REVIEW COMMENTS
6.C.l
GROVE PLAZA CAR WASH
(NWSP 02-007)
NEW SITE PLAN
DEVELOPMENT DEPARTMENT
MEMORANDUM NO. PZ 02-121
SITE PLAN REVIEW STAFF REPORT
PLANNING & DEVELOPMENT BOARD AND CITY COMMISSION
June 17, 2002
DESCRIPTION OF PROJECT
Project Name/No.. Grove Plaza Car Wash / NWSP 02-007
Property Owner. David Daszkal
Applicant: David Daszkal/ Daszkal Development, LLC
Location: Parcel "E" of Grove Plaza Replat, southeast corner of Lawrence Road and
Hypoluxo Road
Land Use: Local Retail Commercial (LRC)
Zoning: Community Commercial (C-3)
Project size:
Adjacent Uses:
North:
South:
East:
West:
Proposal:
Site Area:
Building:
Fabric Shelters:
Covered porch:
Lot Coverage:
0.867 acres /37,768 square feet
3,596 square feet
2,907 square feet
675 square feet
7,178 square feet (19%)
(see Exhibit "A" - Location Map)
Hypoluxo Road right-of-way; farther north is Santaluces High School with a Institutional land
use classification (unincorporated Palm Beach County) and zoned Public Ownership (PO);
Drainage Utility & Ingress/Egress Easement, farther south in developed residential
development with a Medium Density Residential (MR-5) land use classification
(unincorporated Palm Beach County) and zoned Agricultural Residential (AR);
Vacant Parcel "F" of Grove Plaza Replat with a Local Retail Commercial (LRC) land use
classification and zoned Community Commercial (C-3);
Vacant Parcel "0" of Grove Plaza Replat with a Local Retail Commercial (LRC) land use
classification and zoned Community Commercial (C-3).
Daszkal Development, LLC proposes to construct a one-story, 3,596 square foot car wash
facility with 3,582 square feet of covered porch and fabric shelter areas. This project is
being reviewed concurrently with the master plan modification (MPMD 02-001). A carwash
is a permitted use in the C-3 zoning district.
Site Characteristics: The subject property (Parcel "E") is one (1) of six lots of the Grove Plaza master plan.
Parcel "E" of the master plan was originally approved for a fast-food restaurant. The
property is surrounded by a 15-foot wide landscape buffer to the north, Tract "G" (ingress /
egress easement) to the east and south, and Parcel "0" to the west.
Page 2
Grove Plaza Car Wash- Site Plan Review Staff Report
Memorandum No. PZ 02-121
Concurrency'
a. Traffic - A traffic impact statement for this project was submitted and sent to the Palm Beach
County Traffic Division for their review and approval. The Palm Beach County Traffic
Division determined that the project meets the Traffic Performance Standards of
Palm Beach County since the proposed use generates less than 200 new daily trips
(in excess of that previously vested by partial development of the master plan).
b. Drainage - Conceptual drainage information was provided for the City's review The City's
concurrency ordinance requires drainage certification at time of site plan approval.
The Engineering Division is recommending that the review of specific drainage
solutions be deferred until time of permit review, when more complete engineering
documents are required.
Driveways: Tract "G" is the common area which accommodates the access drives, drainage and buffer
wall and landscaping for the Grove Plaza commercial/ retail development. Tract "G" allows
for vehicular ingress/egress to the subject site from Hypoluxo Road. The only point of
ingress / egress from Tract "G" to the subject property will be located along the east property
line. This project does not propose any direct connection onto Hypoluxo Road. The project
will share and utilize Tract "G" with the other parcels. Tract "G" will not be affected as a
result of the proposed development. However, direct access that was originally planned
between the subject property and Parcel "0" (parcel to the west) will be eliminated and
replaced with a landscape buffer
Parking Facility. The Land Development Regulations do not specifically indicate a required parking ratio for
the car wash. According to Chapter 2, Section 11.H.5 no fewer than four (4)-parking spaces
shall be provided for any nonresidential use. Therefore, the proposed use will require the
minimum four (4) spaces for a commercial project. The project proposes nine (9) parking
spaces, including one (1) handicap parking space. All parking spaces will be 90 degrees
and dimensioned nine (9) feet in width by 18 feet in length, except for the handicap space,
which will be 12 feet in width (with 5 feet of striping) by 18 feet in length. The backup
distance of the parking lot is 27 feet in width. Parking will be proposed on the eastern half
of the subject property The west property line, where the access drive to Parcel "0" was
once proposed will be replaced with exit lanes of the car wash.
As proposed, vehicles enter the site from Tract "G" from the east and are directed northward
towards the tunnel entrance. As vehicles pass through the car wash, they exit the building
from the south and are faced with two options. Patrons may either utilize the by-pass lane
to exit the facility or proceed to one (1) of five (5) service lanes for extra detailing. Each
service lane could accommodate approximately two (2) cars.
Landscaping:
A landscape buffer 15 feet in width is proposed along the north property line adjacent to
Hypoluxo Road. Southern Red Cedar shade trees and Washingtonia palm trees are
proposed within this buffer Also, the proposed landscape material along Hypoluxo Road
will consist of Redtip Cocoplum hedges, Pentas, and Dune Sunflower The Dune Sunflower
plants, however, will be planted on both sides of the row of Redtip Cocoplum and will be
visible from both Hypoluxo Road and the interior of the site.
The proposed car wash will be built along the west property line since the C-3 zoning district
allows for a zero (0) side-building setback. The building proposed within the west
landscape buffer will be 124 feet in length. The entire length of the west property line is 249
feet so therefore, the remaining 125 feet of landscape buffer will consist of Cabbage palm,
Page 3
Grove Plaza Car Wash- Site Plan Review Staff Report
Memorandum No. PZ 02-121
Washingtonia palm, and Southern Red Cedar trees. A row of Redtip Cocoplum hedges will
be planted at the base of each tree.
The southern landscape buffer adjacent to Tract "G" will be at least 15 feet in width and will
contain a portion of the retention area. The dumpster enclosure, located within this
landscape buffer towards the southwest corner of the site will have Redtip Cocoplum
hedges planted on all three (3) sides. In addition, two (2) Cabbage palm trees are proposed
to partially conceal the enclosure from the northern view Dune Sunflower is also proposed
in front of the Redtip Cocoplum hedges.
The east side landscape buffer will be similar to the others in that it will contain the same
landscape material. The monument sign is proposed in the northeast corner of the
property Scarlet Hibiscus hedges, Washingtonia palms, Dune Sunflower, and Pentas are
proposed around the monument sign.
All landscape buffers adjacent to roadways will have landscaping that will conceal the
vehicular use area. The plan provides a total of 44 trees and 1,562 shrubs and satisfies the
native plant material requirement.
Building / Site: Building and site regulations will be fully met when staff comments are incorporated into the
permit drawings. The building footprint of the main carwash building will be 3,397 square
feet in area. This area consists of the car wash tunnel, lobby, equipment room, office, and
vacuum room. This excludes the 675 square foot covered porch area and a 199 square
foot service building. The covered porch area will be connected to the front of the building
(which faces Hypoluxo Road) and will be the location where the vehicles enter the car wash
building. The entrance to the covered porch that leads into the building will be at least 10
feet in height. Likewise, according to the applicant, the canopy area will have a 10-foot
clearance.
The maximum height allowed for new buildings in the C-3 zoning district is 45 feet or 4
stories. According to the east elevation, the peak of the cornice molding at top of the
covered porch area will be 24 feet in height. A waiting patio is proposed near the rear of the
building.
Community Design: This project was reviewed in part, according to the standards as identified in the Grove
Plaza Design Guidelines (1998). The design is compatible with the surrounding built
environment and will generally enhance the overall commercial area. The principle building
and trim colors are compatible with the colors of the Grove Plaza Design Guidelines (1998).
The exterior of the middle wall area, which contains the greatest portion of the wall mass,
will have painted light textured stucco finish in a tan color (Behr - Spinx 2A 19-4). The lower
wall area will have an 8" by 16" broken face concrete block finish with dark brown color
(Behr - Rio Grande 3B21-6). The lower and middle wall area will be accented with half-
round decorative molding with a painted light textured finish in a cream color (Behr - Rice
Cake 3B17-1). The top third of the building, painted cream like the main portion, will also
have 8" by 8" brown colored accent stucco tiles. Above each window will be a polyethylene
awning with a metal frame. The awning fabric will be "brown" with one (1) six-inch '1an"
stripe. The frames will be white. The canopy, where vehicles will be detailed, will have a
tabular steel frame space structure. This will support the polyethlyene canopy The canopy
will be white and brown to match the building colors. Decorative metal outdoor lighting
fixtures will be attached to the building. They will be painted red.
Signage:
A freestanding monument sign is proposed in the landscape buffer at the northeast corner
Page 4
Grove Plaza Car Wash- Site Plan Review Staff Report
Memorandum No. PZ 02-121
of the site. Although an exact dimension was not provided, it appears that the top of the
monument sign will be approximately 7 feet - 4 inches in height. The Grove Plaza Design
Guidelines (1998) regulates the size and color of monument signs. For example, the
maximum allowable signage area (sign face) for a monument sign is 60 square feet. The
monument sign may be single or double-face and shall be made of stucco/masonry
construction colored either white or off-white. All elements, including the height, color, and
material of the monument sign would need to comply with the Grove Plaza Design
Guidelines (1998). Staff also recommends placing the site address at the top of the
monument sign (see Exhibit "C" - Conditions of Approval). The "Motor City Car Wash"
letters will be made of plastic and red in color The "Time to Shine" letter will be blue.
Wall signs are proposed on three (3) building sides and collectively, cannot exceed the
maximum allowable signage area (72 square feet / See Exhibit "c" - Conditions of
Approval). The front fayade (north) will have a sign with red "Motor City and Car Wash"
letters and blue "Time to Shine" letters. It will also contain an operating clock. The other
two (2) signs omit the "Time to Shine" letters and operating clock. They are proposed on
the east and west facades. No signs are proposed on the building's south fayade. All other
site signage, such as the menu board and directional signs shall comply with the
requirements as specified in Chapter 21 of the Land Development Regulations (see Exhibit
"C" - Conditions of Approval).
RECOMMENDATION:
Staff recommends that this site plan request be approved subject to the comments included in Exhibit "c" -
Conditions of Approval. The Technical Review Committee (TRC) recommends that the deficiencies identified in
this exhibit be corrected on the set of plans submitted for building permit.
xc: Central File
S:\Planning\SHARED\WP\PROJECTS\grove plaza\Car Wash MPMD & NWSP\NWSP\Staff Report.doc
LOG~~!!z?~w~ap
EXHIBIT "A"
!-~-
1'1
,
,
-I i 11-----1 ,1,
1~r---1II!ii';\:"'II,II~1
~1J;t'(1~_(J~e-~ r--=~
: " L', ~ i r-- I '1i'3!' III
~r-----I---j----<' r~ ~\J L --i'r-~'-:- -;rr
I I --"l'L-.c I ~~ R1
, I G ~ hi [I II II 'l~=; ',=I ,L'C,:~!I:- PU
I P'ri: ~I 'J.,,',lSITEE,:~J,~~,'~-_ 0
f'JQ,F,'IRn City !'LaJ.t Il,1 II" I, ',"--1 ~- ,="
I I P I IIJfi'\lIrH\i I I Ii,' i\J _~ ~",~.~_:lif--
I '---' ~"II"''''r-c~
, 'JiI=1 ' I ' '1,',I"~~~i..clli
, f= r , I -l,LJ~LCL~' ",' ,~
I I ,w ,I I I ~' IIIITI
"~I!!' I," 'II, ,~",,:=;I ~~b
j I i I ~ c----c=:r:- 7""'1- ' ,I ,- ~'-"-I" ,II ' I --;--;-: I t:::1
~:::I:IDf-- r'~ I c-c"c""" lc::~' PUD
-.ll..~' Dr:: I!I ,--,~~M1::E,~ l::lr-- ",~ --=
, c "'_ " F" '~,'--' c~ ~~, '/J' r ~,
1, I' KiT, AGll:~ej . 'PUr5 'iC.cc "M\3a(lQWs" :
, ,cc'.. ,;::cj c- ! i,l,r.,I'! ~\,^,n,~1(~G! ,'ro vJLeT LI =--,~ . - ']-'-',' ,
5i Ijj=U : r' ~ I ! ,/r'U- t'J'\t':1~~, ~ - ~ - ~ q
'I' II' 1,[ 1,DJI1lII'"II',llllill!I" ,', ' ' J'rm>~H
l-J, .-.:Jl.L .
I " I! "'1"1';
II; I ir:J:I2[: I -, ~ I,"
I il-- - L ,1,_ I ~-" I II '
i - TIIIIIJD'OO'-:;U11I!r"d! I " I "I, .,,1, '
",,' , II' ". t::l \ I - ~ ,- ~Irj
, I ,_,' '~ ' , ,J;3 ~~. .,~':: '- , " Hir::;
;~i ~,~- ~ ~J ~__ I' ..,f '( . 1"'iS:-c,...L.u.'- ! j. ' f=j:::J :...'- '- -r:;-,
'~~,"' 7J: II !' ,,'I -, c-iwreO(i), ~"I ,! I e-i--1t:-l:::! IL.' " .
I i.;;,'~ " ~ ~,,'i"tI. ~ .....L- c--c. ' ' ,. '
S ~I~,~';:--inr- I ",ii.~ ,r'r:Oy~~ill;~' ,II I,'I~III', d=,,~_'
~.~ cl~-'! ' I~I~, I' - " I
. " .""",,'11 ' ",""-' ' .ci.JL.; , ~'I ~
,~~c: ,~
soo 0 SOD
1000 1500
I' ~:::Cjl i I i I I I -j---C ! . - c; :
1_---=1
c-"
,~
~:=l
LLI~
~,.-,- ~
~ il't~
..t----'--i!':~
'iB
t'C:
e~2
Ed' :E [B
~i"~'1'
,... Sj
-~2
c~
t:t:
H=i
2000 Feet
,
W~E
s
!$
H""'"
\
',-
~
[1:11
,.AI
..0
~ 'U
.0
-(I>
~ "'
~O
..
f-
o
o
AI
'U
r
I>
Z.
I~
i
.
~
s. '
2' ',',
; 1
I I ~
:11
I
I
~ .
.
! .
.
.
i)>1Ii I ~;!! I~l
II i:.8 1 ·
!I\) I hi
/
I
I
~n_-__m_n_m_n_-.c::::- T---i1
/ I (j '-,- , I'
/ A~'\ ~ ,--- --"" ""'~' ,"r..I..'
.....J /' />\ " L. .~ ,I
\~ '\ "":.~/I'
.y II
/~\ \ i'
C\
I ,
j'ii'
I'
dOH i I ~
--- 0
.,.",
,
\ 1
H Il:~ :'-rli~1
-,t, ;, It--;;-'t;.- ", - ,~jF'
, ,II 'I I, , '
': I Ii II
. ii 'h~'!. t 1.1
.'1 .' ~Ii I
) , " r:', I!. fll
: .J!... : '~:L"~.:
.
~I
" '
"
, ,!I
io.l !I I
!i.
I,
,~
1'0
,I~
,I~
[
1
00 0
D___O=----==!
l' 5:0: ! 1 I
rn
I
1
I
_______J
I;J
I '6 N~W "ULL-S~RVIC~ CAR WAS:H
~ for Mr. David DQ!:zkal
~ II Boynton BQaeh, Palm BQQch County,
. .
EX.,IBIT
Iii
'I
II '
II t
d
I,
Ii
II
,
IIAIl
a ICJ'
!P~
I ~~
e
~~
; E'fR'.
I I r
I I
r. ,
Wr
~
,
.
BAC
~~..!2.c.:.~.:.c~::ct CO~'p;;:'~,~:.I~:
I=lotida ~:::;---:;-......- ~.__ '..::;;:.,:;:.:.::~
!'ilJ
pi
..0
,lJ
~O
:(1)
.- In
'!O
In
~
In
;U
o
;U
In
r
In
~
-l
o
Z
(I>
::I
J>
Z
lD
<=
r
o
Z
~
I
I
)>>. II' ;i I Rl
I f I ii f'
(,.) 1.,
E
In
(I>
-l
In
r
In
-<
J>
-l
o
Z
h
I IIH ~
~tl
~ l
x
IIH -I
I ~II
I
I c
! Ik
, I '"
.
,
I II
I II ~
I .1 .
I I j
..c I
I
I i
! c ~
.
~ .
I .
I ."
. 1IlllI~11I1I II.
g
<=
-l
I
In
r
In
-<
J>
-l
o
Z
=m
I
I
! i
di
~I'I
dl,
'I P
;ul
III I
:Ii!
~ I P
'Ill
i III
III
! I
"H!
I ! ~ "
!Iii
III
l
I
I
EXHIBIT II A"
In ~
J>
(I> .~
-l II
m II
r ,
m ." t
-<
J> II
-l ~, I 'i
0 ~!
z
,
!
l
- "I ,
., ljll !
I
I "IH~i
I H ii-
!II 'I ' i . I
Ip ! III
II! l ! lill
I l I III i. .lj
;1' ql! I!! I
iii '''' I III qi I
Ip IIH !l~ I ! i
Iii ji: I I d
III II . 'I ~
q. ~!!.1
II! . !dli!
IH ! ~~ I II'
HI ...... Iln I
II' I ~
. I ! I r
~ l . I
I I
I I II..... II
U... !'
z
o
;u
-,
I
m
r
m
~
-l
~
l:!1
'-II
I,
!i'l
~lli
l!h
!Ij.
II'
"11'
lill
!1'1
;!l
I td(;W J:ULL-!:(;RVIC(; CAR WA!:~ DAC -'i
'fo.. MI". Dllvfd Da!:zlutl C> I
r~ RAC 8oc. Architect Corpor"Uonl
~ n B~y.!!_~_~~__Bea!?~,___ ~qlrn BgQCh ~Oll,!~Y_, J:1~~'<!q ~..."r:::-"=: ;'::E:L:.=I
!': II t= h. e' I' I; I:: 9!dH BIT "A"
10 J> II ., ,\
'~ ;u '(1) (I> :1 il 'I 1!llbl
0 -< -< !i
,,11 III 10 r I;
'!o r r II il II' rl
: ()> 10 10 'f Ii
.10 ~ < I il ~I Ii l,j ili
"0 I>
-< -< ill Iii
m 2 0 I i II
~ z !! I II II'
III I.
~ .
;u ,; ~ I Ii III
~ ;;--11 II ' , ~
0 ' .
, .
;u & . \
10 ~ ! I ~ ~
r - . ..
III x ! I JJ
< ~ I
J> I! !l!
-I g n II! 0
0 d r
z I I I ! (,)
(J> 1/ !l ~,!H i'! i
IFF . JJ
III , ..
(J> {)
10 II!! PI H "I
;u HI PI l>- I
~ Id! fll , , I"
() I ! I 1 ! I I
III I ! I h!! HI ; III
()I i ' . II! I i ' ' , ill
c I . I .
r Iii IIp Iii
0 U III iil! II H Ii ~!
z I' I !
~ : I , : I I 'l!q Ii. "ql!~!
1'1 1"1 1'1 II . . II I Ii !I II I' ~I
\ ! i !'!! ~ /. II \; I '1
I I I' 1 ! I ~ II i u Ii !~ II Ii ~! II
Iq !l I PI u I II ! - I, I
~ ii, ~ ii, j~ I I II I r I!li i! I
.; !S " 1 'I' 1 r
c . i" "r II ~ Ii. 1'1 Ip' Ii lPI i
~ IH !. -< q II I il
I
III I" Ii, Ii llil 1 I
r III rn I II I! I
~ . it ~ I it I I! i! i! , I
ii~ I> I Iii II I I
::! ,
o I
I Z i
l~ ::I
~ I
I ", I ~I
!l! I
....
'" I I lP
"." 'r . 11 ~
! .i ~ I 'E
I II l>-
I"
I. I
i
!~ IP Gli HI
II ,I ii~ I ·
j'" I I~d
l!i tJl:W I=Ull-~l:RVICl: CAR WM:I-I BAC'i
I / fot Mt. DQvld DQ.z\cQ1 I
II B B SAC - Soc;. Archlr.ct CorDor.rlon
'!I oynton e~ch~ _Palm Bculch County; ':lo"JdQ__~~~-~-:-:- :"'":J.::l.=-Ei
l .
.
I ·
-EXHIBIT "A"
111\11111
1111111111
1111 ill,
1':11
~~
..0
~11
.0
ii(J>
'''I
'!\)
r
J>
Z
\)
(J>
o
J>
11
IR
11
r
J>
Z
.. ........
I II ii 1III
. I. . I I
ilq!i'li
, I ~ . I f
fl"
II ~ . . . . . , .
Il'S'lI' I
i i I
I
ii ij;i ii, i
II II 11111111
I I I
I
U',",_
!jlll!!!l
I I',
, ,
"'_"1 'I
"((1111
! -----II
I .""
I,."
I
H'\"'1I'OLU)ClClIllOAD
!I~ U ill 1
!'lllh!
I "Iud
f · j I~' i
: 1IIIII it
I jl 'j!
! II Iii
I II III
i II il!
I ,I ill
II I /1
Ii
II
'11111111111
111111111"1
1111. .I!
11111 . I'
ji111lif
II I I .1
II iii ii ii ii
$
"""'"
III
'I'
III
Iii
- -II -- ---
Ii
l!--- - ----
I
r- iii ~Il I
I I! ~ I'
~ I_LJ_
I H ~~~~~:~;;~~~;.,~ CAR WM:14 BAC -'j
'I B SAC: - 80ee Archlt..<< Cor,E>or"lIon,
11 ~ynton BgQCh~ PQ'rn BeQch COUn!_~L_E!~~dQ :''":::...~..:~.:::'--'. :-E=I
.'
~ .,,-~:!,' I'~,",'
./ \'.~'to I'~-'
Wv- _......
.-r' t; .(~" ~ I!
I I I '~.,("'
f'l.-
~..
I ,7 rt"'CO, ;
! .1.. . J
'W r-:I II .
jl!' u ~ I .
1111 ~. . ..~ '..
'111 r
!Il I ' ~ I .
ii!l I! II 0 SI.__
I'll ~I \ ,---
'hi \
li'I \
III ~ ~i;
~II. . 'J~H; I
~~
-0
.11
.0
H;
~o
~
-f
111
;g I
J> <
Z -
11
"
()
~
f .
,
I ·
l'
i
I
..-. lEXHI61T
'I II '..\; . ~'i~I"~
f .' I .ml'lilli ~
'~'~ . ~' , 'q!lllllln iii
,""J ~ ~ li:!1511I'1
~" : 1,!II!'~ll. I
II "\ \, 11 r B h!tili .
.,,-- 'I Iii ........ n
\ H ' IUlnllm~
E!C'Hs.1 ,~.,
I fil~f I I
~ Ii! d i I
Unll!lll~
~IP I .1 i
l'I'p.llm~ii~
..llh:IU1mi
I!illhllil~111
l ~ ll!iillbl"
\ a~J!lI'II! I~l! 1
'ill I . I .
, .
1IIIIln Ill!,
. "11"lhi:I,1
Illl". lid
: IlinE it li'l
I!II! 'I
.I' ! I"
I _. !
. . !111li (-Ii
: ; 111111 I ,i
I II hi!!! 1i,
I t i I ~"11' i'
I II III, IiI I'll!! II
... ...,)j" Iii ;ll;;,i I ·
\Iii ! PIIIIII!! I Ill! ~
II!, I i1li' B liB 2
",I! I .....1 1,1 IIIIII
'1' · ...... -I I II
r ' J,"" .1
-1.'--- m__ II, lillii'
-- -l,!- -- II .... i
ill IIli
II II..
- ~
\"-.
II~ ...~. ... ... ...
1;1 I
'II I
__m!~=-\~.__
..~...
I
i
.
;
s
H'Tl"Ol.Ul<<)""""
:J> IP ~! I I
I ,I ~-t I ·
""" I u,
! Ii tJ~w I=Ull-S~RVJC~ CAR WASH BAC -'1
I ~ fo,. M,.. DavId DQ~zk.Q1
r B B SAC - Roca Architect Corpor..tlo~1
!l __o.l'~ton g~~~~~~QQC~~?.~!1.!Y' ._r~,,'da =-"':.:....~~::--.. :-==1
nAil
Exhibit "C"
Conditions of Approval
Project name: Grove Plaza Car Wash
File number: NWSP 02-007
Reference: 2"d review plans identified as New Site Plan file # 02-007 with an June 4, 2002 Planning and Zoning
Department date stamp marking.
. .
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments:
I Prior to permit application contact the Public Works Department (561-
742-6200) re~arding the storage and handling of refuse.
PUBLIC WORKS - Traffic
Comments: None
UTILITIES
Comments: None
FIRE
Comments: None
POLICE
Comments: None
ENGINEERING DIVISION
Comments:
2. A Lighting Plan including photometrics, pole wind loading, and pole
details in conformance with the LDR, Chapter 6, Article IV, Section 11,
Chapter 23, Article I, Section 5.B.7 and Chapter 23, Article II, Section A
will be required at the time of pennitting.
3. Provide typical section(s) for the drainage swale(s) and retention areas on
the proiect.
BUILDING DIVISION
Comments:
Coa
06/19/02
2
DEPARTMENTS INCLUDE REJECT
4 At the time of permit review, submit signed and sealed working drawings
of the proposed construction.
5. At time of permit review, submit for review an addressing plan for the
project.
PARKS AND RECREATION
Comment: None
FORESTERlENVIRONMENT ALIST
Comments: None
PLANNING AND ZONING
Comments:
6. According to the proposed building dimensions, the collective area of all
walls signs cannot exceed 72 square feet (Chapter 21, Article IV, Section
2.C.). Provide dimensions for all three (3) wall signs (in tabular format)
to confirm that all three (3) signs will comply with this requirement.
Include the dimensions of the "bumper" / "clock" as a component of the
wall signage area.
7 On the proposed bumper / clock, eliminate the "MC" watermark
otherwise, it will be classified as a non-word depiction and would be
limited to 20% of the sign erected (Chapter 9, Section 10.1.4 ).
8. The detail of the outdoor freestanding lighting structure shown on the
photometric plan must match the Grove Plaza Master Plan design
guidelines.
9 The monument sign may be single or double-face and shall be made of
stucco/masonry construction colored either white or off-white as required
by the Grove Plaza Design Guidelines (August 1998). On the detail,
provide the correct height and colors so that it complies with the Design
Guidelines (1998). Clearly identify the site address at the top of the
monument sign.
10. The menu board sign shall be an exterior single-face sign with the
illustrated face area not to exceed 25 square feet. The top of the sign
cannot exceed five (5) feet above ground level at the base of the sign
(Chapter 21, Article IV, Section 2.D ).
11 All directional signs shall not exceed four (4) square feet in area, nor five
(5) feet in height with a Jimit of four (4) signs per lot, located at points of
Coa
06/19/02
3
DEPARTMENTS INCLUDE REJECT
parking lot ingress and egress (Chapter 21, Article IV. Section 2.F).
12. If outdoor speakers are proposed, staff recommends locating and directing
the sound in such a way so that it does not create a nuisance to the
residential properties to the south.
13. Staff recommends limiting the evening hour of operation to 6:00 p.m.
14 Staff recommends placing an additional shade tree in the grassy area
behind the proposed monument sil!l1.
IS. Because this is an auto-intensive use, in the north landscape buffer
adjacent to Hypoluxo Road, staff recommends either replacing the two
(2) Washingtonia palm trees (in between the Southern Red Cedar trees)
with two (2) shade trees OR placing an additional shade tree near the two
(2) Washingtonia palm trees.
ADDITIONAL PLANNING & DEVELOPMENT BOARD CONDITIONS
Comments:
16. To be determined.
ADDITIONAL CITY COMMISSION CONDITIONS
Comments:
17 To be determined.
MWRlelj
S:IPlanningISHAREOIWPIPROJECTSlgrove plazalCar Wash MPMO & NWSPINWSPICOA.doc
DEVELOPI\ ~T ORDER OF THE CITY COMMIS, IN OF THE
CITY OF BOYNTON BEACH, FLORIDA
PROJECT NAME. Grove Plaza Car Wash
APPLICANT'S AGENT David Daszkal/ Daszkal Development, LLC
APPLICANT'S ADDRESS. 3837 Jonathans Way Boynton Beach, FL 33436
DATE OF HEARING RATIFICATION BEFORE CITY COMMISSION: July 2,2002
TYPE OF RELIEF SOUGHT New Site Plan
LOCATION OF PROPERTY Parcel E of Grove Plaza, east of Lawrence Road on the south side of
Hypoluxo Road
DRAWING(S): SEE EXHIBIT "B" ATTACHED HERETO
THIS MATTER came before the City Commission of the City of Boynton Beach, Florida
appearing on the Consent Agenda on the date above. The City Commission hereby adopts the findings
and recommendation of the Planning and Development Board, which Board found as follows:
OR
THIS MATTER came on to be heard before the City Commission of the City of Boynton
Beach, Florida on the date of hearing stated above. The City Commission having considered the relief
sought by the applicant and heard testimony from the applicant, members of city administrative staff and
the public finds as follows:
1 Application for the relief sought was made by the Applicant in a manner consistent with the
requirements of the City's Land Development Regulations.
2. The Applicant
HAS
HAS NOT
established by substantial competent evidence a basis for the relief requested.
3. The conditions for development requested by the Applicant, administrative staff, or
suggested by the public and supported by substantial competent evidence are as set forth
on Exhibit "C" with notation "Included"
4 The Applicant's application for relief is hereby
_ GRANTED subject to the conditions referenced in paragraph 3 hereof.
DENIED
5. This Order shall take effect immediately upon issuance by the City Clerk.
6. All further development on the property shall be made in accordance with the terms and
conditions of this order
7 Other
DATED'
City Clerk
S:\Planning\SHARED\WP\PROJECTS\grove plaza\Car Wash MPMD & NWSP\NWSP\DO.doc
{Vlet sf-e J<.
1 st REVIEW COMMENTS
New Site Plan
Project name: Grove Plaza Car Wash
File number' NWSP 02-D07
Reference: I "review Dlans identified as New Site Plan file # 02-007 with an ADril 17.2002 Planning and
Zonincr Denartment date stamn markincr.
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments:
I Prior to pennit application contact the Public Works Department (561-742- /
,/
6200) regarding the storage and handling of refuse.
2. The required gates for the dumpster shall contain long steel rods to drop into
the pavement in order to secure the gates in the open and closed positions. /
Drilled holes (for concrete) or metal sleeves (for asphalt) shall be provided
for the locking rods.
3 Walls for the enclosure shall be provided on three sides and are to be a
minimum of 6 ft high and shall be CBS construction with a finish matching t/
that of the adjacent building(s). Accent shrubs shall be provided along the
screen walles) (LDR, Chapter 7.5, Article II, Section 5.1, Section 5.1 and
Article III, Section 9.A.9.a, and Chapter 9, Section 10 C.3)
PUBLIC WORKS - Traffic
Comments: None
UTILITIES
Comments:
4 Water and sewer systems exist to service this component of the plaza. ,/"
5 Fire flow calculations will be required demonstrating the City Code
requirement of 1,500 g.p.m. as stated in the LDR, Chapter 6, Article IV, 1/
Section 16, or the requirement imposed by insurance underwriters,
whichever is greater (see CODE Sec. 26-16(a)). In addition, the LDR,
Chapter 6, Article IV, Section 16 requires that all points of each building
shall be within 200 feet of an existing or proposed fire hydrant. Please
demonstrate that the Dlan meets this condition, by showing all hydrants.
6. Comprehensive Plan Policy 3.C.3.4 requires the conservation of potable /
water. City water may not, therefore, be used for irrigation where other
sources are readily available.
FIRE
Comments: None
1ST REVIEW COMMENTS complete
05/1 0/02
2
, II
DEPARTMENTS INCLUDE REJECT
POLICE
Comments: None
ENGINEERING DIVISION
Comments:
7 Add a general note to the Site Plan that all plans submitted for specific
permits shall meet the City's Code requirements at time of application. ~
These permits include, but are not limited to, the following: paVIng,
drainage, curbing, site lighting, landscaping and irrigation. Permits required
from other permitting agencies such as Florida Department of
Transportation (FDOT), South Florida Water Management District
(SFWMD), Lake Worth
8. Drainage District (LWDD), Florida Department of Environmental Ii
Protection (FDEP), Palm Beach County Health Department (PBCHD),
Palm Beach County Engineering Department (PBCED), Palm Beach
County Department of Environmental Resource Management (PBCDERM)
and any others, shall be included with the permit request.
9 Show all existing utilities on Site Characteristics Map (Survey) and Site V
Development plan (LDR, Chapter 4, Section A.3).
10 A "Rider to Site Plan Application" shall be submitted with the permit V'
application as specified in the LDR, Chapter 4, Section 7 G.
11 Provide all information, including existing and proposed elevations, on the ./
Drainage Plan in accordance with the LDR, Chapter 4, Section 7.F
12. Provide an engineer's certification on the Drainage Plan as specified in /
LDR, Chapter 4, Section 7.F.2.
13 A Lighting Plan including photometrics, pole wind loading, and pole details
in conformance with the LDR, Chapter 6, Article IV, Section II, Chapter /
23, Article I, Section 5.B.7 and Chapter 23, Article II, Section A will be
required at the time of permitting. If "pg~i:~?I"" pl~"'fW Frs" iek tt:s
iufv~uAttieB ~;:) }JCSH u[ )'v~r TRe plaR Sl:H:JI~tiLLcd:s i[ b UJ\..u...L ...a.JieI t&
idefltif:," ang ~gt:rj'Gt ailJ d,Ji8i~(,lei Y'lnm th~n m~il9 )'011 ......1 "'aitiBg aa a
pefl'Ri.ll.
14 Depict sight triangles on the Site and Landscape Plans (LDR, Chapter 7.5, ~
Article II, Section 5.H.)
15 Add a note to the Landscape Plan that within the sight triangles there shall V
be an unobstructed cross-visibility at a level between 2.5' and 6' above the
1ST REVIEW COMMENTS complete
05/10/02
3
, u
DEPARTMENTS INCLUDE REJECT
pavement (LDR, Chapter 7.5, Article II, Section 5.H.).
16. A proposed 5 foot concrete sidewalk is shown on the Revised Master Site
Plan on the west side of Parcel "E" but is not depicted on any other sheets /
of this submittal. Please indicate if this has been constructed or is to be
constructed as part of the development of Parcel "E"
17 Indicate to what standard(s) the project is to be constructed; if the FDOT
Standard Specifications for Road & Bridge Construction and Standard /
Index are to be used - the 2000 Specifications are recommended since they
contain both English and Metric units. Additionally reference the current
edition of the MUTCD
18. Show written and graphic scale on all sheets. ./
19 Staff recommends reconfiguring the entrance driveway to a separated, one-
way in, one-way out layout. Move the entrance "lane" north to line up with 11
the front parking area (through the two parking spaces). Narrow the
proposed two-lane single driveway to a one-lane exit. The two parking
spaces could be moved to in between the two new drives. It is felt that this
configuration will improve internal flow
20 Show the sidewalk at the handicap parking at the same elevation as the /
accessible paths with 1 12 ramps up in both directions (FL Accessibility
Code 4.6.3). A detail should be provided reflecting this.
21 Revise Note #7, Sheet A-I, to specify the handicap symbol color as white Ii
per City Standard Drawings B-9800I Indicate, by note, that all striping
shall be placed in accordance with City Standard Drawings B-98001
22. The stop sign at the east entrance is incorrectly labeled as #5, it should be /
labeled #9
23 Consider adding a height restriction sign at the front entrance elevation and v'
adding a "no entry" type sign for the east elevation of the covered porch.
24 Provide typical section(s) for the drainage swale(s) and retention areas on vi
the proiect.
BUILDING DIVISION
Comments:
25 Add to the building that is depicted on the drawing titled site plan a labeled ~/
symbol that identifies the location of the handicap accessible entrance doors
to the building. Florida Accessibility Code for Building Construction,
Section 4 1.2,4.3 ,
26. On the floor Dlan drawing, add a labeled svrnbol that identifies the location V
1ST REVIEW COMMENTS complete
05/1 0/02
4
DEP ARTMEJ'fIS INCLUDE REJECT
of the handicap accessible entrance doors to the building. The location of
the door(s) shall match the location of the accessible entrance doors that are
depicted on the site plan drawing. Florida Accessibility Code for Building
. . A 1 ~ A 0
27 Identify within the site data the finish floor elevation (lowest floor elevation
) that is proposed for the building(s). Verify that the proposed elevation is in
compliance with regulations of the code by adding specifications to the site
data that address the following issues [Section 3 107 1.2, Chapter 31 of the /
Florida Building Code]:
a) The design professional-of-record for the project shall add thefollowing
text to the site data. "The proposed finish floor elevation_ _NGVD is
above the highest I OO-year base flood elevation applicable to the building
site, as determined by the South Florida Water Management District's
surface water management construction development regulations."
b) From the FIRM map, identify in the site data the title of the flood zone
that the building is located within. Where applicable specify the base flood
elevation, indicate that on the plans.
c) Identify the floor elevation that the design professional has established for
the building within the footprint of the building that is shown on the
drawings titled site plan, floor plan and paving/drainage (civil plans).
28. On the drawing titled site plan, identify and label the symbol that represents t/
the property line.
29 The building plans are not being reviewed for compliance with the
applicable building codes. Therefore, add the words "Floor plan layout is
conceptual" below the drawing titled Floor Plan found on sheet A-2. V
However, add to the floor plan drawing a labeled symbol that identifies the
location of the handicap accessible entrance doors to the building. The
location of the door(s) shall match the location of the accessible entrance
doors that are depicted on the site plan drawing.
30 Place a note on the elevation view drawings indicating that the wall
openings and wall construction comply with Table 600 of the 200 I Florida t/
Building Code.
31 On all floor plan drawings, indicate within the footprint of the building the
number of stories that are in the building including, where applicable, J
mezzanmes.
32. Identify on the site plan drawing the actual distance that the building(s)
(is/are) set back from the north, east, south and west property lines. /
33 Identify the size or width of the covered walkways, awnings, canopies
and/or other roofed areas that extend out beyond the main walls of the /
building. ,
34 At the time of oermit review submit silmed and sealed workimt drawings of ./
1ST REVIEW COMMENTS complete
05/10102
6
I ,
DEPARTMENTS INCLUDE REJECT
and "Traffic Directional Sign", including their respective colors,
dimensions, and materials. The "Traffic Directional Sign" must be at least
10 feet from the property line.
X The proposed building's trim colors, body colors, accent colors and roof /'
colors must be consistent with the Grove Plaza Design Guidelines (August
1998).
X The elevations must include the outdoor canopy \/
>( On the elevations, identify the "Front Elevation" to include "North V
Elevation" Repeat this methodology of compass direction for all building
sides.
~~ the elevations, it appears as though three (3) building sides will have /
wall signage. According to the proposed building dimensions, the area of
all walls signs collectively, cannot exceed lJt;quare feet. She'.'.' l!;e wlv"
a,.[ic;l'atcd matenals, and dimensions of <<ll ",all ,igus (Chapier 21, AmelIO
IV ~:",;. ~.~.'.
17"'\
~ Pre,.~ae an impn;l"~d rlljlreE~Mtot;on of the PTnp"<p,-l ~^numelll ,igIf,"
inelllsiRg teta! signng~ area afld materials / eeler3 ":A1ichlleedlllldj sh(l"lf
tPP ~ppPRr~n~p. in nrrtPT' tQ eOflfilfl~ arehitoctural e-ouJ.p4LibllltyWlth the /
b'lildiag. The maximum allowable signage area is 60 square feet. The
monument sign may be single or double-face and shall be made of
stucco/masonry construction colored either white or off-white as required by
the Grove Plaza Design Guidelines (August 1998). In addition, clearly
identify the site address at the top of the monument sign.
~ The landscape plan must contain a tabular summary of proposed and ./
required trees / shrubs and methodology used to derive the amounts.
X Two (2) Foxtail palm trees and Scarlet Hibiscus hedges are proposed
outside the property line (at the rear) and cannot be used in meeting /
minimum landscape requirements. Project must obtain consent from the
abutting property owner in order to install this plant material. Also, exclude
said plant material from the landscape plan tabular data.
~ Submit a color sample / swatch of all major exterior finishes (Chapter 4, ,/
Section 7.D.I ).
IX Include a color rendering of all elevations prior to the Technical Review ~
Committee meeting (Chapter 4, Section 7.D.2.).
)/ The landscape plan must contain street name labels and a north arrow /
~ Landscaping at project entrances shall contain a minimum of one (I) ./
signature tree on both sides of the entrance (Chapter 7.5, Artiele II, Section
5.N.). Note that sil!nature trees do not contribute toward the total number of
,
1ST REVIEW COMMENTS complete
05/10/02
5
'7
I ~
DEPARTMENTS INCLUDE REJECT
the proposed construction.
35 Add to the submittal a partial elevation view drawing of the proposed
perimeter masonry wall. Provide a typical section view drawing of the wall /
that includes the depth that the wall supports are below finish grade and the
height that the wall is above finish grade. The location and height of the
wall shall comply with the wall regulations specified in the Zoning Code.
36. At time of permit review, submit for review an addressing plan for the /
proj ect.
37 Add to all plan view drawings of the site a labeled symbol that represents /
the location and perimeter of the limits of construction proposed with the
subiect request.
PARKS AND RECREATION
Comments: None
FORESTERJENVIRONMENT ~.LI.S -kY
Q(~~ 'SO Z- II
Comments: . /
38. The landscape plan (for hedges and groundcover plants) does not meet the -r:x V'
50% native species reauirement.
PLANNING AND ZONING
Comments:
~ Identify the Official Zoning District and Future Land Use designation for V
. the subject property
K The survey must identify the Official Zoning District and Future Land Use i/
designation for the adjacent properties (Chapter 4, Section A.3.).
)( In the site plan tabular data, the "Covered Porch", "Total area under canvas /
shelters" plus the "Net building coverage" shall equal the project's lot
coverage (7,614 s.f./37,768 s.f. = 20% lot coverage).
)( In the site plan tabular data, provide an itemized list of the area (expressed V
in feet) of each use within the building, such as vacuum room, restrooms,
car wash tunnel, etc.
~ The site plan or landscape plan should show the eight (8) foot drainage and /
utility easement.
44 Provide a detail of all directional silffis. including the "Wash Menu Silffi" V
(7
/
/
/
1ST REVIEW COMMENTS complete
05/10/02
7
)(
DEPARTMENTS
required perimeter trees or parking area interior landscaping. (Chapter 7.5,
Article II, Section 5 G.). Provide one (I) additional signature tree, such as
Yellow Elder, Tibouchina granulosa, or Bougainvillea at each side of the
project entrance. These signature trees shall have a minimum of six (6) feet
of clear trunk to preserve the clear sight area.
At least fifty (50) percent of the site landscape material must be of native
species and verified as such in the tabular data of the landscape plan
(Chapter 7.5, Article II, Section 5.P).
All above ground mechanical equipment such as exterior utility boxes,
meters, transformers, and back-flow preventers shall be visually screened
with appropriate landscaping / hedge material (Chapter 9, Section 10 C.4).
Provide a dumpster enclosure detail. The dumpster enclosure shall
resemble with respect to the color and materials, the design of the principal
buildings and shall be integrated with other site elements (Chapter 9,
Section 10.E.3). On the site plan, place a note indicating this requirement.
Provide a detail or typical of all outdoor freestanding lighting fixtures. The
detail must include the pole material, height, and color The design, style,
and illumination level shall be compatible with the building design (height)
and shall consider safety, function, and aesthetic value (Chapter 9, Section
10.F I ). The detail shall be consistent with the typical lighting fixture detail
as identified by the Grove Plaza Design Guidelines ( August 1998).
Staff recommends substituting the Scarlet Hibiscus hedge with native hedge
material, such as Redti Coco lum or Florida Privet.
MWR/sc
INCLUDE REJECT
S:\Planning\SHARED\VvP\PROJECTS\grove pla:za\Car Wash MPMD & NVVSP\NWSP\1 ST REVIEW COMMENTS.doc
v
v'
/'
~
/'
June 04, 2002
,1 r--- _" --
.-
i '\ ~
I ii,
J~ A
, i
L
To Planning and Zoning Division, City of Boynton Beach, Florida
From. Christopher Crawford, Project Architect, BAC-Boca Architect Corporation
Subject: RESPONSE TO 1 st REVIEW COMMENTS FOR GROVE PLAZA CAR WASH
A. CAR WASH OUT PARCEL COMMENTS.
I Will comply as noted.
2. Note added to plans.
3 Already noted and illustrated on plans.
4 Yes.
5 Existing fire hydrant on site already shown on plans. Existing fire hydrant on adjacent
property now also shown and located. All points of new buildings are within 200 feet of existing
hydrants.
6. Irrigation note using well water already on Landscape Plans.
7 Added to Site Plan as noted.
8. Added to Site Plan as noted.
9 Already noted and illustrated on plans.
10 Submitted at this meeting.
II Added to Drainage Plan as noted.
12. Previously submitted. Additional copy provided.
13 Will submit a Photometrics Plan at time of permitting. Detail of Site Light provided.
14 Added to Site and Landscape Plans as noted.
15 Added to Landscape Plan as noted.
16. Proposed sidewalk deleted on Master Site Plan. A new sidewalk has been recently
completed adjacent to new East-bound 3'd lane of Hypoluxo Road next to site.
17 Added to Site Plan as noted.
18. Already shown on all plans previously submitted.
19 The entrance location as shown on our proposed site plan was chosen since it was the curb
cut/out-parcel entrance location indicated on plans for Grove Plaza and approved by the city It
also has an existing rain catch basin located at the proposed curb cut s center. Our staff, civil
engineer, and owner fully reviewed and considered your written recommendation. In our
professional opinion, we believe that the entrance as we have shown it will be less confusing and
more cost effective. We did however make some adjustments to the entrance area that should
improve traffic flow and lessen confusion even more.
20 Added to Site and Floor Plans as noted. Standard ADA Detail of this condition provided.
21 Note added to Site Plan and plan modified to reflect City Standard Drawings B-9800I
22. Changed as noted.
23 "No Entry" sign already indicated on plans. Height restriction sign at front entrance
unnecessary since it will be staffed and monitored by one or more employees during hours of
operation.
24 Civil engineer is preparing this section and will submit at a later date.
25 Added to Site Plan as noted.
26. Added to Floor Plan as noted.
27 Added to Site, Floor, and Drainage Plans as noted.
28. Added to Site Plan as noted.
29 Added to Floor Plan as noted.
30 Added to Exterior Elevations as noted.
31 Added to Floor Plan as noted.
32. Added to Site Plan as noted.
33 Added to Site and Floor Plans as noted.
34 Will comply as noted.
35 There is no proposed perimeter wall in this project.
36. Will comply as noted.
37 Added to Site Plan as noted.
38. Landscape Plan changed to meet 50% code requirement.
39 Added to Master and out-parcel Site Plans as noted.
40 Added to Survey Plan as noted.
41 Changed data as noted.
42. Added to Site Plan as noted.
43 Already noted and illustrated on plans. Additional notes added.
44 Sample details provided as noted and sign moved as indicated.
45 Proposed building's colors are consistent with Grove Plaza Design Guidelines.
46. Outdoor Canopy (Fabric Shelters) and Service Building Exterior Elevations provided.
48. Total frontage is 48'-0", as per North Elevation, meaning 48 x 1.5 = 72 square feet of
allowable signage. Total signage on building as illustrated is 72 square feet.
49 Plan added to Service Building's Exterior Elevations, and details by sign company provided.
50. Added to Landscape Plan as noted.
51 Removed.
52. Color samples/swatch provided.
53 New color renderings of Exterior Elevations provided.
54 Added to Landscape Plan as noted.
55 Changed/added to Landscape Plan as noted.
56. Changed/added to Landscape Plan as noted.
57 Note added to Landscape Plan reflecting this.
58. Already noted and illustrated on plans. Additional notes added.
59 Outdoor lighting fixture detail provided.
60 Landscape Plan changed as per recommendation.
B. MASTER PLAN MODIFICATION 1 ST REVIEW COMMENTS
I Will comply as noted.
2. Will comply as noted.
3 Will comply as noted.
4 Will comply as noted.
5 Will comply as noted.
6. Will comply as noted.
7 Will comply as noted.
8. Corrected as noted.
DEPARTMENT OF DEVELOPMENT
BUILDING DIVISION
MEMORANDUM NO 02-086
FROM
Michael W Rumpf
Director of Planning and Zoni'b,
Timothy K. Large ~.yJ
TRC Member/Building Division
TO'
DATE.
April 26, 2002
SUBJECT
Project - Grove Plaza Car Wash
File No - MPMD 02-001 NWSP 02-007
We have reviewed the subject plans and recommend that the request be forwarded for
Board review with the understanding that all remaining comments will be shown in
compliance on the working drawings submitted for permits.
Buildina Division (Site Specific and Permit Comments) - Timothv K. LarQe (561)
742-6352
1 Add to the building that is depicted on the drawing titled site plan a labeled symbol
that identifies the location of the handicap accessible entrance doors to the
building. Florida Accessibility Code for Building Construction, Section 4 1.2, 4.3
2. On the floor plan drawing, add a labeled symbol that identifies the location of the
handicap accessible entrance doors to the building. The location of the door(s)
shall match the location of the accessible entrance doors that are depicted on the
site plan drawing. Florida Accessibility Code for Building Construction, Section
4 1.2, 4.3
3. Identify within the site data the finish floor elevation (lowest floor elevation) that is
proposed for the building(s). Verify that the proposed elevation is in compliance
with regulations of the code by adding specifications to the site data that address
the following issues [Section 31071.2, Chapter 31 of the 2001 Florida Building
Code].
a) The design professional-of-record for the project shall add the following text to
the site data. "The proposed finish floor elevation _ _ NGVD is above the
highest 100-year base flood elevation applicable to the building site, as
determined by the South Florida Water Management District's surface water
management construction development regulations."
b) From the FIRM map, identify in the site data the title of the flood zone that the
building is located within. Where applicable, specify the base flood elevation. If
there is no base flood elevation, indicate that on the plans
S/Development/Building Code AdministratorfrRC/02/Name of project
Page 10f2
c) Identify the floor elevation that the design professional has established for the
building within the footprint of the building that is shown on the drawings titled
site plan, floor plan and paving/ drainage (civil plans).
4 On the drawing titled site plan, identify and label the symbol that represents the
property line.
5 The building plans are not being reviewed for compliance with the applicable
building codes. Therefore, add the words "Floor plan layout is conceptual" below
the drawing titled Floor Plan found on sheet A-2. However, add to the floor plan
drawing a labeled symbol that identifies the location of the handicap accessible
entrance doors to the building. The location of the door(s) shall match the location
of the accessible entrance doors that are depicted on the site plan drawing.
6. Place a note on the elevation view drawings indicating that the wall openings and
wall construction comply with Table 600 of the 2001 Florida Building Code.
7 On all floor plan drawings, indicate within the footprint of the building the number of
stories that are in the building including, where applicable, mezzanines.
8. Identify on the site plan drawing the actual distance that the building(s) (is/are) set
back from the north, east, south and west property lines.
9 Identify the size or width of the covered walkways, awnings, canopies and/or other
roofed areas that extend out beyond the main walls of the building.
10 At time of permit review, submit signed and sealed working drawings of the
proposed construction
11 Add to the submittal a partial elevation view drawing of the proposed perimeter
masonry wall. Provide a typical section view drawing of the wall that includes the
depth that the wall supports are below finish grade and the height that the wall is
above finish grade. The location and height of the wall shall comply with the wall
regulations specified in the Zoning Code
12. At time of permit review, submit for review an addressing plan for the project.
13. Add to all plan view drawings of the site a labeled symbol that represents the
location and perimeter of the limits of construction proposed with the subject
request.
bf
SIDevelopmentlBuilding Code Administrator/TRCI02lName of project
Page 2 of 2
~
~
~-
""'
~
Planninl! Memorandum: Forester / Environmentalist
To
Lusia Galav, Senior Planner
From.
Kevin J Hallahan, Forester / Environmentalist
Subject:
Grove Plaza Car Wash
NWSP 02-007, I st Review
Date:
May 6, 2002
Exist
rove Plaza Common Area residentiallandsca e buffer
There are twenty-two (22) gead tr"es along this TP<id("'+iaI1"ndscape buffer that must be replaced.
There is dead sod along this residentiallandsca e buffer that must be replaced.
o the Ficusfl" - o~_residentiallandscape buffer wa ar must be replaced.
-rhe existing irrigation system must proviae adequate waterto-aH-ef the landgcape impn:p'ement8 aleng ---
this residential landscape buffer
There is graffiti on sections of the conclck wall that must be removed from this residential buffer
improvement. ,
------rhe existing black vinyl chain link fence along the East perimeter of the residential landscape buffer must
be r -n sections where it onto the ound.
Landscape Plan
"'- /
...:.:.::::-- -----
1\\ \' \ l.. n The landscape plan (for hedges and groundcover plants) does not meet the 50 % native species
l \J V l' requirements
Irr~gv/\
There is an irrigation ~:nt 0 ., e plan include with th~
The pr,*,et sheltl18 eeRtinne in the normal review proSJ'SS.
Xc; Eric Johnson, Planner
Kjh
file
DEPARTMENT OF PUBLIC WORKS
ENGINEERING DIVISION
MEMORANDUM NO. 02-092
TO'
Michael W Rumpf, Director of Planning and Zoning
FROM:
Laurinda Logan, P.E., Civil Engineer
DATE.
May 2, 2002
STANDARD REVIEW COMMENTS
NEW SITE PLAN - 1 ST REVIEW
GROVE PLAZA CAR WASH
FILE NO MPMD 02-001/ NWSP 02-007
RE.
I have reviewed the above referenced Site Plans, forwarded to me on April 22, 2002, against the
Site Plan Review requirements outlined in the City of Boynton Beach Code of Ordinances
(available on-line at www.ci.bovnton-beach.f1.us). Following are my comments with the
appropriate Code and Land Development Regulations (LOR) referenced.
PUBLIC WORKS
Code Requirements
1 Prior to permit application contact the Public Works Department (561-742-6200) regarding the storage and
handling of refuse.
2. The required gates for the dumpster shall contain long steel rods to drop into the pavement in order to secure
the gates in the open and closed positions. Drilled holes (for concrete) or metal sleeves (for asphalt) shall be
provided for the locking rods.
3 Walls for the enclosure shall be provided on three sides and are to be a minimum of 6 ft high and shall be CBS
construction with a finish matching that of the adjacent building(s). Accent shrubs shall be provided along the
screen wall(s) (LDR, Chapter 7.5, Article II, Section 5.J, Section 5.J and Article III, Section 9.A.9.a, and
Chapter 9, Section lO.C.3)
ENGINEERING
Code Requirements
1 Add a general note to the Site Plan that all plans submitted for specific permits shall meet the City's Code
requirements at time of application. These permits include, but are not limited to, the following: paving,
drainage, curbing, site lighting, landscaping and irrigation. Permits required from other permitting agencies
such as Florida Department of Transportation (FDOT). South Florida Water Management District (SFWMD),
Lake Worth
Drainage District (L WDD), F,vcida Department of Environmental Protecc.un (FDEP), Palm Beach County
Health Department (PBCHD), Palm Beach County Engineering Department (PBCED), Palm Beach County
Department of Environmental Resource Management (PBCDERM) and any others, shall be included with the
permit request.
2. Show all existing utilities on Site Characteristics Map (Survey) and Site Development plan (LDR, Chapter 4,
Section A.3).
3 A "Rider to Site Plan Application" shall be submitted with the permit application as specified in the LDR,
Chapter 4, Section 7 G.
4 Provide all information, including existing and proposed elevations, on the Drainage Plan in accordance with
the LDR, Chapter 4, Section 7.F
5 Provide an engineer's certification on the Drainage Plan as specified in LDR, Chapter 4, Section 7.F.2.
6. A Lighting Plan including photometrics, pole wind loading, and pole details in conformance with the LDR,
Chapter 6, Article IV, Section II, Chaptec 23, Article I, Section 5.B.7 and Chapter 23, Article II, Section A will
be required at the time of permitting. If possible please provide this information as part of your TRC plan
submittals it is much easier to identify and correct any deficiencies now than while you are waiting on a
permit!
7 Depict sight triangles on the Site and Landscape Plans (LDR, Chapter 7.5, Article II, Section 5.H.)
8. Add a note to the Landscape Plan that within the sight triangles there shall be an unobstructed cross-visibility at
a level between 2.5' and 6' above the pavement (LDR, Chapter 7.5, Article II, Section 5.H.).
9 A proposed 5 foot concrete sidewalk is shown on the Revised Master Site Plan on the west side of Parcel "E"
but is not depicted on any other sheets of this submittal. Please indicate if this has been constructed or is to be
constructed as part of the development of Parcel "E"
Recommendations/Corrections
I Indicate to what standard(s) the project is to be constructed; if the FDOT Standard Specifications for Road &
Bridge Construction and Standard Index are to be used - the 2000 Specifications are recommended since they
contain both English and Metric units. Additionally reference the current edition of the MUTCD
2. Show written and graphic scale on all sheets.
3 Staff recommends reconfiguring the entrance driveway to a separated, one-way in, one-way out layout. Move
the entrance "lane" north to line up with the front parking area (through the two parking spaces). Narrow the
proposed two-lane single driveway to a one-lane exit. The two parking spaces could be moved to in between
the two new drives. It is felt that this configuration will improve internal flow
4 Show the sidewalk at the handicap parking at the same elevation as the accessible paths with I 12 ramps up in
both directions (FL Accessibility Code 4.6.3). A detail should be provided reflecting this.
5 Revise Note #7, Sheet A-I, to specify the handicap symbol color as white per City Standard Drawings B-
98001 Indicate, by note, that all striping shall be placed in accordance with City Standard Drawings B-9800l
6. The stop sign at the east entrance is incorrectly labeled as #5, it should be labeled #9
7 Consider adding a height restrl~tlOn sign at the front entrance elevation anu adding a "no entry" type sign for
the east elevation of the covered porch.
8. Provide typical section(s) for the drainage swale(s) and retention areas on the project.
UTILITIES
Code Requirements
Water and sewer systems exist to service this component of the plaza.
2. Fire flow calculations will be required demonstrating the City Code requirement of 1,500 g.p.m. as stated in the
LDR, Chapter 6, Article IV, Section 16, or the requirement imposed by insurance underwriters, whichever is
greater (see CODE Sec. 26-16(a)). In addition, the LDR, Chapter 6, Article IV, Section 16 requires that all
points of each building shall be within 200 feet of an existing or proposed fire hydrant. Please demonstrate that
the plan meets this condition, by showing all hydrants.
3 Comprehensive Plan Policy 3.C.3 4 requires the conservation of potable water City water may not, therefore,
be used for irrigation where other sources are readily available.
LUck
Cc: Jeff Livergood, P E., Director, Public Works
Pete Mazzella, Assistant to Director, Utilities
H David Kelley, Jr , P.E./ P S.M., Utility Engineer, Engineering
Glenda Hall, Maintenance Supervisor, Parks
Ken Hall, Engineering Plans Analyst, Engineering (via e-mail)
File
C:\My Documents\Grove Plaza Car Wash, New Site Plan, 1st Review.doc
Sent:
To:
Subject:
Wildner,
Wednesday, May 08, 20024:35 PM
Coale, Sherie
RE. Lighthouse Academy & Grove Plaza
I have no comments on Grove Plaza Car Wash.
John
-----Original Message-----
Frol!l:e9!lIi'iSherie
Sent: Wednesday, May 08, 2002 4:25 PM
To: Galav, Lusia; Hall, Ken; Hallahan, Kevin; Huntington, John; Kelley, David;
Kemmer, Rodger; Large, Tim; Logan, Laurinda; Wildner, John
Subject: Lighthouse Academy & Grove Plaza
Just a reminder that the 1st review comments for these plans are/were due respectively
today & yesterday Please e-mail ASAP Thank you for your cooperation. Sherie