HomeMy WebLinkAboutRefrigeration Electrical Plans - RE1, RE1.1, RE1.2, RE1.32 3 4 5 C D E F G H I NEW CU5 TCO2 (ON ROOF) NEW DTB GLY (ON ROOF) ROOF PENETRATION FOR CONDUIT ETR DTB DX RACK ETR DTA DX RACK EXISTING ROOF MOUNTED COMPRESSOR HOUSES REFRIGERATED CASES EVAP COILS DELI COOLER 1 2 3 4 D E F G H I BAKERY COOLERTYP 16.492 TYP 16.492 REFRIGERATED CASES TYP 16.492 REFRIGERATED CASES TYP 16.492 EXISTING ROOFTOP SPLIT SUCTION HYBRID HOUSE DTB EXISTING ROOFTOP SPLIT SUCTION HYBRID HOUSE DTA COORDINATE DEMOLITION OF EXISTING OGP CASE ELECTRICAL CIRCUITS WITH WALMART CONSTRUCTION MANAGER. SHEET: DRAWN BY: CHECKED BY: PROTO CYCLE: DOCUMENT DATE:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.P (407) 661-9100F (407) 661-9101c-p.comFlorida Corporate Certificate #AA C0005262600 Maitland Center ParkwaySuite #200Maitland, FL 32751CUSHING TERRELL306 W. RAIL ROAD SUITE 104MISSOULA, MT 59802Phone: (406)728-9522Fax: (406)728-8287EXISTING CONDITIONS WERE TAKEN FROM ORIGINAL DRAWINGS AND MAY NOT REFLECT EXACT "AS-BUILT" CONDITIONS. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR SHALL CAREFULLY COORDINATE NEW WORK AND DEMOLITION WITH ALL OTHER DISCIPLINES AND EXISTING CONDITIONS. EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES NOT RELIEVE THE RESPONSIBILITY OF PERFORMING THE WORK PROPERLY. NO ADDITIONAL COMPENSATION SHALL BE ALLOWED BECAUSE OF CONDITIONS THAT OCCUR DUE TO FAILURE TO FAMILIARIZE WORKERS WITH THIS KNOWLEDGE. DOCUMENTS WITHOUT SIGNATURE AND REQUIRED SEAL OF AOR/EOR ARE NOT FOR CONSTRUCTION RE1 OVERALL REFRIGERATION ELECTRICAL PLAN DM20240347BOYNTON BEACH, FL11/07/2511/07/25STORE NO: 5911-2769006/27/25BOYNTON BEACH, FLSP3625 S FEDERAL HWY.KEYNOTES 16.492 E.C. SHALL COORDINATE WITH GENERAL CONTRACTOR AND ARCHITECTURAL DEMOLITION PLANS THE EXTENT OF ELECTRICAL DEMOLITION. REMOVE UNUSED DEVICES, BOXES, CONDUITS, AND WIRING BACK TO ORIGINATING JUNCTION BOXES OR PANELBOARDS. REFERENCE POWER PLANS FOR CIRCUITRY TO BE REUSED. DEMOLITION SHALL NOT AFFECT ACTIVE CIRCUITS. IF CIRCUIT IS DEMOLISHED ALL THE WAY TO PANELBOARD, REMOVE CIRCUIT BREAKER AND REPLACE WITH FILLER PLATE. UPDATE TYPEWRITTEN CIRCUIT DIRECTORY IDENTIFYING CIRCUIT AS "SPACE". COORDINATE EXACT REQUIREMENTS WITH EXISTING CONDITIONS PRIOR TO BID. 1. COORDINATE ALL WORK WITH REFRIGERATION CONTRACTOR (R.C.) PRIOR TO INSTALLATION. 2. REFRIGERATED CASES: E.C. SHALL PROVIDE CONDUIT AND WIRE FOR REFRIGERATED CASE FANS, LIGHTS AND ANTI-SWEAT HEATERS, AND (IF APPLICABLE) ELECTRICAL DEFROST. PROVIDE ADEQUATE CONDUCTOR LENGTH TO ALLOW TERMINATION. NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND LABEL EACH CIRCUIT WITH BRANCH CIRCUIT DESIGNATION AND REFRIGERATION SYSTEM NUMBER FOR FINAL TERMINATION AT CASE BY R.C. REF CASE CONNECTION WIRING DETAIL. 3. IF NEW CASES ARE PROVIDED WITH A FACTORY INSTALLED TERMINAL STRIP AND JUMPERS FOR CONNECTION TO A SINGLE CIRCUIT FOR 120V CASE LOADS. RC SHALL REMOVE FACTORY INSTALLED JUMPERS AS REQUIRED TO UTILIZE EXISTING SEPARATE 120V FAN/LIGHT/ANTI-SWEAT CIRCUITS AS INDICATED ON PLANS AND/OR PANELBOARD SCHEDULES. ANY EXISTING ANTI-SWEAT CONTROL (SWEATMISER) SHALL BE BY-PASSED. CASES UTILIZING ELECTRICAL DEFROST WILL BE PROVIDED WITH SEPARATE 208V TERMINATIONS AT THE TERMINAL STRIP FOR CONNECTION TO THE 208V ELECTRIC DEFROST CIRCUIT. RC SHALL MAKE FINAL TERMINATIONS OF 120V AND 208V POWER CIRCUIT(S) AT CASE TERMINAL STRIP. REFER TO CASE CONNECTION SCHEMATIC ON REFRIGERATION SHEETS. 4. WALK-IN UNITS: PROVIDE CONDUIT AND WIRE FOR EVAPORATOR COIL FANS (CF) AND (IF APPLICABLE) ELECTRIC DEFROST (ED). PROVIDE ADEQUATE CONDUCTOR LENGTH TO ALLOW TERMINATION. NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND LABEL EACH CIRCUIT WITH BRANCH CIRCUIT DESIGNATION AND REFRIGERATION SYSTEM NUMBER FOR FINAL TERMINATION AT COIL BY R.C. REF EVAPORATOR COIL WIRING DETAIL. 5. ROUTE REFRIGERATED CASE AND WALK-IN UNIT COIL FAN, LIGHTS, ANTI-SWEAT AND DEFROST BRANCH CIRCUITS TO WIREWAYS PROVIDED AT REFRIGERATION EQUIPMENT AND/OR PANELBOARDS AS REQUIRED. 6. REFRIGERATED CASE WIRING COMPARTMENT REPRESENTED ON DRAWING BY JUNCTION BOX. 7. KEEP PENETRATIONS THROUGH WALK-IN UNITS TO A MINIMUM. ROUTE ALL CONDUITS SERVING FREEZERS AND COOLERS ON INSIDE OF BOX. 8. ALL CONDUITS INSTALLED ON TOP OF WALK-IN UNITS SHALL BE A MINIMUM OF 6" FROM ANY EDGE TO ALLOW SPACE FOR EDGE PROTECTION NETTING. DO NOT ROUTE CONDUITS ABOVE THE CEILING GRID ACCESS UNLESS CONDUITS ARE INSTALLED IN JOIST SPACE, REF ARCH. 9. UNDERSLAB CIRCUITS SHALL NOT BE ROUTED UNDER WALK-IN FREEZERS AND SHALL BE ROUTED ABOVE REFRIGERANT LINES WHERE THEY CROSS. 10. CIRCUITS FOR REFRIGERATED CASES SERVED BY UNDERSLAB REFRIGERATION PIPING ARE TO BE ROUTED UNDERSLAB AND EXTENDED TO THE FIRST CASE IN EACH SYSTEM. WIRING AND CONDUIT FOR SLAVE WIRING BETWEEN CASES SHALL BE PROVIDED BY R.C. REFER TO UNDERSLAB CASE CONNECTION WIRING DETAIL. 11. ALL UNDERSLAB CONDUITS SHALL BE 3/4" MIN. 12. CIRCUITS FOR REFRIGERATED CASES SERVED BY OVERHEAD REFRIGERATION PIPING ARE TO BE ROUTED DOWN FROM STRUCTURE AT THE SAME LOCATION AS THE REFRIGERATION PIPING AND EXTENDED TO THE FIRST CASE IN EACH SYSTEM. WIRE AND CONDUIT FOR SLAVE WIRING BETWEEN CASES SHALL BE PROVIDED BY THE R.C. REFER TO OVERHEAD CASE CONNECTION WIRING DETAIL. 13. ON GROUPS OF THREE OR MORE REFRIGERATED CASES WITH ELECTRIC DEFROST, R.C. SHALL CONNECT CASES TO CREATE A THREE-PHASE HEATER CIRCUIT. HEATER LOADS SHALL BE BALANCED BETWEEN PHASES AS EVENLY AS POSSIBLE. REF CASE DEFROST WIRING DETAIL. 14. PROVIDE A SEPARATE NEUTRAL FOR EACH NEW BRANCH CIRCUIT SERVING REFRIGERATED CASES OR WALK-IN UNITS. 15. PROVIDE CIRCUIT BREAKER LOCKING DEVICE (LOCK- OFF FOR MAINTENANCE) ON NEW AND/OR EXISTING CIRCUIT BREAKERS SERVING REFRIGERATED CASES. 16. REFERENCE ARCHITECTURAL DEMOLITION PLANS FOR FULL EXTENT OF DEMOLITION WORK REQUIRED. GENERAL REFRIGERATION ELECTRICAL NOTES 08.28.20 FOR LOCKOUT TAG OUT PROCEDURES REFER TO SPECIFICATION SECTION 01351 AND THE MASTER CONSTRUCTION AGREEMENT FOR WALMART GLOBAL ETHICS AND COMPLIANCE, "COMPLIANCE PERFORMANCE STANDARD FOR CONSTRUCTION." A R S OS B DH J SS OS2S OSS 3S 4S DS MS VSS KS S SINGLE POLE SWITCH CIRCUIT, CONCEALED IN WALLS OR CEILING, E INDICATES EXISTING WIRING SMOKE DETECTOR SAIL SWITCH JUNCTION BOX HORN / STROBE ABBREVIATIONS BUZZER CIRCUIT, CONCEALED IN SLAB FLOOR, E INDICATES EXISTING WIRING CONDUIT SLEEVE SURFACE MOUNTED PANELBOARD FLUSH MOUNTED PANELBOARD CIRCUIT, EXPOSED, E INDICATES EXISTING WIRING LOW VOLTAGE WIRING TELEPOWER POLE TELEPHONE / DATA BOX FOR ISD TELEPHONE, FLUSH FLOOR PUSH BUTTON MOTOR ALARM JUNCTION BOX, FOR REMOTE TEST/RESET (WALL MOUNTED/CEILING MOUNTED) EQUIPMENT CONNECTION POINT (PROVIDED WITH EQUIPMENT) NON-FUSED DISCONNECT RECEPTACLE, PLUG-MOLD RECEPTACLE, SIMPLEX RECEPTACLE, SPECIAL JUNCTION BOX (WALL MOUNTED/CEILING MOUNTED) ALARM JUNCTION BOX, (WALL MOUNTED/CEILING MOUNTED) RECEPTACLE, DOUBLE DUPLEX, ISOLATED GROUND FUSED DISCONNECT 4-WAY SWITCH RECEPTACLE, DUPLEX ISOLATED GROUND FLUSH FLOOR RECEPTACLE, DOUBLE DUPLEX RECEPTACLE, DUPLEX FLUSH FLOOR VARIABLE SPEED SWITCH KEYED SWITCH DIMMER SWITCH RECEPTACLE, DUPLEX, MOUNTED HORIZONTALLY RECEPTACLE, DUPLEX MANUAL MOTOR SWITCH 3-WAY SWITCH RECEPTACLE, DUPLEX ISOLATED GROUND LIGHT FIXTURE, NIGHT LIGHT VOLUMETRIC LIGHT FIXTURE LIGHT FIXTURE (WALL MOUNTED/CEILING MOUNTED) LIGHT FIXTURE (SYMBOLS APPLY ONLY WHEN USED ON DRAWINGS) SYMBOL DESCRIPTION RECEPTACLE, DUPLEX TWIST LOCK, ISOLATED GROUND, L5-15R, UNO SINGLE POLE OCCUPANCY SENSOR SWITCH LOW VOLTAGE CABLE BOX FOR OTHER DOOR HOLD OPEN RECEPTACLE, DUPLEX TWIST LOCK, L5-15R, UNO RECEPTACLE, SIMPLEX TWIST LOCK, ISOLATED GROUND, L5-15R, UNO RECEPTACLE, SIMPLEX TWIST LOCK, L5-15R, UNO OCCUPANCY SENSOR SWITCH, ONE-DIRECTION SENSING RECEPTACLE, GFI DOUBLE POLE OCCUPANCY SENSOR SWITCH T THERMOSTAT (WALL MOUNTED/CEILING MOUNTED) EXIT FIXTURE (WALL MOUNTED/CEILING MOUNTED) EMERGENCY LIGHT (WALL MOUNTED/CEILING MOUNTED) EMERGENCY LIGHT REMOTE HEADS (WALL MOUNTED/CEILING MOUNTED) a, b, c LOWER CASE LETTERS INDICATE SWITCHING CONFIGURATION AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE C CONDUIT CCT CIRCUIT CF CEILING FAN CW CASH WRAP EC ELECTRICAL CONTRACTOR EF EXHAUST FAN ETR EXISTING TO REMAIN EWC ELECTRIC WATER COOLER G GROUND GC GENERAL CONTRACTOR GFEP GROUND FAULT EQUIPMENT PROTECTION GFI GROUND FAULT CIRCUIT INTERRUPTER HD HAND DRYER IG ISOLATED GROUND LCU LIGHTING CONTROL UNIT NL NIGHT LIGHT NTS NOT TO SCALE REC REFRIGERATION ELECTRICAL CONTRACTOR RC REFRIGERATION CONTRACTOR RH RADIANT HEATER SC SECURITY CAMERA TR TAMPER RESISTANT TYP TYPICAL UH UNIT HEATER UNO UNLESS NOTED OTHERWISE WH WATER HEATER WP WEATHER PROOF WR WEATHER RESISTANT ELECTRICAL SYMBOLS LEGEND TIME CLOCKTC TRACK LIGHTING 12.17.21 OS OCCUPANCY SENSOR SWITCH, FOUR-DIRECTION SENSING 1" = 20'-0"2 OVERALL REFRIGERATION ELECTRICAL PLAN 1" = 20'-0"1 REFRIGERATION ELECTRICAL DEMO PLAN ARC FLASH HAZARD WARNING LABELING REQUIREMENTS PER NEC ARE PROVIDED BY OWNER UNDER SEPARATE CONTRACT. ARC FLASH CONTRACTOR TO VERIFY THE FEEDER ORIGINATION POINT SOURCE OF POWER FOR ALL DISTRIBUTION BOARDS, PANELBOARDS, AND BUSWAY AFFECTED BY THE REMODEL SCOPE OF WORK. PROVIDE A LAMINATED PLASTIC NAMEPLATE PER SPECIFICATIONS INDICATING THIS INFORMATION. EXAMPLES: H1A FED FROM MSWB L1D FED FROM H1B VIA T1D SOURCE OF SUPPLY NOTE COORDINATE ALL WORK THAT REQUIRES POWER INTERRUPTIONS TO THE STORE WITH THE STORE MANAGER AND THE WALMART CONSTRUCTION MANAGER A MINIMUM OF 48 HOURS IN ADVANCE OF ALL STORE POWER INTERRUPTIONS. IN ADDITION, IF THE MAIN ELECTRICAL SWITCHGEAR REQUIRES WORK AND DOES NOT HAVE A MAIN SERVICE DISCONNECTING MEANS, COORDINATE WITH THE UTILITY COMPANY A MINIMUM OF TWO WEEKS IN ADVANCE OF THE STORE POWER INTERRUPTION. IF STORE IS NOT OPEN 24 HOURS PER DAY, ALL STORE POWER INTERRUPTIONS ARE TO BE ACCOMPLISHED AFTER NORMAL STORE BUSINESS HOURS. PROVIDE TEMPORARY POWER AS REQUIRED PER SPECIFICATIONS. INSTALLATION OF NEW EQUIPMENT SHALL BE COMPLETED AND THE POWER SYSTEM TESTED AND RE-ENERGIZED PRIOR TO THE TIME ESTABLISHED BY THE STORE MANAGER AND THE WALMART CONSTRUCTION MANAGER. POWER INTERRUPTION NOTE 11.30.18 ISSUE BLOCK Not part of this application. A permit application shall be submitted for interior remodeling. J J J J J J J J J JJJ J J J J KE2-RE2-40(BS08 GLY)KE2-RE2-40(BS09 GLY)J J J J J J J J J JJ J CF J CF C J J J 2 BASR3.2 1 2 3 4 5 C D E BS05a GLY BS05b GLY BS05c GLY BS06a GLY BS06b GLY BS01a GLY BS01b GLY BS01c GLY BS02a GLY BS02b GLY BS03a GLY BS03b GLY BS03c GLY BS04a GLY BS04b GLY BS04c GLYBS07a GLYBS07b GLYBS20 GLYBS19b GLYBS19a GLY BS18 GLY BS17 GLYBS08 GLY BS09 GLYCU5a TCO2 CU5b TCO2 CU5c TCO2CU5d TCO2L2D3-81 CHB2-33 L2D1-81COORDINATE BOSS GATEWAY RECEPTACLE LOCATION WITH REFRIGERATION BAS INSTALLER CHB2-27 CHB2-25 16.145 16.145 CHB1-14 CHB1-12 16.145 16.145 CHA2-25 CHA2-23 16.145 16.145 CHA2-35 CHA2-33 16.145 16.145 CHA2-14 16.145 CHA2-19 CHA2-17 16.145 16.145 SPARE OUT EXISTING CIRCUIT CHA2-21 SINCE NEW CASE DOES NOT HAVE ANTI-SWEAT CHB2-11 CHB2-9 16.145 16.145 CHB2-15 CHB2-13 16.145 16.145 CHB2-3 CHB2-1 16.145 16.145 CHB2-7 CHB2-5 16.145 16.145 CHB2-21 CHB2-23 16.145 16.145CHB2-17 CHB2-19 16.145 16.145 16.710 2 RE1.3TYP 16.711 TYP 3 RE1.3TYP 3 RE1.3 TYP 3 RE1.3 TYP 4 RE1.3TYP CHB2-29 CHB2-31 L2D1-79CIRCUIT FOR DEVICES ON NEW BAS BACKBOARD IN EDC2 22 (CF) 22 (CF) WP, WR, GFCI CONVENIENCE RECEPTACLE FOR GLYCOL AND TCO2 CHARGING STATION. 1 2 G H BS14a GLYBS14b GLYBS14 GLYCHB2-16 CHB2-14 16.145 16.145 5 RE1.3 TYP 3 RE1.3 2 RE1.3 SHEET: DRAWN BY: CHECKED BY: PROTO CYCLE: DOCUMENT DATE:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.P (407) 661-9100F (407) 661-9101c-p.comFlorida Corporate Certificate #AA C0005262600 Maitland Center ParkwaySuite #200Maitland, FL 32751CUSHING TERRELL306 W. RAIL ROAD SUITE 104MISSOULA, MT 59802Phone: (406)728-9522Fax: (406)728-8287EXISTING CONDITIONS WERE TAKEN FROM ORIGINAL DRAWINGS AND MAY NOT REFLECT EXACT "AS-BUILT" CONDITIONS. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR SHALL CAREFULLY COORDINATE NEW WORK AND DEMOLITION WITH ALL OTHER DISCIPLINES AND EXISTING CONDITIONS. EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES NOT RELIEVE THE RESPONSIBILITY OF PERFORMING THE WORK PROPERLY. NO ADDITIONAL COMPENSATION SHALL BE ALLOWED BECAUSE OF CONDITIONS THAT OCCUR DUE TO FAILURE TO FAMILIARIZE WORKERS WITH THIS KNOWLEDGE. DOCUMENTS WITHOUT SIGNATURE AND REQUIRED SEAL OF AOR/EOR ARE NOT FOR CONSTRUCTION RE1.1 ENLARGED REFRIGERATION ELECTRICAL PLANS DM20240347BOYNTON BEACH, FL11/07/2511/07/25STORE NO: 5911-2769006/27/25BOYNTON BEACH, FLSP3625 S FEDERAL HWY.1. COORDINATE ALL WORK WITH REFRIGERATION CONTRACTOR (R.C.) PRIOR TO INSTALLATION. 2. REFRIGERATED CASES: E.C. SHALL PROVIDE CONDUIT AND WIRE FOR REFRIGERATED CASE FANS, LIGHTS AND ANTI-SWEAT HEATERS, AND (IF APPLICABLE) ELECTRICAL DEFROST. PROVIDE ADEQUATE CONDUCTOR LENGTH TO ALLOW TERMINATION. NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND LABEL EACH CIRCUIT WITH BRANCH CIRCUIT DESIGNATION AND REFRIGERATION SYSTEM NUMBER FOR FINAL TERMINATION AT CASE BY R.C. REF CASE CONNECTION WIRING DETAIL. 3. IF NEW CASES ARE PROVIDED WITH A FACTORY INSTALLED TERMINAL STRIP AND JUMPERS FOR CONNECTION TO A SINGLE CIRCUIT FOR 120V CASE LOADS. RC SHALL REMOVE FACTORY INSTALLED JUMPERS AS REQUIRED TO UTILIZE EXISTING SEPARATE 120V FAN/LIGHT/ANTI-SWEAT CIRCUITS AS INDICATED ON PLANS AND/OR PANELBOARD SCHEDULES. ANY EXISTING ANTI-SWEAT CONTROL (SWEATMISER) SHALL BE BY-PASSED. CASES UTILIZING ELECTRICAL DEFROST WILL BE PROVIDED WITH SEPARATE 208V TERMINATIONS AT THE TERMINAL STRIP FOR CONNECTION TO THE 208V ELECTRIC DEFROST CIRCUIT. RC SHALL MAKE FINAL TERMINATIONS OF 120V AND 208V POWER CIRCUIT(S) AT CASE TERMINAL STRIP. REFER TO CASE CONNECTION SCHEMATIC ON REFRIGERATION SHEETS. 4. WALK-IN UNITS: PROVIDE CONDUIT AND WIRE FOR EVAPORATOR COIL FANS (CF) AND (IF APPLICABLE) ELECTRIC DEFROST (ED). PROVIDE ADEQUATE CONDUCTOR LENGTH TO ALLOW TERMINATION. NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND LABEL EACH CIRCUIT WITH BRANCH CIRCUIT DESIGNATION AND REFRIGERATION SYSTEM NUMBER FOR FINAL TERMINATION AT COIL BY R.C. REF EVAPORATOR COIL WIRING DETAIL. 5. ROUTE REFRIGERATED CASE AND WALK-IN UNIT COIL FAN, LIGHTS, ANTI-SWEAT AND DEFROST BRANCH CIRCUITS TO WIREWAYS PROVIDED AT REFRIGERATION EQUIPMENT AND/OR PANELBOARDS AS REQUIRED. 6. REFRIGERATED CASE WIRING COMPARTMENT REPRESENTED ON DRAWING BY JUNCTION BOX. 7. KEEP PENETRATIONS THROUGH WALK-IN UNITS TO A MINIMUM. ROUTE ALL CONDUITS SERVING FREEZERS AND COOLERS ON INSIDE OF BOX. 8. ALL CONDUITS INSTALLED ON TOP OF WALK-IN UNITS SHALL BE A MINIMUM OF 6" FROM ANY EDGE TO ALLOW SPACE FOR EDGE PROTECTION NETTING. DO NOT ROUTE CONDUITS ABOVE THE CEILING GRID ACCESS UNLESS CONDUITS ARE INSTALLED IN JOIST SPACE, REF ARCH. 9. UNDERSLAB CIRCUITS SHALL NOT BE ROUTED UNDER WALK-IN FREEZERS AND SHALL BE ROUTED ABOVE REFRIGERANT LINES WHERE THEY CROSS. 10. CIRCUITS FOR REFRIGERATED CASES SERVED BY UNDERSLAB REFRIGERATION PIPING ARE TO BE ROUTED UNDERSLAB AND EXTENDED TO THE FIRST CASE IN EACH SYSTEM. WIRING AND CONDUIT FOR SLAVE WIRING BETWEEN CASES SHALL BE PROVIDED BY R.C. REFER TO UNDERSLAB CASE CONNECTION WIRING DETAIL. 11. ALL UNDERSLAB CONDUITS SHALL BE 3/4" MIN. 12. CIRCUITS FOR REFRIGERATED CASES SERVED BY OVERHEAD REFRIGERATION PIPING ARE TO BE ROUTED DOWN FROM STRUCTURE AT THE SAME LOCATION AS THE REFRIGERATION PIPING AND EXTENDED TO THE FIRST CASE IN EACH SYSTEM. WIRE AND CONDUIT FOR SLAVE WIRING BETWEEN CASES SHALL BE PROVIDED BY THE R.C. REFER TO OVERHEAD CASE CONNECTION WIRING DETAIL. 13. ON GROUPS OF THREE OR MORE REFRIGERATED CASES WITH ELECTRIC DEFROST, R.C. SHALL CONNECT CASES TO CREATE A THREE-PHASE HEATER CIRCUIT. HEATER LOADS SHALL BE BALANCED BETWEEN PHASES AS EVENLY AS POSSIBLE. REF CASE DEFROST WIRING DETAIL. 14. PROVIDE A SEPARATE NEUTRAL FOR EACH NEW BRANCH CIRCUIT SERVING REFRIGERATED CASES OR WALK-IN UNITS. 15. PROVIDE CIRCUIT BREAKER LOCKING DEVICE (LOCK- OFF FOR MAINTENANCE) ON NEW AND/OR EXISTING CIRCUIT BREAKERS SERVING REFRIGERATED CASES. 16. REFERENCE ARCHITECTURAL DEMOLITION PLANS FOR FULL EXTENT OF DEMOLITION WORK REQUIRED. GENERAL REFRIGERATION ELECTRICAL NOTES 08.28.20 1/8" = 1'-0"1 FRONT REFRIGERATION ELECTRICAL PLAN (NOVAR) KEYNOTES 16.145 CONNECT CIRCUIT(S) TO EXISTING BRANCH CIRCUITRY. MINIMUM WIRE SIZE AND PANELBOARD CIRCUIT ARE NOTED. VERIFY SIZE, RATING AND CONDITION OF EXISTING BRANCH CIRCUIT CONDUIT AND WIRE PRIOR TO USE TO ENSURE THAT THEY MEET REQUIRED SIZE, AND ALL U.L. RATINGS AND REPLACE AS REQUIRED. 16.710 BUILDING AUTOMATION CONDUITS: PROVIDE 1" (UNLESS NOTED OTHERWISE) CONDUIT (WITH PULL WIRE) ROUTED FROM 6" ABOVE BOTTOM OF BAR JOIST IN SALES FLOOR ACCESSIBLE CEILING SPACE THROUGH PVC CHASE. 16.711 POINT OF TRANSITION FROM EMT TO FLEX. PROVIDE CONDUIT AND BRANCH CIRCUITS FOR REFRIGERATED CASE FANS, LIGHTS, ANTI-SWEAT HEATERS, AND ELECTRICAL DEFROST (IF REQUIRED). TERMINATION TO REFRIGERATED CASE ELECTRICAL CONNECTION POINT BY R.C. REFER TO CASE CONNECTION WIRING DETAIL. 1/8" = 1'-0"3 REAR REFRIGERATION ELECTRICAL PLAN (NOVAR) FEEDER OR GROUND SIZE ALL CONDUIT AND CONDUCTOR SIZES ARE BASED ON EMT WITH 40% FILL, 75ºC RATED TERMINATIONS AND TYPE THHN/THWN-2 INSULATION. FOR NON-EMT CONDUIT OR TERMINATIONS OR INSULATION TYPES RATED LESS THAN 75ºC, MODIFY SIZES ACCORDING TO NEC. FEEDER SCHEDULE 22 (2)#12, (1)#12 G, 1/2" C ISSUE BLOCK Not part of this application. A permit application shall be submitted for interior remodeling. C 4 5 D L2B-32,34,36NEW CU5 TCO2 PROVIDE 3/4"C FROM LOW VOLTAGE WIRING COMPARTMENT TO ACCESSIBLE INTERIOR JOIST SPACE AND TERMINATE WITH BUSHING. (TYP)WR,WP 100A/3/NF, NEMA 3R MOUNT TO FRAMING OR NON- REMOVABLE ACCESS PANEL TO NEAREST RTU MAINTENANCE RECEPTACLE CIRCUIT 16.250103 2 3 F NEW DTB GLY H1A-25,27,2916.250 16.258 EXISTING ROOF MOUNTED SPLIT SUCTION HYBRID HOUSES ETR DTA DX ETR DTB DX 1 RE1.3 ROOF PENETRATIONBAS CONTROL TRANSFORMER INSTALLED INSIDE PUMP SKID ELECTRICAL CABINET BY BASR CONTRACTOR. FACTORY INSTALLED, WP/WR, GFCI RCPT. PANELS CHA1 AND CHA2 STACKED PANELS CHB1 AND CHB2 STACKED 33 SHEET: DRAWN BY: CHECKED BY: PROTO CYCLE: DOCUMENT DATE:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.P (407) 661-9100F (407) 661-9101c-p.comFlorida Corporate Certificate #AA C0005262600 Maitland Center ParkwaySuite #200Maitland, FL 32751CUSHING TERRELL306 W. RAIL ROAD SUITE 104MISSOULA, MT 59802Phone: (406)728-9522Fax: (406)728-8287EXISTING CONDITIONS WERE TAKEN FROM ORIGINAL DRAWINGS AND MAY NOT REFLECT EXACT "AS-BUILT" CONDITIONS. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR SHALL CAREFULLY COORDINATE NEW WORK AND DEMOLITION WITH ALL OTHER DISCIPLINES AND EXISTING CONDITIONS. EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES NOT RELIEVE THE RESPONSIBILITY OF PERFORMING THE WORK PROPERLY. NO ADDITIONAL COMPENSATION SHALL BE ALLOWED BECAUSE OF CONDITIONS THAT OCCUR DUE TO FAILURE TO FAMILIARIZE WORKERS WITH THIS KNOWLEDGE. DOCUMENTS WITHOUT SIGNATURE AND REQUIRED SEAL OF AOR/EOR ARE NOT FOR CONSTRUCTION RE1.2 ENLARGED REFRIGERATION ELECTRICAL PLANS DM20240347BOYNTON BEACH, FL11/07/2511/07/25STORE NO: 5911-2769006/27/25BOYNTON BEACH, FLSP3625 S FEDERAL HWY.1/8" = 1'-0"1 REFRIGERATION ELECTRICAL ROOF PLAN (FRONT) 1/8" = 1'-0"2 REFRIGERATION ELECTRICAL ROOF PLAN (REAR) 1. COORDINATE ALL WORK WITH REFRIGERATION CONTRACTOR (R.C.) PRIOR TO INSTALLATION. 2. REFRIGERATED CASES: E.C. SHALL PROVIDE CONDUIT AND WIRE FOR REFRIGERATED CASE FANS, LIGHTS AND ANTI-SWEAT HEATERS, AND (IF APPLICABLE) ELECTRICAL DEFROST. PROVIDE ADEQUATE CONDUCTOR LENGTH TO ALLOW TERMINATION. NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND LABEL EACH CIRCUIT WITH BRANCH CIRCUIT DESIGNATION AND REFRIGERATION SYSTEM NUMBER FOR FINAL TERMINATION AT CASE BY R.C. REF CASE CONNECTION WIRING DETAIL. 3. IF NEW CASES ARE PROVIDED WITH A FACTORY INSTALLED TERMINAL STRIP AND JUMPERS FOR CONNECTION TO A SINGLE CIRCUIT FOR 120V CASE LOADS. RC SHALL REMOVE FACTORY INSTALLED JUMPERS AS REQUIRED TO UTILIZE EXISTING SEPARATE 120V FAN/LIGHT/ANTI-SWEAT CIRCUITS AS INDICATED ON PLANS AND/OR PANELBOARD SCHEDULES. ANY EXISTING ANTI-SWEAT CONTROL (SWEATMISER) SHALL BE BY-PASSED. CASES UTILIZING ELECTRICAL DEFROST WILL BE PROVIDED WITH SEPARATE 208V TERMINATIONS AT THE TERMINAL STRIP FOR CONNECTION TO THE 208V ELECTRIC DEFROST CIRCUIT. RC SHALL MAKE FINAL TERMINATIONS OF 120V AND 208V POWER CIRCUIT(S) AT CASE TERMINAL STRIP. REFER TO CASE CONNECTION SCHEMATIC ON REFRIGERATION SHEETS. 4. WALK-IN UNITS: PROVIDE CONDUIT AND WIRE FOR EVAPORATOR COIL FANS (CF) AND (IF APPLICABLE) ELECTRIC DEFROST (ED). PROVIDE ADEQUATE CONDUCTOR LENGTH TO ALLOW TERMINATION. NEATLY BUNDLE CIRCUITS AND CLEARLY TAG AND LABEL EACH CIRCUIT WITH BRANCH CIRCUIT DESIGNATION AND REFRIGERATION SYSTEM NUMBER FOR FINAL TERMINATION AT COIL BY R.C. REF EVAPORATOR COIL WIRING DETAIL. 5. ROUTE REFRIGERATED CASE AND WALK-IN UNIT COIL FAN, LIGHTS, ANTI-SWEAT AND DEFROST BRANCH CIRCUITS TO WIREWAYS PROVIDED AT REFRIGERATION EQUIPMENT AND/OR PANELBOARDS AS REQUIRED. 6. REFRIGERATED CASE WIRING COMPARTMENT REPRESENTED ON DRAWING BY JUNCTION BOX. 7. KEEP PENETRATIONS THROUGH WALK-IN UNITS TO A MINIMUM. ROUTE ALL CONDUITS SERVING FREEZERS AND COOLERS ON INSIDE OF BOX. 8. ALL CONDUITS INSTALLED ON TOP OF WALK-IN UNITS SHALL BE A MINIMUM OF 6" FROM ANY EDGE TO ALLOW SPACE FOR EDGE PROTECTION NETTING. DO NOT ROUTE CONDUITS ABOVE THE CEILING GRID ACCESS UNLESS CONDUITS ARE INSTALLED IN JOIST SPACE, REF ARCH. 9. UNDERSLAB CIRCUITS SHALL NOT BE ROUTED UNDER WALK-IN FREEZERS AND SHALL BE ROUTED ABOVE REFRIGERANT LINES WHERE THEY CROSS. 10. CIRCUITS FOR REFRIGERATED CASES SERVED BY UNDERSLAB REFRIGERATION PIPING ARE TO BE ROUTED UNDERSLAB AND EXTENDED TO THE FIRST CASE IN EACH SYSTEM. WIRING AND CONDUIT FOR SLAVE WIRING BETWEEN CASES SHALL BE PROVIDED BY R.C. REFER TO UNDERSLAB CASE CONNECTION WIRING DETAIL. 11. ALL UNDERSLAB CONDUITS SHALL BE 3/4" MIN. 12. CIRCUITS FOR REFRIGERATED CASES SERVED BY OVERHEAD REFRIGERATION PIPING ARE TO BE ROUTED DOWN FROM STRUCTURE AT THE SAME LOCATION AS THE REFRIGERATION PIPING AND EXTENDED TO THE FIRST CASE IN EACH SYSTEM. WIRE AND CONDUIT FOR SLAVE WIRING BETWEEN CASES SHALL BE PROVIDED BY THE R.C. REFER TO OVERHEAD CASE CONNECTION WIRING DETAIL. 13. ON GROUPS OF THREE OR MORE REFRIGERATED CASES WITH ELECTRIC DEFROST, R.C. SHALL CONNECT CASES TO CREATE A THREE-PHASE HEATER CIRCUIT. HEATER LOADS SHALL BE BALANCED BETWEEN PHASES AS EVENLY AS POSSIBLE. REF CASE DEFROST WIRING DETAIL. 14. PROVIDE A SEPARATE NEUTRAL FOR EACH NEW BRANCH CIRCUIT SERVING REFRIGERATED CASES OR WALK-IN UNITS. 15. PROVIDE CIRCUIT BREAKER LOCKING DEVICE (LOCK- OFF FOR MAINTENANCE) ON NEW AND/OR EXISTING CIRCUIT BREAKERS SERVING REFRIGERATED CASES. 16. REFERENCE ARCHITECTURAL DEMOLITION PLANS FOR FULL EXTENT OF DEMOLITION WORK REQUIRED. GENERAL REFRIGERATION ELECTRICAL NOTES 08.28.20 KEYNOTES 16.250 CONNECT CIRCUITRY TO FACTORY PROVIDED MAINTENANCE RECEPTACLE. ROUTE CIRCUIT TO NEAREST RTU OR AHU MAINTENANCE RECEPTACLE CIRCUIT. 16.258 CONNECT CIRCUITRY TO FACTORY PROVIDED DISCONNECT SWITCH. FEEDER OR GROUND SIZE ALL CONDUIT AND CONDUCTOR SIZES ARE BASED ON EMT WITH 40% FILL, 75ºC RATED TERMINATIONS AND TYPE THHN/THWN-2 INSULATION. FOR NON-EMT CONDUIT OR TERMINATIONS OR INSULATION TYPES RATED LESS THAN 75ºC, MODIFY SIZES ACCORDING TO NEC. FEEDER SCHEDULE 33 (3)#10, (1)#10 G, 1/2” C 103 (3)#3, (1)#8 G, 1" C ISSUE BLOCK Not part of this application. A permit application shall be submitted for interior remodeling. SUPPORT CONDUIT FROM TOP OR BOTTOM OF STRUCTURE ONLY. DO NOT INSTALL CONDUIT BELOW STRUCTURE. ROOF OPENING MAY CONTAIN MULTIPLE CONDUIT TYPES, SEE ELECTRICAL AND BASR PLANS. MINIMUM 2" GAP BETWEEN ADJACENT CONDUITS. OWNER PROVIDED MANUFACTURED CURB, SEE ARCHITECTURAL DETAILS FOR SIZE, INSULATION, ASSEMBLY, AND SEALING REQUIREMENTS SUPPORT CONDUIT PER SPECIFICATIONS, SEE ROOF SUPPORT DETAIL. REMOVABLE HOOD PROVIDED WITH CURB. DROP CONDUIT NEAR HOOD TO ALIGN WITH ROOF SUPPORT HEIGHT IF NEEDED. SECURE CONDUIT TO UNISTRUT AT TOP OF CURB 5" CENTER OF CONDUIT TO TOP OF CURB. PAINT CONDUIT TO MATCH ADJACENT CEILING COLOR TYPICAL REFRIGERATED CASE SYSTEM 12" WIRE PIGTAILS (TYP) 5' FLEX CONDUIT (TYP) ROUTE EMT CONDUITS (UNDER CASES, ABOVE SLAB) TO POINT OF TRANSITION TO FLEX PROVIDE TRANSITION FROM EMT TO FLEX BRANCH CIRCUIT AND EMS CONDUITS TO OTHER REFRIGERATED CASE SYSTEMS (TYP) BRACKET CONDUIT TO FLOOR AS REQUIRED BY CODE (TYP) ROUTE CONDUIT FOR BRANCH CIRCUITS FROM OVERHEAD THRU CHASE, ALONG WITH REFRIGERATION PIPING (TYP) PROVIDE (2) CONDUITS AND BRANCH CIRCUITS PER REFRIGERATED CASE SYSTEM. ONE CONDUIT WILL SERVE 120V CASE FANS, LIGHTS AND ANTI-SWEAT CIRCUITS; ONE CONDUIT WILL SERVE 208V CASE ELECTRIC DEFROST CIRCUIT. ON SYSTEMS WITHOUT ELECTRIC DEFROST, ONLY PROVIDE ONE CONDUIT PROVIDE 5' LENGTH OF FLEX CONDUIT WITH 12" PIGTAIL STUBBED FROM END OF EACH FLEX CONDUIT. PVC CHASE EMS CONDUIT: PROVIDE CONDUIT (WITH PULL WIRE) ROUTED 6" ABOVE BOTTOM OF BAR JOIST IN SALES FLOOR ACCESSIBLE CEILING SPACE THROUGH PVC CHASE. CONDUIT WILL BE SIZED 1" FOR (4) OR FEWER EMS CABLES AND 1-1/4" FOR (5) OR MORE EMS CABLES.REAR HALF OF REFRIGERATED CASE DESIGNATED FOR PIPING AND VALVES FRONT HALF OF REFRIGERATED CASE DESIGNATED FOR ELECTRICAL AND BAS COMPONENTS REFRIGERATED CASE CONTROLLER REFER TO BASR PLANS FOR CASE CONTROLLER TYPE, WIRING DETAILS, AND CONTROLLER TERMINATION POINTS, TYP CONDUITS FOR REFRIGERATED CASE POWER. ONE CONDUIT WILL SERVE 120V FANS, LIGHTS, AND ANTI-SWEAT HEATERS CIRCUITS. ONE CONDUIT WILL SERVE 208V ELECTRIC DEFROST CIRCUIT. REFER TO REFRIGERATION ELECTRICAL PLANS IF ELECTRIC DEFROST IS REQUIRED AND FOR FEEDER AND CONDUIT SIZES. CONDUIT FOR DAISY CHAINED BASR CABLING. FROM PREVIOUS BASR CONTROLLER OR MASTER CONTROLLER. REFER TO BASR PLANS AND ONE-LINE DIAGRAM. TO NEXT BASR CONTROLLER IN DAISY CHAIN OR MASTER CONTROLLER. REFER TO BASR PLANS AND ONE-LINE DIAGRAM. CASE JUNCTION BOX FOR TRANSITION FROM EMT TO FLEX CONDUIT, TYP. FLEX CONDUITS FROM CASE JUNCTION BOX TO CASE CONTROLLER, TYP. ONE CONDUIT FOR 120V CASE FANS, LIGHTS, AND ANTI-SWEAT HEATERS CIRCUIT. ONE CONDUIT FOR 208V ELECTRIC DEFROST CIRCUIT. REFRIGERATED CASE, TYP. REFER TO PLANS FOR QUANTITY OF CASES ON CASE LINEUP. ROUTE CONDUITS WITH REFRIGERATION PIPING TO ACCESSIBLE JOIST SPACE. REFER TO REFRIGERATION PLANS FOR CHASE ROUTING DETAILS, IF REQUIRED. EMT CONDUIT BETWEEN CASE JUNCTION BOXES, TYP PROVIDE CEILING MOUNTED MANUAL SWITCH 'HUBBELL' CLASS HBLDS3 OR ‘EATON’CLASS AHDS30. IF OVER 30 AMPS PROVIDE ‘HUBBEL’CLASS HBLDS6 OR ‘EATON’AHDS60. WITH NEMA 4X WATERTIGHT NON-METALLIC ENCLOSURE FOR CONNECTION OF EVAPORATOR COIL FANS (CF) AND/OR ELECTRIC DEFROST (ED), (WHERE SHOWN ON DRAWINGS). PROVIDE PLACARD ON CEILING DETAILING PURPOSE OF EACH MANUAL SWITCH AND THE ELECTRICAL SOURCE (PANEL AND CIRCUIT NUMBER). NOTE: DO NOT LOCATE WP JUNCTION BOX DIRECTLY IN FRONT OF DISCHARGE FAN, OFFSET TO SIDE. TYPICAL COIL EMT CONDUIT AND WIRING TO NEXT COIL POWER JUNCTION BOX ON SAME SYSTEM WHEN MULTIPLE COILS ARE IN SAME COOLER/FREEZER BOX. POWER CONDUIT AND WIRING SAME SIZE AND QUANTITY AS WIRING TO PANEL. 1" EMT CONDUIT PENETRATION SEALED WITH SILICONE SEALANT. NOTE: TAP DEFROST CIRCUIT IN JUNCTION BOX WITH #10 AWG FOR CONNECTION TO UNIT. MAXIMUM LENGTH OF TAP CONDUCTOR 18" CONDULET AT CEILING PENETRATION FILLED WITH SILICONE COIL FAN/DEFROST POWER EMT CONDUIT AND WIRING TO DESIGNATED PANEL VIA WALK-IN FAN/DEFROST CONTROL DEVICE. FINAL CONNECTION BY RC. COOLER/FREEZER BOX CEILING CEILING MOUNTED WP JUNCTION BOX WITH THREADED HUBS AND GASKETED COVERPLATE. SEAL TOP OF JUNCTION BOX TO COOLER/FREEZER CEILING WITH SILICONE SEALANT. 1" LIQUID-TIGHT FLEXIBLE METAL CONDUIT TO KNOCKOUT ON UNIT. FINAL CONNECTION TO COIL BY RC. Ø Ø Ø PROVIDE 208/3Ø HOME RUN TO DESIGNATED PANEL BOARD . FINAL CONNECTION AT CASE BY R.C. CALCULATION OF 3Ø UNBALANCED LOAD B LOAD = (12.6 A + 12.6 A) x .866 = 21.8 A (HIGH LEG) A LOAD = (12.6 A + 9.9 A) x .866 = 19.5 A B LOAD = (12.6 A + 12.6 A) x .866 = 21.8 A (HIGH LEG) C LOAD = (12.6 A + 9.9 A) x .866 = 19.5 A NOTES: ON SYSTEMS WITH UNEQUAL LOADS, REC (REFRIGERATION ELECTRICAL CONTRACTOR) SHALL ARRANGE CONNECTIONS FOR MAXIMUM BALANCE A CCBBA C B A 12.6 A 9.9 A12.6 A 4 DOOR CASE5 DOOR CASE5 DOOR CASE TYPICAL REFRIGERATED CASE SYSTEM NTS1ROOF PENETRATION (CONDUIT) NTS2CASE CONNECTION WIRING (PVC CHASE) NTS3CASE CONDUIT ROUTING NTS4EVAPORATOR COIL WIRING NTS5CASE DEFROST WIRING SHEET: DRAWN BY: CHECKED BY: PROTO CYCLE: DOCUMENT DATE:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.P (407) 661-9100F (407) 661-9101c-p.comFlorida Corporate Certificate #AA C0005262600 Maitland Center ParkwaySuite #200Maitland, FL 32751CUSHING TERRELL306 W. RAIL ROAD SUITE 104MISSOULA, MT 59802Phone: (406)728-9522Fax: (406)728-8287EXISTING CONDITIONS WERE TAKEN FROM ORIGINAL DRAWINGS AND MAY NOT REFLECT EXACT "AS-BUILT" CONDITIONS. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR SHALL CAREFULLY COORDINATE NEW WORK AND DEMOLITION WITH ALL OTHER DISCIPLINES AND EXISTING CONDITIONS. EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES NOT RELIEVE THE RESPONSIBILITY OF PERFORMING THE WORK PROPERLY. NO ADDITIONAL COMPENSATION SHALL BE ALLOWED BECAUSE OF CONDITIONS THAT OCCUR DUE TO FAILURE TO FAMILIARIZE WORKERS WITH THIS KNOWLEDGE. DOCUMENTS WITHOUT SIGNATURE AND REQUIRED SEAL OF AOR/EOR ARE NOT FOR CONSTRUCTION RE1.3 REFRIGERATION ELECTRICAL PANEL SCHEDULES AND DETAILS DM20240347BOYNTON BEACH, FL11/07/2511/07/25STORE NO: 5911-2769006/27/25BOYNTON BEACH, FLSP3625 S FEDERAL HWY.A. LEGEND: (N) NEW, (E ) EXISTING, (M) MODIFY, B. CONTROLLED VIA 100A-3P CONTACTOR CIRCUIT NOTES: MISCELLANEOUS 0.4 PER NEC 210.20(A) 0.5 WATER HEAT 0.0 100% 0.0 ELECTRIC HEAT 0.0 100% 0.0 DEMAND AMPS 33.9 KITCHEN EQUIPMENT 0.0 PER NEC 220.56 0.0 DEMAND LOAD (kVA):12.2 MOTORS 4.4 PER NEC 430.24 4.7 CONVENIENCE OUTLETS 1.6 PER NEC 220.44 1.6 CONNECTED AMPS:29.9 LIGHTING 4.4 PER NEC 210.20(A) 5.5 CONNECTED LOAD(kVA):10.8 LOAD CLASSIFICATION CONNECTED LOAD(kVA) FACTOR DEMAND LOAD PANEL TOTALS 30.8 31.7 27.2 TOTAL CONNECTED PHASE AMPS 3700 3800 3260 TOTAL CONNECTED PHASE VA SPARE E 1 20 41 42 20 1 E SPACE AS12 CASE LIGHTS (11) E 1 20 39 280 40 20 1 E SPACE AS12 CASE FANS E 1 20 37 150 38 20 1 E SPACE BS20 GLY CASE LIGHTS (11) M 1 20 35 60 36 20 1 E SPACE BS20 GLY CASE FANS M 1 20 33 40 34 20 1 E SPACE AS08 CASE FANS E 1 20 31 1100 32 20 1 E SPACE AS07 CASE LIGHTS (11) E 1 20 29 1260 30 20 1 E SPARE AS07 CASE FANS E 1 20 27 420 28 20 1 E SPARE BS18 GLY CASE LIGHTS (11) M 1 20 25 50 26 20 1 E SPARE BS18 GLY CASE FANS M 1 20 23 110 24 20 1 E SPARE SPARE M 1 20 21 180 22 20 1 E AS11 EMS CONTROLLER BS17 GLY CASE LIGHTS (11) M 1 20 19 90 180 20 20 1 E AS10 EMS CONTROLLER BS17 GLY CASE FANS M 1 20 17 150 180 18 20 1 E AS08 CASE RECEPTACLE AS04 CASE LIGHTS (11) E 1 20 15 590 180 16 20 1 E AS08 CASE RECEPTACLE AS04 CASE FANS E 1 20 13 770 180 14 20 1 M BS17 GLY CASE RECEPTACLE AS03 CASE LIGHTS (11) E 1 20 11 590 180 12 20 1 E AS04 CASE RECEPTACLE AS03 CASE FANS E 1 20 9 770 180 10 20 1 E AS04 CASE RECEPTACLE AS02 CASE LIGHTS (11) E 1 20 7 460 180 8 20 1 E AS03 CASE RECEPTACLE AS02 CASE FANS E 1 20 5 550 180 6 20 1 E AS03 CASE RECEPTACLE AS01 CASE LIGHTS (11) E 1 20 3 980 180 4 20 1 E AS02 CASE RECEPTACLE AS01 CASE FANS E 1 20 1 360 180 2 20 1 E AS02 CASE RECEPTACLE NOTES POLE AMP NO NO AMP POLE NOTESLOAD NAME CKT BRK CKT PHASE A LOAD (VA) PHASE B LOAD (VA) PHASE C LOAD (VA) CKT BRK CKT LOAD NAME MODEL TYPE:EXISTING WIRES:4 MANUFACTURER:EXISTING PHASE:3 NOTES:YES TYPE OF MAIN:100A MLO VOLTAGE:208Y/120 MOUNTING TYPE:EXISTING LOCATION:HYBRID HOUSE DTA AMPS:100 MINIMUM AIC RATING:10,000 EXISTING PANEL: (E)CHA2 A. LEGEND: (N) NEW, (E ) EXISTING, (M) MODIFY, B. CONTROLLED VIA 100A-3P CONTACTOR CIRCUIT NOTES: MISCELLANEOUS 0.2 PER NEC 210.20(A) 0.2 WATER HEAT 0.0 100% 0.0 ELECTRIC HEAT 10.4 100% 10.4 DEMAND AMPS 47.6 KITCHEN EQUIPMENT 0.0 PER NEC 220.56 0.0 DEMAND LOAD (kVA):17.1 MOTORS 2.0 PER NEC 430.24 2.1 CONVENIENCE OUTLETS 0.7 PER NEC 220.44 0.7 CONNECTED AMPS:45.2 LIGHTING 3.0 PER NEC 210.20(A) 3.7 CONNECTED LOAD(kVA):16.3 LOAD CLASSIFICATION CONNECTED LOAD(kVA) FACTOR DEMAND LOAD PANEL TOTALS 44.2 41.6 49.8 TOTAL CONNECTED PHASE AMPS 5300 4990 5970 TOTAL CONNECTED PHASE VA SPARE E 1 20 41 42 20 1 E SPACE B06 CASE LIGHTS (11) E 1 20 39 460 40 20 1 E SPACE B06 CASE A/S HTRS E 1 20 37 1670 38 20 1 E SPACE B06 CASE FANS E 1 20 35 300 36 20 1 E SPACE B05 CASE LIGHTS (11) E 1 20 33 550 34 20 1 E SPACE B05 CASE A/S HTRS E 1 20 31 930 32 20 1 E SPACE B05 CASE A/S HTRS E 1 20 29 1040 30 20 1 E SPACE B05 CASE FANS E 1 20 27 350 28 20 1 E SPACE B04 CASE LIGHTS (11) E 1 20 25 430 26 20 1 E SPACE B04 CASE A/S HTRS (6) E 1 20 23 1560 24 20 1 E SPACE B04 CASE FANS E 1 20 21 280 22 20 1 E SPACE B03 CASE LIGHTS (11) E 1 20 19 430 20 20 1 E SPACE B03 CASE A/S HTRS E 1 20 17 1560 18 20 1 E SPACE B03 CASE FANS E 1 20 15 280 16 20 1 E SPACE B02 CASE LIGHTS (11) E 1 20 13 460 120 14 20 1 M BS19 GLY CASE FANS B02 CASE FANS E 1 20 11 300 100 12 20 1 M BS19 GLY CASE LIGHTS B02 CASE A/S HTRS E 1 20 9 1670 180 10 20 1 E B07 EMS CONTROLLER B01 CASE LIGHTS (11) E 1 20 7 550 180 8 20 1 E B06 CASE RECEPTACLE B01 CASE A/S HTRS E 1 20 5 930 180 6 20 1 E B04 CASE RECEPTACLE B01 CASE A/S HTRS E 1 20 3 1040 180 4 20 1 E B03 CASE RECEPTACLE B01 CASE FANS E 1 20 1 350 180 2 20 1 E B02 CASE RECEPTACLE NOTES POLE AMP NO NO AMP POLE NOTESLOAD NAME CKT BRK CKT PHASE A LOAD (VA) PHASE B LOAD (VA) PHASE C LOAD (VA) CKT BRK CKT LOAD NAME MODEL TYPE:EXISTING WIRES:4 MANUFACTURER:EXISTING PHASE:3 NOTES:YES TYPE OF MAIN:100A MLO VOLTAGE:208Y/120 MOUNTING TYPE:EXISTING LOCATION:HYBRID HOUSE DTB AMPS:100 MINIMUM AIC RATING:10,000 EXISTING PANEL: (E)CHB1 A. LEGEND: (N) NEW, (E ) EXISTING, (M) MODIFY CIRCUIT NOTES: MISCELLANEOUS 1.1 PER NEC 210.20(A) 1.4 WATER HEAT 0.0 100% 0.0 ELECTRIC HEAT 1.1 100% 1.1 DEMAND AMPS 29.4 KITCHEN EQUIPMENT 0.0 PER NEC 220.56 0.0 DEMAND LOAD (kVA):10.6 MOTORS 5.0 PER NEC 430.24 5.2 CONVENIENCE OUTLETS 0.0 PER NEC 220.44 0.0 CONNECTED AMPS:26.3 LIGHTING 2.3 PER NEC 210.20(A) 2.9 CONNECTED LOAD(kVA):9.5 LOAD CLASSIFICATION CONNECTED LOAD(kVA) FACTOR DEMAND LOAD PANEL TOTALS 24.4 29.2 25.1 TOTAL CONNECTED PHASE AMPS 2930 3505 3015 TOTAL CONNECTED PHASE VA SPARE E 1 20 41 42 20 1 E SPACE SPARE E 1 20 39 40 20 1 E SPACE SPARE E 1 20 37 38 20 1 E SPACE SPARE E 1 20 35 36 20 1 E SPACE CU5 CASE FANS & LTS N 1 20 33 1110 34 20 1 E SPACE BS09 GLY COIL FANS M 1 20 31 220 32 20 1 E SPACE BS08 GLY COIL FANS M 1 20 29 305 30 20 1 E SPACE BS07 GLY CASE LIGHTS (11) M 1 20 27 140 28 20 1 E SPACE BS07 GLY CASE FANS M 1 20 25 145 26 20 1 E SPACE BS06 GLY CASE LIGHTS (11) M 1 20 23 190 24 20 1 E SPACE BS06 GLY CASE FANS M 1 20 21 325 22 20 1 E SPACE BS05 GLY CASE LIGHTS (11) M 1 20 19 250 20 20 1 E SPACE BS05 GLY CASE FANS M 1 20 17 410 18 20 1 E SPACE BS04 GLY CASE LIGHTS (11) M 1 20 15 195 245 16 20 1 M BS14 GLY CASE LIGHTS (11) BS04 GLY CASE FANS M 1 20 13 135 205 14 20 1 M BS14 GLY CASE FANS BS03 GLY CASE LIGHTS (11) M 1 20 11 245 650 12 20 1 E BS13 COIL FANS BS03 GLY CASE FANS M 1 20 9 210 430 10 20 1 E BS12 COIL FANS BS02 GLY CASE LIGHTS (11) M 1 20 7 165 540 8 20 1 E BS11 COIL FANS BS02 GLY CASE FANS M 1 20 5 135 1080 6 20 1 E BS10 COIL FANS BS01 GLY CASE LIGHTS (11) M 1 20 3 220 630 4 20 1 E DAIRY COOLER DOOR LTS (11) BS01 GLY CASE FANS M 1 20 1 170 1100 2 20 1 E DAIRY COOLER DOOR HTRS NOTES POLE AMP NO NO AMP POLE NOTESLOAD NAME CKT BRK CKT PHASE A LOAD (VA) PHASE B LOAD (VA) PHASE C LOAD (VA) CKT BRK CKT LOAD NAME MODEL TYPE:EXISTING WIRES:4 MANUFACTURER:EXISTING PHASE:3 NOTES:YES TYPE OF MAIN:100A MLO VOLTAGE:208Y/120 MOUNTING TYPE:EXISTING LOCATION:HYBRID HOUSE DTB AMPS:100 MINIMUM AIC RATING:10,000 EXISTING PANEL: (E)CHB2 ISSUE BLOCK Not part of this application. A permit application shall be submitted for interior remodeling.