Loading...
REVIEW COMMENTS MEMORANDUM UTILITIES DEPT. NO. 99 - 183 TO: Mike Rumpf, Planning Directo~ John A. Guidry, Utilities Director\ -.... June 15, 1999 FROM: DATE: SUBJECT: Morris Building - New site plan - 1st review We offer the following comments on this project: GENERAL COMMENTS 1) Dept. of Health permits will be required for the water and sewer systems serving this project. (Sec. 26-12) 2) Fire flow calculations will be required demonstrating the City Code requirement of 1500 g.p.m. as stated in LDR chap. 6, Art. IV, Sec. 16, or the requirement imposed by insurance underwriters, whichever is greater. (see Sec. 26-16(a)). Please submit these calculations with your HRS permit submittal. 3) Sec. 26-34(E) of the City Code requires that a capacity reservation fee be paid for this project either upon my request for signature on the Health Dept. application forms or within 30 days of site plan approval, whichever occurs first. This fee will be $790.02 based upon a I-inch meter. SPECIFIC CONDITIONS 1) This office will not require surety for installation of the water and sewer utilities, on condition that the systems be fully completed, and given to the City before the first permanent meter is set. Note that setting of a permanent water meter is a prerequisite to obtaining the certificate of occupancy. 2) A building permit for this project shall not be issued until this office has approved the plans for the water and/or sewer improvements required to serve the project. (Sec. 26-15) 3) The waste stream from the manufacturing process must meet the City's pretreatment requirements. A sampling point must be provided to allow monitoring of this waste stream. (Sec. 26-143, 26-147) Please refer any questions on this matter to Peter Mazzella (742-6404) of this office. JAG/PVM Xc: Skip Milor Peter Mazzella File ~211999 MEMORANDUM UTILITIES DEPT. NO. 99 - 183 TO: Mike Rumpf, Planning Director ~fO) - ~ @ ~ n WI ~11 lJ1) Ml15. W J L PLANNING AND ZONING DEPT. FROM: John A. Guidry, Utilities Director DATE: June 15, 1999 SUBJECT: Morris Building - New site plan - 1"1 review We offer the following comments on this project: GENERAL COMMENTS 1) Dept. of Health permits will be required for the water and sewer systems serving this project. (Sec. 26-12) 2) Fire flow calculations will be required demonstrating the City Code requirement of 1500 g.p.m. as stated in LDR chap. 6, Art. IV, Sec. 16, or the requirement imposed by insurance underwriters, whichever is greater. (see Sec. 26-16(a)). Please submit these calculations with your HRS permit submittal. 3) Sec. 26-34(E) of the City Code requires that a capacity reservation fee be paid for this project either upon my request for signature on the Health Dept. application forms or within 30 days of site plan approval, whichever occurs first. This fee will be $790.02 based upon a I-inch meter. SPECIFIC CONDITIONS 1) This office will not require surety for installation of the water and sewer utilities, on condition that the systems be fully completed, and given to the City before the first permanent meter is set. Note that setting of a permanent water meter is a prerequisite to obtaining the certificate of occupancy. 2) A building permit for this project shall not be issued until this office has approved the plans for the water and/or sewer improvements required to serve the project. (Sec. 26-15) 3) The waste stream from the manufacturing process must meet the City's pretreatment requirements. A sampling point must be provided to allow monitoring of this waste stream. (Sec. 26-143, 26-147) Please refer any questions on this matter to Peter Mazzella (742-6404) of this office. JAG/PVM Xc: Skip Milor Peter Mazzella File PUBLIC WORKS DEPARTMENT MEMORANDUM #99-116 TO: Mike Rumpf, Director of Planning & zonin1g J () C. Larry Roberts, Public Works Director (:J..,fV THRU: FROM: Mark Lips, Sanitation Foreman SUBJ: Site Plan Review - 15t Review - The Morris Building DATE: June 16, 1999 The Public Works Department has no objections to the above named project moving forward, however we do request in writing that the gates for the dumpster enclosure have metal pegs to hold the gates open and to lock them closed. Any questions please contact me at (561) 742-6200. 51:11 /f/~ U. r:. ..,,-----:~ : ' ','., \ ~ ; j )"\ i, l \ ';\ \ 6 \999, \ -~ J ~,-,~P". LEISURE SERVICES PARKS DIVISION MEMORANDUM RE: Michael Rumpf, Director of Planning & Zoning John Wildner, Parks superintendeo~ The Morris Building TO: FROM: DATE: June 14, 1999 The Parks Division has reviewed the site plan for The Morris Building. There are no recreation-related issues outstanding on this project. The plan may continue through the normal review process. JW:ad (0 f[;, ~ ,~ ---"1 "",--",-"""'i ~ fDJ.' ii' . rrJ \ D I r"~" 1 c' \ II n \ 1 \L\tl JdN I j, -,.. ,\ ,.;. , J i:.:.. i. .",,_~L.'.; ,:jI. " ..;~~ FIRE & LIFE SAFETY DIVISION Memorandum No. 99-304 NFPA Life Safety Code 101, National Fire Code 1, all applicable National Fire Protection Association codes, and the City Fire code shall be adhered to. TO: Mike Rumpf, Director Planning & Zoning Division FROM: Steve Gale, Deputy Chief Fire Rescue Department DATE: June 14, 1999 SUBJECT: The Morris Building 161 Commerce Road, Lot 4 NWSP 99-013 We have no comment at this time and recommend this plan go forward in the process. CC: File CITY OF BOYNTON BEACH, FLORIDA INTER-OFFICE MEMORANDUM TO: Michael W. Rumpf JoAnn Alea DATE: 6-14 99 FILE: NWSP-99-013 FROM: SGT. THOMPSON SUBJECT: The Morris Building Site Plan REFERENCES: ENCLOSURES: 1. CODE DEFICIENCIES - I reviewed the site plans for "The Morris Building" and I observed no code deficiencies involving Traffic. I have no further comments on these plans, which were submitted for my review. I find the plans acceptable and recommend that they be forwarded through for approval. Parks Division Memorandum- TRC Subject: Mike Rumpf, Planning Director Kevin J Hallahan, Forester I Environmentalist ~11-- The Morris Building New Site Plan- 1 st Review To: From: Date: June 16, 1999 The applicant should indicate if there are any desirable trees on the site. The applicant should indicate if the trees will be preserved, relocated or removed I replaced on the site. The applicant should indicate if the property has been evaluated for the possible existence of gopher tortoises. The project should continue in the normal review process. DEPARTMENT OF DEVELOPMENT BUILDING DIVISION MEMORANDUM NO. 99-134 TO: FROM: Michael Rumpf, Planning and Zoning Director Michael E. Haag, Building Code Permit Administr~ . DATE: June 15, 1999 RE: The Morris Building - New Site Plan (NWSP 99-013) We have reviewed the subject plans and offer the following comments that shall be addressed prior to the project being forwarded for Board review: Buildin~ Division (Permit & Site Specific Comments) - Michael E. Haag (561) 742-6352 1. Add to sheet 101 (site plan) a labeled symbol that represents the location of the accessible entrance door to each tenant space. 2. Add to sheet 101 (site plan) a labeled symbol that represents the location and path ofthe accessible route that is required from the accessible parking space to the accessible entrance door of each tenant space. Add text to the label that indicates the accessible route is in compliance with Section 4.3 (Accessible Route) and 4.6 (Parking and Passenger Loading Zones) of the Florida Accessibility Code for Building Construction. Provide detailed drawings that verify the transition in elevation from the accessible parking space (23.9') to the (24.0') elevation of the sidewalk/finish floor ofthe building is in compliance with the Accessibility Code for Building Construction. Specify the cross slope of the accessible route. One to fifty 1 :50 is the maximum cross slope allowed per the Accessibility Code. 3. Identify the finish floor elevation within the footprint of the building that is illustrated on the site plan (sheet 101) and the floor plan drawings (sheets 301 and 302). Add to the site data, found on sheet 101, the flood zone that the building is located within including, where applicable, base flood elevation. If there is no base flood elevation, indicate that on the plans. Add specifications to the site data that will verify that the proposed finish floor elevation is in compliance with the minimum standards of the following: a) Minimum elevation required by the flood zone. b) Minimum elevation required by the South Florida Water Management District permit for the project. c) Show and provide computations that verify the elevation of the finish floor is six inches or more above the crown ofthe abutting right-of-way. Building Division Memorandum No. 99-134 to Michael Rumpf RE: The Morris Building - New Site Plan - 1 st Review Comments June 15, 1999 Page Two 4. The plans are inconsistent with respect to identifying the use of the facility. See sheet 104 and the site data sheet 101 (Land Use and floor area). Correct the plans accordingly. 5. Place the following note on the site plan: "Site signage is not approved for this project. Separate site plan review and approval is required for site signage." 6. At time of permit review, submit signed and sealed working drawings ofthe proposed construction. 7. On sheet 101 (site plan), identify the symbol that represents the property line. MEH:bg \ \CH\MAIN\SHRDA T A \Development\Building-6870\Documents\TRC\NWSP 99-013 1 st review The Morris Building.doc DEPARTMENT OF DEVELOPMENT MEMORANDUM ENG 99-089 TO: Michael W. Rumpf, Director of Planning & Zoning Jack H. Casler, PE, PLS, Acting City Engineer (),~ 6 June 18, 1999 V FROM: DATE: RE: THE MORRIS BUILDING - (NWSP 99-013) NEW SITE PLAN 1ST REVIEW COMMENTS 1. All plans submitted for specific permits shall meet the City's code requirements at time of application. These permits include, but are not limited to the following: site lighting, paving, drainage, curbing, landscaping and irrigation. Permits required from other permitting agencies, such as FDOT, PBC, SFWMD, DERM, L WDD, DEP and any others, shall be included with your permit request. 2. Recommend ingress aisle be 15' wide for truck traffic and a 12' egress aisle. 3. Change flume cross-section letters to "E-E" (there is already a section "C-C"). 4. Locate the handicap stall as close to the office area as possible to provide the shortest accessible route to an accessible entrance. [Section 4.6.2. of Florida Accessibility Code] 5. Recommend locating dumpster facing northwest so that truck can turn around in loading area and pick up dumpster on way out, subject to Public Works approval. 6. Delete references to (Concrete Flume and Integral Curb Detail) on page 101. 7. Page 101 - Change 5" concrete paving to 6" concrete paving. 8. Information is required for paving details as to sub base materials, thickness, etc. JHC/ck Xc: Ken Hall C:\My Documents\Morris Bldg. (The) - New Site Plan 1st Review.doc 1 st REVIEW COMMENTS Project name: THE MORRIS BUILDING File number: NWSP 99-013 Reference: 1st Review. New Site Plan. File # NWSP 99-013 with a June 8. 1999 Planning and Zoning Department date stamp marking I DEPARTMENTS I INCLUDE I REJECT I PUBLIC WORKS Comments: 1. The Public Works Department has no objections to the above named project moving forward, however we do request in writing that the gates for the dumpster enclosure have metal pegs to hold the gates open and to lock them closed. 2. Construction dumpster and service to be provided by City. UTILITIES Comments: 3. Dept. of Health permits will be required for the water and sewer systems serving this project. (Sec. 26-12) 4. Fire flow calculations will be required demonstrating the City Code requirement of 1500 g.p.m. as stated in LDR chap. 6, Art. IV, Sec. 16, or the requirement imposed by insurance underwriters, whichever is greater. (see Sec. 26-16(a)). Please submit these calculations with your HRS permit submittal. 5. Sec. 26-34(E) of the City Code requires that a capacity reservation fee be paid for this project either upon my request for signature on the Health Dept. application forms or within 30 days of site plan approval, whichever occurs first. This fee will be $790.02 based upon a I-inch meter. 6. This office will not require surety for installation of the water and sewer utilities, on condition that the systems be fully completed, and given to the City before the first permanent meter is set. Note that setting of a permanent water meter is a prerequisite to obtaining the certificate of occupancy. 7. A building permit for this project shall not be issued until this office has approved the plans for the water and/or sewer improvements required to serve the project. (Sec. 26-15) 8. The waste stream from the manufacturing process must meet the City's pretreatment requirements. A sampling point must be provided to allow monitoring of this waste stream. (Sec. 26-143, 26-147) Page 2 The Morris Building File No.: NWSP 99-013 FIRE Comments: None POLICE Comments: None ENGINEERING DIVISION Comments: 9. All plans submitted for specific permits shall meet the City's code requirements at time of application. These permits include, but are not limited to the following: site lighting, paving, drainage, curbing, landscaping and irrigation. Permits required from other permitting agencies, such as FDOT, PBC, SFWMD, DERM, L WDD, DEP and any others, shall be included with your permit request. 10. Recommend ingress aisle be 15' wide for truck traffic and a 12' egress aisle. II. Change flume cross-section letters to "E-E" (there is already a section "C-C"). 12. Locate the handicap stall as close to the office area as possible to provide the shortest accessible route to an accessible entrance. [Section 4.6.2. of Florida Accessibility Code] 13. Recommend locating dumpster facing northwest so that truck can turn around in loading area and pick up dumpster on way out, subject to Public Works approval. 14. Delete references to (Concrete Flume and Integral Curb Detail) on page 101. 15. Page 101 - Change 5" concrete paving to 6" concrete paving. 16. Information is required for paving details as to sub base materials, thickness, etc. BUILDING DIVISION 17. Add to sheet 101 (site plan) a labeled symbol that represents the location of the accessible entrance door to each tenant space. 18. Add to sheet 101 (site plan) a labeled symbol that represents the location and path of the accessible route that is required from the accessible parking space to the accessible entrance door of each tenant space. Add text to the label that indicates the accessible route is in compliance with Page 3 The Morris Building File No.: NWSP 99-013 Section 4.3 (Accessible Route) and 4.6 (Parking and Passenger Loading Zones) of the Florida Accessibility Code for Building Construction. Provide detailed drawings that verify the transition in elevation from the accessible parking space (23.9') to the (24.0') elevation of the sidewalk/finish floor of the building is in compliance with the Accessibility Code for Building Construction. Specify the cross slope of the accessible route. One to fifty 1 :50 is the maximum cross slope allowed per the Accessibility Code. 19. Identify the finish floor elevation within the footprint of the building that is illustrated on the site plan (sheet 10 I) and the floor plan drawings (sheets 301 and 302). Add to the site data, found on sheet 101, the flood zone that the building is located within including, where applicable, base flood elevation. If there is no base flood elevation, indicate that on the plans. Add specifications to the site data that will verify that the proposed finish floor elevation is in compliance with the minimum standards of the following: a) Minimum elevation required by the flood zone. b) Minimum elevation required by the South Florida Water Management District permit for the project. c) Show and provide computations that verify the elevation of the finish floor is six inches or more above the crown of the abutting right-of-way. 20. The plans are inconsistent with respect to identifying the use ofthe facility. See sheet 104 and the site data sheet 101 (Land Use and floor area). Correct the plans accordingly. 2l. Place the following note on the site plan: "Site signage is not approved for this project. Separate site plan review and approval is required for site signage." 22. At time of permit review, submit signed and sealed working drawings of the proposed construction. 23. On sheet 1 0 1 (site plan), identify the symbol that represents the property line. PARKS AND RECREATION Comments: None FORESTER/ENVIRONMENTALIST Comments: 24. The applicant should indicate if there are any desirable trees on the site. The applicant should indicate if the trees will be preserved, relocated or removed/replaced on the site. The applicant should indicate if the property has been evaluated for the possible existence of gophers, tortoises. Page 4 The Morris Building File No.: NWSP 99-013 PLANNING AND ZONING Comments: 25. Sign and seal all drawings prior to building permit submittal 26. On the site plan provide the following information: ChA, Sec.7, Par.B - A color for the wall and gate of the dumpster enclosure. - A location designated as a turn around area at the parking lot terminus. - Proposed sign plan including all wall sign sizes and locations. - Show a wheel stop in the standard stall in the parking detail. - Locate all proposed site lighting. 27. In the site plan tabular data provide the following data: ChA, Sec.7, PaLE - Open space requirement with calculations. - General Note #8 refers to white paint stripes and the parking stall detail refers to the use of black stripes. Verify and correct. - Detail the mezzanine / office data. Is the building one story or two? If possible add a note on the building describing the mezzanine area. 28. Submit colored elevation drawings of all elevations of the building. ChA, Sec.7, Par.D.2. 29. On the landscape plans provide the following information: Ch.7.5, Art.II, Sec.5 - Overall heights for the two groups of Sabal Palms located at the southeast comer (front) of the site. - Label and dimension all required landscape buffers. - Locate all proposed site lighting. - If a hedge exists on either of the adjacent parcels to the east or west, the perimeter hedge requirement for that boundary location can be waived. If a perimeter hedge does exist on an adjacent parcel boundary, it must be shown and labeled. - Based on the information given, a hedge is required along the east property line. J:ISHRDATAIPLANNINGISHAREDlWPIPROJECTSIGEVAS NORTH AMERICAN HDQTRSINWSPI1 ST REVIEW COMMENTS. DOC 06/23/1999 17:3~ 561375625g BOVNTON BEACH P 8 Z . .'........ ..-. 1 .. ._oJ ....~. ......- PAGE 01 ~,L."oI.._ ......... 1 ~ .,..~-... Facsimile TAANSJtAmAL . - .. cny OF IOYNTON lEACH 100 E. BOYNTON BEACH 80UUVAaD ',0. lOX 310 BOVNTON 8IACH, 'lORIDA la4u.G310 FAXr (S6n 142-621. PIANNlNG AND ZONING DlVIS~ON to: Richard C. AhreN . ,...b.....- .. fa II: 561-963.9007 date: June 2S:1T99 !roms Midi..1 Rwnpr- ,..- COMMENTS -- ,""'I rt: ..~ .. ... ....... P...., L., lJ~yl.llng wvc:r m&:et. PI.. tmQ 1b4lb~ lb. nm 11\'6;amm1lU COI your prqJec:t 1"0 __ an d:e Ql~ ~/1lW~, pI.... ., tM foIlowlq-. Uatld be~ tor1he ftC mcttlla ""f(lulld tor July 20. 1999: l) ltvlll yeW' plUIf lll~' .a ~ IJtcJd .... ....ludiq the a41ttiOft of rlDtIt 011 pi.. to .,onftl'm ~ ~..... """"eomm_. Aild btfIJ& JO eopta to till nc ~vi.w: ~) homAt ..Idditioul fntormlUlm u"" wt1b.Ia..~ ~~ ,> ~. ..m.n t'MJlClOU (1 ~..) upJaiDfDa boW'" ~wnent hu beeo IICkhuecl. ~ tb.e r,villl1 p. or wttllll!e ~ ~1UI1.lJHJudJJll ~OQ QO 1M ,1IIn. 'dsia plOlDOtelan txFtdlttou. z- ~,itw ~ iliff. your ,rojeot I1p'Mt.llfIII_l: ,"d ~ 4) PNpII'I tl4IIWQOl (' ~ 1C ) 1) for.. propoIed IitI pIIG 01....... plla, tllvatiolu ancI ~ln. ~ ~ ,.. (CiJ.1I ftCIUJted (or ... ft8aJ NpaN '*' pubUo ....Iadon). Purth..-moro, items rtoOtniIK by _a A* t)'picaUy OLlUWlIliq .. thb pt).lnt iDcJudl!l t U'Iftlc report Mellor GOnfwllat!oQ Ou~ ,.. SIKh COWlt)'. ~... CIl'd.ftclUoa by a J-...s onps_. _ ~lored ~14Y1daaa oft!lt PJ'OP(IIId JI'OJ-:t. 'Ib1l1llf'ora1adclo is JltMMt.tY fbr the Jlt'OJ_1o proceed. Ilyou have $u~ml..s ~ J.nt<.M\atJon, pli... dwtpl1i Ibit lIot.. lO'd vIO'ON lS:t1 66,10 lnr !..006~98I9s:aI S3IN~dWO) SN3dH~ a&/~3)1999 17:33 56137!S62S9 BOYNTON BEAC~ P & Z PAGE e2 1st REVIEW ~MMENTS ProJ~t naml; n. Mom. Sundin, Pil. nwnher. WWSP 99-013 hf~oe: lJt ,.._iew. N~ Site Plan. 'I" 11 NWSP 99.0 IJ. XVith" lwIl!.. 1999 ~~J)jnB and Zonih8 D!PARTMJiNTS puauc WORKS COJM1ctl: INCLUDE kFJECT 1. Th. Publhl Works Depat1m.~' Iw DO obj~tiont to the above name4 ptuJ.."t 1l1uvtuI rurwlf.l'd. tww~"'r ~tt Ill) rtqll~.t in wrldq that the gates for tit dllOlpltlr onclOlure have metal ~8I to hold tlle aates open and to lock them clcud. ' 2. Conltru,tion dum IWftJtd NtVf~ to bt UTILITIES COmmt11t1l ). ~Pf. ora..'tb permits wJII be re'lJ,l1ud tbr th. watlX' and MWIf systoms "'V,W t,W. r 'wL. SlaW, %'..12) 4, PIr, flow ~leylaU(lAl wW be ft'lu1tld dfmooau.tin& the City Cod~ requiftn1cD1 of lS00 ..p.m. u stated tn LDR chap, 6. Art. IV, Sec. 16, Of the rcquLre.monc iqJoud by lNutanc:. underwriter., whichaveJ: ill ~t.1'. (.~ ~", ,1".,1~(")), :PI.M~ luhmlt th.~tfl C'.aJ("Jlllltlt).Q.l wJtb out Has t bmiual. ~. See. 26--34(1) of th. ell)' C<* fOquirtl dial .. capaolty rtwvltion r.. 1Jv ~ ru~' tJ.lia. p.l'{jllNl .111..-J upuu JJJl'''Ll~t .lU~. ,iiHlJ,.hlJ.... VI' lltll Health J)epl. applleatioo form. or within 30 d4)'s of sfte plan lpf)tOvaJ, wftl~hevet ~QW'I ijrst. 'rills foe wlll be $'}W.U2 ~ upon. 1 ~anoh rulter. 6. ", I. 0,"010 will not require surety for inataUatlon of thl watar and sew.t utUiti... OIl ~adition tlw the Iyateml bf filII)' c:ompllttd, a"d $ivln to tht City 1>"0" th. A'.. pttman.nt rntt.r i. ...t. NoN that stttlna of a permanent ",ater meter je .. ~qui.ite to obtainiq the ...J'lwli." u{ U,"~1.l l\O. 1. A buiJdioapomtjt for this projec..hAlJ not be jSaqf(l until tbis offic. hu .pproved the planl fOt the we... and/or .ewer improvement. \tlncho MtV. tho ro'~, ~. 26-J') ., The Wat" .cream from the manufa.~rina procesl mU6t meet tho City's ~tn:l.ot ~"'rern.ntl. A IImplin, point mud b. provided to .llow JUOIitoria oftbt. waste_a.m. Sel:, 26-143.~6-14.?L- ~O'd U10'oN 1S:!t 66,10 lnr l006~98t9s:aI S3INbdWO) SN3~Hd 06/23/199S 17:33 5613756269 BOYNTON BEACH P So Z PAGE 83 Paa.2 lbll Morrla BuUd.lng Ifj1e No.: NWSP 99.013 ~ PIll! --. .. -. I '- ---. COIIlmufa: Ncme ~OUCB .- ~ .... Commlfttl: Non. !NQlN8.ElUNCl D1VfsrON Commtat.l: 9. A.U plm! Jubmitttd COt .ptOitiG plrmits .lIall meet the CitYs CO~ f~q\a\~mClnte ltt Um. or .ppUcatloQ. n... penxaitlt iDclude, but .... not 1hnlted to the fol1owln,: Ilk t1,1bdna. "a\lJ",~ dra'na,a. ~ 1ud~pinl ud iniption. Pwmits required ftoom ather pormfttistl ,,""iIN, 'Uo" Ie PIX>T, pac) SFWM'D, DElUd, 1. WDO, DIP IJJ1d my othtl'lt lhatt bI meJucled with your ponnit (tlll'..t. 10, Rteommtnd. in,re15 atlle ~ J S' w~ for b11ck traffic and a 12' egress aitl~ 11. CJwsa- flumt clOtl-Ud;OIlIetfe.ts.t' "F...R" (tflere i~ .I"",dy "lltctinl'l "e_C"). 12. Lomt the hlDdi~ .taU .1 010.. to u.. oft'lee ~ u pot.lbl. to provf40 .t..lhorrolt a=aIble routI to In ICCOJlibll ont(M~'. [Sfotlufl ~.45.2. of FJorida .AccuaibiUty CocI.tt U. a,comma batlnJ.l dUm".... fHiD~ north~ so that eru.ok QU turn ItOUnd J.o, bldiq.am md pick .t.IP domptCfr on way ~ ..ojeoI t-o Public WOW AJ)1)~It" 14, 0.10" r.fOton~..lt to (ConQnlt.<l :Phuno Uld llitGp_l Curb o.io1l ) on Pas. 101. ~.. -"i U. page 1 Q J - Cbui! ?" ~nc~~ pay'~ to ~II c~ne'" ,.vlnl - 16. Tnformatlon ;s requirtd for ~"ln. detail. 8S to sub bue materIals. thidc.nta.. .10. itJTLOINO DIVISION L ...._P'rl _ - 17. Add to sheet lOt (_it, plan) . llb..ltd ~mbol that rtprcstnll tho JOCBtion of the AOClol3liblo iC>>1rUQg dooJ to Claoh t.cncmt IIPAOO. .,. la. Add tD AbNt 101 (altai plan) a labeled Iymbol Chat reptesen. the loolllon and path of tho aC06ssi~te rout. that is ,equired .6-001 th. acc....b.lo ~ fQ tile ac(eulble .ntt~ door of tACh tenllllt .~*~.. A~~ ~ :? ~O'd P!O.ON GS:!! 66,!O lnr L006~9819s:aI S3INbdWOJ SN3dHo OS/23/1999 17:33 ~613''56259 BOVNiCN BEACH F & Z PAGE: 94 P.3 Th. MUrTi.- EMldlDs 1"il. No.: NWSP 99-013 to," to thtlabcsl tfl.t jndl~a_ tho acoeuJbie"route 1; In cnm"Ji/'tl)ce whit Seat(OfI 4.3 (.A,,,..iJtle 8.0*> ., 4.6 (Parld", and PalleC,et Loading ".em..) ()ffh~ Florid.. Aec..,ibUtty Cod. far Buil4ina Conltn!ption. Provid. detalltd drawlnp that verify the ttauition ill eJovatfon from th. laQooe.l~lo pulcill8 'PIl9Cl (23.9') to tit. (24.0') 41"vlliilJU "fa. ,jo.walkltlnJab floor of ~ b\ln~... it in oompliaooe with the ^"""lblllfY Code for auttcfl~ (:QO.uvcUon. $pecify tile Qro.. slope of'tho lGO"fible rout.. Oft, to tJfty 1 :50 Is t~ t\\oxJmul1l crOS$ slope I aJJawtd pOP th.: AQc~$$tblUty Code. ... 19. I~ntlt)l tilt ftnisll floor ,1'VatiOD within the foolprlnt of tht buildlua that te iU,,~ ~ d). w pl-.n ($11.., lot) and the flQOf pl&n drawi.,S' (Ihoot$ JOt gd 302), Add to the ,iw data, found en sheet! OJ I th.t: flood ZQnQ that tho buildIn, hi J~.wd wldtla ictoll.Klifll, whww applifoable. bUt flood elevation, Ifth... is no base flood olevatJQI\ Indicate tha1 on the plana. Add !S~1'kl4ldon' 10 lb. 'It. 4111 that will verII)' that me propoaed finish floor elD\latiol1 i. in complianoe with the minimum ~dud. orlh~ 1b11owtnt: a) MlDbnum olevation required b)l1he flood ~I. b) MfnUnum .Ievadoc required by tbD South f'lorida W8b5r M.IIIJemMt Dbtrlot (lermft 'nr tM pr4'tj4lCt. 0) $bow fIl4 prov~ ~._vertty thtl1evaU01l of the (lnl.h fl~ if ,ix inoMJ Qr mwo -.b<wQ thf ~OWIt (lftho abuttlna l'iiht~o(Mway . " ..'u. 20, Tbt plans Ire lacoasiattnl with "5J*t 10 ictemif)'inl the use of th. fIcIUey, Sto mc=e.t 104 Nld d.u.: .!to 4J. ih. J 0 I (LMd U~ lU)d floor Ilea). Corrlcrt 1110 Dllns 8QCOrdingly. 21. Plac. tbefoUowina no~ on eM .~ plan: ~ite .i8Jlllo is npt approved for tbl, ,~JOOt. Sopuatu lit~ plIO rcviow and approval i. *l\lir~ for lit. lIimu:.." .- - . .' .. 22. At time of Pttmlt "vIew, .u.bmlt ,1ip6 Ind ualed workln. drawings of tJut Drooostd c;QQItN~tion. 2~. On ,hltt J 0 I (_Ie. pl.-11dent'6' the .ymbol that rcproantl the propeR) 1... ... rAn:KS AND RBCRSAnON ... eornm..Dta1 NOlle . ". FOllE~'MJlIPNVlRONMRNT AJ .J.!IlT Conunentl: 2.4. The applicant should lndicate if there ..,. laIIy deliralitle trMI Ob the lite. The 'PpUc.." should lnCUcatt if the trotS will be preserved. ...Jocated 01 rcmo\ICdlnwpJaood Oft the ,ito. The apPUCU'lt 4hO\lld lAdic.&w if the ~O'd ~tO'ON ~S:tl 66,tO lnr L006~9819s:aI S3INddHOJ SN3dH~ "'~ 1\~~ 4~~~ . ~ C~ vb'~~/l~~~ 17:33 '5613756259 BOYNTON BEACH paz PlllG( 05 Pai' 4 'nl~ M""1I 81.111411", 'UoNo.: NWSP ~13 :~o ;lI'~ proptlty 11.. OCCal evaluated rot'tfio I ~iljbfe exlstenoc o( ~pher tmtoi.... PLANNlNQ AND ZONING Commentl: ZS. Sian u4 ..1 all drawiDal Prior CO buildina pmnit .ubmittal 26, On tht Ii,. p.um. prcw,<t. the foUowins iDfOl'll'llltiou: Ch.4. See.7. Par.8 A A color for th. wN1 ~ti ..... of. dumpQn' ..olDIUIC. ..--;,;> .. A loc:atton 4t.iaaateclu a t\lm around area At the p.tleing lot 1emtlOll. . fln,poMd lian plan iac;luc1ltlJ an waU sip.'. and locationlJ. .. Show I wm..lltop In 111, ItIlldJrd atalllJJ the paatblg detail. .. Le....'U pro.,_ site 1;,...,.... 2? a tbtl sitl!! p4tA u.bulAt lilt" ~(de th. followfna dMa~ Cb.4. !e<t.'7. PIU'.B ~ Open :t~ roqldrcmont with _JCUlldOR'. .. a.. N.', fef.... to whitt palm 8ttipe. Md the plddfti stall dOtaU lOt'eIs to dle.. otblHk mlpe$, Vorl~ and~. .. ~I\ ... mazanlnc: J 0'" "- 18 Ul. bufldln, ~ ttn(y.OI' rwo? If po&sible ICklIl note O,P the building de'Clibio& the nurl.Zlnil1e "'... ~" 8tlbm It ('C)klnwi f.\1..v"t~n ctMWift~ (j' ,,11 tI)M'Atin~.. t)t the hllilttine. Ch.4. SIO.7. P....D.2. 29. On the Imdacape planl pmid, tho following ialofllJ.tion: Ch.? .S, Al'J.nl $Cl~,' . OvenU h.iahU for the Met group. at Slbal.Palms located at the soutbu$C COtMt (&01\0 oftbe ailt. . Label aqd dlmttsioa aU teq\ltrtd *,dlO~Pt buft'n. T JAclte all proposed lite Uptins. .. lr. .~.. el("~ M eit'-r nfthe .u.~t r-cel- tn the cut (I.r wem, ~ ..-- tho perimer,r hed. requlretDent for tftat bo1mWy _tlon Clft be w.Iv... It. ptrlm"., 1M. dot. ~det on jIQ ~aotll' poro.l boundary, it mult be shown md label.d. ~u ,..:'? - Dued on tb. lntorntation given. & bodlC: ls ~ired alool tbc out '!t property liD.. \1D~_'M'~)iOmT"Ii"CMR'IIl.UNWMf'\'6T~COleMlrm.OOC SO'd VlO'ON ~S:1t 66. to lnr L006~98l9s:aI S3INbdWO) SN3~H~ .-._~---~ .-.-.-.-------.---- ,.:PARTMENT OF DEVELOPMENT MEMORANDUM NO. PZ 99-155 TO: TRC MEMBERS Bob Borden, Assistant Fire Marshal Kevin Hallahan, Forester/Environmentalist Lee Thompson, Police Department Pete Mazzella, Utilities Department Michael Haag, Building Division Ken Hall, Engineering Division Larry Quinn, Public Works Department John Wildner, Parks Division Ray Davidson, Acting City Engineer FROM: fVl (,/~ Michael W. Rumpf Director of Planning and Zoning DATE: June 10, 1999 RE: SITE PLAN REVIEW PROCEDURES 1 ST Review - New Site Plan Project - The Morris Building Location - 161 Commerce Road, Lot 4 High Ridge Park Agent Richard C. Ahrens, Ahrens Companies File No. NWSP 99-013 Find attached for your review the plans and exhibits for the above-referenced project. Please review the plans and exhibits and transmit formal written comments or e-mail to JoAnn Alea and I no later than 5:00 P.M. on June 16, 1999. When preparing your comments, please separate them into two categories; code deficiencies with code sections referenced and recommendations that you believe will enhance the project. Adhering to the following review guidelines will promote a comprehensive review and enable the applicant to efficiently obtain Technical Review Committee approval: 1. Use the review standards specified in Part IV, Land Development Regulations, Site Plan Review and the applicable code sections of the Code of Ordinances to review and formulate comments. 2. The documents submitted for the project were determined to be substantially complete with the exception of traffic data, however, if the data provided to meet the submittal requirements is insufficient to properly evaluate and process the project based on the review standards or the documents show code deficiencies, additional data and/or corrections should be requested by the reviewer by contacting Scott Barber, or myself. 3. Each comment shall reference the section of the code that is incorrectly depicted on the documents.