REVIEW COMMENTS DEVELOPMENT DEPARTMENT PLANNING AND ZONING DIVISION MEMORANDUM NO PZ 03-228 TO Chairman and Members Community Redevelopment Agency Board THRU FROM Michael Rumpf Director of Planning and Zoning Eric Lee Johnson, AICP c,:Y Planner (j DATE September 30, 2003 PROJECT Gateway Texaco / COUS 3-007 REQUEST Conditional Use approval for a 681 square foot addition to an existing gasoline dispensing establishment PROJECT DESCRIPTION Property Owner. SUAU Enterprises, Incorporated Applicant/Agent: Mr Beril Kruger of Beril Kruger Planning & Consultants Location 2360 North Federal Highway (see Exhibit "A" - Location Map) Existing Land Use/Zoning Local Retail Commercial (LRC) / Community Commercial (C-3) Proposed Land Use/Zoning No change proposed Proposed Use 681 square foot addition to an existing gasoline dispensing establishment Acreage 0 48 acres (20,830 square feet) Adjacent Uses. North A multi-family residential property zoned Community Commercial (C-3), South Right-of-way for Las Palmas Road, and farther south are single-family attached townhouses (The Harbors), zoned Infill Planned Unit Development (IPUD), East: Vacant commercial lot (proposed car wash), zoned Community Commercial (C-3), and farther east is a single-family residential dwelling (part of Las Palmas development), zoned Single-family residential (R-1AA), and West: Rights-of-way of U.S. 1 and the Florida East Coast Railroad, farther west Gateway Texaco - COUS 03-007 Page 2 Memorandum No PZ 03-228 developed commercial property classified Local Retail Commercial (LRC) and zoned C-2 Neighborhood Commercial BACKGROUND Mr Beril Kruger of Beril Kruger Planning & Zoning Consultants, agent for SUAU Enterprises Incorporated, is requesting conditional use / major site plan modification approval to construct a 681 square foot addition to an existing gasoline dispensing establishment. In addition, the applicant is proposing new parking spaces, a new access drive / easement to facilitate internal access to an adjacent parcel, and a general "make-over" of the exterior building facades of the gasoline station building and canopy The number of gasoline pump islands and fueling positions would remain the same The subject property is a separate lot from the abutting property to the east. The proposed 681 square foot addition to the gas station is considered a conditional use in the C-3 zoning district. Also, the gas station is a legal non-conforming use because it does not comply with Chapter 2, Section 11 L.3.a (2) which requires that gas stations should be located only at intersections "consisting of roads of four (4) lanes or wider" Earlier last year, Mr Beril Kruger, acting on behalf of Mr Zuhair Marouf, expressed a desire to construct a building addition to the gas station, in part, to satisfy outstanding code enforcement violations over the use of a parked vehicle as storage space. He also proposed direct access between the subject lot and the lot directly to the east. The abutting lot to the east was earmarked for a mechanical carwash The direct access was proposed between the lots in order to minimize vehicular traffic onto Las Palmas Road These inquiries were based upon the presumption that the proposed addition would be allowed and that direct access would only require minor site plan review However, after careful consideration, staff determined that the addition would not be permitted "by right" because it would be an unlawful expansion of a non-conforming use (gasoline-dispensing establishment) and that it would exceed the threshold for a minor site plan modification To answer Mr Kruger's inquiries, on July 16, 2002, the Director of Planning & Zoning issued an administrative determination letter that basically prohibited the applicant from increasing the size of the gas station building citing Chapter 2, Sections D and G of the Land Development Regulations (non- conforming uses) Regarding the direct access between lots, the Director determined that the proposed driveway connection between the subject lot and the lot directly to the east would be permitted However, the direct access would only be allowed contingent upon the recordation of a legally binding cross-access agreement and that the entire Texaco site would have to brought into total compliance with the current Land Development Regulations. On July 31, 2002, Mr Kruger filed an appeal (ADAP 03-001) to the aforementioned administrative determination According to the staff report, "in summary, the appeal justifies the proposed expansion by the position that retail sales at this business is a separate component from the non-conforming aspect-gasoline sales, which component can therefore be altered / expanded independent of the gasoline sales element of the business. The applicant supports this position that retail sales is distinguishable from gas sales by the absence of other nearby convenience stores, and therefore, the high demand for convenience item sales at this location" Staff disagreed and recommended denial of Mr Kruger's administrative appeal based on three (3) main points. Firstly, staff argued that the Gateway Texaco - COUS 03-007 Page 3 Memorandum No. PZ 03-228 determination represented the position consistently communicated by staff and therefore, the consistent interpretation of clearly written Land Development Regulations. Secondly, the sale of gasoline is the principal use of the subject business, which is located on one parcel within a single structure, and therefore, cannot be viewed separate from accessory components such as retail sales. Lastly, the applicant did not prove that the expansion of the retail aspect of the business would have been mandatory for the continued operation of the principal use, and that if denied a hardship would have been imposed The Community Redevelopment Agency voted and concurred with staff but the City Commission voted in favor of the applicant with the condition that the expansion would be limited to 600 square feet (see Exhibit "c" - Conditions of Approval) Therefore, this major site plan modification and accompanying variance requests represents the applicant's continuing effort to construct a building addition on the subject property and a stand-alone mechanical car wash on the abutting property Staff provides both an analysis and recommendation for each variance request in their respective staff report. If approved, the construction of the addition, parking lot, and fa~ade improvements would occur in one (1) phase STANDARDS FOR EVALUATING CONDmONAL USES AND ANALYSIS Section 11.2 D of the Land Development Regulations contains the following standards to which conditional uses are required to conform Following each of these standards is the Planning and Zoning Division's evaluation of the application as it pertains to standards. The Community Redevelopment Agency and City Commission shall consider only such conditional uses as are authorized under the terms of these zoning regulations and, in connection therewith, may grant conditional uses absolutely or conditioned upon the conditions including, but not limited to, the dedication of property for streets, alleys, recreation space and sidewalks, as shall be determined necessary for the protection of the surrounding area and the citizens' general welfare, or deny conditional uses when not in harmony with the intent and purpose of this section In evaluating an application for conditional use approval, the Board and Commission shall consider the effect of the proposed use on the general health, safety and welfare of the community and make written findings certifying that satisfactory provisions have been made concerning the following standards, where applicable 1 Ingress and egress to the subject property and proposed structures thereon, with particular reference to automobile and pedestrian safety and convenience, traffic flow and control, and access in case of fire or catastrophe. No driveway openings are being altered as a result of this major site plan modification. The site plan (sheet 1 of 4) shows that there are two existing (2) ''curb drops" on North Federal Highway According to Chapter 2, Section 11.L.3.d. (1), driveway openings for gas-stations are required to be located at least 120 feet from the intersection of the right-of-way lines along streets of higher classification (North Federal Highway). According to the site plan, the northern "curb-drop" is located 102 feet from the intersection of North Federal Highway and Las Palmas Avenue. The southern "curb-drop" on North Federal Highway is located only 23 feet from the intersection of U.S. 1 and Las Palmas A venue. The proposed building addition is a major site plan modification and therefore, the entire site would have to comply with today's code. However, the applicant is not proposing to alter the driveway opening and is requesting a 97-foot variance (ZNCV 03-010) from Gateway Texaco - COUS 03-007 Page 4 Memorandum No PZ 03-228 the 120-foot requirement (see Exhibit "C" - Conditions of Approval). This single variance request would be applied to both non-conforming driveway openings. Staff supports this variance request (see Staff Report ZNCV 03-010). According to Chapter 2, Section 11.L.3.d. (3) of the Land Development Regulations, driveway openings shall not be located less than 30 feet from any interior property line. The northern driveway on North Federal Highway does not comply with this requirement because it is located only 21 feet away from the interior north side property line. Therefore, the applicant is requesting a 10-foot variance from this restriction (ZNCV 03-011). Staff supports this variance request (see Staff Report ZNCV 03-011). Also, the supplemental regulations for gas stations limit the number of driveway openings to one (1) per street frontage. The subject site has two (2) driveway openings on North Federal Highway The applicant is requesting a variance (ZNCV 03-012) from Chapter 2, Section 11.3.d(4) to allow for these two driveway openings. The Engineering Division reviewed the site plan and recommended that no closures should occur to any of the openings due to the proposed on-site traffic circulation and the anticipated completion of the Harbors townhouse project. Note direct access from the subject lot to the lot directly to the east may only occur after the recordation of a cross-access agreement (see Exhibit "C" - Conditions of Approval). Therefore, staff is recommending approval of this variance request to allow two (2) driveway openings (see Staff Report ZNCV 03-012). In any event, all three variance requests regarding the existing driveways would require review and approval by the City Commission. The site plan (sheet 1 of 4) shows an existing driveway opening is located on Las Palmas Avenue. This opening is currently located 32 feet from the intersection of the right-of-way lines and complies with the Land Development Regulations. No change is proposed to this opening. The survey shows that there is no sidewalk along Las Palmas A venue. However, according to Chapter 6, Article 111, Section 10. T of the Land Development Regulations, a sidewalk is required within this right-ot-way A sidewalk would also be required within the right-ot-way (of Las Palmas Avenue) in front of the abutting property to the east where the car wash is proposed (NWSP 03- 011). The applicant submitted an administrative waiver to this requirement but was subsequently denied by the Engineering Division. The applicant is appealing the administrative decision regarding the sidewalk requirements for both lots. 2. Off-street parking and loading areas where required, with particular attention to the items in subsection above, and the economic, glare, noise, and odor effects the conditional use will have on adjacent and nearby properties, and the city as a whole The required parking has been tabulated based on a gasoline dispensing establishment use. The ratio utilized is one (1) space for each 250 square feet of the gross floor area. Based on this methodology, the proposed expansion, coupled with the floor area of the existing building would require 10 parking spaces. The required number of parking spaces needs to be accurately shown on the site plan (sheet 1 of 4) tabular data (see Exhibit "C" - Conditions of Approval). The site plan shows that 12 parking spaces would be provided. The applicant intends to re-stripe the existing spaces and create three (3) more spaces and a drive aisle at the northeast corner of the property The backup distance behind the newly created parking spaces would adhere to current dimension standards. However, one (1) of the new parking spaces would encroach into the required 10-foot wide interior landscape buffer along the east property line. This encroachment will be discussed later in this staff report. Gateway Texaco - COUS 03-007 Page 5 Memorandum No PZ 03-228 3 Refuse and service areas, with particular reference to the items in subsection 1 and 2 above The survey shows that the dumpster is currently located one foot from the south property line at the southeast corner of the property The site plan (sheet 1 of 4) shows that the dumpster would be moved five (5) feet away from the south property line and one (1) foot - eight (8) inches from the east property line. It would be located within a dumpster enclosure as per code. It should be noted that staff would prefer to have the location of the dumpster enclosure away from the highly visible areas such as from the rights-of-way However, staff acknowledges that the current site layout (i e. building, parking space, driveway openings) limits the number of choices for its relocation. The present location facilitates the efficient removal of trash and that this efficiency could be jeopardized if located elsewhere on the site. 4 Utilities, with reference to locations, availability, and compatibility Consistent with Comprehensive Plan policies and city regulations, all utilities, including potable water and sanitary sewer are available for this project. 5 Screening, buffering and landscaping with reference to type, dimensions, and character The subject site had been previously developed as a gas station and related parking areas under former, less stringent standards for gas stations. Therefore, the existing landscape buffer areas are non-compliant. According to Chapter 2, Section 11.3.f(l) of the Land Development Regulations, a ten (10) foot wide landscape buffer is required along both North Federal Highway and Las Palmas A venue. The buffer is required to contain a tree every 30 feet. A continuous row of hedges and flowering groundcover are also required. The intent is to screen the vehicular use areas from the public rights-ot-way The landscape plan (sheet L -1) shows that no change is proposed to the driveways or parking areas. Basically, there is no landscape buffer along North Federal Highway Since 10-foot wide landscape buffers are required along rights-of-way, the applicant is requesting a variance (ZNCV 03-016) from the code to have no landscape buffer along North Federal Highway and a five (5) foot wide landscape buffer along Las Palmas Avenue (see Exhibit "C" - Conditions of Approval) As in the case with the driveway openings, since both landscape buffers are less than 10 feet in width, one (1) variance request would apply to both buffers. The justification lies in the fact that if a 10-foot variance were approved to allow for a zero (0) foot wide landscape buffer, then that same variance approval would nullify the need for a five (5) foot wide buffer Staff is recommending approval of the variance request due to the unavoidable site constraints (see Staff Report ZNCV 03- 016) However, staff is recommending approval with the stipulation that in the southern landscape buffer (along Las Palmas Avenue), the proposed row of Ixora 'Nora Grant'shrubs be 36 inches in height at the time of installation. Also, staff is recommending, where possible, additional screening be provided (i e. planters) along North Federal Highway (see Exhibit "C" - Conditions of Approval). As always, the variance request would have to be reviewed and approved by the City Commission to allow for a deviation from the Land Development Regulations. According to Chapter 2, Section 11.L.3.f (2), a landscape buffer 10 feet in width is required on along all interior property lines. The landscape plan (L-l) shows existing landscape buffers along the north and east property lines. However, the existing landscape buffer along the north property line is Gateway Texaco - COUS 03-007 Page 6 Memorandum No PZ 03-228 approximately five (5) feet in width and does not comply with the 10-foot wide buffer requirement Therefore, the applicant is requesting a variance (ZNCV 03-017) from the aforementioned Land Development Regulations to reduce the landscape buffer by five (5) feet in order to allow a five (5) foot wide landscape buffer in lieu of the required 10-foot wide landscape buffer The variance's justification and analysis is provided in the respective staff report. Staff is recommending approval of the variance request due to the existing site constraints. Again, the variance request would have to be reviewed and approved by the City Commission. The survey shows that along the north property line, the existing parking lot appears to encroach into the required north landscape buffer The existing north landscape buffer does not comply with code because it is less than 10 feet in width. Also, the plans show that a proposed angled parking space would encroach into the eastern landscape buffer The east landscape buffer complies with code. However, vehicle encroachment into landscape buffers is not permitted pursuant to Chapter 7.5, Article II, Section 3.B.4 of the Land Development Regulations. Therefore, the applicant is requesting a variance (ZNCV 03-024) from Chapter 7.5, Article II, Section 3, B. 4., to allow a parked vehicle to encroach two and one-half (2- V2) feet into the east landscape buffer The two and one (2- V2) foot encroachment assumes that the City Commission would approve the variance request for the reduction in buffer width. In both cases, staff is recommending approval of reducing the required width of the north and east landscape buffers to allow for five (5) foot wide landscape buffers (see Staff Report ZNCV 03-017). Staff supports this encroachment into the required north landscape buffer, in part, because the parking lot already exists. However, staff opposes allowing any new spaces / areas of vehicular encroachment. This would occur, by the proposed angled parking space into the east landscape buffer The project requires only 10 parking spaces, not 12 spaces and therefore, any excess parking that would be provided should comply with all aspects of the code. Simply put, the elimination of the proposed angled parking space (at the northeast corner of the property) would cancel the need for this variance. (see Exhibit "C" - Conditions of Approval). The variance would only apply to the existing conditions at the northern portion of the property As in all cases, this variance would require City Commission review and approval The north landscape buffer would contain Crape Myrtle, Dahoon Holly, and Alexander (double- trunked) palm trees. Green Buttonwood and Redtip Cocoplum hedges would be installed at the base. The east landscape buffer would contain Sabal palm trees, Green Buttonwood / Redtip Cocoplum hedges, and an existing five (5) foot high concrete wall 6 Signs, and proposed exterior lighting, with reference to glare, traffic safety, economic effect, and compatibility and harmony with adjacent and nearby properties. This conditional use application proposes wall signs on multiple facades. The elevation pages (sheets 3 and 4 of 4) show the existing wall signs with the proposed wall signage. The maximum allowable wall signage area would be based on the length of the front building fa~ade facing North Federal Highway According to Chapter 21, Article IV, Section 2. C of the Land Development Regulations, the maximum area for all wall signs shall be one and one half (1 V2) square feet of sign area for each one (1) foot of linear building frontage. The elevations do not indicate the proposed cumulative wall signage area. However, the proposed wall and canopy signage are itemized on an attached 8- V2 by 11 inch sheet. This attached sheet lacks the wall signage area in its entirety because it omits the existing / proposed signs on the north and south sides of the building. As proposed, it appears that the wall signage area would not comply with the maximum allowable Gateway Texaco - COUS 03-007 Page 7 Memorandum No PZ 03-228 signage area. Staffs goal is not to regulate the content of the sign but rather to ensure compliance with code and to maximize sign aesthetics thereby preventing project signage from degrading the developments appearance. In order to reduce the wall sign area and upgrade the overall appearance, staff recommends eliminating all non-word depictions (Texacos corporate logo which is a white-star-in-red-circle) that do not directly correspond with wording (see Exhibit "c" - Conditions of Approval). For example, staff recommends eliminating the isolated non-word depiction (shown as Sign '~" on the attached 8- V2 by 11 inch sheet) because this non-word depiction is not attached or a part of a sign containing words. Non-word depictions signs "c" and ''D'' are acceptable because Sign "c" is associated with the ''Food Mart" sign and Sign ''D'' is associated with the "Texaco" sign. Neither Sign "c" or Sign "0" appear to be isolated non-word depictions. Chapter 21, Article III, Section 5 requires all freestanding signs to be located at least 10 feet from the property lines and limits the height to 20 feet. The existing sign is currently located only five (5) feet from the property line and stands over 33 feet tall. Its on-site location is shown on the survey and site plan and its elevation is shown on the attached 8 V2 by ll-inch sheet. The applicant is proposing to add more sign area to this non-conforming structure. The pole sign is non-conforming because it exceeds the height limitations and does not meet minimum setback requirements. The structure must be setback at least 10 feet from the property line(s}. As proposed, the new "Car Wash" portion would be added to the structure. However, no existing sign area is shown on the attached sheet. Therefore, it is unclear if the proposed signage area would comply with Chapter 21, Article Ill, Section 2.8 of the Land Development Regulations. The code allows for a maximum of 64 square feet of sign area (see ExhibIt "c" - Conditions of Approval). Also, the proposed sign itself (Car Wash) appears to be advertising for the mechanical car wash facility, which is proposed on the abutting lot the east. It must be noted that the abutting lot to the east is an entirely separate lot and that no advertising for it may occur on the subject property due to the sign code restrictions regarding off-premise signage (Chapter 21, Article II, Section 3.S. of the Land Development Regulations) Also, because the gas station is a non-conforming use, a Unity of 77tle cannot combine the two (2) lots together However, if the "Carwash" wording is a component of the official business name of the gas station on which the pole sign is located, then the applicant should provide document ion for verification. Wording on the sign should graphically and accurately reflect / correspond with the official business name of the business on the subject property (see Exhibit "c" - Conditions of Approval). Since the structure is non-conforming due to it currently being located within the required setbacks, the applicant is requesting a five (5) foot variance (ZNCV 03-023) to allow the sign to be located five (5) feet from the property line rather than 10 feet as normally required by code. In this instance, staff is recommending denial of the applicants variance request (see Staff Report ZNCV 03-023). The structure can be removed, reduced in height, and relocated on the property so that it would still be highly visible from the rights-ot-way while complying with todays setback, height, and cross-visibility restrictions (see Exhibit "c" - Conditions of Approval). The variance request would require City Commission review and approval 7 Required setbacks and other open spaces. The existing building meets the setback requirements of the C- 3 zoning district. However, the proposed building addition would not meet the rear setback requirements. The required rear setback is 20 feet. The proposed building addition would encroach into the setback by 10 feet. Therefore, the applicant is requesting a 10-foot variance (ZNCV 03-013) from Chapter 2, Section 11.L.3.e.(3} to Gateway Texaco - COUS 03-007 Page 8 Memorandum No PZ 03-228 allow the addition to encroach into the required 20-foot rear setback. As previously mentioned in the Background section of this staff report, the City Commission approved the applicants Administrative Appeal (ADAP 03-001) to allow a 600 square foot addition. The size of the proposed building addition (681 square feet) is not consistent with the previous City Commission approval (600 square feet). Staff is recommending denial of this variance request (see Staff Report ZNCV 03-013). The proposed addition could be configured or reduced in such as way as to meet the setback requirements of the C- 3 zoning district and therefore, not need a variance. Since this is a major site plan modification, all structures (including the canopy and fueling pumps) are required to meet setback requirements. The existing canopy over the gas pump islands does not meet the 20-foot setback requirement. The existing pump islands do not meet the 30-foot setback requirement. The applicant is not proposing any changes to the canopy structure other than cosmetic enhancements. Therefore, the applicant is requesting a 10-V2 foot variance (ZNCV 03-14) to allow the existing canopy to be located nine and one-half (9 - V2) feet from the west property line instead of 20 feet as required by code (see Staff Report ZNCV 03-014). Also, the existing pump islands are located only 19 feet -10 inches from the west property line. Therefore, the applicant is requesting a variance (ZNCV 03-015) to also allow the gas pump islands to be located closer to the west property line rather than the 30 feet required by code (see Exhibit "c" - Conditions of Approval). Again, staff is recommending approval of both variance requests. As always, they would require City Commission review and approval. 8 General compatibility with adjacent property and other property in the zoning district. The proposed use is a conditional use in the C- 3 zoning district. Although auto-intensive in nature, the use is generally compatible with the use of the abutting property to the north. The property directly to the east is vacant and zoned C- 3. This vacant lot is earmarked for a mechanical car wash. Car washes are typically accessory uses to gas stations so therefore, a gas station use would be compatible with the anticipated use of the abutting property to the east. The property south of Las Palmas A venue was previously zoned C- 3, the same as the subject property However, it was recently rezoned from C-3 to Infill Planned Unit Development (IPUD) for the construction of over 50 fee-simple townhouses. Unless properly buffered, a gas station use could be incompatible with a residential use. Buffering would include extra landscaping or a buffer wall. The existing gas station is separated from the townhouse project by Las Palmas A venue and a proposed five (5) foot wide landscape buffer A gas station is a compatible use with other uses in the C-3 zoning district. The proposed building expansion (for extra storage area) would be compatible with both commercial and residential uses. The proposed building colors would be compatible with the existing and proposed buildings within the immediate area. The elevations indicate the proposed colors to be dark green (Benjamin Moore - Chrome Green), white (Benjamin Moore - Brilliant White), and gray (Benjamin Moore - San Antonio Gray). These are the corporate Texaco colors and are recognized nationwide. 9 Height of building and structures, with reference to compatibility and harmony to adjacent and nearby properties, and the city as a whole The maximum allowable height for the C-3 zoning district is 45 feet. The existing building was designed as a one (1)-story structure. The top of the existing canopy is 16 feet - nine (9) inches in Gateway Texaco - COUS 03-007 Page 9 Memorandum No PZ 03-228 height. The elevations show that a "custom clad metal framed decorative element" is proposed at 20 feet - six (6) inches in height. The building and canopy are well below the maximum height limitation and are compatible with the surrounding properties. However, the non-conforming freestanding pole sign would be incompatible with all signs in the C-3 zoning district and neighboring properties. 10 Economic effects on adjacent and nearby properties, and the city as a whole. The existing gas station represents one (1) of two (2) Texaco stations throughout the City Of Boynton Beach. The other Texaco station is located at 645 West Boynton Beach Boulevard. The nearest gas station to the subject property would either be the Mobil gas station, located on the southwest corner of Gateway Boulevard and High Ridge Road or the Citgo gas station, located at the southwest corner of Boynton Beach Boulevard and Federal Highway Therefore, the subject gas station represents additional convenience and choice for the City residents, which is not offered elsewhere in this area of the city The applicant states that "there are no detrimental economic effects on adjacent and nearby properties and the city as a whole" 11 Conformance to the standards and requirements which apply to site plans, as set forth in Chapter 19, Article II of the City of Boynton Beach Code of Ordinances. (Part III Chapter 4 Site Plan Review) The existing use and site is non-conforming in many ways. If all requested variances are approved and all staff comments are addressed, the proposed project would comply with all requirements of applicable sections of the city code. However, staff is recommending denial of two (2) of the 10 requested variances and that these aspects of the site be retrofitted to comply with city regulations. 12. Compliance with, and abatement of nuisances and hazards in accordance with the performance standards within Section 4 N of the Land Development Regulations, Chapter 2, also, conformance to the City of Boynton Beach noise Control Ordinance With incorporation of all conditions and staff recommendations contained herein, the proposed storage addition to the existing gas-station would operate in a manner that is in compliance with the above-referenced codes and ordinances of the City of Boynton Beach. RECOMMENDATION The City Commission approved the applicant's Administrative Appeal (ADAP 03-001) to allow a 600 square foot storage addition to the existing gas station The existing use (gas sales) and site is non- conforming The building addition represents a major site plan modification, which requires that the entire site be brought into compliance with current code However, the applicant is only proposing to expand the building area to accommodate the extra storage area and has no intention of improving the remaining portion of the site to bring it into compliance with today's standards, which would also be cost prohibitive or even impossible due to site constraints. To remedy the situation, the applicant is requesting 10 variances that address the non-conforming aspects of the subject site However, the proposed area of the addition is not consistent with the area that was conceptually approved by the City Commission Furthermore, the proposed expansion itself does not comply with the Gateway Texaco COUS 03-007 Page 10 Memorandum No PZ 03-228 setback requirements of the C-3 zoning district. This is a situation where staff concurs with the applicant's justification for eight (8) of the 10 variances requested that are directly related to existing non-conforming aspects of the site. However, staff is recommending denial of two (2) of the 10 requested variances that specifically pertain to the new or proposed improvements (i e building addition, new sign area) that could, in staffs' opinion, be built to comply with the current code. Also, staff is recommending specific conditions be applied to two (2) of the other variance requests that specifically deal with buffering the subject site from the adjacent properties (i e vehicular encroachment into buffer, potted plants, if possible, along North Federal Highway) Therefore, based on the discussion herein, staff recommends approval of the project contingent upon satisfying all the conditions of approval Any additional conditions by the Community Redevelopment Agency or the City Commission would be placed in Exhibit "C" - Conditions of Approval Pursuant to Chapter 2 - Zoning, Section 11.2 Conditional Uses, a time limit would be required for project development. Staff recommends a period of one (1) year be allowed to obtain a building permit (excluding permits for land clearing) EU S: IPlanningiSHARED\ WPIPROJECTSIGateway T exacolCOUS 03-007 Gateway TlStaff Reportdoc CAR WASH TEXACO ANSWER TO TECH REVIEW COMMENTS September 16 2003 File No COUS 03-007 RESPONSE TO FIRST COMMENTS PUBLIC WORKS 1 Comment Noted 2 Done on site plan Public Works - Traffic 3 Traffic done by Civil Engineer, Burt Smith 4 Done on site plan 5 Done on site plan 6 Done on site plan 7 Done on both Civil and Site Plans 8 Done on site plan 9 Copy of 1 3-foot Ingress-egress easement enclosed UTILITIES 10 Done on site plan 11 Done on site plan 1 2 Done on plan 1 3 Complied 14 Done 1 5 Noted on Plan 16 Comment Noted 1 7 Comment Noted ENGINEERING 1 8 Comment Noted 19 Comment Noted 20 Comment Noted 21 Comment Noted 22 Done 23 Done on Plan 24 Comment Noted 25 Done on Plan 26 Done on Plan 27 Done on Plan 28 13' Easement Information is attached 29 Sidewalk Waiver submitted 30 Noted on Plan 31 Done in Photometric Plan 32 Comment Noted 33 Noted on Plan 34 Noted on Plan 35 Noted on Plan ! 1 r--..---- i ~ r I , r. 1 UJ i SEP I 6 L_u. 1--' ~_~~,_----3 PL '., [,~D ZG~ilr,c: ui:PT .oJ CAR WASH TEXACO ANSWER TO TECH REVIEW COMMENTS September 16 2003 36 Comment Noted 37 Noted on Plan 38 Comment Noted 39 Noted on Plan 40 Comment Noted 41 Noted on Plan 42 Noted on Plan 43 Comment Noted 44 Noted on Plan 45 Noted on Plan 46 Noted on Plan 47 Noted on Plan 48 Noted on Plan 49 Comment Noted 50 Comment Noted 51 Noted on Plan FIRE 52 Comment noted on site plan 53 Comment for info BUILDING DIVISION 54 Done on site plan 55 Done on site plan 56 Comment Noted 57 Done 58 Done 59 Done 60 Done 61 Done 62 Comment Noted 63 No Unity of Title Separate Ownership 64 Comment Noted 65 Done 66 Done on Plan 67 Comment Noted 68 Bollards Added to Plan 69 Done on Plan 70 See #63 FORRESTER/ENVIRONMENT ALlST Landscape Plan 71 Corrected on LIS plan 72 On LIS plan 73 Removed from Plan IrnQatlon Plan 74 Noted 75 Comment and noted PLANNING & ZONING 76 Done 77 Variance Filed 78 Variance Filed 79 Variance Filed 80 Variance Filed 81 Variance Filed 82 Variance Filed 83 Done 84 Comment Noted 85 Done 86 Comment Noted 87 Done 88 Done 89 Done 90 Done 91 Removed from Plan 92 Done 93 Done 94 Comment Noted 95 Comment Noted 96 Done 97 Done 98 Done 99 Done 100 Done 101 Done 102 Comment Noted 103 Done 1 04 Done 105 Comment Noted 106 Variance Filed 107 Comment Noted CAR WASH TEXACO ANSWER TO TECH REVIEW COMMENTS September 16 2003 ~f, Michael From Sent: To Subject: Seril Kruger [bkruger@bellsouth,net] Thursday August 28,200312:25 PM Rumpf, Michael RE Texaco/car wash sign Mike, Yes I am I think that is a very good idea Beril -----Original Message----- From Rumpf, Michael [mailto RumpfM@ci boynton-beach fl us] Sent Wednesday, August 27, 2003 5 48 PM To 'bkruger@bellsouth net' Subject RE Texaco/car wash sign Beril, am I to assume that you are taking advantage of the suggestion about changing the name to include "car wash"? Mike -----Original Message----- From Beril Kruger [mailto bkruger@bellsouth net] Sent Wednesday, August 27, 2003 3 29 PM To Rumpf, Michael Subject RE Texaco/car wash sign Mike We can bring the revised sign in with the Texaco Site Plan Thanks, Beril -----Original Message----- From Rumpf, Michael [mailto RumpfM@ci boynton-beach fl us] Sent Monday, August 25, 2003 4 51 PM To 'bkruger@bellsouth net' Subject Texaco/car wash sign Beril, the City Commission is taking an active role in this issue and want staff to follow up with Mr Marouf prior to the September 16th Commission meeting Have you discussed the issue of changing the business name to include "carwash" so that it can be on the sign without, technically, being an off-premise sign? I think I understood you to prefer to hold this item and bring it forward concurrent with either the car wash site plan approval or Texaco major site plan modification review Let me know and I'll updat the City Manager accordingly Thank you, Mike 1 0Y-7 ...------ /" 1ST REVIEW COMMENTS 08/04/03 12 lC- ~~...... ~ ~ t ;, S ,1 t eo. ,fpl'- .., l- -{t" 'f' /( .R L'? ~ J to;... ?~cp.< r-~ DEPARTMENTS t .1.~..........~~ .~~.1"......~ -----~ 0.-$ .4 J 5 (er{ "'~ ~ \ <yL " f\ "'t^e-~,.tj 1\""(Ji ~~ .{" . 1.- \" ~ JL t)e-';' 1J.. 7;.;. '" l &A:~C'- , I {(~~</!..J' (..~~ (I")' ~ eC ;(C "'-llt:t.- ~ ~ c-S I, b,,/!.. k INCLUDE REJECT (1:#" C(;~t-i I il--' II. '"IW dl oIII::i.~ 3rd }{EVIE\V COIVIlVIENTS Conditional Use ~1~ 01( z- ';l, ProJeCI name Gateway Texaco FIle number' COUS 03-007 Reference 3rJ reVIe\\ plans IdentIfied as a CondItIOnall,se wIth a SePtember 16.2003 PlannIng: and Zonmg De12artment date stamp markmg:, ~ ~ , :1 DEPARTI\-lE~TS rr.CLUDE REJECT I i PUBLIC WORKS - General Comments, 1 Pnor to permIt applIcatIOn contact the PublIc Works Department (561-742- v/' !, 6200) reg:ardmg: the storage and handlmg of refuse I' ! PUBLIC WORKS - Traffic [ i ;1 Comments ii I, 2, For the handIcap accessible parkmg space provIde elevatIOns on the SIte and [I clVlI plans to Illustrate accessibilIty The sIde\valk shall be same elevatIOn as V the adJommg pavement or you may show the SIdewalk at the same elevatIon I , as the five-foot accessible path WIth 1 12 ramps up m both dIrectIOns (FL AccessibIlIty Code 46 3). ThIS needs to be reflected m the details I I 3 Show parkmg stops on the plans, These wIll be reqUIred to prevent vehIcles , from overhangmg SIdewalks and reducmg accessible WIdth, V I 4 ProvIde an acceptable document WIth your re-submIttal for reVIew and ~ approval. UTILITIES Comments ;l !l 5 FIre flow calculations WIll be reqUIred demonstratmg the CIty Code I' reqUIrement of 1,500 g,p,m. as stated m the LDR. Chapter 6, ArtIcle IV v'" ! ! SectIOn 16, or the reqUIrement Imposed by msurance underwnters, whIchever ~ IS greater (CODE, SectIon 26-16(b)) i 6 The LDR, Chapter 6, ArtIcle IV, SectIOn 16 reqUIres that all pomts on each / bUIldmg will be \vIthm 200 feet of an eXlstmg or proposed fire hydrant, Please demonstrate that the plan meets thIS condItIon, by showmg all hydrants, I! 7 Appropnate backflow pre venters will be reqUIred on the domestIc water ~ servIce to the buildmg, and the fire spnnkler lme If there IS one, m accordance WIth the CODE, Section 26-207 ,I 8 UtilIty constructIOn detaIls as shoWTI on ClVlI Engmeenng (CE) sheets 3 of 3 / !i will not be reVIewed for constructIOn acceptabIlIty at thIS tIme All utIlIty ; constructIOn detaIls shall be In accordance WIth the UtIlItIes Department's I "Utilities Engineering Design Handbook and Construction Standards manual, they WIll be reVIewed at the tIme of constructIOn permIt applIcatIOn, ,I :1 E:\'GINEERI~G DIVISION I :1 ,I : 3rd renew comments 0923/03 2 DEP ART\IE"TS DJCLUDE REJECT ; I Comments 9 Please note that changes or revlSlons to these plans may generate addItIonal comments, Acceptance of these plans dunng the TRC process does not V ensure that addItIOnal comments may not be generated by the CommIssIOn I and at permIt reVIew 10 Proof of other agency permIts shall be requIred pnor to the Issuance of the V pavmg and dramage permIt, 11 SpeCIfy use of the FDOT Standard SpeCIficatIOns for Road & Bndge t/ ConstructIOn and Standard Index, 2000 EdItIon. as the constructIon standard, 12 Separate plans for "Gateway Texaco" and "Maroufs Car Wash Each plan ~ IS a separate sublTIlttal and IS reVIewed, each on ItS own ments, and usmg the gUIdelmes establIshed m the LDR for the type submIttal (eg' CondItIonal Use, New SIte Plan, etc,) Plans for the adJacent lot may be shown for mformatIOnal purposes on Iv 13 Show all eXIstmg easements, mcludmg mgress-egress, water, sewer, gas, t/' telephone. etc" on the SIte and CIVIl plans (LDR, Chapter 4. SectIOn 7,A.3) 14 WIll the 10 feet mgress-egress easement m the northerly portIOn of Tract A / be abandoned? i 15 SIdewalks shall be four (4) feet WIde along local streets, and five (5) feet / WIde along streets of hIgher claSSIficatIOn (LDR, Chapter 6, ArtIcle N, SectIon 10 T , and Chapter 22, ArtIcle I, SectIOn 5), ~ 16 SIdewalks shall meet or exceed State HandIcap Code reqUIrements and / comply WIth the Standard Buildmg Code and amendments thereto (LDR, Chapter 23, ArtIcle II, SectIOn K) 17 Show SIght triangles on the landscape plans (LDR, Chapter 7 5, ArtIcle II, I / ! SectIOn 5,H,) Use 25 (twenty-five) foot tnangles for the dnveway ont%ff of ! , Las Palmas Please note, m accordance WIth the referenced sectIOn of the LDR, that the SIght mangles are placed at the mtersectIOn of the property lme and SIde of accessway Use FDOT Standard Index 546 for the sight tnangles along Federal HIghway, followmg that standard for tnangle placement. 18 The medIans on Federal HIghway and the chase area(s) m the vIclmty of thIs proJect have eXlstmg ImgatIOn and plant matenal belongmg to the CIty of / Boynton Beach, Any damage to the ImgatIOn system and/or plant matenal as a result of the contractor's operatIOns shall be repaired or replaced to the eqUIvalent or better grade, as approved by the CIty of BOynton Beach, and I shall be the sole responsibIlIty of the developer Please acknowledge thIS notIce m your comments response and add a note to the plans WIth the above stated mformatIOn. 19 The LDR reqUIres the Landscape plan scale to match that of the SIte plan t/ I I (LDR, Chapter 4, SectIOn 7 C 1) The use of a 10 scale IS preferred. 20 Full dramage plans m accordance WIth the LDR, Chapter 6, ArtIcle IV, ,/ i I SectIOn 5 will be reqUIred at the tIme of permIttmg. Any work done wIthm the nght-of-way and/or to eXIstmg facilItIes WIthIn the nght-of-way of Federal / HIghway will reqUIre reVIew, approval and permIttmg by the Flonda DOT 21 PrOVIde eXlstmg and proposed elevatIOns for Parcel "A" v 22, SpeCIfy storm sewer dIameters, mlets types, etc on dramage plan. IndIcate /' grate, nm and mvert elevatIOns for all structures, IndIcate matenal speCIficatIOns for storm sewer I 3rd review comments 09123/03 3 . 'I DEPART"lE"lTS INCLL:DE REJECT I ,.,'"' The sIte survey IndIcates a propane storage area m the northwest comer of I ...,) I Parcel A, that IS not shmvn on the Pavmg & Gradmg Plan sheet 2 of 3 /" , , (although a 'Propane Gas Storage area m shown on the SIte Plan w Proposed ! il AddItIOn Sheet 1 of 4) Please ensure that all site features are reflected on the !j appropnate sheets, !' 24 Increase SIze of the General Notes on pavmg & gradmg plan sheet 2 of 3 for ~ ,I legibIlIty f 25 Pavmg, dramage and sIte detaIls as sho\vn on sIte development sheet 3 of 3 i I wIll not be reVIewed for constructIon acceptabIlIty at thIS tIme The details / proVIded are outdated, All engmeenng constructIOn detaIls shall be m i accordance with the "CIty of Boynton Beach Engmeenng DeSIgn Handbook I " & ConstructIOn Standards and wIll be reVIewed for constructabIlIty at the tIme I of constructIOn permIt applicatIOn, The Engmeenng DeSIgn Handbook may I be obtamed by contactmg the Engmeenng DIVISIOn, I ;1 Ii FIRE II I Comments. NONE II ; POLICE Comments NONE I BUILDING DIVISION Comments I ! 26 Buildmgs, structures and parts thereof shall be deSIgned to withstand the I lTIlmmum wind loads of 140 mph, Wind forces on every building or structure / I shall be determIned by the provlSlons of Chapter 6 of ASCE 7, and the I prOVlSlons of SectIOn 1606 (Wind Loads) of the 2001 FBC CalculatIOns that I I are SIgned and sealed by a deSIgn profeSSIOnal regIstered m the state of , ; Flonda shall be subrmtted for reVIew at the tIme of permIt applIcatIOn, 27 Add a labeled symbol to the SIte plan drawmg that represents and delIneates I I the path of travel for the accessible route that IS reqUIred between the / I accessible parkIng spaces and the accessible entrance doors to the buildmg. The mstalled symbol, reqUIred along the path, shall start at the accessible I parkmg spaces and termmate at the accessible entrance doors to the buildmg, I !: The symbol shall represent the location of the path of travel, not the locatIOn II of the detectable warnmg or other pavement markmgs, The locatIOn of the 'I accessible path shall not compel the user to travel m a dnveilane area that IS I :1 located behmd parked vehIcles, IdentIfy on the plan the WIdth of the , I i accessible route, (Note The mInImUm WIdth reqUIred by the code IS forty- I i four (44) mches) Add text to the dra\vmg that would mdIcate that the symbol j represents the accessible route and the route IS deSIgned m comphance WIth Section 11-4.3 (Accessible Route) and 11-46 (Parkmg and Passenger Loadmg Zones) of the 2001 FBC Please note that at tIme of permIt reVIew, the applIcant shall proVIde detaIled documentatIOn on the plans that WIll ! venfy that the accessible route IS In comphance with the regulatIOns speCIfied i :1 ! f)\[L&t:v\ 3rd review comments 0923i03 4 ~ DEPARTME~TS INCLUDE REJECT m the 2001 FBC ThIS documentatIOn shall mclude, but not be hmlted to provldmg fimsh grade elevatIons along the path of travel. Parkmg access aIsle shall slo e no more than 1 50 er Flonda Buildmg Code 11-4 6 3 fl 28 IdentIfy wIthIn the sIte data the fimsh floor elevatIOn (lowest oor elevation) , that IS proposed for the bUIldmg. Venfy that the proposed elevatIOn IS In ~ comphance wIth regulatIOns of the code by addmg specIficatIOns to the sIte data that address the followmg Issues [SectIOn 3107 1.2, Chapter 31 of the 2001 FBC] ! a) The deSIgn professIOnal-o f-record for the project shall add the i followmg text to the sIte data. 'The proposed fimsh floor elevatIOn -- NGVD IS above the hIghest 100-vear base flood elevation applIcable to the buildmg sIte, as determmed by the SFWMD's surface water management constructIOn development regulatIOns. 29 At tIme of permIt reVIew, submIt sIgned and sealed workmg drawmgs of the t/ , I proposed constructIOn, II 30 A water-use permIt for the ImgatIOn system IS reqUIred from the SFWMD A / copy of the permIt shall be submItted at the tIme of permIt applIcatIOn, F S ! 373.216 ; , 31 The propane gas storage area shall comply WIth the reqUIrements ofNFPA / i 58 IndIcate the capaCIty of the contamer, how the contamer IS protected from phYSIcal damage, etc ! i PARKS AND RECREATIO" Comments, I. Ii 'I 'I FORESTER/ENVIRON"lE~T ALIST Comments 'I PLAN~ING AND ZONING :1 , ;::-UINuents, ~IS proJect reqUIres condItIonal use approval ! ~~ dnveway shall be located less than 110 feet from the mtersectmg nght-of- I i i way lmes ofpubhc streets (Chapter 2, SectIOn 11.L.3 d(l) Dnveways shall ! not be located less than 30 feet from any mtenor property hne from the i r mtersectIOn of the nght-of-way lmes along local streets and 180 feet along I streets of hIgher claSSIficatIOn such as US 1 (Chapter 23, ArtIcle II,H.3 ) i I Dnveways are lImIted to one (1) per street frontage (Chapter 2, SectIOn i 11.L.3 d(4), Either revise the plans to comply or request a variance from I ~---... these code requirements. i I ~~e rear setback is 20 feet (Chapter 2, SectIOn 11.L.3 e(3) Either revise the j ans to comolv or request a variance from this code requirement. I ~o canopy shall be located less than 20 feet from any property lme (Chapter I 2 SectIOn 11.L.3 e (a), Either revise the plan to comply or request a I lrd redew comments DEP ARTME~TS INCLUDE REJECT variance from this code requirement. o gasolme pump Island shall be located less than 30 feet from any property lme (Chapter 2, SectIon ll.L.3 e(b) Either revise the plan to complv or re uest a variance from this code re uirement. 10-foot wIde landscape buffer shall be located along the street frontage (Chapter 2, SectIOn 11.L.3 f(1), Also, except for permItted dnveway openmgs, a five (5) foot wIde landscape buffer shall be located around that portIOn of the parcel of whIch the gasohne dIspensmg establIshment IS located (Chapter 2, SectIon 11.Lo4 b) Either revise the plan to comply or request variance from these code re uirements. II SIgnS must meet a mImmum of 10-foot setback measured from the property lme to the closest surface ofthe SIgn (Chapter 21 ArtIcle III, SectIon 5) Either revise the plan to comply or request a variance from this code re uirement. ThIS project reqUIres a total of 10 parking spaces (1,719 square feet + 681 s uare feet ,1/250 - 10 s aces), nsure that all the proposed plant quantItIes correspond between what IS shown on the graphIC IllustratIOn and ItS correspondmg plan hst on sheet "L- 1" All elevatIons (sheet 4 of 4) must mdlcate the proposed colors, mcludmg the pamt manufacturer's name and color code (Chapter 4, SectIon 7,D), Please coordmate WIth staff WIth re ard to the ro osed buildm colors, 'on-word depIctIOns on SIgnS shall be hmIted to 20% of the area of the SIgn erected, Color lImItatIOn shall not apply to non-word depIctIOns on SIgnS (Cha ter 9 SectIOn 10 104 ) qUIpment placed on the walls of the buildmgs shall be pamted to match the buildmg color (Chapter 9, SectIon 10 C 4), Place a note on the elevatIOns mdlcatmg thIS re UIrement. 47, ooftops wIll be treated as part of the bUIldmg elevatIOn. All rooftop eqUIpment must be completely screened from VIew at a mInImUm dIstance of o feet Cha ter 9, SectIOn 11.E,) D~l'.'~lgpmeRt Board, On the elevatIOns, mdlcate WIth dImensIOns, and total area the SIze of mdlvIdual SIgnS, the cumulatIve area of all wall sIgnage and total front fayade length to ensure that SIgn area complIes wIth Chapter 21, ArtIcle 4, SectIOn C), In addItIon, mdIcate the letter colors and SIgn matenal. On sheet 3 of 4, remove the *** from the elevatIons. hapter 9, SectIon 10.1.6 of the City Of Boynton Beach Land Development egulatIOns reqUIres that project sIgnage be m scale WIth the bUIldmg, MWR/sc 3rd re\ 'W comments 09 23/03 6 J'\SHF.0ATAPLANNING\SHARED\WP\FORMSIBLANKS FORMS FOLDER' 1 ST REVIEW CQMr.~EN-S.DOC MasteR 1 st REVIEW COMMENTS Conditional Use ProJect name' Gateway Texaco FIle number COUS 03-007 Reference 1 S(revIew plans IdentIfied as a CondItIonal Use wIth a June 17,2003 Plannmg and Zonmg Department date stamp markmg, DEP ARTlVlENTS INCLUDE REJECT PUBLIC WORKS - General i Comments: 1 Pnor to permIt applIcatIOn contact the PublIc Works Department (561-742- 6200) regardmg the storage and handlIng of refuse, 2 ProvIde dumpster enclosure detall(s) (LDR, Chapter 2, SectIOn II,J.2,b, Chapter 7.5, ArtIcle IT, SectIOn 5.J., and ArtIcle Ill, SectIOn 9.A.9,a, Chapter 9, SectIOn 10 C.3 and City Standard Drawmg G-4 ) PUBLIC WORKS - Traffic Comments, 3 ProvIde a traffic analYSIS and notIce of concurrency (Traffic Performance Standards RevIew) from Palm Beach County Traffic Engmeenng. 4 On the SIte and CIvil plans, show and IdentIfy all necessary traffic control I deVIces such as stop bars, stop SIgnS, double yellow lane separators strIpmg, dIrectIOnal arrows and "Do Not Enter" sIgnage, etc Delmeate and strIpe the i "Loadmg Area" (LDR, Chapter 2, SectIon 11,J); mclude a pavement message I I i m yellow mdIcatmg "No Parkmg - Loadmg Zone" See CIty Standard : DraWings "K" Senes for strIpmg details and CIty Standard DraWings G-9 i through G-12 for sIgnmg details. 5 For the handIcap accessible parkmg space provIde elevatIOns on the sIte and CIvil plans to illustrate accessibilIty The SIdewalk shall be same elevatIOn as the adJOImng pavement or you may show the SIdewalk at the same elevatIon as the five-foot accessible path With 1 12 ramps up m both dIrectIOns (FL AccessibilIty Code 46,3), ThIS needs to be reflected m the details. i I i 6 Show an appropnate handIcap parkmg post SIgn (or on the bUIldmg) for the handIcap space 7 Show parking stops on the plans, These will be reqUIred to prevent vehIcles from overhangmg SIdewalks and reducmg accessible WIdth, 8 PrOVIde "One-Way" arrow SIgnS m the Federal Hwy medIan across from each egress dnveway 9 Show on the SIte plan a thIrteen (13) foot mgress/egress easement through the gas statIon SIte to agree WIth the plan dImensIOns. PrOVIde an acceptable document With your re-subrmttal for reVIew and approval 1ST REVIEW COMMENTS 08/04/03 2 DEP ARTl\''lENTS INCLUDE REJECT UTILITIES Comments. 10 All utilIty easements shall be shown on the sIte plan and landscape plans (as well as the Water and Sewer Plan) so that we may determme whIch trees may mterfere wIth utilItIes. In general, palm trees wIll be the only tree speCIes allowed wIthm utIlIty easements. Canopy trees may be planted outSIde of the easement so that roots and branches will not Impact those utilItIes WIthm the easement m the foreseeable future. The LDR, Chapter 7,5, ArtIcle I, SectIOn 18 1 gIves publIc utIlItIes the authonty to Remove any trees that may mterfere With utilIty servIces, eIther m utilIty easements or publIc nghts-of-way 11 FIre flow calculatIOns will be reqUIred demonstratmg the City Code reqUIrement of 1,500 g.p,m. as stated m the LDR, Chapter 6, ArtIcle IV, SectIon 16, or the reqUIrement Imposed by msurance underwnters, whIchever IS greater (CODE, SectIOn 26-16(b)), I 12 ComprehensIve Plan PolIcy 3 C.3 4 reqUIres the conservatIOn of potable i water City water may not, therefore, be used for ImgatIOn where other I sources are readily available, 13 The LDR, Chapter 6, ArtIcle IV, SectIOn 16 reqUIres that all pomts on each bUIldmg Will be WIthm 200 feet of an eXIstmg or proposed fire hydrant. Please demonstrate that the plan meets thIS condItIon, by showmg all hydrants, 14 Appropnate backflow preventers will be reqUIred on the domestIc water sefVIce to the buildmg, and the fire spnnkler lme If there IS one, m accordance With the CODE, SectIOn 26-207 15 The LDR, Chapter 3, ArtIcle IV, SectIOn 3(P) reqUIres a statement be mcluded that utilItIes are avaIlable and will be prOVIded by other appropnate agenCIes. ThIS statement IS lackmg on the submItted plans, 16 UtIlIty constructIOn details as shown on CIvil Engmeenng (CE) sheets 3 of 3 WIll not be revIewed for constructIon acceptabIlIty at thIS tIme. All utilIty constructIOn details shall be m accordance With the UtilItIes Department's "Utilities Engineering Design Handbook and Construction Standards" manual, they will be reVIewed at the tIme of constructIon permIt applIcatIOn, 17 LikeWise, the PaVIng, Dramage and SIte detaIls as shown on CE sheet 3 of 3 wIll be reVIewed for constructabIlIty at the tIme of constructIOn permIt applIcatIOn. 1 ST REVIEW COMMENTS 08/04/03 3 " DEPARTMENTS INCLUDE REJECT ENGINEERING DIVISION Comments. 18 Numerous omISSIOns have been noted on these proposed plans and m thIS reVIew comments report, DraWings need to be thoroughly checked and coordmated by the consultmg engmeer It IS the responsibilIty of the consultmg engmeer to familIanze hImself wIth the CIty of Boynton Beach Land Development RegulatIOns pnor to submIssIOn of plans, 19 All comments requITIng changes and/or correctIOns to the plans shall be reflected on all appropnate sheets. 20 Please note that changes or reVISIons to these plans may generate addItIOnal comments, Acceptance of these plans dunng the TRC process does not ensure that addItIonal comments may not be generated by the CommIssIon and at permIt reVIew 21 Proof of other agency permIts shall be reqUIred pnor to the Issuance of the pavmg and dramage permIt, 22 PrOVIde wntten and graphIC scales on all sheets, mcludmg the Survey 23 SpeCIfy use of the FDOT Standard SpeCIficatIons for Road & Bndge ConstructIon and Standard Index, 2000 EdItIon, as the constructIOn standard. 24 Separate plans for "Gateway Texaco" and "Maroufs Car Wash" Each plan IS a separate submIttal and IS reVIewed, each on ItS own ments, and usmg the gUIdelmes establIshed m the LDR for the type submIttal (eg: CondItIonal Use, New SIte Plan, etc.) Plans for the adjacent lot may be shown for mformatIOnal purposes only 25 Show zomng and land use on SIte charactenstIcs map (Survey) (LDR, Chapter 4, SectIOn 7,A.) 26 Show all eXIstmg utilItIes on SIte development plan (LDR, Chapter 4, SectIOn 7,A.3). 27 Show all eXIstmg easements, mcludmg mgress-egress, water, sewer, gas, telephone, etc., on the SIte and CIvil plans (LDR, Chapter 4, SectIOn 7.A.3). 28 Will the 10 feet mgress-egress easement m the northerly portIon of Tract "A" be abandoned? 29 SIdewalks shall be four (4) feet WIde along local streets, and five (5) feet WIde along streets of hIgher claSSIficatIOn (LDR, Chapter 6, ArtIcle IV, SectIOn lOT, and Chapter 22, ArtIcle I, SectIon 5) 1ST REVIEW COMMENTS 08/04/03 4 DEP ARTl\tlENTS 30 SIdewalks shall meet or exceed State HandIcap Code reqUIrements and comply wIth the Standard Buildmg Code and amendments thereto (LDR, Chapter 23, ArtIcle II, SectIon K) 31 Show proposed sIte lIghtmg on the sIte, clVlI, and landscape plans (LDR, Chapter 4, SectIOn 7.B 4) The lIghtmg desIgn shall provIde a mImmum average lIght level of one foot-candle, Llghtmg levels, under the canopy only, shall not exceed 60 foot-candles, On the LIghtmg Plan, specIfy that the lIght poles shall wIthstand a 140 MPH wmd load (LDR, Chapter 23, ArtIcle II, SectIOn A1.a and Flonda Buildmg Code) PrOVIde a note that the fixtures shall be operated by photo-electrIcal control and are to remam on untIl 2'00 a.m, (LDR, Chapter 23, ArtIcle II, SectIOn AI,a,) Include pole wmd loadmg, and pole details m conformance With the LDR, Chapter 6, ArtIcle IV, SectIon 11, Chapter 23, ArtICle I, SectIOn 5,B 7 and Chapter 23, ArtICle II, SectIOn A on the LIghtmg Plan. Glare, whIch IS readily perceptible at any pomt at or beyond the property on WhICh the use IS located, IS prohibIted (LDR, Chapter 2, SectIOn 4.N 7), Llghtmg shall be dIrected away from any resIdentIal uses (LDR, Chapter 2, SectIOn 4.N 7) Llghtmg shall not be used as a form of advertIsmg m a manner that draws more attentIOn to the buildmg or grounds at mght than m the day (LDR, Chapter 9, SectIOn lO,F,5) ProVIde photometrIcs as part ofvour TRC plan submIttals. 32. It may be necessary to replace or relocate large canopy trees adJacent to lIght fixtures to elImmate future shadowmg on the parkIng surface (LDR, Chapter 23, ArtIcle II, SectIOn A1 b) 33 Show sIght trIangles on the landscape plans (LDR, Chapter 75, ArtIcle II, SectIon 5.H.) Use 25 (twenty-five) foot trIangles for the dnveway ont%ff of Las Palmas. Please note, m accordance wIth the referenced sectIon of the LDR, that the sIght trIangles are placed at the mtersectIon of the property lme and SIde of accessway Use FDOT Standard Index 546 for the sIght trIangles along Federal HIghway, follOWing that standard for trIangle placement. 34 IndIcate, by note on the Landscape Plan, that WIthm the sIght trIangles there shall be an unobstructed cross-VIsibilIty at a level between 2.5 feet and 6 feet above the pavement (LDR, Chapter 7,5, ArtICle II, SectIOn 5.H.) 35 Landscaped areas shall be protected from vehIcular encroachment by a contmuous, raIsed curb (LDR, Chapter 7.5, ArtIcle II, SectIOn 5,A and Chapter 22, ArtIcle II, SectIon E.) Add Type "D" curb around the landscaped area defimng the parkmg lot adjacent to Federal Hwy 36 The medIans on Federal HIghway and the chase area(s) m the VIclmty of thIS proJect have eXlstmg ImgatIOn and plant matenal belongmg to the City of Boynton Beach. Any damage to the ImgatIOn system and/or plant matenal as a result of the contractor's operatIOns shall be repaIred or replaced to the eqUIvalent or better grade, as approved by the CIty of Boynton Beach, and INCLUDE REJECT 1 ST REVIEW COMME~TS 08/04/03 5 DEP ARTlVlENTS INCLUDE REJECT shall be the sole responsibIlIty of the developer Please acknowledge thIS notIce m your comments response and add a note to the plans wIth the above stated mformatIOn, , , 37 The LDR reqUIres the Landscape plan scale to match that of the SIte plan I I (LDR, Chapter 4, SectIon 7 C 1) The use of a 10 scale IS preferred. 38 FICUS IS not a permItted specIes (LDR, Chapter 7.5, ArtIcle II, SectIon 5 C.2 ) SpecIfy an alternatIve speCIes for the proposed FICUS hedge. 39 The landscapmg matenals at the drIveways need to have a clear lme of sIght to a mlmmum of 7 (seven) feet hIgh (eg: PIgeon Plums may mterfere dependmg on how specIficatIOn called out.) 40 The General Notes and Transportmg Notes, Landscape Plans Sheet L-1, are repeated on Sheet L-1A and L-2 Please delete one set. ! i 41 On Pavmg & Gradmg Plan sheet 2 of 3 the wntten legend does not match the symbols used m the plans, specIfically eXIstmg and proposed elevatIons, I Please correct dIscrepancy i 42 ProvIde an engmeer's certIficatIOn on the Dramage Plan as specIfied m LDR, Chapter 4, SectIOn 7,F,2 43 Full dramage plans m accordance With the LDR, Chapter 6, ArtIcle IV, SectIOn 5 Will be reqUIred at the tIme of permIttmg. Any work done WIthm the nght-of-way and/or to eXIstmg facilItIes WIthm the nght-of-way of Federal HIghway will reqUIre reVIew, approval and permlttmg by the Flonda DOT 44 ProvIde eXIstmg and proposed elevatIons for Parcel "A" 45 IndIcate by note that catch basm and manhole covers shall be bIcycle proof (LDR, Chapter 6, ArtIcle IV, SectIOn 5.A.2.g) 46 SpecIfy storm sewer dIameters, mlets types, etc. on dramage plan, IndIcate grate, nm and mvert elevatIOns for all structures. IndIcate matenal speCIficatIOns for storm sewer 47 The SIte survey mdICates a propane storage area m the northwest corner of Parcel "A," that IS not shown on the PaVIng & Gradmg Plan sheet 2 of 3 (although a "Propane Gas Storage area m shown on the SIte Plan w/ Proposed AddItIon Sheet 1 of 4) Please ensure that all SIte features are reflected on the appropnate sheets. ! 48 IndIcate, on all appropnate sheets, surfacmg matenal(s) for the parkmg lot. 49 Please mcrease SIze of details for legibIlIty 1ST REVIEW COMMENTS 08/04/03 6 DEPARTMENTS INCLUDE REJECT 50 Increase SIze of the General Notes on pavmg & gradmg plan sheet 2 of 3 for legibIlIty 51 Pavmg, dramage and sIte details as shown on sIte development sheet 3 of 3 will not be reVIewed for constructIOn acceptabilIty at thIS tIme, The details provIded are outdated, All engmeenng constructIOn details shall be m accordance WIth the "CIty of Boynton Beach Engmeenng DeSIgn Handbook & ConstructIon Standards and WIll be reVIewed for constructabilIty at the tIme of constructIOn permIt applIcatIOn. The Engmeenng DeSIgn Handbook may be obtamed by contactmg the Engmeenng DIVIsIon. FIRE Comments. 52 The sIte plan and master plan deSIgn documents shall adhere to Chapter 9 of the Code of Ordmances of the CIty of Boynton Beach entItled "FIre ProtectIon and PreventIOn." ThIS ordmance adopts NFP A 1, Fire Prevention Code, 2000 edItIOn, and NFP A 101, Life Safety Code, 2000 edItIOn, (These codes, as amended are IdentIfied as the Florida Fire Prevention Code) 53 Pnor to FIre Department approval of a bUIldmg permIt, new constructIon proJects must prOVIde the results of a hydrant flow test mdlcatmg a fire flow not less than 1500 gpm @ 20 pSI above domestIC use. ThIS applIes to new or eXIstmg hydrants WIthm the reqUIred 200 feet of the facilIty POLICE Comments: None BUILDING DIVISION Comments. 54 IndIcate wlthm the SIte data the type of constructIOn of each buildmg as defined m Chapter 6 of the 2001 FBC 55 IndIcate wlthm the SIte data the occupancy type of each bui1dmg as defined m Chapter 3 of the 2001 FBC 56 BUIldmgs, structures and parts thereof shall be deSIgned to Withstand the mlmmum Wind loads of 140 mph, Wind forces on every buildmg or structure shall be determmed by the prOVISIOns of Chapter 6 of ASCE 7, and the prOVISIOns of SectIOn 1606 (Wind Loads) of the 2001 FBC CalculatIOns that are SIgned and sealed by a deSIgn profeSSIOnal regIstered m the state of Flonda shall be submItted for reVIew at the tIme of permIt applIcatIOn. 57 Add to the buildmg that IS dePIcted on the draWing tItled SIte plan and floor 1 ST REVIEW COMMENTS 08/04/03 7 DEPARTMENTS plan a labeled symbol that IdentIfies the locatIOn of the handIcap accessible entrance doors to the bUIldmg, 2001 FBC, SectIOns 11-4 1,2 and 11-4.3 58 Add a labeled symbol to the SIte plan drawmg that represents and delmeates the path of travel for the accessible route that IS reqUIred between the accessible parking spaces and the accessible entrance doors to the bUIldmg. The mstalled symbol, reqUIred along the path, shall start at the accessible parking spaces and termmate at the accessible entrance doors to the buildmg. The symbol shall represent the locatIOn of the path of travel, not the locatIOn of the detectable warmng or other pavement markmgs, The locatIOn of the accessible path shall not compel the user to travel m a dnve/lane area that IS located behmd parked vehIcles, IdentIfy on the plan the WIdth of the accessible route. (Note: The mlmmum WIdth reqUIred by the code IS forty- four (44) mches). Add text to the drawmg that would mdIcate that the symbol represents the accessible route and the route IS desIgned m complIance wIth SectIOn 11-4.3 (Accessible Route) and 11-46 (parking and Passenger Loadmg Zones) of the 2001 FBC Please note that at tIme of permIt revIew, the applIcant shall provIde detailed documentatIon on the plans that will venfy that the accessible route IS m complIance wIth the regulatIOns specIfied m the 2001 FBC ThIS documentatIon shall mclude, but not be lIrmted to, proVIdml! fimsh !!fade elevatIOns alonl! the path of travel. 59 IdentIfy wIthm the SIte data the fimsh floor elevatIOn (lowest floor elevatIOn) that IS proposed for the buildmg. Venfy that the proposed elevatIon IS m complIance wIth regulatIOns of the code by addmg specIficatIOns to the SIte data that address the followmg Issues [SectIOn 3107 1.2, Chapter 31 of the 2001 FBC] a) The desIgn professIOnal-of-record for the proJect shall add the follOWing text to the SIte data. "The proposed fimsh floor elevatIOn _ _ NGVD IS above the hIghest 100-year base flood elevatIOn applIcable to the bUIldmg SIte, as determmed by the SFWMD's surface water management constructIOn development regulatIOns," b) From the FIRM map, IdentIfy m the SIte data the tItle of the flood zone that the buildmg IS located WIthm. Where applIcable, specIfy the base flood elevatIOn, If there IS no base flood elevatIOn, mdlcate that on the plans. c) IdentIfy the floor elevatIOn that the desIgn professIOnal has establIshed for the buildmg wlthm the footpnnt of the buildmg that IS shown on the draWings tItled SIte plan, floor plan and paVIng! dramage (CIVIl plans) 60 On the draWIng tItled SIte plan, IdentIfy and label the symbol that represents the property lme. 61 As reqUIred by Chapter 4, SectIOn 7 of the LDR, submIt a floor plan draWing, The buildmg plans are not bemg reVIewed for complIance WIth the applIcable buildmg codes. Therefore, add the words "Floor plan layout IS conceptual" below the drawmg. Add to the floor plan draWing a labeled symbol that IdentIfies the locatIon of the handIcap accessible entrance doors to the INCLUDE REJECT 1ST REVIEW COMMENTS 08/04/03 8 DEPARTMENTS INCLUDE REJECT buildmg. The locatIOn of the doors shall match the locatIOn of the accessible entrance doors that are depIcted on the sIte plan drawmg, 62. Place a note on the elevatIOn VIew draWings mdlcatmg that the wall opemngs and wall constructIOn comply With Table 600 of the 2001 FBC 63 At tIme of permIt reVIew, provIde a completed and executed CBB Umty of TItle form, The form shall describe all lots, parcels or tracts combmed as one lot. A copy of the recorded deed WIth legal descnptIOns, of each property that IS bemg umfied, IS reqUIred to be submItted to process the form. The property owner that IS IdentIfied on each deed shall match, 64 At tIme of permIt reVIew, submIt SIgned and sealed workmg drawmgs of the proposed constructIOn. 65 Add to all plan VIew draWings of the SIte a labeled symbol that represents the locatIOn and penmeter of the lIrmts of constructIOn proposed With the subJect request. 66 Accordmg to the CBBCPP 3C3 4, the City shall contmue to encourage the use of non-potable water for landscape ImgatIOn. An alternate water source other than CIty water shall be utilIzed for the ImgatIon system. 67 A water-use permIt for the ImgatIon system IS reqUIred from the SFWMD A copy of the permIt shall be submItted at the tIme of permIt applIcatIOn, F.S 373.216 I i 68 The propane gas storage area shall comply With the reqUIrements of NFP A 58 IndIcate the capacIty of the contamer, how the contamer IS protected from phYSIcal damage, etc. 69 IndIcate on the plans what matenals will be stored m the storage area. 70 Will the car wash and the Texaco statIOn be under one ownershIp? If so, a Umty of Title form shall be completed and submItted, PARKS AND RECREATION Comments. None FORESTER/ENVIRONMENT ALIST Comments: 1ST REVIEW COMMENTS 08/04/03 9 , II DEPARTMENTS INCLUDE REJECT Landscape Plan- Existin2 TreesN e2etation 71 The applIcant has mdIcated on the landscape plan the eXlstmg trees that will be preserved, and relocated on the sIte. All eXlstmg trees and / or hedge plants shown for removal must be replaced on the sIte, A separate symbol should be used on the landscape plan to IdentIfy these trees and vegetatIon, The eXlstmg trees and hedge plants may not meet the landscape reqUIrements for the sIte due to grade dIfference between the sIte and the eXIstmg vegetatIon, A cross sectIOn detaIl must be prOVIded to show the landscape buffer between the proposed parkmg dnveways and the eXlstmg trees / newly mstalled landscape. [EnVIronmental RegulatIOns, Chapter 7.5, ArtIcle II Sec 7C] Landscape Plan 72 All newly mstalled trees lIsted on the Plant LIst (includmg mIssmg CIty SIgnature tree) must be lIsted m the speCIficatIons as a mImmum of 12 -14 feet, 3 mch calIper at DBH (4.5 feet off the ground), and Flonda # 1 (Flonda Grades and Standards manual) Chapter 7.5, ArtIcle II Sec 5 C 2.] 73 Trees and plants lIsted m the Palm Beach County "mvasIve plant speCIes" and " mvasIve non-natIve plant" lIstmg should not be mcluded m the landscape deSIgn. FICUS benJamma cannot be planted m the CIty of Boynton Beach (Chapter 7,5, ArtIcle I Sec 19A.51 Irri2ation Plan 74 There IS an ImgatIOn system deSIgn mcluded With the SIte plans, [EnVIronmental RegulatIOns, Chapter 7.5, ArtIcle II Sec. 5A.] 75 Turf and landscape (beddmg plants) areas should be deSIgned on separate zones and tIme duratIOn for water conservatIOn (Chapter 7.5, ArtIcle II Sec 5 C.2 ) PLANl'HNG AND ZONING Comments, ~ 06 IS proJect reqUIres condItIonal use approval. PnVR6e Jtl.,tlb."allvll fvl ~ppr9ual ef the project ba",t;d Ull thG !tttl'l.6Mth fef @vahaatIRg 8enBItIonall:lS81S fOw:lQ III Cl\~t8f 2, ~~~tIQR 11,2,D 6f tfl@ CIl:y ef YB:/RtQR Y8adL Land D 8NO dnveway shall be located less than 110 feet from the mtersectmg nght-of- way lInes of publIc streets (Chapter 2, SectIOn 11.L.3 d(l) Dnveways shall not be located less than 30 feet from any mtenor property lme from the mtersectIOn of the nght-of-way lmes along local streets and 180 feet along 1ST REVIEW COMMENTS 08/04/03 10 DEPARTMENTS streets of hIgher classIficatIOn such as U,S 1 (Chapter 23, ArtIcle n,H.3 ) Dnveways are lIrmted to one (1) per street frontage (Chapter 2, SectIOn 11.L.3 d(4) Either revise the plans to comply or request a variance from these code re uirements. INCLUDE REJECT e rear setback IS 20 feet (Chapter 2, SectIon 11,L.3 e(3) Either revise the lans to com I or re uest a variance from this code re uirement. ~o canopy shall be located less than 20 feet from any property lme (Chapter 2, SectIOn 11.L.3.e (a) Either revise the plan to comply or request a variance from this code re uirement. o gasolme pump Island shall be located less than 30 feet from any property lme (Chapter 2, SectIon 11.L.3 e(b) Either revise the plan to comply or re uest a variance from this code re uirement. 10-foot wIde landscape buffer shall be located along the street frontage (Chapter 2, SectIOn 11.L.3.f(1). Also, except for permItted dnveway opemngs, a five (5) foot Wide landscape buffer shall be located around that portIOn of the parcel of whIch the gasolme dIspensmg establIshment IS located (Chapter 2, SectIOn 11,LA b) Either revise the plan to comply or request a variance from these code re uirements. 82. II SIgnS must meet a mlmmum of 10-foot setback measured from the property lme to the closest surface of the SIgn (Chapter 21, ArtIcle ill, SectIOn 5) Either revise the plan to comply or request a variance from this code re uirement. On the SIte plan (sheet 1 of 4), mdlcate the dIstance from the subJect parcel to the nearest resIdentIal structure, statement IS reqUIred pnor to the TechnIcal ReVIew Cha ter 4 SectIOn 8.F . Include a color rendenn of all four 4 elevatIOns at the TechnIcal RevIew 1 ST REVIEW COMMENTS 08/04/03 11 DEPARTMENTS Cormmttee meetmg (Chapter 4, SectIOn 7.D) V The landscape plan tabular lIst needs to be updated m reference to the ~\ "Intenor Trees" By code, two (2) "mtenor" trees would be reqUIred smce 12 parkIng spaces are proposed (Chapter 7.5, ArtIcle II, SectIOn 5 G). RevIse sheet "L-I " to mdIcate thIS re UIrement. nsure that all the proposed plant quantIties correspond between what IS shown on the graphIc illustratIOn and ItS correspondmg plan hst on sheet "L- I" The removal/relocation of landscape matenal IS subject to reVIew and a roval of the CI Forester / EnVIronmentalIst. The Dahoon Holly trees are to be spaced no less than 30 feet apart from each other A SIgnature tree (such as a Yellow Elder, Tibouchma Granulsola, or Bouganvillea) IS reqUIred at both SIdes of each project entrance / eXIt. The SIgnature trees must have 6 feet of clear trunk If placed WIthm the safe-sIght tnangle (Chapter 7.5, ArtIcle 2, SectIOn 5.N). Alternative plant matenal may be substituted If the above referenced plant matenal IS not avaIlable or undeSIred. Any SubstItutIOn of plant matenal (for the SIgnature tree reqUIrement) will be subject to the City Forester / EnVIronmentahst reVIew and a roval. . All trees are reqUIred to be at least 12 feet overall heIght at the time of mstallatIOn (Chapter 7.5, ArtIcle II, Section 5 C.2 ) All shrubs and hedges are reqUIred to be at mImmum 24 mches m heIght, 24 mches m spread, and planted WIth tIp-tO-tIp spacmg measured Immediately after plantmg to adequately cover the planted areas on the SIte (Chapter 7.5, ArtIcle II, Section 5 C 4 ) FIfty percent (50%) of SIte landscape matenals must be native speCIes. IndIcate the amount of native matenal m the plant lIst of the landscape plan (Chapter 7.5, ArtIcle II, SectIOn 5.P) Please mdIcate by astensk, the natIve s eCIes and ensure that at least 50% of Iandsca e matenalIS native. V'The base of the monument SIgn must be enhanced WIth colorful groundcover /\.pians and a mmImum of two (2) shrub speCIes all selected for entrance com atibilI Cha ter 7.5, ArtIcle II, SectIOn 50 . INCLUDE REJECT and 1 ST REVIEW COMMENTS 08/04/03 12 DEP ARTl\tIENTS II elevatIOns (sheet 4 of 4) must mdIcate the proposed colors, mcludmg the amt manufacturer's name and color code (Chapter 4, Section 7.D) Elease- cQDIdmate "T1tn theuty's Planner / Urbtffi De5Igfler (M~. Mi\ibdly Ddlrau @ 42- 102 on-word depIctIOns on SIgnS shall be lImIted to 20% of the area of the SIgn erected. Color hmItatIOn shall not apply to non-word depIctions on SIgnS Cha ter 9, Section 10.1.4 1 ~e dumpster enclosure shall resemble With respect to the color and .Y\~~tenals, the desIgn of the pnncIpal buildmgs and shall be mtegrated wIth other sIte elements (Chapter 9, SectIOn IO.E.3) On the sIte plan, place a note mdIcatm thIS re UIrement. ProVIde a detail of the dum ster enclosure. r;O~-IPment placed on the walls of the buildmgs shall be pamted to match the ~~mg color (Chapter 9, SectIOn 10 C 4). Place a note on the elevatIOns mdIcatm thIS re UIrement. 05 ooftops will be treated as part of the buildmg elevatIOn. All rooftop eqUIpment must be completely screened from VIew at a mInImUm dIstance of 600 feet Cha ter 9, SectIOn 1 I.E. . ~proVIde a detaIl of the monument SIgn, mcludmg the extenor fimsh, colors, SIgn type, and dImensIOns. The SIgn may not encroach mto the required front landsca e buffer Cha ter 21, ArtIcle N, Section 2.B ~ll project sIgnage IS subject to reVIew and approval of the Plannmg & ~evelopment Board. On the elevatIOns, mdIcate the cumulatIve area of all wall sIgnage to ensure that It comphes With Chapter 21, ArtIcle 4, Section C.) In addItion, mdIcate the letter colors and SI matenal. MWR/sc S:\Planning\SHARED\WP\PROJECTS\Gateway Texaco\COUS 03-007\1 ST REVIEW COMMENTS.doc {1)(;. ~..)iW 3cO t.f I r(~M.(/-1.,\..(" .ThY ~ {)\O+''-- W INCLUDE REJECT _~~AA~ 6 <::.- -( ~lP c.- r ;;; k. ~ oJ'I\5? ~f, Michael From Sent: To Subject: Kelley, David Friday June 27 2003 12.34 PM Logan, Laurinda; Rumpf Michael, Johnson, Eric RE Gateway Texaco The station has been there a long time, and as far as I am concerned, they are grandfathered on the access issue Laurinda, refer to my previous response to you on access and stage-storage lane capacity for westbound traffic from "The Harbors" development. Dave -Original Messagem-- From: Logan, Laurinda Sent: Friday, June 27, 2003 12.28 PM To: Rumpf, Michael, Johnson, Eric Cc: Kelley, David Subject: RE. Gateway Texaco I v!efL-lI'vLteLtj d.ovt t nClve 0. better or evell'v C1 d.LffereVtt, soL:AhoVt - for tne reClSOlI'v tJOiA. stClte ClVtc;l bewiA.se of SL-te c'CI/'vstn? L-Vtts : liVt0StLVI ';/ClS WOl/'vv!enV'vC\ vf tn~s WC1S sovt-tetVlL-V'vO we wOo Vttev! to triA CllI'vv! eVtforc'e. U J , J U I n /l? X ?..r... 2:: -Original Message----- From: Rumpf, Michael Sent: Friday, June 27, 2003 12.24 PM To: Logan, Laurinda; Johnson, Eric Subject: RE: Gateway Texaco I have tried to attack this issue on more than one occasion and was repeatedly told that they have no option with the access needs of the fuel delivery trucks I would say that if we have a solution for them that works, we should comment accordingly to bring the site more into compliance. The clean way would be comment to fix it or obtain a variance MR. -Original Message----- From: Logan, Laurinda Sent: Friday, June 27, 2003 8 16 AM To: Johnson, Eric Cc: Kelley, David; Rumpf, Michael Subject: Gateway Texaco SrL-c', TVte LDR oV'vLtJ ClLLows OVte c;lr~vewC1tj -per street froVttClge for gClS stCltL-OV'vS (en Cl-pter 2, Sec,hoVt 1-LL.3 v! (-4-)) Tne CiCltewCltj Te,xClc'o VtclS two OVt rec;lerClL Hv,/tj ClVtv! OVte OVt LClS 'PClLvt-tClS Are tnetj grClVtc;lfCltVlerev! L-Vt or WVt we clS~ tnevvt to dose OVte of tne rev!erClL HWtj v!rL-VewC1tJs c;lowVt? L-C~ "r/L'I/\.';~? X ..r~ i/:;' 1 ,..----- CITY OF BOYNTON BEACH, FLORIDA INTER-OFFICE MEMORANDUM TO MIchael W Rumpf DATE. 7/7/03 Dlr of Plannmg & Zomng SUBJECT Gateway Texaco FROM Off John Huntmgton REFERENCES SIte Plan PolIce Department CPTED Practitioner ENCLOSURES FILE. NWSP 03-007 I have vIewed the above bUIldmg plans and have the followmg comments No Comment. ~ CITY OF BOYNTON BEACH Fire and Life Safety Division 100 East Boynton Beach Blvd POBox 310 Boynton Beach, Florida 33425-0310 PLAN REVIEW COMMENTS For review of COUS 03-007 1st review Project Name and Address Gatewav Texaco 2360 N. Federal Hwv. R+ Rodqer Kemmer, Fire Protection Enqineer Reviewed by. Department: Fire and Life Safety Phone (561) 742-6753 Comments to Sherie Coale bv email on 6/25/03 CODE REQUIREMENTS ~ The site plan and master plan design documents shall adhere to Chapter 9 of the Code of Ordinances of the City of Boynton Beach entitled "Fire Protection and Prevention" This ordinance adopts NFPA 1, Fire Prevention Code, 2000 edition, and NFPA 101, Life Safety Code, 2000 edition (These codes, as amended are identified as the Florida Fire Prevention Code) ~ Prior to Fire Department approval of a building permit, new construction projects must provide the results of a hydrant flow test indicating a fire flow not less than 1500 gpm @ 20 psi above domestic use This applies to new or existing hydrants within the required 200 ft. of the facility cc Steve Gale Bob Borden DEPARTMENT OF DEVELOPMENT BUILDING DIVISION MEMORANDUM NO 03-138 TO Michael W Rumpf Director of Planning and Zoning Timothy K. Large ~ TRC Member/Building Divisi~ FROM DATE June 26, 2003 SUBJECT Project - Gateway Texaco File No - COUS 03-007 - 1 st review ,-- List of Acronvms/Abbreviations: ASCE American Society of Civil Engineers CBB - City of Boynton Beach CBBCO City of Boynton Beach Code of Ordinances CBBCPP - City of Boynton Beach Comprehensive Plan Policy CFR - Code of Federal Regula- tions FBC - Florida Building Code FIRM - Flood Insurance Rate Map F S. - Florida Statutes LDR - Land Development Regula- tions NGVD - National Geodetic Verti- cal Datum of 1929 SFWMD - South Florida Water Management District We have reviewed the subject plans and recommend that the request be forwarded for Board review with the understanding that all remaining comments will be shown in compliance on the working drawings submitted for permits Buildina Division (Site SDecific and Permit Comments) - Timothv K. Larae (561) 742-6352 1 Indicate within the site data the type of construction of each building as defined in Chapter 6 of the 2001 FBC 2 Indicate within the site data the occupancy type of each building as defined in Chapter 3 of the 2001 FBC 3 Buildings, structures and parts thereof shall be designed to withstand the minimum wind loads of 140 mph. Wind forces on every building or structure shall be determined by the provisions of Chapter 6 of ASCE 7, and the provisions of Section 1606 (Wind Loads) of the 2001 FBC Calculations that are signed and sealed by a design professional registered in the state of Florida shall be submitted for review at the time of permit application 4 Add to the building that is depicted on the drawing titled site plan and floor plan a labeled symbol that identifies the location of the handicap accessible entrance doors to the building 2001 FBC, Sections 11-4 1 .2 and 11-4.3 5 Add a labeled symbol to the site plan drawing that represents and delineates the path of travel for the accessible route that is required between the accessible parking spaces and the accessible entrance doors to the building The installed symbol, required along the path, shall start at the accessible parking spaces and terminate at the accessible entrance doors to the building The symbol shall represent the location of the path of travel, not the location of the detectable warning or other pavement markings The location of the accessible path shall not compel the user to travel in a drive/lane area that is located behind parked vehicles. Identify on the plan the width of the accessible route (Note The minimum width required by the code is forty-four (44) inches) Add text to the drawing that would indicate that the symbol represents the accessible route and the route is designed in compliance with Section 11-43 (Accessible Route) and 11-46 (Parking and Passenger Loading Zones) of the 2001 FBC Please note that at time of permit review, the applicant shall provide detailed documentation on the plans that will verify that the accessible route is in compliance with the regulations specified in the 2001 FBC This documentation shall include, but not be limited to, providing finish grade elevations along the path of travel S IDevelopmentlBuildinglTRCITRC 20031Gateway Texaco Page 1 of 2 6 Identify within the site data the finish floor elevation (lowest floor elevation) that is proposed for the building Verify that the proposed elevation is in compliance with regulations of the code by adding specifications to the site data that address the following issues [Section 31071.2, Chapter 31 of the 2001 FBC] a) The design professional-of-record for the project shall add the following text to the site data. "The proposed finish floor elevation _ _ NGVD is above the highest 100-year base flood elevation applicable to the building site, as determined by the SFWMD's surface water management construction development regulations" b) From the FIRM map, identify in the site data the title of the flood zone that the building is located within Where applicable, specify the base flood elevation If there is no base flood elevation, indicate that on the plans. c) Identify the floor elevation that the design professional has established for the building within the footprint of the building that is shown on the drawings titled site plan, floor plan and paving/ drainage (civil plans) 7 On the drawing titled site plan, identify and label the symbol that represents the property line 8 As required by Chapter 4, Section 7 of the LDR, submit a floor plan drawing The building plans are not being reviewed for compliance with the applicable building codes. Therefore, add the words "Floor plan layout is conceptual" below the drawing Add to the floor plan drawing a labeled symbol that identifies the location of the handicap accessible entrance doors to the building The location of the doors shall match the location of the accessible entrance doors that are depicted on the site plan drawing 9 Place a note on the elevation view drawings indicating that the wall openings and wall construction comply with Table 600 of the 2001 FBC 10 At time of permit review, provide a completed and executed CBB Unity of Title form The form shall describe all lots, parcels or tracts combined as one lot. A copy of the recorded deed with legal descriptions of each property that is being unified, is required to be submitted to process the form The property owner that is identified on each deed shall match 11 At time of permit review, submit signed and sealed working drawings of the proposed construction. 12 Add to all plan view drawings of the site a labeled symbol that represents the location and perimeter of the limits of construction proposed with the subject request. 13 According to the CBBCPP 3C3.4, the City shall continue to encourage the use of non-potable water for landscape irrigation An alternate water source other than city water shall be utilized for the irrigation system 14 A water-use permit for the irrigation system is required from the SFWMD A copy of the permit shall be submitted at the time of permit application, F S 373.216 15 The propane gas storage area shall comply with the requirements of NFPA 58 Indicate the capacity of the container, how the container is protected from physical damage, etc. 16 Indicate on the plans what materials will be stored in the storage area. 17 Will the car wash and the Texaco station be under one ownership? If so, a Unity of Title form shall be completed and submitted bf S:IDevelopmentl8uildinglTRCITRC 20031Gateway Texaco Page 2 of 2 ~ DEPARTMENT OF PUBLIC WORKS ENGINEERING DIVISION MEMORANDUM NO 03-139 TO Michael W Rumpf, Director, Planning and Zoning FROM. Laurinda Logan, P E., Senior Engineer DATE July 7,2003 RE Review Comments Conditional Use - 1 st Review Gateway Texaco File No. COUS 03-007 The above referenced Site Plans, forwarded on June 20, 2003, were reviewed by representatives from Public Works, Engineering, and Utilities against the requirements outlined in the City of Boynton Beach Code of Ordinances Additionally, the adjacent lot, which is depicted on this plan, has previously been submitted to the City as a new site plan The comments generated from that submittal, in November 2001, were also reviewed here The civil plans provided are for Marouf's Car Wash, which was also submitted under separate cover as a new site plan No civil plans for the Gateway Texaco were found and therefore a complete review is not possible However using the available information key elements were looked at and we offer the following comments with the appropriate Code and Land Development Regulations (LDR) referenced PUBLIC WORKS - GENERAL 1 Prior to permit application contact the Public Works Department (561-742-6200) regarding the storage and handling of refuse 2. Provide dumpster enclosure detail(s) (LDR, Chapter 2, Section 11.J 2.b, Chapter 75, Article II, Section 5 J , and Article III, Section 9.A.9.a, Chapter 9, Section 10 C 3 and City Standard Drawing G-4 ) PUBLIC WORKS - TRAFFIC 3 Provide a traffic analysis and notice of concurrency (Traffic Performance Standards Review) from Palm Beach County Traffic Engineering 4 On the Site and Civil plans, show and identify all necessary traffic control devices such as stop bars, stop signs, double yellow lane separators striping, directional arrows and "Do Not Enter" signage, etc. Delineate and stripe the "Loading Area" (LDR, Chapter 2, Section 11 J) include a pavement message in yellow indicating "No Parking - Loading Zone" See City Standard Drawings "K" Series for striping details and City Standard Drawings G-9 through G-12 for signing details 5 For the handicap accessible parking space provide elevations on the site and civil plans to illustrate accessibility The sidewalk shall be same elevation as the adjoining pavement or you may show the sidewalk at the same elevation as the five-foot accessible path with 1 12 ramps up in both directions (FL Accessibility Code 4 6 3) This needs to be reflected in the details. Dept. of Public Works/Engineering Division Memo No 03-139 RE Gateway Texaco, Conditional Use - 1st Review, COUS 03-007 July 7,2003 Page 2 6 Show an appropriate handicap parking post sign (or on the building) for the handicap space. 7 Show parking stops on the plans These will be required to prevent vehicles from overhanging sidewalks and reducing accessible width 8 Provide "One-Way" arrow signs in the Federal Hwy median across from each egress driveway 9 Show on the site plan a thirteen (13) foot ingress/egress easement through the gas station site to agree with the plan dimensions. Provide an acceptable document with your resubmital for review and approval ENGINEERING 10 Numerous omissions have been noted on these proposed plans and in this review comments report. Drawings need to be thoroughly checked and coordinated by the consulting engineer It is the responsibility of the consulting engineer to familiarize himself with the City of Boynton Beach Land Development Regulations prior to submission of plans Quality control is the responsibility of the consulting engineering - not the City of Boynton Beach 11 All comments requiring changes and/or corrections to the plans shall be reflected on all appropriate sheets 12. Please note that changes or revIsions to these plans may generate additional comments. Acceptance of these plans during the TRC process does not ensure that additional comments may not be generated by the Commission and at permit review 13 Proof of other agency permits shall be required prior to the issuance of the paving and drainage permit. 14 Provide written and graphic scales on all sheets, including the Survey 15 Specify use of the FDOT Standard Specifications for Road & Bridge Construction and Standard Index, 2000 Edition, as the construction standard 16 Separate plans for "Gateway Texaco" and "Marouf's Car Wash" Each plan is a separate submittal and is reviewed, each on its own merits, and using the guidelines established in the LDR for the type submittal (eg Conditional Use, New Site Plan, etc.) Plans for the adjacent lot may be shown for informational purposes only 17 Show zoning and land use on Site Characteristics Map (Survey) (LDR, Chapter 4, Section 7.A.) 18 Show all existing utilities on Site Development plan (LDR, Chapter 4, Section 7.A.3) 19 Show all existing easements, including ingress-egress, water, sewer, gas, telephone, etc., on the Site and Civil plans (LDR, Chapter 4, Section 7.A.3) 20 Will the 10ft. ingress-egress easement in the northerly portion of Tract "A" be abandoned? Oept. of Public Works/Engineering ~ivision Memo No 03-139 RE. Gateway Texaco, Conditional Use - 1st Review, COUS 03-007 July 7,2003 Page 3 21 Sidewalks shall be 4 feet wide along local streets, and 5 feet wide along streets of higher classification (LOR, Chapter 6, Article IV, Section 10 T , and Chapter 22, Article I, Section 5) 22 Sidewalks shall meet or exceed State Handicap Code requirements and comply with the Standard Building Code and amendments thereto (LOR, Chapter 23, Article II, Section K) 23 Show proposed site lighting on the Site, Civil, and Landscape plans (LOR, Chapter 4, Section 7 B 4 ) The lighting design shall provide a minimum average light level of one foot-candle Lighting levels under the canopy only, shall not exceed 60 foot-candles On the Lighting Plan specify that the light poles shall withstand a 140 MPH wind load (LOR, Chapter 23, Article II, Section A.1.a and Florida Building Code) Provide a note that the fixtures shall be operated by photo-electrical control and are to remain on until 2 00 a.m (LOR, Chapter 23, Article II, Section A.1.a) Include pole wind loading, and pole details in conformance with the LOR, Chapter 6, Article IV, Section 11, Chapter 23, Article I, Section 5 B 7 and Chapter 23, Article II, Section A on the Lighting Plan Glare, which is readily perceptible at any point at or beyond the property on which the use is located, is prohibited (LOR, Chapter 2, Section 4 N 7) Lighting shall be directed away from any residential uses (LOR, Chapter 2, Section 4 N 7) Lighting shall not be used as a form of advertising in a manner that draws more attention to the building or grounds at night than in the day (LOR, Chapter 9, Section 10 F 5) If possible please provide photometrics as part of your TRC plan submittals - it is much easier to identify and correct any deficiencies now than while you are waiting on a permit! 24 It may be necessary to replace or relocate large canopy trees adjacent to light fixtures to eliminate future shadowing on the parking surface (LOR, Chapter 23, Article II, Section A.1 b) 25 Show sight triangles on the Landscape plans (LOR, Chapter 75, Article II, Section 5 H) Use 25 (twenty-five) foot triangles for the driveway ont%ff of Las Palmas Please note, in accordance with the referenced section of the LOR, that the sight triangles are placed at the intersection of the property line and side of accessway Use FOOT Standard Index 546 for the sight triangles along Federal Highway, following that standard for triangle placement. 26 Indicate, by note on the Landscape Plan that within the sight triangles there shall be an unobstructed cross-visibility at a level between 25' and 6' above the pavement (LOR, Chapter 75, Article II, Section 5 H ) 27 Landscaped areas shall be protected from vehicular encroachment by a continuous, raised curb (LOR, Chapter 7 5, Article II, Section 5.A. and Chapter 22, Article II, Section E) Add Type "0" curb around the landscaped area defining the parking lot adjacent to Federal Hwy 28 The medians on Federal Highway and the chase area(s) in the vicinity of this project have existing irrigation and plant material belonging to the City of Boynton Beach Any damage to the irrigation system and/or plant material as a result of the contractor's operations shall be repaired or replaced to the equivalent or better grade, as approved by the City of Boynton Beach, and shall be the sole responsibility of the developer Please acknowledge this notice in your comments response and add a note to the plans with the above stated information 29 The LOR requires the Landscape plan scale to match that of the Site plan (LOR, Chapter 4, Section 7 C 1) The use of a 1 0 scale is preferred 30 Ficus is not a permitted species (LOR, Chapter 7 5, Article II, Section 5 C 2) Specify an alternative species for the proposed Ficus hedge. Dept. of Public Works/Engineering Division Memo No 03-139 RE Gateway Texaco, Conditional Use - 1 st Review, COUS 03-007 July 7, 2003 Page 4 31 The landscaping materials at the driveways need to have a clear line of sight to a minimum of 7 (seven) ft. high (eg Pigeon Plums may interfere depending on how specification called out.) 32. The General Notes and Transporting Notes, Landscape Plans Sheet L-1, are repeated on Sheet L- 1A and L-2. Please delete one set. 33 On Paving & Grading Plan sheet 2 of 3 the written legend does not match the symbols used in the plans, specifically existing and proposed elevations Please correct discrepancy 34 Provide an engineer's certification on the Drainage Plan as specified in LDR, Chapter 4 Section 7 F 2. 35 Full drainage plans in accordance with the LDR, Chapter 6, Article IV, Section 5 will be required at the time of permitting Any work done within the right-of-way and/or to existing facilities within the right-of-way of Federal Highway will require review, approval and permitting by the Florida DOT 36 Provide existing and proposed elevations for Parcel "A" 37 Indicate by note that catch basin and manhole covers shall be bicycle proof (LDR, Chapter 6, Article IV, Section 5.A.2.g) 38 Specify storm sewer diameters, inlets types, etc. on drainage plan Indicate grate, rim and invert elevations for all structures Indicate material specifications for storm sewer 39 The Site Survey indicates a propane storage area in the northwest corner of Parcel "A," that is not shown on the Paving & Grading Plan sheet 2 of 3 (although a "Propane Gas Storage area in shown on the Site Plan w/ Proposed Addition Sheet 1 of 4) Please ensure that all site features are reflected on the appropriate sheets 40 Indicate, on all appropriate sheets, surfacing material(s) for the parking lot. 41 Please increase size of details for legibility 42 Increase size of the General Notes on Paving & Grading Plan sheet 2 of 3 for legibility 43 Paving, Drainage and site details as shown on Site Development sheet 3 of 3 will not be reviewed for construction acceptability at this time The details provided are outdated All engineering construction details shall be in accordance with the "City of Boynton Beach Engineering Design Handbook & Construction Standards and will be reviewed for constructability at the time of construction permit application The Engineering Design Handbook may be obtained by contacting the Engineering Division UTILITIES All utility easements shall be shown on the site plan and landscape plans (as well as the Water and Sewer Plan) so that we may determine which trees may interfere with utilities. In general, palm trees will be the only tree species allowed within utility easements. Canopy trees may be planted outside of the easement so that roots and branches will not impact those utilities within the easement in the foreseeable future The LDR, Chapter 7 5, Article I, Section 18 1 gives public utilities the authority to Dept. of Public Works/Engineering Division Memo No 03-139 RE Gateway Texaco, Conditional Use - 1st Review COUS 03-007 July 7 2003 Page 5 411' Remove any trees that may interfere with utility services, either in utility easements or public rights- /' of-way 45 Fire flow calculations will be required demonstrating the City Code requirement of 1,500 g pm. as stated in the LDR, Chapter 6, Article IV, Section 16, or the requirement imposed by insurance underwriters, whichever is greater (CODE, Section 26-16(b)) 46 Comprehensive Plan Policy 3 C 3 4 requires the conservation of potable water City water may not, therefore, be used for irrigation where other sources are readily available 47 The LDR, Chapter 6, Article IV, Section 16 requires that all points on each building will be within 200 feet of an existing or proposed fire hydrant. Please demonstrate that the plan meets this condition, by showing all hydrants 48 Appropriate backflow preventers will be required on the domestic water service to the building, and the fire sprinkler line if there is one, in accordance with the CODE, Section 26-207 49 The LDR, Chapter 3, Article IV, Section 3(P) requires a statement be included that utilities are available and will be provided by other appropriate agencies This statement is lacking on the submitted plans 50 Utility construction details as shown on Civil Engineering (CE) sheets 3 of 3 will not be reviewed for construction acceptability at this time All utility construction details shall be in accordance with the Utilities Department's "Utilities Engineering Design Handbook and Construction Standards" manual, they will be reviewed at the time of construction permit application. 51 Likewise, the Paving, Drainage and site details as shown on CE sheet 3 of 3 will be reviewed for constructability at the time of construction permit application Cc: Jeffrey R. Livergood, P E., Director, Public Works (via e-mail) Peter V Mazzella, Deputy Utility Director, Utilities H David Kelley, Jr , P E.I P S M , City Engineer, Public Works/Engineering (via e-mail) Glenda Hall, Maintenance Supervisor, Public Works/Forestry & Grounds Division Larry Quinn, Solid Waste Manager, Public Works/Solid Waste Ken Hall, Engineering Plans Analyst, Public Works/Engineering (via e-mail) File S:\Engineering\Office Associates File\Logan\03-139 Gateway Texaco 1st Review.doc GATEWAY TEXACO COUS 03-007 1st Review Planning August 1, 2003 ThIS proJect reqUIres condItional use approval. ProvIde JustificatIOn for approval of the proJect based on the standards for evaluatmg condItional uses found m Chapter 2, Section Il.2.D of the CIty of Boynton Beach Land Development RegulatIOns. No dnveway shall be located less than 110 feet from the mtersectmg nght-of-way lmes ofpubhc streets (Chapter 2, Section I1.L.3.d(l) Dnveways shall not be located less than 30 feet from any mtenor property lIne from the mtersectIOn of the nght-of-way lmes along local streets and 180 feet along streets of hIgher classIficatIOn such as U S 1 (Chapter 23, ArtIcle II.H.3) Dnveways are lImIted to one (1) per street frontage (Chapter 2, SectIOn 11.L.3.d(4) Either revise the plans to comply or request a variance from these code requirements. The rear setback IS 20 feet (Chapter 2, Section II.L.3 e(3) Either revise the plans to comply or request a variance from this code requirement. No canopy shall be located less than 20 feet from any property lme (Chapter 2, Section I1.L.3.e (a) Either revise the plan to comply or request a variance from this code requirement. No gasohne pump Island shall be located less than 30 feet from any property lme (Chapter 2, SectIon I1.L.3.e(b) Either revise the plan to comply or request a variance from this code requirement. A 10-foot WIde landscape buffer shall be located along the street frontage (Chapter 2, SectIOn 11.L.3.f(1) Also, except for permItted drIveway opemngs, a five (5) foot WIde landscape buffer shall be located around that portIon of the parcel of whIch the gasolIne dispensmg estabhshment IS located (Chapter 2, Section I1.L.4.b) Either revise the plan to comply or request a variance from these code requirements. All SIgnS must meet a mImmum of IO-foot setback measured from the property lIne to the closest surface of the SIgn (Chapter 21, ArtIcle III, Section 5) Either revise the plan to comply or request a variance from this code requirement. On the SIte plan (sheet 1 of 4), mdIcate the dIstance from the subJect parcel to the nearest reSIdential structure ThIS proJect reqUIres a total of 10 parkIng spaces (1,719 square feet + 681 square feet @ 1/250 = 10 spaces) The backup dIstance for the new angled parkIng spaces must be reVIewed and approved by the Engmeenng DIVISIOn. The SIte plan should show the hmIts of the east-west mgress / egress easement. A dramage statement IS reqUIred pnor to the TechnIcal ReVIew CommIttee meetmg (Chapter 4, Section 7.F.2 ) A traffic Impact statement IS reqUIred pnor to the Techmcal RevIew CommIttee meetmg (Chapter 4 Sechon 8.F) Include a color rendenng of all four (4) elevations at the Techmcal ReVIew CommIttee meetmg (Chapter 4, Section 7.D) ProVIde pamt swatches for the elevatIOns (Chapter 4, Section 7.D) Proposed landscape matenal m the nght-of-way IS subJect to reVIew and approval of the Engmeenng DIVISIOn of PublIc Works. The landscape plan tabular lIst needs to be updated m reference to the "Intenor Trees" By code, two (2) "mtenor" trees would be reqUIred smce 12 parkIng spaces are proposed (Chapter 7.5, ArtIcle II, Section 5 G) ReVIse sheet "L-I " to mdIcate thIS reqUIrement. Ensure that all the proposed plant quantIties correspond between what IS shown on the graphIc illustrahon and ItS correspondmg plan lIst on sheet "L-I" The removal/relocation of landscape matenal IS subJect to reVIew and approval of the CIty Forester / EnvIronmentahst. The Dahoon Holly trees are to be spaced no less than 30 feet apart from each other A SIgnature tree (such as a Yellow Elder, Tibouchma Granulsola, or Bouganvillea) IS reqUIred at both SIdes of each proJect entrance / eXIt. The SIgnature trees must have 6 feet of clear trunk If placed WIthm the safe-sIght tnangle (Chapter 7.5, Article 2, SectIOn 5.N) Alternative plant matenal may be substItuted If the above referenced plant matenalIs not available or undeSIred. Any substitutIon of plant matenal (for the SIgnature tree reqUIrement) will be subJect to the CIty Forester / EnVIronmentahst reVIew and approval. All trees are reqUIred to be at least 12 feet overall heIght at the time of mstallatIOn (Chapter 7.5, ArtIcle II, SectIon 5 C.2.) All shrubs and hedges are reqUIred to be at mImmum 24 mches m heIght, 24 mches m spread, and planted WIth tIp-tO-tIp spacmg measured ImmedIately after plantmg to adequately cover the planted areas on the SIte (Chapter 7.5, ArtIcle II, Section 5 C 4 ) FIfty percent (50%) of SIte landscape matenals must be native speCIes. IndIcate the amount of native matenal m the plant lIst of the landscape plan (Chapter 7.5, ArtIcle II, SectIOn 5.P) Please mdIcate by astensk, the native speCIes and ensure that at least 50% of landscape matenal IS native The base of the monument SIgn must be enhanced WIth colorful groundcover plans and a mInImUm of two (2) shrub speCIes all selected for entrance compatibilIty (Chapter 7.5, ArtIcle II, SectIOn 5 0 ) All elevatIOns (sheet 4 of 4) must mdIcate the proposed colors, mcludmg the pamt manufacturer's name and color code (Chapter 4, SectIOn 7.D) Please coordmate WIth the City's Planner / Urban DeSIgner (Ms. Margelly Beltran @ 742-6263) WIth regards to the proposed buildmg colors. Non-word depIctIOns on SIgnS shall be hmIted to 20% of the area of the SIgn erected. Color limItatIOn shall not apply to non-word depIctions on SIgnS (Chapter 9, SectIOn 10.1.4 ). The dumpster enclosure shall resemble wIth respect to the color and matenals, the desIgn of the pnncIpal buildmgs and shall be mtegrated wIth other site elements (Chapter 9, SectIOn 1O.E.3 ) On the sIte plan, place a note mdIcatmg thIS reqUIrement. ProVIde a detail of the dumpster enclosure. EqUIpment placed on the walls of the buildmgs shall be pamted to match the buildmg color (Chapter 9, Section 10 C 4) Place a note on the elevatIOns mdICatmg thIS reqUIrement. Rooftops will be treated as part of the buildmg elevatIOn. All rooftop eqUIpment must be completely screened from VIew at a mImmum dIstance of 600 feet (Chapter 9, Section II.E.) ProvIde a detail of the monument SIgn, mcludmg the extenor fimsh, colors, SIgn type, and dImensIOns. The SIgn may not encroach into the reqUIred front landscape buffer (Chapter 21, ArtICle N, Section 2.B ) All proJect sIgnage IS subJect to reVIew and approval of the Plannmg & Development Board. On the elevatIOns, mdIcate the cumulative area of all wall signage to ensure that It complIes WIth Chapter 21, ArtIcle 4, SectIOn C) In addItion, mdIcate the letter colors and SIgn matenal. ~* 33.36' "TEXACO" lOGO AND lETTERING - EXISTING SIGNAGE ~:l 24.76' Lf~~@ [P@@cdJ [}YA]@~ "Food Mart" IDENTIFICATION- ~%. 22 76' EXISTING SIGNAGE ~ OPEN ~1 20.761 Car Wash "Car Wash" - NEW SIGNAGE ~:t. 15 76' OPEN -$:f: 13.76' lLDlTil[l@@~@~ i1 a ~@ [?>@\VA"J@[f i1 JID]1 "Gasoline" PRICE INDEX- [?>Ol1ll@ EXISTING SIGNAGE [?>@\VA"J@[f ~a~~ ~:I: 8.16' [?> ~11i1il 0 l1ll11i1il [Q)O@@@O ~a@~ "Diesel" PRICE INDEX- ~%. 6 16' EXISTING SIGNAGE OPEN EXISTING GRADE 8 G~8. 8 EXISTING SIGNAGE WI PROPOSED ADDITION 1/4 SC GATEWAY TEXACO 2360 NORTH FEDERAL HIGHWAY BOYNTON BEACH, FLORIDA 33435