REVIEW COMMENTS
DEvELOPMENT DEPARTMENT
MEMORANDUM NO PZ 99-041
SITE PLAN REVIEW STAFF REPORT FOR
PLANNING AND DEVELOPMENT BOARD AND CITY COMMISSION
February 23 1999
DESCRIPTION OF PROJECT
Project Name: Coiltronics, Inc.
Property Owner. Quantum Limited Partners, Ltd.
Applicant/Agent: Sam Pinson I Rhon Earnest-Jones
location 3601 Quantum Park Boulevard, Lot 15 (see Exhibit "N - Location Map)
File No. NWSP 98-026
land Use/Zoning. Industrial (I) I Planned Industrial Development, (PID)
Type of Use. Business office, warehouse, light manufacturing and distribution
Square Footage Site Area. 111,740 sq. ft. (2.56 acre), Building Area. 25,401 sq ft.
Surrounding uses North - Motorola - Lot 14, zoned PID
South - Quantum Park Lot 16, vacant, zoned PID
East - Quantum Boulevard right-of-way
West - Water management tract "H", zoned PID
Existing Site The subject property is vacant and consists of 2.56 acres. The site is
predominately vegetated with a variety of overgrown grasses 11 Slash Pines, two
Pink Tabebuia, a few small Brazilian Pepper and other scrub groupings. To the east
of the site along the Quantum Boulevard right-of-way, is a row of 7 street trees and
a 20 foot wide maintained grass area which provides some screening for the
adjacent uses There is no other significant vegetation on the site
Proposal To construct a 25,401 square foot, 2 story, office I warehouse manufacturing
building and related parking (see Exhibit "B" - proposed site plan)
Concurrency.
a. Traffic - A traffic statement for the project must still be submitted. This study will need to be
prepared showing that the project meets the county's traffic performance standards as it is
related to the 63,752 maximum trips permitted in the Quantum Park PID
b. Drainage Conceptual drainage information was not provided for the city's review The city's
concurrency ordinance requires drainage certification at time of site plan approval. The
Engineering Division recommends that the review of specific drainage solutions be deferred
to time of permit review, when more complete engineering documents are required.
Driveways Proposed on-site traffic circulation consists of a 27 foot wide drive aisle with one
access point to Quantum Boulevard. The proposed vehicular use area will provide
parking areas containing the required 9 foot by 18 foot spaces
Parking Facility.
There are 151 parking spaces proposed, including six (6) spaces designated as
handicapped accessible The parking plan will meet the city's Land Development
Regulations Chapter 2 - Zoning and ADA requirements for this use, and provides
for 57 surplus spaces Regulations for the Planned Industrial Development zoning
J
Memorandum #99-041
Coiltronics, Inc.
Page 2
district require parking requirements be based on number of employees Minimum
required parking spaces is based on 125 maximum shift employees (one and one-
half parking spaces per 2 employees) The conventional methodology which uses
building use ratios (one space per 300 square feet of office use and one space per
800 square feet of warehouse area) also results in a surplus of parking spaces (e g
151 spaces provided - 121 spaces required = 29 spaces surplus)
Landscaping" The landscaping of the site will fully meet the code requirements when staff
comments are incorporated. Special attention will be given to preserving the seven
existing Java Plum along the Quantum Boulevard right-of-way, and relocating two
Pink Tabebuia at the southeast corner of the site Since the completion of the
Quantum Park roadway system, some of the plantings shown on the approved
right-of-way planting plans have died off The proposed landscape plans for
Coiltronics incorporate only the existing tree plantings that remain The Quantum
Park Architectural Review Committee will need to review all proposed landscape
plans for compliance with their requirements, which may exceed city standards.
Other Regulations Building and site regulations will fully meet code requirements when staff comments
are incorporated into the permit drawings. The Quantum Park Architectural Review
Committee will need to review all building plans for compliance with their
regulations, which may exceed city standards.
Community Design The proposed building facade, as viewed from Quantum Boulevard, is within
standard structural characteristic requirements of this predominately industrial use
area. There are no established architectural styles or colors within Quantum Park.
The new structure will receive stucco surface treatments in colors of white blue and
gray with terra-cotta roof trim The project must still be approved by the
Architectural Review Board for Quantum Park.
Signage A proposed sign detail was submitted as part of this site plan review The approved
Quantum Park signage plan allows one monument sign, per parcel, with a
maximum sign dimension of 7 feet high by 14 feet wide, and 64 square feet of sign
face The submitted site plan utilizes a building wall sign and no right-of-way signs.
There are no wall sign regulations established for Quantum Park. The proposed
wall sign meets the requirements of chapter 21 of the City of Boynton Beach Land
Development Regulations In the future, if the developer decides to add a right-of-
way sign, increase the number of wall signs, or propose a sign design change they
will need to request a sign program modification, as a separate submittal to the City
of Boynton Beach Planning and Zoning Division, or conform with the existing sign
program for Quantum Park.
RECOMMENDA TION.
The Planning and Zoning Division recommends approval of this site plan request, subject to the
comments included in Exhibit "C" - Conditions of Approval The Technical Review Committee (TRC)
recommends that the deficiencies identified in this exhibit be corrected on the set of plans submitted for
building permit.
xc: Central File
J;\SHRDATA\Planning\SHARED\WP\PROJECTS\CoiltronicslNWSP\s~e plan staff report ciollronics,doc
/1
;L
LACATION Mt~P EXHIBIT"
COILTRONICS, INC.
~:::::
.:=:
---..
~
-...
-
-
~:intf~
~L
. ..l i\\.
9
.- ....----
-111 t:::Irlllllll..II~'
I ~J JU. lj'"'' I I .z f "[7 N aT
A~r:; ~ \Q {iJ t:= . l. nNI
\/1.., <:I il!J . '\ E t" : ; C I ~NV c' c.:..: ~
-~ ~.Up' ='i: ..1rit~
J{i ~ ~-~. '.~Wl - =:~ i,'l
~ ~ - I\aT ::- Qo~ 7 ~ /" TT-
=ITV' ~ EJ~ 2',- , .:.~\ __ ____\~ /
\S r;: ~ "$... - -- 7 ! r- \
~ rI]4);6'~~ /. lL~nl!,= !/_~\f.~
~ <VY II'-j 1f4tfr L I - ~
~~t~. l~ "1', !/l:~ _ C&~ ~ ~,-
- ~ ~ : '\ 1: ~ " .~\ - ~d': I
:Jill) ..;J . , .' P' . '~ '_
\ \. ',:, : ~ .~.,.. .... . ~ .:
\ '- - -' '-."" -. =="".
f\::J : :.~! \ ~~ /'. "\ r;
1 : i ,\,. 1.-- ;:."i). ..'.. .." .... ~
= _.u _ . -{N. W !1t4o., :'., W ,/'1
I r ~ \' \ .... 'r.
~: _': __ ,_~!tffut\'~ I . "
I " ~: //} f ~ ,,,.i, - ~J'J' \ L" ~
_=.....[ ~/ I'. \ ~JIOVNT~ _:~eAtH
-- - K OF COMMERU1:-
~ . ';r:lUANTUM PARKJ
P I D ,~--
. -, ,
I;jJ"T
I
1
f
--
I
"MOTORDLA, '[/\- ~'
I \' , .
l~~ . 'to "~:' -
ft\ . ,
,~.
i~ , ....
P"". Me
];~
j
....'t:n,
J
.~
....-:;;:::, Z:
,..-- I II
_JJ I r1 'Ii
MILE'SV' "
I
~
~
l~~
I ~
, ~
I 141
~I
~~ ~l
R AA
,
\ \~'I:::::: i, :~(Q]jUIID I' ~r~ ...
, '- rl -~---.....- - -:'
: l~ : I R I - ~ -IU
i :t:1... ~ IE: :. f-.... - ::c
J.'Q~ : _~ -~
. .~ ~ --: E ~~ 0 1/8
",~l ~ - ~ II 'I
", 'r;' I I , ,Il ~: nm
.! it:l~T1r ~ ----:n 400 Rnn ~;::;::T
--
.,.." a.
. rn.
'-"-'-
i
"
~l%
:A
:~.
li~
~'i
w'
~
..
i
:..i!
~i~~'J
I F~~I
~
::a
;>c
~
;
<n
.."
~
.,.,
z
...
'J:
,,:It
~:I:
enO
c:z
5m
Z:It
(;)z
~m
I~
:DO
~z
zm
P.
P.:~.l"
!:f,. ..
Ie-. . ';$.-
~.-. Sf! ~
.~
~511 ~
:!.~ iiUf
rrr.: m ~
!l~i!~
! a!"!fi
: ,'i' lfI
I l -, .~
! '. ~
i !If
i.
~~
~~ j
.!':~ 1
~~;;; ~f
~j~
;~! i
!~:
io~
!:J
;~
i.=:
"I:;
I.s
~"i
~
i
a
. .
.
,- -
:: f
oil .
,t., ..
":: .
i~ i
i::
:!
=~
~~
~.~_._. ;t
t il
;~~- ~
!f -1,"'--':'
t. . .a
,'~ I' .
1-1~::r ::
: ."
~. -~,-: .:;-~I:
~
=q." ..
I.:.I:;~.,.;;
;, E i= If E
:. ilS,.
~~ e- .;; i: lor
s- .... r =
:.t ~ I-=! c
.~~ ... .1 .... ~
:.!i b. =; i.
"0 ., '. to
~;=:1n
-:I ij ~
. --i
9 Ii
I! I.."
~!
i
r"
~ ~
- .
H
. ~
"'C
EX-HfBIT
!
t
i
i
I
I
i
I
I
i
~~ ,.f' ~
;-0 ..
~;:; ..~~----~
-~ -e===---- ,:----~
;1""- .
=1~ f
- " ii ItIJ jQ
.. II !ill m
ii \;
~
~~
!
i
/
~-
~-i
- .
..=
i .
!
j
~
i1~
f'
j
".
:
~
iIi
;:~~
30 ;
. - ..
~~ ~
-..-
~;,r.: a
'''3
ji.: 0
z
wh
if,,:
1;-'
-I...
".-
---
.-
....................
.....................
i
..
..
'"
....
:; ;:
:r.
~ ;;
...
~ I
:;;
.::
. .,..;
:t~ ~t
.... ...~ .....
..}...~-- -~~~~'_.
-: ' Q{ ~ -.I
~ ~. . r{ Jt ,..... :;-
-,. .'10 ( .
..........~-."_ .:"ta. I. ~~
'- i .Ilia
..--................ -"
t~ f """:-~
,. .................... :--
ili "-"-..f, ~
....................... .
................. :
..........:::.- .
...................
..................:~
.;
.::..
-'t:'
~,.
.
"C
~.'; ~
- =i
f
A
;;.":
-j
--
.
z
.n':
I
" ...... --
i ~""'; ~ -,;
i E~:; ~~.i
· ~i~ '.~
f. :~i :
. .
s~!l
~ =.
in
~ ';;~r
,~
..;
T:
~ 7!ji ! ~~
~ i :, II...
~i'r ~~;~ :-
n 1. " f!f :=. ~. i ii
.f ;!i;
:t "
.i ' F !~!f
Ii ., ji
.- ~
~.L!'
-'!"""
----. ---"S.~::..;..~~~~,
. ',' i;:;.~-- '
~. -\-~-....~..~---,
_~i ,,~ ~~r -.;:
' ~.;. ,,'~ ',,' - j!
-=-~ ~ ~~.. '{J
---;i! ~-t .,L___~
, .s~ t";-~_.:_~--.-,\- ~
-' -., ~_ :.te=J - To"
-'-..~' .~
-- - ----=-- '0' I I . .....
--.~ I : LLJ
.~~.
~f
Ii c~
.. ~,
I -'
~ P i
i :~ '
i ,~ ~
c; '. f
III ~~ ~
.~ l;
llo .
~, ~
q: ;
ii
!
!. ~
f
<
~.....
........
--
ltj
~
<~.
...
:
. :~
~~
~l
i
=:~
! I ~
~ I
It '
,... f~
1m. ~ ~~
i
I
I
F.\CILITY
. i
- --e
Ii!!
iH
I: I
; .
!H
Ii:!
li
;.
" .
COiLTROJ\ICS
.
.P:-
_ li!~
-.I! 1'::.:)
i EI!;. fl
I
I QUANTUM CORPORATE PARI\ .L...}
I'
EXHIBIT "e"
Conditions of Approval
Project name' ColltronICS, Inc.
File number' NWSP 98-026
Reference: The plans consist of 11 sheets Identified as 2nd Review. New Site Plan. File # NWSP 98-026
with a February 2. 1999 Planning and Zoning Department date stamp markmg.
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS
Comments:
1 Waste removal m connection with construction process must be serviced X
by City of Boynton Beach. Place note on plan to indicate same.
2. Dumpster enclosure must be minimum 10 feet by 10 feet internally X
dimensIOned.
3 Pave small area on north side of enclosure to enable space for gate to X
swmg clear of opening.
UTILITIES
Comments.
4 All utilitIes easements shall be shown on the rectified landscaping X
drawmgs so that we may determme which trees may interfere with
utilities. In general, palm trees Will be the only tree species allowed
wlthm utihty easements. Canopy trees may be planted outside of the
easement so that roots and branches will not Impact those utihties withm
the easement m the foreseeable future. LDR Sec. 7.5-18. I gives public
utlhties the authonty to remove any trees that mterfere with utihty
services, either in utility easements or public nghts-of-way There
appears to be a direct conflict between a canopy tree and the fire hydrant
at the termmus of the water main.
S Department of HRS permits will be reqUIred for the water system X
serving thiS proJect. (Sec. 26-12)
6 Fire flow calculations will be required demonstratmg the City Code X
requirement of 1500 g.p.m. as stated in LDR Chap 6, Art. , Sec. 16, or
the reqUIrement Imposed by msurance underwriters, whichever IS
greater (See Sec 26-16(a)) Please submit these calculations with your
HRS permit submittal.
7 Sec. 26-34(E) of the City Code reqUIres that a capacity reservation fee be X
paid for thiS project either upon the Utilities Department request for
signature on the Health Dept. application forms or within 30 days of site
plan approval, whichever occurs first. Based upon a 2-inch meter, the fee
Page 2
Coiltronics, Inc.
FIle No. NWSP 98-026
DEPARTMENTS INCLUDE REJECT
is $2,106 72.
8 Comp Plan policy 3C.3 4 requIres the conservatIon of potable water X
City water may, therefore, not be used for Irrigation where other sources
area readily available.
9 Provide an engineer's written certIfication that draInage will conform X
with all rules of the city and the South FlorIda Water Management
District. (LOR Chap. 4, Sec. 7F)
10 This office will not reqUIre surety for installation of the water and sewer X
utilities, on condItion that the systems be fully completed, and gIven to
the City before the first permanent meter IS set. Note that settIng of a
permanent water meter IS a prereqUIsIte to obtainIng the certIficate of
occupancy
11 A bUIldIng permIt for this project shall not be issued untIl thIs office has X
approved the plans for the water and/or sewer improvements required to
serve the project. (Sec. 26-15)
FIRE
Comments.
12. PrOVIde mInImum 5 foot clearance between hydrantslFire Department X
connections and vegetatIOn.
POLICE
Comments: None
ENGINEERING DIVISION
Comments.
13 All plans submitted for specific permIts shall meet the CIty'S code X
requirements at time of applicatIOn. These penmts mclude, but are not
lImited to the follOWIng: sIte lIghtmg, pavmg, drainage, curbmg,
landscaping and lITIgatIon. PermIts reqUIred from other permlttmg
agencIes, such as FDOT, PBC, SFWMD, DERM, L WOO, DEP and any
others, shall be included with your permit request.
14 ProvIde sealed engIneer's certificatIon in WrIting that draInage will X
conform with all rules, regulatIOns, codes, etc includmg, but not lImIted
to, Chapter 6, Article IV, SectIOn 5 of these Land Development
RegulatIOns. [LDR Chapter 4, SectIOn 7.F.2.]
Page 3
CoIltromcs, Inc
File No NWSP 98-026
BUILDING DIVISION
Comments.
15 Compliance with the bUIlding codes will be evaluated at time of permit X
review The permit fee, water and sewer facility fees, county fees and
state fees will be determined at time of permit review
PARKS AND RECREATION
Comments: None
FORESTER/ENVIRONMENT ALIST
Comments.
16 The applicant must apply for a clearing and grubbmg permit 10 reference X
to the eXisting trees.
PLANNING AND ZONING
Comments
17 Sign and seal all landscape plans. Ch. 4, Sec 7, Par C 1 X
18 In the site plan tabular data provide the following: X
- Acreage (total gross project area) Ch. 4, Sec. 7, Par E.l
19 Traffic review required to monitor/record cumulative impacts within the X
Planned Industnal Development.
20 Add breakdown (square feet) of all uses proposed within the bUlldmg X
(show 10 tabular form).
21 Provide wntten venficatIon that the Quantum Park Architectural ReView X
Board has reviewed and approved the plans.
ADDITIONAL PLANNING AND DEVELOPMENT BOARD CONDITIONS
22. None X
ADDITIONAL CITY COMMISSION CONDITIONS
23 To be determmed.
J -\SHRDA T A \Planning\SHARED\ WP\PROJECTS\CoiltronicsINWSP\cond. of appr 2nd review.doc
/bme
EXHIBIT "C"
CondItions of Approval
Project name CoiltronIcs, Inc
File number' NWSP 98-026
Reference The plans consIst of 11 sheets IdentIfied as 2nd RevIew. New SIte Plan. File # NWSP 98-026
with a Februarv 2. 1999 Plannmg and ZOnIng Department date stamp marking.
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS
Comments.
1 Waste removal in connectIon WIth construction process must be serviced
by CIty of Boynton Beach. Place note on plan to mdIcate same.
2 Dumpster enclosure must be mmImum 10 feet by 10 feet internally
dImenSIOned.
3 Pave small area on north side of enclosure to enable space for gate to
swmg clear of openIng.
UTILITIES
Comments.
4 All utIlItIes easements shall be shown on the rectIfied landscapmg
draw lOgs so that we may determme whIch trees may interfere WIth
utIlitIes. In general, palm trees will be the only tree species allowed
wlthm utIlIty easements. Canopy trees may be planted outSIde of the
easement so that roots and branches wIll not Impact those utilitIes wlthm
the easement 10 the foreseeable future. LDR Sec 7 5-18.1 gIves public
utilIties the authonty to remove any trees that mterfere WIth utilIty
services, eIther 10 utility easements or public nghts-of-way There
appears to be a direct conflict between a canopy tree and the fire hydrant
at the termmus of the water malO.
5 Department of HRS permIts WIll be reqUIred for the water system
serving thIS project. (Sec 26-12)
6 Fire flow calculations will be required demonstrating the City Code
reqUIrement of 1500 g.p.m. as stated 10 LDR Chap 6, Art. , Sec. 16, or
the reqUIrement Imposed by msurance underwnters, whichever IS
greater (See Sec 26-16(a)). Please submIt these calculatIons with your
HRS permIt submIttal.
7 Sec. 26-34(E) of the CIty Code reqUIres that a capaCIty reservatIon fee be
paId for thIS project either upon the UtilItIes Department request for
SIgnature on the Health Dept. applIcation forms or WIthin 30 days of site
plan approval, whIchever occurs first. Based upon a 2-inch meter, the fee
Page 2
Coiltromcs, Inc
File No NWSP 98-026
DEPARTMENTS INCLUDE REJECT
is $2,106 72.
8 Comp Plan polIcy 3C.3 4 reqUIres the conservation of potable water
City water may, therefore, not be used for lITIgation where other sources
area readily avaIlable
9 Provide an engmeer's wntten certification that dramage will conform
with all rules of the City and the South Florida Water Management
District. (LDR Chap 4, Sec 7F)
10 This office will not reqUIre surety for installatIOn of the water and sewer
utIlities, on condition that the systems be fully completed, and given to
the City before the first permanent meter IS set. Note that settmg of a
permanent water meter IS a prereqUIsite to obtammg the certificate of
occupancy
11 A buildmg permit for thiS project shall not be Issued untIl this office has
approved the plans for the water and/or sewer Improvements required to
serve the project. (Sec. 26-15)
FIRE
Comments
12 ProVide mlmmum 5 foot clearance between hydrantsIFire Department
connectIOns and vegetatIOn.
POLICE
Comments. None
ENGINEERING DIVISION
Comments.
13 All plans submitted for speCific permits shall meet the City'S code
requirements at time of applIcation. These permits mclude, but are not
lImited to the followmg: site lIghtmg, pavmg, dramage, curbmg,
landscapmg and lITIgation. Permits required from other permitting
agencies, such as FDOT, PBC, SFWMD, DERM, L WDD, DEP and any
others, shall be mcluded with your permit request.
14 Provide sealed engineer's certification in wnting that drainage will
conform with all rules, regulations, codes, etc. mcludmg, but not lImited
to, Chapter 6, Article IV, Section 5 of these Land Development
Regulations. [LDR Chapter 4, SectIOn 7.F.2.]
Page 3
Coiltronics, Inc
File No NWSP 98-026
BUILDING DIVISION
Comments.
15 ComplIance wIth the bUlldmg codes wIll be evaluated at tIme of permIt
reVIew The permIt fee, water and sewer facility fees, county fees and
state fees wIll be determmed at time of permIt review
PARKS AND RECREATION
Comments None
FORESTER/ENVIRONMENT ALIST
Comments.
16 The applIcant must apply for a cleanng and grubbing permit in reference
to the existmg trees.
PLANNING AND ZONING
Comments
17 SIgn and seal all landscape plans. Ch. 4, Sec. 7, Par C 1
18 In the SIte plan tabular data proVIde the followmg:
- Acreage (total gross project area) Ch. 4, Sec. 7, Par E.l
19 Traffic reVIew reqUIred to momtor/record cumulatIve impacts withm the
Planned Industrial Development.
ADDITIONAL PLANNING AND DEVELOPMENT BOARD CONDITIONS
20 To be determmed.
ADDITIONAL CITY COMMISSION CONDITIONS
21 To be determmed.
J '\SHRDA T A \Planning\SHARED\ WP\PROJECTS\Coiltronics\NWSP\cond. of appr 2nd review.doc
/bme
6--bJc.'hr (~/,..c~
fYL..-s tc \
0/02 /7r
/Va -Ie .~"x VI- f~ ~ c7(' 1'- 4<- ~~, v;C:-<.,.
15t REVIEW COMMENTS
PrOject name COIltromc5, Inc
File number- NWSP 98-026
Reference The plans consIst of 11 sheets IdentIfied as 1 st ReVIew. New Site Plan. FIle # NWSP 98-026 wIth a
December 22. 1998 Planning and Zoning Department date stamp marking.
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS
.Y<i.. os "f'<=- G"'-{V">C" ....( .", <. c:.-..- V"'"". '(->c.v'\. {.J ,-~ n_ sfr.... c h~ IF" =5 (Y\ ~ ~ r- .(;,
Comments. ~Jv ~<:L- b7 c;f1 cJ /3c,,"l"f-v. K=<- t... p~~ //.h ~ j'> fc.-",,- *- ,.' ~~ =- Jf- oS 0. ~(
....D ~cv-r""~ ':::/'C(..,,,c.-(":' VV'-...,,<- &- Ie:." "" Ir.r i",-(-='(f\...(l.,. cC~ ~c ,,~J.2 _
1 r. > ,p.,/f dl.=., ~ rk. ..{' p>,.,."",~", . L.{:. r QC:~+c... -rl- So,J, r!",~
. '.....\I'c. (._,c::..._ <..'^ -So. c- r. c:",c.(..,,-~_. ~ =('.C;" (/_.5''''''<-<:'' '.
1 ,., v c
UTILITIES
Comments
i' All utilItIes easements shall be shown on the rectIfied landscapmg
V drawmgs so that we may determme whIch trees may mterfere WIth
utIlIties. In general, palm trees wIll be the only tree specIes allowed
wlthm utIlIty easements. Canopy trees may be planted outsIde of the
easement so that roots and branches wIll not Impact those utIlItIes WIthin
the easement m the foreseeable future LDR Sec. 7.5-18 1 gIves public
utIlItIes the authority to remove any trees that interfere WIth utility
services, eIther In utIlIty easements or publtc nghts-of-way There
appears to be a dIrect conflict between a canopy tree and the fire hydrant
at the ternunus of the water main.
(i) Dept. of HRS permIts WIll be reqUIred for the water system servmg thIs
proJect. (Sec. 26-12)
U FIre flow calculations WIll be reqUIred demonstrating the CIty Code
reqUIrement of 1500 g.p.m as stated m LDR Chap. 6, Art. , Sec. 16, or
the reqUIrement Imposed by Insurance underwnters, whichever IS
greater (See Sec. 26-16(a)). Please submIt these calculatIons WIth your
HRS permit submIttal.
(1; Sec. 26-34(E) of the CIty Code requires that a capacIty reservatIOn fee be
paId for thIs project eIther upon the UtIlItIes Department request for
signature on the Health Dept. application forms or wlthm 30 days of sIte
plan approval, whIchever occurs first. Based upon a 2-inch meter, the fee
is $2,10672.
(0 Comp Plan policy 3C.3 4 reqUIres the conservation of potable water
City water may, therefore, not be used for irrigatIon where other sources
area readily avaIlable.
,1) PrOVIde an engmeer's wntten certificatIOn that dramage will conform
~-
d-c.,.. cf
~. '1'
Page 2
File Name Coiltronlcs, Inc
File No NWSP 98-026
I DEPARTMENTS I INCLUDE I REJECT I
wIth all rules of the CIty and the South FlorIda Water Management
DIstnct. (LDR Chap 4, Sec 7F)
I \ ThIs office wIll not reqUIre surety for mstallatIOn of the water and sewer
~
utilIties, on condItion that the systems be fully completed, and gIven to
the City before the first permanent meter IS set. Note that settmg of a
permanent water meter IS a prereqUIsIte to obtammg the certIficate of
occupancy
-
J>) A bUIldmg permIt for thIS project shall not be issued until thIS office has
approved the plans for the water and/or sewer improvements required to
serve the project. (Sec 26-15)
~ The waste stream from any manufactunng process must meet the city's
pretreatment reqUirements. A samplIng po lOt must be provIded to allow
momtorIng of thIS waste stream (Sec 26-143,26-147)
/ To mamtam potable water qualIty 10 the plpmg system, please extend the
water malO 10 the rear of the buildmg to the south property line, to enable
future loopmg through the adjacent parcel.
FIRE j:-, ,<.-f /r p- u,.. Fe-- -f(e>"
Vle.~ . 1}g..r,-okc:. in' '" 1fY",,,",,,,," 5 c./.,.<uO~-'" C ~ ~ c- -ft.,= "^ ~y ( 17 ~-nfJ 1F.,., ~\J~y~ ~*
Comments. 1
/ Location of the fire department connection for fire sprmklers must be
shown, BBCC 9-6 A fire flow test IS reqUIred.
POLICE
Comments: None
ENGINEERING DIVISION
Comments.
~
(!V All plans submItted for speCIfic permIts shall meet the city's code
requirements at time of applIcatIOn. These permits include, but are not
limited to the followmg: SIte lightmg, pavmg, dramage, curbmg,
landscapmg and lITigatIOn. Permits required from other permitting
agencies, such as FDOT, PBC, SFWMD, DERM, L WOD, DEP and any
others, shall be included WIth your permit request.
14') Provide sealed engmeer's certIficatIOn 10 wrIting that drainage will
V conform WIth all rules, regulations, codes, etc. mcluding, but not limited
to, Chapter 6, Article IV, Section 5 of these Land Development
Page 3
FIle Name CoIltronIcs, Inc
FIle No NWSP 98-026
I DEPARTMENTS I INCLUDE I REJECT I
RegulatIOns. [LDR Chapter 4, SectIOn 7.F.2 ]
/ On the "parkmg space" detaIl, show a 5 foot by 5 foot level landing at
the end of the 5 foot handIcap access aIsle wIth the appropnate ramps up
and down wlthm the sIdewalk. Curb ramps must be located outsIde of
access aIsles per 4 7 of the Flonda AccessibIlity Code. Correct sIte plan
accordmgly
/' On the sIte plan, extend the parkmg space stnpes from 15 feet to 18 feet
wlthm the "Island" parkmg areas.
7 Correct the accessibIlIty route from the sIdewalk to the bui1dmg on the
landscape plan to agree wIth the site and pavmg and drainage plans.
V Obtam vanance for relIef from mInImum dIstance between driveways as
specIfied m LDR Chapter 6, Article IV, SectIon I.B
V Correct the "SIgn Tnangle Note" to read "SIght Triangle" And correct
spelling the word "sIte"
BUILDING DIVISION
Comments
~ Change the ratIO of the sIde slopes of the ramp that IS Illustrated m the
detaIl drawmg tItled Parkmg Space. To be in complIance wIth the
accessibIlIty code, the sIde slope shall reflect as 1 12 ratIo rather than
1 10
V IndIcate on the site plan, wIthm the area of the buildmg, the proposed
finIsh floor elevatIon. The finIsh floor elevation shall not be less than six
inches above the crown of the abuttmg nght-of-way Also, provide a
copy of the South Flonda Water Management District permit that
venfies the proposed finIsh floor elevatIOn IS m compliance wIth the
mmlmum standards of the permIt.
~ The accessible route between the parkmg spaces and the buildmg
entrance, depicted on the drawing titled Water, Sewer, Paving, Gradmg
and Dramage plan, appears to have ramps and the same route shown on
the sIte plan does not. Correct the inconSIstency
Y To venfy that the accessible route between the parking spaces and the
building entrance is m complIance wIth the accessibility code, add the
followmg information to the site plan drawing:
a. IdentIfy the finish elevation of the sidewalk area on the outside of
Page 4
File Name Coiltronlcs, Inc
File No NWSP 98-026
I DEPARTMENTS
the bUildIng at the accessible entrance
b Identify the finish elevatIOn of the sidewalk at the pOInt where the
sidewalk and each accessible parkIng space access aisle abut each
other
c If the elevatIOn at the entrance and the elevatIOn at the access
aisles are different, show with detail draWIngs how the transitIOn
In elevatIOn will be accomplished. The method of transitIOn
Illustrated on the site plan shall comply with the accessibility
code
d. Show on the site plan that the finish elevatIOn of each accessible
parking space access aisle is the same elevation as the sIdewalk at
the pOint where they connect.
e. If the accessible route reqUires the installatIOn of ramps and/or
handraIls, provIde detail drawings of both. The slope, cross slope
and length of ramps shall be shown and identified, including
labeling, dimenSIOning and Identifying the elevatIOn of the
reqUired landings. Where handrails are applicable, provide
detailed and dimensioned drawings that specify height, shape and
locatIOn.
f Identify the cross slope of the sidewalk that abuts the accessible
parking spaces. Also, Identify the slope and cross slope of the
sidewalk area that IS located at the accessible entrance to the
bUilding.
g. All aspects of the accessible route shall comply with the
regulatIOns specified In the Florida Accessibility Code for
Building ConstructIOn, Section 4.3, Accessible Route and SectIOn
4 6, Parking and Passenger Loading Zones.
~)
/'
Compliance WIth the bUilding codes will be evaluated at time of permit
review The permit fee, water and sewer facility fees, county fees and
state fees WIll be determined at time of permit reVIew
The follOWing comment IS for informatIOnal purposes only and will be
reqUIred at time of permIt reVIew To property reVIew the project for
compliance WIth the applicable codes and to determine the appropriate
fees that Will be accessed at the time of building permit, add to the site
plan and/or floor plan drawing the below listed data. The efficiency of
the permit review would be increased If the data would be provided In
tabular form.
a. Describe the primary use of the facility
b Identify the accessory use(s).
c. IndIcate the gross floor area of the primary use.
d. Identify the total gross floor area of each level of the building.
I INCLUDE I REJECT I
Page 5
FIle Name CoIltromcs, Inc
FIle No NWSP 98-026
I DEPARTMENTS I INCLUDE I REJECT I
e IdentIfy the total gross floor area of each level of the building.
f IdentIfy the total gross floor area of all levels of the bUIldmg.
The gross floor area shall be computed as defined m the
Standard BUilding Code
g. Identify the overall heIght of the facIlity The overall heIght of
the bUIldmg shall be determmed consIstent WIth the
specIficatIOns Identified m the Standard BUIldmg Code
h. Identify the overall heIght of the facIlity The overall heIght of
the buIldmg shall be determmed consistent wIth the
specIficatIOns IdentIfied m the Standard Buildmg Code.
t. IdentIfy the type of construction that the bUIldmg is designed to
comply wIth. If the bUIldmg is desIgned as a mixed occupancy,
Identify each occupancy clasSIfication. The speCIficatIOns
Identified in the Standard BUIldmg Code.
PARKS AND RECREATION
Comments(None' =::;
FORESTER/ENVIRONMENT ALIST
Comments
/' The applicant should mdIcate on the landscape plans, If any of the 13
eXIstmg trees on the sIte WIll be preserved, relocated or removed!
replaced above the code reqUired trees
@) The applicant must apply for a clearIng and grubbing permIt in reference
to the existmg trees.
PLANNING AND ZONING
Comments
,/ Label areas whIch are to be planted wIth sod. Provide a descriptIOn of
the type of sod to be used and the square footage reqUired in the plant list
on page L- 2 Ch. 4, Sec. 7, Par C 1
29 SIgn and seal all landscape plans. Ch. 4, Sec. 7, Par C 1
30 In the SIte plan tabular data prOVIde the following:
- Acreage (total gross project area) Ch. 4, Sec. 7, Par E.1
vte U~
!bme' 1/<... fie '(? f': ;<tv
s:lprojectslcond of appr\
~ 1'~Y1-t'~
rLtc- '-.~J
~ ~ 1l?<K\>~r/ C VyY)c.. {r---f uc / flJP<t':~ (Yr.f4 ^
r~cc-...{J
fnd.Ls -fn';-t ~~,
COt L.llZ-o \J. \C-S !AUL-lTr
~~
f,U:>6, . WA 1;:.'5. l 'S (.;.1- ~
lo 2..::: · <.~ F t C-C. '?..D I ~ 2..- 'L If::' /w;.
"1~ ~ l4
_~~____ ~-\Q,)~ l6.~.:2...... O. .. !e~
rt z. z.. ' <;;f~ 1- 1Z-EQ..0 t ru=.o
f F~.i.)'''\Ol7-D I 5 l
/-- . --.-- -
oj-L--
'* 6;lkrL,a",llL "';;0
__:~ eV./_n.. t2J2\M?-L~_
· __c...::~~.> ~4'1'fl~ ..Cg.~~4"\IQ'\l....:.c) _~ ...._.._____..
- LL.?L..;1be. _~ ~E:...O ~~J r ~..:r c~O~~
I f'J ~iJi3 D~l.,..E:_..L_
APPLICATION TRACKING LOG
PROJECT TITLE: Coiltronics, Inc. FILE N: NWSP 98-026
PROJECT LOCATION: Quantum Park
TYPE OF APPLICATION: New Site Plan
PUBLIC NOTICE REQUIRED: (YIN) 0 REVIEWER'S NAME
AGENT David Goldfarb ADDRESS:
AGENT PHONE: (954)344-9855 FAX:
DATE REC'D: AMOUNT
RECEIPT NO
t 2 SETS OF PRE-ASSEMBLED PLANS SUBMITTED FOR REVIEW:
2 OF t 2 SETS SIGNED AND SEALED 0
SURVEY 0
LANDSCAPE PLAN 0
FLOOR PLAN 0
SITE PLAN WITH SITE DATA 0
APPLICATION/SUBMITTAL: DATE ACCEPTED:
DRAINAGE PLAN
ELEVATION VIEW DRAWINGS
COLORED ELEVATIONS RECEIVED
MATERIAL SAMPLES RECEIVED
PHOTOGRAPHS RECEIVED
o
o
o
o
o
DATE DENIED:
DATE OF SUBMITTAL ACCEPTANCE LETTER:
DATE OF LETTER TO APPLICANT IDENTIFYING SUBMISSION DEFICIENCIES:
I RETURN DATE: tit 3/99
I INITIAL 1 ST REVIEW MEMO: DATE SENT I MEMO NO. 98-348
t ST REVIEW COMMENTS RECEIVED
DATE OF LETTER SENT TO SENT TO APPLICANT IDENTIFYING TRC REVIEW COMMENTS:
90 DAY CALENDAR DATE WHEN APPLICATION BECOMES NULL AND VOID:
DATE t 2 COMPLETE (ASSEMBLED) SETS OF AMENDED PLANS SUBMITTED FOR 2ND REVIEW
PRE-ASSEMBLED PLANS SUBMITTED FOR REVIEW:
UTIL.
PW
PARKS
FIRE
POLICE
PLANNING
BLDG
ENGR
FORESTER
AMENDED APPLICATION 0
2 OF12 SETS SIGNED AND SEALED 0
SURVEY 0
LANDSCAPE PLAN 0
FLOOR PLAN 0
SITE PLAN WITH SITE DATA 0
2ND REVIEW MEMO: DATE SENT
PLANS MEMON
o
o
o
DATE
DRAINAGE PLAN
ELEVATION VIEW DRAWINGS
COLORED ELEVATIONS RECEIVED
MATERIAL SAMPLES RECEIVED
TRANSPARENCY RECEIVED
PHOTOGRAPHS RECEIVED
o
o
o
o
o
o
MEMO NO
RETURN DATE:
2nd REVIEW COMMENTS RECEIVED
PLANS MEMON DATE PLANS MEMON DATE
UTIL. 0 PLANNING 0
PW 0 BLDG 0
PARKS 0 ENGR 0
FIRE 0 FORESTER 0
POLICE 0
BOARD MEETING DATE:
BOARD:
LAND DEVELOPMENT SIGNS PLACED AT THE PROPERTY DATE SENT / SIGNS INSTALLED:
DATE:
CITY COMMISSION: DATE:
DEVELOPMENT ORDER RECEIVED FROM CITY CLERK: 0 DATE:
DEVELOPMENT ORDER SENT TO APPLICANT 0 DATE:
S:\FORMS\TRACKING LOG FORM
revised 4/25/97
~@~n~rml.
DEe 301998 !~I
I .
!
J
PLANr~ING ~D
lON!NG DEPT.
LEISURE SERVICES. PARKS MEMORANDUM
roo
I
I
!
TO
Michael Rumpf, Planmng and Zomng Manager
RE
John Wildner, Parks supenntendei
Quantum Park, Lot 15
FROM.
DATE
December 30 1998
The LeIsure ServIces Department, Parks DIvIsIon, has receIved the sIte plan for Quantum
Park, Lot 15 There are no recreatIon-related comments The plan may contmue through
the normal reVIew process.
JWad
FIRE & LIFE SAFETY DIVISION
Memorandum No 98-428
NFPA Life Safety Code 101, National Fire Code 1, all applicable National Fire
Protection Association codes, and the City Fire code shall be adhered to
TO Mike Rumpf, Act. Director
Planning & Zoning Division
FROM Steve Gale, Fire Marshal L~
Deputy Chief - Fire Rescue o;;ch?ment
SUBJECT Coiltronics, Inc
Quantum Park, Lot 15
NWSP 98-026
rr~-r~
1 \ 0 \ or
I .{ \
\In)l JAN
\;,.., d _ .~________
'D
.---.-~~.=-22J..
DATE December 30, 1998
. ""J, rm
4 i~
----'
Location of the fire department connection for fire sprinklers must be shown,
BBCC 9-6 A fire flow test is required
CC File
RECREATION & PARK MEMORANDUM
TO
Mike Rumpf, Actmg DIrector of Planmng and Zomng
/~ U.
Kevm John Hallahan, Forester/EnvlronmentalIst /'-(; /1
FROM.
Re:
Coiltronics- Quantum Park, Lot 15
New Site Plan - 1st Review
DATE
January 4, 1999
The apphcant should mdlcate on the landscape plans, If any of the 13 eXlstmg trees on the sIte
WIll be preserved, relocated or removed / replaced above the code reqUIred trees
The applIcant must apply for a cleanng and grubbmg permIt m reference to the eXlstmg trees.
The project should contmue III the normal reVIew process
KJh
FIle
~rJL@~~ U \If ~7m
i JAN 4. ! I; f,
..J[
~--i !
'J
U
cn Y OF BOYNTON BEACH, FLORIDA
INTER-OFFICE MEMORANDUM
FROM
Ofc ~~
DATE 010599
SUBJECT C011tromcs Inc
REFERENCES PZ 98-348
ENCLOSURES
FILE
NWSP 98-026
TO
MIchael Rumpf
I have no comments In reference to thIS pro] ect at thIS tIme
ill ~ : ~ ~ I: ~ 100
PLANNING AND
ZONING DEPT.
DEPARTMENT OF DEVELOPMENT
MEMORANDUM NO. ENG 99-005
rnrn
rn~w~r'"'
.,28 IW
TO
Michael Rumpf, Actmg Planrung and Zonmg AdmmIstrator
Raymond F DavIdson, P.E., Actmg CIty EngI~~
Vr~
January 11, 1999
FROM
DATE
RE
COIL TRONICS, INC. QUANTUM PARK, LOT 15 - (NWSP 98-026)
NEW SITE PLAN 1sT REVIEW COMMENTS
We have revIewed the subject plans and offer the followmg comments that should be addressed pnor
to the project bemg forwarded for Board reVIew'
Engineering Division (Site Specific Comments) - SebastIan Puda & Ken Hall 561-742-6280
1 All plans submItted for specIfic permIts shall meet the CIty'S code reqUIrements at tIme of
apphcatIOn. These permIts mclude, but are not hmIted to the followmg SIte hghtmg, pavmg,
dramage, curbmg, landscapmg and ImgatIOn. PermIts reqUIred from other permIttmg agencIes,
such as FDOT, PBC, SFWMD, DERM, LWDD, DEP and any others, shall be mcluded with your
permIt request.
2 ProvIde sealed engmeer's certIficatIOn m wnting that dramage will conform with all rules,
regulatIOns, codes etc. mcludmg, but not hmIted to, Chapter 6 ArtIcle IV, SectIOn 5 of these Land
Development RegulatIOns. [LDR Chapter 4, SectIOn 7.F.2.]
3 On the "parkmg space" detail, show a 5' x 5' levellandmg at the end of the 5' handIcap access
aIsle WIth the appropnate ramps up and down WIthm the SIdewalk. Curb ramps must be located
outsIde of access aIsles per 4 7 of the Flonda Accessibihty Code. Correct SIte plan accordmgly
4 On the SIte plan, extend the parkmg space stnpes from 15' to 18' WIthm the "island" parkmg areas.
5 Correct the accessibIhty route from the SIdewalk to the bUIldmg on the landscape plan to agree
WIth the SIte and pavmg & dramage plans.
6 Obtam varIance for rehef from mmImum dIstance between driveways as specified m LDR
Chapter 6, ArtIcle IV, Section I.B
7 Correct the "SIgn Tnangle Note" to read "SIght Tnangle" and correct spellIng the word "SIte"
RD/SP/KH.ck
Xc Bulent Kastarlak
SebastIan Puda
Ken Hall
C'\My Documents\Coiltronics, Inc. Quantum Park. Lot 15, New Site Plan 1st Review.doc
ill
o WI ~
... 28
@
DEPARTMENT OF DEVELOPMENT
MEMORANDUM NO BD 99-014
RE
Michael Rumpf, Actmg Planmng and Zomng Admmlstrator ~
MIchael E. Haag, BUIldmg Code PermIt Admmlstrato{~\~
January 11, 1999 \J
Coiltronics Facility - New Site Plan (NWSP 98-026) 1 st review comments
TO
FROM
DATE
We have revIewed the subject plans and offer the followmg comments that should be addressed
pnor to the project bemg forwarded for Board reVIew'
Buildin~ Division (site specific and permit comments) - MIchael E Haag (561) 742-6352
1 Change the ratIO of the SIde slopes of the ramp that IS Illustrated m the detail drawmg tItled
Parkmg Space To be m comphance WIth the accessiblhty code, the SIde slope shall reflect as
1 12 ratIO rather than 1 10
2 IndIcate on the SIte plan, wlthm the area of the bUIldmg, the proposed fimsh floor elevatIOn.
The fimsh floor elevatIOn shall not be less than SIX mches above the crown of the abuttmg
nght-of-way Also, proVIde a copy of the South Flonda Water Management Dlstnct permIt
that venfies the proposed fimsh floor elevatIOn IS m comphance WIth the mlmmum standards
of the permIt.
3 The accessible route between the parkmg spaces and the bUIldmg entrance, depIcted on the
drawmg tItled Water, Sewer, Pavmg, Gradmg and Dramage plan, appears to have ramps and
the same route shown on the SIte plan does not. Correct the mconslstency
4 To venfy that the accessible route between the parkmg spaces and the bUIldmg entrance IS m
comphance WIth the accessiblhty code, add the followmg mformatIOn to the site plan
drawmg:
a. IdentIfy the fimsh elevatIOn of the SIdewalk area on the outSIde of the bUIldmg at the
accessible entrance
b IdentIfy the fimsh elevatIOn of the SIdewalk at the pomt where the SIdewalk and each
accessible parkmg space access aisle abut each other
c If the elevatIOn at the entrance and the elevatIOn at the access aIsles are dIfferent, show
WIth detail drawmgs how the tranSItIOn m elevatIOn WIll be accomphshed. The method of
tranSItIon Illustrated on the SIte plan shall comply WIth the accessiblhty code
d. Show on the SIte plan that the fimsh elevatIOn of each accessible parkmg space access
aIsle IS the same elevatIOn as the SIdewalk at the pomt where they connect.
Memorandum No BD 99-014 to MIchael Rumpf
RE COlltromcs FacIlIty
January 11, 1999
Page Two
e. If the accessible route reqUIres the mstallatIon of ramps and/or handrails, provIde detail
drawmgs of both. The slope, cross slope and length of ramps shall be shown and
IdentIfied, mcludmg labelmg, dlmensIOnmg and IdentIfymg the elevatIOn of the reqUIred
landmgs Where handrails are applIcable, provIde detailed and dImenSIOned drawmgs
that specIfy heIght, shape and locatIOn.
f. IdentIfy the cross slope of the sIdewalk that abuts the accessible parkmg spaces. Also,
IdentIfy the slope and cross slope of the sIdewalk area that IS located at the accessible
entrance to the bUIldmg.
g. All aspects of the accessible route shall comply WIth the regulatIOns speCIfied m the
Flonda AccessibIlIty Code for BUIldmg ConstructIOn, SectIOn 43, Accessible Route and
SectIOn 4 6, Parkmg and Passenger Loadmg Zones
5 ComplIance WIth the bUIldmg codes wIll be evaluated at tIme ofpenmt reVIew The permIt
fee, water and sewer faCIlIty fees, county fees and state fees wIll be determmed at tIme of
permIt reVIew
6 The followmg comment IS for mformatIOnal purposes only and wIll be reqUIred at tIme of
permIt reVIew To properly reVIew the project for complIance WIth the applIcable codes and
to determme the appropnate fees that wIll be assessed at the tIme ofbUIldmg permIt, add to
the SIte plan and/or floor plan drawmg the below lIsted data. The effiCIency of the permIt
reVIew would be mcreased If the data would be proVIded m tabular form.
a. Describe the pnmary use of the faCIlIty
b IdentIfy the accessory usee s)
c IndIcate the gross floor area of the pnmary use.
d. IndIcate the gross floor area of the accessory use(s)
e IdentIfy the total gross floor area of each level of the bUIldmg.
f. IdentIfy the total gross floor area of all levels of the bUIldmg. The gross floor area shall
be computed as defined m the Standard BUIldmg Code
g. IdentIfy the overall heIght of the faCIlIty The overall heIght ofthe bUIldmg shall be
determmed conSIstent WIth the speCIficatIOns IdentIfied m the Standard BUIldmg Code.
h. IdentIfy the type of constructIOn that the bUIldmg IS deSIgned to comply WIth. The type
of constructIOn and deSIgn of the bUIldmg shall be conSIstent WIth the speCIficatIOns
IdentIfied m the Standard BUIldmg Code
IdentIfy the occupancy claSSIficatIOn that the bUIldmg IS deSIgned to comply WIth. If the
bUIldmg IS deSIgned as a mIxed occupancy, IdentIfy each occupancy claSSIficatIOn. The
occupancy claSSIficatIOns and deSIgn of the bUIldmg shall be conSIstent WIth the
speCIficatIOns IdentIfied m the Standard BUIldmg Code
MEH.bg
XC Bulent I. Kastarlak
\\C}f,,\1AE\'\SHRDA T A \Development\Building-6870\Documents\TRC\NWSP 98-026 I st review Coiltronics Facility,doc
MEMORANDUM
UTILITIES DEPT NO 99 - 026
00
@ ~ n Wc,~]
il.
.' l!l
JIIN . 5 HI) ~ :J!
I
!
TO.
Mike Rumpf, Planning Director
PlANNING AND
ZONING DEPT.
FROM.
John A. Guidry, Utilities Director
DATE.
January 15, 1999
SUBJECT.
Coiltronics, Inc - New Site Plan 1st Review
We offer the following comments on this project.
GENERAL COMMENTS
12 All utilities easements shall be shown on the rectified landscaping drawings so that we may
determine which trees may interfere with utilities In general, palm trees will be the only tree
species allowed within utility easements Canopy trees may be planted outside of the easement so
that roots and branches will not impact those utilities within the easement in the foreseeable future
LDR Sec 7 5-18 1 gives public utilities the authority to remove any trees that interfere with utility
services, either in utility easements or public rights-of-way There aDDears to be a direct conflict
between a canODV tree and the fire hydrant at the terminus of the water main.
2) Dept. of HRS permits will be required for the water system serving this project. (Sec 26-12)
3) Fire flow calculations will be required demonstrating the City Code requirement of 1500 g p.m. as
stated in LDR chap 6, Art. , Sec 16, or the requirement imposed by insurance underwriters,
whichever is greater (see Sec 26-16(a)) Please submit these calculations with your HRS permit
submittal
4) Sec 26-34(E) of the City Code requires that a capacity reservation fee be paid for this project
either upon my request for signature on the Health Dept. application forms or within 30 days of site
plan approval, whichever occurs first. Based upon a 2-inch meter, the fee is $2,106 72
5) Comp Plan pohcy 3C.3 4 requires the conservation of potable water City water may, therefore, not
be used for irngation where other sources are readIly avaIlable
6) Provide an engineer's wntten certIficatIOn that drainage will conform with all rules of the City and
the South Flonda Water Management DIstnct. (LDR Chap 4, sec 7F)
SPECIFIC CONDITION
1) This office will not require surety for installation of the water and sewer utilities on condition that
the systems be fully completed, and given to the City before the first permanent meter is set. Note
that setting of a permanent water meter is a prerequisite to obtaining the certificate of occupancy
2) A building permit for this project shall not be issued until this office has approved the plans for the
water and/or sewer improvements required to serve the project. (Sec 26-15)
3) The waste stream from any manufacturing process must meet the City's pretreatment requirements
A sampling point must be provided to allow monitoring of this waste stream. (Sec 26-143,26-147)
4) To maintain potable water quality in the piping system, please extend the water main in the rear of
the building to the south property line, to enable future looping through the adjacent parcel
Please refer any questions on this matter to Peter Mazzella (742-6404) of this office
JAG/PVM
Xc Skip Milor
Peter Mazzella
File
~'"
.~......-......-.,....~~---,
~fl :-~ fn'1
:i i> Il
.~..,,~;?., n I'
, I 11 ,I
: i Ii r
" i U I
ilU: FEB 4 - ,U
lL-~.L\
. pu. ./" ,iG 11.NO
ZON NG DEPT.
Board of Supervisors
C Stanley Weaver
Kermit Dell
John I. Whitworth III
Secretary/Manager
William G. Winters
Assistant Manager
Ronald L. Crone
Attorney
Perry & Schone, P.A.
LAKE WORTH DRAINAGE DISTRICT
13081 MILITARY TRAIL
DELRAY BEACH, FLORIDA 33484
February 3, 1999
MIchael W Rumpf, Chairman
Planmng and Zoning DiviSIOn
CIty of Boynton Beach
Post Office Box 310
Boynton Beach, Florida 33425-0310
Re C011tromcs (Lot 15, Quantum Corporate Park, NW Quad of Gateway Blvd. &
Quantum Blvd)
Technical Review Committee Meeting-Tuesday, February 3, 1999
Dear Mr Rumpf
This petition is located within the Lake Worth Drainage DIstnct's boundary and
wIll reqUIre permit(s) from the DIStrict prior to construction.
Should this petition reqUIre a plat, then the District will withhold permit approval
until a review of the plat has been completed to ensure that the DIstnct's nght-of-way
concerns have been addressed
Thank you for giving us the opportunity to review and comment on thIS petition.
Should you have any questIOns or concerns please contact me
Respectfully,
LAKE WORTH DRAINAGE DISTRICT
(~4L~~
Lisa A Rowland
Right-of-Way Technician
Delray Beach & Boca Raton (561) 498-5363 · Boynton Beach & West Palm Beach (561) 737 3835 · Fax (561) 495-9694
:PARTMENT OF DEVELOPMENT
MEMORANDUM NO PZ 98-348
TO
TRC MEMBERS
Bulent Kastarlak, Director of Development
Bob Borden, Assistant Fire Marshal
Kevin Hallahan, Forester/Environmentalist
Ofc. Robert Riggle, Police Department
Pete Mazzella, Utilities Department
Michael Haag, Building Division
Ken Hall, Engineering Division
AI Kim, Public Works Department
John Wildner, Parks Division
Ray Davidson, Acting City Engineer
Bob Donovan, Permit Application Group
FROM
Michael W Rumpf
Planning and Zoning Manager
DATE
December 28, 1998
RE.
SITE PLAN REVIEW PROCEDURES
1 ST Review - New Site Plan
Project - Coiltronics, Inc.
Location - Quantum Park, Lot 15
Agent David Goldfarb
File No NWSP 98-026
Permit No - 98-5178
Find attached for your review the plans and exhibits for the above-referenced project. Please review the
plans and exhibits and transmit formal written comments to me no later than 5:00 P.M. on
January 13. 1999. When preparing your comments, please separate them into two categories,
code deficiencies with code sections referenced and recommendations that you believe will
enhance the project.
Adhering to the following review guidelines will promote a comprehensive review and enable the
applicant to efficiently obtain Technical Review Committee approval'
1
Use the review standards specified in Part IV, Land Development Regulations, Site Plan Review
and the applicable code sections of the Code of Ordinances to review and formulate comments.
2.
The documents submitted for the project were determined to be substantially complete with the
exception of traffic data, however, if the data provided to meet the submittal requirements is
insufficient to properly evaluate and process the project based on the review standards or the
documents show code deficiencies additional data and/or corrections should be requested by
the reviewer by contacting Michael Rumpf
3
Each comment shall reference the section of the code that is incorrectly depicted on the
documents
Page 2
Development Department Memo PZ 98-348
Coiltronics, Inc
TO' TRC Members
4 Technical Review Committee member(s) shall identify in their comments when the plans depict or
when the location and installation of their departmental required improvements may conflict with
other departmental improvements
5 When a TRC Member finds a code deficiency that is outside of his/her review responsibility, the
comment and the specific code section may be included in their review comments with the name
of the appropriate TRC Member that is responsible for the review specified
6 If a TRC member finds the plans acceptable, he/she shall forward a memorandum, within the time
frame stated above, to me The memorandum shall state that the plans are approved and that
they do not have any comments on the plans submitted for review and that they recommend the
project be forwarded through the approval process
All comments shall be typed, addressed and transmitted to me for distribution to the applicant. Please
include the name and phone number of the reviewer on this memorandum Michael Rumpf will be the
Planning and Zoning staff member coordinating the review of the project. First review comments will be
transmitted to the applicant along with a list of Technical Review Committee (TRC) members
MWR.bme
Attachment
XC William Bingham, Fire Chief
Marshall Gage, Police Chief
John Guidry, Utilities Director
Don Johnson, Building Division
Sebastian Puda, Engineering Division
Larry Roberts, Public Works Director
Central File