITRY TO FACTORY PROVIDED
DISCONNECT SWITCH.
FEEDER OR GROUND SIZE
ALL CONDUIT AND CONDUCTOR SIZES ARE BASED ON EMT WITH 40%
FILL, 75ºC RATED TERMINATIONS AND TYPE THHN/THWN-2 INSULATION.
FOR NON-EMT CONDUIT OR TERMINATIONS OR INSULATION TYPES
RATED LESS THAN 75ºC, MODIFY SIZES ACCORDING TO NEC.
FEEDER SCHEDULE
33 (3)#10, (1)#10 G, 1/2” C
103 (3)#3, (1)#8 G, 1" C
ISSUE BLOCK
Not part of this application. A
permit application shall be
submitted for interior remodeling.
SUPPORT CONDUIT FROM TOP
OR BOTTOM OF STRUCTURE
ONLY. DO NOT INSTALL
CONDUIT BELOW STRUCTURE.
ROOF OPENING MAY CONTAIN
MULTIPLE CONDUIT TYPES, SEE
ELECTRICAL AND BASR PLANS.
MINIMUM 2" GAP BETWEEN ADJACENT
CONDUITS.
OWNER PROVIDED
MANUFACTURED CURB, SEE
ARCHITECTURAL DETAILS FOR
SIZE, INSULATION, ASSEMBLY,
AND SEALING REQUIREMENTS
SUPPORT CONDUIT PER
SPECIFICATIONS, SEE ROOF SUPPORT
DETAIL.
REMOVABLE HOOD
PROVIDED WITH CURB.
DROP CONDUIT NEAR HOOD TO ALIGN WITH
ROOF SUPPORT HEIGHT IF NEEDED.
SECURE CONDUIT TO
UNISTRUT AT TOP OF
CURB
5" CENTER OF CONDUIT TO TOP OF CURB.
PAINT CONDUIT TO
MATCH ADJACENT
CEILING COLOR
TYPICAL REFRIGERATED CASE SYSTEM
12" WIRE PIGTAILS (TYP)
5' FLEX CONDUIT (TYP)
ROUTE EMT CONDUITS (UNDER CASES, ABOVE
SLAB) TO POINT OF TRANSITION TO FLEX
PROVIDE TRANSITION FROM EMT TO FLEX
BRANCH CIRCUIT AND EMS CONDUITS TO OTHER
REFRIGERATED CASE SYSTEMS (TYP)
BRACKET CONDUIT TO FLOOR
AS REQUIRED BY CODE (TYP)
ROUTE CONDUIT FOR BRANCH CIRCUITS FROM OVERHEAD
THRU CHASE, ALONG WITH REFRIGERATION PIPING (TYP)
PROVIDE (2) CONDUITS AND BRANCH CIRCUITS PER REFRIGERATED
CASE SYSTEM. ONE CONDUIT WILL SERVE 120V CASE FANS, LIGHTS
AND ANTI-SWEAT CIRCUITS; ONE CONDUIT WILL SERVE 208V CASE
ELECTRIC DEFROST CIRCUIT. ON SYSTEMS WITHOUT ELECTRIC
DEFROST, ONLY PROVIDE ONE CONDUIT
PROVIDE 5' LENGTH OF FLEX CONDUIT WITH 12" PIGTAIL STUBBED
FROM END OF EACH FLEX CONDUIT.
PVC CHASE
EMS CONDUIT: PROVIDE CONDUIT (WITH PULL WIRE) ROUTED 6"
ABOVE BOTTOM OF BAR JOIST IN SALES FLOOR ACCESSIBLE CEILING
SPACE THROUGH PVC CHASE. CONDUIT WILL BE SIZED 1" FOR (4) OR
FEWER EMS CABLES AND 1-1/4" FOR (5) OR MORE EMS CABLES.REAR HALF OF
REFRIGERATED CASE
DESIGNATED FOR
PIPING AND VALVES
FRONT HALF OF
REFRIGERATED CASE
DESIGNATED FOR
ELECTRICAL AND
BAS COMPONENTS
REFRIGERATED CASE CONTROLLER
REFER TO BASR PLANS FOR CASE
CONTROLLER TYPE, WIRING DETAILS,
AND CONTROLLER TERMINATION
POINTS, TYP
CONDUITS FOR REFRIGERATED CASE POWER. ONE CONDUIT WILL SERVE
120V FANS, LIGHTS, AND ANTI-SWEAT HEATERS CIRCUITS. ONE CONDUIT
WILL SERVE 208V ELECTRIC DEFROST CIRCUIT. REFER TO REFRIGERATION
ELECTRICAL PLANS IF ELECTRIC DEFROST IS REQUIRED AND FOR FEEDER
AND CONDUIT SIZES.
CONDUIT FOR DAISY CHAINED BASR CABLING. FROM PREVIOUS
BASR CONTROLLER OR MASTER CONTROLLER. REFER TO BASR
PLANS AND ONE-LINE DIAGRAM.
TO NEXT BASR CONTROLLER IN DAISY CHAIN
OR MASTER CONTROLLER. REFER TO BASR
PLANS AND ONE-LINE DIAGRAM.
CASE JUNCTION BOX FOR TRANSITION
FROM EMT TO FLEX CONDUIT, TYP.
FLEX CONDUITS FROM CASE JUNCTION BOX
TO CASE CONTROLLER, TYP. ONE CONDUIT FOR
120V CASE FANS, LIGHTS, AND ANTI-SWEAT
HEATERS CIRCUIT. ONE CONDUIT FOR
208V ELECTRIC DEFROST CIRCUIT.
REFRIGERATED CASE, TYP. REFER TO PLANS
FOR QUANTITY OF CASES ON CASE LINEUP.
ROUTE CONDUITS WITH REFRIGERATION
PIPING TO ACCESSIBLE JOIST SPACE.
REFER TO REFRIGERATION PLANS FOR
CHASE ROUTING DETAILS, IF REQUIRED.
EMT CONDUIT BETWEEN
CASE JUNCTION BOXES, TYP
PROVIDE CEILING MOUNTED MANUAL SWITCH 'HUBBELL' CLASS
HBLDS3 OR ‘EATON’CLASS AHDS30. IF OVER 30 AMPS PROVIDE
‘HUBBEL’CLASS HBLDS6 OR ‘EATON’AHDS60. WITH NEMA 4X
WATERTIGHT NON-METALLIC ENCLOSURE FOR CONNECTION
OF EVAPORATOR COIL FANS (CF) AND/OR ELECTRIC DEFROST
(ED), (WHERE SHOWN ON DRAWINGS). PROVIDE PLACARD ON
CEILING DETAILING PURPOSE OF EACH MANUAL SWITCH AND
THE ELECTRICAL SOURCE (PANEL AND CIRCUIT NUMBER).
NOTE: DO NOT LOCATE WP JUNCTION BOX DIRECTLY IN FRONT OF DISCHARGE FAN, OFFSET TO SIDE.
TYPICAL COIL
EMT CONDUIT AND WIRING TO NEXT
COIL POWER JUNCTION BOX ON SAME
SYSTEM WHEN MULTIPLE COILS ARE IN
SAME COOLER/FREEZER BOX. POWER
CONDUIT AND WIRING SAME SIZE AND
QUANTITY AS WIRING TO PANEL.
1" EMT CONDUIT
PENETRATION SEALED
WITH SILICONE SEALANT.
NOTE: TAP DEFROST CIRCUIT IN
JUNCTION BOX WITH #10 AWG FOR
CONNECTION TO UNIT. MAXIMUM
LENGTH OF TAP CONDUCTOR 18"
CONDULET AT CEILING PENETRATION
FILLED WITH SILICONE
COIL FAN/DEFROST POWER EMT CONDUIT
AND WIRING TO DESIGNATED PANEL VIA
WALK-IN FAN/DEFROST CONTROL DEVICE.
FINAL CONNECTION BY RC.
COOLER/FREEZER BOX CEILING
CEILING MOUNTED WP JUNCTION BOX WITH THREADED HUBS
AND GASKETED COVERPLATE. SEAL TOP OF JUNCTION BOX
TO COOLER/FREEZER CEILING WITH SILICONE SEALANT.
1" LIQUID-TIGHT FLEXIBLE METAL CONDUIT
TO KNOCKOUT ON UNIT. FINAL
CONNECTION TO COIL BY RC.
Ø
Ø
Ø
PROVIDE 208/3Ø HOME RUN TO DESIGNATED PANEL
BOARD . FINAL CONNECTION AT CASE BY R.C.
CALCULATION OF 3Ø UNBALANCED LOAD
B LOAD = (12.6 A + 12.6 A) x .866 = 21.8 A (HIGH LEG)
A LOAD = (12.6 A + 9.9 A) x .866 = 19.5 A
B LOAD = (12.6 A + 12.6 A) x .866 = 21.8 A (HIGH LEG)
C LOAD = (12.6 A + 9.9 A) x .866 = 19.5 A
NOTES:
ON SYSTEMS WITH UNEQUAL LOADS, REC
(REFRIGERATION ELECTRICAL CONTRACTOR) SHALL
ARRANGE CONNECTIONS FOR MAXIMUM BALANCE
A CCBBA
C
B
A
12.6 A 9.9 A12.6 A
4 DOOR CASE5 DOOR CASE5 DOOR CASE
TYPICAL REFRIGERATED CASE SYSTEM
NTS1ROOF PENETRATION (CONDUIT)
NTS2CASE CONNECTION WIRING (PVC CHASE)
NTS3CASE CONDUIT ROUTING
NTS4EVAPORATOR COIL WIRING
NTS5CASE DEFROST WIRING
SHEET:
DRAWN BY:
CHECKED BY:
PROTO CYCLE:
DOCUMENT DATE:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.P (407) 661-9100F (407) 661-9101c-p.comFlorida Corporate Certificate #AA C0005262600 Maitland Center ParkwaySuite #200Maitland, FL 32751CUSHING TERRELL306 W. RAIL ROAD SUITE 104MISSOULA, MT 59802Phone: (406)728-9522Fax: (406)728-8287EXISTING CONDITIONS WERE TAKEN FROM
ORIGINAL DRAWINGS AND MAY NOT REFLECT
EXACT "AS-BUILT" CONDITIONS. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS
PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR
SHALL CAREFULLY COORDINATE NEW WORK AND
DEMOLITION WITH ALL OTHER DISCIPLINES AND
EXISTING CONDITIONS.
EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING
A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND
SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE
TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES
NOT RELIEVE THE RESPONSIBILITY OF PERFORMING
THE WORK PROPERLY. NO ADDITIONAL
COMPENSATION SHALL BE ALLOWED BECAUSE OF
CONDITIONS THAT OCCUR DUE TO FAILURE TO
FAMILIARIZE WORKERS WITH THIS KNOWLEDGE.
DOCUMENTS WITHOUT
SIGNATURE AND REQUIRED
SEAL OF AOR/EOR ARE NOT
FOR CONSTRUCTION
RE1.3
REFRIGERATION
ELECTRICAL
PANEL
SCHEDULES
AND DETAILS
DM20240347BOYNTON BEACH, FL11/07/2511/07/25STORE NO: 5911-2769006/27/25BOYNTON BEACH, FLSP3625 S FEDERAL HWY.A. LEGEND: (N) NEW, (E ) EXISTING, (M) MODIFY, B. CONTROLLED VIA 100A-3P CONTACTOR
CIRCUIT NOTES:
MISCELLANEOUS 0.4 PER NEC 210.20(A) 0.5
WATER HEAT 0.0 100% 0.0
ELECTRIC HEAT 0.0 100% 0.0 DEMAND AMPS 33.9
KITCHEN EQUIPMENT 0.0 PER NEC 220.56 0.0 DEMAND LOAD (kVA):12.2
MOTORS 4.4 PER NEC 430.24 4.7
CONVENIENCE OUTLETS 1.6 PER NEC 220.44 1.6 CONNECTED AMPS:29.9
LIGHTING 4.4 PER NEC 210.20(A) 5.5 CONNECTED LOAD(kVA):10.8
LOAD CLASSIFICATION CONNECTED LOAD(kVA) FACTOR DEMAND LOAD PANEL TOTALS
30.8 31.7 27.2 TOTAL CONNECTED PHASE AMPS
3700 3800 3260 TOTAL CONNECTED PHASE VA
SPARE E 1 20 41 42 20 1 E SPACE
AS12 CASE LIGHTS (11) E 1 20 39 280 40 20 1 E SPACE
AS12 CASE FANS E 1 20 37 150 38 20 1 E SPACE
BS20 GLY CASE LIGHTS (11) M 1 20 35 60 36 20 1 E SPACE
BS20 GLY CASE FANS M 1 20 33 40 34 20 1 E SPACE
AS08 CASE FANS E 1 20 31 1100 32 20 1 E SPACE
AS07 CASE LIGHTS (11) E 1 20 29 1260 30 20 1 E SPARE
AS07 CASE FANS E 1 20 27 420 28 20 1 E SPARE
BS18 GLY CASE LIGHTS (11) M 1 20 25 50 26 20 1 E SPARE
BS18 GLY CASE FANS M 1 20 23 110 24 20 1 E SPARE
SPARE M 1 20 21 180 22 20 1 E AS11 EMS CONTROLLER
BS17 GLY CASE LIGHTS (11) M 1 20 19 90 180 20 20 1 E AS10 EMS CONTROLLER
BS17 GLY CASE FANS M 1 20 17 150 180 18 20 1 E AS08 CASE RECEPTACLE
AS04 CASE LIGHTS (11) E 1 20 15 590 180 16 20 1 E AS08 CASE RECEPTACLE
AS04 CASE FANS E 1 20 13 770 180 14 20 1 M BS17 GLY CASE RECEPTACLE
AS03 CASE LIGHTS (11) E 1 20 11 590 180 12 20 1 E AS04 CASE RECEPTACLE
AS03 CASE FANS E 1 20 9 770 180 10 20 1 E AS04 CASE RECEPTACLE
AS02 CASE LIGHTS (11) E 1 20 7 460 180 8 20 1 E AS03 CASE RECEPTACLE
AS02 CASE FANS E 1 20 5 550 180 6 20 1 E AS03 CASE RECEPTACLE
AS01 CASE LIGHTS (11) E 1 20 3 980 180 4 20 1 E AS02 CASE RECEPTACLE
AS01 CASE FANS E 1 20 1 360 180 2 20 1 E AS02 CASE RECEPTACLE
NOTES POLE AMP NO NO AMP POLE NOTESLOAD NAME
CKT BRK CKT PHASE A
LOAD (VA)
PHASE B
LOAD (VA)
PHASE C
LOAD (VA)
CKT BRK CKT
LOAD NAME
MODEL TYPE:EXISTING WIRES:4
MANUFACTURER:EXISTING PHASE:3 NOTES:YES
TYPE OF MAIN:100A MLO VOLTAGE:208Y/120 MOUNTING TYPE:EXISTING
LOCATION:HYBRID HOUSE DTA AMPS:100 MINIMUM AIC RATING:10,000
EXISTING PANEL: (E)CHA2
A. LEGEND: (N) NEW, (E ) EXISTING, (M) MODIFY, B. CONTROLLED VIA 100A-3P CONTACTOR
CIRCUIT NOTES:
MISCELLANEOUS 0.2 PER NEC 210.20(A) 0.2
WATER HEAT 0.0 100% 0.0
ELECTRIC HEAT 10.4 100% 10.4 DEMAND AMPS 47.6
KITCHEN EQUIPMENT 0.0 PER NEC 220.56 0.0 DEMAND LOAD (kVA):17.1
MOTORS 2.0 PER NEC 430.24 2.1
CONVENIENCE OUTLETS 0.7 PER NEC 220.44 0.7 CONNECTED AMPS:45.2
LIGHTING 3.0 PER NEC 210.20(A) 3.7 CONNECTED LOAD(kVA):16.3
LOAD CLASSIFICATION CONNECTED LOAD(kVA) FACTOR DEMAND LOAD PANEL TOTALS
44.2 41.6 49.8 TOTAL CONNECTED PHASE AMPS
5300 4990 5970 TOTAL CONNECTED PHASE VA
SPARE E 1 20 41 42 20 1 E SPACE
B06 CASE LIGHTS (11) E 1 20 39 460 40 20 1 E SPACE
B06 CASE A/S HTRS E 1 20 37 1670 38 20 1 E SPACE
B06 CASE FANS E 1 20 35 300 36 20 1 E SPACE
B05 CASE LIGHTS (11) E 1 20 33 550 34 20 1 E SPACE
B05 CASE A/S HTRS E 1 20 31 930 32 20 1 E SPACE
B05 CASE A/S HTRS E 1 20 29 1040 30 20 1 E SPACE
B05 CASE FANS E 1 20 27 350 28 20 1 E SPACE
B04 CASE LIGHTS (11) E 1 20 25 430 26 20 1 E SPACE
B04 CASE A/S HTRS (6) E 1 20 23 1560 24 20 1 E SPACE
B04 CASE FANS E 1 20 21 280 22 20 1 E SPACE
B03 CASE LIGHTS (11) E 1 20 19 430 20 20 1 E SPACE
B03 CASE A/S HTRS E 1 20 17 1560 18 20 1 E SPACE
B03 CASE FANS E 1 20 15 280 16 20 1 E SPACE
B02 CASE LIGHTS (11) E 1 20 13 460 120 14 20 1 M BS19 GLY CASE FANS
B02 CASE FANS E 1 20 11 300 100 12 20 1 M BS19 GLY CASE LIGHTS
B02 CASE A/S HTRS E 1 20 9 1670 180 10 20 1 E B07 EMS CONTROLLER
B01 CASE LIGHTS (11) E 1 20 7 550 180 8 20 1 E B06 CASE RECEPTACLE
B01 CASE A/S HTRS E 1 20 5 930 180 6 20 1 E B04 CASE RECEPTACLE
B01 CASE A/S HTRS E 1 20 3 1040 180 4 20 1 E B03 CASE RECEPTACLE
B01 CASE FANS E 1 20 1 350 180 2 20 1 E B02 CASE RECEPTACLE
NOTES POLE AMP NO NO AMP POLE NOTESLOAD NAME
CKT BRK CKT PHASE A
LOAD (VA)
PHASE B
LOAD (VA)
PHASE C
LOAD (VA)
CKT BRK CKT
LOAD NAME
MODEL TYPE:EXISTING WIRES:4
MANUFACTURER:EXISTING PHASE:3 NOTES:YES
TYPE OF MAIN:100A MLO VOLTAGE:208Y/120 MOUNTING TYPE:EXISTING
LOCATION:HYBRID HOUSE DTB AMPS:100 MINIMUM AIC RATING:10,000
EXISTING PANEL: (E)CHB1
A. LEGEND: (N) NEW, (E ) EXISTING, (M) MODIFY
CIRCUIT NOTES:
MISCELLANEOUS 1.1 PER NEC 210.20(A) 1.4
WATER HEAT 0.0 100% 0.0
ELECTRIC HEAT 1.1 100% 1.1 DEMAND AMPS 29.4
KITCHEN EQUIPMENT 0.0 PER NEC 220.56 0.0 DEMAND LOAD (kVA):10.6
MOTORS 5.0 PER NEC 430.24 5.2
CONVENIENCE OUTLETS 0.0 PER NEC 220.44 0.0 CONNECTED AMPS:26.3
LIGHTING 2.3 PER NEC 210.20(A) 2.9 CONNECTED LOAD(kVA):9.5
LOAD CLASSIFICATION CONNECTED LOAD(kVA) FACTOR DEMAND LOAD PANEL TOTALS
24.4 29.2 25.1 TOTAL CONNECTED PHASE AMPS
2930 3505 3015 TOTAL CONNECTED PHASE VA
SPARE E 1 20 41 42 20 1 E SPACE
SPARE E 1 20 39 40 20 1 E SPACE
SPARE E 1 20 37 38 20 1 E SPACE
SPARE E 1 20 35 36 20 1 E SPACE
CU5 CASE FANS & LTS N 1 20 33 1110 34 20 1 E SPACE
BS09 GLY COIL FANS M 1 20 31 220 32 20 1 E SPACE
BS08 GLY COIL FANS M 1 20 29 305 30 20 1 E SPACE
BS07 GLY CASE LIGHTS (11) M 1 20 27 140 28 20 1 E SPACE
BS07 GLY CASE FANS M 1 20 25 145 26 20 1 E SPACE
BS06 GLY CASE LIGHTS (11) M 1 20 23 190 24 20 1 E SPACE
BS06 GLY CASE FANS M 1 20 21 325 22 20 1 E SPACE
BS05 GLY CASE LIGHTS (11) M 1 20 19 250 20 20 1 E SPACE
BS05 GLY CASE FANS M 1 20 17 410 18 20 1 E SPACE
BS04 GLY CASE LIGHTS (11) M 1 20 15 195 245 16 20 1 M BS14 GLY CASE LIGHTS (11)
BS04 GLY CASE FANS M 1 20 13 135 205 14 20 1 M BS14 GLY CASE FANS
BS03 GLY CASE LIGHTS (11) M 1 20 11 245 650 12 20 1 E BS13 COIL FANS
BS03 GLY CASE FANS M 1 20 9 210 430 10 20 1 E BS12 COIL FANS
BS02 GLY CASE LIGHTS (11) M 1 20 7 165 540 8 20 1 E BS11 COIL FANS
BS02 GLY CASE FANS M 1 20 5 135 1080 6 20 1 E BS10 COIL FANS
BS01 GLY CASE LIGHTS (11) M 1 20 3 220 630 4 20 1 E DAIRY COOLER DOOR LTS (11)
BS01 GLY CASE FANS M 1 20 1 170 1100 2 20 1 E DAIRY COOLER DOOR HTRS
NOTES POLE AMP NO NO AMP POLE NOTESLOAD NAME
CKT BRK CKT PHASE A
LOAD (VA)
PHASE B
LOAD (VA)
PHASE C
LOAD (VA)
CKT BRK CKT
LOAD NAME
MODEL TYPE:EXISTING WIRES:4
MANUFACTURER:EXISTING PHASE:3 NOTES:YES
TYPE OF MAIN:100A MLO VOLTAGE:208Y/120 MOUNTING TYPE:EXISTING
LOCATION:HYBRID HOUSE DTB AMPS:100 MINIMUM AIC RATING:10,000
EXISTING PANEL: (E)CHB2
ISSUE BLOCK
Not part of this application. A
permit application shall be
submitted for interior remodeling.