REVIEW COMMENTS
7.E.2
GROVE PLAZA SUBDIVISION
MASTER PLAN (MPMD 03-003)
MASTER PLAN MODIFICATION
DEVELOPMENT DEPARTMENT
MEMORANDUM NO. PZ 04-031
TO:
FROM:
Eric Lee Johnson, AICP
Planner
Chairman and Members
Planning and Development Board
Michael W. Rumpf ~.y:lL/
Director of Planning & Zoning
y--'
.J,
"
THROUGH:
DATE:
February 12, 2004
SUBJECT:
Grove Plaza - File No. MPMD 03-003
Master Plan Modification (Change of use on Parcel "F')
PROJECT NAME:
Grove Plaza - MPMD 03-003
LOCATION:
Grove Plaza, southeast corner of Lawrence Road and Hypoluxo Road
LAND USE/ZONING:
Local Retail Commercial (LRC) / Community Commercial (C-3)
NATURE OF REQUEST
Mr. Michael Weiner, agent for the owner, KMA Investments, is requesting to modify the Subdivision Master
Plan for Grove Plaza. This development is located on the south side of Hypoluxo Road, just east of Lawrence
Road (see Exhibit "A" - Location Map). The specific request is to construct a one-story 7,180 square foot auto
supply retail store (NWSP 03-027) on Parcel "F". Parcel "F" was originally approved for a 3,600 square foot
restaurant. This master plan modification is required for the development of the auto supply retail store
instead of a restaurant on Parcel "F".
BACKGROUND/ ANALYSIS
The subject property was formerly the location of a landscaping and nursery business until it was annexed and
rezoned. On September 19, 1995, the subdivision master plan was approved with six (6) separate parcels,
each of which would require separate site plan review and approval. In 1999, a major modification to the
master plan was approved for the development of the first parcel (Parcel "A') and several changes to the
remaining parcels. Parcel "A" was approved for a gas station (7-Eleven convenience store with gas sales).
The remaining parcels consisted of the following: 3,800 square-foot bank on Parcel "B", 6,540 square feet of
retail on Parcel "C", 9,000 square feet of retail on Parcel "D", a 3,600 square foot restaurant on Parcel "E", and
another 3,600 square foot restaurant on Parcel "F". In July of 2002, the City Commission approved a master
plan modification (MPMD 02-001) for a change in Parcel "E", from a restaurant to a one-story car-wash facility
(Motor City Car Wash). The accompanying site plan (NWSP 02-007) for the car wash was approved as well.
Tract "G" is the common area, which accommodates the access drives, drainage and buffer wall and
landscaping for the Grove Plaza master plan. Tract "G" allows for vehicular ingress/egress from Hypoluxo
Road to all parcels within the master plan. The points of ingress / egress from Tract "G" to Parcel "F" would
occur only along it's west property line (of Parcel "F'). This project does not propose any new direct
Memorandum No. PZ 03-031
Grove Plaza (Grove Plaza AutoZone), MPMD 03-003
Page 2
connections onto Hypoluxo Road. The AutoZone project would share and utilize Tract "G" along with the
other parcels. Tract "G" would not be affected as a result of the proposed development.
Each parcel is required to provide the minimum parking for their respective use as designated on the plan.
The following summary indicates the required and provided parking for each parcel:
Parcel Name Required Parkina Provided Parkina
Parcel A 12 28
Parcel B 16 28
Parcel C 33 35
Parcel D 45 45
Parcel E 04 09
Parcel F 36 38
According to the applicant, the proposed change would represent a minimal difference in traffic impacts. On
December 10, 2003, Mr. Jay M. Huebner, P.E., prepared a traffic impact statement indicating that the
proposed auto parts store would generate less traffic than the originally approved restaurant. The statement
was sent to the Traffic Division of Palm Beach County for their review and approval. The Traffic Division had
the following comment: "A complete traffic study needs to be prepared and submitted to the City of Boynton
Beach and Palm Beach County Traffic Division. The study must address all requirements of Palm Beach
County Traffic Performance Standards". On January 16, 2004, the applicant submitted a revised statement.
At this time, the project is still under review and staff has not yet received confirmation from the Traffic
Division that it meets the Traffic Performance Standards of Palm Beach County. Therefore, no building
permits would be issued until such time of confirmation (see Exhibit "C" - Conditions of Approval).
RECOMMENDATION
The Technical Review Committee (TRC) has reviewed this master plan modification request. Staff
recommends approval, contingent upon the comments indicated in Exhibit "C" - Conditions of Approval. Any
additional conditions recommended by the Board or City Commission shall be documented accordingly in the
Conditions of Approval.
MR/ej
Xc: Central File
S:\PlanningISHAREDlWP\PROJECTS\grove plaza\Grove Plaza MPMDlAuto Zone MPMD 03-Q03\Staff Report.doc
. EXHIBIT "A"
..
,
1 in. = 313.0 feet
COUNTY PO
IIIIII111 r f--
~
. '""
.
MTl""uLUXO RD
7fr r
-
I- -
--
r--- ~ --
- I--.
CO I AR t
I YI ...... .- --.
...I..
.... '- \..
~ I- ]
-
)- '--- ~
~
Q -
I- =
LAWRENCE. RD
----------
r--- I I
'\
./
.- .,. "'"' I J
- I \ .-,-. !loI
~\
- I' I ~
I- =ffr \ \ r I
"- "J..--" ~
"- ~,~~
l-
I- t--- t--
I- \ ~ t--
LOCATION MAP 1"1
".
.~
PROPQSED MASTER PLAN EXHIBIT "B"
~ ~!I'i Iii!; III; mSii;; ; ; I'
. ii' IJ'I 11"11-' III!
: 1"'11:111". :.11, I; M
......... 'I'lq'~p'" 1!I'fl. I:
i;f: f.ID !iil =,;iM ~ i i
II;; elm ;i': lii,'!li q f
1:1; ;,'II~ .d; li!I' liij I
Illi ~ I I ul. -i' . .
: .i. if JH;' 1':1111
:: II I. ;.1 'i
-.-
..-..- 'Oftc.
1:
t
()
n )>
q~
! ~ )>
h~ ji
II~ z
HI -u
51 ill ::0
, 0
i . ()
i!i d
liS ~
~. ::0
!;t 0
I LgJ
ill z
~ ~
~
a
I
f
a
I
.
;
i
I! II
e~1
,.1
,I"
..
i~~
II
G)
3:::0
)0 0
(J> <
iil m
::0 '1:J
~ ~
~
o
i! ...
. .
~.:~
~ w
~
........
~II
..-.. ,=:.~ --.- I
~
I
~
........
~
~
!
.
.
r i
II ~ I(
f 'a
I
I
I
:1
:i
f
I:
i:
.
.. ;; ~. p p
:1 n "e 1'1::111 I
In'. hlt,llbal "=
'1" ~I!IJ ,IU ;; 'li11; I
Iii I' idi i
II . tlli =1 !il'l I
I !iI,i; If !!I~ ,~
: Iii I,I ; I i~r,! I
li..lili"
I ~ 11"
11I11I1f I
~ ~ ~ ~ ~ :11 i
111111111111,',' !
ilninnin .
1IIIIIIIIIIt
..;;....ii;i;11
III~mmn
-r--.
Lilli
- t . . . .
. - , , . ,
i !:' ~ !
~ml;i& if Ii
mnJJ 'z ~
Ifnll!.'
nUl!!! J
fU~jiEE
,~....
........:"..
..:':'11:-
:wa!,a
'lrl'~!:
!-!: -
Ii
,=
.'
I
C!
$z
EXHIBIT "C"
Conditions of Approval
Project name: Auto Zone
File number: MPMD 03-003
Reference: 2nd review plans identified as a Master Plan Modification with a January 27. 2004 Planning and
Zoning Department date stamp marking.
,
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments: None
PUBLIC WORKS - Traffic
Comments: None
ENGINEERING DIVISION
Comments: None
UTILITIES
Comments: None
FIRE
Comments: None
POLICE
Comments: None
BUILDING DIVISION
Comments: None
PARKS AND RECREATION
Comments: None
FORESTER/ENVIRONMENTALIST
Comments: None
PLANNING AND ZONING
Comments:
COA
02/12/04
2
,
DEPARTMENTS INCLUDE REJECT
1. A revised traffic impact statement, prepared by Carnahan, Proctor, and Cross,
Incorporated was sent to the Palm Beach County Traffic Division for their
review and approval. This statement must be approved prior to the issuance
of any building permits for the corresponding site plan for AutoZone (NWSP
03-028).
PLANNING & DEVELOPMENT BOARD COMMENTS:
Comments:
2. To be determined.
CITY COMMISSION COMMENTS:
Comments:
3. To be determined.
elj
S:IPlanningISHAREDIWPIPROJECTSlgrove plazalGrove Plaza MPMDlAuto Zone MPMD 03-003ICOA.doc
1 st REVIEW COMMENTS
Master Plan Modification
hci.:=""/'/-e R
Project name: Auto Zone
File number: MPMD 03-003
Reference: I "review plans identified as a Master Plan Modification with a December 10. 2003 Planninl! and
Z'D d kin
omnl! . Jenartment ate stamp mar 1l!.
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments:
I. Prior to permit application contact the Public Works Department (561-742- j/
6200) regarding the storage and handling of refuse (CODE, Chapter 10).
2. The location depicted for the dumpster enclosure is not accessible for Solid /
Waste pick up. Relocate enclosure to the south end of the parking area to
allow direct pickup across from the south driveway.
PUBLIC WORKS - Traffic
Comments:
3. Provide a statement verifying that the proposed use does not impact
previously established traffic concurrency. !/'
4. The proposed site depicts parking stalls at 9 ft. x 18 ft. Current City
standards require a minimum stall size of 9 Y, ft. x 18 Y, ft. The applicant t.../
must meet the new standard at the time of site plan submittal for approval.
5. Provide a current survey accurately depicting the adjacent outparcels and
driveway locations to allow for evaluation ofintemal site traffic flow. /
ENGINEERING DIVISION
Comments:
6. Provide a generalized statement of subsurface conditions as required in the c./"'
LDR, Chapter 3, Article IV, Section 3.M.
7. Provide a copy of the Master Storm Water Management plan and the effect
of this site on the master plan as required in the LDR, Chapter 3, Article IV, l/""
Section 3.T.
8. Provide a minimum of one handicap accessible guest parking space. V
UTILITIES
Comments:
9. Show all required utilities and utility easements for the proposed site, /
including sanitary sewer (as required in the LDR, Chapter 3, Article IV,
Section 3.0.)
1ST REVIEW COMMENTS
01/07/04
2
z
DEPARTMENTS INCLUDE REJECT
FIRE
Comments:
10. Prior to Fire Department approval of a building permit, new construction /
projects must provide the results of a hydrant flow test indicating a fire flow
not less than 1500 gpm@20psi above domestic use. This applies to new
or existing hydrants within the required 200 feet of the facility.
POLICE
Comments: NONE
BUILDING DIVISION
Comments: NONE
PARKS AND RECREATION
Comments: NONE
FORESTER/ENVIRONMENT ALIST
Comments: NONE
PLANNING AND ZONING
Comments:
II. The master plan should be modified to show the updated information
regarding Parcel "E". The Motor City Carwash project developed Parcel
"E" and this information cannot be excluded from this master plan.
- R. <? L h ~c'?--
~ The Palm Beach County Traffic Division reviewed the traffic generation
statement and has the following comment: A complete traffic study needs /
to be prepared and submitted to the City of Boynton Beach and Palm Beach
County Traffic Division. The study must address all requirements of Palm
Beach County Traffic Performance Standards.
MWRIsc
S:\PlannlngISHAREDlWPIPROJECTSlAuto ZonelAuto Zone HypoluxolMPMO 03-00311ST REVIEW COMMENTS.doc
1 st REVIEW COMMENTS
Master Plan Modification
13~ bc::
Project name: Auto Zone
File number: MPMD 03-003
Reference: 1 "review plans identified as a Master Plan Modification with a December 10. 2003 PlanniPl! and
Z'D d kin
omn!! . Jeoartment ate stamn mar l!!.
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments:
1. Prior to pennit application contact the Public Works Department (561-742-
6200) regarding the storage and handling of refuse (CODE, Chapter 10).
2. The location depicted for the dumpster enclosure is not accessible for Solid
Waste pick up. Relocate enclosure to the south end of the parking area to
allow direct pickup across from the south driveway.
PUBLIC WORKS - Traffic
Comments:
3. Provide a statement verifying that the proposed use does not impact
previously established traffic concurrency.
4. The proposed site depicts parking stalls at 9 ft. x 18 ft. Current City
standards require a minimum stall size of 9 Y, ft. x 18 Y. ft. The applicant
must meet the new standard at the time of site plan submittal for approval.
5. Provide a current survey accurately depicting the adjacent outparcels and
driveway locations to allow for evaluation of internal site traffic flow.
ENGINEERING DIVISION
Comments:
6. Provide a generalized statement of subsurface conditions as required in the
LDR, Chapter 3, Article IV, Section 3.M.
7. Provide a copy of the Master Storm Water Management plan and the effect
of this site on the master plan as required in the LDR, Chapter 3, Article IV,
Section 3.T.
8. Provide a minimum of one handicap accessible guest parking space.
UTILITIES
Comments:
9. Show all required utilities and utility easements for the proposed site,
including sanitary sewer (as required in the LDR, Chapter 3, Article IV,
Section 3.0.)
1ST REVIEW COMMENTS
01107/04
2
DEPARTMENTS INCLUDE REJECT
FIRE
Comments:
10. Prior to Fire Department approval of a building permit, new construction
projects must provide the results of a hydrant flow test indicating a fire flow
not less than 1500 gpm @ 20 psi above domestic use. This applies to new
or existing hydrants within the required 200 feet of the facility.
POLICE
Comments: NONE
BillLDING DIVISION
Comments: NONE
PARKS AND RECREATION
Comments: NONE
FORESTER/ENVIRONMENT ALIST
Comments: NONE
PLANNING AND ZONING
Comments:
11. The master plan should be modified to show the updated information
regarding Parcel "E". The Motor City Carwash project developed Parcel
"E" and this information cannot be excluded from this master plan.
12. The Palm Beach County Traffic Division reviewed the traffic generation
statement and has the following comment: A complete traffic study needs
to be prepared and submitted to the City of Boynton Beach and Palm Beach
County Traffic Division. The study must address all requirements of Palm
Beach County Traffic Performance Standards.
MWR/sc
S:\planningISHAREDlWPlPROJECTSlAulo ZonelAulo Zone HypoluxolMPMD 03-00311ST REVIEW COMMENTS.doc
K& ~-\
\ .2 f/ .0"1
1 st REVIEW COMMENTS
Master Plan Modification
Project name: Auto Zone
File number: MPMD 03-003
Reference: I "review olans identified as a Master Plan Modification with a December 10. 2003 Planninl!: and
Zonin" DPnartment date st.rnn marldn".
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments:
1. Prior to permit application contact the Public Works Department (561-742-
6200) regarding the storage and handling of refuse (CODE, Chapter 10).
2. The location depicted for the dumpster enclosure is not accessible for Solid
Waste pick up. Relocate enclosure to the south end of the parking area to
allow direct pickup across from the south driveway.
PUBLIC WORKS - Traffic
Comments:
3. Provide a statement verifying that the proposed use does not impact
previously established traffic concurrency.
4. The proposed site depicts parking stalls at 9 ft. x 18 ft. Current City
standards require a minimum stall size of 9 Yz ft. x 18 Yz ft. The applicant
must meet the new standard at the time of site plan submittal for approval.
5. Provide a current survey accurately depicting the adjacent outparcels and
driveway locations to allow for evaluation of internal site traffic flow.
ENGINEERING DIVISION
Comments:
6. Provide a generalized statement of subsurface conditions as required in the
LDR, Chapter 3, Article N, Section 3.M.
7. Provide a copy of the Master Storm Water Management plan and the effect
of this site on the master plan as required in the LDR, Chapter 3, Article N,
Section 3.T.
8. Provide a minimum of one handicao accessible l!lIest oarkinl!: soace.
UTILITIES
Comments:
9. Show all required utilities and utility easements for the proposed site,
including sanitary sewer (as required in the LDR, Chapter 3, Article N,
Section 3.0.)
1ST REVIEW COMMENTS
01/07/04
2
DEPARTMENTS INCLUDE REJECT
FIRE
Comments:
10. Prior to Fire Department approval of a building permit, new construction
projects must provide the results of a hydrant flow test indicating a fire flow
not less than 1500 gpm @ 20 psi above domestic use. This applies to new
or existing hydrants within the required 200 feet of the facility.
POLICE
Comments: NONE
BUILDING DIVISION
Comments: NONE
PARKS AND RECREATION
Comments: NONE
FORESTER/ENVIRONMENTALIST
Comments: NONE
PLANNING AND ZONING
Comments:
11. The master plan should be modified to show the updated information
regarding Parcel "E". The Motor City Carwash project developed Parcel
"E" and this information cannot be excluded from this master plan.
12. The Palm Beach County Traffic Division reviewed the traffic generation
statement and has the following comment: A complete traffic study needs
to be prepared and submitted to the City of Boynton Beach and Palm Beach
County Traffic Division. The study must address all requirements of Palm
Beach County Traffic Performance Standards.
MWRIsc
S:\PlanningISHAREDlWPIPROJECTSlAuto ZonelAulo Zone HypoluxolMPMD 03-o0311ST REVIEW COMMENTS.doc
1/~11avi
/
V" (L-17 l~
!2k(
1 st REVIEW COMMENTS
Master Plan Modification
Project name: Auto Zone
File number: MPMD 03-003
Reference: 1 "review olans identified as a Master Plan Modification with a December 10. 2003 Planninl! and
d ki
Zoninl! Deoartment ate stamo mar nl!.
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments:
1. Prior to permit application contact the Public Works Department (561-742-
6200) regarding the storage and handling of refuse (CODE, Chapter 10).
2. The location depicted for the dumpster enclosure is not accessible for Solid
Waste pick up. Relocate enclosure to the south end of the parking area to
allow direct pickup across from the south driveway.
PUBLIC WORKS - Traffic
Comments:
3. Provide a statement verifying that the proposed use does not impact
previously established traffic concurrency.
4. The proposed site depicts parking stalls at 9 ft. x 18 ft. Current City
standards require a minimum stall size of 9 Yz ft. x 18 \12 ft. The applicant
must meet the new standard at the time of site plan submittal for approval.
5. Provide a current survey accurately depicting the adjacent outparcels and
driveway locations to allow for evaluation of internal site traffic flow.
ENGINEERING DIVISION
Comments:
6. Provide a generalized statement of subsurface conditions as required in the
LOR, Chapter 3, Article IV, Section 3.M.
7. Provide a copy of the Master Storm Water Management plan and the effect
of this site on the master plan as required in the LOR, Chapter 3, Article IV,
Section 3.T.
8. Provide a minimum of one handicao accessible l!IIest oarkinl! soace.
UTILITIES
Comments:
9. Show all required utilities and utility easements for the proposed site,
including sanitary sewer (as required in the LOR, Chapter 3, Article IV,
Section 3.0.)
1ST REVIEW COMMENTS
01/07/04
2
DEPARTMENTS INCLUDE REJECT
FIRE
Comments:
10. Prior to Fire Department approval of a building permit, new construction //
projects must provide the results of a hydrant flow test indicating a fire flow
not less than 1500 gpm @ 20 psi above domestic use. This applies to new
or existing hydrants within the required 200 feet of the facility.
POLICE
Comments: NONE
BUILDING DMSION
Comments: NONE
PARKS AND RECREATION
Comments: NONE
FORESTER/ENVIRONMENTALIST
Comments: NONE
PLANNING AND ZONING
Comments:
II. The master plan should be modified to show the updated information
regarding Parcel "E". The Motor City Carwash project developed Parcel
"E" and this information cannot be excluded from this master plan.
12. The Palm Beach County Traffic Division reviewed the traffic generation
statement and has the following comment: A complete traffic study needs
to be prepared and submitted to the City of Boynton Beach and Palm Beach
County Traffic Division. The study must address all requirements of Palm
Beach County Traffic Performance Standards.
MWRJsc
S:IPlanningISHAREDlWPIPROJECTSlAuto ZonelAuto Zone HypoluxolMPMD 03-Q0311ST REVIEW COMMENTS.doc
1 st REVIEW COMMENTS
Master Plan Modification
Project name: Auto Zone
File number: MPMD 03-003
Reference: l"review plans identified as a Master Plan Modification with a December 10.2003 Planning and
Z . d kin
omn" D""artment ate starnn mar ~g.
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments:
1. Prior to permit application contact the Public Works Department (561-742- q
6200) regarding the storage and handling of refuse (CODE, Chapter 10). .,
I"
2. The location depicted for the dumpster enclosure is not accessible for Solid \
Waste pick up. Relocate enclosure to the south end of the parking area to i
allow direct pickup across from the south driveway. ,
-
PUBLIC WORKS - Traffic
Comments:
3. Provide a statement verifYing that the proposed use does not impact {,-,
previously established traffic concurrency. " '
"
, ,
4. The proposed site depicts parking stalls at 9 ft. x 18 ft. Current City
standards require a minimum stall size of 9 Y, ft. x 18 Y, ft. The applicant ,
must meet the new standard at the time of site plan submittal for approval. :
5. Provide a current survey accurately depicting the adjacent outparcels and .....
driveway locations to allow for evaluation of internal site traffic flow. ,~
ENGINEERING DIVISION
Comments:
6. Provide a generalized statement of subsurface conditions as required in the k~~ -
LDR, Chapter 3, Article IV, Section 3.M. \ .,
, I
,\
7. Provide a copy of the Master Storm Water Management plan and the effect I
of this site on the master plan as required in the LDR, Chapter 3, Article IV, ,
Section 3.T. "
8. Provide a minimum of one handicao accessible guest parking space. '\,
UTILITIES
Comments:
9. Show all required utilities and utility easements for the proposed site, \"'
including sanitary sewer (as required in the LDR, Chapter 3, Article IV, . ,c ~
Section 3.0.) :
"
,