REVIEW COMMENTS
PUBLIC WORKS DEPARTMENT
MEMORANDUM #94-194
TO: Tambri Heyden, Planning & Zoning Director
FROM: Robert Eichorst, Public Works Director
SUBJ: New Site Plan - Miami Subs
DATE: July 21, 1994
The present location of the dumpster at the above site is
acceptable, however approach angle will need to be changed.
Eichorst
Works Director
RE/cr
00
m 0 ,
JUL L 5 1994
00
ENGINEERING DEPARTMENT MEMORANDUM NO. 94-211 (Amended)
TO:
Tambri J. Heyden
Planning & Zoning Director
w~~~~m ~ukill, P.E.
~Englneer
FROM:
DATE:
July 21, 1994
RE:
MIAMI SUB'S GRILL, PLANNING FILE COUS 94-004
Attached please find Mr. Finizio's review comments on subject plans
and exhibits. Paragraph #1 is self explanatory.
with respect to paragraph #2, plans are not consistent. The
sidewalk along the north side of the building scales 6' on site
plan (cover) sheet, 8' on landscape plan L-l and site plan A-I and
5' on floor plan A-2. Depending on which configuration is correct,
you mayor may not comply with the required backup space Mr.
Finizio describes. Please provide revisions to plans to
demonstrate compliance.
WVH/ck
C:MIAMISUB.TRC
attachment: Engineering Memo No. 94-208
ENGINEERING DEPARTMENT MEMORANDUM NO. 94-208 (Amended)
TO:
william Hukill, P.E.
City Engineer
FROM:
vincent A. Finizio
Deputy City Engineer
DATE:
July 20, 1994
RE:
Miami Sub's Grill
Planning Department File No. COUS 94-004
I am in receipt of the above referenced plan and herein offer the
following comments(s):
1. The handicap stalls along the west property line of the
parking facility do not comply with minimum width requirements
for handicap stalls and access ramps required in Section 5-
142(k), "Handicap Requirements". The total width of the two
handicap stalls and access area should equal 29', however,
when I scale the drawings the total width of the two stalls
and access area equals 26.5'. This deviation from City codes
will impact the layout in the general vicinity of the stalls
possibly requiring a modification to the plans. There is
however a note that indicates these spaces are existing and it
is possible that the inplace stalls comply with code but in
any event the plans should be revised to provide a true
representation of that which exists.
2. The area depicted along the north side of the parking
facility, specifically the seven existing parking spaces
immediately north of the restaurant, do not comply with the
required 27' free and unobstructed backup space required by
Section 5-142(i), "Parking Lot Layout", Subsection (1),
" Appendix" .
*
VAF/ck
C:MIAMISUB.VF2
BUILDING DEPARTMENT
MEMORANDUM NO. 94-181
July 18, 1994
From:
Tambri J. Heyden, Planning &lO ing
Don Jaeger, Building Officia
Al Newbold, Deputy Building ficial
Director
To:
Via:
Re:
TRC COMMENTS - Site Plan
Miami Subs, 4742 N. Congress (Boynton Lakes Plaza)
The Building Department has reviewed the documents submitted and
offer the following comments:
1. Handicap ramps and walks from the road right-of-way to
the entrance of the building must be provided per the
handicap code, and the building must also be handicap
accessible.
2. Unless this property is a separate, deeded, out-parcel,
it cannot have its own free-standing sign. The
location of the sign needs to be shown on the site
plan.
Contingent upon the handicap requirements and all sign codes
being met, we support proceeding with this project.
A~
AN:mh
A:MIAMISUB.TRC
.'99lA
Plz ANNING AND
ONING DEPT.
"
FIRE PREVENTION MEMORANDUM NO. 94-259 WDC
TO:
PLANNING DEPARTMENT
FROM:
FIRE DEPARTMENT
DATE:
JULY 25, 1994
RE: TRC - SITE PLAN (I)
MIAMI SUBS AT BOYNTON LAKES PLAZA
4742 N CONGRESS AVENUE
There are no objections to this plan.
(
MEMORANDUM
Utilities #94-252
TO: Tambri J. Heyden
Planning & Zon'
FROM: John A. Guidry,
Director of Utilities
DATE: July 29, 1994
SUBJECT: Miami Subs
Staff has reviewed the above referenced project and offers the following comments:
1. Show proposed location of water meter and backflow preventor on Sheet A -1,
(Sec. 26-16( c) and Sec. 26-107).
2. Show proposed location for grease trap. Drive-through area should be avoided for
access and maintenance safety.
3. Dumpster is shown on irrigation pump pad and/or well. Relocation of one to be
considered.
4. Oak trees are not acceptable in utility easements. Relocate or change to palm
trees off set from water main, (Sec. 7.5-18.1).
It is our recommendation that the plan proceed through the review process.
If you have any questions regarding this subject, please contact Skip Milor at 375-6407 or Peter
Mazzella at 375-6404.
19b
xc:
Clyde "Skip" Milor
Peter Mazzella Y
File
ill
Boynton Beach Police Department
TraffIC Unit Memorandum
From:
Tambri Heyden
Director
Sgt. James Cummings
Date:
22 July 1994
Ile: Miami Subs
To:
I would request tha! the plans indicate by standard drawing, the signage
and space depiction Tor the handicapped parking spaces. Both existing
and new should be included.
m
.22~
ill
MEMORANDUM
TO:
Tarnbri Heyden,
Planning & Zoning Direc~or
super~ntendent ~
FROM:
John Wildner, Parks
0/ ~/9'-1
DATE:
RE:
/~ o",~..tt'ONA-(.
Site Plan Review - Major Site Plan Modification -" 1..0( Sc J
1st Review r
Proj ect: ftu"A h1l . S '-t I5S
The Recreation and Parks Department has reviewed the
above referenced proj ect. There are no outstanding
recreation related issues on this project.
m
u; 3mA
PlANNING AND
ZONING DEPT.
C:PARKS.MSP
MEMORANDUM
FROM:
Tambri J. Heyden
Planning and zon~ Dir~1l
Michael E. Haag ~ ~
Site and Zoning Development Administrator
TO:
DATE:
August 8, 1994
RE:
Site Plan Review - 1st Review - Conditional Use
Approval/New Site
Project:
Location:
Agent:
File No.:
Miami Subs
Boynton Lakes Plaza
David Daszkal
COUS 94-004
The following is a list of 1st review comments regarding the site
Plan Review of the plans for the above-referenced project. It
should be noted that the comments are divided into two (2)
categories; the first category is a list of comments that
identify deficiencies that are required to be corrected and shown
in compliance on the plans and/or documents submitted for second
(2nd) review in order for the project to continue through the
site plan review process. The second set of comment(s) are
recommendations that the Planning and Zoning Department staff
believe will enhance the proposed development. The applicant
shall understand that all documents/plans submitted for site plan
and/or permit review are subject to additional comments. I
recommend that the applicant) agent contact me regarding
questions related to the comments. If the applicant is not
intending to correct code deficiencies they should contact me
regarding the procedures, application forms, fees and submittal
deadline dates for seeking relief from the code requirement.
I. SITE PLAN REVIEW COMMENTS:
1. Add the tabular information below to your overall site plan:
SITE DATE
Gross Leasable
BUilding Area
123 ,432 sq. ft.
Outparcel #1
Floor Area
2,934
Outparcel #2
Floor Area
4,910
Outparcel #3
Floor Area
5,883
Total leasable area and outparcels
137,159 sq. ft.
Total parking required
Based on square footage
Variance received Case #190
Board of Adjustment 1994
Total parking required
686
27
659
(14 handicap)
Total existing parking
664
(15 handicap)
1st site plan review
Miami Subs
page 2
2. The project is located in Community Design District II -
Spanish Mediterranean. There are five (5) architectural
design features missing from the list provided in the
Community Design Ordinance as required features (see
attached marked list). There are several choices;
1) Required design features can be added.
2) Other features could be pointed out that exist and
an appeal to the code requirements could be requested
accordingly.
3) A variance could be requested deleting requirements for
these features.
The variance request can be processed simultaneously with
the project but if the Planning and Development Board and
the Commission disagree with the request, the features will
have to be added at permit time.
3. A loading zone that does not interfere with traffic flow or
parking back up distance is required by code section II J.
Provide a loading zone or request a variance from Board of
Adjustment. Application with fee will be required by August
12, 1994 to be heard by the Board at the September 19, 1994
meeting.
4. For signage to be considered by the Board at one time, sign
location, size, colors, etc., must be shown on the second
submittal. Signage can not be located on easement or be
within ten feet (10') of property line. Please show
dimensions.
5. On specific site plan, show all driveway and parking space
dimensions.
II. RECOMMENDATION(S):
1. To remain compatible with the exterior coloring of the
existing shopping center, it is recommended that the
color of the exterior walls proposed for the new
restaurant be changed from white to a color that will
match the color of the lower portion of the wall at the
west side of the Walgreens tenant space. The following
changes are also recommendations that would bring the
new building into harmony with the existing shopping
center building:
a. omit the color pink and aqua from the top raised
band and replace with the color displayed along
the top of the walls of the shopping center.
b. omit the pink and aqua architectural lighting.
c. Omit the center band of pink and aqua tile.
d. Omit the pink and aqua tile around the base of the
building.
e. Specify on the plan the new spanish stile wil1
match the tile on the existing shopping center.
Note: The color of the awning and the color of other
features and/or treatments will be reviewed by
the Planning and Development Board and City
commission.
2. To avoid a safety hazard regarding traffic flow,
relocate the menu sign and order speaker closer to the
take-out window. Relocate the sign to allow a distance
of no less than the length of three vehicles to be
parked between the east edge of the access aisle
located west of the building and the speaker box where
the food is ordered.
a!spreview.mi&
ENVIRONMENTAL REOULATION
I Coostal Village
Archltectutol features
and/or treabneilts
won nccessorles:
'SlmUcrs
Lnttlce work
Decorotlve moldings
Balcony
Windows:
. M,,1U"I'IlUe gl099
wind'Jw
Fixed gins!
Beveled glass
Extra fentures:
Decorative benches
Exterfor Jumps
Related omamenta
U l\fediterrn-
nean/Spanish
Iron decoratlva
Grills
Wood decorative
srllle
y"Accent tile
Bnlcony
Arches
Dell tower
Shutters
App. II
3 R~Qv\1RQ;'O
\ 0 N t> R I~ vJ uv b-~
-
2.. M v~SING-
MulU.pone glass}
~ Fixed nlns9 Z.
Stained glass t
I
Amenltles~
Front polio
He or I'tlUO
Wooll deck
Trellises
Ootebo
Picket fence
Dominant exterior
colors:
Beige
Pole yellow
Egg 6h\ n
Blue to groy tone
lOrd. No. 90.88, 9.18.90)
Decorative
lamps
JrofJ ~otes
Multl.panel
door8
Carved doors
R IZ Q" ~R lS D
o tv t>RA<N .pt-
"'MI,~~/AJ &
.t "
2 RL2 Q\)~R~ D
" () I, 0 /..J DR. A-vV ~ A.> c,.
.. 2. ol M ( ~~, N" f:r
Interior court }
Fountains ANY OF THESE
Covered walk. AMENITIES MAY
ways BE SUBSTITUTE[
FOR THE ABOVE
REQUIRED
ARCHITECTURAL
FEATURES.
AND/OR
TREATMENTS.
rlnlt
White
Red to orang"
Earth tones
MEMORANDUM
TO: tambR.; :J. He.iden I
FROM: Ke.v; n S. f+ttlla..l-.a'"
I
DATE: 8.z.Q4
fJ/41')1l'1~ -t 2 tUH '"'5 i) (~ec?;rL.
rO~~STelC.l cnvlfwn "1eV\IQ/'5 T
RE:
Site PIan Review - New Site Plan -_~~~d~qp{an~S€
.
Project: MIAMi Subs
After reviewinq the
referenced project
--eepartmeB~ recommends
the Planninq and
consideration.
amended plans for the above
the Fo~esre~1 GnvlR..onJlvleV) /A/or
that the project be forwarded to
Development Board for their
This department will not be required to siqn-off the
permit documents associated with the subject project.
C:AMEND1.ALD
MEMORANDUM
TO:
Tambri J. Heyden
Planning and Zoning Director
FROM:
Michael E. Haag
Site and Zoning Development Administrator
DATE:
August 11, 1994
RE:
Site Plan Review - 1st Review - Conditional Use
Approval/New Site
Project:
Location:
Agent:
File No.:
Miami Subs
Boynton Lakes Plaza
David Daszkal
COUS 94-004
ADDENDUM #1
Please add the following comment to the Planning and Zoning
memorandum dated August 8, 1994 as attached to letter dated
August 8, from Tambri Heyden to David Daszkal.
6. Further review of the subdivision of the property indicates
a landscape barrier may not have been placed around the
entire property. A landscape barrier or hedge is required
by code. If this hedge does not exist, a variance can be
requested by letter, or the hedge must be installed.
a~ac!dendum.llia
TO:
PUBLIC WORKS DEPARTMENT
MEMORANDUM #94-213
Tambri J. Heyden, Planning & Zoning Director ~.
FROM:
Robert Eichorst, Public Works Director
DATE:
August 22, 1994
SUBJ:
2nd Review/Conditional - Miami Subs
The Public Works Department has no objections to the above site and
the plans should be forwarded to the Planning and Development
Board/Community Redevelopment Board.
Eichorst
Works Director
RE/cr
@. ~
lU\) AUG 2 3 \994
n W ffi
ill
PlANNING AND
OMlMG DEPT.
ENGINEERING DEPARTMENT MEMORANDUM NO. 94-253
TO:
Tambri J. Heyden
Planning & Zoning Director
J~Jlram ~ukill, P.E.
~Englneer
August 18, 1994
FROM:
DATE:
RE:
MIAMI SUBS - AMENDED SITE PLAN REVIEW
Previous comments by the Office of the City Engineer have been met
by the applicant for subject site plan approval.
WVH/ck
C:MIAMISUB.COM
xc: vincent Finizio, Dep. City Engineer
Ken Hall, Engineering Aide
Jim Du Vall, Engineering Inspector
00
@rnuwm
@
AUG / 9 tcql1
BUILDING DEPARTMENT
MEMORANDUM NO. 94-191
August 23, 1994
TO:
Tambri Heyden
Planning Di ector
FROM:
Al Newbol
Deputy Building Official
THRU:
Don Jaege
Building
RE:
TRC COMMENTS - SITE PLAN REVIEW
2ND REVIEW/CONDITIONAL USE
MIAMI SUBS - 4142 N. CONGRESS AVENUE
The Building Department has reviewed the amended site plan and
the attached documents and offers the following comments:
1. section 4.3 of the State Handicapped Code requires an
accessibility route from the street right-of-way or public
sidewalk to the entrance of the building. This requirement
has not been met.
2. All signs must be in compliance with the Boynton Beach Sign
Code. The menu board can not exceed 25 square feet and must
be constructed no more than five feet above ground level.
Directional signs are limited to four per lot. The maximum
allowable square footage for wall signs is 111 square feet.
Since the above comments can be addressed at time of building
permit submittal, we recommend that the plans be forwarded to the
Planning and Development Board/Community Redevelopment Advisory
Board.
AN: bh
rnv~ @ ~ ~ ~I
l\l\1 AUG 231994 IW
...~
SUB
FIRE PREVENTION MEMORANDUM NO. 94-266 woe
TO:
PLANNING DEPARTMENT
FROM:
FIRE DEPARTMENT
DATE:
AUGUST 23, 1994
RE: TRC - SITE PLAN (II)
MIAMI SUBS AT BOYNTON LAKES PLAZA
4742 N CONGRESS AVENUE
There are no objections to this plan.
I'
...-~. . ,., ..
;l,,'
.~.'
MEMORANDUM
Utilities #94-277
TO: Tambri 1. Heyden,
Planning & Zoning Director
FROM: JohnA.Guidry, ~ ~,~
Director of Utilities
DATE: August 22,1994
SUBJECT: Miami Subs - Second Review
Staff has reviewed the above referenced project and offers the following comments:
The Utilities Department offers no additional comments at this time.
This Department will review the plans for this project again at the time of
Building Department Permit Application for compliance with all City Codes
and Ordinances.
It is our recommendation that the request proceed through the review process.
If you have any questions regarding this subject, please contact Skip Milor at 375-6407 or Peter
Mazzella at 375-6404.
19b
xc:
Clyde "Skip" Milor
Peter Mazzella /!Jv
File
AUG 2 3 1996
~
P NNING AND
Boynton Beach Police Department
TraffIC Unit Memorandum
To: Tambri Heyden
Director
I>ate: 23 August 1994
FroEn: Sgt. James Cummings
Re: Miami Subs
The only addition I would like to see would be the drawings for the
handicapped parking spaces added to the plans '.__
~..~
~~(/
J es
MEMORANDUM
TO: ,. p.1ts~ I -:r. H Ej ~,cvJ I f'(,AnJiV'WC <t ZON ,JlJG D/~Ev1b~
FROM: :;. 01-1,.> W, <- ~ "'1""" I f'1'r'l b S ~I" T . 0
DATE: rJ F). 3/ f'l (j
RE: Site Plan Review - New Site Plan - Amended Plans
Project:
kiA-hi" St.tl3..s
After reviewinq the
referenced project
Department recommends
the Planning and
consideration.
amended plans for the above
the f'?[C:fl~ll(tl'-o..,.J../ Pmk b.eptWtn,e..4
that the project be forwarded to
Development Board for their
This department will not be required to siqn-off the
permit documents associated with the subject project.
~
AUG ~ : 'qq4
m u w m
C:AMEND1.ALD
RECREATION & PARK MEMORANDUM #94-309
TO: Tambri Heyden, Director
Planning/Zoning/Community Improvement
FROM:
Kevin Hallahan, ForesterlEnvironmentalist K;} cfJ
Miami Subs - 2nd Review/Conditional Use
RE:
DATE:
August 22, 1994
------------------------------------------------------------------------------------------------------------
There are no existing trees on the site. The project should continue in the normal review
process.
KH:bjm
m
U; 2 2 1994
ID
MEMORANDUM
FROM:
Tambri Heyden
Planning & Zoning Director
Michael E. Ha:Oa;~
zoning and sit velopment
September 2, 199
Administrator
TO:
DATE:
RE:
Site Plan
Review 2nd Review Conditional Use
Approval/Site plan Review
Miami Subs Grill
4742 No. congress Ave at Boynton Lakes Plaza
David Daszkal
CallS 94-004
Project:
Location:
Agent:
File No:
The following is a list of comments regarding the second review of
the above-referenced project. It should be noted that the comments
are divided into two (2) categories:
The first category is a list of comments that identify unresolved
comments either from the first review or new comments as a result
of the second review. To show compliance with these comments will
not substantially alter the configuration of the site and the
design of the building.
The second category is a list of recommendations I believe will
enhance the aesthetics and function of the project.
All comments and recommendations can be rectified on the plans at
time of permitting if the request is approved. The applicant must
understand that additional comments may be generated upon review of
the documents and wor)<.ing drawings submitted to the Building
Department for permits for the proposed project. These comments
will result from the review for technical compliance with the City
code of ordinances.
I. SITE PLAN REVIEW COMMENTS:
1. On the site plan drawing dimension the location of the free
standing sign from the adjacent property line. Note that ten
(10) feet is the minimum setback allowed.
2. If the landscaping located on the adjacent property along the
north property line of the subject property is proposed to
satisfy the vehicle use area visual barrier requirements of
the subject property, note same on the plans. The note shall
include the following statement: If the existing hedge does
not comply with the minimum standards for vehicle use area
screening/visual barrier ( the required barrier shall be placed
on the subject property.
3. On the elevation view drawings identify the name of the
manufacturer and manufacturer's number for the following
exterior materials and color of same: tiles, vinyl awnings,
barrel tile, wall signs, site signs and automatic air curtain
units.
4. Prior to receiving permits to construct the building, submit
a legible copy of the corrected, City approved and recorded
"Declaration of Restrictions and Grant of Easements" for the
Boynton Lakes Plaza and Miami subs property.
/1
page 2 2nd review Miami Subs COllS 94-004
5. Identify the correct address on the plans.
6. Show and dimension on the site plan drawings, sheet C-1 and A-
1, a distance of no less than eighteen (18) feet from the east
side of the intersection of the ingress aisle leading to the
diagonal parking spaces and the access aisle south of the
building to the south edge of the first diagonal parking
space.
7. On the site plan drawing, sheet C-l, ensure that the following
site data is listed, shown and labeled:
Gross Leasable
Building Area (Boynton Lakes Plaza)
outparcel #1
Floor Area (Miami Subs Grill)
Outparcel #2
Vacant - maximum assigned floor area
outparcel #3
Floor Area (Cuco's rest. - leased site on
Boynton Lakes Plaza property)
Total leasable area including outparcels
123,432 sq. ft.
2,934 sq. ft.
6,751 sq. ft.
5,883 sq. ft.
139,000 sq. ft.
area (1:200) 695
of Adjustment
- 27
668
Total parking required
Based on square footage of leasable
Reduction in parking spaces - Board
Case #190 approved
Total parking required
(including 14 handicapped spaces)
Total parking provided
(including 15 handicapped spaces)
668
8. Modify the site plan drawing to depict a loading zone in
compliance with code specifications or receive approval of a
variance from the Board of Adjustment to omit the required
loading zone.
II. RECOMMENDATION(S):
1. To remain compatible with the exterior color scheme of the
existing main shopping center building, a condition attached
to the original shopping center approval, it is recommended
that the color of the exterior walls proposed for the new
restaurant be changed from white to a color that will match
the color of the lower portion cf the wall at the west side of
the Walgreens tenant space. The following changes are also
recommendations that would bring the new building into harmony
with the colors of the existing main shopping center building:
a. Omit the color pink and aqua from the top raised band and
replace with the color displayed along the top of the
walls of the existing main building of the shopping
center.
b. Omit the pink and aqua architectural lighting.
c. Omit the center band of pink and aqua tile.
d. change the color of the wall tile located below the
windows to a color that will match the new wall color
(matching the existing main building of the shopping
center)
e. Specify on the plan that the spanish barrel tile roof
material will match the color of the roof tile on the
main building of the existing shopping center.
/2
Page 3 2nd review Miami Subs COUS 94-004
f. Specify on the plans that the color of the storefront
windows and door frames will match the color of the
storefronts located on the main shopping center building.
g. Where a wall sign has a stucco finish background, modify
the color to match the recommended new color of the walls
of the building.
Note: The color of the back-lit awnings and the color of other
features and/or treatments will be reviewed by the
Planning and Development Board and city Commission.
2. Omit the neon from the free standing sign. Also, change the
color of the blue and pink border and sign background to the
colors that match the exterior walls of the main building of
the shopping center as described above in recommendation 1 and
la.
3. close the outparcel entrance near Plaza Lane and relocate
dumpster and enclosure to the southwest corner of the parking
lot near the irrigation pad. Also, modify the turning radius
at the ingress to the one-way access aisle to accommodate the
turning radius of the city sanitation vehicles.
NOTE: If recommendations are approved, incorporate them into the
working drawings required for permits for the project.
MEH/jj
a:6prev2nd.mia
/3
PUBLIC WORKS DEPARTMENT
MEMORANDUM #94-194
TO: Tambri Heyden, Planning & Zoning Director
FROM: Robert Eichorst, Public Works Director
SUBJ: New Site Plan - Miami Subs
DATE: July 21, 1994
The present location of the dumpster at the above site is
acceptable, however approach angle will need to be changed.
Eichorst
Works Director
REier
rn moomowm illi
JUL L j 1994
ft.AN,~G AND
lONI DEn
rr1ie City of
r.Boynton 'Beach
100 'E. 'Boynton 'Beatfl 'Boulevard
P.O. 'Bo~310
'Boynton 'lJuufr., ~CorUfa. 33425-0310
City 9ftz[[: (407) 375-6()()()
~JU: (407) 375-6090
August 8, 1994
Mr. David Daszkal
5334 Buckhead Circle
Boca Raton, FL 33486
RE: Initial Review Comments
Miami Subs New Site Plan
Conditional Use
File No. COUS 94-004
Dear Mr. Daszkal:
The City of Boynton Beach has completed its first review of the
documents submitted for the above-referenced proj ect. Attached are
comments made by the reviewing departments during their initial
review of your project.
In order to complete the review process, the site plan and
documents must be amended to comply with these comments within 90
days of the date of this letter. (If amended plans are not
submitted in 90 days, a new application fee will be required.)
When there are comments made by the reviewers that you feel are not
applicable to the approval of the project or will be addressed
separately and you have not amended the plans to comply with the
comment(s), you must prepare written explanation for each comment
stating why the comment is not applicable and return the
explanation with the amended plans and documents.
After amending the plans and documents, please submit twelve (12)
complete sets (including surveys) of the plans to the Planning and
Zoning Department. When the amended plans and documents have been
submi tted to the Planning and Zoning Department, they will be
distributed to the reviewing departments for a second review and
the reviewers will recommend if the site plan will be placed on a
board meeting agenda for approval (see attached meeting schedule).
If there are major comments not addressed by new plans or the
reviewers recommend that the plan not be forwarded through the
approval schedule, this office will notify you of your alternatives
regarding the site plan as soon as possible.
5tmerica's (jateway to tfie (julfstream
To: Mr. Daszkal
Re: Initial Review Comments, File No.: COUS 94-004
Page 2 of 2
We have also enclosed for your convenience an approval schedule and
a checklist that contains information regarding the second
submission of the plans and documents for review.
If you should have any questions regarding the comments or on the
approval schedule, please feel free to call Michael E. Haag, who is
coordinating the review of your site plan for the Planning and
Zoning Department.
Director
xc: central File
Chron. File
Project File
A:ISTCOMMT.mia
CHECKLIST
The following list and inrorrnation is provided as a checklist to ensnre that
the submittal of amended plans and documents is substantially complete for
revievI. Turning in t.his list and the appropriate plans and documents will
enable the submittal to be efficiently checked prior to being accepted by the
Planning and zoning Department.
Project Name:
IifIPl!l1I .JoBS ~ ell L-
1. Submit an amended site plan Review/Conditional Use application form that
reflects the changes that were made as a result of amending the plans and
documents to comply with the Code of Ordinances and the Technical Review
Committee comments. A copy of the original form with a distinguishable
symbol identifying the change(s) may be submitted or a completed new form
with the changes identified. If there are no changes required to be
documented on the application form, a letter from the applicant stating
same must be turned in with the amended submittal.
2. Submit twel ve (12) assembled and complete sets of plans and document s,
including surveys that show compliance with the Code of ordinances and
comments made by the Technical Review Committee. Two (2) of the sets slJ.::'\ll
have the appropriate leqible raised seal and signature of the designo?r
responsible fer tIel? drawi'.1gls). Plans and documents shall be assembled in
t~.,elve (12) individ'.131 complete packages with the title of t-.he prnji?ct on
all p,::lge~: and/ or S}F?et sand I:> acll page or sheet numerically numbered sucll
as the following e~:ample: 1. of 3, 2 of 3, 3 of 3.
3. Submit color photograph:" of thl? bui.ldings on the site that are to remain
in their existing concH tion and photos of existing buildings that are
located on the siti?S that abut the perimeter of the subject property. 'rhe
mi.nimum size is 5" by 7". Each photograph shall be labeled to identify the
location of tll? existing structures with respect to the location of the
proposed project.
4. Submit colored elevation view drawings - a colored duplicate copy of all
draY-ling:, c f the elevation viewE of each side of all buildings and signage
associated with the project. The colored elevation views shall match the
e leva t iOll;.:; sllOV'.TlJ :L11 the c:Jc.cumen ts tha t were submi tt.ed fOl- site plan
review. The app 1 icable exterior surfaces as identified above shall be
colo1'ed ~'Ji t-ll the color name and associated color reference number
identified. The t.ype of ext.erior surface material shall be identified next
to the af;sr:wiai:ea co1;)1". The colored elevation drawings shall have compass
c1i]~ec t. ion c r ti t Ie of the s ide of the building ident if ied. The tit} e bl:)c1-:
of t:llf? <'r.lgtn.31 drawing shall be shown. The maximum size is 24" by 36". Do
nos ub m i t 01\ boa r d 0 fan y k i 11 d .
5. Suhmit color samples as an example of the proposed colors. Each sample
3ha1 t hove attached a 1 a.be 1 that iden t if j.es the color by 11 ame and
numerical/letter code from an established color chart.
6. Submi t a 8 1/2 II :-: 11" transpal ency of the 1 andscape site plan drawing to
be uRed 011 an overhead projector at board meetings.
1994 REVIEW SCHEDULE
SECOND HALF
SITE PLAN REVIEW AND
CONDITIONAL USE APPROVAL
*PROJECTS LCCATED WITHIN THE CENTRAL BUSINESS DISTRICT
*
ORIGINAL AMENDED CITY COMM REDEV
SUBMI'1"1'AL PLANS P&D COMMISSION AGENCY
DEADLINE DEADLINE MEETING HEETING & MEETING
Jun 01 Jul 13 Aug 09 Aug 16
Jul 06 E~~ Sep 13 Sep 20
Aug 01 Sep 12 oct 11 Oct 1B
Aug 30 Oct 11 Nov OB Nov 15
sep 30 Nov 10 Dee 13 Dee 20
Oct 25 Dee DB Jan 10,'95 Jan 17 , , 95
t~OTE : ( 1 >> TO FACILITATE 'I'HE PROCESSING OF THE REQUEST, 1'1' IS RECOHMEt~DED THAT THE
APPLICANT SET-UP, BY APPOINTMENT, A PRE-APPLICATION MEETING WITH THE DIRECTOR OF
TilE PLAtUtING " ZOflIflG DEPARTMEJrr (407) 375-6260 PRIOR TO THE SUBMITTAL DEADLIUE
DATE. THE MEETING WILL ADDRESS CONCERNS REGARDING TilE TYPE OF SUBMITTAL, BOARD
REVIEW SCHEDULE, SUBMITTAL PROCEDURES, FEE, APPLICATION FORM, AI~D TYPE AND UUMBER
OF PLANS/DOCUMENTS THAT ARE REQUIRED TO BE SUBMITTED.
( 2 ) IF A SUBMITTAL IS RECEIVED BY THE ORIGIflAL SUBMI'1"1'AL DEADLINE DATE AND
WITHIN TWO ( 2 ) WORKING DAYS FOLLOWING THE ORIGINAL SUBMI'1"1'AL DEADLINE, TIlE
SUBMITTAL IS DETERMINED ACCEPTABLE FOR PROCESSING, THE SUBMI'1"1'AL WILL FOLLOW THE
APPROVAL SCHEDULE IDENTIFIED ABOVE. HOWEVER, IT SHALL BE NOTED THAT THE AMENDED
PLANS DEADLINE DATE ALLOCATES ONLY TEfl (10) WORKING DAYS FOR THE APPLICAI~T TO
SUBMIT A COMPLETE PACKAGB THAT INCLUDES THB PLANS THAT HAVE BEEN AMENDED TO COMPLY
WITH THB TRC COMMBNTS GBNBRATED FROM THE RBVIBW 01' 'l'HB ORIGII~AL SUBMI'1"1'AL
DOCUMENTS. TO KEBP '1'HB RIVIEW PROCESS ON SCHIDULE Till AMINDID PLANS DIADLIUB DATE
IS STRICTLY ENFORCED. IT SHALL ALSO BB NOTED, THAT PRIOR TO A PROJECT BEING
RECOMMENDED FOR APPROVAL BY THE PLAHNlflG & ZONING DEPARTMEtfr, AND BEING PRESENTED
TO THE PLANNING" DEVELOPMENT BOARD OR THE COMMUNITY REDEVELOPMENT ADVISORY BOARD,
THE PROJECT SHALL BE RECOMMENDED FOR APPROVAL BY THE. TECHNICAL REVIEW COMMITTEE.
(3) APPLICATIONS WHICH REQUIRE SUBMITTAL OF A TRAFFIC IMPACT ANALYSIS,
PURSUANT TO THE MUNICIPAL IMPLEMEJrrATION ORDINANCE OF PALM BEACH COUNTY TRAFFIC
PERFORMANCE STANnARDS ORDINANCE REQUIRE ADDITIONAL REVIEW TIME. NOTE: REFER
QUESTIONS REGARDING TRAFFIC TO THE DIRECTOR OF THE PLANNING & ZONING DEPARTMENT.
(4) THE ABOVE DATES HAY BE SUBJECT TO CHANGE.
A: 94REV2HF.frb
~-
:"
MEMORANDUM
TO:
FROM:
Tambri J. Heyden
planning and zon~ Dir~ Il
Michael E. Haag ~ ~
Site and Zoning Development Administrator
DATE:
August 8, 1994
RE:
Site Plan Review - 1st Review - Conditional Use
Approval/New Site
Project:
Location:
Agent:
File No.:
Miami subs
Boynton Lakes Plaza
David Daszkal
COUS 94-004
The following is a list of 1st review comments regarding the Site
Plan Review of the plans for the above-referenced project. It
should be noted that the comments are divided into two (2)
categories; the first category is a list of comments that
identify deficiencies that are required to be corrected and shown
in compliance on the plans and/or documents submitted for second
(2nd) review in order for the project to continue through the
site plan review process. The second set of comment(s) are
recommendations that the Planning and Zoning Department staff
believe will enhance the proposed development. The applicant
shall understand that all documents/plans submitted for site plan
and/or permit review are subject to additional comments. I
recommend that the applicant/ agent contact me regarding
questions related to the comments. If the applicant is not
intending to correct code deficiencies they should contact me
regarding the procedures, application forms, fees and submittal
deadline dates for seeking relief from the code requirement.
I. SITE PLAN REVIEW COMMENTS:
1. Add the tabular information below to your overall site plan:
SITE DATE
Gross Leasable
Building Area
123,432 sq. ft.
Outparcel #1
Floor Area
2,934
Outparcel #2
Floor Area
4,910
Outparcel #3
Floor Area
5,883
Total leasable area and outparcels
137,159 sq. ft.
Total parking required
Based on square footage
variance received Case #190
Board of Adjustment 1994
Total parking required
686
27
659
(14 handicap)
(15 handicap)
Total existing parking
664
ENGINEERING DEPARTMENT MEMORANDUM NO. 94-211 (Amended)
TO:
Tambri J. Heyden
Planning & Zoning Director
WA~~~m ~ukill, P.E.
~Englneer
FROM:
RE:
July 21, 1994
MIAMI SUB'S GRILL, PLANNING FILE COUS 94-004
DATE:
Attached please find Mr. Finizio's review comments on subject plans
and exhibits. Paragraph #1 is self explanatory.
with respect to paragraph #2, plans are not consistent. The
sidewalk along the north side of the building scales 6' on site
plan (cover) sheet, 8' on landscape plan L-l and site plan A-I and
5' on floor plan A-2. Depending on which configuration is correct,
you mayor may not comply with the required backup space Mr.
Finizio describes. Please provide revisions to plans to
demonstrate compliance.
WVH/ck
C:MIAMISUB.TRC
attachment: Engineering Memo No. 94-208
ill
JUt.. 2 2 1994
m~
PUBLIC WORKS DEPARTMENT
MEMORANDUM #94-194
TO: Tambri Heyden, Planning & Zoning Director
FROM: Robert Eichorst, Public Works Director
SUBJ: New Site Plan - Miami Subs
DATE: July 21, 1994
The present location of the dumpster at the above site is
acceptable, however approach angle will need to be changed.
Eichorst
Works Director
REIer
ill m@IED"~ 00.
JUL I. j 1994
PlAN~WS AND
ZONIN EPT.
ENGINEERING DEPARTMENT MEMORANDUM NO. 94-208 (Amended)
TO:
william Hukill, P.E.
City Engineer
FROM:
vincent A. Finizio
Deputy City Engineer
DATE:
July 20, 1994
RE:
Miami Sub's Grill
Planning Department File No. COUS 94-004
I am in receipt of the above referenced plan and herein offer the
following comments(s):
1. The handicap stalls along the west property line of the
parking facility do not comply with minimum width requirements
for handicap stalls and access ramps required in Section 5-
142(k), "Handicap Requirements". The total width of the two
handicap stalls and access area should equal 29', however,
when I scale the drawings the total width of the two stalls
and access area equals 26.5'. This deviation from City codes
will impact the layout in the general vicinity of the stalls
possibly requiring a modification to the plans. There is
however a note that indicates these spaces are existing and it
is possible that the inplace stalls comply with code but in
any event the plans should be revised to provide a true
representation of that which exists.
2. The area depicted along the north side of the parking
facility, specifically the seven existing parking spaces
immediately north of the restaurant, do not comply with the
required 27' free and unobstructed backup space required by
Section 5-142(i), "Parking Lot Layout", Subsection (I),
" Appendix" .
~.
VAF/ck
C:MIAMISUB.VF2
BUILDING DEPARTMENT
MEMORANDUM NO. 94-181
July 18, 1994
From:
Tambri J. Heyden, Planning &lO ing
Don Jaeger, Building Officia
Al Newbold, Deputy Building ficial
Director
To:
Via:
Re: TRC COMMENTS - Site Plan
Miami Subs, 4742 N. Congress (Boynton Lakes Plaza)
The Building Department has reviewed the documents submitted and
offer the following comments:
1. Handicap ramps and walks from the road right-of-way to
the entrance of the building must be provided per the
handicap code, and the building must also be handicap
accessible.
2. Unless this property is a separate, deeded, out-parcel,
it cannot have its own free-standing sign. The
location of the sign needs to be shown on the site
plan.
Contingent upon the handicap requirements and all sign codes
being met, we support proceeding with this project.
A~
AN: mh
---==----..-
A:MIAMISUB.TRC
n. , 9 /9q,1
PLZOANNING AND
NING DEPT.
FIRE PREVENTION MEMORANDUM NO. 94-259 WDC
TO:
PLANNING DEPARTMENT
FROM:
FIRE DEPARTMENT
DATE:
JULY 25, 1994
RE: TRC - SITE PLAN (I)
MIAMI SUBS AT BOYNTON LAKES PLAZA
4742 N CONGRESS AVENUE
There are no objections to this plan.
~
William
~
m
JJ. 2. 6 1994
r
MEMORANDUM
Utilities #94-252
TO: Tambri J. Heyden
Planning & Zon'
FROM: John A. Guidry,
Director of Utilities
DATE: July 29, 1994
SUBJECT: Miami Subs
Staff has reviewed the above referenced project and offers the following comments:
1. Show proposed location of water meter and backflow preventor on Sheet A-I,
(Sec. 26-I6( c) and Sec. 26-107).
2. Show proposed location for grease trap. Drive-through area should be avoided for
access and maintenance safety.
3. Dumpster is shown on irrigation pump pad and/or well. Relocation of one to be
considered.
4. Oak trees are not acceptable in utility easements. Relocate or change to palm
trees offset from water main, (Sec. 7.5-18.1).
It is our recommendation that the plan proceed through the review process.
If you have any questions regarding this subject, please contact Skip Milor at 375-6407 or Peter
Mazzella at 375-6404.
19b
xc:
Clyde "Skip" Milor
Peter Mazzella ~
File
~~WgE'P~~
Boynton Beach Police Department
Traffic Unit Memorandum
From:
Tambri Heyden
Director
Sgt. James Cummings
Date:
22 July 1994
Ftc: Miami Subs
To:
I would request that the plans indicate by standard drawing, the signage
and space depiction~ the handicapped parking spaces. Both existing
and new should be included.
nu rn
ill
JI. 2 2 lqoll
PlANNING AND
ZONING DEPT.
MEMORANDUM
TO:
Tambri Heyden,
Planning & Zoning Director
super~ntendent ~
FROM:
John Wildner, Parks
~/!l19{-/
/ j
DATE:
/c oou~..t,.o-o
RE: Site Plan Review - Major Site Plan Modification -, l..C. s.c
1st Review
Proj ect: )11/'/4. i'I1 t' S '1 ~.s
The Recreation and Parks Department has reviewed the
above referenced proj ect. There are no outstanding
recreation related issues on this project.
00
m 0 , m
rn
AUG 3 1qQ~
PLANNING AND
ZONING DEPT.
C:PARKS.MSP
MEMORANDUM
TO : -ram b R.; :J .
FROM: 1-< ev ," W'\ :s.
Heyden I
l+t:tllttha",
)
fJlal'llli~5 1" 217""'\5 i) (~ec7;R-
rO~"STeR..1 iEnvlIlon ~V17q I,~ T
DATE:
B.~.Cf4
Site Plan Review - New Site Plan - ~~d~~p{an~SE
RE:
.
Project: MIAMi Subs
After reviewing the
referenced project
--aepartmeB~ recommends
the Planning and
consideration.
amended plans for the above
the Fo~es~R.1 [5flVIR.onMe'1 !AJ,}T
that the project be forwarded to
Development Board for their
This department will not be required to sign-off the
permit documents associated with the subject project.
\'t~nm~~t~~
C:AMEND1.ALD
PLANNING AND ZONING DEPARTMENT MEMORANDUM #94-262
TO: Chairman and Members
Planning and Development Board
THRU: Tambri J. Heyden ~
Planning and Zoning Director
FROM: Michael E. Haag
Zoning and Site Development Administrator
DATE: September 9, 1994
SUBJECT: Miami Subs Grill - COUS #94-004
Conditional Use (drive-through)
INTRODUCTION: David Daszkal, applicant, through his agent,
American Architrave, Inc., is requesting conditional use approval
to construct a 2,934 square feet drive-through restaurant on
outparcel flA" of Boynton Lakes Plaza, located at the northeast
corner of Plaza Lane and Congress Avenue. The outparcel was
created by an exception to platting request granted by the Planning
and Development Board on September 14, 1993. The site was
developed as part of the shopping center and the following
improvements exist on the vacant site: utili ties, drainage,
landscaping/irrigation, parking spaces, access aisles and a vacant
building pad. The site does not have direct access to the abutting
rights-af-way and a cross access/cross parking agreement between
outparcel flAfI and the shopping center was a condition of the
exception to platting approval. The building pad will remain
unchanged except for a portion of the south end and east side which
will become part of the proposed drive-through lane. The parking
spaces located east of the pad will be reconfigured to accommodate
the proposed drive-through lane. The reconfigured spaces, which
will become diagonal with a one-way access, reduced the existing
spaces for the overall project by four (4) spaces from 672 to 668.
A Board of Adjustment variance for eliminating a loading zone has
been requested and is being processed and considered separately by
the Board of Adjustment on September 19, 1994.
PROJECT DATA: (See attached drawing)
Project Name: Miami Subs Grill
Location: Northeast corner of Plaza Lane and Congress Avenue
File No.: COliS 94-004
Land Use Plan Designation:
Local Retail Commercial (LRC)
Zoning District: Community Commercial (C-3)
Type of Use:
Restaurant with drive-through
Number of Units: N/A
Square Footage: Building: 2,934 square feet
site: 31,051 square feet (.713 acres)
SURROUNDING LAND USES AND ZONING (See attached location map):
The subject outparcel and Boynton Lakes Plaza are located in the C-
3, Community Commercial, zoning district. The following is a
description of the land uses and zoning districts of the properties
that abut outparcel "A":
I
TO: Planning and Development Board
-2-
September 9, 1994
North -
an existing major driveway entrance leading to the
Boynton Lakes shopping center; farther north is outparcel
"B", a separately owned, vacant outparcel adj acent to
Boynton Lakes Plaza, zoned C-3, Community Commercial.
East
an existing shopping center (Boynton Lakes Plaza), zoned
C-3, Community Commercial.
south -
Plaza Lane, a City right-of-way; farther south is
undeveloped residential land zoned PUD, Boynton Lakes.
West
Congress Avenue, a county right-of-way; farther west is
Meadows Plaza, an existing shopping center, zoned C-3,
community Commercial.
STANDARDS FOR EVALUATING CONDITIONAL USES: Section 11.2.D of the
Zoning Code contains the following standards to which conditional
uses are required to conform. Following each of these standards is
the Planning and Zoning Department's evaluation of the application
as it pertains to the standards;
The Planning and Development Board and City commission
shall consider only such conditional uses as are
authorized under the terms of these zoning regulations
and, in connection therewith, may grant conditional uses
absolutely or conditioned upon the conditions including,
but not limited to, the dedication of property for
streets, alleys, recreation space and sidewalks, as shall
be determined necessary for the protection of the
surrounding area and the citizens' general welfare, or
deny conditional uses when not in harmony with the intent
and purpose of this section. In evaluating an
application for conditional use, the Board and Commission
shall consider the effect of the proposed use on the
general health, safety and welfare of the community and
make written findings certifying that satisfactory
provision has been made concerning the following
standards, where applicable:
1. Ingress and egress to the subject property and
proposed structures thereon, with particular reference
to automobile and pedestrian safety and convenience,
traffic flow and control, and access in case of fire
or catastrophe.
A cross access agreement between the owners of the shopping
center and outparcel "A" will allow access to the proposed
use. No changes are proposed to the location, shape or size
of the existing shopping center ingress/egresses. Additional
signage proposed for the subject site will be provided to help
direct the increased traffic flow generated by the restaurant.
The closest ingress/egresses to the subject site are the major
driveway entrance on Congress Avenue and the access aisle at
the Plaza Lane driveway.
The Planning and Zoning Department is recommending that the
proposed outparcel ingress/egress near the access aisle at the
Plaza Lane driveway be closed. The reason for this is
twofold. First, this outparcel ingress/egress is within 25
feet of the shopping center driveway off of Plaza Lane. This
driveway is heavily used and there have been problems with
cars, as well as delivery trucks, parking and blocking one of
the traffic lanes along the west side of Walgreens, creating
a bottleneck. Also, it is anticipated that cars may back up
into Plaza Lane, waiting to turn left into this outparcel
entrance, due to the limited stacking area. Therefore, it is
believed that this outparcel ingress/egress would worsen the
current situation, since of the two outparcel entrances
proposed, it would be the one most used.
2-
TO: Planning and Development Board
-3-
September 9, 1994
second, a "hairpin" turn has been designed at the south side
of the drive-through lane entrance. A vehicle entering the
outparcel at this entrance would not be able to enter the
drive-through lane from the south without making several
maneuvers which would block oncoming parking lot traffic. The
outparcel entrance proposed on the north side of the outparcel
near Congress Avenue provides adequate and and encourages
safer traffic flow to the restaurant parking lot and drive-
through. This recommendation will necessitate relocation of
the dumpster to the southwest corner of the outparcel, which
has been accepted by the Public works Department.
2. Off-street parking and loading areas where required, with
particular attention to the items in subsection I above,
and the economic, glare, noise, and odor effects the
conditional use will have on adjacent and nearby properties,
and the city as a whole.
A cross parking agreement between the shopping center and two
of the three outparcels (the Cuco1s outparcel is leased) known
as outparcel "A" and "B" of Boynton Lakes Plaza was
established to allow the project to be developed and function
by sharing parking spaces. The parking spaces provided for
the overall project and a previously approved variance for 27
parking spaces will support the proposed shopping center uses.
However, the actual total number of parking spaces required
for the overall project, which includes the shopping center
site, cuco's restaurant, and outparcels "A" and "B", will not
be realized until outparcel liB" is developed. The total gross
leasable floor area for the project, including the shopping
center building, Cuco I s restaurant, the proposed drive-through
restaurant, excluding the vacant outparcel "B", is 132,249
square feet. This figure requires 662 parking spaces based on
the shopping center parking ratio of 1 space for each 200
square feet of gross leasable floor area. A total of 668
parking spaces are proposed for the overall proj ect. This
total does not consider the variance (Case #190) that allowed
a reduction of 27 required spaces.
The subject outparcel has 55 existing parking spaces that will
adequately support the proposed restaurant. The restaurant
building is required to have 15 parking spaces. The
applicant has requested a variance from the Board of
Adjustment to eliminate the requirement for a loading zone in
order to retain existing parking spaces. Provision of a
loading zone decreases the amount of parking spaces available
to the overall project by only four (4) spaces. Compliance
wi th Planning and Zoning Department comment #6 will also
reduce the number of parking spaces for the overall project.
3. Refuse and service areas, with particular reference to the
items in subsection 1 and 2 above.
The dumpster location has been approved by public works and
the enclosure meets all code requirements. As previously
mentioned in item #1 above, due to the recommendation to close
the outparcel entrance near Plaza Lane, the dumpster will need
to be relocated to the southwest corner of the outparcel.
Public Works has accepted this revised location.
4. utilities, with reference to locations, availability, and
compatibility.
The proposed project meets all code requirements with respect
to availability and location of utilities.
3
TO: Planning and Development Board
-4-
September 9, 1994
5. Screening, buffering and landscaping with reference to
type, dimensions, and character.
The applicant will provide landscape materials adequate to
meet all code requirements. An existing six (6) feet high
si te wall borders the south property line of the subject
property.
6. Signs, and proposed exterior lighting, with reference to
glare, traffic safety, economic effect, and compatibility
and harmony with adjacent and nearby properties.
The signage complies with the shopping center sign program and
will be permitted consistent with the requirements of the sign
code. The exterior lighting around the top of the new
building is neon. The existing shopping center does not have
neon lighting around the top of the building and the shopping
center and outparcel building located to the west across
Congress Avenue do not have neon lighting around the top of
the buildings. The only ornamental lighting in the vicinity
are the christmas lights located on the exterior of the Cuco1s
restaurant. A recommendation by the planning and Zoning
Department to omit the neon lighting is included in the
attached comments.
7. Required setbacks and other open spaces.
All required setbacks are in compliance with the C-3 zoning
district building and site regulations.
8. General compatibility with adjacent properties, and
other property in the zoning district.
The restaurant has modified their standard franchise
architectural features to meet the requirements of the
mediterranean spanish design district in which they are
located. The applicant feels that their color motif must be
incorporated for their customers to readily recognize their
building, particularly since the colors meet the design
district requirements. A recommendation by the Planning and
Zoning Department to match the shopping center colors is
identified in the attached comments.
9. Height of buildings and structures, with reference to
compatibility and harmony to adjacent and nearby properties,
and the city as a whole.
The building height is eighteen (18) feet, which is lower than
the main shopping center building.
10. Economic effects on adjacent and nearby properties, and
the city as a whole.
The restaurant will most likely attract additional people to
the shopping center and a positive economic benefit should
accrue to the center and the city.
11. conformance to the standards and requirements which apply
to site plans, as set forth in Chapter 19, Article II of the
Ci ty of Boynton Beach Code of Ordinances. [Part III Land
Development Regulations Chapter 4]
Permit drawing compliance with the attached staff comments
will provide conformance to site plan standards and
requirements.
4
TO: Planning and Development Board
-5-
September 9, 1994
12. Compliance with, and abatement of nuisances and hazards
in accordance with the performance standards section 4 of
the zoning regulations; also, conformance to the City of
Boynton Beach Noise control Ordinance.
Compliance with performance standards section 4 is anticipated
and no additional nuisance or noise would be generated by the
proposed use in comparison with the remainder of the shopping
center.
REVIEW OF DEPARTMENT COMMENTS
ATTACHED MEMORANDUMS #
Public works
utilities
Fire
Police
Engineering
Building
Parks and Recreation
Forester
planning and Zoning
N/A
94-277 & 94-252
N/A
N/A
N/A
94-197
N/A
N/A
Memo Dated 09/02/94
The utilities, Building and Planning and Zoning Department comments
may all be addressed at permit time.
RECOMMENDATION:
The Planning and Zoning Department recommends approval of this
condi tional use request, subj ect to the permit plans for the
project being amended to show compliance with staff comments and
the applicable City of Boynton Beach Code of Ordinances.
a:cond-use.mia
s
CO"-lGRE"55 AVENUE
~ ~ rn
~ : ~
~ I'~
! I ~
(; "'f'SnN4 ~
0
-
00 00
. $1
-
J Iii !
I i
I
-~(-
OO~'
~ '=F\
-1-:1
=F =l=J-=t=
I !
* 1
i (
I
s: :..)-~o
- c::==J oM
-
00
00
,,0
v-o ~ 2: \:>0::1:. ~ '::'0
.a =..... t====:>.....
00
-
o
o
PISTUU~ ~"'c
c
.,1
u
I~
t~
:I
n
1
I
,
~i
~~
tz.
;0 .
~~
x
;;;
:
~
J
~
\J
<=:)
oil
ql))
~ ~
. ~
~ov""TOI,rLAKES e.LVD
~ ~
t -
~ r
~
~ ~
c; lj\
~
,
~ (1 .II. ~! ~I ~I ~r
. I ~, i11
.
! .- ~ ~ .
,"I~,"I S,iUI3S fS~ILL 000 AMERICAH ARCHITRAVE IHTERHATlOHAL
_n_ ""_Int_~"""'" _..II.. _.....nt.
._ 47770 NORTHCONGAESS AVENUE. 14".......... ... .,............... OM 1. C40'1 .......,..
----_..- - ____1IlUD ~..........-_.._"'...._"
LANTANP" FLORID~6~..,.Q" ~F-A''''' 1...._______ _,..... ............---.-----...........".........
_____.......a-......,.~ c.u. ..-..............- ,_.0 ...."...... -...... ......
......... ............---. =-.::-====':"~-:-:~~~,
......................-..-... ..--,.-
:::::=..:.,:=:--u..-.ou ___...:... _____....~_"'.....~__'#It.......'1
---.--._......_1_...., .,~,.,...
.........a.u.a.u. u,.... ...........ftINI,........,M.,_te"II'ft..""'".. ..
h
-
\- ....
0: I
T-
....
~~
H
.tk
~
U
1\ II ~'\
IPI H
~.
d . . . 1/
.
i m~ gll\ ~ 11'1"', \
.. &~ ~4
~l ~ ~
!!" ~ II ~i~~ ~t ~
:! =~L ~ ~ '\ ~ ~ n~l
~~ ~\'.\1: P
H~ . I \I l.~ ~ll l · 11
", ~ ~l ~ ll~ it i li ~ i;~~
!II {~ f'i
~ ~ ~.. " l r
.. " ,.lJ <t. 1
2 \ ' Q '\ r ;;- ~~
t \ - .... l"~
1 nit
~ ~ r' ~~~
Met>.t;:C'V Sc><Uu.r.E: elC?p1l-lCo CTI2l & I
""*'..~S .vEHUE
<t
H
n r :-
I I 2/>1
\ I
I
o \~ g
-{
~
~;~~t 1
~~",js .13 ~
\At~i~ -~ . r
~~~ :t !f \ ~
~. >/-. i1I
t- I \fl
\\
~J \ 1;;
~
:<-t
'I ~ lr-~tlll
h 11 i~i; .. (
au ~
Wt)1l l\i~ ~~
l~ ~
~~ till ,6-
~ I~ t
~ iih ~I ii .
t ~.r- i- I ~I I
. !5
~ l~!i t~
1;...... I il
6i!! ~".
... l' l!><>y'fJToN lJ>,I<.es PL"Z""'
11
.
.~
,
~ ~ ~
.. ", ~l ~! ~l ~,
t'I Ih
...... :a .
I ~ ~
..
7
MEMORANDUM
Utilities #94-277
TO: Tambri 1. Heyden,
Planning & Zoning Director
FROM: JohnA. Guidry, ~ /fr',-:r;i<'
Director of Utilities
DATE: August 22, 1994
SUBJECT: Miami Subs - Second Review
Staff has reviewed the above referenced project and offers the following c.ornments:
The Utilities Department offers no additional comments at this time.
This Department will review the plans for this project again at the time of
Building Department Permit Application for compliance with all City Codes
and Ordinances.
It is our recommendation that the request proceed through the review process.
If you have any questions regarding this subject, please contact Skip Milor at 375-6407 or Peter
Mazzella at 375-6404.
19b
xc:
Clyde "Skip" Milor
Peter Mazzella /!!Y'
File
Alll~ ) 3 Iq0~
~
PLANNING ANtD
NlNG DEP
~
MEMORANDUM
Utilities #94-252
TO: Tambri J. Heyden
Planning & Zon'
DATE: July 29, 1994
FROM: John A. Guidry,
Director of Utilities
SUBJECT: Miami Subs
Staffhas reviewed the above referenced project and offers the following comments:
I. Show proposed location of water meter and backflow prp.ventor on Sheet A -I,
(Sec. 26-16( c) and Sec. 26-107).
2. Show proposed location for grease trap. Drive-through fJ"ea should be avoided for
access and maintenance safety.
3. Dumpster is shown QIl irrigation pump pad and/or well. Relocation of one to be
considered.
4. Oak trees are not acceptable in utility easements. Relocate or change to palm
trees off set from water main, (Sec. 7.5-18.1).
It is our recommendation that the plan proeeed through the review process.
If you have any questions regarding this subject, please contact Skip Milor at 375-6407 or Peter
Mazzella at 375-6404.
/gb
xc:
ill
^U6 . 2 ~~4
Clyde "Skip" Milor
Peter Mazzella ~
File
PlANNING AND
ONING DEPt
q
BUILDING DEPARTMENT
MEMORANDUM NO. 94-197
August 23, 1994
TO:
Tambri Heyden
Planning Di ector
THRU:
Don Jaege
Building
FROM:
Al Newbol
Deputy Building Official
RE:
TRC COMMENTS - SITE PLAN REVIEW
2ND REVIEW/CONDITIONAL USE
MIAMI SUBS - 4742 N. CONGRESS AVENUE
The Building Department has reviewed the amended site plan and
the attached documents and offers the following comments:
1. Section 4.3 of the State Handicapped Code requires an
accessibility route from the street right-of-way or public
sidewalk to the entrance of the building. This requirement
has not been met.
2. All signs must be in compliance with the Boynton Beach Sign
Code. The menu board can not exceed 25 square feet and must
be constructed no more than five feet above ground level.
Directional signs are limited to four per lot. The maximum
allowable square footage for wall signs is 111 square feet.
Since the above comments can be addressed at time of building
permit submittal, we recommend that the plans be forwarded to the
Planning and Development Board/Community Redevelopment Advisory
Board.
AN : bh
~ ~ A~'O ~.. ~ i:9A~ ~
SUB
III
MEMORANDUM
TO:
Tambri Heyden
Planning & Zoning Director
FROM:
Michael E. Haag
Zoning and Site Development Administrator
DATE:
september 2, 1994
RE:
site Plan Review 2nd Review Conditional Use
Approval/Site pIan Review
Project: Miami Subs Grill
Location: 4742 No. congress Ave at Boynton Lakes Plaza
Agent: David Daszkal
File No: COUS 94-004
The following is a list of comments regarding the second review of
the above-referenced project. It should be noted that the comments
are divided into two (2) categories:
The first category is a list of comments that identify unresolved
comments either from the first review or new comments as a result
of the second review. To show compliance with these comments will
not subEtantially alter the configuration of the site and the
design of the building.
The second category is a list of recommendations I believe will
enhance the aesthetics and function of the project.
All comments and recommendations can be rectified on the plans at
time of permitting if the request is approved. The applicant must
understand that additional comments may be generated upon review of
the documents and wor]~ing drawings submitted to the Building
Departrrent for permits for the proposed project. These comments
will result from the review for technical compliance with the city
code of ordinances.
I. SITE PLAN REVIEW COMMENTS:
1. On the site plan drawing dimension the location of the free
standing sign from the adjacent property line. Note that ten
(10) feet is the minimum setback allowed.
2. If the l~ndscaping located on the adjacent property along the
north property line of the subject property is proposed to
satisfy the vehicle use area visual barrier requirements of
the subject property, note same on the plans. The note shall
include the following statement: If the existing hedge does
not comply \'1i th the minimum standards for vehicle use area
screening/visual barrier ( the required barrier shall be placed
on the subject property.
3. On the elevation vie",' drawings identify the name of the
manuf ac turer and manufacturer's number for the follovving
e~:terior materials and color of same: tiles, vinyl a\^mings,
barrel tile, wall signs, site signs and automatic air curtain
units.
4. Prior to receiving permits to construct the building, submit
a legible copy of the corrected, City approved and recorded
"Der:laration of Restrictions and Grant of Easements" for the
Boynton Lakes Plaza and Miami Subs property.
/1
page 2 2nd review Miami Subs ceDS 94-004
5. Identify the correct address on the plans.
6. show and dimension on the site plan drawings, sheet C-1 and A-
I, a distance of no less than eighteen (18) feet from the east
side of the intersection of the ingress aisle leading to the
diagonal parking spaces and the access aisle south of the
building to the south edge of the first diagonal parking
space.
7. On the site plan drawing, sheet C-1, ensure that the following
site data is listed, shown and labeled:
Gross Leasable
Building Area (Boynton Lakes Plaza)
Outparcel #1
Floor Area (Miami Subs Grill)
outparcel #2
Vacant - maximum assigned floor area
eutparcel #3
Floor Area (Cuco's rest. - leased site on
Boynton Lakes Plaza property)
Total leasable area including outparcels
123,432 sq. ft.
2,934 sq. ft.
6,751 sq. ft.
5,883 sq. ft.
139,000 sq. ft.
area (1:200) 695
of Adjustment
- 27
Total parking required
Based on square footage of leasable
Reduction in parking spaces - Board
Case #190 approved
Total parking required
(including 14 handicapped spaces)
668
Total parking provided
(including 15 handicapped spaces)
668
8. Hodi fy the site pI an drawing to depict a loading zone in
compliance with code specifications or receive approval of a
variance from the Board of Adjustment to omit the required
loading zone.
II. RECOMMENDATION(S}:
1. To remain compatible with the exterior color scheme of the
existing main shopping center building, a condition attached
to the original shopping center approval, it is recommended
that the color of the exterior walls proposed for the new
restaurant be changed from white to a color that will match
the color of the lower portion of the wall at the west side of
the Walgreens tenant space. The following changes are also
recommendations that would bring the new building into harm0ny
with the colors of the existing main shopping center building:
a. Omit the color pink and aqua from the top raised band and
replace with the color displayed along the top of the
walls of the existing main building of the shopping
center.
b. Omit the pink and aqua architectural lighting.
c. Omit the .:enter band of pink and aqua tile.
d. change the color of the wall tile located below the
windows to a color that will match the new wall color
(matching the existing main building of the shopping
center}
e. Specify on the plan that the spanish barrel tile roof
material will match the color of the roof tile on the
main building of the existing shopping center.
/2
Page 3 2nd review Miami Subs caus 94-004
f. Specify on the plans that the color of the storefront
windows and door frames will match the color of the
storefronts located on the main shopping center building.
g. Where a wall sign has a stucco finish background, modify
the color to match the recommended new color of the walls
of the building.
Note: The color of the back-lit awnings and the color of other
features and/or treatments will be reviewed by the
Planning and Development Board and city Commission.
2. omit the neon from the free standing sign. Also, change the
color of the blue and pink border and sign background to the
colors that match the exterior walls of the main building of
the shopping center as described above in recommendation 1 and
la.
3. Close the outparcel entrance near Plaza Lane and relocate
dumpster and enclosure to the southwest corner of the parking
lot near the irrigation pad. Also, modify the turning radius
at the ingress to the one-way access aisle to accommodate the
turning radius of the City sanitation vehicles.
NOTE: If recommendations are approved, incorporate them into the
working drawings required for permits for the project.
MEH/jj
!i:Gprev2r:d.mili
)3
~ ' __ ~ ,_ ~.." ,." ~i\=i\ ':i '1; ~ f =- r
~~ ~.::>.-"'.~...... F\ill~i i t:m1 ::;~ 1 c:
~ C ',,"," -: ir ~ "5?-' :~ ;. .
..,e \: ."'-'-:,;. : ~ l.m1.<-=-
pUO ..IC 1/ ~. ~ -- Fi .~~,.."'~ E
\-U'- t/ ~ rf:~t(----'" .ft.=.'" ~"<i~ ~, '.J !
f\ -~ ~1 '~:[f' ,.... ]J.~.r':'~0;..' ~ >-J I
''', 6.0 ' \,^ -= -;;;, "'~ '17 ~.-..<".,. ,'i"ll! ~'
r \ \ .. , -- , ,f' tI ....-iJ? 'I
\~"'::?";j ,$~~;'\1" - ~:S ~:~~~ J;~i~J~';~l(r)
1i\7..~.p'J).","C .l-li' (G'~~ = r.' .h.
... II~'J ',', t'l _ 1- ""./ ' ,L"~" ,
. ~.... .. ~:::?! ~)" ~" ;: if' .-,.....-: \'.' ." ~ !dJ'fJ '" ~ ~
. \~ -:::-- J ;:._ ",I ~.. : J' \" 111 . riJi3 ,~
tiEI"'::::-- 1~it'D :.. :/ >.,,~. .. ~ ~,- .::\ -e\B ~ FI ~ ff 'Ji,;\,~. J ~
'1:. ...: :/":; ,Iii:: ,. ,,'In r ", ~ !!!!J ~ ~. .. 7'~' \ ',,\. ~ ~,
~ ~,~ .,' ., _' .,,;;;;., "".-l"'Il' - s;iio
~ ....' .1.... 'n 1~.. ~. " ,,,'iT lIU' II 1~.1"
"'-/1 ......... o:=!:'t1 . '1: C t:I 0'" 'n ~
t":';- "1--' .. T'----\ \~ Cf'J~ ,< ~,g, ,,~d' I. -~ d'rp~
'_')" 'c['l' ,,)..r _ _ '^.~ ~J" .J ,'~ If' .
f:. ?jt ~~ 'i M:i U' ,.; ~/t ft". ~ ~o ... ~;;; .J', "", fC' ",en irr :JI:: ,. ," IE ~
_ , I tlll!!" ' ,0/ "','" - , =,-," !-= ~
~ _. co : . ~ u_ ,,- ;-5" , " .: r. " cr .
g?, W ';::;: .... ..~~ .' :>~' ',~ I:rU ~ \~: :"" ~ f~
~, 1 _ . ~\\ ~\ "~fiitJ=~._j ~ ,C E!ltJl'~"" till: " S..:'"' '-' r > '- .
.. \17 ''i''' H: l "'" rd " H 7 cor':' "~'.-i' 7 :::
-<1 HI:1j,.o~ lIVl ~, \ ~..-,-~. " )." ''!1ifj f
~:\ \\i ;-~'........: 1.~.v' ~:-; ~\-~ .:;,.---,.".::.@\\
~~,)e-; "p- '" iT m\\\~ "". F' ,
'--<::: '<;;i. :: ~ \I (l./j 7 c::,"" t II::g
l~, ~A1"m~~~~~ lilro2\ [rIil;;~(Jt1r' .--!~ ·
J~.F ~ " 'Ii' "-7fili : "'-
r-" T -', r --\ ' ~ ",! ' '"
~ 1 \ ;::::: \ "'''' lJ./l,! :=::
_ '1' r\ ;.-_ r \ \\ ,=,.~ C' '1if"",,,' ~
...-, ~-" - "" _. "
, ..... ,_A . =--4J I
, ..... '.-< \/' ,," __ C," ,-~. ="'==-- ~ '
,-~~~if~1 :;1 - -u.1 ~c'i\ ~ ~\&B t-t.-: "-/~- .- Cj
1 ~~\" ~JG'J'-, l!) -0~ t::,~ I: \
\ "~fj^,-~r~P0 \'e:'-N ,C - ~ .'-_..-\~ \
~l"ill~ p~ 7:/ \ ':J!J/J ~--.. ~ r ~ t : \ .~
"" Iti'm'::== \..~ , . ;;a.~1,.I [( I n ~ I, " ~ ~ , "'~ I r-.
~\I1\'A;:: A ~ ...., 1\\ ...."",l /J 1. ::1 ' ' '
"'" \l-g~ .~ ~ 'I,,, iiF'~ ~ ~ / . 'i i)'
~ ~~~ ..""e\..::-~ ,f"""77 '~~~\',;jr.. . - ,.'..... ':'>~'
t:: :" t::: ~\....-'l ~, ~" ?'. 1-:: · .. .,
\'=' '~ ~ __ ~ r."\~ E:.---J (:!
""; ~ " ,\-7'" ' '
D- > : ..IV --1 ,:
~I) ;:::: r}\ V.... VfjJ_;:: ~ : it
i
I
,
.
,
.;::.1. L"'.-W...---- ,_........-- '0 400 800 fE.EI
r-J~-c-:J:~ ~Q / ,\ cf4j!J ,...=>>I '\ ~\r.
LOC~,.\ON M~P
M\~M\ SueS GR\LL
.... ....
, ~
. '
.,
.~
r'" ~'
~, .... ... '
,~ .
"'\ 'lo" ~ ~...\
., ,
~
.~.
,
~,. ~
. "~::~
'.'
F' #\ J'
PLANNING AND ZONING DEPARTMENT
MEMORANDUM NO. 95-142
FROM:
Chairman and Members of the
Planning and Development Board
Tambri J. Heyden ~CL,Ji ,~
Planning and Zoning Directo{ - ~
Michael E. Haa:q- r~
Planning and ZOn~Administrator
April 7, 1995
TO:
THRU:
DATE:
SUBJEC'l':
Miami Subs (1920 South Federal Highway)
Community Design Plan Appeal - exterior lighting
File No. CDPA 95-003
NATURE OF REQUEST
Joe Marouf, owner of the Miami Subs restaurant at 1920 South
Federal Highway, is requesting approval of an appeal to Section
10.F.6. of the Community Design PIan (see Exhibit "A" - letter of
request) . The appeal is in connection with a building permit
submittal to install two (2) rows of exposed neon lighting to the
painted trim at the top of the parapet waIl of the building.
BACKGROUND
city records indicate the existing building was built in 1979 as a
Wuv's restaurant. In 1989 the City Commission approved a site plan
modification which allowed renovation to the building for its
present appearance. This modification was for a Mr. Submarine
restaurant which changed to a Miami Subs in 1991. The building is
located on the west side of Federal Highway, across from Spring
House adult congregate living facility (see attached 10cation map).
ANALYSIS
The neon lighting proposed for the parapet wall is exposed and
colored to match the existing pink and aqua painted trim; a color
scheme customary of Miami Subs. The attached drawing depicts the
shape of the building and the proposed location of the neon (see
Exhibit "B" - proposed elevations) .
Section 10.F.6. of the new community Design Plan states:
"Lighting attached to the form of the exterior of the
building or part of the building exterior or visible from
the exterior of the building shall not be permitted if it
is contrary to the architectural style of t!1e building."
Until the recent adoption of the new community Design Plan, neon
was not specifically addressed in either the sign code or the
previous Community Design Plan. It is staff's conclusion that the
proposed exposed neon lighting is contrary to the architecture of
the Miami Subs building which is somewhat of a "south-of-the
border" /mission style building, typically not having a modern,
flashy appearance. Also, the buildings in the area do not use
exposed neon to accentuate their outline. However, if the exposed
neon would be limited to the three (3) irregular shaped sections of
the parapet wall the neon could be acceptable. This limited use
would be consistent with the location of the neon on the recently
approved Miami Subs Grill, located at the northeast corner of Plaza
Lane and Congress Avenue.
/
Page 2
Miami Subs
Community Design Plan Appeal - exterior lighting
File No. CDPA 95-003
Memorandum No. 95-142
RECOMMENDATION
staff recommends approval of this request, subject to the
limi tation of the two rows of exposed neon to the three (3)
irregular shaped sections of the parapet wall. All documents shal1
be amended to comply with the final commission determination of
this request.
MEH:dim
xc: Central File
.:M1..18p...D/App..l
'"'7
/---..
EXHIBIT A
3
---
"[ ---~
, ; .,'.------
,. .
,
. ,
1 " l
! ~'
_ ~ l
----.--.~-l..
, '
I
'-.
J
'-'
: I
-:I
'J '
4/6/95
MIAMI SUBS. GRIJ.
1920 S. FEDfMY
"""ON 8EAQf. fL",
r ;
" I
.' i
r
I "
Attn: Tambri Heiden Re: Miami Sub's,
City of Boynton :Beach ' 1920 S Federal Hwy. ';
Pl~nhing & Zon1.nq Director Boynton Beach, F~. I.i>
hd ietter is to request approval for architectural lighting J the:, ....
b~r~meter of the abo~e referenced restaurant. 'f ".:
'~h~~ lighting consists of two neon tubes to enhance the colors (Pihk:'
top~and aqua bottom) which are painted on the top part of our ,! ;:
bu~lding. t -
'" ' (,
Th~~ neon matches these pink & aqua colors and highlights the . . ':
architecture of the building. This is an importa.nt part of the Miami. ,!,
~\lb',s th~me and a1'so is very helpful in providing additional 11ghtlng' ,
at .night. which is necessary due to our late night operating hours.' i: ,:
~h~~ lighting allows the public to see we are open and provides-a wel1~
~i~{SeCUre area. . . I .'
~e~~re located in a commercial area and have no residential area which
th~f lighting would affect. I
Th:tk y'ou for your consideration of this matter.
Sincerely,
\!.~~ .jIl a rt!J IA r
~
...........
1_ 8.......,
IIOVNTON EACH. Pl.'"
!
~ ~
i
: I
i)
: 1
4
., ~U' '.F; 1:1,:: II
I !.~ r U ~ - c::::: ~I J ;. ;'1
C _ ~ :,=::1' ., , I
---~ . :.0::
: : ~ II: I I! - ~-= = Ii ,.:' S ii
II J1Tl ' '-
~;:
II r;" :...... 1-..... ..... I: ........ . ';1
I~'~ II I ./ :!t/ I -._.. N,1
11 i F '-- I n. .'~ ......; _ , I r 1 I / [W,LL
I , I r I: f- I: '
"'"" -'- i"J-':1 :.::r I I . I <J,tN I
Ilj __' ~J.iilI' ;.';tu'U".i.i~I-'_"';': .~F' "'-!-I .
I" WIn '. J... l ..' .. : {'r; , I IT.". .
rrl r"'1 ~ .r i ". i2 ,.of,., I ( I I ' : Ii ....
II ; ..,: !::ail
I /I... I I I J [./ ! 'i :f J'I
Ij -7 .~"I_~.;,:i ~_----,
::; =I ~ J~".I/(~'.' :.~' 7 I I
I J;; ~ - -- J- ~ I L I I .! l ~ I I I 7 --, 'O.=,
'I : 'T ___ 'j,: i.C1 '.-J I I 7 /-+~I : ' W
, ~~~I ;1 Ii
11 : -". - - I:' ,: :'~ / 1 I / . / ~~ I
1 I~ ..... :rt", 'I I {-. '/Ar--I-~r-~
! j L - !i ;: ~/ n
~! : ,..~. ~1'.rEI ( .:':.~'" ;-~/:II! ....L ~-
~\j! i 0 ~ ....,. I I r i' ,'~' V' r-;J I I.
1(' I r I ~rl- : : ;" . -=;- I I I I
~.. ~~ ! L ~~_ : ;;'f' · .-' . ,~, 1.
=:J' - !91~~~ JI.. r ,...._~ JJ]~. I,:.: r - '~~ j'/ - ,.1:- "-r1~T'-'-----:-I-l
~ " -- j ~ ~ - Ji ;' i - ~,,'" -. !' I ii' I
1 ~ / i! '1111 : .~,.,. r" R~ / .! ~_ l:m~ ~j u : .J}]
~c, ~/- ',":,j.,j IT: .i:.: "" ~~ - _:'~I~ WW4i~14;Pi'
~.cE L.r:. ...: . := - _ . :. E:J~~.;~'- Uj r~~: ,:i ~::j
L..~,jr' 1 ,:-: ~ ',"~~ ':, I .. IiJWJI I
~ 1 -' ~2 ; I'. I ..H. .;tl. 'g" ~ /7
. ,.1.... ~ J : ' ~'-/ ,. .~ ~ ~
.... JJ~ I
!J II. I
f
I ]11. \F' I ;\J~I I_~ - .'
" ~ if~~~'~ REC .r if-:-~. u '.-
III .,~" l(-,. .. ...._~_ ,
T I I ,:Ir>>.r.)L i /r:::::-..... :' I ~~ L. - R3--
I T Clr I Ij~d I =- :Y '')) ',: ~--~ ~
-1!liF\. I . ::: ,_-
I LJ I ' '- .-' I_
I I I I 1.J .
I
J I I I I I I ""-' ' l/ - f-+-
I I 1111:,' ,: L-~~':' j r--~;
II~:' ~~. ~ I
' I~/J/ ---
.I. r~.,.- Ir ,_
f I 1, ,.f . --- .I ~ 1---',-
',r;: I ~'" r'f'~ ,~i ~
, y1rrf=:j f~ '._ ~. ~ -rr[ -r7 -'-
~~',. ~ T I1t-J e:"[ ;. ~ . ~
~ IH.~l. . . i - ~/ --,-.0 1/8 MILEsf' ~
C~J 7 I I / !i;~ r'"' I-t-. "'1111 'I' "';
~ ~ r "'Jt-f:~iA,::.U/ . 1-'.. . . ~
0-.. r~.i" ~:F' ;1l.,J., , :~. t=i !l 0400. 8~^,~~;,T Peer: i"
-.c:J T Y - f - t:; ~aj .' .F;l." .' >r-/ - P t:- 1(' . , /".,. -
---- -~ '~ ~.:i--l1- i! :t.,,', l~
. I I I
.J
III "If r
Ii
!
I I
III
IIIIIDl D J I
~III
m
II
"
H I II
H I II "'
J-~i' "I II
~IIJiIII
LI I I II
H" I III
f-l I III
t-1 II ',1
.
.
,
I
r',
B{
-..,..... .J
-r- .,
-f-
- ~
--'
f-r-.l
'-.....'
" I I I I I I
~
I ;
~ :
I :
R&{
,
.
,
//
:1
:11.
j
LOCATION MAP
.....MIAMI. SUBS
~'Ir"'_""
& -
!: ~I
II! ~ I
Ill, _
I '--JI-~ M: J-U -/
--'::...:.... ~
1
. ....
II 11
~ I II
II II II
I II \I
II
! I
--
I-- .
f--
--
'-. - -< '--
III II I
" II I
I III
1111
:1 n
II II J
]: I
.~:I till
o
PU~
I
- .~
I
!/t~
PLANNING AND ZONING DEPARTMENT MEMORANDUM #94-262
TO: Chairman and Members
Planning and Development Board
'fHRU: Tambri J. Heyden ~
Planning and Zoning Director
FROM: Michael E. Haag
Zoning and Site Development Administrator
DATE: September 9, 1994
SUBJECT: Miami Subs Grill - COUS #94-004
Con~itional Use (drive-through)
INTRODUCTION: David Daszkal, applicant, through his agent,
American Architrave, Inc., is requesting conditional use approval
t,:, c.:>nstruct a 2,934 square feet drive-through restaural1t on
ollt.prJ.r'cel "A" of Boynton La}:es Plaza, lCJcated at the northeast
con1er of Plaza Lane and Congress Avenue. The outpo.l'cel .'lab
crear.ed by an exception to platting request granted by the Planning
and Development Board on September- 14, 1993. The site _'las
developed as part of the shopping center and the following
improvements exist on the vacant site : utilities, drainage,
landscaping/irrigation, parking spaces, access aisles and a vacant
bUilding pad. The site does not bave direct access to the abutting
rights-of-way and a cross access/cross parking agreement between
out~parcel "A" and the shopping center \folaS a condition of the
E~zception to platting approval. The building pad will remain
unchanged except for a portion of the south end and east side which
will become part of the proposed drive-through lane. The parking
spaces located east of the pad will be reconfigured to accommodate
the ~roposed drive-through lane. The reconfigured spaces, which
will become diagonal with a one-way access, reduced the existing
s~~ces for the overall project by four (4) spaces from 672 to 668.
A Board of Adjustment variance for eliminating a loading zone has
been requested and is being processed and considered separately by
the Board of Adjustment on September 19, 1994.
PROJECT DATA: (See attached drawing)
Project Name: Miami Subs Grill
Location: Northeast corner of Plaza Lane and Congress Avenue
File No.: COUS 94-004
Land Use plan Designation:
Local Retail Commercial (LRC)
Zoning District: Community Commercial (C-3)
Type of Use:
Restaurant with drive-through
Number of Units: NIA
square Footage: Building: 2,934 square feet
site: 31,051 square feet (.713 acres)
SURROUNDING LAND USES AND ZONING (see attached location map):
Th,::: subj ect outparcel and Boynton Lakes Plaza are located in the C-
:~, Community Commer'cial, zoning district. The following is a
description of the land uses and zoning districts of the properties
tL It 3but ,)utparcel "A":
I
TO: Planning and Development Board
-')-
September 9, 1994
NCJl'tll -
an existing major driveway entrance leading to the
Eoynton Lakes shopping center; farther north is outparcel
ItBII, a separately owned, vacant outparcel adjacent to
Boynton Lakes Plaza, zoned C-3, Community Commercial.
East
an existing shopping center (BoynLon Lakes Plaza), zoned
C-3, Community Commercial.
south -
Plaza Lane, a city right-of-way; farther south is
undeveloped residential land zoned PUD, Boynton Lakes.
West
Congress Avenue, a County right-of-way; farther west is
Meadows Plaza, an existing shopping center, zoned C-3,
Community Commercial.
STANDARDS FOR EVALUATING CONDITIONAL USES: Section 11.2.D of the
Z0ninq Code contains the following standards to which conditional
m:es are required to conform. Following each of th:?se s'tandards is
the Plallnlng and Zoning Department's evaluation of the application
as it pertains to the standards;
The Planning and Development Board and City Commission
shall consider only such conditional uses as are
authorized under the terms of these zoning regulations
and, in connection therewith, may grant conditional uses
absolutely or conditioned upon the conditions including,
but not limited to, the dedication of property for
streets, alleys, recreation space and sidewalks, as shall
be determined necessary for the protection of the
surrounding area and the citizens' general welfare, or
deny conditional uses when not in harmony wi th the intent
and purpose of this section. In evaluating an
appllcation for conditional use, the Board and Commission
shall consider the effect of the proposed use on the
general health, safety and welfare of the community and
make written findings certifying that satisfactory
prOVision has been made concerning the following
standards, where applicable:
1. Ingress and egress to the subject property and
proposed structures thereon, with particular reference
to automobile and pedestrian safety and convenience,
traffic flow and control, and access in case of fire
or catastl'ophe.
A cross access agreement between the owners of the shopping
center and outparcel IIAIt will allow access to the proposed
use. No changes are proposed to the location, shape or size
of the existing shopping center ingress/egresses. Additional
signage proposed for the subject site will be provided to help
direct the increased traffic flow generated by the restaurant.
The closest ingress/egresses to the subject site are the major
driveway entrance on Congress Avenue and the access aisle at
the Plaza Lane driveway.
The Planning and Zoning Department is recommending that the
proposed outparcel ingress/egress near the access aisle at the
Plaza Lane driveway be closed. The reason for this is
twofold. First, this outparcel ingress/egress is within 25
feet of the shopping center driveway off of Plaza Lane. This
driveway is heaVily used and there have been problems with
cars, as well as delivery trucks, parking and blocking one of
the traffic lanes along the west side of Walgreens, creating
a bottleneck. Also, it is anticipated that cars may back up
into Plaza Lane, waiting to turn left into this outparcel
entrance, due to the limited stacking area. Therefore, it is
believed that this outparcel ingress/egress would worsen the
:urrent situation, since of the two outparcel entTances
i)::cr~of.;ed . it '.lculc' bE~ the ':,ne mest tu:(:d.
2-
TO: planning and Development Board
-3-
September 9, 1994
second, a "hairpin" turn has been designed at the south side
of the drive-through lane entrance. A vehicle entering the
outparcel at this entrance would not be able to enter the
dl-i ve-through lane from the south without making sevel-al
maneuver3 which would block oncoming parking lot traffic. The
outparcel entrance proposed on the north side of the outparcel
near Congress Avenue provides adequate and and encourages
safer traffic flow to the restaurant parking lot and drive-
through. This recommendation will necessitate relocation of
the dumpster to the southwest corner of the outparcel, which
has been accepted by the Public Works Department.
2. Off-street parking and loading areas where required, with
particular attention to the items in subsection 1 above,
and the economic, glare, noise, and odor effects the
conditional use will have on adjacent and nearby properties,
and the city as a whole.
A cross parking agreement between the shopping center and two
of the three outparcels (the Cuco's outparcel is leased) known
as outparcel "A" .3.nd "E" of Boynr.or1 Lakes Plaza ~,/as
established to allow the project to be developed and function
by sharing parking spaces. The parking spaces provided for
the overall project and a previously approved variance for 27
parking spaces will support the proposed shopping center uses.
However, the actual total number of parking spaces required
for the overall project, which includes the shopping center
site, cuco's restaurant, and outparcels "A" and "B", will not
be realized until outparcel "B" is developed. The total gross
leasable floor area for the project, including the shopping
center building, cuco IS restaul-ant, the proposed drive-through
restaurant, e~~cluding the vacant outparcel liB", is 132,249
square feet. This figure reqUires 662 parking spaces based on
the shopping center parking ratio of 1 space for each 200
square fE:et of gross leasable floor area. A total of 668
parking spaces are proposed for the overall proj ect. This
total does not consider the variance (Case #190) that allowed
a reduction of 27 required spaces.
The subject outparcel has 55 existing parking spaces that will
adequately support the proposed restaurant. The restaurant
building is required to have 15 parking spaces. The
applicant has requested a variance from the Board of
Adjustment to eliminate the requirement for a loading zone in
order to retain existing parking spaces. Provision of a
loading zone decreases the amount of parking spaces available
to the overall project by only four (4) spaces. Compliance
with Planning and Zoning Department comment #6 will also
reduce the number of parking spaces for the overall project.
3. Refuse and service areas, with particular reference to the
items in subsection I and 2 above.
The dumpster location has been approved by public works and
the enclosure meets all code requirements. As previously
mentioned in item #1 above, due to the recommendation to close
the outparcel entrance near Plaza Laner the dumpster will need
to be relocated to the southwest corner of the outparcel.
Public Works has accepted this revised location.
4. utilities, with reference to locations, availability, and
compatibility.
The proposed project meets all code requirements with respect
to availability and location of utilities.
-~
TO: Planning and Development Board
-4-
September 9, 1994
t.:
--' .
Screening, buffering and landscaping with reference to
type, dimensions, and character.
The applicant will provide landscape materials adequate to
meet all code requirements. An existing six (6) feet high
site \^lall borders the south property line of the subject
property.
6. Signs, and proposed exterior lighting, with reference to
glare, traffic safety, economic effect, and compatibility
and harmony with adjacent and nearby properties.
The signage complies with the shopping center sign program and
will be permitted consistent with the requirements of the sign
code. The exterior lighting around the top of the new
building is neon. The existing shopping center does not have
neon lighting around the top of the building and the shopping
center and outparcel building located to the west across
congress Avenue do not have neon lighting around the top of
the bUildings. The only ornamental lighting in the vicillity
are the christmas lights located on the exterior of the Cucols
restaurant. A recommendation by the planning and Zoning
Department to omit the neon 1 ighting is included in the
attached comments.
7. Required setbacks and other open spaces.
All required setbacks are in compliance with the C-3 zoning
district building and site regulations.
3. General compatibility with adjacent properties, and
other property in the zoning district.
The restaurant has modified their standard franchise
architectural features to meet the requirements of the
mediterranean spanish design district in which they are
located. The applicant feels that their color motif must be
incorporated for their customers to readily recognize their
building, particularly since the colors meet the design
district requirements. A recommendation by the Planning and
Zoning Department to match the shopping center colors is
identified in the attached comments.
9. Height of buildings and structures, with reference to
compatibility and harmony to adjacent and nearby properties,
and the city as a whole.
The bUilding height is eighteen (18) feet, which is lower than
the main shopping center building.
10. Economic effects on adjacent and nearby properties, and
the city as a whole.
The restaurant will most likely attract additional people to
the shopping center and a positive economic benefit should
accrue to the center and the city.
11. Conformance to the standards and requirements which apply
to site plans, as set forth in Chapter 19, Article II of the
ci ty of Boynton Beach Code of Ordinances. [Part III Land
Development Regulations Chapter 4]
Permit drawing compliance with the attached staff comments
will provide conformance to site plan standards and
requirements.
/1-
TO: Planning and Development Board
-5-
September 9, 1994
12. Compliance with, and abatement of nuisances and hazards
in accordance with the performance standards section 4 of
the zoning regulations; also, conformance to the City of
Boynton Beach Noise contr~l Ordinance.
Compliance with performance standards section 4 is anticipated
and no additional nuisance or noise would be generated by the
proposed use in comparison with the remainder of the shopping
center.
REVIEW OF DEPARTMENT COMMENTS
ATTACHED MEMORANDUMS #
Public works
Utilities
Fire
Police
Engineering
Building
Parks and Recreation
E')rester
Planning and Zoning
N/A
94-277 & 94-252
N/A
N/A
N/A
94-197
N/A
N/A
Memo Dated 09/02/94
The Utilities, Building and Planning and Zoning Department comments
may all be addressed at permit time.
RECOMMENDATION:
The Planning and zoning Department recommends approval of this
conditional use request, subject to the permit plans for the
project being amended to show compliance with staff comments and
the applicable City of Boynton Beach Code of Ordinances.
!:I;C"Jlld-t.l6-3.mia
t::~
- )
I
C Ol-lGRES5 AVENU~
l.rsn"'4 ~
;;;:J ~l- -
<>~ 00 00
00
. 'I ~.~\
"
~ 1~ 00
l I
Ii ' -r- '
I ,. ;t; ~l:i=
I ~
-<
~
I ! 00 r-
c
II ~
yO
~I
i l
~' r-
~I
I~'
I r-
m , V~z.2:V~z.I~';:;O
I ' :, ~ x. :..)-~o .a ===' _ =:::=:l- 00
- c::::= AI -
C .J
~ 0 PISTIN~ ~.\[~ C
1 1:- c::)
) oil
.~
0)0
0 n
I~ 1 t
H:
~ I . .
~<J
l~
, 111
~' \ ,
"-.-'
~I
Ilt
.~ ~ en
~ : ~
t "tL1
. I ~
Oil
.at
~
, ~
_~OVt-lTC""L"KES I!.LVD
~
~
~
'1i1
i'
~
~
,
l Cl Jl [I ~! ~I
I :r ~I
I ~
I I-l ~ ~ .
;
MIAMI ~U~S e3~ILL @@O AMERICAH ARCHlmAVE IHTERHATlOttAL
...bl...... ,1__ ..._ ~.......... _otroc"", .....n...'
,_ 47770 NOATH CONGRESS AVENUE. un.......... .....lDt. .....-. ...... CISII 1.r. 1.&0"11.....1&'
~-- - --....~....-..~ ~ML....__..~'II...._'I
lANTANE. FlORID~6t'...,..c.,_ ..._....~...r-I I._ML NK.....____.._.._.. ...._"'...""a1
____.-..JIt'I_......,___ """.................._.......,.at (1Il.........0JUI ,.,,,
.,.. c.u ......... .."..........., ____".__.._~______n
;:A''''' ~~=--:::'MO:::':-: :::=.~~.'=-..::::-::.:."r::.':::u-~~~:~:
1111.'.............., MI.InrIn'I........,...........,_..... .,~",.,
l_dLMWU ..~.. ......, ""~"'_"'~""'_","_""""",,',
--
h
"
0:
=
I
~
~I
h
"a
~
..
.
~ ~ ~ 1'&
!~ a 3.
~~... t'
~ l" F
i at !
r ~"
It ~"
a "b
t \
III
I
~~
n
~
u
i~\ { ~ ,
i 1\'11
5 1
MeADC'V sc;;UAPoE eMCpplNC, CTF>
a~
~=
d
. . .
1\; mm~
!. ~~iht
1\:
II
~ ~ ~
i i Ii
h
r
. \
! U~l
l i~a.,
,~al
I \"
~ I
.;;; ~~
. t....
t ~Zt
.... ~~l
I
..........."55 AVEHUE
- ~
~l:i!
. -[
ii!l~
!;!..I ~-
. ~ ? '--
Ip~~ ~ ~ CJJ I
r~r\~ ~a f ~/"
lH Jt ~ ~ I
l~,,~ ~ ~ I"d
J '. ~ ~
t ;1 ~ . ~ g
\~ -{
',," 1.
~;~1t ~ ~
~~Oi:;;~ ill
tE~a~ -~ ~
It
~~ .q 111
IfI
HI I "\l
C
.r I I ~
:<.t I
UI lHl'<1l~ I
i
r~ i~H .. (
iti~ ~~
~l!I
~i \~I ,G,
~ J I
t ~h ,I It Jun fl l
I ~i. I ~l I
ld ~r iijl
I f~ t
1;.... II
d~! it ii{~ ...,
.. ...~ .1; c4 l' 1!oC>'y'IJTot,j LAl'>15S F\..~z;A
'I ~~~~
t,
~ IIll
.~
,
A ~ )-
.. ". ~I ~! ~I k-I
1'1 lh ~. ~
jooooL :0 .
J & t
MI4.MI SUES C3~ILL
47770 NOATH CONGRESS AVENUE
LANTANA, FLOAIDB---~.~2 A... r""''''''' ___---:.'::.-::.~-:
CK~ y ~~..
7
MEMORANDUM
Utilities #94-277
TO: Tambri J. Heyden,
Planning & Zoning Director
FROM: John A. Guidry, ~ ~,1l<'
Director of Utilities
DATE: August 22, 1994
SUBJECT: Miami Subs - Second Review
Staff has reviewed the above referenced project and offers the following comments:
The Utilities Department offers no additional comments at this time.
This Department will review the plans for this project again at the time of
Building Department Permit Application for compliance with all City Codes
and Ordinances.
It is our recommendation that the request proceed through the review process.
If you have any questions regarding this subject, please contact Skip Milor at 375-6407 or Peter
Mazzella at 375-6404.
.---
19b
xc:
Clyde "Skip" Milor
Peter Mazzella /!!y
File
~
Alll~ ) 3 Iqo1
~~
PLANNINGEAp"TD
NING \) .
"P
MEMORANDUM
Utilities #94-252
TO: Tambri 1. Heyden
Planning & Zon'
FROM: John A. Guidry,
Director of Utilities
DATE: July 29, 1994
SUBJECT: Miami Subs
Staff has reviewed the above referenced project and offers the following comments:
1. Show proposed location of water meter and backflow pr~ventor on Sheet A-I,
(Sec. 26-16( c) and Sec. 26-107).
2. Show proposed location for grease trap. Drive-through ,.rea should be avoided for
access and maintenance safety.
3. Dumpster is shown QI1 irrigation pump pad and/or well. Relocation of one to be
considered.
4. Oak trees are not acceptable in utility easements. Relocate or change to palm
trees offset from water main, (Sec. 7.5-18.1).
It is our recommendation that the plan proceed through the review process.
If you have any questions regarding this subject, please contact Skip Milor at 375-6407 or Peter
Mazzella at 375-6404.
Clyde "Skip" Milor
Peter Mazzella r
File
m
19b
xc:
AUG . 2 ~l9~
J; ',~
P'
~ '
"
tp
PlANNING AND
ZONING DEPt
q
BUILDING DEPARTMENT
MEMORANDUM NO. 94-197
August 23, 1994
TO:
Tambri Heyden
Planning Di ector
FROM:
Al Newbol
Deputy Building Official
THRU:
Don Jaege
Building
RE:
TRe COMMENTS - SITE PLAN REVIEW
2ND REVIEW/CONDITIONAL USE
MIAMI SUBS - 4742 N. CONGRESS AVENUE
The Building Department has reviewed the amended site plan and
the attached documents and offers the following comments:
1. Section 4.3 of the State Handicapped Code requires an
accessibility route from the street right-of-way or public
sidewalk to the entrance of the building. This requirement
has not been met.
2. All signs must be in compliance with the Boynton Beach Sign
Code. The menu board can not exceed 25 square feet and must
be constructed no more than five feet above ground level.
Directional signs are limited to four per lot. The maximum
allowable square footage for wall signs is 111 square feet.
Since the above comments can be addressed at time of building
permit submittal, we recommend that the plans be forwarded to the
Planning and Development Board/Community Redevelopment Advisory
Board.
AN: bh
~ m ~~,om ~ ,:9Am ~
SUB
10
TO:
FROM:
DATE:
RE:
MEMORANDUM
Tambri Heyden
Planning & Zoning Director
Michael E. Haag
zoning and Site Development Administrator
September 2, 1994
site Plan
Review 2nd Review Conditional Use
Approval/Site Plan Review
Miami subs Grill
4742 No. Congress Ave at Boynton Lakes Plaza
David Daszkal
COUS 94-004
Project:
Location:
Agent:
File No:
The following is a list of comments regarding the second review of
the above-referenced project. It should be noted that the comments
are divided into two (2) categories:
The first category is a list of comments that identify unresolved
comments either from the first review or new comments as a result
of the second review. To show compliance with these comments will
not sub::-tantially alter the conf iguration of the site and the
design of the building.
The second category is a list of recommendations I believe will
enhance the aesthetics and function of the project.
All comments and recommendations can be rectified on the plans at
time of permitting if the request is approved. The applicant must
understand that additicnal comments may be generated upon review of
the documentE and v-lor]"ing drawings submitted to the Building
Departrrent for permits for the proposed project. These comments
will reslllt from the review for technical compliance with the city
code of ordinances.
1.
1.
')
.... .
3 .
4 .
SITE PLAN REVIEW COMMEN'rs:
On the site pI an dra\Aling dimension the loc a tion of the free
st~nding sign from the adjacent property line. Note that ten
(10) feet is the minimum setback allowed.
If the l~ndscaping located on the adjacent property along the
ncrth prcperty line of the subject property is proposed to
satisfy the vehicle use area visual barrier requirements of
the subject. property, not.e same on the plans. The note s11all
include the following statement: If the existing hedge does
not comply vii th the minimum standards for vehicle use area
screening/visual barrier r the required barrier shall be placed
on the subject property.
On the elevation vieh' drawings identify the name of the
manufacturer and manufacturer's number for the follm"ling
e~~terior materials and color of same: tiles f vinyl av-mings,
barrel tile, wall signs, site signs and automatic air curtain
units.
Prior to receiving permits to construct the building, submit
a legible copy of the corrected, City approved and recor~ed
"De.:laration of Restrictions and Grant of .Sasements" for the
Boynton Lakes Plaza and Miami Subs property.
/1
page 2 2nd review Miami Subs caus 94-004
5. Identify the correct address on the plans.
6. show and dimension on the site plan drawings, sheet C-1 and A-
1, a distance of no less than eighteen (18) feet from the east
side of the intersection of the ingress aisle leading to the
diagonal parking spaces and the access aisle south of the
building to the south edge of the first diagonal parking
space.
7. On the site plan drawing, sheet C-l, ensure that the following
site data is listed, shown and labeled:
Gross Leasable
Building Area (Boynton Lakes Plaza)
outparcel #1
Floor Area (Miami subs Grill)
Outparcel #2
Vacant - maximum assigned floor area
Outparcel #3
Floor Area (Cuco's rest. - leased site on
Boynton Lakes Plaza property)
Total leasable area including outparcels
123,432 sq. ft.
2,934 sq. ft.
6,751 sq. ft.
5,883 sq. ft.
139,000 sq. ft.
area (1:200) 695
of Adjustment
- 27
Total parking required
Based on square footage of leasable
Reduction in parking spaces - Board
Case #190 approved
Total parking required
(including 14 handicapped spaces)
668
Total parking provided
(including 15 handicapped spaces)
668
8. 110di fy the site pi an dra\'-7ing to depict a loading zone in
compliance with code specifications or receive approval of a
variance from the Board of Adjustment to omit the required
loading 20ne.
II. RECOMMENDATION(S):
1. To rgmain compatible with the exterior color scheme of the
existing main shopping center building, a condition attached
to the original shopping center approval, it is recommended
tlnt the color cf the exterior walls proposed for the nE'W
restaurant be changed from Hhite to a color that will match
the color of the lower portion cf the wall at the west side of
the Walgreens tenant space. The following changes are also
recommendations that would bring the ne\'1 building into harmony
with the colors of the existing main shopping center building:
a. Omit the color pink and aqua from the top raised band and
replace with the color displayed along the top of the
walls of the existing main building of the shopping
center.
b. Omit the pink and aqua architectural lighting.
c. Omit the center band of pink and aqua tile.
d. Change the color of the wall tile located below the
windows to a color that will match the new wall color
(matching the existing main building of the s 11 0 pp in g
center)
e. Specify on the plan that the spanish barrel tile roof
material will match the color of the roof tile on the
main building of the existing shopping center.
/2
Page 3 2nd review Miami Subs CaDS 94-004
f. Specify on the plans that the color of the storefront
windows and door frames will match the color of the
storefronts located on the main shopping center building.
g. where a wall sign has a stucco finish background, modify
the color to match the recommended new color of the walls
of the building.
Note: The color of the back-lit awnings and the color of other
features and/or treatments will be reviewed by the
planning and Development Board and City Commission.
2. Omit the neon from the free standing sign. Also, change the
color of the blue and pink border and sign background to the
colors that match the exterior walls of the main building of
the shopping center as described above in recommendation 1 and
la.
3. Close the outparcel entrance near Plaza Lane and relocate
dumpster and enclosure to the southwest corner of the parking
lot near the irrigation pad. Also, modify the turning radius
at the ingress to the one-way access aisle to accommodate the
turning radius of the City sanitation vehicles.
NOTE: If recommendations are approved, incorporate them into the
working drawings required for permits for the project.
MEH/jj