REVIEW COMMENTS
Johnson, Eric
From:
Sent:
To:
Subject:
Large, Tim
Friday, July 08, 2005 11 :25 AM
Johnson, Eric
Heritage Club
Eric,
Here are a list of the comments that were addressed in the meeting of 7/7/05 for the Heritage Club.
Comments # 35,39,42,43,44,45,46,47,48,49,50,51,52.
Tim
\lA--t (
l3 Q;\~ lo~~fA-\-0
1
Johnson. Eric
Subject:
Jason Mankoff [JMankoff@zonelaw.com]
Tuesday, July 12, 2005 3:41 PM
'Johnson, Eric'
RMathias@NewCenturyCompanies.com; Ashlee Vargo; Michael; 'Andrea Troutman PE
(pinder troutman)'; 'Stuart Debowsky'; 'Jose Saumell (msa)'
RE: Heritage Club Shared Parking
From:
Sent:
To:
Cc:
Eric,
Based on the below, please feel free to' add the following two conditions:
1. Each of the 12 units will be assigned a space.
2. Buyers of each of these 12 residential units shall be provided
written notice at execution of contract that they are guaranteed only 1
space.
Thanks,
Jason S. Mankoff, Esq.
weiner & Aronson, P.A.
102 N. Swinton Avenue
Delray Beach, FL 33444
561.265.2666 x 303
561.272.6831 (fax)
jmankoff@zonelaw.com
-----Original Message-----
From: Johnson, Eric [mailto:JohnsonE@ci.boynton-beach.fl.us]
Sent: Tuesday, July 12, 2005 3:32 PM
To: 'jmankoff@zonelaw.com'
Subject: FW: Heritage Club Shared Parking
Jason. . . FYI
> -----Original Message-----
> From: Livergood, Jeffrey
> Sent: Friday, July 08, 2005 11:48 AM
> To: Johnson, Eric
> Cc: Breese, Ed
> Subject: RE: Heritage Club Shared Parking
>
> Eric,
>
> I have reviewed the shared parking analysis for the Heritage Club
> Development prepared by Pinder Troutman Consulting, Inc. The analysis
> evaluates the potential for shared parking for portions of the development
> including office, retail, restaurant and residential. pinder Troutman has
> utilized a shared parking analysis procedure based upon study data
> provided by the Urban Land Institute (ULI).
>
> The analysis concludes that peak parking period for the above referenced
> uses will occur on a typical weekday between the hours of 1:00 PM and 2:00
> PM. The study finds the need for 104 parking spaces. The development is
> providing 110 parking spaces. The extra six spaces will provide some
> cushion for other peak periods such as holidays that are not considered in
> the study.
>
> I believe that the study is sound for a typical weekday. However, given
> the mixed use parking demand, there may very well be periods such as
> holidays in which the parking demand will exceed the supply of 110 spaces.
> Furthermore, the study utilizes sample data from the ULI for base data.
1
> This data does not consider that a restaurant, for example, could be
> highly successful with the parking demand limited only by the amount of
> time that patrons are willing to wait to be seated. In other words, the
> parking demand for a successful restaurant should not be based upon full
> occupancy of all restaurant tables. It is difficult to define a successful
> restaurant. In this scenario, a highly successful restaurant would
> absorb all parking and could negatively affect the residential component.
> The peak use period requires that 12 parking spaces be assigned to the
> residential component. Therefore, only 12 of the 110 parking spaces can be
> identified for residential use only. Buyers of each of the residential
> units would need to be informed that they are guaranteed only one parking
> space.
>
>
> Jeff
>
>
> Jeffrey R. Livergood, P.E.
> Director of Public Works
> City of Boynton Beach
>
> -----Original Message-----
> From: Johnson, Eric
> Sent: Wednesday, June 29, 2005 9:17 AM
> To: Livergood, Jeffrey
> Cc: Breese, Ed
> Subject: Heritage Club Shared Parking
>
> Jeff,
>
> As you know, the Heritage Club project is a large scale, mixed-use
> development, set for the July 12, 2005 CRA meeting. The developer
> submitted a shared parking analysis utilizing the ULI's methodology.
> Today (Wednesday), I will be forwarding it to your office via inter-office
> snail mail.
>
> At your earliest convenience, please review the analysis and make your
> usual determination on its accuracy and acceptability. Thank you for your
> consideration in this matter.
>
> Eric
2
DEVELOPMENT DEPARTMENT
PLANNING AND ZONING DIVISION
MEMORANDUM NO. PZ 05-117
STAFF REPORT
TO:
Chair and Members
Community Redevelopment Agency and City Commission
DATE:
Michael Rumpf
Planning and Zoning Director
Eric Lee Johnson, AICP ~
Planner 0
July 6, 2005 .
THRU:
FROM:
PROJECT NAME/NO:
REQUEST:
Heritage Club / NWSP 05-014
New Site Plan
PROJECT DESCRIPTION
Property Owner: Thirty Six Hundred Holdings, LLC
Applicant: New Century Companies, LLC and Thirty Six Hundred Holdings, LLC
Agent: Mr. Michael Weiner, Esquire / Weiner & Aronson, P.A.
Location: Northwest corner of the intersection of Federal Highway and Gulfstream
Boulevard (Exhibit "A'')
Existing Land Use: Local Retail Commercial (LRC)
Existing Zoning: Community Commercial (C-3)
Proposed Land Use: Special High Density Residential
Proposed Zoning: PUD Planned Unit Development
Proposed Uses:
Office:
Retail:
Restaurant:
Residential:
6,544 square feet
9,494 square feet
3,500 square feet
70 townhouse units
96 multi-family units
Acreage:
:t8.302 acres
Adjacent Uses:
North:
Developed property (self-service storage) designated Local Retail Commercial
and zoned C-3 Community Commercial;
Staff Report - Heritage Club (NWSP 05-014)
Memorandum No PZ 05-117
Page 2
South:
Developed outparcel (adult entertainment) designated Local Retail Commercial
and zoned C-3 Community Commercial, then the right-of-way of Gulfstream
Boulevard, then developed commercial (fast-food and office bUilding)
designated Local Retail Commercial and zoned C-3 Community Commercial;
East:
Right-of-way of Federal Highway then undeveloped property in the Town of
Gulfstream designated Recreation and zoned OR Outdoor Recreation; and
West:
Rights-of-way of Old Dixie Highway and the Florida East Coast Railroad, then
vacant property in Palm Beach County designated MR-5 (5 du/ac) and zoned
RS-Single-family Residential.
PROPERTY OWNER NOTIFICATION
Owners of properties within 400 feet of the subject conditional use were mailed a notice of this request
and its respective hearing dates. The applicant certifies that they posted signage and mailed notices in
accordance with Ordinance No. 04-007.
BACKGROUND
Proposal:
Mr. Michael Weiner, agent for the property owner (Thirty Six Hundred Holdings,
LLC) is requesting to develop a large scale, mixed-use project. The survey shows
that the subject property is currently developed with a one (l)-story shopping
center and related parking areas. The intent is to raze the existing shopping center
and redevelop the site with 13 townhouse buildings and two (2) mixed-use
buildings, including their interior parking garages. Approval of this project is
contingent upon the approval of the accompanying request to amend the Future
Land Use Map and rezone (LUAR 05-005) the property from Community
Commercial (C-3) to Planned Unit Development (PUD). It should be noted that the
current PUD regulations permit neighborhood commercial uses within the
residential development, but require that the areas designated for commercial
activities not front on exterior or perimeter streets and preferably are located
centrally within the project. Staff is proposing an amendment to the Land
Development Regulations, Chapter 2.5 Planned Unit Development, Section 9.D.
Commercial Standards, to allow for commercial uses in PUDs to front on exterior or
perimeter streets, when such locations are consistent with adopted redevelopment
policies and plans. Therefore, approval of this site plan is contingent upon the staff
initiated request for code review (CDRV 05-011). Also, the PUD zoning district
allows for a maximum height of 45 feet. The applicant submitted an accompanying
request for height exception (HTEX 05-004) because as proposed, decorative
features of the building would exceed the 45-foot heightthreshold (see Exhibit "C"
- Conditions of Approval).
Staff Report - Heritage Club (NWSP 05-014)
Memorandum No PZ 05-117
Page 3
ANALYSIS
Concurrency:
Traffic: Generally, anticipated project traffic is generated by two factors, namely the
proposed use and its intensity. Intensity is typically measured by the proposed
building area (in square feet). The project's traffic statement was reviewed and
approved by the Palm Beach County Traffic Division. Based on the Traffic
Division's review, it has been determined that the residential portion of the
proposed mixed-use redevelopment project is located within the Coastal Residential
Exception Areas of Palm Beach County, while the retail and office components
generate less daily and peak hour trips than the existing retail space which is to be
demolished. The project meets the Traffic Performance Standards of Palm Beach
County, contingent upon the provision of a southbound exclusive right-turn lane on
North Federal Highway leading to the project access driveway. No building permits
are to be issued after the build-out date of 2008 (see Exhibit "C" - Conditions of
Approval).
Utilities: The purchase of up to 5 million gallons of potable water per day from Palm Beach
County Utilities would supply potable water for this project (projected to a total of
83,885 gallons per day). Local piping and infrastructure improvements may be
required for the project, dependent upon the final project configuration and fire-
flow demands. These local improvements would be the responsibility of the site
developer and would be reviewed at the time of permitting. Sufficient sanitary
sewer and wastewater treatment capacity is currently available to serve the project
total of 44,225 gallons per day, subject to the applicant making a firm reservation
of capacity, following approval of the site plan.
Police/Fire: For the purposes of this study, a statistical analysis was completed to show the
percentage of increase of police calls for service for the selected project area. A
crime analysis for 2004 shows that there have been 9,814 calls for service for zone
5, which represents 14.4% of all calls for service. There are no other existing
developments to use as a comparison for this assessment. It must be noted that
this project is one of six (6) mixed-use projects planned for completion. An
increase of 12% of total calls for service is projected from proposed citywide
growth. The subject project would have a direct impact on providing an adequate
level of public service to this area. The need for additional officers in Zone 5 is
evident by the high percentage of calls for service that one officer is currently
handling. Due to new development throughout the city, all city services will be
affected. Service requirements for the police department will be impacted greatly
and the demand for more police personnel and equipment will be needed to
balance the increase in population.
Fire staff reviewed the site plan and determined that current staffing levels would
be sufficient to meet the expected demand for services. Infrastructure
requirements such as hydrants and roadways would be addressed during the
Staff Report - Heritage Club (NWSP 05-014)
Memorandum No PZ 05-117
Page 4
permitting process (see Exhibit "C" - Conditions of Approval).
Drainage: Conceptual drainage information was provided for the City's review. The
Engineering Division is recommending that the review of specific drainage solutions
be deferred until time of permit review (see Exhibit "C" - Conditions of Approval).
School: Regarding school concurrency, the proposed project lies within Concurrency Service
Areas (CSA) 19 and SAC 283. Based on the School District of Palm Beach County's
adopted multiplier's for an average multi-family dwelling unit, the proposed
development may generate 14 elementary school students, seven (7) middle school
students, and 10 high school students. The School District determined that
adequate capacity exists to accommodate the projected resident children.
Driveways: The project can be characterized as "urban infill, mixed-use" development whereby
front building setbacks are minimal and off-street parking is relegated to a
subordinate role. The site plan shows that the development would be divided into
two (2) distinct areas, namely, the townhouse portion and the mixed-use portion.
The plans show that parking garages would provide for the majority of off-street
parking spaces for the mixed-use portion. The garages are intentionally proposed
as hidden structures located within the core of the project and virtually unseen from
the major roadways. Likewise, the project is not proposing traditional driveways or
surface parking lots like that of "suburban"-type of projects (where driveways
connect to off-street parking located in front of the buildings).
The site plan shows that vehicles would enter the site from three (3) points of
entry. Utilizing the existing curb-cut, the main entrance is proposed on Federal
Highway. This entrance would serve as the primary point of ingress for both the
mixed-use portion and the townhouse portion of the development. Vehicles
traveling southbound on Federal Highway would enter the site by utilizing the
deceleration lane proposed on Federal Highway and drive within the 15-foot wide
ingress lane. The egress lane would also be 15 feet wide and allow for right-turn
(south) traffic movement. The driveway, drive aisles, and turning radius, internal
to the development, would be improved to conform to current city engineering
standards.
An alternate entrance is also proposed along Federal Highway, at the northeast
corner of the site. However, this entrance would only be used as a one (l)-way
service drive for mixed-use Building 1. The drive aisle would connect to Old Dixie
Highway. Although not dimensioned, when scaled, it appears as though the
driveway opening would be 15 feet in width.
The third point of ingress is proposed along Gulfstream Boulevard. This driveway
opening would serve as the secondary point of ingress but proposed for only the
townhouse portion of the site. It would be gated and no access would be permitted
to the mixed-use areas. Although not dimensioned, when scaled, it appears as
though the driveway opening would be 15 feet in width. Likewise, the egress lane
would also be 15 feet in width. It would allow for right (west) and left (east) turn
traffic movements onto Gulfstream Boulevard.
Staff Report - Heritage Club (NWSP 05-014)
Memorandum No PZ 05-117
Page 5
Parking Facility: Off-street parking proposed within the development must meet the requirements in
Chapter 2, Section 11.H. of the Boynton Beach Land Development Regulations.
The project proposes a mix of residential, retail, restaurant, and office uses. One-
bedroom apartment units require one and one-half (1 V2) parking spaces. Two
bedroom apartment units require two (2) parking spaces. The project proposes
166 dwelling units (a mixture of one, two, and three bedrooms), requiring 330
parking spaces. Retail uses proposed within mixed-use projects require one (1)
parking space per 200 square feet of gross leasable floor area. For this project, a
total of 48 parking spaces would be required for the retail uses. Office uses require
one (1) parking space per 300 square feet of gross floor area. The project
proposes 6,544 square feet of office and therefore, would require 21 parking
spaces. Restaurants require one (1) parking space per two and one-half (2-112)
seats but not less than one (1) parking space per 100 square feet of gross floor
area. The site plan proposes 3,500 square feet and therefore, would require 35
parking spaces. In conclusion, under these standardized parking methodologies, a
total of 434 parking spaces would be required. In summary, the plan would provide
46 surface parking spaces, 235 parking garage spaces, and 140 townhouse garage
spaces. The project would only provide a grand total of 421 parking spaces, a
deficiency of 13 spaces. To comply, the applicant submitted a shared parking
analysis which demonstrates that 413 parking spaces would be required, resulting
in an excess of eight (8) spaces.
Building 1 proposes a mix of residential, commercial, restaurant, and office uses,
requiring 237 parking spaces. The parking garage internal to Building 1 would
provide only 152 spaces. Fifteen surface spaces are also proposed near Building 1,
which provides a total of 167 parking spaces but a deficit of 70 spaces. It should
be noted that the residential portion of Building 1 would require 164 spaces. The
intent is to restrict access to the garage to be used solely by the residents who
reside within Building 1. The commercial users would park in the surplus spaces
provided by Building 2.
The townhouse portion of the development would be self-sufficient in terms of its
required parking. The townhouses would require 145 spaces and would provide
155 spaces. This would be accomplished by providing 140 garage spaces and 15
on-street parking spaces. In addition to the off-street parking, the project is
proposing 21 on-street parking spaces within the Old Dixie Highway and Gulfstream
Boulevard rights-of-way. However, these spaces cannot contribute towards the
number of provided parking spaces. According to the applicant, however, they will
be unrestricted and open for public use.
Landscaping:
The cover sheet tabular data indicates that the proposed pervious areas would
equal 3.112 acres or 37.52% of the site. The tree removal plan (sheet T-1)
indicates the subject site currently contains 93 trees with a total of 955 caliper
inches to mitigate. The existing tree species are as follows: Black Olive, Cabbage
palm, Fish Tail palm, Mahogany, and several unknown trees. Eight (8) of the 93
trees would remain. The landscape plan proposes a 110% replacement of the
caliper inches, with a total of 62 canopy trees, 185 small non-shade trees, 164
Staff Report - Heritage Club (NWSP 05-014)
Memorandum No PZ 05-117
Page 6
palm trees, 34 small palm trees, 7,013 shrubs, and 3,381 groundcover plants.
According to the plant list, 226 of the 423 trees or 53% would be native. The
landscape plan also proposes a total of 6,073 plants or 58% of the shrubs / hedges
/ accents would be native species.
The plant material proposed along Federal Highway within the east landscape
(east) buffer would consist of the following species: Ixora Nora Grant, Dwarf Ilex
Holly, Golden Duranta, Redtip Cocoplum, Dwarf Bougainvillea shrub, Eugenia,
Washingtonia palm, Zahidi Date palm, Tree Ligustrum, and Florida Royal palm.
The Florida Royal palm trees would be 25 feet tall at the time of installation. Their
height would help soften the upper stories of the four (4) story buildings.
Ligustrum trees are proposed in between the Royal palm trees. These smaller
trees are strategically placed to provide more of a human scale. Both trees would
not interfere with overhead lines along Federal Highway.
The south landscape buffer would be 10 feet in depth in areas where it abuts the
out-parcel to the south. The existing mature Black Olives would remain and eight
(8) Pigeon Plum trees are also proposed to help soften the two (2) story parking
structure. A row of Redtip Cocoplum hedges are proposed (along the periphery of
the subject property) adjacent to the sides of the out-parcel. A row of Pigeon plum
trees are proposed along Gulfstream Boulevard within the fee-Simple lot area of the
three (3)-story townhouses. A row of Live Oak trees are proposed outside the fee-
simple area and within both the right-of-way for Gulfstream Boulevard and Old
Dixie Highway. In addition, the developer is proposing trees and shrubs at the
northwest corner of Federal Highway and Gulfstream Boulevard, which would serve
as a grand entrance into the City. Staff fully supports the installation of the trees
and shrubs within the rights-of-way. However, all plant material proposed outside
the property line must be excluded from the plant list in terms of meeting the
minimum required landscape requirement (see Exhibit "C" - Conditions of
Approval).
In the past, the Old Dixie Highway corridor was not improved to current City
standards. Therefore, the developer will be required to set aside the western 20
feet of the subject property for right-of-way purposes. As proposed, the
townhouse buildings along Old Dixie Highway would be setback 20 feet from the
sidewalk interior. The interior of the sidewalk would demarcate between private
and public ownership. This 20-foot wide setback area would also function as the
western landscape buffer. A black aluminum rail fence (42 inches in height) is
proposed within the buffer area. It would be setback approximately six (6) feet
from the back of the sidewalk. Additionally, either Pigeon Plum trees or Live Oak
trees, in conjunction with various shrubs / groundcover (Purple Crinum Lily, Dwarf
Indian Hawthorne, and Tricolor Shefflera) is also proposed within this 20 foot wide
buffer, within the limits of the fee-simple area of the townhouses. It should be
noted that the choice of canopy trees, proposed within the northern half of this
west landscape buffer, is limited due to the presence of overhead power lines that
currently run parallel to Old Dixie Highway. There are no overhead power lines
present within the southern half of the west landscape buffer and therefore, Live
Oak (street) trees may be planted there.
Staff Report - Heritage Club (NWSP 05-014)
Memorandum No PZ 05-117
Page 7
The north landscape buffer would be four (4) feet in width at its narrowest point
and 12 feet wide at its widest point. It would contain a mix of trees, shrubs, and
groundcover (Silver Buttonwood, Yellow Elder, Redtip Cocoplum, and Wild Coffee).
A one (l)-way drive aisle would run parallel to this landscape buffer.
The interior of the site would contain a substantial amount of plant material. Staff
focused on the location and height of the proposed trees, especially in areas where
the parking structures are proposed. The landscape plan shows that the planting
strip along the north fa<;ade of Building 1 would be approximately 12 wide. The
landscape plan proposes a row of Cabbage palm (installed at 16 feet to 23 feet of
clear trunk), Fishtail palm (12 feet to 14 feet in height), and Ligustrum (10 feet).
These trees would help to provide an upper level and lower level canopy. In
addition, the northeast, northwest, and southwest corners of Building 1 would have
clusters of Washingtonia palm trees installed at 18 feet to 24 feet in height. The
front (south) fa<;ade of Building 1 would have a row of Solitaire palm trees installed
at 18 feet to 22 feet in height. Building 2 is also proposed as a four (4)-story
building but mainly along Federal Highway. The interior parking garage would only
be two (2)-stories tall. The landscape plan proposes a row of Pigeon Plum trees
along the north fa<;ade of Building 2. Staff recommends substituting the Pigeon
Plum trees, proposed at the main access drive with Royal palm trees (see Exhibit
"C" - Conditions of Approval).
Building and Site: The site plan proposes a mix of residential and commercial uses. The commercial
square footage would total 3.52% of the entire site. Building and site design as
proposed would generally meet code requirements when staff comments are
incorporated into the permit drawings. The maximum allowed density of the SHDR
land use category would be 20 dwelling units per acre. The proposed project
density would be 20 dwelling units per acre. As previously mentioned, the existing
commercial buildings would be replaced with the proposed four (4)-story mixed-use
buildings and three (3)-story townhouse buildings. The depth of the parcel extends
westward from Federal Highway to Old Dixie Highway, excluding the lone out-
parcel where the adult entertainment establishment is located. As such, the
subject property fronts on three (3) rights-of-way. The taller, four (4)-story,
mixed-use buildings would front on Federal Highway whereas the three (3)-story
townhouse buildings would face Old Dixie Highway and Gulfstream Boulevard. The
mixed-use buildings would contain an internal parking garage. All buildings are
oriented so that they "face" the street, a characteristic fully endorsed by staff. The
PUD zoning district allows for a maximum height of 45 feet. The elevations of
Building 1 and Building 2 show that portions of their roofline would exceed the
maximum allowed height. However, these appurtenances are decorative
architectural elements and / or inhabitable spaces, and would be considered
eligible for height exception. The applicant requested a height exception of 15
feet. The review of the height exception is discussed in an accompanying staff
report (HTEX 05-004). The height, as defined by the Land Development
Regulations of Building 1 and 2 would be 41 feet. Their parapet walls are proposed
at 46 feet in height, which is permitted by the Regulations. Generally, the three
(3)-story townhouses are proposed at 35 feet - nine (9) inches in height.
Staff Report - Heritage Club (NWSP 05-014)
Memorandum No PZ 05-117
Page 8
However, the townhouse building proposed directly west of Building 2 would be 31
feet - six (6) inches in height. The building was designed with a different roofline
in order to achieve greater compatibility with Building 2 in terms of its style, mass,
and height. In summary, all proposed buildings meet code as it relates to
maximum building height.
All buildings are proposed within close proximity of the property lines (that front on
rights-of-way) in order to create a more urban environment, consistent with
recommendations of the Federal Highway Corridor Redevelopment Plan. The east
setback along Federal Highway would vary slightly but maintain at least a 20-foot
front setback. This is to maintain a clear line-of-site and to accommodate a
deceleration lane along Federal Highway. The south side setback of Building 2,
where it abuts the outparcel, would be 10 feet in width. The townhouse buildings
proposed along Gulfstream Boulevard would have a setback 15 feet in width. The
closest a townhouse building would be from the property line where it abuts the
commercial outparcel would be 20 feet. As previously mentioned, the townhouses
proposed along Old Dixie Highway would be 20 feet from the interior of the
sidewalk. It should be noted that there are a few places along the west property
line that are notched inward. As such, the proposed building setbacks would be
reduced. The greatest building setbacks occur along the north property line.
Building 1 would be 32 feet- four (4) inches at minimum while the closest
townhouse would be 50 feet away from the north property line. This is due to the
location of the existing one (l)-way drive aisle.
The proposed building composition would be as follows: Residential - 282,271
square feet; Retail- 9,494 square feet; Office - 6,544 square feet; and Restaurant
- 3,500 square feet. The plans show that the commercial areas of the mixed-use
buildings would occur on the first and second floors only. The condominium units
would occur on all floors. According to the tabular data, the one (l)-bedroom and
two (2)-bedroom units are proposed in the mixed-use buildings would come in a
variety of sizes. The smallest one (l)-bedroom unit would be 790 square feet
(under A/C) and the largest three (3)-bedroom unit would be 1,725 square feet in
area.
Design:
The proposed development is generally divided into two (2) distinct halves. The
eastern half would be comprised on the mixed-use buildings and the western half
would be comprised on the townhouse buildings. The proposed architecture could
be described as contemporary for the mixed-use buildings and traditional for the
three (3)-story townhouse buildings. Both styles, as proposed, transition well and
are compatible with each other. Also noteworthy is that the project parking would
be virtually hidden from all views and is considered to be a subordinate,
unobtrusive element of the plan. Vehicular traffic is contained within the internal
framework of the project. The parking garage would be enclosed but would have
decorative openings compliant with Florida Building Code. These openings would
resemble large windows.
The elevations show that the exterior finish of the walls would be textured stucco.
The applicant is proposing a variety of colors schemes as shown in tabular format
Staff Report - Heritage Club (NWSP 05-014)
Memorandum No PZ 05-117
Page 9
on sheet A-28. The project's proposed building colors are as follows:
White
Peach
Light Yellow
Yellow
Light Gray
Beige
Light Green
Light Blue
Charleston White
Drawing Room
Black House Yellow
Lowcountry Spoon bread
Aunt Bety's China
Aiken Ivory
Acanthus
St. Cecilia
DCR 100
DCR 035
DCR 008
DCR 014
DCR 101
DCR 002
DCR 084
DCR 069
The project also proposes hunter green canvas awnings on the mixed-use
buildings. The intent is to have all buildings (both mixed-use and townhouses)
with multiple colors. A general intent of Chapter 9 (Community Design Plan) is to
ensure that buildings achieve visual unity of character and design concepts, in part,
through the use of building colors. However, there are no established noteworthy
building colors or architectural themes within the immediate area with which this
project should be compatible. Therefore, the proposed colors for this site plan
would not be inappropriate, incompatible, or obtrusive.
The mixed-use buildings would have a unique roofline with Monier concrete tiles
(grey) and multiple-styled decorative towers. The decorative towers would come in
two (2) styles. As previously mentioned, this theme would be carried over to the
townhouse building proposed directly west of Building 2.
Signage:
Minimal project detail regarding proposed signage was shown with this submittal.
In the future, the applicant intends to submit a sign program but for now, the
signage would consist of 18-inch tall black reverse channel letters with Helvetica
font for the mixed-use buildings. A note on the elevations of Buildings 1 and 2
indicates that the entire project will follow similar signage with similar fonts and
colors. As presented however, the elevations are incomplete when referring to
project signage. Therefore, staff recommends utilizing a sign program for the
entire project to ensure sustained continuity throughout the life of the project (see
Exhibit "C" - Conditions of Approval). All project signage shall conform to the
regulations as set forth in Chapter 9 (Community Design Plan) and Chapter 21 of
the Land Development Regulations.
The site plan shows the location of the two (2) monument signs. The sign, located
along Federal Highway, would be primarily for the mixed-use portion of the
development while the other sign, located along Gulfstream Boulevard, would be
used to identify the townhouse portion of the development. Both structures would
be located at least 10 feet from the property line. The commercial sign would be
generally five (5) feet in height with a decorative portion of it, proposed at eight (8)
feet in height. The residential sign would be five (5) feet in height its peak. Both
sign's colors would be compatible with the building colors but again, a more
thorough investigation would occur at the time when the sign program is reviewed.
Staff Report - Heritage Club (NWSP 05-014)
Memorandum No PZ 05-117
Page 10
RECOMMENDATION:
Staff has reviewed this request and recommends approval, contingent upon the approval of the concurrent
rezoning application, height exception request, and all items noted within Exhibit "C" - Conditions of
Approval. Prior to Community Redevelopment Agency Board review, the applicant shall satisfactorily
address building division issues including but not limited to the comments pertaining to the interior parking
structures, percentage of wall openings, and type of construction. Any additional conditions recommended
by the Board or City Commission shall be documented accordingly in the Conditions of Approval.
S:\Planning\SHARED\WP\PROJECTS\Heritage Club @ Boynton Beach\NWSP 05-014\Staff Report.doc
LOCATION MAP
Heritage Club @ Boynton Beach
Exhibit A
(.)
If
III
....
E
.-
-J
.b
(j
...
cC
z
a
Ill:
cC
200
100
o
200 Feet
N
A
..
EXHIBIT B
/f-t_..._...
-~t~~~__
- -
J\
.,<~~~~~ I
~l:~,<3;~;
ii~ :~~.a ~
~il~i8f;
i~~~~~i
,..~H!
nun
~; ~.!."
~l i ii
!. H
i "!
.
.I;~I
imll
1,\
Llll' l~! .
: .i
1,1
@il
...
I
...
t~~~CTS
..., & PlANNING
~~~~SllMC
~=i:',~"J~l'"
M ~0008'~
HERITAGE CLU
BoynU: Beach 'B
New eenn:; Companies
i
~
i;~
~~ ~
L
" ~
}
~ ~u
r~.~ '~~ .~ ~~' t!~
, ;~ ~ f ~ t~
L-- ~M u~ ---'~
~
Iii ~ [I.:.i
~~iil ~ m
~h i izi
8if3" ,-'
ll,.. IZ......I,
,..~'"
ill :~:
~a !1cn:
Ii! l i~!
i!;:;!l ), '"
!ii~ ; Lr:t;IJ
lL~ ~
t~
~~
~J
i
~
!" ~J" ~,"!-.ecn
~ 2 . ....Su-
l ~ ~ '@il1~~~
~~ !ig ;U!;I~
6~ ~~I ~~~Siii~~
~~ H ~J~M~
~i r~ U ~~;m
p hi !h
E ! 2 ~~ ~~~
~ ~ : i! .~~
q ~ ! ~~
EXHIBIT B
~-~~ ~ .~. ~ "1. ~[~~~
~~ ~Il il~ : n f~
L- . ~ ,,~~ it
-<1(;-<>" * '- ~I ";
~
~ ~;g~it
fi
~
/
"tMSA. ;;;~: HERITAGE CLUB
ARCHITECTS ;:-~-" Boynto~Beacb
~~~~~~_~~~~~~:_'-';"", "",_",,","':"~=:-"':'~=="'_ _ .",,,,",,'. ~~w_ Cenlury Coml"lflies
\
l
h.
m
<
o I ,"
, '. / ~
r r[rr~ 11 P II
} .!
~ilr,~rr~ ~ I
t q6~~~~ "tMSI\ ~.~~'"
, . . IIRCHITECTS::: "~,;,- NLYUTA!,E aUB
, !. ~~ruu ."""'~ ""'""-
'" ~ =="'-:""''''=.'==~-==-'= ~~-~-
~
~I
i~~
~ ~
~'
.d:1g
~
~
un;
~
u'el
!Ql
'el 0
~
~ ~
~ Ii I
~
u'el
(Q)
W
~ 0
EXHIBIT B .
r -~~ r~:. ~-""-. -'1 ~~; ~ ~~
~ ~l~ l~ +~~ +~
l . ~ ! t~ ,.'
~= ~" ~~-\I ~!
~ I
'\
~
~XHIBIT B .
~I
un
~
tJ
n
[Q)
tJ
tJ 0
ij
~
. m
~ ~ m ED
~ti ii
ji! f ~-r!! N. ~ -]. ~1.. ~ :+~
~ l~ ,J ~ t ' ~~
8 ~ i L ~ ~~ ~'I \,
~ ~ ; ~r' ~ I
@ -l
ffi II.
~- !'=- ~ =: ~-'= 1'1~ l~
~~ ~i i~ ~Il ~~ ~I~
l- - - ---""". . "--~I \~
I
I' M
Nt ---
SI\. ~i"oo'oo'," HERITAGE C
_.~~ ,,,. 'LUB
ARCHITECTS ::",;.::.:;"" Boynro!Beach
ARCHITECTURE &: PLANNING New Century Companies
~~c ...~"':: ~~~,."';;.'~:.=;::,'~'";:" do."."."" -.. ........... "" ",.. -' ...../~ "- ~
___ .%.._ '" _.... ... ''''" _..",.ct- ... ~ """'....,t. ...- _ ,.,. '_"""""". :.:;;t"",,<on. '" ...".;.:',:... .. ... .0
I~
. ~
un b
~
n~
(Q)
~
~
f~ __
,ij
Iff
'j~ ~
, r ~"1. !~" ~ N" ~_.~" ~]~; ~ ~"t:~ l'~
1~ .~ i~ ~ III n. ~ I
I . . '\, ~ ~ l'
. -. ---- <<.:~-- -- J ..~ \,
~ _ I i
.~~.
9,D
n
(Q)
~
~
~
Iii
,,'i~
~~~
~~ ~
L:
h
:~ ~
~ .".or'o
:~ e~~~~~
o
.d>
~ @ -Ii
~ i I.
EXHIBIT B
r---------'
I
I
,
I
I
I
,
j -:r~"l~-~~ n~
l . --"~~. --- - ~~ !i~
~
~
.ij
~.~
~.~
~~
i
~
~I
un
~
n~
(Q)
1'!J
~ 0
1.
i~r" NC1 H'i H- t"'":l;~l. ~ ~ ~ ~~
it ;j ~ , t~ ~~ ~~
'l--- - :...,,~' ~ ..g ~!
~ ~
~
r;i
,-II
1m,
,ZI
I)>'
!l.g" IZ'
, if' ~ ,:
l[!" ,-I,
..ih ?I,
!ZH ; j(J),
.'f~ ~ .. ':J:!I
I 10 z: 1.......1
'6 j 10'
::J "i: I
"ie Lml
I ~~ ~
~- ... "=--- f. I N.- ~ ~ ~nH~~ f~
t~ ~~ ji ; i ~ il~
L -- -~"". <; -: ~I '";
~i U" ~:Es~~f5
Sa i~i ~~!Ia" z
~; a;~ mij;l~
~a u~ ~li~~~~z
I~ ;~i n ~~I~
t i i ~~ d=
~ a ~ es M
I d ;. ~Ii
~ P i ~I
r
ti
>.
111
~
/t\ MS/\ --- ~
~n:.'~-" HERITAGE CLUB
O:::i~~"JJI"" at: ~
2E~~~~~~,,~-~~~~~.:~=~=,.=-.. ._'~"'. ~_~:::;~':'ies ~
~
~
~.
~~~
~i
~
~~
~~~~ ~rLr~
~ -<~~ gZ
U
do
~ i;
'1.1
.::XHIBIT B
~
.~
J
2l
't'J
n
[Q)
1'!l
't'J 0
,.rr-,;-. -_n'~~f1'~-I- '~l~;]~~'.
. ~ ~ i ~H~
II ' ~ ~.~
I-- ~""---- ---- .'
~
~
2
I> 0
5 ~
'" m
I ~
I> ~
r m
r >J
m ~
I>
~ ~
'" I>
:'l '"
m I>
m ~
1) 0
o <
z m
'" lJ
(jj "
F ~
~ ~
~ f)
~ ~
lJ ~
~ ~
r ~
~ 3
~ ~
lii
I>
f)
r
n
n ['T1 Z
Oz
~-1~
6C
~~
i
. .
""'EXHIBIT B
;;; ~
ffi !!'
~ ~
~ 0
B
~ 0
>J m
~ ~
'"
I ~
E Z
~ ~
I> 1)
'" r
I> !t
>J ~
m 3
'" I>
c ~
r m
~ >J
~ ~
ffi :
8 ~
z ~
~ I>
>J "
I> 0
f) Z
~ g
(p ~
lJ
'"
C
~
~
"
,.,
]>
3:
J~
)
'\1'1
II
Q ~
ji
T
sr4rl:
'<04D
"'0. S
ql.'t(I?a.~ l!t~' HI - -.",,-----_____ ----0-.1
~'~"E~4Y 1...-0--'~
~tC7l~ N. r __-'
'JQI cos, E:DE:R4L __~=~~,v....., _
HIGH" l~. .....-._... '.
4 Y)~_, _',
.~-
o _.]~. ~
-I
81. - ~
- >
",- J;;
o I:~
r$- -:
o
=
"
~ i
i'
i!
!
,
B~~OJ Overall Landscape Plan EJO ....,,""'..
Heritage Club at Boynton Beach .n3__6rTE"'l.AN . ~".n\ll~1 "N\lM'TI~YURI
(ll ~:; 00,'- [t ~ IllEVl61~ e 0 :::::::::~:: """....
~~iq~~ ~ i
New Century Companies ARCHITECTURAL ALLIANCE
-J ' g Boynton Beach, Florida .......,.I'l;Um+--............-.., ......."._..
R~~I~on D~t... s...., T~_I_"""'_I-.on1 ~_
" '"
" c
~6
;z
~C1
-
j~~ i,
i'l'
~p
~
II~ ~i:l~ Ii ~I~ I!; i!
[ 1i. ~ 1~ ~ 1:! 11
) , /' /
,~ /'
'"
~
'"
m
~
~
(5
Z
;"
<l" !!
U
~!
C:XHIBIT B
L !I;
i'!
:~
a'.
. '
i
~ Ii Ii 1\
~1111i ~
!U1 UI i'~ !iii!!IS^
1U 3'11 ~ 'i II. "~Ii' I~
~I -+f!
I~ I~~ :ib In 1.1 !il
! ; ~ ~ '-1 ' 'I S '
r.
~~
ill'
r' ~ ,illl ~
I, ~ ' i; n 'j ~ ~ ~
h III id~ :; a II~
i ~ I ~ i t1'j" i ~ 'i~
i dU -ili . ;~ i i I;
In .!-dd; jl~ ~~
:iI!
o '" '"
"C C
1'" 6
;0
;z Z
~C1 C1
- -
'" '"
0 0
m CD m
m m
r- r-
~ :2
~
(5 (5
z z
'"
'\ n n
H j~1 U m -I
~ ie 3i lj. e
! i'
. . .
I
,- ,-
"'"
"C
~6
;z
~C1
-
-n
'"
o
Z
-i
m
r-
~
(5
z
;
i~
:is
--L~~__
/
:.
j~
e,
e
'"
~
=n !)~
lj. ;
,. Ii
'i ~I
~ l~ . . "1':''' . HERITAGE CLUB
i . : :ll'j'
)> J ~ ! ... . :Hi · AT BOYNTON BEACH
-<
N ~; i ;1l .!iW.
0') FOR NEW CENTURY COMPANIES
i~ 1 - . i!i!! .
BOYNTON BEACH, FLORIDA
o
i.
~ , 1 " 1 " , !U
~
~ ~
s
.
H, I~ H Ii Ii IPII~
Pi ~ u UU
h · l' -,
I ' i ~ I ~
i I -I ~ iI i I
I I I I I I P
i i i i i i i
~ ~ ~ ~ ~ ~ ~
;~ i i i i i Ii
; ~ ~ ~ ~ ~ ~
I;I!
iiii
ilil
~~~~
.m ~
......"'''' ~
!!!~; Ii ~ ~ Ii
::ii; ,* ~ !~
1!I:~a 51 i -8
~:::J i~ ~ ;
i i ~~
= ~l F.
51 0
i ~
!
I
i
;;
.;..1
i~
;;lie! ~ ~!
~~~~ l! II ~i
;~iiilll !SI!ls.. Ii
. i I
, ji!l ~
.II~! Ji~
: Iff ;till..
. ili II
~o -C
([)ro.
!!!.ro
O'ClN
::l
I, II;
i' !
~
~ j ~n
:~ ~ :~ ~
!" i :t!i
i 3i "II
)'
/ /
/
m /
d
~i
,
'.
!~
Ii
!!
EXHIBIT B
jl
Ii i=i~ !!!~~ Ii i !~ n
~! iii! ::;~~ ;~ ~ ~~
ifii ..- ,I ~ Ii
~~~~ ,,' i~. ~! ~~
i~ii ~ 1 "I
"'Ill"!'" qi o~
>
i i i ~
".
111111 I. !
;;~e!l ~ i! I
~~~~ i
.:;.11 ;:::: Ii
. I'll ! ~o -c
Uhf!; (t)(1).
!!l.ro
. lil, i OQ N
::l
.'"
" c
~6
.. z
cO
e~
."
m
~ ~I ~
\il ~ ~J;I l;l ~
I' )1 :'
/'
n
II~
:..)llll
"a
/J'
/
\
I~ 3U
i Ie !w Ullp ~iim!S; i'l '
! " i ~'a q i\il;if"' I~ !~. ~
r~ ~"'Ii "j , ,
~ 'I' i~; ;;1 .
3~! i j j
Ih I -'I · J! S '
!~.
i-
.'"
" c
-::6
,-
.z
;. 0
'~
."
m
<:
<:
'"
s:
'"
m
~
(5
Z
1,,1;
i' !
Iii 'ill
leI iii~~'
'I- .",li
~ IJ ~ i;!il~
\il ~~I q ~t!C1...1
l~ !n ;~'H;
.."
'"
o
Z
..,
m
~
(5
Z
I, ...,1;
;'!
d.
!i ~
~
~I~
i
~ '"
" c
-::6
;z
; 0
'~
ril
'"
s
6
z
o
~
."
m
<:
V>
~
m
~
~
(5
z
<:
V>
a
m
I!l
~
(5
z
"
In 3i! m
31s Ie "'5
-j! .
:1 ~
lCEI~
1 311
i ':
3 .
I r-. .'loll HERITAGE CLUB
J~t i . : :1I~1
)> . d' i ;m AT BOYNTON BEACH
. f : ;!lK
N po FOR NEW CENTURY COMPANIES
" , , . i
i:;::: N : llIii BOYNTON BEACH, FLORIDA
5 , , , , , , 'U
,
.
. ~
!
,
~ ...)ll IH! Ii !i ill; I ~
; ~I Ii ~~
. .. ~ n
~ dl Ii; ~ 1~ ~;
= ' ~~ ~ i ! i
a ;
! ! ! ! ! ! P
. . . . e e .
i i i i j j j
a a a a 1 a a
;~ a a a a a U
; ~ ~ ~ ~ ~ ~
"""
~ c
;=
"0
;z
cC'l
'<
'"
~
'"
~
~
o
z
,"
""
c
6
z
C'l
<
V>
i5
m
m
~
o
z
I ~!I;
i'!
E:XHIBIT B
" ""
~ c
;=
~o
: Z
;. C'l
0.<
I, !I;
i'!
pI
_I;
.!u
-! II~ d ;I~
I~ ~ 11 ~
)
/u..
e
j
/
/
/
~/
"
j~
t .
i~ I
~'. I
1i ~
."
'"
o
z
-;
m
r-
~
o
z
"
..
n
!.
..
-.
Ii
ji
" ""
~ c
;=
~o
: Z
; C1
'<
V>
~
~
:;:
~
o
z
I, il;
i'!
~ , , , - , , lU
.
~ ~
!
.
! {~ IH~ Si !i n UI~
. " Ii I~
~ Ai ~ .U ~ ~
r . ,. . ! I
5 ' ~; i -I !
a i a
~ ~ ~ ~ ~ ~ Ii
. i i . . . i
m m m m
i i i i i i i
!~ a a a a a Ii
.; ~ ~ ~ ~ ~ ~
il~ i
[n
:; ~..
it ~
~ Ij; ~!o!.
t'H U I'.
/' )
," ~ \ 1;lg ~~m Ii I ~~ n
i; i! Ii II n ~. ! r iiii
.! ! ::~~;;i ~l!
ji jl ji -I ~i j' i 1; .... ~~~ !~ ~ ~i
I .!~ s~ 1 ~;G~ I . ;2 ~~
iim ~ HI F<
~III"''''
II "
~! i ~
.::JI
I. 2
jl:!.i ~ ~I I
~~~~
i;;:n ;~~:: I.
~ P . ~rl;llt HERITAGE CLUB . I ill! ~O~
I J :11!1
:t> ~ ! .... ml AT BOYNTON BEACH :Il"fj' ('1)....
... ~.('1)
!'.:l I ;ll . ;il~ Im!"i
00 ~~ i < FOR NEW CENTURY COMPANIES OQ N
~~ : ilia.. BOYNTON BEACH, FLORIDA ::::l
t ~ ~
=1
I;
:n
:7
//
I;I~
i.i.
~igi
G~G~
i~ii ~
'<l1Cl'41Cl ~
m!71~ I
~~~~~ U l~ ~ to
..~ ;j .1. j- ! ~
:::~~ !! j ii ~
i. < I!
I ~i ~ ~
i:5 ~ x
- >
a ~
! ..
I
"'"
"C
. r=
.0
.. Z
bel
'x
e!.e.
~;;~I
I-
~ Ii
~~~~: I:
'!IIW!!Iii1
oq","l'll
;1.;:1
I;I~
mi
f>.,."I'C!
OGGi
i~ili ~
'lIllIlllll1 I!
m~~ 1I1!~ ! ~
~:~r ~i ~t:
,,= i~ j II
j:i ~ ~
i ~I F m
u 0><
i 'f!
! &J
I
i
jl:, .,! 'I
l~i' hU~~"^
.~81 .~8' 'I..a
h~~i 8si:!i-UI
t 3'~. ~_.thI8
Q'l : 4 n
i.. i~ ~. 8" "
i _ ' , , ia ~
i : !;l Ii
j;8 '$
/)
nn_ // / ~ ~
~~
.z
~el
x
""
~
....11
I;
~ I~
!~~~: I:
!liE!!!
~~"'~
;;i:11
'"
i5
...,
...,
~
6
z
)>
c.J
N
""
'\
!H il!
i' ji
iii.=! a~
d ·
HERITAGE CLUB
FORAT BOYNTON BEACH
NEW CENTUR
BOYNTON BE Y COMPANIES
ACH, FLORIOA
~ l~P
r~!1 i
,~ -
_ ~~ ~ f
":" i
m-t
~~S
~)Ci
~QItC)
Ul"Ul
.~W.
. ""1.
. ;,1 :
;il~
. ill!! ·
iXHIBIT B
1\ il !l
[ ~ i
.,.,
""
o
~
...,
,....
~
~
6
z
"
i"I.; ~ ;I~ ~I~
[ ~ i
u
I!lll
j;B .n
'8~
~
~
6
z
I~
Ii
i!
Wmll^
"~5i' I~
"'~. I~
Nt-ell
,!al 8
. I. i I ~
: )di I ;
hn J!~ ;
: ill;- I' ~
: I ~
~o""'C
(!)(!)..
~.ro
~N
EXHIBIT "C"
Conditions of Approval
Project name: Heritage Club @ Boynton Beach
File number: NWSP 05-014
Reference: 3rd review plans identified as a New Site Plan with a June 14. 2005 Planning and Zoning
Department date stamp marking
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments:
1. The applicant has indicated that compactors will be used for the mixed-use
buildings and will be brought out to central areas adjacent to the buildings for
pickup. Please indicate the number and size of these containers so we can
evaluate the required pad sizes and our ability to perform the pickup
operation.
PUBLIC WORKS - Traffic
Comments:
2. Additional right-of-way shall be dedicated to the City, via plat, to provide a
50-ft. right-of-way width. Reconstruct Old Dixie Highway and Gulfstream
Boulevard to provide two II-foot wide lanes, curb & gutter, sidewalk,
appropriate green space with landscaping, and necessary signing / striping.
Complete construction plans will be required in conjunction with the plat and
will be reviewed and approved prior to issuance of the Land Development
Permit (LDP). Construction of the required improvements shall be completed
prior to issuance of the final COs for the project as required by the
Amendments to the Building Code. A surety shall be provided for the
required off-site improvements in the amount of 110% of the engineer's
estimate for the off-site work prior to issuance of the LDP.
The applicant shall also provide design plans for reconstruction of the
FECRR / Gulfstream Boulevard crossing, including roadway re-alignment,
curb & gutter, concrete median dividers, striping, and signals. The applicant
shall provide an engineer's estimate for the railroad crossing. The City will
consider sharing the cost of construction of the FECRR crossing. The extent
of cost share is subject to allocation of funds in the City budget for fiscal year
2006 / 2007.
3. At the time of permitting, delineate and stripe 12- foot x 35 foot loading zones
for the retail buildings; include a pavement message in yellow indicating "No
Parking - Loading Zone".
ENGINEERING DIVISION
Comments:
4. Full drainage plans, including drainage calculations, in accordance with the
LDR, Chapter 6, Article IV, Section 5 will be required at the time of
COA.doc
07/06/05
2
DEPARTMENTS INCLUDE REJECT
permitting.
5. It may be necessary to replace or relocate large canopy trees adjacent to light
fixtures to eliminate future shadowing on the parking surface (Chapter 23,
Article II, Section A.1.B.). Further evaluation will occur at the time of
permitting.
6. Paving, Drainage and Site details will not be reviewed for construction
acceptability at this time. All engineering construction details shall be in
accordance with the applicable City of Boynton Beach Standard Drawings
and the "Engineering Design Handbook and Construction Standards" and
will be reviewed at the time of construction permit application.
UTILITIES
Comments:
7. Palm Beach County Health Department permits will be required for the water
and sewer systems serving this project (CODE, Section 26-12).
8. Fire flow calculations will be required demonstrating the City Code
requirement of 1,500 g.p.m. (500 g.p.m. some residential developments) with
20 p.s.i. residual pressure as stated in the LDR, Chapter 6, Article IV, Section
16, or the requirement imposed by insurance underwriters, whichever is
greater (CODE, Section 26-16(b)).
9. The CODE, Section 26-34(E) requires that a capacity reservation fee be paid
for this project either upon the request for the Department's signature on the
Health Department application forms or within seven (7) days of site plan
approval, whichever occurs first. This fee will be determined based upon
final meter size, or expected demand.
10. Comprehensive Plan Policy 3.C.3.4. requires the conservation of potable
water. As other sources are readily available City water shall not be allowed
for irrigation.
11. A building permit for this project shall not be issued until this Department has
approved the plans for the water and/or sewer improvements required to
service this project, in accordance with the CODE, Section 26-15.
12. Show all off-site improvements to the existing water and sewer infrastructure
as follows:
a. The on-site lift station must be upgraded or replaced so as to
accommodate the added demand and the constraints imposed by site
changes. Existing gravity and pressure flows to the station must be
accommodated in the design.
COA.doc
07/06/05
3
DEPARTMENTS INCLUDE REJECT
b. The water system must be connected to the existing 8-in. water main
located on the east side of Federal Highway. In addition, an 8-in. water
main connection must be established from the 12-in. water main located
on the west side of Seacrest Boulevard, to the existing 8-in. line that
terminates on SE 34th Ave. in the vicinity of SE 3rd Court; or an alternate
route may be considered to establish an 8-in. water main connection to
the 12-in. main on Seacrest Boulevard. The intent of the design is to
establish an 8-in. loop from Federal Highway to Seacrest Blvd., thereby
assuring adequate fire protection and domestic supply.
13. Utility construction details will not be reviewed for construction acceptability
at this time. All utility construction details shall be in accordance with the
Utilities Department's "Utilities Engineering Design Handbook and
Construction Standards" manual (including any updates); they will be
reviewed at the time of construction permit application.
FIRE
Comments:
14. All hydrants shall be in service before any vertical construction. Hydrant
flow is a minimum 1500 gpm @ 20psi.
POLICE
Comments: None
BUILDING DIVISION
Comments:
15. The height and area for buildings or structures of the different types of
construction shall be governed by the intended use or occupancy of the
building, and shall not exceed the limits set forth in Table 500 of the 2001
FBC.
16. Every exterior wall within 15 feet of a property line shall be equipped with
approved opening protectives per 2001 FBC, Section 705.1.1.2.
17. Buildings, structures and parts thereof shall be designed to withstand the
minimum wind loads of 140 mph. Wind forces on every building or structure
shall be determined by the provisions of ASCE 7, Chapter 6, and the
provisions of 2001 FBC, Section 1606 (Wind Loads). Calculations that are
signed and sealed by a design professional registered in the state of Florida
shall be submitted for review at the time of permit application.
COA.doc
07/06/05
4
DEPARTMENTS INCLUDE REJECT
18. Every building and structure shall be of sufficient strength to support the
loads and forces encountered per the 2001 FBC, Section 1601.2.1 and Table
1604.1. Indicate the live load (pst) on the plans for the building design.
19. Buildings three-stories or higher shall be equipped with an automatic
sprinkler system per F.S. 553.895. Fire protection plans and hydraulic
calculations shall be included with the building plans at the time of permit
application.
20. At time of permit review, submit signed and sealed working drawings of the
proposed construction.
21. On the site plan and floor plan, indicate the number of stories that are in each
building including, where applicable, mezzanines. Indicate the overall height
of each building.
22. Add to each building that is depicted on the site plan drawing a labeled
symbol that identifies the location of the proposed handicap accessible units.
Add to the drawing the calculations that were used to identify the minimum
number of required units. Also, state the code section that is applicable to the
computations. Show and label the same units on the applicable floor plan
drawings. Compliance with regulations specified in the Fair Housing Act is
required (Federal Fair Housing Act Design and Construction Requirements,
Title 24 CFR, Part 100.205).
23. At the time of permit review, submit details of reinforcement of walls for the
future installation of grab bars as required by the Federal Fair Housing Act
Title 24 CFR, Part 100.205, Section 3, Requirement #6. All bathrooms within
the covered dwelling unit shall comply.
24. Add to the drawing the calculations that were used to identify the minimum
number of required handicap accessible parking spaces.
25. Add a labeled symbol to the site plan drawing that represents and delineates
the path of travel for the accessible route that is required between the
accessible units and the recreational amenities that are provided for the
project and other common area elements located at the site. The symbol shall
represent the location of the path of travel, not the location of the detectable
warning or other pavement markings required to be installed along the path.
The location of the accessible path shall not compel the user to travel in a
drive/lane area that is located behind parking vehicles. Identify on the plan
the width of the accessible route. (Note: The minimum width required by the
Code is 44 inches). Add text that would indicate that the symbol represents
the accessible route and the route is designed in compliance with regulations
specified in the Fair Housing Act. Please note that at time of permit review,
the applicant shall provide detailed documentation on the plans that will
verify that the accessible route is in compliance with the regulations specified
in the 2001 FBC. This documentation shall include, but not be limited to,
providing finish grade elevations along the path of travel.
COA.doc
07/06/05
5
DEPARTMENTS
INCLUDE REJECT
26. As required by the CBBCO, Part III titled "Land Development Regulations",
submit a site plan that clearly depicts the setback dimensions from each
property line to the leading edge of the buildings. The leading edge of the
buildings begins at the closest point of the overhang or canopy to the property
line. In addition, show the distance between all the buildings on all sides.
27. To properly determine the impact fees that will be assessed for the
clubhouse/recreation building, provide the following:
a. Will the clubhouse/recreation building be restricted to the residents of
the entire project only?
b. Will the residents have to cross any major roads or thoroughfares to get to
the clubhouse/recreation building?
c. Will there be any additional deliveries to the site?
d. Will there be any additional employees to maintain and provide service to
the site?
Please have the applicant provide the City with a copy of the letter that will be
sent to the impact fee coordinator. To allow for an efficient permit review, the
applicant should request that the County send the City a copy of their
determination of what impact fees are required for the clubhouse/recreation
building.
28. Add to the floor plan drawing of the clubhouse/recreation building a
breakdown of the floor area. The area breakdown shall specify the total area
of the building, covered area outside, covered area at the entrances, total floor
area dedicated for the clubhouse/recreation building and other uses located
within the building. Specify the total floor area that is air-conditioned. Label
the use of all rooms and floor spaces.
29. CBBCPP 3.C.3.4 requires the conservation of potable water. City water may
not, therefore, be used for landscape irrigation where other sources are readily
available.
30. A water-use permit from SFWMD is required for an irrigation system that
utilizes water from a well or body of water as its source. A copy of the permit
shall be submitted at the time of permit application, F.S. 373.216.
31. If capital facility fees (water and sewer) are paid in advance to the City of
Boynton Beach Utilities Department, the following information shall be
provided at the time of building permit application.
a. The full name of the project as it appears on the Development
Order and the
Commission-approved site plan.
a. If the project is a multi-family project, the building number/s
must be provided. The building numbers must be the same as
noted on the Commission-approved site plans.
b. The number of dwelling units in each building.
c. The number of bedrooms in each dwelling unit.
COA.doc
07/06/05
6
DEPARTMENTS INCLUDE REJECT
d. The total amount paid and itemized into how much is for water
and how much is for sewer.
(CBBCO, Chapter 26, Article II, Sections 26-34)
At time of permit review, submit separate surveys of each lot, parcel or tract. For
purposes of setting up property and ownership in the City computer, provide a
copy of the recorded deed for each lot, parcel or tract. The recorded deed shall
be submitted at time of permit review.
32. At time of building permit application, submit verification that the City of
Boynton Beach Parks and Recreation Impact Fee requirements have been
satisfied by a paid fee or conveyance of property. The following information
shall be provided:
a. A legal description of the land.
b. The full name of the project as it appears on the Development
Order and the Commission-approved site plan.
c. If the project is a multi-family project, the building number/s
must be provided. The building numbers must be the same as
noted on the Commission-approved site plans.
d. The number of dwelling units in each building.
e. The total amount being paid.
(CBBCO, Chapter 1, Article V, Section 3(f))
33. Pursuant to approval by the City Commission and all other outside agencies,
the plans for this project must be submitted to the Building Division for
review at the time of permit application submittal. The plans must incorporate
all the conditions of approval as listed in the development order and approved
by the City Commission.
34. The full address of the project shall be submitted with the construction
documents at the time of permit application submittal. If the project is multi-
family, then all addresses for the particular building type shall be submitted.
The name of the project as it appears on the Development Order must be
noted on the buildin!! permit application at the time of aoolication submittal.
35. Sheet SP-l - Indicate the number of handicapped parking spaces for the retail
area and the residences and the total number of handicapped spaces provided.
36. Submit a floor plan for the retail, amenity, office, live/work, office/retail
areas.
37. The elevator shall comolv with the 2001 FBC, Section 11-4.10.1.
38. Submit square footage of oarkin!! !!arages.
39. According to 2001 FBC, Section 11-4.1.2, "if parking spaces are provided for
self-parking by employees or visitors, or both, then accessible spaces
complying with 2001 FBC, Section 11-4.6 shall be provided in each such
COA.doc
07/06/05
7
DEPARTMENTS INCLUDE REJECT
parking area. Show accessible spaces in all areas. Comply with the 2001
FBC. (Include parallel parking.).
40. The distance of all exterior walls to adjacent buildings/property line lli an area
of concern. The allowances set forth in the 2001 FBC, Table 600 are for the
percentage of wall openings permitted. This is a life-safety issue. Submit
calculations showing the percentage of wall and wall openings for this
proiect, and clearly show the distances between the buildings.
41. All the single-story dwelling units located in the multi-family building are
"covered dwelling units" under the Florida Fair Housing Act, and thus must
comply. Indicate on the plan which design option (A or B) is being used for
this proiect and show the required clear floor space for the fixtures.
42. Sheet SP-l - Clarify the type of construction for building #1 under the
Building Tabulation Table. There is no Type I protected construction in 2001
FBC, Chapter 6.
43. Sheet SP-1 notes the parking garages occupancy as "open". This is not a
correct occupancy type. To be considered "open", the structure shall comply
with all the requirements of the 2001 FBC, Section 411.3.2, 411.3.3, and
411.3.4. As designed, the garage cannot be considered "open". Indicate the
correct occupancy per 2001 FBC, Chapter 3.
44. Clearly show all the setback dimensions from each building to each property
line. In addition, show the distance between each building on all four sides.
All setback dimensions and distances between buildings are not shown on
SP-1.
45. Clarify the number of surface parking spaces dedicated for building #1 and
building #2. A handicap accessible parking space is required in each parking
area per the 2001 FBC, Section ll-4.1.2(5)(a). Also, indicate on the plans if
the parking garages are strictly for the use of the residents or for both the
retail/restaurant/office areas and the residents.
46. Provide the occupancy classification and construction type for the clubhouse.
Comply with 200 I FBC, Chapters 3 and 6.
47. Sheet ALl - The balcony at the clubhouse shall be provided with vertical
accessibility. This is considered a "common area" and shall comply with the
2001 FBC, Section 11-4.1.3.
48. Submit a tabulation table that clearly reflects each building, number of units
in each building, the type of units (model type), number of stories in each
building, and square footage per floor.
COA.doc
07/06/05
8
DEPARTMENTS INCLUDE REJECT
49. Sheet A-25 indicates a floor plan for a "new townhouse". Submit additional
information on this unit:
A Model type or model number (identify units).
B Which buildings will contain this structure?
50. Sheet A-6 - Indicate the number of parking spaces on each level of the
garage.
51. Sheet A -12 - The square footage for units "C" and "D 1" does not correlate
with the square footage listed on Sheet SP-l. Also, identify unit "D" as "D 1 "
on SP-1.
52. On sheets A26-A32, your calculations for the percentage of openings are
incorrect. The percentage of openings is based upon Table 600 of the 2001
FBC and the distance separation of buildings from property lines or assumed
property lines (in the case of multiple buildings on the same lot). Refer to
2001 FBC, Chapter 2 for the term "Property line, assumed", and submit
correct calculations for the percentage of openings.
PARKS AND RECREATION
Comments:
53. Impact Feee:
70 single family attached units @ $771.00 each = $57,054
96 multi family units @ $656 each = $60,352
TOTAL $ 117,406
Impact fee is due prior to the issuance of the first applicable permit.
FORESTER/ENVIRONMENTALIST
Comments:
54. The Landscape Architect should tabulate the total number of existing trees on
the site. The plan should indicate where the relocated trees are to be installed
throughout the site. The total diameter inches of trees removed should be
shown as replacement trees on the site landscape plan. These replacement
trees should be shown by a separate symbol on the landscape plan sheet L-5
(Chapter 7.5, Article I Sec. 7.D.p. 2.).
PLANNING AND ZONING
Comments:
55. Approval of this site plan is contingent upon approval of the accompanying
request for land use amendment / rezoning (LUAR 05-005).
COA.doc
07/06/05
9
DEPARTMENTS
56. Approval of this site plan is subject to the approval of the proposed code
amendment (CDRV 05-011) to allow commercial uses in the PUD Planned
Unit Development zoning district but with the caveat that they front on
exterior or perimeter streets, when such locations are consistent with adopted
redevelopment policies and plans.
57. Based on the Traffic Division's review, it has been determined that the
residential portion of the proposed mixed-use redevelopment project is
located within the Coastal Residential Exception Areas of Palm Beach
County, while the retail and office components generate less daily and peak
hour trips than the existing retail space which is to be demolished. The
project meets the Traffic Performance Standards of Palm Beach County but
contingent upon the provision of a southbound exclusive right-turn lane onto
the project access driveway on North Federal Highway. No building permits
are to be issued after the build-out date of 2008.
58. Approval of this site plan is subject to the accompanying request for height
exception (HTEX 05-004).
59. Parking spaces required in this ordinance for one use or structure may be
allocated in part or in whole for the required parking spaces of another use or
structure if quantitative evidence is provided showing that parking demand
for the different uses or structures would occur on different days of the week
or at different hours. Quantitative evidence shall include estimates for peak
hour / peak season demand based on statistical data furnished by the Urban
Land Institute or an equivalent traffic engineering or land planning and design
organization (Chapter 2, Section 11.H.13.).
60. At the time of permitting, all elevation pages shall indicate the exterior
finishes, roof material, paint manufacturer's name, and color codes. Staff
recommends using a color schedule (Chapter 4, Section 7.D.). Also, provide
color swatches and awning samples.
61. Fifty percent (50%) of all site landscape materials must be native species
(Chapter 7.5, Article II, Section 5.P). Please categorize as follows: Shade
trees, Palm trees, Shrubs & Groundcover.
62. All trees, if proposed as trees, must be at least 12 feet in height and three (3)
caliper inches at the time of their installation (Chapter 7.5, Article II, Section
5.C.2.). This applies to Tree Ligustrum.
63. Staff recommends that a master sign program be provided that shows the
number, location, dimensions, exterior finish, and color(s) of all signs
(Chapter 2, Section 5.H.9.). The sign program would address all types of
signs, including commercial wall signs, identification signs, residential
subdivision signs, freestanding monument signs, canopy signs, way-finding
signs, directional signs, and all other signs as regulated by Chapter 21 of the
Land Development Regulations.
INCLUDE REJECT
COA.doc
07/06/05
10
DEPARTMENTS INCLUDE REJECT
64. At the time of permitting, the detail of the typical outdoor freestanding
lighting fixture must include the proposed color. The applicant informed staff
that the color will be black.
68. All plant material proposed outside the property line must be excluded from
the plant list m terms of meeting the minimum required landscape
requirement. Revise plant list at the time of Dermitting.
69. The common areas shall be maintained by an established association. Provide
documents to confirm same.
70. Staff recommends substituting the Pigeon Plum trees with Florida Royal palm
trees at the main entrance drive, where the angled street parking spaces. The
heights of these trees shall not conflict with the freestanding outdoor lighting
Doles.
71. Staff originally recommended that the site plan provide a full-size clubhouse /
recreation building within the townhouse portion of the development, in part,
to accommodate homeowner association meetings. However, the developer
informed staff that the meeting rooms (proposed within Building 1) could
accommodate the townhouse owner association meetings and that the
townhouse owners would be authorized to use the meeting rooms once per
month for their association meetings. This is acceptable to staff and
therefore, the condominium documents should reflect this intention.
ADDITIONAL COMMUNITY REDEVELOPMENT AGENCY
COMMENTS:
Comments:
72. To be determined.
ADDITIONAL CITY COMMISSION COMMENTS:
Comments:
73. To be determined.
MWR/elj
S:\Planning\SHARED\WP\PROJECTS\Heritage Club @ Boynton Beach\NWSP 05-014\COA.doc
Page 1 of 1
Johnson, Eric
From: Logan, Laurinda
Sent: Friday, July 08, 2005 8:44 AM
To: Byrne, Nancy; Livergood, Jeffrey
Cc: Rumpf, Michael; Breese, Ed; Johnson, Eric; Coale, Sherie
Subject: RE: Michael Weiner - Gulf Stream Mall site
Please add the following language (highlighted) to the Conditions of Approval for this project:
The applicant shall also provide design plans for reconstruction of the FECRR/Gulfstream Blvd. crossing,
including roadway re-alignment, curb & gutter, concrete median dividers, striping, and signals. The applicant shall
provide an engineer's estimate for the railroad crossing. The City will consider sharing the cost of construction of
the FECRR crossing. The extent of cost share is subject to allocation of funds in the City budget for fiscal year
2006/2007. Plans shall be submitted and approved by the City prior to issuance of any building permits.
I understand Staff reports have already gone to the CRA. This condition may be added at Tuesday's meeting.
Please let me know if you have questions or need additional information regarding this matter.
C.o
-----Original Message-----
From: Byrne, Nancy
Sent: Thursday, July 07, 2005 4:24 PM
To: Logan, Laurinda; Livergood, Jeffrey
Cc: Rumpf, Michael; Breese, Ed; Johnson, Eric; Coale, Sherie
Subject: Michael Weiner - Gulf Stream Mall site
Importance: High
Jeff & Laurinda,
I received a call from Michael Weiner today, (re-routed by Joyce as he attempted to reach Kurt), stating
that the developer for the Gulf Stream Mall site will not be able to have the drawings of the off-site
improvements in time for the upcoming CRA meeting. His specific request was to find out if this could be
included as a comment in lieu of the actual drawings.
I explained to him that this was a decision only you could make and that I would relay the request. (He kept
insisting that it was Tim Large's comment and I did attempt to correct him, but I'm not sure he got it.)
He can be reached at 265-2666 and is anxious to hear back soon so the project can stay on schedule.
Thanks,
Nancy
7/8/2005
Johnson, Eric
From:
Sent:
To:
Subject:
MazzeI/a, Pete
Friday, July01, 200510:16AM
Johnson, Eric
RE: Heritage Club / "Utilities" description of staff report
Eric
Here is the response, and a revised spreadsheet. I noticed that the numbers did not add correctly on the original. Maybe
that explains the discrepancy you saw.
Pete
~
WATER & SEWER
heritage club fk...
-----Original Message-----
From: Johnson, Eric
Sent: Friday, July 01, 2005 10:04 AM
To: Mazzella, Pete
Subject: Heritage Club / "Utilities" description of staff report
The interim purchase of up to 5 million gallons of potable water per day from Palm Beach County Utilities
would supply potable water for this project (projected to a total of 83,885 gallons per day). Local piping
and infrastructure improvements may be required for the project, dependent upon the final project
configuration and fire-flow demands. These local improvements would be the responsibility of the site
developer and would be reviewed at the time of permitting. Sufficient sanitary sewer and wastewater
treatment capacity is currently available to serve the project total of 44,225 gallons per day, subject to
the applicant making a firm reservation of capacity, following approval of the site plan (see Exhibit "C" -
Conditions of Approval).
Pete, are we okay with above paragraph? Feel free to make changes as you see fit. Thanks much,
Eric Johnson
L
JUL - '2005
,___J
""----------.,.. ._~
1
JUl - , 2005
~
III
(j)
c:
-
iil'
g-
CD
III
:3
-I ~
0
-I :::::
)> cn--f >
r .0 C') 0
:E c g ::E c: Z
~ Q) a. :J Z -I
Cil 0 ::r
_ 0 =i -
m o c (")
AJ o C/l -
RO .... (1) "'C
en ./:>. )>:E ~
w
m 0 r)>
:E G) r-l m
m )> Om C
AJ r o;:;c
- :e
c 0 ~-n
m )>
3: 0-< _r ~
)> .... 00
Z N z:E m
c CJ1 :::c
-
"tI c:Z
AJ >
0 Z~ Z
c.. (0 =iO
m ./:>..... C
(") (00) CA-n
-I ./:>.0) CJ)
""C m
--n:E0 :e
G')r)>-I m
~ ~ ""CO-l)> :::c
..... .... .... c:Emm
w :""'w - ;:;cr C
00 COco m
0 ~o m
)> s:
r >
r-nCA Z
Orm C
Oo::E
~:Em CJ)
~ - ;:;c
.... .... 0
0(0 Z
a./:>.
--nCA
Co) w G')rm
~I\) N ""C0::E
..... (0:"'" C:Em
I\) ./:>.N - ;:;c
..... (0....
--J
3rd REVIEW COMMENTS
New Site Plan
JL{ru)~
Project name: Heritage Club @ Boynton Beach
File number: NWSP 05-014
Reference: 2nd review plans identified as a New Site Plan with a Mav 17. 2005
Department date stamp marking.
Planning and Zoning
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments:
1. There are multiple dead end sections throughout the project that will not be ,/
able to be serviced by our automatic pickup Solid Waste Truck. Please
correct these conditions. Extend "bump-out" sections and the end of each
condition to allow more room for Solid Waste during pickup operations.
All dead ends have been extended to ten feet in depth to assist in the
collection of trash; see plan.
2. The applicant has indicated that compactors will be used for the mixed-use V
buildings and will be brought out to central areas adjacent to the buildings for
pickup. Please indicate the number and size of these containers so we can
evaluate the required pad sizes and our ability to perform the pickup
operation.
Containers will be depicted on the site plan on trash pick-up holding areas.
3. Staff strongly recommends removing the parallel parking spaces north of the /
north dumpster location due to concerns for safety during backing operations
by Solid Waste and to allow room for backing and turning movements for
delivery vehicles accessing the loading area.
All pal'allel spaces along the north boundary have been removed and will be
compensated for as part of the shared parking study.
PUBLIC WORKS - Traffic
Comments:
4. Reconstruct Old Dixie Hwy. and Gulfstream Blvd. to provide for curb &
gutter, storm sewer, appropriate left turn lanes, striping and landscaped ~/
parkways adjacent to the proposed development. As part of this design the
developer is asked to consider but not required to build a barrier median on
both side of the FECRRlGulfstream Blvd. crossing with the intent to qualifY
this crossing as a Quiet Zone with the Federal Railroad Administration The
applicant has shown an additional 20 feet of right-of-way along Old Dixie
Highway (providing a total 50 foot right-of-way) as agreed upon with staff.
However, the applicant was also required to provide improvements along Old
Dixie Highway and Gulfstream Boulevard, which were not shown on the
provided 2nd review plans. As such, the applicant shall show all required off-
site improvements for this project prior to proceeding to the CRA Board and
Commission.
3rd Review Responses from All Team Members
06/14/05
2
DEPARTMENTS INCLUDE REJECT
Additional right-of-way space has been allocated by the developer for off-
site improvements to Dixie Highway. All work that falls outside of the
property boundary will be depicted on another plan, submitted in the future.
5. Revise the drawings for the driveway at the northeast corner of the V
development to show one (1 )-way ingress only.
The plan has been revised to show one-wav ingress only.
6. Delineate and stripe 12-foot x 35 foot loading zones for the retail buildings; ~
include a pavement message in yellow indicating "No Parking - Loading
Zone".
See the Preliminary Engineering Plans for the loading zone stripin1!.
7. The driveway at the northeast corner of the development is less than 24 foot V'"
in width. Please correct this condition.
Drivewav along the northern propertv edge is onlv a one-way street.
ENGINEERING DIVISION
Comments:
8. All comments requiring changes and/or corrections to the plans shall be /
reflected on all appropriate sheets.
Acknowledged, all plans resubmitted.
9. Please note that changes or revisions to these plans may generate additional /
comments. Acceptance of these plans during the TRC process does not
ensure that additional comments may not be generated by the Commission
and at permit review.
Acknowledged.
10. Show sight triangles on the Landscape plans (LDR, Chapter 7.5, Article n,
Section 5.H.). Reference FDOT Standard Index 546 for the sight triangles
along Federal Highway. Use 35-foot sight triangles for Gulfstream Boulevard /
and Old Dixie Highway. Show 35 foot sight triangles for the driveway from
the development to Gulfstream Boulevard.
In accordance with FOOT Standard Index 546, 20' x 450' sight triangles are
indicated with a diagonal hatch pattern at the entrances along Federal Hwy.
on sheet L-3. On Sheets L-2 and L-4, 35' sight triangles are indicated with a
diagonal hatch pattern on Gulfstream Blvd. and Old Dixie Hwv.
11. Full drainage plans, including drainage calculations, in accordance with the /
LDR, Chapter 6, Article N, Section 5 will be required at the time of
permitting.
Acknowledged.
12. Paving, Drainage and Site details will not be reviewed for construction 7
acceptability at this time. All engineering construction details shall be in
3rd Review Responses from All Team Members
06/14/05
3
DEPARTMENTS INCLUDE REJECT
accordance with the applicable City of Boynton Beach Standard Drawings
and the "Engineering Design Handbook and Construction Standards"
and will be reviewed at the time of construction permit application.
Acknowledged.
UTILITIES
Comments:
13. Palm Beach County Health Department permits will be required for the water \./
and sewer systems serving this project (CODE, Section 26-12).
Acknowledged.
14. Fire flow calculations will be required demonstrating the City Code
requirement of 1,500 g.p.m. (500 g.p.m. some residential developments) with V
20 p.s.i. residual pressure as stated in the LDR, Chapter 6, Article IV, Section
16, or the requirement imposed by insurance underwriters, whichever is
greater (CODE, Section 26-16(b)).
Acknowledged. Fire Flow calculations will be provided at time of building
permit review.
15. The LDR, Chapter 6, Article IV, Section 16 requires that all points on each /
building will be within 200 feet of an existing or proposed fire hydrant.
Please demonstrate that the plan meets this condition, by showing all
hydrants.
Fire Hydrants are shown on the Preliminary Engineering Plans and meet
this criteria.
16. The CODE, Section 26-34(E) requires that a capacity reservation fee be paid
for this project either upon the request for the Department's signature on the ~
Health Department application forms or within seven (7) days of site plan
approval, whichever occurs first. This fee will be determined based upon
final meter size, or expected demand.
Acknowledged.
17. Comprehensive Plan Policy 3.C.3.4. requires the conservation of potable /
water. As other sources are readily available City water shall not be allowed
for irrigation.
Irrigation water is expected to be from a groundwater well.
18. A building permit for this project shall not be issued until this Department has /
approved the plans for the water and/or sewer improvements required to
service this project, in accordance with the CODE, Section 26-15.
Acknowledged.
19. Show all off-site improvements to the existing water and sewer infrastructure t/
as follows:
3rd Review Responses from All Team Members
06/14/05
4
DEPARTMENTS
a. The on-site lift station must be upgraded or replaced so as to
accommodate the added demand and the constraints imposed by site
changes. Existing gravity and pressure flows to the station must be
accommodated in the design.
There is a note on the Preliminary Engineering Plan that the lift station
shall be upgraded as necessary. The existing flow from south of
Gulfstream Boulevard is maintained by the preservation of the gravity
sewer line immediately west of US 1. This station also provides service
to development north of the Heritage Club site.
b. The water system must be connected to the existing 8-in. water main
located on the east side of Federal Highway. In addition, an 8-in. water
main connection must be established from the 12-in. water main located
on the west side of Seacrest Boulevard, to the existing 8-in. line that
terminates on SE 34th Ave. in the vicinity of SE 3rd Court; or an alternate
route may be considered to establish an 8-in. water main connection to
the 12-in. main on Seacrest Boulevard. The intent of the design is to
establish an 8-in. loop from Federal Highway to Seacrest Blvd., thereby
assuring adequate ftre protection and domestic supply.
The water main has been shown to be connected to the 8" water main
located on the east side of liS 1. The offsite water main improvements to
the west can remain as a condition of approval so time may be afforded
to determine the most appropriHte route.
20. Utility construction details will not be reviewed for construction acceptability
at this time. All utility construction details shall be in accordance with the
Utilities Department's "Utilities Engineering Design Handbook and
Construction Standards" manual (including any updates); they will be
reviewed at the time of construction permit application.
Acknowledged.
FIRE
Comments:
21. All buildings 30' in height or more than three stories will require a ftre
sprinkler system
Acknowledged; mixed use buildings are sprinkled with an NFPA 13 svstem.
22. All entrance gate shall have Fire Department access from the beginning to the
end of the project
Acknowledged.
23. Access roads shall meet DOT requirements. They shall be compacted, during
construction to 32 tons to support the weight of our emergency vehicles. The
roads shall be completed from the entry gate to furthest point of construction.
INCLUDE REJECT
c/
V'
/
3rd Review Responses from All Team Members
06/14/05
5
DEPARTMENTS INCLUDE REJECT
Roads shall be a minimum of 20' wide if two way, and 12' if one way. ~
Sufficient emergency vehicle turn around shall be maintained at all times.
Please see Fire and Life Safety Note No. 2 on Sheet 2 of the Preliminary
En2ineerin2 Plan.
24. All hydrants shall be in service before any vertical construction. Hydrant /
flow is a minimum 1500 gpm @ 20psi.
Please see Fire and Life Safety Note No. 1 on Sheet 2 of the Preliminary
En2ineerin2 Plan.
25. Final inspections shall be called only after all construction is completed in the /
building or apartment in question.
Acknowled2ed.
./
26. Site addresses and any buildings under construction shall be visible at all /'
times. Numbers shall be a minimum of six inches high with at least a 1 in
width and shall contrast with the building.
Acknowled2ed.
POLICE
Comments:
27. Show direction of traffic on plans. /
All traffic directional arrows are shown on sheet SP-l.
~ /..
28. Concern regarding number of gated entries; i.e. police/fife emergency
response.
Acknowled2ed; all 2ated entries will have "knox box" access to enter.
BUILDING DIVISION
Comments:
29. Please note that changes or revisions to these plans may generate additional
comments. Acceptance of these plans during the TRC process does not ensure
that additional comments may not be generated by the commission and at
permit review.
Acknowled2ed.
30. Indicate within the site data the type of construction of each building as /
defmed in 2001 FBC, Chapter 6.
The tabular site data on sheet SP-l calls out the type of construction for all.
31. Indicate within the site data the occupancy type of each building as defined in /
2001 FBC, Chapter 3.
The tabular site data on sheet SP-l calls out the occupancy type for all.
3rd Review Responses from All Team Members
06/14/05
6
DEPARTMENTS INCLUDE REJECT
32. The height and area for buildings or structures of the different types of
construction shall be governed by the intended use or occupancy of the
building, and shall not exceed the limits set forth in Table 500 of the 2001
FBC.
Acknowled~ed.
33. Place a note on the elevation view drawings indicating that the exterior wall \/
openings and exterior wall construction comply with 2001 FBC, Table 600.
Submit calculations that clearly reflect the percentage of protected and
unprotected wall openings permitted per 2001 FBC, Table 600.
That note is on all elevation sheets; please see set.
34. Every exterior wall within 15 feet of a property line shall be equipped with V'
approved opening protectives per 2001 FBC, Section 705.1.1.2.
Acknowled~ed.
35. Buildings, structures and parts thereof shall be designed to withstand the ~
minimum wind loads of 140 mph. Wind forces on every building or structure
shall be determined by the provisions of ASCE 7, Chapter 6, and the
provisions of 2001 FBC, Section 1606 (Wind Loads). Calculations that are
signed and sealed by a design professional registered in the state of Florida
shall be submitted for review at the time of permit application.
Acknowled~ed.
36. Every building and structure shall be of sufficient strength to support the V
loads and forces encountered per the 2001 FBC, Section 1601.2.1 and Table
1604.1. Indicate the live load (pst) on the plans for the building design.
Acknowledged, all structural loads will be calculated for building permits.
37. Buildings three-stories or higher shall be equipped with an automatic
sprinkler system per F.S. 553.895. Fire protection plans and hydraulic V
calculations shall be included with the building plans at the time of permit
application.
Acknowled~ed, both mixed-use buildin~s will include a sprinkler svstem.
38. At time of permit review, submit signed and sealed working drawings of the V
proposed construction.
Acknowledged.
39. On the site plan and floor plan, indicate the number of stories that are in each v'
building including, where applicable, mezzanines. Indicate the overall height
of each building.
Each building is labeled on the site plan with the number of stories and the
overall height. There are no mezzanines in any of the spaces.
40. Add to each building that is depicted on the site plan drawing a labeled /
symbol that identifies the location of the proposed handicap accessible units.
Add to the drawing the calculations that were used to identifY the minimum
number of required units. Also, state the code section that is applicable to the
3rd Review Responses from All Team Members
06/14/05
7
DEPARTMENTS
computations. Show and label the same units on the applicable floor plan
drawings. Compliance with regulations specified in the Fair Housing Act is
required (Federal Fair Housing Act Design and Construction Requirements,
Title 24 CFR, Part 100.205).
All units in the mixed-use buildin~s are handicap accessible on the ~round
level and all upper floors may be accessed by the elevator. A clear path to
the 2round floor units and the buildinl! elevators is depicted in the Dlan.
41. At the time of permit review, submit details of reinforcement of walls for the
future installation of grab bars as required by the Federal Fair Housing Act
Title 24 CFR, Part 100.205, Section 3, Requirement #6. All bathrooms within
the covered dwelling unit shall comply.
Acknowled2ed; will be submitted as part of the permit drawin2s.
42. Add to the drawing the calculations that were used to identify the minimum
number of required handicap accessible parking spaces.
Adaequate handicapped parkin2 is provided, see sheet SP-l for calculations.
43. Add a labeled symbol to the site plan drawing that represents and delineates
the path of travel for the accessible route that is required between the
accessible units and the recreational amenities that are provided for the
project and other common area elements located at the site. The symbol shall
represent the location of the path of travel, not the location of the detectable
warning or other pavement markings required to be installed along the path.
The location of the accessible path shall not compel the user to travel in a
drive/lane area that is located behind parking vehicles. Identify on the plan
the width of the accessible route. (Note: The minimum width required by the
Code is 44 inches). Add text that would indicate that the symbol represents
the accessible route and the route is designed in compliance with regulations
specified in the Fair Housing Act. Please note that at time of permit review,
the applicant shall provide detailed documentation on the plans that will
verify that the accessible route is in compliance with the regulations specified
in the 2001 FBC. This documentation shall include, but not be limited to,
providing finish grade elevations along the path of travel.
A dotted line is shown on SP-l to depict the path of travel for accessibilitv.
44. As required by the CBBCO, Part III titled "Land Development Regulations",
submit a site plan that clearly depicts the setback dimensions from each
property line to the leading edge of the buildings. The leading edge of the
buildings begins at the closest point of the overhang or canopy to the property
line. In addition, show the distance between all the buildings on all sides.
All setbacks are depicted and all site dimensions are shown on sheet SP-l.
45. To properly determine the impact fees that will be assessed for the
clubhouse/recreation building, provide the following:
a. Will the clubhouse/recreation building be restricted to the residents of
the entire project only? Yes
b. Will the residents have to cross any major roads or thoroughfares to get to
the clubhouse/recreation buildinl!? Nor
INCLUDE REJECT
./
/'
/'
/
3rd Review Responses from All Team Members
06/14/05
8
DEPARTMENTS
c. Will there be any additional deliveries to the site? No
d. Will there be any additional employees to maintain and provide service to
the site? No
Please have the applicant provide the City with a copy of the letter that will be
sent to the impact fee coordinator. To allow for an efficient permit review, the
applicant should request that the County send the City a copy of their
determination of what impact fees are required for the clubhouse/recreation
building.
Acknowled!!ed; the developer will provide all proper documentation.
46. Add to the floor plan drawing of the clubhouse/recreation building a
breakdown of the floor area. The area breakdown shall specifY the total area
of the building, covered area outside, covered area at the entrances, total floor
area dedicated for the clubhouse/recreation building and other uses located
within the building. SpecifY the total floor area that is air-conditioned. Label
the use of all rooms and floor spaces.
Sheet A- I.I depicts the amenity for the mixed-use pro.ject and sheet A-1.2
depicts the amenity for the town houses. All spaces are clearly labeled.
47. CBBCPP 3.C.3.4 requires the conservation of potable water. City water may
not, therefore, be used for landscape irrigation where other sources are readily
available.
Acknowledged; It is anticipated that the source of irrigation water will be a
!!roundwater well.
48. A water-use permit from SFWMD is required for an irrigation system that
utilizes water from a well or body of water as its source. A copy of the permit
shall be submitted at the time of permit application, F.S. 373.216.
Acknowledged.
49. If capital facility fees (water and sewer) are paid in advance to the City of
Boynton Beach Utilities Department, the following information shall be
provided at the time of building permit application.
a. The full name of the project as it appears on the Development
Order and the
Commission-approved site plan.
a. If the project is a multi-family project, the building number/s
must be provided. The building numbers must be the same as
noted on the Commission-approved site plans.
b. The number of dwelling units in each building.
c. The number of bedrooms in each dwelling unit.
d. The total amount paid and itemized into how much is for water
and how much is for sewer.
(CBBCO, Chapter 26, Article II, Sections 26-34)
At time of permit review, submit separate surveys of each lot, parcel or tract. For
purposes of setting up property and ownership in the City computer, provide a
copy of the recorded deed for each lot, parcel or tract. The recorded deed shall
be submitted at time of permit review.
Acknowled!!ed.
INCLUDE REJECT
~
/
/
/
/
3rd Review Responses from All Team Members
06/14/05
9
DEPARTMENTS INCLUDE REJECT
50. At time of building permit application, submit verification that the City of
Boynton Beach Parks and Recreation Impact Fee requirements have been
satisfied by a paid fee or conveyance of property. The following information
shall be provided:
a. A legal description of the land. /
b. The full name of the project as it appears on the Development
Order and the Commission-approved site plan.
c. If the project is a multi-family project, the building number/s
must be provided. The building numbers must be the same as
noted on the Commission-approved site plans.
d. The number of dwelling units in each building.
e. The total amount being paid.
(CBBCO, Chapter 1, Article V, Section 3(f))
Acknowled!!ed.
51. Pursuant to approval by the City Commission and all other outside agencies, /
the plans for this project must be submitted to the Building Division for
review at the time of permit application submittal. The plans must incorporate
all the conditions of approval as listed in the development order and approved
by the City Commission.
Acknowled!!ed.
52. The full address of the project shall be submitted with the construction /
documents at the time of permit application submittal. If the project is multi-
family, then all addresses for the particular building type shall be submitted.
The name of the project as it appears on the Development Order must be
noted on the building permit application at the time of application submittal.
Acknowledged.
53. Sheet SP-I -Indicate the number of handicapped parking spaces for the retail
area and the residences and the total number of handicapped spaces provided.
All handicapped parkin!! calculations are shown on sheet SP-l.
54. Submit a floor plan for the retail, amenity, office, live/work, office/retail /
areas.
Floor plans are included for the amenity areas and the retail/office spaces.
With no tenants at present, there is limited information on commercial area.
55. The elevator shall comply with the 2001 FBC, Section 11-4.10.1. /
Acknowledged
56. Note: If all of the living units are multistory dwelling units (if all the living /--
space is not on one floor) then these units are not covered by the Florida Fair
Housing Act, the 2001 FBC, Chapter 11 shall apply.
The only multistory dwelling nnits in the pro.ject are the townhomes. ;'
57. Sheet SP-l - Building Tabulation - clarifY the residential sub-classification ~
for buildin1:?; #3 throu1:?;h #15. "R" is unacceptable.
3rd Review Responses from All Team Members
06/14/05
10
DEPARTMENTS
Acknowled ed, the tabular data on sheet SP-l has been u dated.
58. Sheet SP-1 - Building Tabulation - There are no construction type. Is "Type
r', one-hour protected? Comply with 2001 FBC, Chapter 6.
Acknowled ed, the tabular data on sheet SP-l has been u dated.
59. ClarifY the construction type and the occupancies of the mixed-use buildings.
The building tabulation shows occupancy of Buildings # 1 and #2 as
residential, yet there are commercial uses located in these buildings. Comply
with 2001 FBC, Chapter 3 for occupancy types.
Acknowled ed, the tabular data on sheet SP-l has been u dated.
60. Submit square footage of parking garages.
Acknowled ed, the s uare foota e of each ara e is now indicated on SP-l.
61. Sheet SP-1 - Clearly indicate the number of levels for the south parking
garage and the maximum height. Also indicate the number of parking spaces
provided in each garage.
Acknowled ed, the data on sheet SP-I has been u dated.
62. According to 2001 FBC, Section 11-4.1.2, "if parking spaces are provided
for self-parking by employees or visitors, or both, then accessible spaces
complying with 2001 FBC, Section 11-4.6 shall be provided in each such
parking area. Show accessible spaces in all areas. Comply with the 2001
FBC. (Include parallel parking.)
Acknowledoed, accessible arkino is located in all arkin areas - see SP-l.
63. Clearly show the required accessible route complying with 2001 FBC,
Section 11-4.3 that shall connect accessible buildings, accessible facilities,
accessible elements, and accessible spaces that are on the same site. Passing
spaces shall be provided per 2001 FBC, Section 11-4.3.3.
A dotted line is shown on SP-I to de ict the ath of travel for accessibili '.
64. Your response to comment #65 is unacceptable. The distance of all exterior
walls to adjacent buildings/property line ~ an area of concern. The
allowances set forth in the 2001 FBC, Table 600 are for the percentage of
wall openings permitted. This is a life-safety issue. Submit calculations
showing the percentage of wall and wall openings for this project, and clearly
show the distances between the buildings.
Acknowledged, calculations, albeit preliminary, have been done to determine
ermitted ercenta es of 0 en in s and distances between buildinos.
65. Your response to comment #69 is unacceptable. A 13R automatic sprinkler
system is only applicable to residential occupancies up to four stories in
height. An automatic sprinkler system designed in accordance with NFP A 13
is required for the parking garages and other non-residential areas.
Acknowled ed, an NFPA 13 s 'stem will be em 10 ed in said areas.
66. Your response to comment #72 is non-relevant. All the single-story dwelling
units located in the multi-family building are "covered dwelling units" under
the Florida Fair Housing Act, and thus must comply. Indicate on the plan
which design option (A or B) is being used for this project and show the
required clear floor space for the fixtures.
Acknowled ed; units will com Iv with FHA; see unit ' es for desi nations.
67. Your response to comment #74 is unacceptable. Submit calculations for the
required number of handicap accessible spaces for the common areas and the
amount of s aces dedicated to the multi-famil units covered under the Fair
INCLUDE
/
I
/
REJECT
~/
./
/
/
3rd Review Responses from All Team Members
06/14/05
11
DEPARTMENTS INCLUDE REJECT
Housing Act. The common area parking spaces shall comply with the 2001
FBC, Chapter II.
Acknowledged, accessible parking calculations may be found on sheet SP-l.
NOTE: The remainder of the comments (#43,44,43,49,53,54) have not been
addressed properly. The applicant shall provide proper responses to all comments.
Acknowledged, all comments have responses.
PARKS AND RECREATION
Comments:
68. Impact Feee:
74 70 single family attached units @ $771.00 each = $57,054 $53,970 ~
92 96 multi family units @ $656 each = $60,352 $62,976
TOTAL $ 117,406 $116,946
Impact fee is due prior to the issuance of the first applicable permit.
Acknowledl!ed bv the developer.
69. Irrigation coverage needs to be 110% ~
A note has been included on Sheet L-5 under general planting requirements
stating that a fully automatic sprinkler system with 110'Yo coverage shall be
provided.
70. Indicate the site triangles at the entrances and exits and assure that /
landscaping does not block the line of site.
On sheetsL-2, L-3, and L-4, the sight triangles have been indicated with a
diagonal hatch pattern and the landscaping shown in those areas does not
exceed 24" hi2h.
71. Mark the sodded areas. /
On Sheets L-2, L-3 and L-4, the sodded areas have been indicated with the
word "SOD".
FORESTERlENVIRONMENTALIST
Comments:
Tree Removal Plan-Sheet T-1
72. The Landscape Architect should tabulate the total number of existing trees on /
the site. The plan should indicate where the relocated trees are to be installed
throughout the site. The total diameter inches of trees removed should be
shown as replacement trees on the site landscape plan. These replacement
trees should be shown by a separate symbol on the landscape plan sheet L-5.
[Environmental Regulations, Chapter 7.5, Article I Sec. 7.D.p. 2.].
On Sheet T -1, the existing trees being removed or remaining and the existing
caliper inches are indicated and the total caliper inches of proposed trees is
shown as a percental!e of the existing tree caliper. On Sheet L-5, the
3rd Review Responses from All Team Members
06/14/05
12
DEPARTMENTS INCLUDE REJECT
replacement trees are indicated on the plant list with a dark circle next to the
ta2.
Landscape Plan Sheet L-5
73. All shade and palm trees on the Plant list must be listed in the specifications
as a minimum of3" diameter at DBH (4.5' off the ground), 12'-]4' height,
and Florida # 1. The height of the trees will be larger than 12' -14' to meet the
3" diameter requirement. [Environmental Regulations, Chapter 7.5, Article n
Sec. 5.C. 2.].
On Sheet L-5, all shade and palm tree specifications have been modified to
show 12-14' heights, 3" cat. (il' 4' DBH, and Florida #1. The palms not listed
as such are not counted as trees but as shrubs.
74. The details section for the Tree Planting Detail should include a line
indicating where the height of the tree and the diameter @ DBH (4.5' off the
ground) will be measured at time of planting and inspection.
The tree planting detail on Sheet L-5 has been modified to show a dimension
line at 4.5' DBH indicatin~ a 3" caliper.
75. The details section for the Palm Planting Detail should include a line
indicating where the height of the palm, gray wood (GW) and the clear
trunk (C.T.) will be measured at time of planting and inspection.
The palm planting detail on sheet L-5 has been modified to show a
dimension line at 4.5' indicating a 3" caliper, as well as dimension lines
indicating to where the g,.ay wood and clear trunk will be measured on the
palm.
PLANNING AND ZONING
Comments:
~ The traffic impact statement must be approved by the Palm Beach County V--
Traffic Division for traffic concurrency purposes (Chapter 4, Section 8.F.).
See attached approval letter from Palm Beach County dated May 23, 2005.
I ~CCOT<j;ng to Chapter 2.5, Section 8.0., areas designated for commercial
activities shall not generally front on exterior or perimeter streets, and shall be V
preferably centrally located within the project. The proposed plan would be
in conflict with the aforementioned code. Therefore, an amendment to the CV~\J WOv\
code would be required to allow the project as it is proposed.
Acknowledl!ed; PUD text amendment went before the CRA on June 9, 2005.
l;>: P:id- ~~ ~~ lS"~T [;~4 e'~r
78. em' urn building hei t in the un zoning istrict is 45 et. Either
reduce the building height of Building I to comply with code or formally V
request a height exception pursuant to Chapter 2, Section 4.F.3 of the Land
Development Regulations.
Formal Height Exception Letter was submitted to the City on May 25, 2005
alonl! with the reQuired $250.00 processin2 fee.
3rd Review Responses from All Team Members
06/14/05
13
DEPARTMENTS
INCLUDE REJECT
. The site plan should indicate proposed fences and walls, including their
dimensions, setbacks, material, and color(s) pursuant to Chapter 4, Section
7.B.3. Provide a detail of any walls or fences, including their dimensions,
exterior finish, and color(s) (Chapter 4, Section 7.0.). Make a note on the
detail that the fences will be colored black.
On Sheet L-6, Detail 206 shows the proposed aluminum fence with
dimensions and black color indicated. Detail 201 on the same sheet shows the
townhouse entry monument sign elevation with colors and finish indicated
and detail 207 shows the retail entry monument sign elevation with colors
and finish indicated.
v
sd. e site plan tabular data (sheet SP-I) should accurately indicate the number of required parking spaces.
The required parking projects is as follows:
Proposed Use
Required Parking
Provided
Parkin
36
124
160
10
48
21
35
434
spaces (Mixed Use
140
46
21
235
442
Parking spaces required in this ordinance for one use or structure may be allocated in part or in whole for the
required parking spaces of another use or structure if quantitative evidence is provided showing that
parking demand for the different uses or structures would occur on different days of the week or at
different hours. Quantitative evidence shall include estimates for peak hour / peak season demand based
on statistical data furnished by the Urban Land Institute or an equivalent traffic engineering or land
planning and design organization (Chapter 2, Section l1.H.13.). Submit a shared parking analysis prior
to the Technical Review Committee meeting.
A shar'ed parking study will be submitted fOJ' review by the City.
. Are fee-simple townhouses proposed for this project? If so, on the site plan
(sheet SP-l), show the extent of their lot lines.
Townhomes are fee sim Ie and the ro er 'lines are delineated on SP-l.
L/""
. Provide a west elevation for Building 2 (Chapter 4, Section 7.0.).
A western view of buildin #2 has been added.
v/'
3rd Review Responses from All Team Members
06/14/05
14
DEPARTMENTS
INCLUDE REJECT
All elevation pages shall indicate the exterior fmishes, roof material, paint
manufacturer's name, and color codes. Staff recommends using a color
schedule (Chapter 4, Section 7.D.). Also, provide color swatches and awning
samples.
II elevation sheets will contain all the re uired information, as re uested.
. The removal/relocation of landscape material is subject to review and
approval of the City Forester / Environmentalist. The City Forester /
Environmentalist will determine the fate of the existing Black Olive trees
located near the Aphrodites out-parcel.
On Sheet T -1, a note has heen added at the bottom of the tree removal list
that indicates a roval of the Citv Forester.
5. On the landscape plan, ensure that the plant quantities must match between
the tabular data and the graphic illustration. The landscape plan shall provide
total plant material quantities for the following categories: Shade trees, palm
trees, Shrubs / Groundcover.
The phmt quantities in the plant list correspond with the plant symbols
shown on the planting plan. Please note that with the exception of Royal
Palms, Date Palms, and Coconut Palms, palms are counted as 3 palms = 1
tree. A column has been added to the plant list on Sheet L-5 that indicates
whether that lant is a shade tree, aim tree, shrub, or roundcover.
0ifty percent (50%) of!;;ihsite landscape materials must be native species
qChapter 7.5, Article II,\slction 5.P). Please categorize as follows: Shade
trees, Palm trees, Shrubs & Groundcover.
On Sheet L-5, under City of Boynton Beach landscape requirements, native
tree and shrub requirement, the number of natives and percentages of trees
62% of total and shrubs and roundcovers (60% of total) is shown.
cd;, ~ t7}, ~ - ct Nf Cf>VvL{l/'
. A signature \free (such as a Yellow Elder, Tibouchina Granulsola, or
Bouganvillea) is required at both sides of the project entrances (along U.S. I
and Old Dixie Highway). The signature trees must have eight (8) feet of clear
trunk if placed within the safe-sight triangle (Chapter 7.5, Article 2, Section
5.N.). Alternative plant material may be substituted if the above referenced
plant material is not available or undesired. Any substitution of plant material
(for the signature tree requirement) will be subject to the City Forester /
Environmentalist review and approval.
The signature trees p,'ovided have been indicated on Sheet L-5 under City of
Boynton Beach landscape requirements, entry landscaping. These have been
rovided at all three (3) ro'ect entrances.
~ll trees. if proposed as trees, must be at least 12 feet in beight and three (3)
caliper inches at the time of their installation (Chapter 7.5, Article II, Section
5.C.2.). f ~_ L.\f\.~~rJ\
All trees being counted as trees 8n tile plant list on Sheet L-5 are indicated at
12-14' hei hts and 3" cali ler.
v
~
v
./
~
v
3rd Review Responses from All Team Members
06/14/05
15
DEPARTMENTS
INCLUDE REJECT
f
e palm trees proposed around the townhouse buildings must be installed at
Y2 the building height ofthe building (Chapter 7.5, Article II, Section S.M.).
All Sunshine and Solitaire Palms around the townhouse buildings are
proposed at 18' or higher O.A. heights, which is Yz of the 35.75' height
b 'Idin facade. These hei hts are indicated on the lant list on Sheet L-S.
90. II proposed wall signage is subject to the Community Redevelopment
Agency Board and City Commission review and approval. Staff recommends
that you submit a master sign program that shows the number, location,
dimensions, exterior finish, and color(s) of all signs (Chapter 2, Section
S.H.9.). The sign program would address all types of signs, including
commercial wall signs, identification signs, residential subdivision signs,
freestanding monument signs, canopy signs, way-fmding signs, directional
signs, and all other signs as regulated by Chapter 21 of the Land
Development Regulations.
Acknowledged by the developer, signage calculations are included in the set.
Sign wall elevations for the townhouse and retail entry monument signs are
shown in Details 201 and 207 on sheet L-6.
~1I signage is subject to review and approval uf Ibe Commuuity
Redevelopment Agency Board and City Commission. Provide a detail of any
proposed outdoor freestanding monument signs and indicate their setback
from the property line (minimum 10 feet), and include the sign area,
dimensions, exterior finish, and letter color(s) (Chapter 4, Section 7.D.).
A monument sign on the east and south have been depicted on sheet SP-l.
Sign wall details including finish, sign panel area, setback, dimensions, and
letter colors are included on Sheet L-6.
\>ot~ w \\-\ \DL l,.fUu ~ ._ c::;.i#A ' ~
92. rovide a detail of a typical ~t<k>or:lteestanaingllighting fixture. The detail
of the typical freestanding outdoor lighting fixture should include the overall
height, exterior finish, materials used (i.e. concrete or aluminum) and
color(s). The lighting fixture height, style, design, and illumination level
shall be compatible with the building design and height and shall consider
safety, function, and aesthetic value (Chapter 9, Section 1 O.F .1.). The height
of the lighting fixtures should be the same throughout the entire commercial /
mixed-use areas. Indicate on the plans that the poles will be col lack.
. 'heet PH-I contains a detail of the intended Ii ht ole, colore black.
clude covered bike racks at intermittent locations t rou out the
commercial/public spaces. Also, more attention and detail should made for
a possible location of a bus stop since this location is off of Palm Tran Route.
Covel'ed bike racks are provided and shown on the SP-l sheet. A bus stop
as so been de icted in the southeast corner of the site.
. Rooftops will be treated as part of the building elevation. All rooftop
equipment must be completely screened from view at a minimum distance of
600 feet.
Acknowledged; all rooftop equipment will not be visible to the pedestrians.
~'
v
v
v
v
3rd Review Responses from All Team Members
06/14/05
16
INCLUDE REJECT
DEPARTMENTS
. Additional architectural detail is needed on the parking structure elevations,
in order to be compliant with the CRA design guidelines.
The exposed (north) face of the parking structure has been amended to
a e'r more like a buildin and less like a arkin structure.
. Indicate the planting of St. Augustine sod in the swale areas with appropriate
irrigation.
On Sheet L-5, under the General Planting Requirements, a paragraph has
been added indicating St. Augustine sod and irrigation shall be installed in
w' areas.
. Staff suggests that ingress, as well the egress indicated, be provided from Old
Dixie Highway.
The northern road on site is onlv rovided for e ress onto Old Dixie.
. Will the existing hedge around the southernmost wellhead be retained? If not,
it should be, at a minimum, landscaped to the extent of the one on the west
property line.
Yes, and a note stating, "All existing landscape to remain, and any damaged
landscape is to be replaced by the landscape contractor" is provided on
Sheet L-4.
1
. No landscape is depicted on the Landscape Plan around the lift station at the
north property line. It should be heavily landscaped due to its visibility from
Federal Highway.
The lift station has been heavily landscaped with a 30" high Jamaica Caper
hedge, a 30" high Cocoplum hedge, and Ligustrum trees on the west and
south sides. The east side is off the property line, and because of the existing
c n ete ad, landsca e cannot be rovided.
. A planting scheme involving taller shrub material than the proposed 24 inch
, igh hedge should be selected for the north property line. Possibly a tiered
landscape approach of different size materials may be more appropriate.
On the north property line, a 36" high Jamaica Caper hedge has been
provided, along with a 30" high Cocoplum and an 18" high Gold Mound
ana where the width allows.
lOA full-size clubhouse/recreation building should be provided at the pool for
the townhouses. ~1t\.o docs ~\N~J:'. /~. ~ ~~<;:'
The recreation build in b' the 001 has been enlar(Jed - see sheet A-1.2.
102. The recreation space is not adequate around the pool for the townhouses. A
green, outdoor, play space should be provided to give the residents a park
setting for outdoor activities, since there is not a park in the immediate
vicinity. Staff suggests the elimination of the streets surrounding the pool area
and their conversion to park/green space, since the remainder of the
circulation pattern appears adequate. 5~ L - -Z-
Additional green space has been added on adjacent blocks for outdoor
activities. A si nificant amount of as halt has been removed from the site.
/
/
v
v
/'
/
~
/
3rd Review Responses from All Team Members
06/14/05
17
DEPARTMENTS
COMMUNITY REDEVELOPMENT AGENCY COMMENTS:
Comments:
l~rovide north elevations of the parking garage. Staff recommends ironwork
/ qr other decorative elements to enhance the structure's appearance.
The exposed (north) face of the parking structure has been amended to
ear more like a build in and less like a arkin structure.
4 ow openings of Unit "C" on the north side under arcade.
nowled ed, the ent 'doors on the north elevation are now de icted.
~~
...-- L~ l~q '^
~
INCLUDE REJECT
~
3rd Review Responses from All Team Members
06/14/05
17
DEPARTMENTS INCLUDE REJECT
COMMUNITY REDEVELOPMENT AGENCY COMMENTS:
Comments:
103. Provide north elevations of the parking garage. Staff recommends ironwork
or other decorative elements to enhance the structure's appearance.
The exposed (north) face of the parking structure has been amended to
appear more like a buildinl! and less like a parkin!?; structure.
104. Show openings of Unit "C" on the north side under arcade.
Acknowled!?;ed, the entry doors on the north elevation are now depicted.
'-'
S1a(o ~~ .~T~ ~ or./M'h ~
(~#r,.lDl t\JO{~ ~
!Tp ~'i.~ ~ f~ 9fZf'
S~ p~ fr ftN~ WrfkAMf~~ ~~
~tnet> ML ~ Stpf c;~ 10<- 10~Le
See sb-t L-l/ .f.~r;~ ~ "e-ocLU I affUffwf t4-e.1
'1J f/h0ftvef 1- ~ f~~ ~ lfr- ~-(J-W,
~ ~ pl~ ~'iSl<; l2l=5<. ..f:M n s~. l'YIl4.'7t ~ "t'hcf I,
CMtfXt?,,- ~ct'~ ~ ~ fAl_gr'Jevlt ~ g)~P1 G_
CO/of!- SL-vlyfv~
5~cvU'; ~ t\"t,\tlt'1Si s.
~ ~ 11)" f~~"l--C-~*.u
Johnson, Eric
From:
Sent:
To:
Subject:
Large, Tim
Friday, June 17, 2005 10:47 AM
Johnson, Eric
heritage club
Eric, you are correct in your assumption that the other list of comments are additional comments and are to be
added to the list of comments from the 3rd review.
TIM
1
DATE: June 16, 2005
'l""-t of Acronvms/Abbreviations:
ASCE - American Society of Civil
Engineers
CBB - City of Boynton Beach
CBBA - Boynton Beach Amendments
CBBCO - City of Boynton Beach
Code of Ordinances
CBBCPP - City of Boynton Beach
Comprehensive Plan Policy
CFR - Code of Federal Regulations
EPA - Environment Protection Agency
FBC - Florida Building Code
FIRM - Flood Insurance Rate Map
F.S. - Florida Statutes
LDR - Land Development Regulations
NEC - National Electric Code
NFPA - National Fire Prevention Assn
NGVD - National Geodetic Vertical
Datum of 1929
SFWMD - South Florida Water
Management District
FFPC - Florida Fire Prevention Code
DEPARTMENT OF DEVELOPMENT
BUILDING DIVISION
MEMORANDUM NO. 05-117
TO: Ed Breese
Principal Planner
FROM: Timothy K. Lar~
TART Membe~vision
SUBJECT: Project - Heritage Club @ Boynton Beach
File No. - NWSP 04-016 - 3rd review
Buildina Division (Site Specific and Permit Comments) - Timothv K. Larae (561) 742-6352
1 Sheet SP-1 - Clarify the type of construction for building #1 under the Building Tabulation
Table. There is no Type I protected construction in 2001 FBC, Chapter 6.
2 Sheet SP-1 notes the parking garages occupancy as "open". This is not a correct
occupancy type. To be considered "open", the structure shall comply with all the
requirements of the 2001 FBC, Section 411.3.2, 411.3.3, and 411.3.4. As designed, the
garage cannot be considered "open". Indicate the correct occupancy per 2001 FBC,
Chapter 3.
3 Clearly show all the setback dimensions from each building to each property line. In
addition, show the distance between each building on all four sides. All setback dimensions
and distances between buildings are not shown on SP-1.
4 Clarify the number of surface parking spaces dedicated for building #1 and building #2. A
handicap accessible parking space is required in each parking area per the 2001 FBC,
Section 11-4.1.2(5)(a). Also, indicate on the plans if the parking garages are strictly for the
use of the residents or for both the retail/restaurant/office areas and the residents.
5 Provide the occupancy classification and construction type for the clubhouse. Comply with
2001 FBC, Chapters 3 and 6.
6 Sheet A 1.1 - The balcony at the clubhouse shall be provided with vertical accessibility.
This is considered a "common area" and shall comply with the 2001 FBC, Section 11-4.1.3.
7 Submit a tabulation table that clearly reflects each building, number of units in each
building, the type of units (model type), number of stories in each building, and square
footage per floor.
S:\Deve/opment\Building\TRC\TRC 2005\Heritage Club @ Boynton Beach Page 1 of 2
..
8 Sheet A-25 indicates a floor plan for a "new townhouse". Submit additional information on
this unit:
A Model type or model number (identify units).
B Which buildings will contain this structure?
9 Sheet A-6 - Indicate the number of parking spaces on each level of the garage.
10 Sheet A-12 - The square footage for units "C" and "01" does not correlate with the square
footage listed on Sheet SP-1. Also, identify unit "0" as "01" on SP-1.
11 On sheets A26-A32, your calculations for the percentage of openings are incorrect. The
percentage of openings is based upon Table 600 of the 2001 FBC and the distance
separation of buildings from property lines or assumed property lines (in the case of
multiple buildings on the same lot). Refer to 2001 FBC, Chapter 2 for the term "Property
line, assumed", and submit correct calculations for the percentage of openings.
bf
S:\Deve/opment\Building\ TRC\ TRC 2005\Heritage Club @ Boynton Beach
Page 20f2
DEPARTMENT OF DEVELOPMENT
BUILDING DIVISION
MEMORANDUM NO. 05-094
TO: Ed Breese
Principal Planner
FROM: Timothy K. Large
TRC Member/Building Division
DATE: May 20,2005
SUBJECT: Project - Heritage Club @ Boynton Beach
File No. - NWSP 05-014 - second review
The Building Division has the following issues:
1 Sheet SP-1 - Building Tabulation - clarify the residential sub-classification for
building #3 through #15. "R" is unacceptable.
2 Sheet SP-1 - Building Tabulation - There are no construction type. Is "Type I", one-
hour protected? Comply with 2001 FBC, Chapter 6.
3 Clarify the construction type and the occupancies of the mixed-use buildings. The
building tabulation shows occupancy of Buildings #1 and #2 as residential, yet there
are commercial uses located in these buildings. Comply with 2001 FBC, Chapter 3
for occupancy types.
4 Submit square footage of parking garages.
5 Sheet SP-1 - Clearly indicate the number of levels for the south parking garage and
the maximum height. Also indicate the number of parking spaces provided in each
garage.
6 According to 2001 FBC, Section 11-4.1.2, "if parking spaces are provided for self-
parking by employees or visitors, or both, then accessible spaces complying with
2001 FBC, Section 11-4.6 shall be provided in each such parking area. Show
accessible spaces in all areas. Comply with the 2001 FBC. (Include parallel parking.)
7 Clearly show the required accessible route complying with 2001 FBC, Section 11-4.3
that shall connect accessible buildings, accessible facilities, accessible elements,
and accessible spaces that are on the same site. Passing spaces shall be provided
per 2001 FBC, Section 11-4.3.3.
8 Your response to comment #65 is unacceptable. The distance of all exterior walls to
adjacent buildings/property line is an area of concern. The allowances set forth in
the 2001 FBC, Table 600 are for the percentage of wall openings permitted. This is a
S:\Deve/opment\Building\ TRC\ TRC 2005\Heritage Club @ Boynton Beach second review Page 1 of 2
life-safety issue. Submit calculations showing the percentage of wall and wall
openings for this project, and clearly show the distances between the buildings.
9 Your response to comment #69 is unacceptable. A 13R automatic sprinkler system
is only applicable to residential occupancies up to four stories in height. An
automatic sprinkler system designed in accordance with NFPA 13 is required for the
parking garages and other non-residential areas.
10 Your response to comment #72 is non-relevant. All the single-story dwelling units
located in the multi-family building are "covered dwelling units" under the Florida Fair
Housing Act, and thus must comply. Indicate on the plan which design option (A or
B) is being used for this project and show the required clear floor space for the
fixtures.
11 Your response to comment #74 is unacceptable. Submit calculations for the required
number of handicap accessible spaces for the common areas and the amount of
spaces dedicated to the multi-family units covered under the Fair Housing Act. The
common area parking spaces shall comply with the 2001 FBC, Chapter 11.
NOTE: The remainder of the comments (#75, 77, 79, 82, 91 & 92) have not been
addressed properly. The applicant shall provide proper responses to all comments.
tkl:bf
S:\Deve/opment\Building\TRC\TRC 2005\Heritage Club @ Boynton Beach second review Page 2 of 2
..
FROM: Timothy K. Large
TRC Member/Building Division
Li!!t~>!!l'f Acronvms/Abbreviations:
ASCE - American Society of Civil
Engineers
CBB - City of Boynton Beach
CBBA - Boynton Beach Amendments
CBBCO - City of Boynton Beach
Code of Ordinances
CBBCPP - City of Boynton Beach
Comprehensive Plan Policy
CFR - Code of Federal Regulations
EPA - Environment Protection Agency
FBC - Florida Building Code
FIRM - Flood Insurance Rate Map
F .S. - Florida Statutes
LDR - Land Development Regulations
NEC - National Electric Code
NFPA - National Fire Prevention Assn
NGVD - National Geodetic Vertical
Datum of 1929
SFWMD - South Florida Water
Management District
FFPC - Florida Fire Prevention Code
DEPARTMENT OF DEVELOPMENT
BUILDING DIVISION
MEMORANDUM NO. 05-060
TO: Ed Breese
Principal Planner
DATE: April 6, 2005
SUBJECT: Project - Heritage Lakes @ Boynton Beach
File No. - NWSP 05-014 - 1st review
We have reviewed the subject plans and recommend that the request be forwarded for Board
review with the understanding that all remaining comments will be shown in compliance on the
working drawings submitted for permits.
Buildina Division (Site Specific and Permit Comments) - Timothv K. Larae (561) 742-6352
1 Please note that changes or revisions to these plans may generate additional comments.
Acceptance of these plans during the TRC process does not ensure that additional
comments may not be generated by the commission and at permit review.
2 Indicate within the site data the type of construction of each building as defined in 2001
FBC, Chapter 6.
3 Indicate within the site data the occupancy type of each building as defined in 2001 FBC,
Chapter 3.
4 The height and area for buildings or structures of the different types of construction shall be
governed by the intended use or occupancy of the building, and shall not exceed the limits
set forth in Table 500 of the 2001 FBC.
5 Place a note on the elevation view drawings indicating that the exterior wall openings and
exterior wall construction comply with 2001 FBC, Table 600. Submit calculations that
clearly reflect the percentage of protected and unprotected wall openings permitted per
2001 FBC, Table 600.
6 Every exterior wall within 15 feet of a property line shall be equipped with approved
opening protectives per 2001 FBC, Section 705.1.1.2.
7 Buildings, structures and parts thereof shall be designed to withstand the minimum wind
loads of 140 mph. Wind forces on every building or structure shall be determined by the
provisions of ASCE 7, Chapter 6, and the provisions of 2001 FBC, Section 1606 (Wind
Loads). Calculations that are signed and sealed by a design professional registered in the
state of Florida shall be submitted for review at the time of permit application.
S:\Deve/opment\Building\TRC\TRC 2005\Heritage Club @ Boynton Beach
Page 1 of 5
8 Every building and structure shall be of sufficient strength to support the loads and forces
encountered per the 2001 FBC, Section 1601.2.1 and Table 1604.1. Indicate the live load
(pst) on the plans for the building design.
9 Buildings three-stories or higher shall be equipped with an automatic sprinkler system per
F.S. 553.895. Fire protection plans and hydraulic calculations shall be included with the
building plans at the time of permit application.
10 At time of permit review, submit signed and sealed working drawings of the proposed
construction.
11 On the site plan and floor plan, indicate the number of stories that are in each building
including, where applicable, mezzanines. Indicate the overall height of each building.
12 Add to each building that is depicted on the site plan drawing a labeled symbol that
identifies the location of the proposed handicap accessible units. Add to the drawing the
calculations that were used to identify the minimum number of required units. Also, state
the code section that is applicable to the computations. Show and label the same units on
the applicable floor plan drawings. Compliance with regulations specified in the Fair
Housing Act is required (Federal Fair Housing Act Design and Construction Requirements,
Title 24 CFR, Part 100.205).
13 At the time of permit review, submit details of reinforcement of walls for the future
installation of grab bars as required by the Federal Fair Housing Act Title 24 CFR, Part
100.205, Section 3, Requirement #6. All bathrooms within the covered dwelling unit shall
comply.
14 Add to the drawing the calculations that were used to identify the minimum number of
required handicap accessible parking spaces.
15 Add a labeled symbol to the site plan drawing that represents and delineates the path of
travel for the accessible route that is required between the accessible units and the
recreational amenities that are provided for the project and other common area elements
located at the site. The symbol shall represent the location of the path of travel, not the
location of the detectable warning or other pavement markings required to be installed
along the path. The location of the accessible path shall not compel the user to travel in a
drive/lane area that is located behind parking vehicles. Identify on the plan the width of the
accessible route. (Note: The minimum width required by the Code is 44 inches). Add text
that would indicate that the symbol represents the accessible route and the route is
designed in compliance with regulations specified in the Fair Housing Act. Please note that
at time of permit review, the applicant shall provide detailed documentation on the plans
that will verify that the accessible route is in compliance with the regulations specified in the
2001 FBC. This documentation shall include, but not be limited to, providing finish grade
elevations along the path of travel.
16 Identify within the site data the finish floor elevation (lowest floor elevation) that is proposed
for the building. Verify that the proposed elevation is in compliance with regulations of the
code by adding specifications to the site data that address the following issues:
S:\Deve/opment\Building\TRC\TRC 2005\Heritage Club @ Boynton Beach
Page 2 of 5
a. The design professional-of-record for the project shall add the following text to the site
data. "The proposed finish floor elevation _' _ NGVD is above the highest 1 DO-year
base flood elevation applicable to the building site, as determined by the SFWMD's
surface water management construction development regulations."
b. From the FIRM map, identify in the site data the title of the flood zone that the building is
located within. Where applicable, specify the base flood elevation. If there is no base
flood elevation, indicate that on the plans.
c. Identify the floor elevation that the design professional has established for the building
within the footprint of the building that is shown on the drawings titled site plan, floor
plan and paving/drainage (civil plans).
17 As required by the CBBCO, Part III titled "Land Development Regulations", submit a site
plan that clearly depicts the setback dimensions from each property line to the leading edge
of the buildings. The leading edge of the buildings begins at the closest point of the
overhang or canopy to the property line. In addition, show the distance between all the
buildings on all sides.
18 To properly determine the impact fees that will be assessed for the clubhouse/recreation
building, provide the following:
a. Will the clubhouse/recreation building be restricted to the residents of the entire project
only?
b. Will the residents have to cross any major roads or thoroughfares to get to the
clubhouse/recreation building?
c. Will there be any additional deliveries to the site?
d. Will there be any additional employees to maintain and provide service to the site?
Please have the applicant provide the City with a copy of the letter that will be sent to the
impact fee coordinator. To allow for an efficient permit review, the applicant should request
that the County send the City a copy of their determination of what impact fees are required
for the clubhouse/recreation building.
19 Add to the floor plan drawing of the clubhouse/recreation building a breakdown of the floor
area. The area breakdown shall specify the total area of the building, covered area outside,
covered area at the entrances, total floor area dedicated for the clubhouse/recreation
building and other uses located within the building. Specify the total floor area that is air-
conditioned. Label the use of all rooms and floor spaces.
20 CBBCPP 3.C.3.4 requires the conservation of potable water. City water may not, therefore,
be used for landscape irrigation where other sources are readily available.
21 A water-use permit from SFWMD is required for an irrigation system that utilizes water from
a well or body of water as its source. A copy of the permit shall be submitted at the time of
permit application, F.S. 373.216.
22 If capital facility fees (water and sewer) are paid in advance to the City of Boynton Beach
Utilities Department, the following information shall be provided at the time of building
permit application.
a. The full name of the project as it appears on the Development Order and the
Commission-approved site plan.
b. If the project is a multi-family project, the building number/s must be provided. The
building numbers must be the same as noted on the Commission-approved site plans.
S:\Deve/opment\Building\TRC\TRC 2005\Heritage Club @ Boynton Beach Page 3 of 5
c. The number of dwelling units in each building.
d. The number of bedrooms in each dwelling unit.
e. The total amount paid and itemized into how much is for water and how much is for
sewer.
(CBBCO, Chapter 26, Article II, Sections 26-34)
23 At time of permit review, submit separate surveys of each lot, parcel or tract. For purposes
of setting up property and ownership in the City computer, provide a copy of the recorded
deed for each lot, parcel or tract. The recorded deed shall be submitted at time of permit
review.
24 At time of building permit application, submit verification that the City of Boynton Beach
Parks and Recreation Impact Fee requirements have been satisfied by a paid fee or
conveyance of property. The following information shall be provided:
a. A legal description of the land.
b. The full name of the project as it appears on the Development Order and the
Commission-approved site plan.
c. If the project is a multi-family project, the building number/s must be provided. The
building numbers must be the same as noted on the Commission-approved site plans.
d. The number of dwelling units in each building.
e. The total amount being paid.
(CBBCO, Chapter 1, Article V, Section 3(t))
25 Add a general note to the site plan that all plans submitted for permitting shall meet the
City's codes and the applicable building codes in effect at the time of permit application.
26 Pursuant to approval by the City Commission and all other outside agencies, the plans for
this project must be submitted to the Building Division for review at the time of permit
application submittal. The plans must incorporate all the conditions of approval as listed in
the development order and approved by the City Commission.
27 The full address of the project shall be submitted with the construction documents at the
time of permit application submittal. If the project is multi-family, then all addresses for the
particular building type shall be submitted. The name of the project as it appears on the
Development Order must be noted on the building permit application at the time of
application submittal.
28 Show the proposed site lighting on the site and landscape plans. (LRD, Chapter 4, Section
7.B.4) If possible, provide photo metrics as part of your TRC plan submittals.
29 The area breakdowns for each unit shall specify the total area of the unit, area of the balcony,
total area that is air-conditioned and, where applicable, total area of storage and garage space.
If the garage and storage areas are not part of a specific unit, the area shall be included and
identified within the area of the building. Indicate how many of each type of unit will be on each
floor and within the building.
30 Add to the site data the total area under roof of each residential building. Provide tabular area
data for each floor of each building. The breakdown shall include the following areas and each
area shall be labeled on the applicable floor plan drawing:
a. Common area covered walkways;
S:\Deve/opment\Building\ TRC\ TRC 2005\Heritage Club @ Boynton Beach
Page 4 of 5
b. Covered stairways;
c. Common area balconies;
d. Entrance area outside of a unit;
e. Storage areas (not part of a unit);
f. Garages (not part of a unit);
g. Elevator room;
h. Electrical room;
i. Mechanical room;
j. Trash room;
k. Mailbox pickup and delivery area; and
I. Any other area under roof.
(Chapter 4 - Site Plan Review, Section 7.E.2 and 3)
31 Van accessible parking spaces are required in the parking garages per the 2001 FBC, Section
11-4.1.2(5)(b).
32 Sheet SP-1 - Indicate the number of handicapped parking spaces for the retail area and the
residences and the total number of handicapped spaces provided.
33 Submit a floor plan for the retail, amenity, office, live/work, office/retail areas.
34 The elevator shall com ply with the 2001 FBC, Section 11-4.10.1.
Note: If all of the living units are multistory dwelling units (if all the living space is not on one floor)
then these units are not covered by the Florida Fair Housing Act, the 2001 FBC, Chapter 11 shall
apply.
bf
S:\Development\Building\ TRC\ TRC 2005\Heritage Club @ Boynton Beach
Page 5 of 5
3rd REVIEW COMMENTS
New Site Plan
f} /2h~ -
h--{!M~
&1/~/tJ~
~.
17. 2005
Project name: Heritage Club @ Boynton Beach
File number: NWSP 05-014
Reference: 2nd review plans identified as a New Site Plan with a May
Department date stamp marking.
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments:
1. There are multiple dead end sections throughout the project that will not be
able to be serviced by our automatic pickup Solid Waste Truck. Please
correct these conditions. Extend "bump-out" sections and the end of each
condition to allow more room for Solid Waste during pickup operations.
All dead ends have been extended to ten feet in depth to assist in the
collection of trash; see plan.
2. The applicant has indicated that compactors will be used for the mixed-use
buildings and will be brought out to central areas adjacent to the buildings for
pickup. Please indicate the number and size of these containers so we can
evaluate the required pad sizes and our ability to perform the pickup
operation.
Containers will be depicted on the site plan on trash pick-up holding areas.
3. Staff strongly recommends removing the parallel parking spaces north of the
north dumpster location due to concerns for safety during backing operations
by Solid Waste and to allow room for backing and turning movements for
delivery vehicles accessing the loading area.
All parallel spaces along the north boundary have been removed and will be
compensated for as part of the shared parking study.
PUBLIC WORKS - Traffic
Comments:
4. Reconstruct Old Dixie Hwy. and Gulfstream Blvd. to provide for curb &
gutter, storm sewer, appropriate left turn lanes, striping and landscaped
parkways adjacent to the proposed development. As part of this design the
developer is asked to consider but not required to build a barrier median on
both side of the FECRRlGulfstream Blvd. crossing with the intent to qualify
this crossing as a Quiet Zone with the Federal Railroad Administration The
applicant has shown an additional 20 feet of right-of-way along Old Dixie
Highway (providing a total 50 foot right-of-way) as agreed upon with staff.
However, the applicant was also required to provide improvements along Old
Dixie Highway and Gulfstream Boulevard, which were not shown on the
provided 2nd review plans. As such, the applicant shall show all required off-
site improvements for this project prior to proceeding to the CRA Board and
Commission.
3rd Review Responses from All Team Members
06/14/05
5
DEPARTMENTS INCLUDE REJECT
Roads shall be a minimum of 20' wide if two way, and 12' if one way.
Sufficient emergency vehicle turn around shall be maintained at all times.
Please see Fire and Life Safety Note No. 2 on Sheet 2 of the Preliminary'
En~ineerin~ Plan.
24. All hydrants shall be in service before any vertical construction. Hydrant
flow is a minimum 1500 gpm @ 20psi.
Please see Fire and Life Safety Note No. I on Sheet 2 of the Preliminary
En~ineerin~ Plan.
25. Final inspections shall be called only after all construction is completed in the
building or apartment in question.
Acknowled~ed.
26. Site addresses and any buildings under construction shall be visible at all
times. Numbers shall be a minimum of six inches high with at least a 1 in
width and shall contrast with the building.
Acknowled~ed.
POLICE
Comments:
27. Show direction of traffic on plans.
All traffic directional arrows are shown on sheet SP-l.
28. Concern regarding number of gated entries; I.e. police/fire emergency
response.
Ackliuwled~ed; all ~ated entries will have "knox box" access to enter.
BUILDING DIVISION
\' I,
Comments: . ,A-Je r
29. Please note that changes or revisions to these Plan~~erate additional /
comments. Acceptance of these plans during the ~rocess does not ensure
that additional comments may not be generated by the commission and at
permit review.
Acknowled2ed.
30. Indicate within the site data the type of construction of each building as il
defmed in 2001 FBC, Chapter 6.
The tabular site data on sheet SP-l calls out the type of construction for all.
31. Indicate within the site data the occupancy type of each building as defmed in /
2001 FBC, Chapter 3.
The tabular site data on sheet SP-l calls out the occupancy type for all.
3rd Review Responses from All Team Members
06/14/05
6
7
DEPARTMENTS INCLUDE REJECT
32. The height and area for buildings or structures of the different types of
construction shall be governed by the intended use or occupancy of the
building, and shall not exceed the limits set forth in Table 500 of the 2001
FBC.
Acknowledged.
33. Place a note on the elevation view drawings indicating that the exterior wall
openings and exterior wall construction comply with 2001 FBC, Table 600. V
Submit calculations that clearly reflect the percentage of protected and
unprotected wall openings permitted per 2001 FBC, Table 600.
That note is on all elevation sheets; please see set.
34. Every exterior wall within 15 feet of a property line shall be equipped with i/
approved opening protectives per 2001 FBC, Section 705.1.1.2.
Acknowledged.
35. Buildings, structures and parts thereof shall be designed to withstand the
minimum wind loads of 140 mph. Wind forces on every building or structure J
shall be determined by the provisions of ASCE 7, Chapter 6, and the
provisions of 2001 FBC, Section 1606 (Wind Loads). Calculations that are
signed and sealed by a design professional registered in the state of Florida
shall be submitted for review at the time of permit application.
Acknowledgecl.
36. Every building and structure shall be of sufficient strength to support the
loads and forces encountered per the 2001 FBC, Section 1601.2.1 and Table 1/'
1604.1. Indicate the live load (pst) on the plans for the building design.
Acknowledged, all structural loads will be calculated for building permits.
37. Buildings three-stories or higher shall be equipped with an automatic
sprinkler system per F.S. 553.895. Fire protection plans and hydraulic V
calculations shall be included with the building plans at the time of permit
application.
Acknowledged, both mixed-use buildings will include a sprinkler system.
38. At time of permit review, submit signed and sealed working drawings of the /
proposed construction.
Acknowledged.
39. On the site plan and floor plan, indicate the number of stories that are in each
building including, where applicable, mezzanines. Indicate the overall height /
of each building.
Each building is labeled on the site plan with the number of stories and the
overall height. There are no mezzanines in any of the spaces.
40. Add to each building that is depicted on the site plan drawing a labeled
symbol that identifies the location of the proposed handicap accessible units.
Add to the drawing the calculations that were used to identify the minimum
number of required units. Also, state the code section that is applicable to the
'1
I
3rd Review Responses from All Team Members
06/14/05
7
DEPARTMENTS
computations. Show and label the same units on the applicable floor plan
drawings. Compliance with regulations specified in the Fair Housing Act is
required (Federal Fair Housing Act Design and Construction Requirements,
Title 24 CFR, Part 100.205).
All units in the mixed-use buildings are handicap accessible on the ground
level and all upper floors may be accessed by the elevator. A clear path to
the ground floor units and the building elevators is depicted in the plan.
41. At the time of permit review, submit details of reinforcement of walls for the
future installation of grab bars as required by the Federal Fair Housing Act
Title 24 CFR, Part 100.205, Section 3, Requirement #6. All bathrooms within
the covered dwelling unit shall comply.
Acknowledged; will be submitted as part of the permit drawings.
42. Add to the drawing the calculations that were used to identify the minimum
number of required handicap accessible parking spaces.
Adaequate handicapped parking is provided, see sheet SP-l for calculations.
43. Add a labeled symbol to the site plan drawing that represents and delineates
the path of travel for the accessible route that is required between the
accessible units and the recreational amenities that are provided for the
project and other common area elements located at the site. The symbol shall
represent the location of the path of travel, not the location of the detectable
warning or other pavement markings required to be installed along the path.
The location of the accessible path shall not compel the user to travel in a
drive/lane area that is located behind parking vehicles. Identify on the plan
the width of the accessible route. (Note: The minimum width required by the
Code is 44 inches). Add text that would indicate that the symbol represents
the accessible route and the route is designed in compliance with regulations
specified in the Fair Housing Act. Please note that at time of permit review,
the applicant shall provide detailed documentation on the plans that will
veritY that the accessible route is in compliance with the regulations specified
in the 2001 FBC. This documentation shall include, but not be limited to,
providing finish grade elevations along the path of travel.
A dotted line is shown on SP-l to depict the path of travel for accessibilitv.
44. As required by the CBBCO, Part III titled "Land Development Regulations",
submit a site plan that clearly depicts the setback dimensions from each
property line to the leading edge of the buildings. The leading edge of the
buildings begins at the closest point of the overhang or canopy to the property
line. In addition, show the distance between all the buildings on all sides.
All setbacks are depicted and all site dimensions are shown on sheet SP-l.
45. To properly determine the impact fees that will be assessed for the
clubhouse/recreation building, provide the following:
a. Will the clubhouse/recreation building be restricted to the residents of
the entire project only? Yes
b. Will the residents have to cross any major roads or thoroughfares to get to
the clubhouse/recreation building? No
INCLUDE REJECT
t/
v
v/
1/
t/
~
3rd Review Responses from All Team Members
06/14/05
8
DEPARTMENTS INCLUDE REJECT
c. Will there be any additional deliveries to the site? No
d. Will there be any additional employees to maintain and provide service to
the site? No
Please have the applicant provide the City with a copy of the letter that will be
sent to the impact fee coordinator. To allow for an efficient permit review, the ./
applicant should request that the County send the City a copy of their
determination of what impact fees are required for the clubhouse/recreation
building.
Acknowledged; the develope.' willllrovide all proper documentation.
~t-v -;;0: tt (yU,~ ~ ~-JI.
46. Add to the fl r plan drawing of the cUilihouse/recreation building a
breakdown of the floor area. The area breakdown shall specify the total area
of the building, covered area outside, covered area at the entrances, total floor V
area dedicated for the clubhouse/recreation building and other uses located
within the building. Specify the total floor area that is air-conditioned. Label
the use of all rooms and floor spaces.
Sheet A-I.I depicts the amenity for the mixed-use project and sheet A-1.2
dellicts the amenity for the town houses. All spaces are c1earlv labeled.
47. CBBCPP 3.C.3.4 requires the conservation of potable water. City water may /
not, therefore, be used for landscape irrigation where other sources are readily
available.
Acknowledged; It is anticipated that the source of irrigation water will be a
groundwater well.
48. A water-use permit from SFWMD is required for an irrigation system that j
utilizes water from a well or body of water as its source. A copy of the permit
shall be submitted at the time of permit application, F.S. 373.216.
Acknowledged.
49. If capital facility fees (water and sewer) are paid in advance to the City of
Boynton Beach Utilities Department, the following information shall be j
provided at the time of building permit application.
a. The full name of the project as it appears on the Development
Order and the
Commission-approved site plan.
a. If the project is a multi-family project, the building number/s
must be provided. The building numbers must be the same as
noted on the Commission-approved site plans.
b. The number of dwelling units in each building.
c. The number of bedrooms in each dwelling unit.
d. The total amount paid and itemized into how much is for water
and how much is for sewer.
(CBBCO, Chapter 26, Article II, Sections 26-34)
At time of permit review, submit separate surveys of each lot, parcel or tract. For
purposes of setting up property and ownership in the City computer, provide a
copy of the recorded deed for each lot, parcel or tract. The recorded deed shall
be submitted at time of permit review.
Acknowledged.
3rd Review Responses from All Team Members
06/14/05
9
DEPARTMENTS INCLUDE REJECT
50. At time of building permit application, submit verification that the City of
Boynton Beach Parks and Recreation Impact Fee requirements have been
satisfied by a paid fee or conveyance of property. The following information
shall be provided:
a. A legal description of the land.
b. The full name of the project as it appears on the Development
Order and the Commission-approved site plan. V
c. If the project is a multi-family project, the building number/s
must be provided. The building numbers must be the same as
noted on the Commission-approved site plans.
d. The number of dwelling units in each building.
e. The total amount being paid.
(CBBCO, Chapter 1, Article V, Section 3(f))
Acknowledged.
51. Pursuant to approval by the City Commission and all other outside agencies,
the plans for this project must be submitted to the Building Division for
review at the time of permit application submittal. The plans must incorporate V
all the conditions of approval as listed in the development order and approved
by the City Commission.
Acknowledged.
52. The full address of the project shall be submitted with the construction
documents at the time of permit application submittal. If the project is multi- V
family, then all addresses for the particular building type shall be submitted.
The name of the project as it appears on the Development Order must be
noted on the building permit application at the time of application submittal.
Acknowledged.
53. Sheet SP-l - Indicate the number of handicapped parking spaces for the retail V
area and the residences and the total number of handicapped spaces provided.
All handicapped parking calculations are shown on sheet SP-t.
54. Submit a floor plan for the retail, amenity, office, live/work, office/retail v!
areas.
Floor plans are included for the amenity areas and the retail/office spaces.
With no tenants at present, there is limited information on commercial area.
55. The elevator shall comply with the 2001 FBC, Section 11-4.10.1. 1/
Acknowledged
56. Note: If all of the living units are multistory dwelling units (if all the living 1/
space is not on one floor) then these units are not covered by the Florida Fair
Housing Act, the 2001 FBC, Chapter 11 shall apply.
The only multistorv dwelling units in the proiect are the townhomes.
57. Sheet SP-l - Building Tabulation - clarifY the residential sub-classification V
for building #3 through #15. "R" is unacceptable.
3rd Review Responses from All Team Members
06/14/05
10
DEPARTMENTS INCLUDE REJECT
Acknowledl!ed, the tabular data on sheet SP-l has been updated.
58. Sheet SP-l - Building Tabulation - There are no construction type. Is "Type V
I", one-hour protected? Comply with 2001 FBC, Chapter 6.
Acknowledl!ed, the tabular data on sheet SP-l has been updated.
59. Clarify the construction type and the occupancies of the mixed-use buildings.
The building tabulation shows occupancy of Buildings # 1 and #2 as
residential, yet there are commercial uses located in these buildings. Comply V
with 2001 FBC, Chapter 3 for occupancy types.
Acknowledl!ed, the tabular data on sheet SP-l has been updated.
60. Submit square footage of parking garages. v'
Acknowledged, the square footage of each garage is now indicated on SP-t.
61. Sheet SP-l - Clearly indicate the number of levels for the south parking
garage and the maximum height. Also indicate the number of parking spaces V
provided in each garage.
Acknowledl!ed, the data on sheet SP-l has been updated.
62. According to 2001 FBC, Section 11-4.1.2, "if parking spaces are provided
for self-parking by employees or visitors, or both, then accessible spaces
complying with 2001 FBC, Section 11-4.6 shall be provided in each such
parking area. Show accessible spaces in all areas. Comply with the 2001 V
FBC. (Include parallel parking.)
Acknowledged, accessible parking is located in all parking areas - see SP-t.
63. Clearly show the required accessible route complying with 2001 FBC,
Section 11-4.3 that shall connect accessible buildings, accessible facilities,
accessible elements, and accessible spaces that are on the same site. Passing V
spaces shall be provided per 2001 FBC, Section 11-4.3.3.
A dotted line is shown on SP-l to depict the path of travel for accessibilitv.
64. Your response to comment #65 is unacceptable. The distance of all exterior
walls to adjacent buildings/property line .lli an area of concern. The
allowances set forth in the 2001 FBC, Table 600 are for the percentage of
wall openings permitted. This is a life-safety issue. Submit calculations ~
showing the percentage of wall and wall openings for this project, and clearly
show the distances between the buildings. V
Acknowledged, calculations, albeit preliminal1', have been done to determine
permitted percental!es of openinl!s and distances between buildings.
65. Your response to comment #69 is unacceptable. A l3R automatic sprinkler
system is only applicable to residential occupancies up to four stories in
height. An automatic sprinkler system designed in accordance with NFP A 13 ~
is required for the parking garages and other non-residential areas.
Acknowledl!ed, an NFPA 13 system will be emploved in said areas.
66. Your response to comment #72 is non-relevant. All the single-story dwelling
units located in the multi-family building are "covered dwelling units" under V
the Florida Fair Housing Act, and thus must comply. Indicate on the plan
which design option (A or B) is being used for this project and show the
required clear floor space for the fixtures.
Acknowledged; units will comply with FHA; see unit types for designations.
67. Your response to comment #74 is unacceptable. Submit calculations for the
required number of handicap accessible spaces for the common areas and the
amount of spaces dedicated to the multi-family units covered under the Fair
3rd Review Responses from All Team Members
06/14/05
11
DEPARTMENTS INCLUDE REJECT
Housing Act. The common area parking spaces shall comply with the 2001
FBC, Chapter 11. , t,/
Acknowledged, accessible parking calculations may be found on sheet SP-l.
NOTE: The remainder of the comments (#43,44,43,49,53,54) have not been
addressed properly. The applicant shall provide proper responses to all comments.
Acknowled2ed, all comments have responses.
PARKS AND RECREATION
Comments:
68. Impact Feee:
74 70 single family attached units @ $771.00 each = $57,054 $53,970
92 96 multi family units @ $656 each = $60,352 $62,976
TOTAL $ 117,406 $116,946
Impact fee is due prior to the issuance of the ftrst applicable permit.
Acknowled2ed by the developer.
69. Irrigation coverage needs to be 110%
A note has been included on Sheet L-5 under general planting requirements
stating that a fully automatic sprinkler system with 1100/.. coverage shall be
provided.
70. Indicate the site triangles at the entrances and exits and assure that
landscaping does not block the line of site.
On sheetsL-2, L-3, and L-4, the sight triangles have been indicated with a
diagonal hatch pattern and the landscaping shown in those areas does not
exceed 24" hi2h.
71. Mark the sodded areas.
On Sheets L-2, L-3 and L-4, the sodded areas have been indicated with the
word "SOD".
FORESTERlENVIRONMENT ALIST
Comments:
Tree Removal Plan-Sheet T-1
72. The Landscape Architect should tabulate the total number of existing trees on
the site. The plan should indicate where the relocated trees are to be installed
throughout the site. The total diameter inches of trees removed should be
shown as replacement trees on the site landscape plan. These replacement
trees should be shown by a separate symbol on the landscape plan sheet L-5.
[Environmental Regulations, Chapter 7.5, Article I Sec. 7.n.p. 2.].
On Sheet T -1, the existing trees being removed or remaining and the existing
caliper inches are indicated and the total caliper inches of proposed trees is
shown as a percenta2e of the existing tree caliper. On Sheet L-5, the
. (C (; ('</:J ~
(/1 'I!;! S 3rd REVIEW COMMENT~
tV" New Site Plan
Project name: Heritage Club @ Boynton Beach
File number: NWSP 05-014
Reference: 2nd review plans identified as a New Site Plan with a May 17. 2005 Planning and Zoning
Department date stamp marking.
I
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments:
1. There are multiple dead end sections throughout the project that will not be
able to be serviced by our automatic pickup Solid Waste Truck. Please
correct these conditions. Extend "bump-out" sections and the end of each
condition to allow more room for Solid Waste during pickup operations.
All dead ends have been extended to ten feet in depth to assist in the
collection of trash; see Dlan.
2. The applicant has indicated that compactors will be used for the mixed-use
buildings and will be brought out to central areas adjacent to the buildings for
pickup. Please indicate the number and size of these containers so we can
evaluate the required pad sizes and our ability to perform the pickup
operation.
Containers will be depicted on the site plan on trash pick-up holding areas.
3. Staff strongly recommends removing the parallel parking spaces north of the
north dumpster location due to concerns for safety during backing operations
by Solid Waste and to allow room for backing and turning movements for
delivery vehicles accessing the loading area.
All parallel spaces along the north boundary have been removed and will be
comDensated for as part of the shared parking study.
PUBLIC WORKS - Traffic
Comments:
4. Reconstruct Old Dixie Hwy. and Gulfstream Blvd. to provide for curb &
gutter, storm sewer, appropriate left turn lanes, striping and landscaped
parkways adjacent to the proposed development. As part of this design the
developer is asked to consider but not required to build a barrier median on
both side of the FECRR/Gulfstream Blvd. crossing with the intent to qualify
this crossing as a Quiet Zone with the Federal Railroad Administration The
applicant has shown an additional 20 feet of right-of-way along Old Dixie
Highway (providing a total 50 foot right-of-way) as agreed upon with staff.
However, the applicant was also required to provide improvements along Old
Dixie Highway and Gulfstream Boulevard, which were not shown on the
provided 2nd review plans. As such, the applicant shall show all required off-
site improvements for this project prior to proceeding to the CRA Board and
Commission.
3rd Review Responses from All Team Members
06/14/05
4
DEPARTMENTS
a. The on-site lift station must be upgraded or replaced so as to
accommodate the added demand and the constraints imposed by site
changes. Existing gravity and pressure flows to the station must be
accommodated in the design.
There is a note on the Preliminary Engineering Plan that the lift station
shall be upgraded as necessary. The existing flow from south of
Gulfstream Boulevard is maintained by the preservation of the gravity
sewer line immediately west of US 1. This station also provides service
to development north of the Heritage Club site.
b. The water system must be connected to the existing 8-in. water main
located on the east side of Federal Highway. In addition, an 8-in. water
main connection must be established from the 12-in. water main located
on the west side of Seacrest Boulevard, to the existing 8-in. line that
terminates on SE 34th Ave. in the vicinity of SE 3rd Court; or an alternate
route may be considered to establish an 8-in. water main connection to
the 12-in. main on Seacrest Boulevard. The intent of the design is to
establish an 8-in. loop from Federal Highway to Seacrest Blvd., thereby
assuring adequate fire protection and domestic supply.
The water main has been shown to be connected to the 8" water main
located on the east side of US 1. The offsite water main improvements to
the west can remain as a condition of approval so time may be afforded
to determine the most appropriate route.
20. Utility construction details will not be reviewed for construction acceptability
at this time. All utility construction details shall be in accordance with the
Utilities Department's "Utilities Engineering Design Handbook and
Construction Standards" manual (including any updates); they will be
reviewed at the time of construction permit application.
Acknowled2:ed.
FIRE
Comments:
21. All buildings 30' in height or more than three stories will require a fire
sprinkler system
Acknowled!!ed; mixed use buildin2:s are sprinkled with an NFP A 13 system.
22. All entrance gate shall have Fire Department access from the beginning to the
end of the project
Acknowled2:ed.
23. Access roads shall meet DOT requirements. They shall be compacted, during
construction to 32 tons to support the weight of our emergency vehicles. The
roads shall be completed from the entry gate to furthest point of construction.
INCLUDE REJECT
v
v
3rd Review Responses from All Team Members
06/14/05
5
DEPARTMENTS INCLUDE REJECT
Roads shall be a minimum of 20' wide if two way, and 12' if one way. /
Sufficient emergency vehicle turn around shall be maintained at all times. L/
Please see Fire and Life Safety Note No.2 on Sheet 2 of the Preliminary
En2ineerin2 Plan.
24. All hydrants shall be in service before any vertical construction. Hydrant n
flow is a minimum 1500 gpm @ 20psi. ~: ~i ~,I ..:~-. {\.-A0 \
Please see Fire and Life Safety Note No. t on Sheet 2 of the Preliminary
En2ineerin2 Plan.
25. Final inspections shall be called only after all construction is completed in the V
building or apartment in question.
Acknowled2ed.
26. Site addresses and any buildings under construction shall be visible at all
times. Numbers shall be a minimum of six inches high with at least a 1 in l .
width and shall contrast with the building. ,/
Acknowled2ed.
POLICE
Comments:
27. Show direction of traffic on plans.
All traffic directional arrows are shown on sheet SP-l.
28. Concern regarding number of gated entries; i.e. police/fire emergency
response.
Acknowled2ed; all 2ated entries will have "knox box" access to enter.
BUILDING DIVISION
Comments:
29. Please note that changes or revisions to these plans may generate additional
comments. Acceptance of these plans during the TRC process does not ensure
that additional comments may not be generated by the commission and at
permit review.
Acknowled2ed.
,
30. IndiCate within the site data the type of construction of each building as
defined in 2001 FBC, Chapter 6.
The tabular site data on sheet SP-t calls out the type of construction for all.
31. Indicate within the site data the occupancy type of each building as defined in
2001 FBC, Chapter 3.
The tabular site data on sheet SP-t calls out the occupancy type for all.
3rd Review Responses from All Team Members
06/14/05
5
DEPARTMENTS INCLUDE REJECT
Roads shall be a minimum of 20' wide if two way, and 12' if one way.
Sufficient emergency vehicle turn around shall be maintained at all times.
Please see Fire and Life Safety Note No. 2 on Sheet 2 of the Preliminary
Enl.!ineerinl.! Plan.
24. All hydrants shall be in service before any vertical construction. Hydrant
flow is a minimum 1500 gpm @ 20psi.
Please see Fire and Life Safety Note No. 1 on Sheet 2 of the Preliminary
Engineerinl! Plan.
25. Final inspections shall be called only after all construction is completed in the
building or apartment in question.
Acknowledl.!ed.
26. Site addresses and any buildings under construction shall be visible at all
times. Numbers shall be a minimum of six inches high with at least a I in
width and shall contrast with the building.
Acknowledl!ed.
POLICE
Comments: \
27. Show direction of traffic on plans. / y
All traffic directional arrows are shown on sheet SP-l.
28. Concern regarding number of gated entries; i.e. police/fire emergency /
response.
Acknowledl.!ed; alll!ated entries will have "knox box" access to enter.
BUILDING DIVISION
Comments:
29. Please note that changes or revisions to these plans may generate additional
comments. Acceptance of these plans during the TRC process does not ensure
that additional comments may not be generated by the commission and at
permit review.
Acknowledl!ed.
30. Indicate within the site data the type of construction of each building as
defined in 2001 FBC, Chapter 6.
The tabular site data on sheet SP-I calls out the type of construction for all.
31. Indicate within the site data the occupancy type of each building as defmed in
2001 FBC, Chapter 3.
The tabular site data on sheet SP-l calls out the occupancy type for all.
3rd Review Responses from All Team Members
06/14/05
11
J60,,", (.<~~
'fR
DEPARTMENTS INCLUDE REJECT
Housing Act. The common area parking spaces shall comply with the 2001
FBC, Chapter 11.
Acknowledged, accessible parking calculations may be found on sheet SP-l.
NOTE: The remainder of the comments (#43,44,43,49,53,54) have not been
addressed properly. The applicant shall provide proper responses to all comments.
Acknowledl!ed, all comments have responses.
PARKS AND RECREATION
Comments:
68. Impact Feee:
74 70 single family attached units @ $771.00 each = $57,054 $53,970 ~
92 96 multi family units @ $656 each = $60,352 $62,976
TOTAL $ 117,406 $116,946
Impact fee is due prior to the issuance of the first applicable permit.
Acknowledl!ed by the developer.
69. Irrigation coverage needs to be 110% /
A note has been included on Sheet L-5 under general planting requirements
stating that a fully automatic sprinkler system with 110% coverage shall be
provided.
70. Indicate the site triangles at the entrances and exits and assure that
landscaping does not block the line of site. v/
On sheetsL-2, L-3, and L-4, the sight triangles have been indicated with a
diagonal hatch pattern and the landscaping shown in those areas does not
exceed 24" hil!h.
71. Mark the sodded areas. \/'
On Sheets L-2, L-3 and L-4, the sodded areas have been indicated with the
word "SOD".
FORESTER/ENVIRONMENT ALIST
Comments:
Tree Removal Plan-Sheet T-l
72. The Landscape Architect should tabulate the total number of existing trees on
the site. The plan should indicate where the relocated trees are to be installed
throughout the site. The total diameter inches of trees removed should be
shown as replacement trees on the site landscape plan. These replacement
trees should be shown by a separate symbol on the landscape plan sheet L-5.
[Environmental Regulations, Chapter 7.5, Article I Sec. 7.D.p. 2.].
On Sheet T-l, the existing trees being removed or remaining and the existing
caliper inches are indicated and the total caliper inches of proposed trees is
shown as a percental!e of the existing tree caliper. On Sheet L-5, the
3rd Review Responses from All Team Members
06/14/05
11
~*ft\D~
DEPARTMENTS INCLUDE REJECT
Housing Act. The common area parking spaces shall comply with the 2001
FBC, Chapter 11.
Acknowledged, accessible parking calculations may be found on sheet SP-l.
NOTE: The remainder of the comments (#43,44,43,49,53,54) have not been
addressed properly. The applicant shall provide proper responses to all comments.
Acknowled2ed, all comments have responses.
PARKS AND RECREATION
Comments:
68. Impact Feee:
74 70 single family attached units @ $771.00 each = $57,054 $53,970
92 96 multi family units @ $656 each = $60,352 $62,976
TOTAL $ 117,406 $116,946
Impact fee is due prior to the issuance of the first applicable permit.
Acknowledged by the developer.
69. Irrigation coverage needs to be 110%
A note has been included on Sheet L-5 under general planting requirements
stating that a fully automatic sprinkler system with 110% coverage shall be
provided.
70. Indicate the site triangles at the entrances and exits and assure that
landscaping does not block the line of site.
On sheetsL-2, L-3, and L-4, the sight triangles have been indicated with a
diagonal hatch pattern and the landscaping shown in those areas does not
exceed 24" high.
71. Mark the sodded areas.
On Sheets L-2, L-3 and L-4, the sodded areas have been indicated with the
word "SOD".
FORESTER/ENVIRONMENTALIST
Comments:
Tree Removal Plan-Sheet T-l
72. The Landscape Architect should tabulate the total number of existing trees on ~
the site. The plan should indicate where the relocated trees are to be installed /
throughout the site. The total diameter inches of trees removed should be
shown as replacement trees on the site landscape plan. These replacement
trees should be shown by a separate symbol on the landscape plan sheet L-5.
[Environmental Regulations, Chapter 7.5, Article I Sec. 7.D.p. 2.].
On Sheet T -1, the existing trees being removed or remaining and the existing
caliper inches are indicated and the total caliper inches of proposed trees is
shown as a percentage of the existing tree caliper. On Sheet L-5, the
::lid Re-view Responses from All Team Members
06/14/05
12
DEPARTMENTS
replacement trees are indicated on the plant list with a dark circle next to the
ta!!.
Landscaoe Plan Sheet L-S
73. All shade and palm trees on the Plant list must be listed in the specifications
as a minimum of3" diameter at DBH (4.5' off the ground), 12'-14' height,
and Florida # 1. The height of the trees will be larger than 12' -14' to meet the
3" diameter requirement. [Environmental Regulations, Chapter 7.5, Article II
Sec. 5.C. 2.].
On Sheet L-S, all shade and palm tree specifications have been modified to
show 12-14' heights, 3" cal. (ti' 4' DBH, and Florida #1. The palms not listed
as such are not counted as trees but as shrubs.
74. The details section for the Tree Planting Detail should include a line
indicating where the height of the tree and the diameter @ DBH (4.5' off the
ground) will be measured at time of planting and inspection.
The tree planting detail on Sheet L-5 has been modified to show a dimension
line at 4.5' DBH indicatine; a 3" caliper.
75. The details section for the Palm Planting Detail should include a line
indicating where the height of the palm, gray wood (GW) and the clear
trunk (C.T.) will be measured at time of planting and inspection.
The palm planting detail on sheet L-5 has been modified to show a
dimension line at 4.5' indicating a 3" caliper, as well as dimension lines
indicating to where the gray wood and clear trunk will be measured on the
palm.
PLANNING AND ZONING
Comments:
76. The traffic impact statement must be approved by the Palm Beach County
Traffic Division for traffic concurrency purposes (Chapter 4, Section 8.F.).
See attached approval letter from Palm Beach County dated May 23, 2005.
77. According to Chapter 2.5, Section 8.D., areas designated for commercial
activities shall not generally front on exterior or perimeter streets, and shall be
preferably centrally located within the project. The proposed plan would be
in conflict with the aforementioned code. Therefore, an amendment to the
code would be required to allow the project as it is proposed.
Acknowlede;ed; PUD text amendment went before the CRA on June 9, 2005.
78. The maximum building height in the PUD zoning district is 45 feet. Either
reduce the building height of Building 1 to comply with code or formally
request a height exception pursuant to Chapter 2, Section 4.F.3 of the Land
Development Regulations.
Formal Height Exception Letter was submitted to the City on May 25, 2005
alone; with the required $250.00 processine; fee.
INCLUDE REJECT
VV
~
-----
~l---
Page 1 of2
Johnson, Eric
From: Logan, Laurinda
Sent: Wednesday, June 29, 2005 3:53 PM
To: Johnson, Eric
Cc: Breese, Ed
Subject: RE: Heritage Club at Boynton Beach
Yes, my review is complete, they complied, and I provided you a copy of the typical section for the files. They
may proceed. No more memos!
LC1l/.VL
-----Original Message-----
From: Johnson, Eric
Sent: Wednesday, June 29, 2005 3:44 PM
To: Logan, Laurinda
Cc: Breese, Ed
Subject: RE: Heritage Club at Boynton Beach
Laurinda,
The last Engineering memorandum regarding the above referenced site plan (dated June 14,2005) did
NOT recommend the project go forward to the July 12, 2005 CRA meeting until key items were addressed
by the applicant.
Friday, June 24, 2005 was a deadline date that we set for Jeff Schnars to provide you with cross-sections.
The applicant met our deadline. (see below). Yesterday (Tuesday), you left a set of Preliminary
Engineering Plans on my desk. Is your review complete? Will there be another memorandum
forthcoming? Thank you for your assistance in this matter. Eric
-----Original Message-----
From: Logan, Laurinda
Sent: Monday, June 27,20059:48 AM
To: Johnson, Eric
Subject: RE: Heritage Club at Boynton Beach
Yes
-----Original Message-----
From: Johnson, Eric
Sent: Monday, June 27,20058:59 AM
To: Logan, Laurinda
Cc: Breese, Ed
Subject: FW: Heritage Club at Boynton Beach
Laurinda,
Did anyone from Schnar's give you cross-section for the Heritage Club project? From what I
know, they didn't give anything to Sherie (for us to give to you). I just wanted to make sure
that the developer is doing what they're supposed to be doing in order keep their project
scheduled for the July CRA meeting. Thanks, Eric
6/29/2005
6/29/2005
Page 2 0[2
-----Orig i na I Message-----
From: Ashlee Vargo [mailto:avargo@zonelaw.com]
Sent: Friday, June 24, 2005 10:08 AM
To: 'Johnson, Eric'
Subject: FW: Heritage Club at Boynton Beach
Eric,
Can you please give me an update on the status of the cross-sections for the Heritage Club
at Boynton Beach?
Thanks
Ashlee L. Vargo
Weiner & Aronson, P.A
102 North Swinton Avenue
Delray Beach, Florida 33444
561.265.2666 ext.305
561.272.6831 (fax)
avargo@zonelaw.com
From: Jeffrey Schnars [mailto:jeff@schnars.com]
Sent: Wednesday, June 22, 20053:14 PM
To: avargo@zonelaw.com; RMathias@NewCenturyCompanies.com; Stuart Debowsky;
Francisco Perez [Perez Arch]
Cc: Jason Mankoff; Michael
Subject: RE: Heritage Club at Boynton Beach
I already send Laurinda Logan the revised engineering plans with the cross-sections of Old
Dixie and Gulfstream.
Jeff
[{:.\\~_O/'
I .\
",( . m . }
(1,,1(1
C> /~
1/.. ~~
! () ;'-.J \:.;
DEPARTMENT OF PUBLIC WORKS
ENGINEERING DIVISION
MEMORANDUM NO. 05-077
TO:
Ed Breese, Principal Planner, Planning and Zoning
FROM:
Laurinda Logan, P.E., Senior Engineer
DATE:
June 14, 2005
RE:
Review Comments
New Site Plan - 3rd Review
Heritage Club at Boynton Beach
File No. NWSP 05-014
Please revise the following comments as noted below based on the 3rd Review of this project performed
June 14, 2005. Following are comments that were either not addressed, or are intended to follow the
Site Plan as Conditions of Approval. New comments are shown in bold type. Given the number and
significance of these comments we do not recommend moving forward to the CRA until these items have
been addressed.
PUBLIC WORKS - GENERAL
1. There are multiple dead end sections throughout the project that will not be able to be serviced by
our automatic pickup Solid Waste Truck. Please correct these conditions. Extend "bump-out"
sections and the end of each dead-end condition to allow more room for Solid Waste during pickup
operations. DELETE
2. The applicant has indicated that compactors will be used for the mixed-use buildings and will be
brought out to central areas adjacent to the buildings for pickup. Please indicate the number and
size of these containers so we can evaluate the required pad sizes and our ability to perform the
pickup operation. INCLUDE
3. Staff strongly recommends removing the parallel parking spaces north of the north dumpster location
due to concerns for safety during backing operations by Solid Waste and to allow room for backing a
turning movements for delivery vehicles accessing the loading area. DELETE
PUBLIC WORKS - TRAFFIC
4. Reconstruct Old Dixie Hwy. and Gulfstream Blvd. to provide for curb & gutter, storm sewer,
appropriate left turn lanes, striping and landscaped parkways adjacent to the proposed development.
As part of this design the developer is asked to consider but not required to build a barrier median on
both sides of the FECRR/Gulfstream Blvd. crossing with the intent to qualify this crossing as a Quiet
Zone with the Federal Railroad Administration. The applicant has shown an additional 20-ft. of right-
of-way along Old Dixie Hwy. (providing a total 50-ft. right-of-way) as agreed upon with Staff.
However, the applicant was also required to provide improvements along both Old Dixie Hwy. and
Gulfstream Blvd. which were not shown on the provided Second Review plans. The applicant shall
show all required off-site improvements for this project prior to proceeding to the CRA Board and
Commission. REVISE AS FOLLOWS: Reconstruct Old Dixie Hwy. and Gulfstream Blvd. to
provide two 11-ft. lanes, curb & gutter, sidewalk, appropriate green space with landscaping,
and necessary signing and striping. A typical section depicting the work to be completed
Department of Public Works/Engineering Division Memo No. 05-077
Re: Heritage Club at Boynton Beach New Site Plan - 3rd Review
June 14,2005
Page 2
shall be provided prior to the scheduled CRA Board meeting. Complete construction plans
will be required in conjunction with the plat and will be reviewed and approved prior to
issuance of the Land Development Permit (LDP.) Construction of the required improvements
shall be completed prior to issuance of the final CO's for the project as required by the
Amendments to the Building Code. A surety shall be provided for the required off-site
improvements in the amount of 110% of the engineer's estimate for the off-site work prior to
issuance of the LDP.
The applicant shall also provide design plans for reconstruction of the FECRRlGulfstream
Blvd. crossing, including roadway re-alignment, curb & gutter, concrete median dividers,
striping, and signals. The applicant shall provide an engineer's estimate for the railroad
crossing. The City will consider sharing the cost of construction of the FECRR crossing. The
extent of cost share is subject to allocation of funds in the City budget for fiscal year
2006/2007.
5. Delineate and stripe 12-ft.x35-ft. loading zones for the retail buildings; include a pavement message
in yellow indicating "No Parking - Loading Zone". INCLUDE
6. Revise the drawings for the driveway at the northeast corner of the development to show one-way
ingress only. DELETE
ENGINEERING
7. All comments requiring changes and/or corrections to the plans shall be reflected on all appropriate
sheets. DELETE
8. Please note that changes or revIsions to these plans may generate additional comments.
Acceptance of these plans during the TRC process does not ensure that additional comments may
not be generated by the Commission and at permit review. INCLUDE
9. It may be necessary to replace or relocate large canopy trees adjacent to light fixtures to eliminate
future shadowing on the parking surface (LDR, Chapter 23, Article II, Section A.1.b.) INCLUDE
10. Show sight triangles on the Landscape plans (LDR, Chapter 7.5, Article II, Section 5.H.). Reference
FDOT Standard Index 546 for the sight triangles along Federal Highway. Use 35-ft. sight triangles
for Gulfstream Boulevard and Old Dixie Highway. DELETE
11. Full drainage plans, including drainage calculations, in accordance with the LDR, Chapter 6, Article
IV, Section 5 will be required at the time of permitting. INCLUDE
12. Paving, Drainage and Site details will not be reviewed for construction acceptability at this time. All
engineering construction details shall be in accordance with the applicable City of Boynton Beach
Standard Drawings and the "Engineering Design Handbook and Construction Standards" and
will be reviewed at the time of construction permit application. INCLUDE
UTILITIES
13. Palm Beach County Health Department permits will be required for the water and sewer systems
serving this project (CODE, Section 26-12). INCLUDE
Department of Public Works/E?'n'gineering Division Memo No. 05-077
Re: Heritage Club at Boynton Beach New Site Plan - 3rd Review
June 14,2005
Page 3
14. Fire flow calculations will be required demonstrating the City Code requirement of 1,500 g.p.m. (500
g.p.m. some residential developments) with 20 p.s.i. residual pressure as stated in the LDR, Chapter
6, Article IV, Section 16, or the requirement imposed by insurance underwriters, whichever is greater
(CODE, Section 26-16(b)). INCLUDE
15. The LDR, Chapter 6, Article IV, Section 16 requires that all points on each building will be within 200
feet of an existing or proposed fire hydrant. Please demonstrate that the plan meets this condition,
by showing all hydrants. DELETE
16. The CODE, Section 26-34(E) requires that a capacity reservation fee be paid for this project either
upon the request for the Department's signature on the Health Department application forms or within
seven (7) days of Site Plan approval, whichever occurs first. This fee will be determined based upon
final meter size, or expected demand. INCLUDE
17. Comprehensive Plan Policy 3.C.3.4. requires the conservation of potable water. As other sources
are readily available City water shall not be allowed for irrigation. INCLUDE
18. A building permit for this project shall not be issued until this Department has approved the plans for
the water and/or sewer improvements required to service this project, in accordance with the CODE,
Section 26-15. INCLUDE
19. Show all off-site Improvements to the existing water and sewer infrastructure will be required as
follows:
a. The on-site lift station must be upgraded or replaced so as to accommodate the added demand
and the constraints imposed by site changes. Existing gravity and pressure flows to the station
must be accommodated in the design. INCLUDE
b. The water system must be connected to the existing 8-in. water main located on the east side of
Federal Highway. In addition, an 8-in. water main connection must be established from the 12-in.
water main located on the west side of Seacrest Boulevard, to the existing 8-in. line that
terminates on SE 34th Ave. in the vicinity of SE 3rd Court; or an alternate route may be considered
to establish an 8-in. water main connection to the 12-in. main on Sea crest Boulevard. The intent
of the design is to establish an 8-in. loop from Federal Highway to Seacrest Blvd., thereby
assuring adequate fire protection and domestic supply. INCLUDE
20. Utility construction details will not be reviewed for construction acceptability at this time. All utility
construction details shall be in accordance with the Utilities Department's "Utilities Engineering
Design Handbook and Construction Standards" manual (including any updates); they will be
reviewed at the time of construction permit application. INCLUDE
lL/ck
Cc: Jeffrey R. Livergood, P.E., Director, Public Works (via e-mail)
Peter V. Mazzella, Deputy Utility Director, Utilities
H. David Kelley, Jr., P.E./ P.S.M., City Engineer, Public Works/Engineering (via e-mail)
Glenda Hall, Maintenance Supervisor, Public Works/Forestry & Grounds Division
Larry Quinn, Solid Waste Manager, Public Works/Solid Waste
Kenneth Hall, Engineering Plans Analyst, Public Works/Engineering (via e-mail)
File
S:\Engineering\Kribs\Heritage Club @ B.B. New Site Plan 3rd Review.doc
,;!I'~
""
W COMMENT~
IV Site Plan
Pr
Fi
Rl
D
~w Site Plan with a May 17. 2005 Planning and Zoning
=
s
=
ieneral
\....,.Ulllllltw-Hl..J.
1. There are multiple dead end sections throughout the project that will not be
able to be serviced by our automatic pickup Solid Waste Truck. Please
correct these conditions. Extend "bump-out" sections and the end of each
condition to allow more room for Solid Waste during pickup operations.
All dead ends have been extended to ten feet in depth to assist in the
collection of trash; see plan.
2. The applicant has indicated that compactors will be used for the mixed-use
buildings and will be brought out to central areas adjacent to the buildings for
pickup. Please indicate the number and size of these containers so we can
evaluate the required pad sizes and our ability to perform the pickup
operation.
Containers will be depicted on the site plan on trash pick-up holding areas.
3. Staff strongly recommends removing the parallel parking spaces north of the
north dumpster location due to concerns for safety during backing operations
by Solid Waste and to allow room for backing and turning movements for
delivery vehicles accessing the loading area.
All parallel spaces along the north boundary have been removed and will be
compensated for as part of the shared parking study.
PUBLIC WORKS - Traffic
Comments:
4. Reconstruct Old Dixie Hwy. and Gulfstream Blvd. to provide for curb &
gutter, storm sewer, appropriate left turn lanes, striping and landscaped
parkways adjacent to the proposed development. As part of this design the
developer is asked to consider but not required to build a barrier median on
both side of the FECRR/Gulfstream Blvd. crossing with the intent to qualify
this crossing as a Quiet Zone with the Federal Railroad Administration The
applicant has shown an additional 20 feet of right-of-way along Old Dixie
Highway (providing a total 50 foot right-of-way) as agreed upon with staff.
However, the applicant was also required to provide improvements along Old
Dixie Highway and Gulfstream Boulevard, which were not shown on the
provided 2nd review plans. As such, the applicant shall show all required off-
site improvements for this project prior to proceeding to the CRA Board and
Commission.
INCLUDE
"
,.. ,. ~
REJECT
\..
'.
'"
3rd Review Responses from All Team Members
06/14/05
2
DEPARTMENTS
Additional right-of-way space has been allocated by the developer for off-
site improvements to Dixie Highway. All work that falls outside of the
property boundary will be depicted on another plan, submitted in the future.
5. Revise the drawings for the driveway at the northeast comer of the
development to show one (I)-way ingress only.
The plan has been revised to show one-way in2ress only.
6. Delineate and stripe 12-foot x 35 foot loading zones for the retail buildings;
include a pavement message in yellow indicating "No Parking - Loading
Zone".
See the Preliminary En2ineerin2 Plans for the loadin2 zone stripin2.
7. The driveway at the northeast comer of the development is less than 24 foot
in width. Please correct this condition.
Driveway alon2 the northern property ed2e is only a one-way street.
ENGINEERING DIVISION
Comments:
8. All comments requiring changes and/or corrections to the plans shall be
reflected on all appropriate sheets.
Acknowled2ed, all plans resubmitted.
INCLUDE REJECT
9. Please note that changes or revisions to these plans may generate additional
comments. Acceptance of these plans during the TRC process does not '
ensure that additional comments may not be generated by the Commission
and at permit review.
Acknowled2ed.
10. Show sight triangles on the Landscape plans (LOR, Chapter 7.5, Article II,
Section 5.H.). Reference FOOT Standard Index 546 for the sight triangles
along Federal Highway. Use 35-foot sight triangles for Gulfstream Boulevard
and Old Dixie Highway. Show 35 foot sight triangles for the driveway from
the development to Gulfstream Boulevard.
In accordance with FDOT Standard Index 546, 20' x 450' sight triangles are
indicated with a diagonal hatch pattern at the entrances along Federal Hwy.
on sheet L-3. On Sheets L-2 and L-4, 35' sight triangles are indicated with a
dia20nal hatch pattern on Gulfstream Blvd. and Old Dixie Hwv.
11. Full drainage plans, including drainage calculations, in accordance with the
LOR, Chapter 6, Article IV, Section 5 will be required at the time of
permitting.
Acknowledged.
12. Paving, Drainage and Site details will not be reviewed for construction
acceptability at this time. All engineering construction details shall be in
,
3rd Review Responses from All Team Members
06/14/05
3
DEPARTMENTS INCLUDE REJECT
accordance with the applicable City of Boynton Beach Standard Drawings
and the "Engineering Design Handbook and Construction Standards"
and will be reviewed at the time of construction permit application.
Acknowled!!ed.
UTILITIES
Comments:
13. Palm Beach County Health Department permits will be required for the water
and sewer systems serving this project (CODE, Section 26-12).
Acknowled!!ed.
I
14. Fire flow calculations will be required demonstrating the City Code
requirement of 1,500 g.p.m. (500 g.p.m. some residential developments) with
20 p.s.i. residual pressure as stated in the LDR, Chapter 6, Article IV, Section ,
16, or the requirement imposed by insurance underwriters, whichever is
greater (CODE, Section 26-16(b)).
Acknowledged. Fire Flow calculations will be provided at time of building
oermit review.
15. The LDR, Chapter 6, Article IV, Section 16 requires that all points on each
building will be within 200 feet of an existing or proposed fire hydrant.
Please demonstrate that the plan meets this condition, by showing all
hydrants.
Fire Hydrants are shown on the Preliminary Engineering Plans and meet
this criteria.
16. The CODE, Section 26-34(E) requires that a capacity reservation fee be paid
for this project either upon the request for the Department's signature on the
Health Department application forms or within seven (7) days of site plan
approval, whichever occurs first. This fee will be determined based upon
final meter size, or expected demand.
Acknowled!!ed.
17. Comprehensive Plan Policy 3.C.3.4. requires the conservation of potable
water. As other sources are readily available City water shall not be allowed
for irrigation.
Irrigation water is expected to be from a !!roundwater well.
18. A building permit for this project shall not be issued until this Department has
approved the plans for the water and/or sewer improvements required to
service this project, in accordance with the CODE, Section 26-15.
Acknowledged.
19. Show all off-site improvements to the existing water and sewer infrastructure
as follows:
,
3rd Review Responses from All Team Members
06/14/05
4
DEPARTMENTS
a. The on-site lift station must be upgraded or replaced so as to
accommodate the added demand and the constraints imposed by site
changes. Existing gravity and pressure flows to the station must be
accommodated in the design.
There is a note on the Preliminary Engineering Plan that the lift station
shall be upgraded as necessary. The existing flow from south of
Gulfstream Boulevard is maintained by the preservation of the gravity
sewer line immediately west of US 1. This station also provides service
to development north of the Heritage Club site.
b. The water system must be connected to the existing 8-in. water main
located on the east side of Federal Highway. In addition, an 8-in. water
main connection must be established from the 12-in. water main located
on the west side of Seacrest Boulevard, to the existing 8-in. line that
terminates on SE 34th Ave. in the vicinity of SE 3rd Court; or an alternate
route may be considered to establish an 8-in. water main connection to
the 12-in. main on Seacrest Boulevard. The intent of the design is to
establish an 8-in. loop from Federal Highway to Seacrest Blvd., thereby
assuring adequate fire protection and domestic supply.
The water main has been shown to be connected to the 8" water main
located on the east side of US 1. The offsite water main improvements to
the west can remain as a condition of approval so time may be afforded
to determine the most appropriate route.
20. Utility construction details will not be reviewed for construction acceptability
at this time. All utility construction details shall be in accordance with the
Utilities Department's "Utilities Engineering Design Handbook and
Construction Standards" manual (including any updates); they will be
reviewed at the time of construction permit application.
Acknowled2ed.
FIRE
Comments:
21. All buildings 30' in height or more than three stories will require a fire
sprinkler system
Acknowledged; mixed use buildings are sprinkled with an NFPA 13 system.
22. All entrance gate shall have Fire Department access from the beginning to the
end of the project
Acknowledged.
23. Access roads shall meet DOT requirements. They shall be compacted, during
construction to 32 tons to support the weight of our emergency vehicles. The
roads shall be completed from the entry gate to furthest point of construction.
INCLUDE
REJECT
Facsimile
TRANSMITTAL
CITY OF BOYNTON BEACH
100 E. BOYNTON BEACH BOULEVARD
P.O. BOX 310
BOYNTON BEACH, FLORIDA 33425-0310
FAX: (561) 742-6259
PlANNING AND ZONING DIVISION
to: Michael Weiner, Esquire
fax #: 272-6831
date: May 24, 2005
from: Sherie Coale
re: 3rd REVIEW COMMENTS FOR Herita2e Club
Please find attached the first review comments for your project. To stay on the
current review schedule, please do the following steps listed below, and bring all
documents to the Technical Application Review Team who will meet on Tuesday,
June 14, 2005.
1. Revise your plans incorporating all comments listed herein, including the addition of
notes on plans to confirm response to general statements/ comments, and bring 12 copies
to the TART meeting (full sets including all pages originally submitted);
2. Submit the additional information as requested within the attached comments; ( i.e. traffic
analysis, engineering certification, etc.)
3. Prepare a written response (7 copies) consisting of a list briefly summarizing how each
comment has been addressed on the revised plans or with the supplemental information
including location on the plans (this promotes an expeditious 3rd review by staff and your
project representatives during the TART meeting );and
4.
Submit reductions (8 ~ X 11) and in digital
format (JPEG) for the proposed site plans,
elevations and landscaping plan (this is required
for the final report and public presentation).
Planning and Zoning Division
City of Boynton Beach
Boynton Beach, Florida 33425
742-6260
Fax: 742-6259
The applicant should not attend a third review meeting until all documents have been revised and
copied for staff review. Ifplans will not be fully revised and brought to the scheduled meeting,
contact Ed Breese in this office by the Thursday prior to the scheduled meeting date. Projects
deviating from the original schedule are eligible for review at subsequent meetings, which are
held every Tuesday. To reschedule, contact Sherie Coale, by the Thursday prior to the Tuesday
meeting that you desire to attend. The remainder of the review schedule will be adjusted
accordingly. If you have questions on the attached comments, please contact the respective
reviewer using the attached list of review representatives.
If the plans are reasonably complete and all significant comments are addressed following 3rd
review, the project is forwarded to the Community Redevelopment Agency Board meeting that
falls approximately 2 to 3 weeks following the TART meeting. An "*,, by any comment
identifies a comment that must be addressed prior to moving forward to the Planning and
Development board.
Note: Items recognized by staff as typically outstanding at this point include a traffic report
and/or confirmation ofthe traffic concurrency approval from the Palm Beach County
drainage certification by a licensed engineer, signed "Rider to Site Plan Application"
form and colored elevations ofthe proposed project. This information is necessary for
the project to proceed. If you have submitted this information, please disregard this note.
DEPARTMENT REPRESENT A TIVE REPRESENT A TIVES' PHONE FAX
DESIGNEE
Engineering Dave Kelley Laurinda Logan 742-6482 742-6485
Building Don Johnson Timothy Large 742-6352 742-6352
Fire Department Rodger Kemmer Rick Lee 742-6753 742-6357
Police Department Marshall Gage John Huntington 737-6167 737-3136
Utilities Pete Mazzella H. David Kelley Jr. 742-6401 742-6485
Public Works-General Larry Quinn Laurinda Logan 742-6482 742-6485
Public W orks- Traffic Jeffrey Livergood Laurinda Logan 742-6482 742-6485
Parks & Recreation Jody Rivers 742-6227 742-6233
Forester/Environmentalist Kevin Hallahan Kevin Hallahan 742-6267 742-6259
Planning & Zoning Michael Rumpf, Ed Breese 742-6262 742-6259
CHAIRMAN
REVISED 4/12/05
S:IPlanninglSHAREDlWPIPROJECTSlHeritage Club@ Boynton BeachINWSP 05-014\I't Review comment, FAX COVER2.doc
3rd REVIEW COMMENTS
New Site Plan
Project name: Heritage Club @ Boynton Beach
File number: NWSP 05-014
Reference: 2nd review plans identified as a New Site Plan with a May 17. 2005 Planning and Zoning
Department date stamp marking.
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments:
1. There are multiple dead end sections throughout the project that will not be
able to be serviced by our automatic pickup Solid Waste Truck. Please
correct these conditions. Extend "bump-out" sections and the end of each
condition to allow more room for Solid Waste during pickup operations.
2. The applicant has indicated that compactors will be used for the mixed-use
buildings and will be brought out to central areas adjacent to the buildings for
pickup. Please indicate the number and size of these containers so we can
evaluate the required pad sizes and our ability to perform the pickup
operation.
3. Staff strongly recommends removing the parallel parking spaces north of the
north dumpster location due to concerns for safety during backing operations
by Solid Waste and to allow room for backing and turning movements for
delivery vehicles accessing the loading area.
PUBLIC WORKS - Traffic
Comments:
4. Reconstruct Old Dixie Hwy. and Gulfstream Blvd. to provide for curb &
gutter, storm sewer, appropriate left turn lanes, striping and landscaped
parkways adjacent to the proposed development. As part of this design the
developer is asked to consider but not required to build a barrier median on
both side of the FECRR/Gulfstream Blvd. crossing with the intent to qualify
this crossing as a Quiet Zone with the Federal Railroad Administration The
applicant has shown an additional 20 feet of right-of-way along Old Dixie
Highway (providing a total 50 foot right-of-way) as agreed upon with staff.
However, the applicant was also required to provide improvements along Old
Dixie Highway and Gulfstream Boulevard, which were not shown on the
provided 2nd review plans. As such, the applicant shall show all required off-
site improvements for this project prior to proceeding to the CRA Board and
Commission.
5. Revise the drawings for the driveway at the northeast comer of the
development to show one (1 )-way ingress only.
6. Delineate and stripe 12-foot x 35 foot loading zones for the retail buildings;
include a pavement message in yellow indicating "No Parking - Loading
3rd REVIEW COMMENTS
OS/24/05
2
DEPARTMENTS INCLUDE REJECT
Zone".
7. The driveway at the northeast comer of the development is less than 24 foot
in width. Please correct this condition.
ENGINEERING DIVISION
Comments:
8. All comments requiring changes and/or corrections to the plans shall be
reflected on all appropriate sheets.
9. Please note that changes or revisions to these plans may generate additional
comments. Acceptance of these plans during the TRC process does not
ensure that additional comments may not be generated by the Commission
and at permit review.
10. Show sight triangles on the Landscape plans (LDR, Chapter 7.5, Article II,
Section 5.H.). Reference FDOT Standard Index 546 for the sight triangles
along Federal Highway. Use 35-foot sight triangles for Gulfstream Boulevard
and Old Dixie Highway. Show 35 foot sight triangles for the driveway from
the development to Gulfstream Boulevard.
11. Full drainage plans, including drainage calculations, in accordance with the
LDR, Chapter 6, Article IV, Section 5 will be required at the time of
permitting.
12. Paving, Drainage and Site details will not be reviewed for construction
acceptability at this time. All engineering construction details shall be in
accordance with the applicable City of Boynton Beach Standard Drawings
and the "Engineering Design Handbook and Construction Standards"
and will be reviewed at the time of construction permit application.
UTILITIES
Comments:
13. Palm Beach County Health Department permits will be required for the water
and sewer systems serving this project (CODE, Section 26-12).
14. Fire flow calculations will be required demonstrating the City Code
requirement of 1,500 g.p.m. (500 g.p.m. some residential developments) with
20 p.s.i. residual pressure as stated in the LDR, Chapter 6, Article IV, Section
16, or the requirement imposed by insurance underwriters, whichever is
greater (CODE, Section 26-16(b)).
15. The LDR, Chapter 6, Article IV, Section 16 requires that all points on each
building will be within 200 feet of an existing or proposed fire hydrant.
3rd REVIEW COMMENTS
OS/24/05
3
DEPARTMENTS
Please demonstrate that the plan meets this condition, by showing all
hydrants.
16. The CODE, Section 26-34(E) requires that a capacity reservation fee be paid
for this project either upon the request for the Department's signature on the
Health Department application forms or within seven (7) days of site plan
approval, whichever occurs first. This fee will be determined based upon
final meter size, or expected demand.
17. Comprehensive Plan Policy 3.C.3.4. requires the conservation of potable
water. As other sources are readily available City water shall not be allowed
for irrigation.
18. A building permit for this project shall not be issued until this Department has
approved the plans for the water and/or sewer improvements required to
service this project, in accordance with the CODE, Section 26-15.
19. Show all off-site improvements to the existing water and sewer infrastructure
as follows:
a. The on-site lift station must be upgraded or replaced so as to
accommodate the added demand and the constraints imposed by site
changes. Existing gravity and pressure flows to the station must be
accommodated in the design.
b. The water system must be connected to the existing 8-in. water main
located on the east side of Federal Highway. In addition, an 8-in. water
main connection must be established from the 12-in. water main located
on the west side of Seacrest Boulevard, to the existing 8-in. line that
terminates on SE 34th Ave. in the vicinity of SE 3rd Court; or an alternate
route may be considered to establish an 8-in. water main connection to
the 12-in. main on Seacrest Boulevard. The intent of the design is to
establish an 8-in. loop from Federal Highway to Seacrest Blvd., thereby
assuring adequate fire protection and domestic supply.
20. Utility construction details will not be reviewed for construction acceptability
at this time. All utility construction details shall be in accordance with the
Utilities Department's "Utilities Engineering Design Handbook and
Construction Standards" manual (including any updates); they will be
reviewed at the time of construction permit application.
FIRE
Comments:
21. All buildings 30' in height or more than three stories will require a fire
sprinkler system
INCLUDE REJECT
3rd REVIEW COMMENTS
OS/24/05
4
DEPARTMENTS INCLUDE REJECT
22. All entrance gate shall have Fire Department access from the beginning to the
end of the project
23. Access roads shall meet DOT requirements. They shall be compacted, during
construction to 32 tons to support the weight of our emergency vehicles. The
roads shall be completed from the entry gate to furthest point of construction.
Roads shall be a minimum of 20' wide if two way, and 12' if one way.
Sufficient emergency vehicle turn around shall be maintained at all times.
24. All hydrants shall be in service before any vertical construction. Hydrant
flow is a minimum 1500 gpm @ 20psi.
25. Final inspections shall be called only after all construction is completed in the
building or apartment in question.
26. Site addresses and any buildings under construction shall be visible at all
times. Numbers shall be a minimum of six inches high with at least a 1 in
width and shall contrast with the building.
POLICE
Comments:
27. Show direction of traffic on plans.
28. Concern regarding number of gated entries; I.e. police/fire emergency
response.
BUILDING DIVISION
Comments:
29. Please note that changes or revisions to these plans may generate additional
comments. Acceptance of these plans during the TRC process does not ensure
that additional comments may not be generated by the commission and at
permit review.
30. Indicate within the site data the type of construction of each building as
defined in 2001 FBC, Chapter 6.
31. Indicate within the site data the occupancy type of each building as defined in
2001 FBC, Chapter 3.
32. The height and area for buildings or structures of the different types of
construction shall be governed by the intended use or occupancy of the
building, and shall not exceed the limits set forth in Table 500 of the 2001
FBC.
3rd REVIEW COMMENTS
OS/24/05
5
DEPARTMENTS INCLUDE REJECT
33. Place a note on the elevation view drawings indicating that the exterior wall
openings and exterior wall construction comply with 2001 FBC, Table 600.
Submit calculations that clearly reflect the percentage of protected and
unprotected wall openings permitted per 2001 FBC, Table 600.
34. Every exterior wall within 15 feet of a property line shall be equipped with
approved opening protectives per 2001 FBC, Section 705.1.1.2.
35. Buildings, structures and parts thereof shall be designed to withstand the
minimum wind loads of 140 mph. Wind forces on every building or structure
shall be determined by the provisions of ASCE 7, Chapter 6, and the
provisions of 2001 FBC, Section 1606 (Wind Loads). Calculations that are
signed and sealed by a design professional registered in the state of Florida
shall be submitted for review at the time of permit application.
36. Every building and structure shall be of sufficient strength to support the
loads and forces encountered per the 2001 FBC, Section 1601.2.1 and Table
1604.1. Indicate the live load (pst) on the plans for the building design.
37. Buildings three-stories or higher shall be equipped with an automatic
sprinkler system per F.S. 553.895. Fire protection plans and hydraulic
calculations shall be included with the building plans at the time of permit
application.
38. At time of permit review, submit signed and sealed working drawings of the
proposed construction.
39. On the site plan and floor plan, indicate the number of stories that are in each
building including, where applicable, mezzanines. Indicate the overall height
of each building.
40. Add to each building that is depicted on the site plan drawing a labeled
symbol that identifies the location of the proposed handicap accessible units.
Add to the drawing the calculations that were used to identify the minimum
number of required units. Also, state the code section that is applicable to the
computations. Show and label the same units on the applicable floor plan
drawings. Compliance with regulations specified in the Fair Housing Act is
required (Federal Fair Housing Act Design and Construction Requirements,
Title 24 CFR, Part 100.205).
41. At the time of permit review, submit details of reinforcement of walls for the
future installation of grab bars as required by the Federal Fair Housing Act
Title 24 CFR, Part 100.205, Section 3, Requirement #6. All bathrooms within
the covered dwelling unit shall comply.
42. Add to the drawing the calculations that were used to identify the minimum
number of required handicap accessible parking spaces.
3rd REVIEW COMMENTS
OS/24/05
6
DEPARTMENTS
43. Add a labeled symbol to the site plan drawing that represents and delineates
the path of travel for the accessible route that is required between the
accessible units and the recreational amenities that are provided for the
project and other common area elements located at the site. The symbol shall
represent the location of the path of travel, not the location of the detectable
warning or other pavement markings required to be installed along the path.
The location of the accessible path shall not compel the user to travel in a
drive/lane area that is located behind parking vehicles. Identify on the plan
the width of the accessible route. (Note: The minimum width required by the
Code is 44 inches). Add text that would indicate that the symbol represents
the accessible route and the route is designed in compliance with regulations
specified in the Fair Housing Act. Please note that at time of permit review,
the applicant shall provide detailed documentation on the plans that will
verify that the accessible route is in compliance with the regulations specified
in the 2001 FBC. This documentation shall include, but not be limited to,
providing finish grade elevations along the path of travel.
44. As required by the CBBCO, Part III titled "Land Development Regulations",
submit a site plan that clearly depicts the setback dimensions from each
property line to the leading edge of the buildings. The leading edge of the
buildings begins at the closest point of the overhang or canopy to the property
line. In addition, show the distance between all the buildings on all sides.
45. To properly determine the impact fees that will be assessed for the
clubhouse/recreation building, provide the following:
a. Will the clubhouse/recreation building be restricted to the residents of
the entire project only?
b. Will the residents have to cross any major roads or thoroughfares to get to
the clubhouse/recreation building?
c. Will there be any additional deliveries to the site?
d. Will there be any additional employees to maintain and provide service to
the site?
Please have the applicant provide the City with a copy of the letter that will be
sent to the impact fee coordinator. To allow for an efficient permit review, the
applicant should request that the County send the City a copy of their
determination of what impact fees are required for the clubhouse/recreation
building.
46. Add to the floor plan drawing of the clubhouse/recreation building a
breakdown of the floor area. The area breakdown shall specify the total area
of the building, covered area outside, covered area at the entrances, total floor
area dedicated for the clubhouse/recreation building and other uses located
within the building. Specify the total floor area that is air-conditioned. Label
the use of all rooms and floor spaces.
47. CBBCPP 3.C.3.4 requires the conservation of potable water. City water may
not, therefore, be used for landscape irrigation where other sources are readily
available.
INCLUDE REJECT
3rd REVIEW COMMENTS
OS/24/05
7
DEPARTMENTS INCLUDE REJE~
48. A water-use permit from SFWMD is required for an irrigation system that
utilizes water from a well or body of water as its source. A copy of the permit
shall be submitted at the time of permit application, F.S. 373.216.
49. If capital facility fees (water and sewer) are paid in advance to the City of
Boynton Beach Utilities Department, the following information shall be
provided at the time of building permit application.
a. The full name of the project as it appears on the Development
Order and the
Commission-approved site plan.
a. If the project is a multi-family project, the building number/s
must be provided. The building numbers must be the same as
noted on the Commission-approved site plans.
b. The number of dwelling units in each building.
c. The number of bedrooms in each dwelling unit.
d. The total amount paid and itemized into how much is for water
and how much is for sewer.
(CBBCO, Chapter 26, Article II, Sections 26-34)
At time of permit review, submit separate surveys of each lot, parcel or tract. For
purposes of setting up property and ownership in the City computer, provide a
copy of the recorded deed for each lot, parcel or tract. The recorded deed shall
be submitted at time of permit review.
50. At time of building permit application, submit verification that the City of
Boynton Beach Parks and Recreation Impact Fee requirements have been
satisfied by a paid fee or conveyance of property. The following information
shall be provided:
a. A legal description of the land.
b. The full name of the project as it appears on the Development
Order and the Commission-approved site plan.
c. If the project is a multi-family project, the building number/s
must be provided. The building numbers must be the same as
noted on the Commission-approved site plans.
d. The number of dwelling units in each building.
e. The total amount being paid.
(CBBCO, Chapter 1, Article V, Section 3(f))
51. Pursuant to approval by the City Commission and all other outside agencies,
the plans for this project must be submitted to the Building Division for
review at the time of permit application submittal. The plans must incorporate
all the conditions of approval as listed in the development order and approved
by the City Commission.
52. The full address of the project shall be submitted with the construction
documents at the time of permit application submittal. If the project is multi-
family, then all addresses for the particular building type shall be submitted.
3rd REVIEW COMMENTS
OS/24/05
8
DEPARTMENTS INCLUDE REJECT
The name of the project as it appears on the Development Order must be
noted on the building permit application at the time of application submittal.
53. Sheet SP-l - Indicate the number of handicapped parking spaces for the retail
area and the residences and the total number of handicapped spaces provided.
54. Submit a floor plan for the retail, amenity, office, live/work, office/retail
areas.
55. The elevator shall comply with the 2001 FBC, Section 11-4.10.1.
56. Note: If all of the living units are multistory dwelling units (if all the living
space is not on one floor) then these units are not covered by the Florida Fair
Housing Act, the 2001 FBC, Chapter 11 shall apply.
57. Sheet SP-l - Building Tabulation - clarify the residential sub-classification
for building #3 through #15. "R" is unacceptable.
58. Sheet SP-l - Building Tabulation - There are no construction type. Is "Type
I", one-hour protected? Comply with 2001 FBC, Chapter 6.
59. Clarify the construction type and the occupancies of the mixed-use buildings.
The building tabulation shows occupancy of Buildings #1 and #2 as
residential, yet there are commercial uses located in these buildings. Comply
with 2001 FBC, Chapter 3 for occupancy types.
60. Submit square footage of parking garages.
61. Sheet SP-l - Clearly indicate the number of levels for the south parking
garage and the maximum height. Also indicate the number of parking spaces
provided in each garage.
62. According to 2001 FBC, Section 11-4.1.2, "if parking spaces are provided
for self-parking by employees or visitors, or both, then accessible spaces
complying with 2001 FBC, Section 11-4.6 shall be provided in each such
parking area. Show accessible spaces in all areas. Comply with the 2001
FBC. (Include parallel parking.)
63. Clearly show the required accessible route complying with 2001 FBC,
Section 11-4.3 that shall connect accessible buildings, accessible facilities,
accessible elements, and accessible spaces that are on the same site. Passing
spaces shall be provided per 2001 FBC, Section 11-4.3.3.
64. Your response to comment #65 is unacceptable. The distance of all exterior
walls to adjacent buildings/property line ~ an area of concern. The
allowances set forth in the 2001 FBC, Table 600 are for the percentage of
wall openings permitted. This is a life-safety issue. Submit calculations
showing the percentage of wall and wall openings for this project, and clearly
show the distances between the buildings.
3rd REVIEW COMMENTS
OS/24/05
9
DEPARTMENTS INCLUDE REJECT
65. Your response to comment #69 is unacceptable. A 13R automatic sprinkler
system is only applicable to residential occupancies up to four stories in
height. An automatic sprinkler system designed in accordance with NFP A 13
is required for the parking garages and other non-residential areas.
66. Your response to comment #72 is non-relevant. All the single-story dwelling
units located in the multi-family building are "covered dwelling units" under
the Florida Fair Housing Act, and thus must comply. Indicate on the plan
which design option (A or B) is being used for this project and show the
required clear floor space for the fixtures.
67. Your response to comment #74 is unacceptable. Submit calculations for the
required number of handicap accessible spaces for the common areas and the
amount of spaces dedicated to the multi-family units covered under the Fair
Housing Act. The common area parking spaces shall comply with the 2001
FBC, Chapter 11.
NOTE: The remainder of the comments (#43,44,43,49,53,54) have not been
addressed properly. The applicant shall provide proper responses to all comments.
PARKS AND RECREATION
Comments:
68. Impact Feee:
74 single family attached units @ $771.00 each = $57,054
92 multi family units @ $656 each = $60,352
TOTAL $ 117.406
Impact fee is due prior to the issuance of the first applicable permit.
69. Irrigation coverage needs to be 110%
70. Indicate the site triangles at the entrances and exits and assure that
landscaping does not block the line of site.
71. Mark the sodded areas.
FORESTER/ENVIRONMENTALIST
Comments:
Tree Removal Plan-Sheet T-l
72. The Landscape Architect should tabulate the total number of existing trees on
3rd REVIEW COMMENTS
OS/24/05
10
DEPARTMENTS INCLUDE REJECT
the site. The plan should indicate where the relocated trees are to be installed
throughout the site. The total diameter inches of trees removed should be
shown as replacement trees on the site landscape plan. These replacement
trees should be shown by a separate symbol on the landscape plan sheet L-5.
rEnvironmental Regulations, Chapter 7.5, Article I Sec. 7.D.p. 2.].
Landscape Plan Sheet L-5
73. All shade and palm trees on the Plant list must be listed in the specifications
as a minimum of 3" diameter at DBH (4.5' off the ground), 12'-14' height,
and Florida #1. The height of the trees will be larger than 12'-14' to meet the
3" diameter requirement. [Environmental Regulations, Chapter 7.5, Article II
Sec. 5.C. 2.].
74. The details section for the Tree Planting Detail should include a line
indicating where the height of the tree and the diameter @ DBH (4.5' off the
ground) will be measured at time of planting and inspection.
75. The details section for the Palm Planting Detail should include a line
indicating where the height of the palm, gray wood (GW) and the clear
trunk (C.T.) will be measured at time of planting and inspection.
PLANNING AND ZONING
Comments:
76. The traffic impact statement must be approved by the Palm Beach County
Traffic Division for traffic concurrency purposes (Chapter 4, Section 8.F.).
77. According to Chapter 2.5, Section 8.D., areas designated for commercial
activities shall not generally front on exterior or perimeter streets, and shall be
preferably centrally located within the project. The proposed plan would be
in conflict with the aforementioned code. Therefore, an amendment to the
code would be required to allow the project as it is proposed.
78. The maximum building height in the PUD zoning district is 45 feet. Either
reduce the building height of Building 1 to comply with code or formally
request a height exception pursuant to Chapter 2, Section 4.F.3 of the Land
Development Regulations.
79. The site plan should indicate proposed fences and walls, including their
dimensions, setbacks, material, and color(s) pursuant to Chapter 4, Section
7.B.3. Provide a detail of any walls or fences, including their dimensions,
exterior finish, and color(s) (Chapter 4, Section 7.D.). Make a note on the
detail that the fences will be colored black.
3rd REVIEW COMMENTS
OS/24/05
11
DEPARTMENTS
INCLUDE REJECT
80. The site plan tabular data (sheet SP-l) should accurately indicate the number of required parking spaces.
The required parking projects is as follows:
Proposed Use
Required Parking
Provided
Parkin
24 One-bedroom units
36
116
168
10
48
33
35
446
Please com lete
Use
Please com lete
Parking spaces required in this ordinance for one use or structure may be allocated in part or in whole for the
required parking spaces of another use or structure if quantitative evidence is provided showing that
parking demand for the different uses or structures would occur on different days of the week or at
different hours. Quantitative evidence shall include estimates for peak hour / peak season demand based
on statistical data furnished by the Urban Land Institute or an equivalent traffic engineering or land
planning and design organization (Chapter 2, Section I1.H.13.). Submit a shared parking analysis prior
to the Technical Review Committee meeting.
81. Are fee-simple townhouses proposed for this project? If so, on the site plan
sheet SP-l), show the extent of their lot lines.
82. Provide a west elevation for Buildin 2 Cha ter 4, Section 7.D. .
83. All elevation pages shall indicate the exterior finishes, roof material, paint
manufacturer's name, and color codes. Staff recommends using a color
schedule (Chapter 4, Section 7.D.). Also, provide color swatches and awning
sam les.
84. The removal/relocation of landscape material is subject to review and
approval of the City Forester / Environmentalist. The City Forester /
Environmentalist will determine the fate of the existing Black Olive trees
located near the A hrodites out- arcel.
85. On the landscape plan, ensure that the plant quantities must match between
the tabular data and the gra hic illustration. The landscape Ian shall rovide
3rd REVIEW COMMENTS
OS/24/05
12
DEPARTMENTS INCLUDE REJECT
total plant material quantities for the following categories: Shade trees, palm
trees, Shrubs / Groundcover.
86. Fifty percent (50%) of all site landscape materials must be native species
(Chapter 7.5, Article II, Section 5.P). Please categorize as follows: Shade
trees, Palm trees, Shrubs & Groundcover.
87. A signature tree (such as a Yellow Elder, Tibouchina Granulsola, or
Bouganvillea) is required at both sides of the project entrances (along U.S. 1
and Old Dixie Highway). The signature trees must have eight (8) feet of clear
trunk if placed within the safe-sight triangle (Chapter 7.5, Article 2, Section
5.N.). Alternative plant material may be substituted if the above referenced
plant material is not available or undesired. Any substitution of plant material
(for the signature tree requirement) will be subject to the City Forester /
Environmentalist review and approval.
88. All trees, if proposed as trees, must be at least 12 feet in height and three (3)
caliper inches at the time of their installation (Chapter 7.5, Article II, Section
5.C.2.).
89. The palm trees proposed around the townhouse buildings must be installed at
Yz the building height of the building (Chapter 7.5, Article II, Section 5.M.).
90. All proposed wall signage is subject to the Community Redevelopment
Agency Board and City Commission review and approval. Staff recommends
that you submit a master sign program that shows the number, location,
dimensions, exterior finish, and color(s) of all signs (Chapter 2, Section
5.H.9.). The sign program would address all types of signs, including
commercial wall signs, identification signs, residential subdivision signs,
freestanding monument signs, canopy signs, way-finding signs, directional
SIgnS, and all other SIgnS as regulated by Chapter 21 of the Land
Development Regulations.
91. All sIgnage IS subject to reVIew and approval of the Community
Redevelopment Agency Board and City Commission. Provide a detail of any
proposed outdoor freestanding monument signs and indicate their setback
from the property line (minimum 10 feet), and include the sign area,
dimensions, exterior finish, and letter color(s) (Chapter 4, Section 7.D.).
92. Provide a detail of a typical outdoor freestanding lighting fixture. The detail
of the typical freestanding outdoor lighting fixture should include the overall
height, exterior finish, materials used (i.e. concrete or aluminum) and
color(s). The lighting fixture height, style, design, and illumination level
shall be compatible with the building design and height and shall consider
safety, function, and aesthetic value (Chapter 9, Section 10.F.1.). The height
of the lighting fixtures should be the same throughout the entire commercial /
mixed-use areas. Indicate on the plans that the poles will be colored black.
93. Include covered bike racks at intermittent locations throughout the
3rd REVIEW COMMENTS
OS/24/05
13
DEPARTMENTS INCLUDE REJECT
commercial/public spaces. Also, more attention and detail should made for
a possible location of a bus stop since this location is off of Palm Tran Route
1.
94. Rooftops will be treated as part of the building elevation. All rooftop
equipment must be completely screened from view at a minimum distance of
600 feet.
95. Additional architectural detail is needed on the parking structure elevations,
in order to be compliant with the CRA design guidelines.
96. Indicate the planting of St. Augustine sod in the swale areas with appropriate
irrigation.
97. Staff suggests that ingress, as well the egress indicated, be provided from Old
Dixie Highway.
98. Will the existing hedge around the southernmost wellhead be retained? Ifnot,
it should be, at a minimum, landscaped to the extent of the one on the west
property line.
99. No landscape is depicted on the Landscape Plan around the lift station at the
north property line. It should be heavily landscaped due to its visibility from
Federal Highway.
100. A planting scheme involving taller shrub material than the proposed 24 inch
high hedge should be selected for the north property line. Possibly a tiered
landscape approach of different size materials may be more appropriate.
101. A full-size clubhouse/recreation building should be provided at the pool for
the townhouses.
102. The recreation space is not adequate around the pool for the townhouses. A
green, outdoor, play space should be provided to give the residents a park
setting for outdoor activities, since there is not a park in the immediate
vicinity. Staff suggests the elimination of the streets surrounding the pool area
and their conversion to park/green space, since the remainder of the
circulation pattern appears adequate.
COMMUNITY REDEVELOPMENT AGENCY COMMENTS:
Comments:
103. Provide north elevations of the parking garage. Staff recommends ironwork
or other decorative elements to enhance the structure's appearance.
104. Show openings of Unit "C" on the north side under arcade.
MWR/elj
'"
.
J ~
DEPARTMENT OF DEVELOPMENT
BUILDING DIVISION
MEMORANDUM NO. 05-094
TO:
FROM:
Ed Breese
Principal Planner fi!j
Timothy K. Large ~
TRC Member/Building vision
DATE:
May 20,2005
SUBJECT:
Project - Heritage Club @ Boynton Beach
File No. - NWSP 05-014 - second review
The Building Division has the following issues:
1 Sheet SP-1 - Building Tabulation - clarify the residential sub-classification for
building #3 through #15. "R" is unacceptable.
2 Sheet SP-1 - Building Tabulation - There are no construction type. Is "Type I", one-
hour protected? Comply with 2001 FBC, Chapter 6.
3 Clarify the construction type and the occupancies of the mixed-use buildings. The
building tabulation shows occupancy of Buildings #1 and #2 as residential, yet there
are commercial uses located in these buildings. Comply with 2001 FBC, Chapter 3
for occupancy types.
4 Submit square footage of parking garages.
5 Sheet SP-1 - Clearly indicate the number of levels for the south parking garage and
the maximum height. Also indicate the number of parking spaces provided in each
garage.
6 According to 2001 FBC, Section 11-4.1.2, "if parking spaces are provided for self-
parking by employees or visitors, or both, then accessible spaces complying with
2001 FBC, Section 11-4.6 shall be provided in each such parking area. Show
accessible spaces in all areas. Comply with the 2001 FBC. (Include parallel parking.)
7 Clearly show the required accessible route complying with 2001 FBC, Section 11-4.3
that shall connect accessible buildings, accessible facilities, accessible elements,
and accessible spaces that are on the same site. Passing spaces shall be provided
per 2001 FBC, Section 11-4.3.3.
8 Your response to comment #65 is unacceptable. The distance of all exterior walls to
adjacent buildings/property line is an area of concern. The allowances set forth in
the 2001 FBC, Table 600 are for the percentage of wall openings permitted. This is a
S:\Development\Building\TRC\TRC 2005\Heritage Club @ Boynton Beach second review Page 1 of 2
..
4-
life-safety issue. Submit calculations showing the percentage of wall and wall
openings for this project, and clearly show the distances between the buildings.
9 Your response to comment #69 is unacceptable. A 13R automatic sprinkler system
is only applicable to residential occupancies up to four stories in height. An
automatic sprinkler system designed in accordance with NFPA 13 is required for the
parking garages and other non-residential areas.
10 Your response to comment #72 is non-relevant. All the single-story dwelling units
located in the multi-family building are "covered dwelling units" under the Florida Fair
Housing Act, and thus must comply. Indicate on the plan which design option (A or
B) is being used for this project and show the required clear floor space for the
fixtures.
11 Your response to comment #74 is unacceptable. Submit calculations for the required
number of handicap accessible spaces for the common areas and the amount of
spaces dedicated to the multi-family units covered under the Fair Housing Act. The
common area parking spaces shall comply with the 2001 FBC, Chapter 11.
V..../ ././ I c./
NOTE: The remainder of the comments (#75, 77, 79, 82, 91 & 92) have not been
addressed properly. The applicant Sh:l: provide 70pe res, ~on\ to all~mentS.
tkl:bf '-::/'1 41 ..j \r~ 5"4
/ J ~J ,
'.-'
1to
S:\Development\Building\TRC\TRC 2005\Heritage Club @ Boynton Beach second review Page 2 of 2
PIO 4~oq 6uole s~UawaAoJdw! ap!AoJd O~ paJ!nbaJ oSle SeM ~ue:>!Idde a4~ 'JaAaMOH '.u.e~s
4~!M uodn paaJ6e se (~eM-.J0-~46!J 'V-OS le~o~ e 6U!P!AOJd) '~MH a!X!O PIO 6uole ~eM-.J0-~46p
.Jo 'V-OZ leuo!J!ppe ue UM04S se4 ~ue:>!Idde a4J. 'UO!leJlS!U!WPV peoJl!e~ leJapa.::l aLll Lll!M auoz
la!no e se OU!SSOJ:> S!Lll AJ!lenb OllUalU! aLll Lll!M OU!SSOJ:> 'PAI8 WeaJlsJln8~~~3.::1 aLll JO sap!s Llloq
uo ue!paw JapJeq e PI!nq Ol paJ!nbaJ lOU lnq Jap!suo:> Ol pa>lse S! JadOlaAap aLll uo!sap S!Lll JO tJed sv
'luawdolaAap pasodoJd aLll ollua:>efpe SAeM>lJed pade:>spuel pue ou!dPlS 'sauel UJnl Ual alepdoJdde
'JaMaS WJOlS 'JannO ~ qJn:> JOJ ap!AoJd Ol 'PAI8 WeaJlsJln8 pue 'AMH a!x!o PIO pnJlSuo:>a~ '9
OI:l:l~J. - S}J~OM OI1Snd
"eaJe 6u!peOI a4~ 6u!ssa:>:>e sal:>!4aA AlaA!lap JO.J s~uawaAow 6u!uJn~ pue 6u!>J:>eq JO.J WOOJ
MOlle o~ pue a~seM P!lOS ~q SUOlleJado 6u!>J:>eq 6u!Jnp ~~a.Jes JO.J SUJa:>uo:> o~ anp UO!~e:>OI
Ja~sdwnp 4lJOU a4~ .JO 4lJOU sa:>eds 6u!>JJed lalleJed a4~ 6U!AOWaJ spuawwo:>aJ ~16uOJ~s .u.e~s '17
'uo!~eJado dn>J:>!d a4~ wJojJad o~
~~!I!qe Jno pue saz!s ped paJ!nbaJ a4~ a~enleAa ue:> aM OS sJau!e~uo:> asa4~.J0 az!s pue Jaqwnu
a4~ a~e:>!pu! aseald 'dn>J:>!d JO.J s6u!pl!nq a4~ o~ ~ua:>erpe seaJe leJ~ua:> o~ ~no ~46noJq aq
IJ!M pue s6u!pl!nq asn-pax!w a4~ JO.J pasn aq IJ!M sJo~:>edwo:> ~e4~ pa~e:>!pu! se4 ~ue:>!ldde a4J. '8
"SUOlleJado dn>J:>!d
6upnp a~seM P!lOS JO.J WOOJ aJOW MOlle O~ uO!J!puo:> pua-peap 4:>ea .Jo pua a4~ pue suo!~:>as
"~no-dwnq,, pua~x3 'suo!l!puo:> asaLll paJJo:> aseald '>I:>nJ1 alseM P!IOS dn>l:>!d :>!leWOlne Jno
Aq pa:>!AJas aq Ol alqe aq lOU II!M leLll pafoJd aLlllnOLlOnOJLll suo!pas pua peap aldmnw aJe aJaLl1 'G
'(e) 9G-O ~ uo!pas '3aO~ aLll Jad asnJaJ JO OU!IPUeLl pue aOeJOlS
aLll ou!pJeoaJ (OOG9-GpL-~99) luawtJedaa s>lJOM :>!Iqnd aLll peluo:> UO!le:>!Idde l!WJad Ol JOPd .~
Tv~3N3~ - S}J~OM OI1Snd
'passaJppe uaaq aAeLl SWal! asaLlll!lun V~~
aLll Ol pJeMJoJ OU!AOW puawwo:>aJ lOU op aM sluawwo:> asaLll JO a:>ue:>!J!uo!S pue Jaqwnu aLll uaA!8
'adAl Ploq U! UMoLlS aJe sluawwo:> MaN 'leAOJddv JO SUO!l!PUO~ se ueld al!S aLll MOlloJ Ol papUalU!
aJe JO 'passaJppe lOU JaLll!a aJaM leLll sluawwo:> aJe OU!MOIIO.::l '900G' ~ ~ IPdV palep owaw Aq pap!AoJd
sluawwo:> aLlllSU!eOe 900G 'L ~ AeV\l pawJoJJad seM sueld al!S pa:>uaJaJaJ aAoqe aLll JO Ma!Aa~ puo:>as
r-,(/~J~;}'t!__l I
J
~~O-SO dSMN "ON al!:I
4:>eas UO~U~OS ~e qnlO a6e~paH
Ma!Aa~ puZ - ueld a~!s MaN
s~uawwoo Ma!Aa~
:3~
I
I
I
~n(}7. n 7 A \:.M
900G '6 ~ AeV\l
:3.lVa
JaaU!OU3 Jo!uas "3'd 'ueool epupnel
:V\I0~.::I
OU!UOz pue OU!UUeld 'JaUUeld ledpuPd 'aSaaJ8 P3
:01
EgO-SO 'ON II\InaN~01l\l311\1
NOISIAla ~NI~33NI~N3
S)I~OM ~1l8nd :10 .lN3I1\1.l~"d3a
'SlueJpALllle 6u!MOLlS Aq
'UO!l!PUO~ S!L1l Slaaw ueld aLllleLll aleJlSUOWap aseald 'lUeJpALI aJ!j pasodoJd JO 6u!lS!Xa ue jO laaj
OO~ U!L1l!M aq II!M 6u!PI!nq L1~ea uo SlU!od lie leLll saJ!nbaJ 9 ~ uo!pas 'AI ap!lJ'v' '9 JaldeLl~ '~al aLII '9 ~
'((q)9~-9~ uo!pas '3aO~)
JaleaJ6 S! JaAaLl~!L1M 'SJalPMJapUn a~ueJnsu! Aq pasodw! lUaWaJ!nbaJ aLll JO '9~ uo!pas 'AI ap!lJ'v' '9
JaldeLl~ '~al aLll U! palels se aJnssaJd lenp!saJ TS'd o~ L1l!M (sluawdolaAap le!lUap!SaJ awos 'w'd'6
OOg) 'w'd'6 OOg' ~ jO lUaWaJ!nbaJ apo~ Al!~ aLll 6u!leJlSUowap paJ!nbaJ aq II!M SUO!lelmle::> MOlj aJ!=i "9 ~
'(~~-9~ uo!pas '3aO~) pafoJd S!L1l6u!AJas
swalsAs JaMaS pue JaleM aLll JOj paJ!nbaJ aq II!M Sl!WJad lUaWlJedaa L1lleaH Aluno~ L1~ea8 wled '17 ~
S3111l11n
'UO!le::>!ldde l!WJad UO!pnJlSUO~ jO aW!l aLllle paMa!AaJ aq II!M
pue IIspJepUelS uO!l:mJISuO~ pue )looqpueH u6!sao 6u!JaaU!6u311 aLll pue s6u!MeJa pJepUelS
L1~ea8 UOlUA08 jO Al!~ alqe~!ldde aLll L1l!M a~uepJo~~e U! aq lIeLls sl!elap UO!pnJlSUO~ 6upaau!6ua
IIV' 'aW!l slLllle Al!I!qelda~~e UO!pnJlSUO~ JOj paMa!AaJ aq lOU 111M Sl!elap al!S pue a6eu!eJa '6ulAed .~ ~
'6u!ll!WJad jO aW!l aLllle paJ!nbaJ aq II!M 9 uO!l~as 'AI
apllJV' '9 JaldeLl~ '~al aLll L1l!M a~uepJo~~e U! 'SUO!leln~le~ a6eu!eJp 6u!pnpu! 'sueld a6eu!eJa IIn.::l .~ ~
'PAIS WeaJIS~ln~ olluawdolaAap aLII WOJ~
AeMaA!Jp aLII JO~ sal6uepllLl6!s 'U-SE MOllS 'AeMLl6!H a!X!a Pia pue pJeAaln08 WeaJlSjlnE) JOj
sal6uepllLl6!s ':y-g~ asn 'AeMLl6!H leJapa.::l 6uole sal6uepllLl61S aLll JOj 9179 xapul pJepUelS 10a.::l
a:::>uaJaja~ '('H'9 uOlpas 'II ap!lJV' '9'L JaldeLl~ '~al) sueld ade~spuel aLll uo sal6uepllLl6!s MOllS . ~ ~
'(q' ~'V' uo!pas 'II aP!lJV' '~~ JaldeLl~ '~al) a~ej.Jns 6u!)jJed aLll uo 6u!MOpeLlS aJnlnj
aleU!W!la Ol SaJnlX!j lLl611 ollua~efpe SaaJl Adoue~ a6Jel ale::>olaJ JO a~eldaJ Ol AJessa~au aq Aew II '0 ~
'Ma!AaJ l!WJad le pue UO!SS!WWO~ aLll Aq paleJaua6 aq lOU
Aew sluawwo~ leUO!l!ppe leLll aJnsua lOU saop ssa~oJd ~~l aLll 6upnp sueld asaLll jO a~uelda~~V'
'Sluawwo~ leuO!l!ppe aleJaua6 Aew sueld asaLll Ol SUO!S!AaJ JO sa6ueLl~ leLll alOU aseald '6
'slaaLls
alepdoJdde lie uo papaljaJ aq lIeLls sueld aLll Ol SUo!paJJO~ Jo/pue sa6ueLl~ 6up!nbaJ Sluawwo~ IIV' '9
~NI~33NI~N3
'AIUO ssaJ6u! AeM
-auo MOlls olluawdolaAap aLII ~o JaUJo::> ISeaLllJOU aLII Ie AeMaA!Jp aLII JO~ S6U!MeJp aLII as!Aa~ . L
'lIauoz 6u!peOl- 6u!)jJed ON" 6u!le~!pU! MOllaA U!
a6essaw luawaAed e apnpu! :s6u!PI!nq l!elaJ aLll JOj sauoz 6u!peOI 'lJ-g~x'lJ-~ ~ adpls pue aleaU!laa '9
'UO!SS!WWO~ pue pJeOS ~~ aLII 01 6u!paa::>oJd
01 JO!Jd l::>aroJd S!LlI JO~ slUaWaAoJdw! al!S-'uo paJ!nbaJ lie MOllS lIeLls lue::>!Idde aLII .sueld
Ma!Aa~ puo::>as pap!AoJd aLII uo UMOLlS IOU aJaM LI::>!LlM 'PAIS WeaJIS~ln~ pue 'AMH a!x!o
~ a6ed
900~ '6 ~ AeV\l
Ma!Aa~ pu~ - ueld al!S MaN 'L1~ea8 UOlUA08 le qnl~ a6elpaH :a~
~90-90 'ON owaV\l UO!S!A!a 6upaau!61J-=3/luawdolaAaa jO lUawlJedaa
::lOp'M.;}~A;}lI pUl uUld ;}l~S M.;}N "8:'8: @ qnIJ ;}2Unl;}H\sq~.I)I\2ll!1;};}u~2uffi:S
al!.:!
(l!eW-a e!A) 6upaaU!6u3/S)!JOM ~!Iqnd 'lSA/euV' sueld 6upaaU!6u3 'lIeH lHaUUa)!
alseM P!IOS/S)!JOM ~!Iqnd 'Ja6eueV\l alseM P!IOS 'uu!no AJJel
UO!S!A!a spunOJE) ~ A1lSaJO.:!/S)!JOM ~!Iqnd 'Jos!AJadns a~UeUalU!eV\l 'lIeH epualE)
(I!ew-a e!A) 6upaaU!6u3/S)!JOM ~!Iqnd 'JaaU!6U3 Al!~ "V\I'S'd (3.d "Jr 'Aalla)! p!Aea 'H
sammn 'JopaJ!a Al!mn Alndaa 'ellaZZeV\l '^ Jalad
(l!eW-a e!A) S)!JOM ~!Iqnd 'JopaJ!a '.3'd 'po06JaA!l .~ AaJjJar :~~
)!~/ll
'uO!le~!ldde l!WJad UO!l~nJlSUOO JO aW!l ala le paMa!AaJ
aq II!M Aala :( salepdn Aue 6u!pnpu!) lenuew "spJepueJS uOI':>nJJsuo:) pue >looqpueH u6!saa
6uIJaaU!6u3 sammn" sJuaw:J,Jedaa sammn alH Lll!M a~uepJo~~e U! aq lIeLls sl!elap UOn~nJlSUO~
Al!mn IIV' 'aW!l S!Lll le Al!l!qelda~~e UO!pnJlSUO~ JOJ paMa!AaJ aq lOU II!M SI!elap UO!pnJlSUO~ Al!l!ln . ~G
'Alddns ~!lSaWOp pue UO!palOJd aJ!J alenbape 6upnsse
AqaJaLll "PAI8 lSaJ~eas Ol AeMLl6!H leJapa.:! WOJJ dOOI .U!-B ue LlS!lqelsa Ol S! u6!sap aLll JO
lUalU! aLll 'pJeAaln08 lSaJ~eas uo u!ew 'U!-G ~ aLll Ol uo!pauuo~ u!ew JaleM 'U!-B ue LlS!lqelsa Ol
paJap!suo~ aq Aew alnOJ aleUJalle ue JO ::J,Jno~ pJ8 3S JO Al!UP!A aLll U! 'aAV' IHV8 3S uo SaleU!WJal
leLll au!! .U!-B 6u!lS!Xa aLll Ol 'pJeAaln08 lSaJ~eas JO ap!s lsaM aLll uo pale~ol u!ew JaleM
'U!-G ~ aLll WOJJ paLls!!qelsa aq lsnw uo!pauuo~ u!ew JaleM 'U!-B ue 'uomppe ul 'AeMLl6!H leJapa.:!
JO ap!s lsea aLll uo pal~ol u!ew JaleM 'U!-B 6u!lS!Xa aLll Ol pal~auuo~ aq lsnw walsAs JaleM aLll 'q
'u6!sap aLll U! palepowwo~~e aq lsnw
UOnels aLll Ol SMOIJ aJnssaJd pue Al!AeJ6 6u!lS!X3 'sa6ueLl~ al!S Aq pasodw! SlU!eJlSUO~ aLll pue
puewap pappe aLll alepowwo~~e Ol se os pa~eldaJ JO papeJ6dn aq lsnw UO!lelS U!I al!S-UO aLll 'e
:sMOIIOJ
se pOJ!nbBJ oq 1I't'l\ BJnpnJlSeJJU! JBMBS pue JBleM 6u!lS!XB BlH Ol slUBWaAOJdwl BJ!S-,yO lie M04S 'OG
'9~-9G uo!pas
'3aO~ aLll Lll!M a~uepJo~~e U! 'pafoJd S!Lll a~!AJas Ol paJ!nbaJ slUaWaAOJdw! JaMaS Jo/pue JaleM aLll
JOJ sueld aLll paAoJdde seLlluaw:J,Jedaa S!Lll mun panss! aq lOU lIeLls pafoJd S!Lll JOJ l!WJad 6u!PI!nq V' '6 ~
'uO!le6pJ! JOJ paMolle aq lOU lIeLls JaleM Al!~ alqel!eAe Al!peaJ aJe
sa~Jnos JaLllO sV' 'JaleM alqelod JO UO!leAJaSUO~ aLll saJ!nbaJ 'v'8'~'8 A~!I0d ueld aA!SUaLlaJdwo~ 'B ~
'puewap papadxa JO 'az!s JalaW leu!J
uodn paseq paU!WJalap aq II!M aaJ S!Lll 'lSJ!J SJn~~o JaAaLl~!LlM 'leAOJdde ueld al!S JO sAep (L) uaAas
U!Lll!M JO SWJoJ UO!le~!Idde luaw:J,Jedaa LllleaH aLll uo aJnleu6!s sJuaw:J,Jedaa aLll JOJ lSanbaJ aLll uodn
JaLll!a pafoJd S!Lll JOJ Pled aq aaJ UO!leAJaSaJ Alpede~ e leLll saJ!nbaJ (3)v8-9G uo!pas '3aO~ aLll 'H
8 a6ed
900G '6 ~ AeV\l
Ma!Aa~ puG - ueld al!S MaN 'Ll~ea8 UOlUA08 le qnl~ a6elpaH :aCl
890-90 'ON owaV\l UO!S!A!a 6upaau!611':3/luawdolaAaa JO luaw:J,Jedaa
'p\lP!AO.ld U\l\lq seq lU\lW\llelS AJU\l.l.lnJuoJ
, . P\lS!A\lM 'UO!S!A!Q JyjU.I.L A}unOJ qJe\lg wled WO.lj SlU\lWWOJ p\lA!\lJ\lM
" ''3U!l::l::lU!'3U3: :)!JJlU.L Aluno;) q:)~::la wl~d WO.I.J (M::l!M~ spl~pU~lS
::l:)UllWlOJl::ld :)!JJ~l.L) A:)U::llln:)uo:) JO ::l:)!lOU pu~ S!SA(~U~ :)!JJ~ll ~ ::lp!AOld 'L
:SlU::lWWO;)
J!Ue.l.L - S)lMOM. JrUIIld
')10 S! \ll!S \lql qono.lql JyjU.ll .IelnJ!q\lA ~ P\lAIOS\l.l U\l\lq \lAUq SPU\l pe\lp IIV
'suo!l!puo:) ::lS::lql p::lllO:)
l ')pnl.L ::ll!ffii\\. P!loS dmp!d :)!l~woln~ mo Aq P::l:)!Al::lS ::lq Ol ::llq~
::l!ffi::l(d
::lq lOU II!M l~ql p::lfOld ::lqllnoq'3nOlql SUO!P::lS PU::l p~::lp ::lldmnw ::ll~ ::ll::lq.L '9
'P\llUJOI\l.l \lq II!M wnld UO\lo!d \lql puu AIOU!p.loJJe p\lWW!.Il
\lq II!M \lA!IO )fJUIH \lq.L 'ueld ~u!duJspUel U! p\l!J!pow pue p\l~p\lIA\OU)fJV
. '::lmsopu::l ::lqljo ::lp!S lS::lM
::lql uo wnld UO::l'3!d ::lql pUll ::lmsopu::l ::lql JO lS~::l S::lA!lO ){:)~IH '3u!lS!X::l ::lql
pUll (Z '3U!pI!na JO qlnos) l::llSdwnp ::lql U::l::lM}::lq P!Uuo:) 1~:)!l.I::lA ~ S! ::ll::lq.L .~
'<tn )fJ!<t .I0j spud \lqllu S\lp!q\lA \loeq.le~ ~u!peol-lUO.lj
qlr" S! uo!punj P\lPU\llUl 'dn )fJ!d .I0j se\l.le ~U!Ploq \lql Ol U\l)fel \lq U\lql
II!M qse.ll \lql pue ~u!Pl!nq qJU\l U!ql!M p\lsn \lq II!M W\llSAS uo!pedwoJ \lq.L
'dn )fJ!d .I0j Ol P\lIlO.l \lq Ol S.I\lU!elUOJ .10) \l.le UMOqS SU\l.lU ~U!Ploq qsu.ll \lq,L
'::lu!I 4I::ldold ql.Iou ::lql
'. "\ '3uol~ MOY :)!JJB.ij p::lsodold ::lql Ol ::lnp l::lU!~lUO:) ::lql dn ){:)!d Ol )(:)n.ij '3U!P~OI
-l~::ll ~ lOJ ::llq!SS::l:):)~ ::lq lOU II!M ~::ll~ '3U!Ploq lSOWW::lql.IOU ::lql AII~uo!l!PPV
'P::l'3l~IU::l ::lq Ol p::l::lU II!M s::lmso(:)u::l ::lql p::lsn ::lq Ol ::ll~ slop~dwo:)
JI 'slop~dwo:) lO Sl::llsdwnp lOJ ::lq II!M S~::l.m '3U!Ploq qs~.ij ::lql J! ~!lU::lPI 'v
'(spud \ll\l.lJUOJ) SU\l.lU ~U!Ploq qsu.lllsn!' - s\l.lnsofJu\l .I\llsdwnp 109 \l.lU
\lS\lq.L '(sHun tS) 1 ~u!Pl!nq U! ,~!U\lWU/lU\luodwOJ IUHU\lP!S\l.l \lql pue ~jUJ
\lql \lA.l\lS AI!.Iuw!.Id II!M I ~u!Pl!nq jO \lp!S ql.lou \lql UO U\l.lU ~U!Ploq qsu.ll
\lq.L '\llenb\lpu uuql \l.lOW S! ~u!pl!nq S!ql jO qlnos U\l.lU ~U!Ploq qsu.ll \lql os
" Z ~u!pl!nq U! (sl!un ZI) IUHU\lP!S\l.l pue HUl\l.l WO.lj p\lp\ldx\l S! qse.ll (UW!U!W
"
'UO!S!:)::lP S!ql ~!lsnf ::lS~::lld 'W~::l.ijS ::llS~M p::lp::ldx::l ::lql ::lAl::lS
OllU::l!:)!JJns ::lq Oll~::ldd~ lOU S::lOp S!q.L 'A~Mq'3!H 111l::lp::ld '3uOll1 s'3u!pI!nq
111!lU::lp!S::ll/::l:)!JJO/I!~l::ll ::lql ::l:)!Al::lS Ol p::lP!d::lp ::l.m s::lmsopu::l qSl1.ij OM} AluO '(
'uuld uo p\llOU 'p\l~p\lIMOU)fJV
" 'v-O '3U!Ml1lO pl~pUl1lS Al!;) ql!M ::l:)Ul1PlO:):)l1
U! P::lpnllSUO:) ::lq IIl1qs s::lmsopu::l l::llsdwnp ::ll!S ::lql ll1ql ::llOU Aq ::lll1:)!PUl 'z
'P\l3p\lIMOU)fJV
~ ,-,'. '(11) n-o I
..- ."
.''''- - . , UO!P::lS '3:00;) ::lqll::ld ::lSt1J::ll JO '3u!lPUl1q PUl1 ::l'3l1l0lS ::lql '3U!p.m'3::ll (00Z9
-ZvL-19~) lU::luij,md::lO S){lOi\\. :)!Iqnd ::lql Pl1lUO:) uO!ll1:)!Iddl1l!Wl::ld OllOPd '1
:SlU::lWWO;)
le.l\lu;)~ - S)lMOM. JrUIIld
.L;)3:fffil 3:0fl'1;)N! S.LN3W.LMV d3<I
. .+--
':OU!){ll1W OUIBlS ::lll1p lU::lUQl110::l0
:aU!UOZ PUl1 :aU!UUl1ld ~OO(:: '(Z q:)ll1W 11 ql!M Ul1ld ::ll!S M::lN 11 Sl1 p::lmlU::lp! SUllld M::l!A::lljS 1 :::l:)U::ll::lJ::l~
V 1 O-~O dSi\\.N :l::lqwnu ::lI!d
q:)l1::la UOlUAOa @ qnI;) ::l'3l1lP::lH :::lUIBU P::lfOld
URld OlJ!S MOl N
<,..~.' SLN:tIWW03 M:tIIA:nI lS I
h. _"*",, __....' .
, ,,'
'-''0,
"
>,
:x..
"
"
".
l:J3f::rn
3Qfl'1:JNI
'ACMpCO.l S!ql uo ;).IC salc~ oN 'UCld al!s aas :AIUO (lsaM aql P.lCMOl) aA!.Ip
ACM auo C sc papUalU! S! A.mpunoq q.J.Iou aql ~UOIC palcau!lap ACMpCO.l aql
'<lmIP~j J<lMod U jO lU<lA<l <lql U! <lll?~ <lql u<ldo AIIU::lpUwOlnu Ol
Almqudu::l dmpuq A1<lUUq ql!M P<ltG}!S<lP <lq PInoqs <llU~ <lql JO AUMpUOJ qlnos
-q:).lou AUM-<lUO <lql uo sI!Uj <llU~ <lqU! punoJu WIll Ol P;:l;:lU ;:lql ;:llUPOWWO::l::lY '8 I
'UCI al!S aas: IUO lsaM aql P.lCMOl aA!.Ip
,{CM auo C sc papUalU! S! A.Icpunoq q.J.Iou aql ~UOIC palcaU!lap ACMpCO.l aql
'UO!l!PUO::l S!ql P;:lJlO::l ;:lSU;:lId 'qlP!M U! lOOj-17Z uuql SS<lI S! lU;:lwdopA;:lp
;:lql jO J;:lWO::l lS;:lMq:).lOU ;:lql U! AUMpUOJ qlnos-q:).loU AUM-OA\l ;:lql . L I
. CMq !H IC.lapad uo pappc uaaq aAcq su !S CM auo
'AUMq~!H IUJ;:lP;:ld OlUO
SAUM;:lAPP SS<lJ~<l punoqlSU;:l ;:lql WO.IJ SSOJ::lU SU~!S ,Auo AU 1\\ -;:lUO" ;:l::lUId '9 I
'awp uc lC salc aql q nO.lql al!s aql Ol ssa;);)c aAcq IIcqs Sap!qaA alsc M
P!loS puc an;)saH/a.l!d 'UCId aql uo pa)f.lcw AI.lCap a.lc salc~ (W.lC .Iuaf) IIV
'<llSU1\\ P!IoS puu <In::ls<l~pJ!d
JOj Almq!SS;:l::l::lU J!;:lql ;:llU::l!PU! puu S;:llU~ jO UO!lU::lOI ;:lql A]!lU;:lP! A{JU;:lI:J . ~ I
'sucld U!HaU! u3 cu!w!la.ld aql JO Z laaqs uo t# aloN IC.laua9 aas
'SI!Ul;:lP ~u!dplS JOj S;:lP;:lS ")I,, S~U!MUJQ p.rnptrnlS Al!:J ;:l::lU;:lJ;:lj;:l~ '17 I
'pa !.IlS puc palcau!lap uaaq aAcq sauoz u!pcol aql
. r I' .. ',,;:lUOZ
~U!PUO'1 - ~UPJlUd oN" ~U!lU::l!PU! MOIPA U! ;:l~USS<lW lU;:lW;:lAUd U <lpnpu!
:s~u!PI!nq I!Ul;:lJ ;:lql JOj S;:lUOZ ~U!PUOI lOOj ~t: x lOOj-ZI ;:ldPlS puu ;:llU;:lu!I;:lQ 'n
'paAOWa.l uaaq aAcq sa;)c s u!)f.lc 'pa palMompv
'P;:lJlO::l
;:lSU<lId ';:lJIll::lnJlS ~uPI.rnd OMl ~u!PI!n8: ;:lql wo.IJ punoqlSU;:l ~u!l!x;:l S;:lP!q;:lA
ptrn S;:lP!q<lA ~UP;:llU;:l punoqlS<lM JOj pJuzuq ::lYJRIl U ;:llU<lJ::l lI!M AUMq~!H
IUJ;:lP;:ld lJo A.nU;:l U!UW ;:lql Ol lU;:l::lUfpU ~uPJlud IUUO~U!P p;:lsodOJd ;:lql 'z I
'ucl aas 'pau !sapa.l uaaq scq aU!I a 0.1 UHlsa M
'~uPI.rnd
I;:lIIu.rnd ql!M P!lJUO::l AUlU ;:lu!I A:)J;:ldoJd lS;:lM ;:lql ~uoIu p;:lsodOJd S){UO ;:lA!'1 . I I
'UCI al!S aql uo ClCp .Iclnqcl aql JO.J.Ic lOU S! puc pa paIMOU)f;)V
'Slu;:lw;:lJ!nb<lJ ~U!){Jud IUW;:llU!
SpJUMOl p<llUnO::l ;:lq lOU AUW puu ~u!){.rnd ::lHqnd ;:lq uuqs ~u!){Jud l;:l;:l.IlS-UO '0 I
'ucl al!S aas :, CMq !H a!x!Q UOIC UOPCZ!lCl!Aa.l JO UCI .I!aql
lua(Ualdw! Ol q;)ca8 UOlU,\08 JO .\lD aql .IoJ a;)cds alC;)olIc II!A\ HdolaAaQ
'UO!lU.IlS!U!WPV pUOJI!u~ IUJ<lP<ld ;:lql ql!M <lUOZ l<l!no U su ~U!SSOJ::l S!ql
A]Hunb OllU;:llU! <lql ql!M ~U!SSOJ::l 'PAI8 WU<lJlSjInOm1l:J3d ;:lquo ;:lP!S qloq
UO UU!P;:lW J<l!Jluq U PI!nq Ol p;:lJ!nb;:lJ lOU lnq J;:lP!SUO::l Ol P;:l){SU S! J;:ldOI<lA;:lP
;:lql tG}!S<lP S!ql jO :).Iud sy 'lU<lwdoI;:lMP p<lsodOJd <lql OllU<l::lUfpU SAUM){Jud
p;:ldu::lsPUUI pUU ~u!dplS 'S<lUUI WIll lj<ll <llUpdoJddu 'J;:lM<lS WlOlS 'J<lun~
7fl qm::l JOj ;:lp!AOJd Ol 'PAI8 WU;:l.IlsjInO pUU 'AMH <l!X!Q PIO PnJlSUO::l<l~ '6
'UCI al!S aas: CMq !H a!x!G JO uOPCz!lcl!Aa.l pauucl s, D;)
Ol ;);)cds ;).IOW alC;)!pap Ol palC;)OlIu uaaq scq a;)p,ds AP,M-JO-lq~!.1 Icuo!l!PPV
's;:lsodmd ::l!Iqnd JOj qlP!M IUlOl
lOOj-OL jO lUlOlU JOj MOUU Ol ;:lu!I A:)J;:ldOJd lS<lM ;:lql ~UOIU q::lU;:l8: UOlUA08:
jO Al!:J ;:lql Ol SlU;:lW<lSU;:l JO AUM-jO-lq~p jO lOOj-017 IUUO!l!PPU uu <llU::l!P<lQ '8
SlN3WlHV d3Q
(;
~O/L I/~O
SJ;)qW;)W Wll;)l\lV WO.IJ s;)suods;)~ J~l
---
'las aql U! pap!Ao.Jd MOU S! SUOnUln;}IU;} ;}!.JlalU
oloqd al!S ql!M laaqs alu.Judas U puu SUUld adu;}spUUI uo UMOqS S! iJunqiJn al!S
'Sllrll!lUqns u~ld ;)~l mOA}o:).rnd S~ S"Pl~lUOlOqd
~P!A01d ~s~~ld '(L'N'v UO!P~s 'z l~ld~q;) '~0'1) s~sn 1~!lU~P!S~l
AU~ lUOl] A~M~ P~P~l!P ~q II~qs iJu!lqiJn '([,N'v UO!P~S 'z l~ld~q;) '~0'1)
P~l!q!qOld S! P~l~"ol S! ~sn ~ql q"!qM UO 4I~d01d ~ql pUOA~q 10 l~ lU!Od
AU~ w ~lq!ld~"l~d AI!P~~l S! q"!qM ~l~ID 'U~ld iJU!lqiJn ~ql uo V UO!P~S 'II
~P!llV 'fZ l~ld~q;) pU~ [,S'~ UO!P~S 'I ~P!llV 'fZ l~ld~q;) 'I 1 UO!P~S 'AI
~P!llV '9 l~ld~q;) '~0'1 ~ql ql!M ~"U~UUO}UO" U! SI!~l~P ~Iod pu~ 'iJU!P~OI
PU!M ~Iod ~pnl"uI ('~TV UO!P~S 'II ~1"!llV 'fZ l~ld~q;) '~0'1) 'lU'~
oo:z mun uo U!~lU~l Ol ~.rn pUll 10.lluo" 1~"!.Il"~P-oloqd Aq P~l~l~do ~q II~qs
; S~lmX!J ~qll~ql ~lOU ~ ~P!A01d .( ~PO;) iJu!pI!ns ~ppof.o:I pu~ ~. I'V UO!P~S
., 'II ~P!llV 'fZ l~ld~q;) '~0'1) P~ol PU!M HdW 0171 ~ pU~lsql!M II~qs s~lod
.- \
lqiJ!{ ~qll~ql Ajp~ds 'Ullld iJu!lqiJn ~ql uO '~lpU~"-lOO} ~uo }O I~MI lqiJ!{
~iJ~l~A~ lUnlU!U!lU ~ ~P!A01d II~qs illl!s~p iJU!lqiJ!{ ~ql ('V'S' L UO!P~S 'v
l~ld~q;) '~0'1) SUllld ~d~"spu~'1 pUll ~l!S ~ql uo iJU!lqiJ!{ ~l!S p~SOd01d MOqS .~Z
'Slaaqs IIU Ol pappu uaaq suq aIU;}S ;}!qau.Jo pUl~ UanpM V
" .', 'Sl~~qs II~ uo s~l~"s "!qd~liJ pUll U~UpM ~P!A01d 'VZ
'paopal,",ompv
'M~!M1l!UU~d l~ pu~
;, UO!SS!lUlUO;) ~ql Aq P~l~l~U~iJ ~q lOU A~lU SlU~lUlUO" I~UO!l!PP~ l~ql ~msu~
lOU s~op ss~"old ;)~l ~ql iJupnp sU~ld ~s~ql }O ~"U~ld~""V 'SlU~lUlUO"
I~uompp~ ~l~l~U~iJ A~lU sU~ld ~s~ql Ol SUO!S!M110 s~iJu~q" l~ql ~lOU ~SB~ld 'fZ
'paopal,\\ompv
... , 'Sl~~qs ~l~pd01dd~ II~ UO P~P~LJ~l
~q II~qs SUllld ~ql Ol SUO!P~llO" lO/PU~ s~iJu~q" iJup!nb~l SlU~lUlUO" IIV 'zz
'suuld iJu!.Jaau!~u3
,UUU!lUna.Jd aql JO Z laaqs uo L# aloN IU.Jaua9 aas - paiJpalMompv
'ls~nb~ll!UU~d ~ql ql!M p~pnpu! ~q II~qs 'sl~qlo AU~ pu~ (W~aO;)Sd)
lU~lU~iJ~U~W ~"mos~~ l~lU~lUU01!AUa }O lu~uQ.md~o ,.\Juno;) q"~~S
lUI~d '(Oa;)Sd) lu~uQ.md~o iJup~~U!iJua ,.\Juno;) q"~~S lUI~d '(OH;)Sd)
lu~uQ.md~o qll~~H ,.\Juno;) q"~~S lUI~d '(daOd) UO!P~lOld l~lU~lUU01!AUa
}O lU~lU.llBd~O ~P!lOf.o:I '(OOM'1) PPlS!O ~iJ~U!~lO qlloM ~~1 '(OWMdS)
P!.IlS!O lU~lU~iJ~U~W l~l~ M ~Ppold qlnos '(lOad) UO!l~llOdsu~ll }O
lU~Ul~md~a uPpokl su q::ms S~!OU;)iJu iJurll!uu~d J;)qlo lUOJj p;)J!nb;)J Sl!UU;)d '1'<:
:SlU~lUlUO;)
NOISIAIO 9NUI33NIDN3
'uuld al!S aas ~paAolUa.J uaaq suq uO!l!PUO;} uO!pas.JalU! AUM-.JnoJ aql
, .j.' 'uO!P~Sl~lU! A~M-mO} ~ OlU! iJupp~q}O sw~"uo" ,.\J~}~S Ol
~np ~~1~ lood ~quo lS~Mqlnos ~qll~ s~,,~ds iJuPI.rnd l~uoiJ~!P OMl ~ql ~l~I~O 'oz
'uula al!S aas ~AIUO osaM aql P.JUMOl) aA!.Jp
AUM auo U su papUalU! S! A.Jupunoq ql.lou aql iJUOIU paluaUnap AR\\PUO.J aql
, 'UompUO" S!ql p~llO" ~SB~ld 'qlP!M U!
lOO} vZ u~ql sS~1 S! lU~lUdopA~p ~ql}O l~WO" lSB~qllOU ~qll~ A~M~A!lP ~ql '61
l;)arffiI aOfl'1;)N! S.LN3W.LlIV d30
t
r;o/ L l/r;o
Sl;)qW;}W UI!l;}.L !IV WOl] s;)suods;)lI :J1I.L
- - "
'. 'su~ld ~U!-l;l;lU!~U3 A.I~U!W!PJd ;lqJ JO Z J;l;lqS uo L# ;lJoN ~U!p~J~ ;lJ!S ;l;lS
'Z'd'L UO!P;)S 'p l;)Jd~q;) '110'1
U! p;)y!:l;)ds S~ u~ld ;):a~U!~lO ;)ql UO UO!l~:ly!ll;):l S,l;);)U!:aU;) U~ ;)P!AOld 'S(
. A~M;lA!Jp ;lql q~nOJql ~J!qJ S;lqJU! 9 S! ~1~M;lP!S ;lqJJ~qJ ;lJ~J!PU!
OJ sU~ld ~U!H;lU!~U3 A.I~U!W!I;lJd ;lqJ JO T J;l;lqS OJ p;lpp~ u;l;lq s~q ;lJOU V
'(d UO!P;)S 'II
;){:l!llV '(Z l;)ld~q;) '110'1) SA~M;)APP U!ql!M ){:l!ql S;)q:lU! (9) X!S ;)q Il~qs pU1~
SA~M;)APP Il~ q:anolql snonu!luo:l ;)q Il~qs slol :au!){l~d OllU;):l~fp~ S){l~M;)P!S 'P(
'u~ld uo P;llOU pu~ P;l3p;lIMOIDIJV
'UO!l~WlOjU! P;)l~lS ;)AOq~ ;)ql ql!M Stmld ;)ql OJ
;)lOU ~ pp~ pu~ ;)SUOdS;)l SlU;)WWO:l mOA U! ;):l!lou S!ql ;):aP;)lMOID[:l~ ;)~;)ld
'l;)dol;)MP ;)qljO Almq!SUOdS;)l ;)lOS ;)ql;)q Il~qs pu~ 'q:l~;)H UOlUAOHjO Al!;)
., ;)ql Aq P;)AOldd~ ~ ';)P~l:a l;)ll;)q 10 lU;)l~A!nb;) ;)ql Ol P;):l~ld;)110 p;)l!~d;)l ;)q
Il~qs SUO!l~l;)dO S,lOpRijUO:l ;)ql jO lInS;)l ~ S~ I~P;)l~W lU~Id 10/PU~ W;)lSAS
UO!J~:apl! ;)lll Ol ;):a~W~P AUV 'll:l~;)H UOlUAOH jO Al!;) ;)lll Ol :aU!:aUOl;)q
I~P;)l~W ltmld pU~ UO!l~:a!ll! :aU!lS!X;) ;)A~ll A~Mll:a!H I~l;)P;)d uo SU~!P;)W ;)lll '((
'AI~U!PJOJJ~ P;lS!A;lM
'P;)ll!Wl;)d ;)q lOU II!M
ptm A~M-jO-lll:aP A~Mq:a!H l~l;)P;)d ;)lll U!llJ!M Il~j PtmIS! ;)lll pu~ s:au!ltmld
. ;)S;)ql jO UO!llod V 'A~Mll:a!H l~l;)P;)d JJo ;):lU~llU;) U!~W ;)lll l~ tm!P;)W
l;)lU;):l ;)lll U!lll!M P;)SOdOld ;)l~ S:au!lu~ld l;)llJo pu~ ~l;)j!lAl:l~O X!U;)Olld 'Z(
'p;l~U~qJ pu~ p;l~p;lIMOU~JV
.,' 'P;)llO:l ;)~;)Id 'S;)U!ll;)MOd :aU!JS!X;)
ql!M P!lJUO:l A~W ;)u!l A:j.1;)dOld l~;) ;)lll :auoI~ sWI~d I~AOll P;)SOdOld ;)lll . I (
'S;l!J;lds Hq10u~ OJ p;l~U~q:J pu~ p;l~p;lIMOU~JV
#\ 'S;)!:l;)ds l;)lllOUB ;)In.msqns ;)S~;)Id 'P;)ll!Wl;)d
' .
lOU ;)l~ s;)!:l;)ds sn:l!d 'Z';)'S UO!P;)S 'II ;){:l!llV 'So L l;)ld~ll;) '110'1 ;)llll;)d .O(
'qJnJ ql!M UMOqS ;lJ~ SPU~IS! p;ldRJSPU~IIIV 'p;l3p;lIMOU~JV
('3 UO!P;)S 'II ;){:l!llV 'zz l;)ld~q;)
'\ ptm 'V. S UO!P;)S 'II ;){:l!llV 's' L l;)ld~ll;) '110'1) qm:l P;)S!~l 'snonu!luo:l
~ Aq lU;)wq:l~Ol:lU;) l~In:l!ll;)A WOlj P;)l:l;)JOld ;)q Il~lls ~;).rn p;)d~:lSpu~'1 '6Z
'S-'1J;l;lqS 'S;lJOU I~HU;l~ 01 p;lpp~ S~M S!ql
" '('H'S UO!P;)S 'II ;){:l!llV 'S'L l;)ld~q;) '110'1) lU;)W;)A~d ;)llJ ;)AOq~
.' J;);)J 8 pu~ J;);)JS'Z U;);)MJ;)q I;)MI ~ J~ AJ!I!q!S!A-SS01:l P;)pn.qsqoun U~ ;)q Il~qs
;)l;)ql S;)I:atmPllq:a!S ;)ql U!lll!M l~ql 'u~ld ;)d~:lspu~'1 ;)lll uo ;)JOU Aq ';)l~:l!PUI '8Z
'p;lpp~ S;lI~U~!JJ 'SURld ;ld~JSPU~1 ;l;lS
, .' '. 'A~Mll:a!H ;)!X!O PlO pu~ p.rnMlnoH
.' W~;)llSjlnD 10j S;)I:aU~Pl lll:a!S lOOJ S ( ;)S 0 'A~Mll:a!H l~l;)P;)d :aUOl~
S;)l:atm!ll lq:a!S ;)llllOj 9PS X;)PUI p.rnptmlS lOOd ;):lU;)l;)j;)lI '('R'S uO!l:l;)S
'II ;){:l!llV 'So L l;)ld~ll;) '110'1) SU~Id ;)d~:lsptm'1 ;)ql uo S;)l:au~!ll lq:a!S MOllS 'a
';lIOd Jq3!1 WOJJ wnw!u!w 1ST S! ;l;lJJ U;lM~ JO J;lJU;lJ J~qJ os p;lJ~ds
;lJ~ S;l;lJJ Adou~:J :~U!UU~ld ;ld~JsPU~1 qJ!M P;lJ~U!pJOOJ pu~ p;l~p;lIMOU~JV
" .( q' I'V uO!l:l;)S 'II ;){:l!llV '(Z l;)Jd~q;)
'110'1) ;):l~jlnS :au!){l~d ;)ql uo :aU!MOP~llS ;)llllnj ;)l~U!W!l;) Ol S;)llllxy
lll:a!l OllU;):l~fp~ S;);)ll Adou~:l ;):a.rnI ;)l~:lOl;)llO ;):l~Id;)J Ol A.rnSS;):l;)U ;)q A~W 1I '9(;
l;)3filll 300'1;)N! SlN3WlllVd3([
V
SOl L l/sa
Sl:)qW:)W Uffi:)l IIV WOlJ s:)suods:)lI JlIl
-
, .
",
lJ3fmI
...
'"
"
3001JNI
'l!1U.I;}d JO ;}1U!llU P;}p!AO.ld ;}q II!A\ SUOnUln31u3 A\OO ;}.I!J - P;}~p;}IA\Ompv
'((q)91-9Z uon:>~s '300J) l~lR~~ S! l~Mq:>!qA\
'Sl~lpM.l~pUn ~:>URmSU! Aq P~SOd1U! lU~1U~l!nb~l ~ql 10 '91 uon:>~s
'AI ~P!:j.lV '9 l~ldRqJ '~Ol ~ql U! P~lRlS SR ~mss~ld lRnp!S~l Ts'd OZ ql!M
(SlU~UldopA~p lRnU~P!S~l ~UlOS 'Ul'd'~ OO~) 'Ul'd'~ 00~'1 JO lU~Ul~l!nb~l
~poJ AlD ~ql ~U!lRllSUOUl~p p~l!nb~l ~q Il!M SUOnR[n:>[R:> MO{J ~lkl '1 V
'p;}np;}lA\ompv
,(Z 1-9Z UO!P~S '300J) p~rOld S!ql ~U!Al~S SUl~lSAS l~M~S pUR l~lRM
~ql 10J p~l!nb~l ~q Il!M Sl!UU~d lU~UQlRd~O ql[R~H AlUnOJ q:>R~H Ul[Rd '017
'SUUld IIU UO UA\oqs U;};}q ;}AUq SlU;}Ul;}SU;} Al!lHO
'ARM-JO-slq~p :>Hqnd 10 SlU~Ul~SR~ Al!l!ln U! l~ql!~ 'S~:>!Al~S
AlHnn ql!M ~1~J1~lU! lRql S~~ll Alrn ~AOUl~l Ol AlPoqlnR ~ql s~!l!mn :>Hqnd
S~A!~ l'Sl UO!P~S 'I ~P!:j.lV '~'L l~ldRqJ '~Ol ~ql '~lml1J ~[qR~~S~lOJ ~ql
U! lU~Ul~SR~ ~ql U!ql!M s~!l!mn ~soql PRdUl! lOU Il!M S~q:>UR1q pUR SlOOlluql
OS lU~Ul~SU~ ~ql JO ~P!SlnO P~lUu[d ~q AUUl S~~ll AdouuJ 'SlU~Ul~SR~ AlHnn
U!ql!M p~MOnU s~!:>~ds ~~ll A[UO ~ql ~q Il!M S~~ll Ullud '[U1~U~~ UI 'S~!l!mn
ql!M ~1~J1~lU! AUUl A.I~qqOlqS 10 S~~ll 's~:>uuu~:j.lnddu q:>!qM ~U!UU~l~P
AUUl ~M luql OS (Slrnld l~M~S puu l~luM ~ql su n~M su) Slrnld ~du:>splrnl
puu uUld ~l!S ~ql UO UMOqS ~q nuqs s~uH AlHnn plrn SlU~Ul~SU~ AlHnn nv '6f
900Z '1 HqOpO :;}l;}IOUlOJ UO!pn.llsuoJ
900Z '11!.IdV :IUAo.lddV lUld UO!SS!UlUlOJ AlD
SOOZ '1 .I;}qUl;}AON :IUn!UlqnS lUld / uUld ~U!H;}U!~U3
SOOZ 'z lsn~nv :UO!SS!UlUlOJ .\JD
'~lq!ssod su ~lum:>:>R SR ~q ~su~ld os 'UO!l~ldUlo:> sp~rOld ~ql uodn
p~rOld mOA 10J Al!:>udu:> lU~UllU~ll l~lUM~lSUM plrn l~lUM JO A:>unb~pu ~ql
~U!UU~l~P Ol p~sn ~q Il!M ~UH~Ul!l S!ql 'l~l~Ul l~lUM lSllJ ~ql JO ~U!U~S ~ql
puu 'UO!POllSUO:> JO :J.ffilS ~ql 'UO!lR:>Hddu l!uu~d 10J s~lup ~UOlS~l!Ul ~P!A01d
oSIV 'luA01ddu UO!SS!UlUlOJ Al!J JO ~lUp ~ql ~q Plnoqs ~UH~Ul!l ~ql 10J
~lup ~U!:j.lUlS mo A 'p~r01d p~SOd01d ~ql ~Al~S Ol p~l!nb~l ~q [l!M s~:>!Al~S
l~M~S puu l~lUM U~qM s~lullsnIl! Allu~P luql ~UH~Ul!l u ~P!A01d ~su~ld 'Sf
:SlU~UlUlOJ
S3Il.I'II~il
'P;}~P;}IA\OU}(3V
'uonu:>Hddu l!uu~d UO!PtUlsuo:> JO ~Ul!l ~qllu P~M~!A~l ~q Il!M puu
"SP.lUPUUlS UO!pn.llsuoJ pUU }(ooqpuuH U~!S;}<I ~U!.I;};}U!~U3" ~ql puu
S~U!MU10 p1UplrnlS q:>R~H UOlUAOH JO Al!J ~lqu:>Hddu ~ql ql!M ~:>UUp10:>:>U
U! ~q nRqs Sl!Ul~P UO!pn1lSUO:> ~UP~~U!~U~ nv '~Ul!l S!lH lU Al!l!quld~:>:>u
UO!PtUlSUO:> 10J P~M~!A~l ~q lOU [l!M Sl!ul~P ~l!S puu ~~UU!U10 '~U!AUd 'Lf
'P;}~P;}IA\OU}(3V
'~urmuu~d
JO ~Uln ~ql lU p~l!nb~l ~q [l!M ~ UO!P~S 'AI ~P!:j.lV '9 l~lduqJ '~Ol
~ql ql!M ~:>UUplO:>:>U U! 'Suo!luln:>lu:> ~~UU!UlP ~u!pnpu! 'suu[d ~~UU!U1P nnd '9f
S~N3J\UllV d3<I
~
~O/L l/~O
Sl<lqW<lW Uffi<l.L IlV wOlJ s<lsuods;)~ J~.L
...
',,>
"
l:>3fffil
"',,-
"
'.
3GIYI:>NI
P::ll~OOI U!~W l::ll~M 'U!-Zl ::lql wo.y p::lqsHq~lS::l ::lq lsnw UOnO::lUUOO U!~W
l::ll~M 'U!-8 tm 'uompp~ uI 'A~Mq~!H I~I::lp::ld JO ::lp!S lSB::l ::lql uo P::ll~OOI
U!~W l::ll~M 'U!-8 ~U!lS!X::l ::lql Ol P::lP::lUUOO ::lq lsnw W::llSAS l::ll~M ::lql 'q
'MOUU! pUC AlPcdc;) ~UnS!xa
w.lguO;) Ol uoncw.loJU! uOnClS un ~UnS!xa ap!Ao.ld aSC<lld - pa~paIMOU>pv
'mi!S::lP ::lql U! p::ll~POWWOOO~
::lq lsnw UO!l~lS ::lql Ol SMOlJ ::lmss::lId pu~ Al!Am~ ~UnS!X3 'S::l~u~qo
::ll!S Aq p::lsodw! SlU!RqSUOO ::lql pu~ pU~W::lp p::lpp~ ::lql ::ll~POWWOOO~
Ol S~ os P::lO~Id::l1 IO p::lp~l~dn ::lq lsnw UO!l~lS YH ::ll!S-UO ::lql .~
:sMoIIoJ S~
p::ll!nb::l1 ::lq IHM ::lmpn.qS~IJU! I::lM::lS pu~ l::ll~M ~UnS!X::l ::lql Ol SlU::lW::lAOIdwI '8'17
'pa'OpaIMou>PV
9L'I I = SlU::lUll!WWOO pu~ pU~W::lO
OOW Zl = Al!o~d~o I::lM::lS A.I~l!tmS 'q
OOW t'IZ = SlU::lUll!WWOO pu~ ptmW::lO
OOW LZ = Al!o~d~o l::ll~M ::lIq~lod .~
",
:SMOIIOJ SB ::l1~ SlU::lUll!WWOO
pu~ S::l!l!o~d~o lU::lllnO mo 'I::lM::lS A.I~l!U~S pu~ l::ll~M ::llq~lod IOJ
pill} 000'9f Al::ll~W!xoldd~ JO pU~W::lp p::ll~WnS::l U~ ::lA~q IHM qO!qM 'P::lfOId
S!ql ::lO!Al::lS Ol Al!o~d~o I::lM::lS ptm l::ll~M lU::lPllins s~q Allu::lllno Al!:> ::lql . L '17
'p<l'Op<lIMOU>pV
.~ 1-9Z UO!P::lS '300:> ::lql ql!M ::lOU~pIOOO~ U! 'P::lfOId S!ql ::lO!Al::lS
Ol p::ll!nb::l1 SlU::lW::lAOIdw! I::lM::lS lO/ptm l::ll~M ::lqlIOJ sU~Id ::lql p::lAoIdd~ s~q
lU::lw:j.md::lO S!ql mun p::lnss! ::lq lOU II~qs P::lfOld S!qlIOJ l!uu::ld ~u!PI!nq Y '9'17
'P<loP<lIMOU}PV
. Aou~dnooo JO ::ll~Oy!ll::l:>
::lql ~U!U!~NO Ol ::ll!S!nb::lI::lId ~ S! l::ll::lW l::ll~M lU::lU~uu::ld ~ JO ~u!ll::lS
l~ql ::llON 'l::lS S! l::ll::lW lU::lU~uu::ld lSlg ::lql ::lIOpq lU::luq.Illd::lO S::l!l!Ino Al!:>
::lql Ol U::lA!~ ptm 'p::ll::lldwoo AIItlJ ::lq SW::llSAS ::lqll~ql uompuoo uo 'S::ln!I!ln
I::lM::lS pu~ l::ll~M ::lql JO UO!l~II~lSU! IOJ Al::lInS ::l1!nb::l1 lOU IHM ::lOlliO S!ql .~t
'II<lM HlCMpUnO.l'O C WO.lJ <lq Ol P<lP<l<tX<l S! HlcM UO!lCo!.I.lI
'UOn~~!ll! IOJ
P::lMOII~ ::lq lOU II~qs l::ll~M Al!:> ::lIq~I!~A~ AI!P~::l1 ::l1~ S::lomOS I::lqlo sy 'l::ll~M
::lIqBlod JO UOnBAl::lSUOO ::lql s~l!nb~1 .tT:>'f AOHod tmld ::lA!SU::lq::lIdwo:> ''17'17
'paopal.\\ou>pV
'pu~W::lp P::lP::ldX::lIO '~Z!S l::ll::lW I~ug uodn
p::lS~q P::lU!UU::ll::lP ::lq IHM ::l::lJ S!ql 'lSlg smooo I~MqO!qM 'I~AoIdd~ U~Id
::ll!S JO SA~p (0 U::lMS U!ql!M IO suuoJ uon~OHdd~ lU::lwl,md::lO qlI~::lH ::lql uo
::l111lBmi!S S,lu::lUll.md::lO ::lqlIOJ lS::lnb~1 ~ql uodn I::lql!::l P::lfOld S!qlIOJ P!~d
~q ::l::lJ UOnBAl::lS~1 Al!o~d~o ~ Wql s~l!nb::l1 (3)vf-9Z UO!P~S '300:> ::lql 'fv
'UCld oU!.I<l<lU!oU3 A.lCU!W!P.ld aql uo U,\\oqs <lJC SlUC.lpAH <l.lB
'SltmIpAq
II~ ~U!MOqS Aq 'UO!l!PUOO S!ql Sl~::lW u~Id ::lql l~ql ::llRIlSUOW::lP ::lSB::lld
'lU~lpAq ::llg p::lSOdOld IO ~U!lS!X::l tm JO l::l::lJ OOZ U!ql!M ::lq IHM ~u!PI!nq
qO~::l uo SlU!od lIB lBql s::ll!nb::l1 91 UO!lO::lS 'AI ~IO!llY '9 I::lld~q:> '~O'l ::lql 'ZV
S.LN3WlllV d30
9
~o/ L l/~O
SI:lqW:lW Wll:ll IIV wo.y s:lsuods:l~ J~l
-
'ueld ~upaau!~u3 .ueU!w!la.ld
aql jOZ laaqs uo 1# aloN Alajes aj!'1 pue a.l!.>:l aas - pa~paIMOU)PV
!sdOZ @ wd~ oo~ I WnW!U!Ul B S! MOLJ
lUBJP,(H 'UO!pn.Ilsuo" IB"!:jl~A ,(UB ~JOJ~q ~"!AJ~S U! ~q lIBqs SlUlUp,(q lIV '9!;
'paOpalMompv
S~Ul!l liB
lB P~U!BlU!BUl ~q lIBqs pUnOJB wnl ~I"!q~A ,("U~~J~Ul~ lU~!"YJns ',(UM ~UO J!
.Z I puu ',(UM OM.} J! ~P!M ,OZ JO UlnUl!U!Ul U ~q lIuqs spuo~ 'UO!pn.Ilsuo" JO
lU!od ls~q:jll1J Ol ~lU~ AJlU~ ~ql UlOJJ P~l~IdUlo:) ~q lIuqs SpUOJ ~ql 'S~l"!q~A
,(:)U~~J~Ul~ JOO JO lq~!~M ~ql :jloddns Ol SUOl Z€ Ol UO!pn.Ilsuo:) ~u!lnp
'P~PUdUlO:) ~q lIuqs ,(~ql 'SlU~Ul~J!nb~J lOO l~~Ul lIuqs SpUOJ SS~:):)V .~~
'pa~paIMompv
p~roJd ~quo pu~ ~ql
Ol ~U!UU!~~q ~ql UlO.g ss~:):)u lU~uQ.md~o ~J!d ~AUq lIuqs ~lU~ ~:)UB.IlU~ lIV 'v~
'las 0:) U! papnpu! aq II!M pue paopalMompv
Ul~lS,(S J~IJ[U!Jds
~JY U ~J!nb~J II!M S~!lOlS ~~Jql uBql ~JOUl JO lq~!~q U! .Of s~u!PI!nq lIV 'f~
:SlU~UlUlO:)
3HM
'paopalMompv
'UO!lU:)!Iddu l!Ull~d UO!ptl.Qsuo:) JO ~Ul!l ~qllu P~M~!A~J ~q II!M ,(~ql
:(s~lBpdn ,(uu ~U!pnI:)U!) IunuuUl "sp.lepueJS uO!l3n.lJsuo:) pue JfooqpueH
~ '. U~!S30 ~U!.l33U!~U3 S3!J!l!lil" s.lu~uQ.md~o s~!l!I!lfl ~ql ql!M ~:)UBpJO:):)U
",..-",-
U! ~q lIBqs SI!Ul~P UO!pn.Ilsuo:) AJ!I!ln lIV '~Ul!l S!ql lU AJ!I!quld~:):)u
UO!ptl.Qsuo:) JOJ P~M~!MJ ~q lOU II!M SI!Ul~P UO!ptl.Qsuo:) AJ!I!m 'Z~
'sueJd oupaauplu3 A.leu!Ul!la.ld 3ql jO Z laaqs uo 1# aloN Ilu3ua~ aas
'sUBld p~U!Ulqns ~ql uo ~U!J[:)uI S! lU~Ul~lUlS S!ql 's~!:)u~~u ~lU!ldoJddu
", J~qlO lIB ,(q P~P!AOJd ~q II!M pUB ~IqBI!BAU ~JU s~!l!I!ln luql p~pnl"U!
~q lU~Ul~lBlS U s~J!nb~J (d)f UO!P~S 'AI ~l"!:jlV 'f J~lduq:) '~Ol ~ql 'l~
'suel<l oupaau!Oua leug aql
uo sau!l a.lg pue Sa3!,UaS ~u!Pl!nq aql uo UA\OqS aq II!M SHlUHa.ld ,,"oUJf3eg
\, . LOZ-9Z UO!P~S '300:J ~ql ql!M ~:)UBpJO:):)U
U! ',(uu ~m ~J~ql J! (S)~U!I J~IJ[U!Jds ~JY ~ql pUU 's~u!PI!nq ~ql Ol ~:)!AJ~S
J~WM "!lS~lliOp ~qJ uo p~J!nb~J ~q II!M (s)J~Ju~MJd MOLJJ["Bq ~Ju!JdoJddV 'OS
'dlO se u,"oqs a.le sau!lllV
,. ('~u!I
" J~lUM :JAd U P~LJ~J lllA '1l AI s~dAJ ~u!PI!nq U~~M.}~q ~u!I JOds ~uo) dIG
~q lIuqs s~u!I IIV 'Ul~lS,(s J~lUM SA!;) ~ql uo p~U!Ull~d lOU S! IU!l~lUUl :JAd '6v
'pa~pal,\\OUJf3V
-AJddns "!lS~UlOp puu UO!P~lOJd ~JY ~llmb~pu ~u!lnssu
,(q~J;}ql "PAl8: lS;}J:)U;}S Ol ,(UMq~!H IUJ~P;}d UlO.g dOOl 'U!-8 UB qS!Iquls~
Ol S! U~!S~P ;}ql JO lU;}lU! ~ql 'pmMlnos: lS~J:)B~S UO U!UUl 'U!-ZI ~ql
Ol UO!P~uuo:) U!UUl J~lBM 'U!-8 UB qS!Iquls~ Ol p~J~P!suo:) ~q ,(BUl ~lnOJ
;}lUW;}lIU UB JO ::jlno:J Plf 3S JO AJ!U!"!^ ;}ql U! '~^V qjvf 3S uo S;}lBU!Ull~l
luql ~u!I 'U!-8 ~U!lS!X~ ;}ql Ol 'pmMlnos: lS;}J:)U~S JO ;}P!S lS~M ~ql uo
l:J3fffil 30fll:JNI S.LN3W.LHVd30
L
SOl L I/SO
SJ~qw~W WB~lllV wO.lJ s;}suods;)~ ;)~l
. .......
1st REVIEW COMMENTS
New Site Plan
~\\Lt3ic~
Project name: Heritage Club @ Boynton Beach
File number: NWSP 05-014
Reference: 1 st review plans idtmtified as a New Site Plan with a March 23. 2005
D t dat tam k'
I '1 iJJ:
Planning and Zoning
epartmen es 10 mar mg.
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments:
1. Prior to permit application contact the Public Works Department (561-742- /
6200) regarding the storage and handling of refuse per the CODE, Section 1./
10-26 (a).
Acknowled~ed.
2. Indicate by note that the site dumpster enclosures shall be constructed in l/
accordance with City Standard Drawing G-4.
Acknowled2ed. noted on plan.
3. Only two trash enclosures are depicted to service the retail/office/residential
buildings along Federal Highway. This does not appear to be sufficient to /
serve the expected waste stream. Please justify this decision.
Minimal trash is expected from retail and residential (12 units) in building 2
so the tmsh holding area south of this building is more than adequate. The
trash holding area on the north side of building 1 will primarily serve the
cafe and the residential component/amenity in building 1 (84 units). These
are not dumpster enclosures - .just trash holdin~ areas (concrete pads).
4. Identify if the trash holding areas will be for dumpsters or compactors. If
compactors are to be used the enclosures will need to be enlarged. ~
Additionally the northernmost holding area will not be accessible for a rear-
loading truck to pick up the container due to the proposed traffic flow along
the north property line.
The trash holding areas shown are for containers to be rolled to for pick up.
The compaction system will be used within each building and the trash will
then be taken to the holding areas for pick up. Intended function is with
front-Ioadin~ ~arba~e vehicles at the pads for pick up.
5. There is a vertical conflict between the dumpster (south of Building 2) and
the existing Black Olives east of the enclosure and the Pigeon Plum on the V
west side of the enclosure.
Acknowledged and modified in landscaping plan. The Black Olive will be
trimmed accordin~ly and the Pi~eon Plum will be relocated.
6. There are multiple dead end sections throughout the project that will not be ~
able to be serviced by our automatic pickup Solid Waste Truck. Please
correct these conditions.
All dead ends have been resolved & vehicular traffic throu2h the site is OK.
PUBLIC WORKS - Traffic
Comments:
7. Provide a traffic analysis and notice of concurrency (Traffic Performance ~
Standards Review) from Palm Beach County Traffic Engineering.
Received comments from Palm Beach County Traffic Division. Revised
Concurrencv Statement has been provided.
TRC Responses from All Team Members
05/17/05
2
DEPARTMENTS INCLUDE REJECT
8. Dedicate an additional 40-foot of right-of-way or easements to the City of /
Boynton Beach along the west property line to allow for a total of 70-foot
total width for public purposes.
Additional right-of-way space has been allocated to dedicate more space to
the City's planned revitalization of Dixie Hi2hway; see site plan.
9. Reconstruct Old Dixie Hwy. and Gulfstream Blvd. to provide for curb &
gutter, storm sewer, appropriate left turn lanes, striping and landscaped
parkways adjacent to the proposed development. As part of this design the
developer is asked to consider but not required to build a barrier median on
both side ofthe FECRR/Gulfstream Blvd. crossing with the intent to qualify
this crossing as a Quiet Zone with the Federal Railroad Administration.
Developer will allocate space for the City of Boynton Beach to implement
their plan of revitalization alon2 Dixie Hi2hway; see site plan.
10. On-street parking shall be public parking and may not be counted towards /
internal parking requirements.
Acknowled2ed and is not part of the tabular data on the site plan.
11. Live Oaks proposed along the west property line may conflict with parallel v/
parking.
Westem property line has been redesi2ned, see plan.
12. The proposed diagonal parking adjacent to the main entry off Federal /
Highway will create a traffic hazard for westbound entering vehicles and
vehicles exiting eastbound from the Building Two parking structure. Please
correct.
Acknowled2ed, parkin2 spaces have been removed.
13. Delineate and stripe l2-foot x 35 foot loading zones for the retail buildings; ~
include a pavement message in yellow indicating "No Parking - Loading
Zone" .
The loadin2 zones have been delineated and striped. /'
14. Reference City Standard Drawings "K" Series for striping details. /
See General Note #4 on sheet 2 of the Preliminarv En2ineerin2 Plans.
15. Clearly identifY the location of gates and indicate their accessibility for V
FirelRescue and Solid Waste.
All (lever arm) gates are clearly marked on the plan. Fire/Rescue and Solid
Waste vehicles shall have access to the site throu2h the 2ates at any time.
16. Place "One-Way Only" signs across from the eastbound egress driveways V
onto Federal Highway.
One way si2ns have been added on Federal Hi2hwav.
17. The two-way north-south roadway III the northwest corner of the /'
development is less than 24-foot in width. Please correct this condition.
The roadway delineated along the north boundary is intended as a one way
drive (toward the west) only; see site plan.
18. Accommodate the need to turn around if the gate fails on the one-way north- t/
south roadway or the gate should be designed with battery backup capability
to automatically open the gate in the event of a power failure.
The roadway delineated along the north boundar)' is intended as a one way
drive (toward the west) only; see site plan. No gates are on this roadway.
TRC Responses from All Team Members
05/17/05
3
DEPARTMENTS INCLUDE REJECT
19. The driveway at the northeast comer of the development is less than 24 foot /
in width. Please correct this condition.
The roadway delineated along the north boundary is intended as a one way
drive (toward the west) onlv; see site plan.
20. Delete the two diagonal parking spaces at the southwest of the pool area due /
to safety concerns of backing into a four-way intersection.
The four-way intersection condition has been removed; see site plan.
ENGINEERING DMSION
Comments:
21. Permits required from other permitting agencies such as Florida Department /
of Transportation (FDOT), South Florida Water Management District
(SFWMD), Lake Worth Drainage District (LWDD), Florida Department of
Environmental Protection (FDEP), Palm Beach County Health Department
(PBCHD), Palm Beach County Engineering Department (PBCED), Palm
Beach County Department of Environmental Resource Management
(PBCDERM) and any others, shall be included with the permit request.
Acknowledged - see General Note #7 on sheet 2 of the Preliminary
En2ineerin2 Plans. /'
22. All comments requiring changes and/or corrections to the plans shall be /
reflected on all appropriate sheets.
Acknowled2ed.
23. Please note that changes or revisions to these plans may generate additional
comments. Acceptance of these plans during the TRC process does not ;/'
ensure that additional comments may not be generated by the Commission
and at permit review.
Acknowled2ed. ,
24. Provide written and graphic scales on all sheets. /'
A written and 2raphic scale has been added to all sheets.
25. Show proposed site lighting on the Site and Landscape plans (LDR, Chapter /'
4, Section 7.B.4.) The lighting design shall provide a minimum average
light level of one foot-candle. On the Lighting Plan, specify that the light
poles shall withstand a 140 MPH wind load (LDR, Chapter 23, Article II,
Section A.l.a and Florida Building Code). Provide a note that the fixtures
shall be operated by photo-electrical control and are to remain on until 2:00
a.m. (LDR, Chapter 23, Article II, Section A.1.a.) Include pole wind
loading, and pole details in conformance with the LDR, Chapter 6, Article
IV, Section 11, Chapter 23, Article I, Section 5.B.7 and Chapter 23, Article
II, Section A on the Lighting Plan. Glare which is readily perceptible at any
point at or beyond the property on which the use is located is prohibited
(LDR, Chapter 2, Section 4.N.7). Lighting shall be directed away from any
residential uses (LDR, Chapter 2, Section 4.N.7). Please provide
photometrics as part of your TRC plan submittals.
Site lighting is shown on landscape plans and a separate sheet with site photo
metric calculations is now provided in the set.
TRC Responses from All Team Members
05/17/05
4
DEPARTMENTS INCLUDE REJECT
26. It may be necessary to replace or relocate large canopy trees adjacent to light t/
fIxtures to eliminate future shadowing on the parking surface (LDR,
Chapter 23, Article II, Section A.1.b).
Acknowledged and coordinated with landscape planning; Canopy trees are
spaced so that center of Gwen tree is 15' minimum from 1i2ht pole.
27. Show sight triangles on the Landscape plans (LDR, Chapter 7.5, Article II, ,/
Section 5.H.). Reference FOOT Standard Index 546 for the sight triangles /
along Federal Highway. Use 35 foot sight triangles for Gulfstream
Boulevard and Old Dixie Highway.
See landscape plans, trianl!les added.
28. Indicate, by note on the Landscape Plan, that within the sight triangles there ./
shall be an unobstructed cross-visibility at a level between 2.5feet and 8 feet
above the pavement (LDR, Chapter 7.5, Article II, Section 5.H.).
This was added to 2eneral notes, Sheet L-5.
29. Landscaped areas shall be protected from vehicular encroachment by a ./
continuous, raised curb (LDR, Chapter 7.5, Article II, Section 5.A. and
Chapter 22, Article II, Section E.)
Acknowled2ed. All landscaped islands are shown with curb.
30. Per the LDR, Chapter 7.5, Article II, Section 5.C.2. Ficus species are not V
permitted. Please substitute another species.
Acknowledl!ed and Chanl!ed to another species.
31. The proposed Royal Palms along the east property line may conflict with V
existing power lines. Please correct.
Acknowledl!ed and chanl!ed.
32. Phoenix Dactylifera and other plantings are proposed within the center
median at the main entrance off Federal Highway. A portion of these f-/'r
plantings and the island fall within the Federal Highway right-of-way and
will not be permitted.
Revised accordingly.
33. The medians on Federal Highway have existing irrigation and plant material
belonging to the City of Boynton Beach. Any damage to the irrigation ~
system and/or plant material as a result of the contractor's operations shall
be repaired or replaced to the equivalent or better grade, as approved by the
City of Boynton Beach, and shall be the sole responsibility of the developer.
Please acknowledge this notice in your comments response and add a note
to the plans with the above stated information.
Acknowledl!ed and noted on plan.
34. Sidewalks adjacent to parking lots shall be continuous through all driveways V
and shall be six (6) inches thick within driveways (LDR, Chapter 23, Article
II, Section P).
A note has been added to Sheet 1 of the Preliminary Engineering Plans to
indicate that the sidewalk is 6 inches thick through the driveway.
35. Provide an engineer's certifIcation on the Drainage Plan as specifIed in
LDR, Chapter 4, Section 7.F.2. V
See Site Grading Note #7 on Sheet 2 of the Preliminary Engineering Plans.
TRC Responses from All Team Members
05/17/05
5
DEPARTMENTS
36. Full drainage plans, including drainage calculations, in accordance with the
LDR, Chapter 6, Article IV, Section 5 will be required at the time of
permitting.
Acknowledged.
37. Paving, Drainage and Site details will not be reviewed for construction
acceptability at this time. All engineering construction details shall be in
accordance with the applicable City of Boynton Beach Standard Drawings
and the "Engineering Design Handbook and Construction Standards"
and will be reviewed at the time of construction permit application.
Acknowledged.
UTILITIES
Comments:
38. Please provide a time line that clearly illustrates when water and sewer
services will be required to serve the proposed project. Your starting date
for the time line should be the date of City Commission approval. Also
provide milestone dates for permit application, the start of construction, and
the setting of the ftrst water meter. This time line will be used to determine
the adequacy of water and wastewater treatment capacity for your project
upon the project's completion, so please be as accurate as possible.
City Commission: August 2, 2005
Engineering Plan / Plat Submittal: November 1,2005
City Commission Plat Approval: April!, 2006
Construction Complete: October 1,2006
39. All utility easements and utility lines shall be shown on the Site plan and
Landscape plans (as well as the Water and Sewer Plans) so that we may
determine which appurtenances, trees or shrubbery may interfere with
utilities. In general, palm trees will be the only tree species allowed within
utility easements. Canopy trees may be planted outside of the easement so
that roots and branches will not impact those utilities within the easement in
the foreseeable future. The LDR, Chapter 7.5, Article I, Section 18.1 gives
public utilities the authority to remove any trees that interfere with utility
services, either in utility easements or public rights-of-way.
Utility easements have been shown on all plans.
40. Palm Beach County Health Department permits will be required for the
water and sewer systems serving this project (CODE, Section 26-12).
Acknowledged.
41. Fire flow calculations will be required demonstrating the City Code
requirement of 1,500 g.p.m. (500 g.p.m. some residential developments)
with 20 p.s.i. residual pressure as stated in the LDR, Chapter 6, Article IV,
Section 16, or the requirement imposed by msurance underwriters,
whichever is greater (CODE, Section 26-l6(b)).
Acknowledged - fire flow calculations will be provided at time of permit.
INCLUDE REJECT
./
v
/'
V
[//
v
/
TRC Responses from All Team Members
05/17/05
6
DEPARTMENTS INCLUDE REJECT
42. The LDR, Chapter 6, Article IV, Section 16 requires that all points on each /
building will be within 200 feet of an existing or proposed fIre hydrant. V
Please demonstrate that the plan meets this condition, by showing all
hydrants.
Fire Hydrants are shown on the Preliminary En~ineerinf! Plan.
43. The CODE, Section 26-34(E) requires that a capacity reservation fee be
paid for this project either upon the request for the Department's signature /
on the Health Department application forms or within seven (7) days of site V
plan approval, whichever occurs fIrst. This fee will be determined based
upon final meter size, or expected demand.
Acknowledf!ed.
44. Comprehensive Plan Policy 3.C.3.4. requires the conservation of potable /'
water. As other sources are readily available City water shall not be allowed V
for irrigation.
lrri~ation water is expected to be from a ~roundwater well.
45. This office will not require surety for installation of the water and sewer
utilities, on condition that the systems be fully completed, and given to the
City Utilities Department before the fIrst permanent meter is set. Note that V
setting of a permanent water meter is a prerequisite to obtaining the
Certificate of Occupancy.
Acknowled~ed.
46. A building permit for this project shall not be issued until this Department
has approved the plans for the water and/or sewer improvements required to /
service this project, in accordance with the CODE, Section 26-15.
Acknowledf!ed.
47. The City currently has sufficient water and sewer capacity to service this
project, which will have an estimated demand of approximately 36,000 gpd /
for potable water and sanitary sewer. Our current capacities and V
commitments are as follows:
a. Potable water capacity = 27 MGD
Demand and commitments = 21.4 MGD
b. Sanitary sewer capacity = 12 MGD
Demand and commitments = 11.76
Acknowledf!ed.
48. Improvements to the existing water and sewer infrastructure will be required
as follows:
a. The on-site lift station must be upgraded or replaced so as to
accommodate the added demand and the constraints imposed by site
changes. Existing gravity and pressure flows to the station must be
accommodated in the design.
Acknowledged - please provide existing lift station information to confirm
existing capacit), and inflow.
/
b. The water system must be connected to the existing 8-in. water main
located on the east side of Federal Highway. In addition, an 8-in. water
main connection must be established from the 12-in. water main located
TRC Responses from All Team Members
05/17/05
7
DEPARTMENTS INCLUDE REJECT
on the west side of Seacrest Boulevard, to the existing 8-in. line that
tenninates on SE 34th Ave. in the vicinity of SE 3rd Court; or an alternate
route may be considered to establish an 8-in. water main connection to
the 12-in. main on Seacrest Boulevard. The intent of the design is to
establish an 8-in. loop from Federal Highway to Seacrest Blvd., thereby
assuring adequate fire protection and domestic supply.
Acknowled2ed.
49. PVC material is not pennitted on the City's water system. All lines shall be /
DIP (one spur line between building types IV & VIII reflect a PVC water
line.)
All lines are shown as DIP.
50. Appropriate backflow preventer(s) will be required on the domestic water /
service to the buildings, and the fire sprinkler line(s) if there are any, in
accordance with the CODE, Section 26-207.
Backflow preventers will be shown on the building services and fire lines on
the final en2ineerin2 plans. /
51. The LDR, Chapter 3, Article IV, Section 3(P) requires a statement be t/
included that utilities are available and will be provided by all other
appropriate agencies. This statement is lacking on the submitted plans.
See General Note #1 on sheet 2 of the Preliminary En2ineerin2 Plans.
52. Utility construction details will not be reviewed for construction ~
acceptability at this time. All utility construction details shall be in
accordance with the Utilities Department's "Utilities Engineering Design
Handbook and Construction Standards" manual (including any updates);
they will be reviewed at the time of construction pennit application.
Acknowled2ed.
FIRE
Comments:
53. All buildings 30' in height or more than three stories will require a fire //'
sprinkler system I
Acknowled2ed and will be included in CD set.
54. All entrance gate shall have Fire Department access from the beginning to v-
the end of the project (/
Acknowled2ed.
55. Access roads shall meet DOT requirements. They shall be compacted,
during construction to 32 tons to support the weight of our emergency ~ -
vehicles. The roads shall be completed from the entry gate to furthest point V
of construction. Roads shall be a minimum of 20' wide if two way, and 12'
if one way. Sufficient emergency vehicle turn around shall be maintained at
all times
Acknowled2ed.
56. All hydrants shall be in service before any vertical construction. Hydrant
flow is a minimum 1500 gpm @ 20psi V
Acknowledged - see Fire and Life Safety Note #1 on Sheet 20f the
Preliminary Engineering Plan.
TRC Responses from All Team Members
05/17/05
8
DEPARTMENTS INCLUDE REJECT
57. Final inspections shall be called only after all construction is completed in /
the building or apartment in question.
Acknowled2ed.
58. Site addresses and any buildings under construction shall be visible at all /
times. Numbers shall be a minimum of six inches high with at least a 1 in
width and shall contrast with the building.
Acknowled2ed.
POLICE
Comments: /
59. Show direction of traffic on plans. tlj
Acknowled2ed, see revised site plan.
60. Concern regarding number of gated entries; i.e. police/fIre emergency v'
response.
Acknowled!!ed.
BUILDING DMSION
Comments:
61. Please note that changes or revisions to these plans may generate additional
comments. Acceptance of these plans during the TRC process does not l//
ensure that additional comments may not be generated by the commission
and at permit review.
Acknowled2ed.
62. Indicate within the site data the type of construction of each building as
defmed in 2001 FBC, Chapter 6. v'"
Building 1 shall be construction Type I protected/sprinkled and Building 2 is
type IV protected/sprinkled. Townhouses are Type V unprotected
sprinkled.
63. Indicate within the site data the occupancy type of each building as defmed L//
in 2001 FBC, Chapter 3.
Mixed-use, multi-family buildin~s shall he occupancy type R-2; townhouses
are occupancv type R.
64. The height and area for buildings or structures of the different types of t//
construction shall be governed by the intended use or occupancy of the
building, and shall not exceed the limits set forth in Table 500 of the 2001
FBC.
Acknowled2ed, see site data.
65. Place a note on the elevation view drawings indicating that the exterior wall
openings and exterior wall construction comply with 2001 FBC, Table 600. V
Submit calculations that clearly reflect the percentage of protected and
unprotected wall openings permitted per 2001 FBC, Table 600.
A note will be added to the elevation sheets. However, the distance of all
exterior walls to adjacent buildings/property lines are not cause for concern.
Percentage of openings on elevations will he considered during CD phase.
TRC Responses from All Team Members
05/17/05
9
DEPARTMENTS INCLUDE REJECT
66. Every exterior wall within 15 feet of a property line shall be equipped with /
approved opening protectives per 2001 FBC, Section 705.1.1.2.
Acknowled!!ed and will be included in CD set.
67. Buildings, structures and parts thereof shall be designed to withstand the
minimum wind loads of 140 mph. Wind forces on every building or t/
structure shall be determined by the provisions of ASCE 7, Chapter 6, and
the provisions of 2001 FBC, Section 1606 (Wind Loads). Calculations that
are signed and sealed by a design professional registered in the state of
Florida shall be submitted for review at the time of permit application.
Acknowled!!ed.
68. Every building and structure shall be of sufficient strength to support the /
loads and forces encountered per the 2001 FBC, Section 1601.2.1 and Table
1604.1. Indicate the live load (pst) on the plans for the building design.
Acknowled!!ed; live load will be addressed on structural plans in CD phase.
69. Buildings three-stories or higher shall be equipped with an automatic
sprinkler system per F.S. 553.895. Fire protection plans and hydraulic V
calculations shall be included with the building plans at the time of permit
application.
Acknowled!!ed and will be included in CD set as an NFP A R 13 system.
70. At time of permit review, submit signed and sealed working drawings of the V
proposed construction.
Acknowled!!ed.
71. On the site plan and floor plan, indicate the number of stories that are in /
each building including, where applicable, mezzanines. Indicate the overall
height of each building.
Acknowled!!ed, see site plan.
72. Add to each building that is depicted on the site plan drawing a labeled
symbol that identifies the location of the proposed handicap accessible t//
units. Add to the drawing the calculations that were used to identify the
minimum number of required units. Also, state the code section that is
applicable to the computations. Show and label the same units on the
applicable floor plan drawings. Compliance with regulations specified in the
Fair Housing Act is required (Federal Fair Housing Act Design and
Construction Requirements, Title 24 CFR, Part 100.205).
Accessibility route of travel is depicted on the site plan. All public areas are
built in compliance with the FHA and Florida Buildin!! Code.
73. At the time of permit review, submit details of reinforcement of walls for V
the future installation of grab bars as required by the Federal Fair Housing
Act Title 24 CFR, Part 100.205, Section 3, Requirement #6. All bathrooms
within the covered dwelling unit shall comply.
Acknowled!!ed and will be included as a detail in the CD phase.
74. Add to the drawing the calculations that were used to identify the minimum
number of required handicap accessible parking spaces. V
See site plan for accessible parking calculations. Adequate accessible
parking is provided in both parking garage structures.
TRC Responses from All Team Members
05/17/05
10
DEPARTMENTS
75. Add a labeled symbol to the site plan drawing that represents and delineates
the path of travel for the accessible route that is required between the
accessible units and the recreational amenities that are provided for the
project and other common area elements located at the site. The symbol
shall represent the location of the path of travel, not the location of the
detectable warning or other pavement markings required to be installed
along the path. The location of the accessible path shall not compel the user
to travel in a drive/lane area that is located behind parking vehicles. Identify
on the plan the width of the accessible route. (Note: The minimum width
required by the Code is 44 inches). Add text that would indicate that the
symbol represents the accessible route and the route is designed in
compliance with regulations specified in the Fair Housing Act. Please note
that at time of permit review, the applicant shall provide detailed
documentation on the plans that will verify that the accessible route is in
compliance with the regulations specified m the 2001 FBC. This
documentation shall include, but not be limited to, providing fmish grade
elevations along the path of travel.
Accessibility route of travel is depicted on the site plan. All public areas are
built in compliance with the FHA and Florida Building Code.
76. Identify within the site data the fmish floor elevation (lowest floor elevation)
that is proposed for the building. Verify that the proposed elevation is in
compliance with regulations of the code by adding specifications to the site
data that address the following issues:
a. The design professional-of-record for the project shall add the
following text to the site data. "The proposed fmish floor
elevation _15_. 5'_ NGVD is above the highest 100-year
base flood elevation applicable to the building site, as determined
by the SFWMD's surface water management construction
development regulations."
b. From the FIRM map, identify in the site data the title of the flood
zone that the building is located within. Where applicable,
specify the base flood elevation. If there is no base flood
elevation, indicate that on the plans.
c. Identify the floor elevation that the design professional has
established for the building within the footprint of the building
that is shown on the drawings titled site plan, floor plan and
paving/drainage (civil plans).
See Site Grading Notes on sheet 2 of the Preliminary Engineering Plans.
77. As required by the CBBCO, Part III titled "Land Development
Regulations", submit a site plan that clearly depicts the setback dimensions
from each property line to the leading edge of the buildings. The leading
edge of the buildings begins at the closest point of the overhang or canopy
to the property line. In addition, show the distance between all the buildings
on all sides.
All setbacks are clearly depicted from buildings to property buundal'ies.
INCLUDE REJECT
/
v/
TRC Responses from All Team Members
05/17/05
11
DEPARTMENTS
78. To properly determine the impact fees that will be assessed for the
clubhouse/recreation building, provide the following:
a. Will the clubhouse/recreation building be restricted to the residents of
the entire project only? Yes
b. Will the residents have to cross any major roads or thoroughfares to get to
the clubhouse/recreation building? No
c. Will there be any additional deliveries to the site? No
d. Will there be any additional employees to maintain and provide service to
the site? No
Please have the applicant provide the City with a copy of the letter that will be
sent to the impact fee coordinator. To allow for an efficient permit review, the
applicant should request that the County send the City a copy of their
determination of what impact fees are required for the clubhouse/recreation
building.
Acknowledl?;ed; developer will provide all proper documentation.
79. Add to the floor plan drawing of the clubhouse/recreation building a
breakdown of the floor area. The area breakdown shall specify the total area
of the building, covered area outside, covered area at the entrances, total
floor area dedicated for the clubhouse/recreation building and other uses
located within the building. Specify the total floor area that is air-
conditioned. Label the use of all rooms and floor spaces.
Amenity plan is shown (new sheets added) with all rooms c1earlv depicted.
80. CBBCPP 3.C.3.4 requires the conservation of potable water. City water may
not, therefore, be used for landscape irrigation where other sources are
readily available.
Acknowledged - It is anticipated that the source of in-igation water will be a
groundwater well.
81. A water-use permit :from SFWMD is required for an irrigation system that
utilizes water from a well or body of water as its source. A copy of the
permit shall be submitted at the time of permit application, F. S. 373.216.
Acknowledged
82. If capital facility fees (water and sewer) are paid in advance to the City of
Boynton Beach Utilities Department, the following information shall be
provided at the time of building permit application.
d. The full name of the project as it appears on the Development
Order and the
Commission-approved site plan.
a. If the project is a multi-family project, the building number/s
must be provided. The building numbers must be the same as
noted on the Commission-approved site plans.
b. The number of dwelling units in each building.
c. The number of bedrooms in each dwelling unit.
d. The total amount paid and itemized into how much is for water
and how much is for sewer.
(CBBCO, Chapter 26, Article II, Sections 26-34)
At time of permit review, submit separate surve)'s of each lot, parcel or
tract. For purposes of setting up property and ownership in the City
computer, provide a copy of the recorded deed for each lot, parcel or tract.
The recorded deed shall be submitted at time of permit review.
INCLUDE REJECT
/
/
/
t/
/
TRC Responses from All Team Members
05/17/05
12
DEPARTMENTS INCLUDE REJECT
83. At time of building permit application, submit verification that the City of
Boynton Beach Parks and Recreation Impact Fee requirements have been
satisfied by a paid fee or conveyance of property. The following information
shall be provided: /
a. A legal description of the land.
b. The full name of the project as it appears on the Development
Order and the Commission-approved site plan.
c. If the project is a multi-family project, the building number/s
must be provided. The building numbers must be the same as
noted on the Commission-approved site plans.
d. The number of dwelling units in each building.
e. The total amount being paid.
(CBBCO, Chapter I, Article V, Section 3(0).
84. Add a general note to the site plan that all plans submitted for permitting ~
shall meet the City's codes and the applicable building codes in effect at the
time of permit application.
This note will appear on the site plan.
85. Pursuant to approval by the City Commission and all other outside agencies,
the plans for this project must be submitted to the Building Division for /
review at the time of permit application submittal. The plans must
incorporate all the conditions of approval as listed in the development order
and approved by the City Commission.
Acknowled~ed.
86. The full address of the project shall be submitted with the construction
documents at the time of permit application submittal. If the project is multi- /
family, then all addresses for the particular building type shall be submitted.
The name of the project as it appears on the Development Order must be
noted on the building permit application at the time of application submittal.
Acknowled~ed.
87. Show the proposed site lighting on the site and landscape plans. (LDR, /
Chapter 4, Section 7.B.4) If possible, provide photo metrics as part of your
TRC plan submittals.
See landscape plans Light pole locations are shown on landscape plans as
requested; photometries incorporated into architectural set.
88. The area breakdowns for each unit shall specify the total area ofthe unit, area
of the balcony, total area that is air-conditioned and, where applicable, total v/
area of storage and garage space. If the garage and storage areas are not part
of a specific unit, the area shall be included and identified within the area of
the building. Indicate how many of each type of unit will be on each floor
and within the building.
Acknowledged; all units will be clearlv marked and a unit mix provided.
89. Add to the site data the total area under roof of each residential building. /
Provide tabular area data for each floor of each building. The breakdown
shall include the following areas and each area shall be labeled on the
applicable floor plan drawing:
a. Common area covered walkways;
b. Covered stairways;
c. Common area balconies;
d. Entrance area outside of a unit;
TRC Responses from All Team Members
05/17/05
13
DEPARTMENTS INCLUDE REJECT
e. Storage areas (not part of a unit);
f. Garages (not part of a unit);
g. Elevator room;
h. Electrical room;
1. Mechanical room;
J. Trash room;
k. Mailbox pickup and delivery area; and
I. Any other area under roof.
(Chapter 4 - Site Plan Review, Section 7.E.2 and 3)
Shown on plan in site data (8 kiosk's located for townhouses).
90. Van accessible parking spaces are required in the parking garages per the /
2001 FBC, Section 11-4.1.2(5)(b).
Acknowledj;!ed and shown on the site plan.
91. Sheet SP-l - Indicate the number of handicapped parking spaces for the retail
area and the residences and the total number of handicapped spaces /
provided.
All accessible parkinj;! is calculated and specified on SP-l.
92. Submit a floor plan for the retail, amenity, office, live/work, office/retail /
areas.
Amenity area is the only known plan at this time. All other space TBD. ~
93. The elevator shall comply with the 2001 FBC, Section 11-4.1 0.1. t/
Acknowledj;!ed. ./
94. Note: If all of the living units are multistory dwelling units (if all the living /'
space is not on one floor) then these units are not covered by the Florida
Fair Housing Act, the 2001 FBC, Chapter 11 shall apply.
No multi-family units are multi-story. Townhomes are all three story.
PARKS AND RECREATION
Comments:
95. Impact Fee: 1/
70 single family attached units @ $771.00 each = $53,970
96 multi family units @ $656 each = $62,976
TOTAL $ 116,946
Impact fee is due prior to the issuance ofthe first applicable permit.
96. Irrigation coverage needs to be 110% /
Irrigation note added to general notes on Sheet L-5.
97. Indicate the site triangles at the entrances and exits and assure that /
landscaping does not block the line of site.
Site triangles added.
98. Mark the sodded areas. V
Sod areas la be led "sod".
TRC Responses from All Team Members
05/17/05
14
DEPARTMENTS INCLUDE REJECT
FORESTER/ENVIRONMENTALIST
Comments:
99. Tree Removal Plan-Sheet T-l
The Landscape Architect should tabulate the total number of existing trees on the /
site. The plan should indicate where the relocated trees are to be installed
throughout the site. The total diameter inches of trees removed should be shown
as replacement trees on the site landscape plan. These replacement trees should
be shown by a separate symbol on the landscape plan sheet L-5. [Environmental
Regulations, Chapter 7.5, Article I Sec. 7.D.p. 2.]
See Sheet L-5 and T - I.
100. Landscape Plan Sheet L-S
All shade and palm trees on the Plant list must be listed in the specifications /
asa minimum of3" diameter at DBH (4.5' off the ground), 12'-14'
height, and Florida # 1. The height of the trees will be larger than 12' -14' to
meet the 3" diameter requirement. [Environmental Regulations, Chapter
7.5, Article II Sec. 5.C. 2.]
Chan2;e plant list to 3" DBH-14'+6' ht.
101. The details section for the Tree Planting Detail should include a line /
indicating where the height of the tree and the diameter @ DBH (4.5' off
the ground) will be measured at time of planting and inspection.
See Sheet L-5.
102. The details section for the Palm Planting Detail should include a line /
indicating where the height of the palm, gray wood (GW) and the clear
trunk (C.T.) will be measured at time of planting and inspection
See Sheet L-5.
103. The details section for the Shrub and Groundcover Planting Detail should /
include a line indicating where the height, spread and spacing of the plant
will be measured at time planting and inspection
See Sheet L-5.
104. The applicant should add a note indicating that all utility boxes or structures /
(not currently known or shown on the plan) should be screened with Coco
plum hedge plants on three sides
A2;reed, note added to 2eneral notes on Sheet L-5.
105. The landscape buffer detail should be shown to scale (height and canopy t/
spread) at time of planting and include the height scale of the buildings
See section L-6.
106. Irri2ation Plan-No Irri2ation plan included in the submittal /
The irrigation system design (not included in the plans) should be low
volume water conservation using non-portable water.
Note added on 2eneral notes and Sheet L-5.
107. Turf and landscape (bedding plants) areas should be designed on separate /
zones and time duration for water conservation.
Will he done at time irrigation plans are submitted.
TRC Responses from All Team Members
05/17/05
15
DEPARTMENTS
108. Trees should have separate irrigation bubblers to provide water directly to
the root ball. [Environmental Regulations, Chapter 7.5, Article II Sec. 5.
C.2.]
Noted, and will be added to irrioation lans.
PLANNING AND ZONING
ents:
ubmit a traffic' pact analysis prior to Technical Revl w Committee
meeting. The analysis must be approved by the Palm Beach County Traffic
Division for concurrency purposes (Chapter 4. Section 8.F.). The proposed
uses and intensities on the traffic study must be consistent with the proposed
uses and intensities itemized on the site plan (sheet SP-l).
Received comments from Palm Beach County Traffic Division. Revised
Concurrencv Statement has beed rovided.
~
According to Chapter 2.5, Section 8.D., areas designated for commercial
activities shall not generally front on exterior or perimeter streets, and shall
be preferably centrally located within the project. The proposed plan would
be in conflict with the aforementioned code. Therefore, an amendment to
the code would be required to allow the project as it is proposed.
ow led ed.
The maximum building height in the PUD zoning district is 45 feet. Either
reduce the building height of Building 1 to comply with code or formally
request a height exception pursuant to Chapter 2, Section 4.F.3 of the Land
Development Regulations.
cknowled ed, a formal waiver will be submitted b the develo er.
The site plan should indicate proposed fences and walls, including their
dimensions, setbacks, material, and color(s) pursuant to Chapter 4, Section
7.B.3. Provide a detail of any walls or fences, including their dimensions,
exterior fmish, and color(s) (Chapter 4, Section 7.D.).
locations and details rovided. t) iL -1'\C-~"S
Will an on-site lift-station be required as a result 0 this development? If so,
show its location on the site plan (sheet SP-l).
An on-site lift station will not be required. There is an existing lift station
t . e the ro' ect boundaries at the NE corner of the site.
Abandonment and rededication of easements must be recorded prior to
issuance of a building permit for the project.
ow led ed.
The dimensions of the roadway (pavement), drive aisles, back-up areas, and
rights-of-way are subject to the Engineering Division of Public Works'
review and approval.
Acknowled ed.
INCLUDE
v
t/
/'
~
/
/
TRC Responses from All Team Members
05/17/05
16
DEPARTMENTS
INCLUDE REJECT
e site plan tabular data (sheet SP-l) should accurately indicate the number of required parking
spaces. The required parking projects is as follows:
Proposed Use
Required Parking
36
124
160
10
48
21
35
434
24 One-bedroom units
Use
Provided
Parkin
140
50
21
229
440
Parking spaces required in this ordinance for one use or structure may be allocated in part or in whole for the
required parking spaces of another use or structure if quantitative evidence is provided showing that
parking demand for the different uses or structures would occur on different days of the week or at
different hours. Quantitative evidence shall include estimates for peak hour / peak season demand based
on statistical data furnished by the Urban Land Institute or an equivalent traffic engineering or land
planning and design organization (Chapter 2, Section 11.H.13.). Submit a shared parking analysis prior
to the Technical Review Committee meeting.
f
Please explain the use for the room indicated as "amenity" on the ground
floor plan (sheet A-I) and second floor plan (sheet A-2) of Building 1. Will
it be a gym or racquetball courts?
Amenity space is only on the ground floor of building 1 and is intended as a
building lobby, lounge, mail room, club room and exercise room adjacent to
the common 001 and outdoor atio area.
118. Is an amenity room proposed for Building 27 Is the garage open to below?
Staff recommends creating a recreation deck on the roof of the garage of
building 2 (sheet A-6). VO
Amenity space in building 1 is for all residents. Note that building 2 only
has 12 total units so any recreational s ace there would be excessive.
~ On the site plan (sheet SP-l), graphically show the building setback
proposed along the south property line.
Acknowledged and depicted on site plan along the south property line.
~
/
TRC Responses from All Team Members
05/17/05
17
DEPARTMENTS
On the site plan (sheet SP-l), indicate the number of stories for Building 1
and Building 2.
owled ed and shown on the site Ian.
Are fee-simple townhouses proposed for this project? If so, on the site plan
\
(sheet SP-I), show the extent of their lot lines.
e . ot lines will be de icted on lat. B \
. Indicate the proposed floor area (expressed in square feet) tl r the retail area
as shown on second floor plan (sheet A-5).
No actual retail area is intended for the second floor of either buildin~.
er, the s ace is shown as "double hei ht" in most areas.
Staff recommends decreasing the building setback along the east property
line (along Federal Highway) so that buildings would be placed no further
than 10 feet from the property line. The lO-foot front setback of 10 feet
may contain public plazas and landscape material.
There is an existing 20 foot utility easement along the east property line that
contains an existing gravit), sewer line and water main that are proposed to
re 'in.
'*. Provide a detail of the security gates, including dimensions, material, and
color.
ck ' \vIed ed and de icted as art of the CD hase for Citv's a roval.
Label the clubhouse on the floor plan (sheet A-I) of Building 1.
'led ed and labeled.
Label the types of rooms (i.e. bedroom, living room) on all three floors of
the townhouses for Building III and Building VII (sheet A-14).
ow led ed and labeled.
Provide a west elevation for Building 2 (Chapter 4, Section 7.D.).
e 'ations.
Provide rear and side elevations of Townhouse Building V (sheet A-21).
evations.
All elevation pages shall indicate the exterior finishes, roof material, paint
manufacturer's name, and color codes. Staff recommends using a color
schedule (Chapter 4, Section 7.D.). Also, provide color swatches and
awning samples.
, e e'ations and color boards.
Include a color rendering of all elevations at the Technical Review
Committee meeting (Chapter 4, Section 7.D.).
owled ed and included for meetin . Colored site Ian rovided.
The removal/relocation of landscape material is subject to review and
approval of the City Forester / Environmentalist. The City Forester /
Environmentalist will determine the fate of the existing Black Olive trees
located near the Aphrodites out-parcel.
determined.
On the landscape plan, ensure that the plant quantities must match between
the tabular data and the graphic illustration. The landscape plan shall
provide total plant material quantities for the following categories: Shade
trees, palm trees, Shrubs / Groundcover.
See plant list/ tahular data.
INCLUDE
/'
REJECT
t/
t/
/
/
v'
V'
/
~
/
t/'"
/
TRC Responses from All Team Members
05/17/05
18
T$
INCLUDE REJECT
Fifty percent (50%) of all site landscape materials must be native species
(Chapter 7.5, Article II, Section 5.P). Please categorize as follows: Shade
trees, Palm trees, Shrubs & Groundcover.
vided. t . .
134. A sign re tree (such as a e low Elder, Ti u ina Granulsola, or
Bouganvillea) is required at both sides of the project entrances (along U.S. 1
and Old Dixie Highway). The signature trees must have eight (8) feet of
clear trunk if placed within the safe-sight triangle (Chapter 7.5, Article 2,
Section 5.N.). Alternative plant material may be substituted if the above
referenced plant material is not available or undesired. Any substitution of
plant material (for the signature tree requirement) will be subject to the City
Forester / Environmentalist review and approval.
ro," . ded.
13 5 All trees, if proposed as trees, must be at least 12 feet in height and three (3)
caliper inches at the time of their installation (Chapter 7.5, Article II,
Section 5.C.2.).
'ded.
All shrubs and hedges are required to be at minimum 24 inches in height,
24 inches in spread, and planted with tip-to-tip spacing measured
immediately after planting to adequately cover the planted areas on the site
(Chapter 7.5, Article II, Section 5.C.4.).
lant s ecifications.
The palm trees proposed around the townhouse buildings must be installed
at !h the building height of the building (Chapter 7.5, Article II, Section
5.M.).
in'mum hei ht 18' OA.
. All freestanding monument signs shall have colorful groundcover installed
at the base (Chapter 7.5, Article II, Section 5.0).
rov' ed.
. What will be the dimensions of the interior and terminal landscape islands?
r 'ided on site Ian. Minimum width of islands is 10'.
All proposed wall signage is subject to the Community Redevelopment
Agency Board and City Commission review and approval. Staff
recommends that you submit a master sign program that shows the number,
location, dimensions, exterior finish, and color(s) of all signs (Chapter 2,
Section 5.H.9.). The sign program would address all types of signs,
including commercial wall signs, identification signs, residential subdivision
signs, freestanding monument signs, canopy signs, way-finding signs,
directional signs, and all other signs as regulated by Chapter 21 of the Land
Development Regulations. 1l "~ V /
owledued - see site Ian for siuna e criteria. €() y
~
~
1/
~
v
~
7
All signage is subject to review and approval of the Community
Redevelopment Agency Board and City Commission. Provide a detail of
any proposed outdoor freestanding monument signs and indicate their
setback from the property line (minimum 10 feet), and include the sign area,
dimensions, exterior fmish, and letter color(s) (Chapter 4, Section 7.D.).
Acknowledued - see site Ian for siuna e criteria.
TRC Responses from All Team Members
05/17/05
19
DEPARTMENTS INCLUDE REJECT
\ '
iM:Provide a d~tail of a typic.al outdoor fre~s~ding lighting fixture: The detail
(,~ of the typIcal freestandmg outdoor hghtmg fixture should mclude the
overall height, exterior finish, materials used (i.e. concrete or aluminum)
and color(s). The lighting fixture height, style, design, and illumination
level shall be compatible with the building design and height and shall
consider safety, function, and aesthetic value (Chapter 9, Section 1O.F.1.).
The height of the lighting fixtures should be the same throughout the entire
commercial/mixed-use areas. If
nowled ed and included on hotometric sheet. V
3. Lighting shall not be of an intensity that produces glare on adjacent property ./
(Chapter 9, Section 10.F.2.). V"
c now led ed.
144 Feature lighting emphasizing plants, trees, barriers, entrances, and exits is
encouraged (Chapter 9, Section 10.F.3.). V
Acknowledged and will be incorporated into the project as it develops. See
e 'minan' Ii htin Ian included, see Sheet L- 7.
Lighting may be used to illuminate a building and its grounds for safety
purposes and to enhance its beauty. However, the visual effect shall be /
subtle (Chapter 9, Section 10.F.4.). Please submit a photometric plan so V
that staff can review the photometric levels (footcandles).
wled ed and included.
Lighting shall not be used as a form of advertising in a manner that draws
more attention to the building or grounds at night than in the day (Chapter V
9, Section lO.F.5.).
owledaed.
Sculptures, fountains, gardens, pools, trellises an benches shall be
encouraged within the site design (Chapter 9, Section 10.H.). Provide /"
details of said amenities.
led ed and added. See lans and details on Sheet L-6.
clude covered bike racks at intermittent locations throughout the /
commercial/public spaces. Also, more attention and detail should made
for a possible location of a...!Es stop since th!s locat~~ is off of Palm Tran
Route 1. -- S ~,~ 1 ~ U\t\ ;Jr2 fJ'j.tJJIL '
c nowled ed and rovided. See site Ian. ,
Staff recommends re-orienting the building proposed along Old Dixie
Highway so that the front doors face Old Dixie Highway rather than the
garage doors face Old Dixie Highway. This would help to perpetuate "new ~
urbanism" principles, in part, by placing importance on the public spaces
(Le. front doors facing the street) while reducing the amount of impervious
surface (Le. no need for two driveways to one purpose).
'led ed and modified, see revised site Ian.
Staff recommends installing the Royal Palms (proposed along Federal ./'
Highway) at halfthe height of the adjacent mixed-use buildings.
25' verall, 18' revwood rovided.
1. Indicate the location of the mailbox kiosk(s) within the townhouse area.
'osks located.
DEPARTMENTS INCLUDE
152. Rooftops will be treated as part of the building elevation. All rooftop
equipment must be completely screened from view at a minimum
distance of 600 feet.
now led ed.
53 Additional architectural detail is needed on the parking structure
elevations, in order to be compliant with the eRA design guidelines r/
kn wled ed; arkin ara e will be further develo ed for the CD set.
. Indicate the planting of St. Augustine sod in the swale areas with
appropriate irrigation.
A reed.
155. Staff'suggests that ingress, as well the egress indicated, be provided from
Old Dixie Highway.
Onlv access to Dixie Hi hwa will be as an exit from the north access road.
156. Will the existing hedge around the southernmost wellhead be retained? If
not, it should ~e, at a minimum, landscaped to ~e extent of ~he one on Ute
west property hne. rIVe IM&tR VV\ t? . ~. ') ~J~'
Yes. /W"'
157. No landscape is depicted on the Landscape Plan around the lift s tion at the
north property line. It should be heavily landscaped due to its visibility from
Federal Highway. 1o/1A'J S 1-
ca e rovided. lCVY'otl~c ~ "V vv"YV\. VI.,. .
planting scheme involving taller shrub material than the proposed 24 inch
high hedge should be selected for the north property line. Possibly a tiered V'
landscape approach of different si~~materials may be more appropriate.
A reed, see landsca e lans. Lf I 'Vl" .{1--"Y/
159. A full-size clubhouse/recreation building should be provided at the pool for
the townhouses.
A structure has been desi ned to house bathrooms and a atherin area.
160. The recreation space is not adequate around the pool for the townhouses. A
green, outdoor, play space should be provided to give the residents a park
setting for outdoor activities, since there is not a park in the immediate
vicinity. Staff suggests the elimination of the streets surrounding the pool
area and their conversion to park/green space, since the remainder of the
circulation pattern appears adequate,
Several "~reen" spaces have been added on adjacent blocks. Although
vehicular circulation still exists, the amount of asphalt has been si~nificantly
reduced. Eliminated road north pool, provided narrowel' mad south of
001. Please see the u dated site Ian.
TRC Responses from All Team Members
05/17/05
20
~
2
REJECT
z/
By f l?- I b7/-- ]I
- ~tVltj~ SP--l
l .
- ~ I~ y II
- ~ tsc
- r~ ukp~
.,.- W eCtf ~ (wof7~
- ?; Y""2- 'f: t I co ~ M.7lj
rJ,
~ f(~~Ms ~ ~1 j~fl(g
5t1~( JJJt ~ ltA Iff ~ b;lte f<<-& v
I v.. l~<;
* cASt ~ ~ irJr7~ ~
<)~-I ~5}J(f ~ ~ ~
1st REVIEW COMMENTS
New Site Plan
Project name: Heritage Club @ Boynton Beach
File number: NWSP 05-014
Reference: 1 st review plans identified as a New Site Plan with a March 23. 2005 Planning: and Zoning
da k'
Department te stamo mar mil,
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments:
1. Prior to permit application contact the Public Works Department (561-742-
6200) regarding the storage and handling of refuse per the CODE, Section
10-26 (a).
Acknowledged.
2. Indicate by note that the site dumpster enclosures shall be constructed in
accordance with City Standard Drawing G-4.
Acknowledged, noted on plan.
3. Only two trash enclosures are depicted to service the retaiVoffice/residential
buildings along Federal Highway. This does not appear to be sufficient to
serve the expected waste stream. Please justify this decision.
Minimal trash is expected from retail and residential (12 units) in building 2
so the trash holding area south of this building is more than adequate. The
trash holding area on the north side of building 1 will primarily serve the
cafe and the residential component/amenity in building 1 (84 units). These
are not dumpster enclosures - just tI'ash holding areas (concrete pads).
4, Identify if the trash holding areas will be for dumpsters or compactors, If
compactors are to be used the enclosures will need to be enlarged.
Additionally the northernmost holding area will not be accessible for a rear-
loading truck to pick up the container due to the proposed traffic flow along
the north property line.
The trash holding areas shown are for containers to be rolled to fOl' pick up.
The compaction system will be used within each building and the trash will
then be taken to the holding areas for pick up. Intended function is with
front-loading garbage vehicles at the pads for pick up.
5. There is a vertical conflict between the dumpster (south of Building 2) and
the existing Black Olives east of the enclosure and the Pigeon Plum on the
west side of the enclosure.
Acknowledged and modified in landscaping plan, The Black Olive will be
tl'immed accordinglv and the Pigeon Plum will be relocated.
6. There are multiple dead end sections throughout the project that will not be
able to be serviced by our automatic pickup Solid Waste Truck. Please
correct these conditions.
All dead ends have been resolved & vehicular traffic through the site is OK.
PUBLIC WORKS - Traffic
Comments:
7. Provide a traffic analysis and notice of concurrency (Traffic Performance
Standards Review) from Palm Beach County Traffic Engineering.
Received comments from Palm Beach County Traffic Division. Revised
Concurrency Statement has been provided.
TRC Responses from All Team Members
05/17/05
2
DEPARTMENTS INCLUDE REJECT
8. Dedicate an additional 40-foot of right-of-way or easements to the City of
Boynton Beach along the west property line to allow for a total of 70-foot
total width for public purposes.
Additional right-of-way space has been allocated to dedicate more space to
the City's planned I'evitalization of Dixie Hi2hway; see site plan.
9. Reconstruct Old Dixie Hwy. and Gulfstream Blvd. to provide for curb &
gutter, storm sewer, appropriate left turn lanes, striping and landscaped
parkways adjacent to the proposed development. As part of this design the
developer is asked to consider but not required to build a barrier median on
both side of the FECRR/Gulfstream Blvd. crossing with the intent to qualify
this crossing as a Quiet Zone with the Federal Railroad Administration.
Developer will allocate space for the City of Boynton Beach to implement
their plan of revitalization alon2 Dixie Highway; see site plan.
10. On-street parking shall be public parking and may not be counted towards
internal parking requirements,
Acknowled2ed and is not part of the tabular data on the site plan.
11. Live Oaks proposed along the west property line may conflict with parallel
parking.
Western property line has been redesi!!ned, see plan.
12. The proposed diagonal parking adjacent to the main entry off Federal
Highway will create a traffic hazard for westbound entering vehicles and
vehicles exiting eastbound from the Building Two parking structure. Please
correct.
Acknowled!!ed, parkin!! spaces have been removed.
13. Delineate and stripe 12-foot x 35 foot loading zones for the retail buildings;
include a pavement message in yellow indicating "No Parking - Loading
Zone".
The load in!! zones have been delineated and striped.
14. Reference City Standard Drawings "K" Series for striping details.
See General Note #4 on sheet 2 of the Preliminary En2ineerin!! Plans.
15. Clearly identify the location of gates and indicate their accessibility for
Fire/Rescue and Solid Waste.
All (level' arm) gates are cleal'ly marked on the plan. Fire/Rescue and Solid
Waste vehicles shall have access to the site thl'ou2h the 2ates at anv time.
16. Place "One-Way Only" signs across from the eastbound egress driveways
onto Federal Highway.
One way si!!ns have been added on Federal Hi2hway.
17. The two-way north-south roadway in the northwest comer of the
development is less than 24-foot in width. Please correct this condition.
The roadway delineated along the north boundary is intended as a one way
drive (toward the west) only; see site plan.
18. Accommodate the need to turn around if the gate fails on the one-way north-
south roadway or the gate should be designed with battery backup capability
to automatically open the gate in the event of a power failure,
The l'Oad\\ay delineated along the north boundary is intended as a one way
drive (toward the west) only; see site plan. No gates are on this roadway.
TRC Responses from All Team Members
05/17/05
3
DEPARTMENTS INCLUDE REJECT
19. The driveway at the northeast comer of the development is less than 24 foot
in width. Please correct this condition.
The roadway delineated along the north boundary is intended as a one way
drive (toward the west) only; see site plan.
20. Delete the two diagonal parking spaces at the southwest of the pool area due
to safety concerns of backing into a four-way intersection.
The four-wav intersection condition has been removed; see site plan.
ENGINEERING DIVISION
Comments:
21. Permits required from other permitting agencies such as Florida Department
of Transportation (FDOT), South Florida Water Management District
(SFWMD), Lake Worth Drainage District (LWDD), Florida Department of
Environmental Protection (FDEP), Palm Beach County Health Department
(PBCHD), Palm Beach County Engineering Department (PBCED), Palm
Beach County Department of Environmental Resource Management
(PBCDERM) and any others, shall be included with the permit request.
Acknowledged - see General Note #7 on sheet 2 of the Preliminary
Engineering Plans.
22. All comments requiring changes and/or corrections to the plans shall be
reflected on all appropriate sheets.
Acknowledl!ed.
23. Please note that changes or revisions to these plans may generate additional
comments. Acceptance of these plans during the TRC process does not
ensure that additional comments may not be generated by the Commission
and at permit review.
Acknowledged.
24. Provide written and graphic scales on all sheets.
A written and l.!:raphic scale has been added to all sheets.
25. Show proposed site lighting on the Site and Landscape plans (LDR, Chapter
4, Section 7.Bo4.) The lighting design shall provide a minimum average
light level of one foot-candle. On the Lighting Plan, specify that the light
poles shall withstand a 140 MPH wind load (LDR, Chapter 23, Article II,
Section A.I.a and Florida Building Code). Provide a note that the fixtures
shall be operated by photo-electrical control and are to remain on until 2:00
a.m. (LDR, Chapter 23, Article II, Section A.1.a.) Include pole wind
loading, and pole details in conformance with the LDR, Chapter 6, Article
IV, Section 11, Chapter 23, Article I, Section 5.B.7 and Chapter 23, Article
II, Section A on the Lighting Plan. Glare which is readily perceptible at any
point at or beyond the property on which the use is located is prohibited
(LDR, Chapter 2, Section 4.N.7). Lighting shall be directed away from any
residential uses (LDR, Chapter 2, Section 4.N.7). Please provide
photometrics as part of your TRC plan submittals.
Site lighting is shown on landscape plans and a separate sheet with site photo
metric calculations is now provided in the set.
TRC Responses from All Team Members
05/17/05
4
DEPARTMENTS INCLUDE REJECT
26. It may be necessary to replace or relocate large canopy trees adjacent to light
fixtures to eliminate future shadowing on the parking surface (LDR,
Chapter 23, Article II, Section A.l.b).
Acknowledged and coordinated with landscape planning; Canopy trees are
soaced so that center of Gwen tree is 15' minimum from Iil!ht oole.
27. Show sight triangles on the Landscape plans (LDR, Chapter 7.5, Article II,
Section 5.H.). Reference FDOT Standard Index 546 for the sight triangles
along Federal Highway. Use 35 foot sight triangles for Gulfstream
Boulevard and Old Dixie Highway.
See landscape plans, trianl!les added.
28. Indicate, by note on the Landscape Plan, that within the sight triangles there
shall be an unobstructed cross-visibility at a level between 2.5feet and 8 feet
above the pavement (LDR, Chapter 7.5, Article II, Section 5.H.).
This was added to general notes, Sheet L-5.
29. Landscaped areas shall be protected from vehicular encroachment by a
continuous, raised curb (LDR, Chapter 7.5, Article II, Section 5.A. and
Chapter 22, Article II, Section E.)
Acknowled!!ed. All landscaped islands are shown with curb.
30. Per the LDR, Chapter 7.5, Article II, Section 5.C.2. Ficus species are not
permitted. Please substitute another species.
Acknowledl!ed and Chanl!ed to another species.
31. The proposed Royal Palms along the east property line may conflict with
existing power lines. Please correct.
Acknowledl!ed and chanl!ed.
32. Phoenix Dactylifera and other plantings are proposed within the center
median at the main entrance off Federal Highway. A portion of these
plantings and the island fall within the Federal Highway right-of-way and
will not be permitted.
Revised accordingly.
33. The medians on Federal Highway have existing irrigation and plant material
belonging to the City of Boynton Beach. Any damage to the irrigation
system and/or plant material as a result of the contractor's operations shall
be repaired or replaced to the equivalent or better grade, as approved by the
City of Boynton Beach, and shall be the sole responsibility of the developer.
Please acknowledge this notice in your comments response and add a note
to the plans with the above stated information.
Acknowledl!ed and noted on olan.
34. Sidewalks adjacent to parking lots shall be continuous through all driveways
and shall be six (6) inches thick within driveways (LDR, Chapter 23, Article
II, Section P).
A note has been added to Sheet I of the Preliminary Engineering Plans to
indicate that the sidewalk is 6 inches thick throul!h the driveway.
35. Provide an engineer's certification on the Drainage Plan as specified in
LDR, Chapter 4, Section 7.F.2.
See Site Grading Note #7 on Sheet 2 of the Preliminary Engineering Plans.
TRC Responses from All Team Members
05/17/05
5
DEPARTMENTS
36. Full drainage plans, including drainage calculations, in accordance with the
LDR, Chapter 6, Article IV, Section 5 will be required at the time of
permitting.
Acknowledged.
37. Paving, Drainage and Site details will not be reviewed for construction
acceptability at this time. All engineering construction details shall be in
accordance with the applicable City of Boynton Beach Standard Drawings
and the "Engineering Design Handbook and Construction Standards"
and will be reviewed at the time of construction permit application.
Acknowledged.
UTILITIES
Comments:
38. Please provide a time line that clearly illustrates when water and sewer
services will be required to serve the proposed project. Your starting date
for the time line should be the date of City Commission approval. Also
provide milestone dates for permit application, the start of construction, and
the setting of the fIrst water meter. This timeline will be used to determine
the adequacy of water and wastewater treatment capacity for your project
upon the project's completion, so please be as accurate as possible.
City Commission: August 2,2005
Engineering Plan 1 Plat Submittal: November 1,2005
City Commission Plat Approval: April 1, 2006
Construction Complete: October' 1,2006
39. All utility easements and utility lines shall be shown on the Site plan and
Landscape plans (as well as the Water and Sewer Plans) so that we may
determine which appurtenances, trees or shrubbery may interfere with
utilities. In general, palm trees will be the only tree species allowed within
utility easements. Canopy trees may be planted outside of the easement so
that roots and branches will not impact those utilities within the easement in
the foreseeable future. The LDR, Chapter 7.5, Article I, Section 18.1 gives
public utilities the authority to remove any trees that interfere with utility
services, either in utility easements or public rights-of-way.
Utility easements have been shown on all plans.
40. Palm Beach County Health Department permits will be required for the
water and sewer systems serving this project (CODE, Section 26-12).
Acknowledged.
41. Fire flow calculations will be required demonstrating the City Code
requirement of 1,500 g.p.m. (500 g.p.m. some residential developments)
with 20 p.s.i. residual pressure as stated in the LDR, Chapter 6, Article IV,
Section 16, or the requirement imposed by insurance underwriters,
whichever is greater (CODE, Section 26-l6(b)).
Acknowledged - fire flow calculations will be provided at time of permit.
INCLUDE REJECT
TRC Responses from All Team Members
05/17/05
6
DEPARTMENTS
42. The LDR, Chapter 6, Article IV, Section 16 requires that all points on each
building will be within 200 feet of an existing or proposed fIre hydrant.
Please demonstrate that the plan meets this condition, by showing all
hydrants.
Fire Hydrants are shown on the Preliminary Enj!ineerin2: Plan.
43. The CODE, Section 26-34(E) requires that a capacity reservation fee be
paid for this project either upon the request for the Department's signature
on the Health Department application forms or within seven (7) days of site
plan approval, whichever occurs first. This fee will be determined based
upon fmal meter size, or expected demand.
Acknowled2:ed.
44. Comprehensive Plan Policy 3.C.3.4. requires the conservation of potable
water. As other sources are readily available City water shall not be allowed
for irrigation.
lrrij!ation water is expected to be from a 2:roundwater well.
45. This office will not require surety for installation of the water and sewer
utilities, on condition that the systems be fully completed, and given to the
City Utilities Department before the fIrst permanent meter is set. Note that
setting of a permanent water meter is a prerequisite to obtaining the
Certificate of Occupancy.
Acknowledj!ed.
46. A building permit for this project shall not be issued until this Department
has approved the plans for the water and/or sewer improvements required to
service this project, in accordance with the CODE, Section 26-15.
Acknowledj!e<I.
47. The City currently has sufficient water and sewer capacity to service this
project, which will have an estimated demand of approximately 36,000 gpd
for potable water and sanitary sewer. Our current capacities and
commitments are as follows:
a. Potable water capacity = 27 MGD
Demand and commitments = 21.4 MGD
b. Sanitary sewer capacity = 12 MGD
Demand and commitments = 11.76
Acknowled2:ed.
48. Improvements to the existing water and sewer infrastructure will be required
as follows:
a. The on-site lift station must be upgraded or replaced so as to
accommodate the added demand and the constraints imposed by site
changes. Existing gravity and pressure flows to the station must be
accommodated in the design.
Acknowledged - please pmvide existing lift station information to confirm
existing capacity and inflow.
b. The water system must be connected to the existing 8-in. water main
located on the east side of Federal Highway. In addition, an 8-in. water
main connection must be established from the 12-in. water main located
INCLUDE REJECT
TRC Responses from All Team Members
05/17/05
7
DEPARTMENTS INCLUDE REJECT
on the west side of Seacrest Boulevard, to the existing 8-in. line that
terminates on SE 34th Ave. in the vicinity of SE 3rd Court; or an alternate
route may be considered to establish an 8-in. water main connection to
the 12-in. main on Seacrest Boulevard. The intent of the design is to
establish an 8-in. loop from Federal Highway to Seacrest Blvd., thereby
assuring adequate fire protection and domestic supply.
Acknowledged.
49. PVC material is not permitted on the City's water system. All lines shall be
DIP (one spur line between building types IV & VIII reflect a PVC water
line.)
All lines are shown as DIP.
50. Appropriate backflow preventer(s) will be required on the domestic water
service to the buildings, and the fire sprinkler line(s) if there are any, in
accordance with the CODE, Section 26-207.
Backflow preventers will be shown on the building services and fire lines on
the final engineering plans.
51. The LDR, Chapter 3, Article IV, Section 3(P) requires a statement be
included that utilities are available and will be provided by all other
appropriate agencies. This statement is lacking on the submitted plans.
See General Note #1 on sheet 2 of the Preliminary En2ineerin2 Plans.
52. Utility construction details will not be reviewed for construction
acceptability at this time. All utility construction details shall be in
accordance with the Utilities Department's "Utilities Engineering Design
Handbook and Construction Standards" manual (including any updates);
they will be reviewed at the time of construction permit application.
Acknowledged.
FIRE
Comments:
53. All buildings 30' in height or more than three stories will require a fire
sprinkler system
Acknowledged and will be included in CD set.
54. All entrance gate shall have Fire Department access from the beginning to
the end of the project
Acknowled2ed.
55. Access roads shall meet DOT requirements. They shall be compacted,
during construction to 32 tons to support the weight of our emergency
vehicles. The roads shall be completed from the entry gate to furthest point
of construction. Roads shall be a minimum of 20' wide if two way, and 12'
if one way. Sufficient emergency vehicle turn around shall be maintained at
all times
Acknowled2ed.
56. All hydrants shall be in service before any vertical construction. Hydrant
flow is a minimum 1500 gpm @ 20psi
Acknowledged - see Fire and Life Safety Note #1 on Sheet 20f the
Preliminary Engineering Plan.
TRC Responses from All Team Members
05/17/05
8
DEPARTMENTS INCLUDE REJECT
57. Final inspections shall be called only after all construction is completed in
the building or apartment in question.
Acknowledged.
58. Site addresses and any buildings under construction shall be visible at all
times. Numbers shall be a minimum of six inches high with at least a 1 in
width and shall contrast with the building.
Acknowledged.
POLICE
Comments:
59. Show direction of traffic on plans.
Acknowledged, see revised site plan.
60. Concern regarding number of gated entries; l.e. police/fire emergency
response.
Acknowledged.
BUILDING DIVISION
Comments:
61. Please note that changes or revisions to these plans may generate additional
comments. Acceptance of these plans during the TRC process does not
ensure that additional comments may not be generated by the commission
and at permit review.
Acknowledged.
62. Indicate within the site data the type of construction of each building as
defined in 2001 FBC, Chapter 6.
Building t shall be construction Type I protected/sprinkled and Building 2 is
f)'pe IV p rotectedls p rinkled. Townhouses are Type V unprotected
sprinkled.
63. Indicate within the site data the occupancy type of each building as defmed
in 2001 FBC, Chapter 3.
Mixed-use, multi-family buildings shall be occupancy f)'pe R-2; townhouses
are occupancy f)'pe R.
64. The height and area for buildings or structures of the different types of
construction shall be governed by the intended use or occupancy of the
building, and shall not exceed the limits set forth in Table 500 of the 2001
FBC.
Acknowledged, see site data.
65. Place a note on the elevation view drawings indicating that the exterior wall
openings and exterior wall construction comply with 2001 FBC, Table 600.
Submit calculations that clearly reflect the percentage of protected and
unprotected wall openings permitted per 2001 FBC, Table 600.
A note will be added to the elevation sheets. Howeyer, the distance of all
exteriol' walls to adjacent buildings/property lines are not cause for concern.
Percentage of openings on elevations will be considered during CD phase.
TRC Responses from All Team Members
05/17/05
9
DEPARTMENTS INCLUDE REJECT
66. Every exterior wall within 15 feet of a property line shall be equipped with
approved opening protectives per 2001 FBC, Section 705.1.1.2.
Acknowled~ed and will be included in CD set.
67. Buildings, structures and parts thereof shall be designed to withstand the
minimum wind loads of 140 mph. Wind forces on every building or
structure shall be determined by the provisions of ASCE 7, Chapter 6, and
the provisions of 2001 FBC, Section 1606 (Wind Loads). Calculations that
are signed and sealed by a design professional registered in the state of
Florida shall be submitted for review at the time of permit application.
Acknowled~ed.
68. Every building and structure shall be of sufficient strength to support the
loads and forces encountered per the 2001 FBC, Section 1601.2.1 and Table
1604.1. Indicate the live load (pst) on the plans for the building design.
Acknowledged; live load will be addressed on structural plans in CD phase.
69. Buildings three-stories or higher shall be equipped with an automatic
sprinkler system per F.S. 553.895. Fire protection plans and hydraulic
calculations shall be included with the building plans at the time of permit
application.
Acknowled~ed and will be included in CD set as an NFP A R 13 system.
70. At time of permit review, submit signed and sealed working drawings of the
proposed construction.
Acknowledged.
71. On the site plan and floor plan, indicate the number of stories that are in
each building including, where applicable, mezzanines. Indicate the overall
height of each building.
Acknowledged, see site plan.
72. Add to each building that is depicted on the site plan drawing a labeled
symbol that identifies the location of the proposed handicap accessible
units. Add to the drawing the calculations that were used to identify the
minimum number of required units. Also, state the code section that is
applicable to the computations. Show and label the same units on the
applicable floor plan drawings. Compliance with regulations specified in the
Fair Housing Act is required (Federal Fair Housing Act Design and
Construction Requirements, Title 24 CFR, Part 100.205).
Accessibilit)' route of travel is depicted on the site plan. All public areas are
built in compliance with the FHA and Florida Building Code.
73. At the time of permit review, submit details of reinforcement of walls for
the future installation of grab bars as required by the Federal Fair Housing
Act Title 24 CFR, Part 100.205, Section 3, Requirement #6. All bathrooms
within the covered dwelling unit shall comply.
Acknowledged and will be included as a detail in the CD phase.
74. Add to the drawing the calculations that were used to identify the minimum
number of required handicap accessible parking spaces.
See site plan for accessible parkin~ calculations. Adequate accessible
parkin~ is provided in both parking garage structures.
TRC Responses from All Team Members
05/17/05
10
DEPARTMENTS
75. Add a labeled symbol to the site plan drawing that represents and delineates
the path of travel for the accessible route that is required between the
accessible units and the recreational amenities that are provided for the
project and other common area elements located at the site. The symbol
shall represent the location of the path of travel, not the location of the
detectable warning or other pavement markings required to be installed
along the path. The location of the accessible path shall not compel the user
to travel in a drive/lane area that is located behind parking vehicles. Identify
on the plan the width of the accessible route. (Note: The minimum width
required by the Code is 44 inches). Add text that would indicate that the
symbol represents the accessible route and the route is designed in
compliance with regulations specified in the Fair Housing Act. Please note
that at time of permit review, the applicant shall provide detailed
documentation on the plans that will verify that the accessible route is in
compliance with the regulations specified m the 2001 FBC. This
documentation shall include, but not be limited to, providing fmish grade
elevations along the path of travel.
Accessibility route of travel is depicted on the site plan. All public areas are
built in compliance with the FHA and Florida Building Code.
76. Identify within the site data the fmish floor elevation (lowest floor elevation)
that is proposed for the building. Verify that the proposed elevation is in
compliance with regulations of the code by adding specifications to the site
data that address the following issues:
a. The design professional-of-record for the project shall add the
following text to the site data. "The proposed finish floor
elevation _15_. 5'_ NGVD is above the highest 100-year
base flood elevation applicable to the building site, as determined
by the SFWMD' s surface water management construction
development regulations."
b. From the FIRM map, identify in the site data the title of the flood
zone that the building is located within. Where applicable,
specify the base flood elevation. If there is no base flood
elevation, indicate that on the plans.
c. Identify the floor elevation that the design professional has
established for the building within the footprint of the building
that is shown on the drawings titled site plan, floor plan and
paving/drainage (civil plans).
See Site Grading Notes on sheet 2 of the Preliminary Engineering Plans.
77. As required by the CBBCO, Part III titled "Land Development
Regulations", submit a site plan that clearly depicts the setback dimensions
from each property line to the leading edge of the buildings. The leading
edge of the buildings begins at the closest point of the overhang or canopy
to the property line. In addition, show the distance between all the buildings
on all sides.
All setbacks are c1eal'ly depicted from buildings to property boundaries.
INCLUDE REJECT
TRC Responses from All Team Members
05/17/05
11
DEPARTMENTS INCLUDE REJECT
78. To properly determine the impact fees that will be assessed for the
clubhouse/recreation building, provide the following:
a. Will the clubhouse/recreation building be restricted to the residents of
the entire project only? Yes
b. Will the residents have to cross any major roads or thoroughfares to get to
the clubhouse/recreation building? No
c. Will there be any additional deliveries to the site? No
d. Will there be any additional employees to maintain and provide service to
the site? No
Please have the applicant provide the City with a copy of the letter that will be
sent to the impact fee coordinator. To allow for an efficient permit review, the
applicant should request that the County send the City a copy of their
determination of what impact fees are required for the clubhouse/recreation
building.
Acknowled~ed; developer will provide all proper documentation.
79. Add to the floor plan drawing of the clubhouse/recreation building a
breakdown of the floor area. The area breakdown shall specify the total area
of the building, covered area outside, covered area at the entrances, total
floor area dedicated for the clubhouse/recreation building and other uses
located within the building. Specify the total floor area that is air-
conditioned. Label the use of all rooms and floor spaces.
Amenity plan is shown (new sheets added) with all rooms clearly depicted.
80. CBBCPP 3.C.3.4 requires the conservation of potable water. City water may
not, therefore, be used for landscape irrigation where other sources are
readily available.
Acknowledged - It is anticipated that the source of irrigation water will be a
groundwater well.
81. A water-use permit from SFWMD is required for an irrigation system that
utilizes water from a well or body of water as its source. A copy of the
permit shall be submitted at the time of permit application, F.S. 373.216.
Acknowledged
82. If capital facility fees (water and sewer) are paid in advance to the City of
Boynton Beach Utilities Department, the following information shall be
provided at the time of building permit application.
d. The full name of the project as it appears on the Development
Order and the
Commission-approved site plan.
a. If the project is a multi-family project, the building number/s
must be provided. The building numbers must be the same as
noted on the Commission-approved site plans.
b. The number of dwelling units in each building.
c. The number of bedrooms in each dwelling unit.
d. The total amount paid and itemized into how much is for water
and how much is for sewer.
(CBBCO, Chapter 26, Article II, Sections 26-34)
At time of permit n'view, submit sepamte surveys of each lot, parcel or
tract. For purposes of setting up property and ownership in the City
computer, provide a copy of the recorded deed for each lot, parcel or tract.
The recorded deed shall be submitted at time of permit review.
TRC Responses from All Team Members
05/17/05
12
DEPARTMENTS INCLUDE REJECT
83. At time of building permit application, submit verification that the City of
Boynton Beach Parks and Recreation Impact Fee requirements have been
satisfied by a paid fee or conveyance of property. The following information
shall be provided:
a. A legal description of the land.
b. The full name of the project as it appears on the Development
Order and the Commission-approved site plan.
c. If the project is a multi-family project, the building number/s
must be provided. The building numbers must be the same as
noted on the Commission-approved site plans.
d. The number of dwelling units in each building.
e. The total amount being paid.
(CBBCO, Chapter 1, Article V, Section 3(t)).
84. Add a general note to the site plan that all plans submitted for permitting
shall meet the City's codes and the applicable building codes in effect at the
time of permit application.
This note will appear on the site plan.
85. Pursuant to approval by the City Commission and all other outside agencies,
the plans for this project must be submitted to the Building Division for
review at the time of permit application submittal. The plans must
incorporate all the conditions of approval as listed in the development order
and approved by the City Commission.
Acknowledged.
86. The full address of the project shall be submitted with the construction
documents at the time of permit application submittal. If the project is multi-
family, then all addresses for the particular building type shall be submitted.
The name of the project as it appears on the Development Order must be
noted on the building permit application at the time of application submittal.
Acknowledged.
87. Show the proposed site lighting on the site and landscape plans. (LOR,
Chapter 4, Section 7.B.4) If possible, provide photo metrics as part of your
TRC plan submittals.
See landscape plans Light pole locations are shown on landscape plans as
requested; photometries incorporated into architectural set.
88. The area breakdowns for each unit shall specify the total area of the unit, area
of the balcony, total area that is air -conditioned and, where app licab Ie, total
area of storage and garage space. If the garage and storage areas are not part
of a specific unit, the area shall be included and identified within the area of
the building. Indicate how many of each type of unit will be on each floor
and within the building.
Acknowled1!:ed; all units will be c1earlv marked and a unit mix provided.
89. Add to the site data the total area under roof of each residential building.
Provide tabular area data for each floor of each building. The breakdown
shall include the following areas and each area shall be labeled on the
applicable floor plan drawing:
a. Common area covered walkways;
b. Covered stairways;
c. Common area balconies;
d. Entrance area outside of a unit;
TRC Responses from All Team Members
05/17/05
13
DEPARTMENTS INCLUDE REJECT
e. Storage areas (not part of a unit);
f. Garages (not part of a unit);
g. Elevator room;
h. Electrical room;
1. Mechanical room;
j. Trash room;
k. Mailbox pickup and delivery area; and
l. Any other area under roof.
(Chapter 4 - Site Plan Review, Section 7.E.2 and 3)
Shown on plan in site data (8 kiosk's located for townhouses).
90. Van accessible parking spaces are required in the parking garages per the
2001 FBC, Section 11-4.1.2(5)(b).
Acknowledged and shown on the site plan.
91. Sheet SP-l - Indicate the number of handicapped parking spaces for the retail
area and the residences and the total number of handicapped spaces
provided.
All accessible parking is calculated and specified on SP-l.
92. Submit a floor plan for the retail, amenity, office, live/work, office/retail
areas.
Amenitv area is the only known plan at this time. All other space TBD.
93. The elevator shall comply with the 2001 FBC, Section 11-4.10.1.
Acknowledged.
94. Note: If all of the living units are multistory dwelling units (if all the living
space is not on one floor) then these units are not covered by the Florida
Fair Housing Act, the 2001 FBC, Chapter 11 shall apply.
No multi-family units are multi-story. Townhomes are all three story.
PARKS AND RECREATION
Comments:
95. Impact Fee:
70 single family attached units @ $771.00 each = $53,970
96 multi family units @ $656 each = $62,976
TOTAL $ 116,946
Impact fee is due prior to the issuance ofthe fIrst applicable permit.
96. Irrigation coverage needs to be 110%
Irrigation note added to general notes on Sheet L-5.
97. Indicate the site triangles at the entrances and exits and assure that
landscaping does not block the line of site.
Site triangles added.
98. Mark the sodded areas.
Sod areas labeled "sod".
TRC Responses from All Team Members
05/17/05
14
DEPARTMENTS INCLUDE REJECT
FORESTER/ENVIRONMENT ALIST
Comments:
99. Tree Removal Plan-Sheet T-l
The Landscape Architect should tabulate the total number of existing trees on the
site. The plan should indicate where the relocated trees are to be installed
throughout the site. The total diameter inches of trees removed should be shown
as replacement trees on the site landscape plan. These replacement trees should
be shown by a separate symbol on the landscape plan sheet L-5. [Environmental
Regulations, Chapter 7.5, Article I Sec. 7.D.p. 2.]
See Sheet L-5 and T-1.
100. Landscape Plan Sheet L-5
All shade and palm trees on the Plant list must be listed in the specifications
asa minimum 00" diameter at DBH (4.5' off the ground), 12'-14'
height, and Florida # 1. The height of the trees will be larger than 12' -14' to
meet the 3" diameter requirement. [Environmental Regulations, Chapter
7.5, Article II Sec. 5.C. 2.]
Change plant list to 3" D8H-14'+6' ht.
101. The details section for the Tree Planting Detail should include a line
indicating where the height of the tree and the diameter@ DBH (4.5' off
the ground) will be measured at time of planting and inspection.
See Sheet L-5.
102. The details section for the Palm Planting Detail should include a line
indicating where the height of the palm, gray wood (GW) and the clear
trunk (C.T.) will be measured at time of planting and inspection
See Sheet L-5.
103. The details section for the Shrub and Groundcover Planting Detail should
include a line indicating where the height, spread and spacing of the plant
will be measured at time planting and inspection
See Sheet L-5.
104. The applicant should add a note indicating that all utility boxes or structures
(not currently known or shown on the plan) should be screened with Coco
plum hedge plants on three sides
Agreed, note added to general notes on Sheet L-5.
105. The landscape buffer detail should be shown to scale (height and canopy
spread) at time of planting and include the height scale of the buildings
See section L-6.
106. Irrieation Plan-No Irri2ation plan included in the submittal
The irrigation system design (not included in the plans) should be low
volume water conservation using non-portable water.
Note added on general notes and Sheet L-5.
107. Turfand landscape (bedding plants) areas should be designed on separate
zones and time duration for water conservation.
Will be done at time irrigation plans are submitted.
TRC Responses from All Team Members
05/17/05
15
DEPARTMENTS INCLUDE REJECT
108. Trees should have separate irrigation bubblers to provide water directly to
the root ball. [Environmental Regulations, Chapter 7.5, Article II Sec. 5.
C.2.]
Noted, and will be added to irri2ation plans.
PLANNING AND ZONING
Comments:
109. Submit a traffic impact analysis prior to the Technical Review Committee
meeting. The analysis must be approved by the Palm Beach County Traffic
Division for concurrency purposes (Chapter 4. Section 8.F.). The proposed
uses and intensities on the traffic study must be consistent with the proposed
uses and intensities itemized on the site plan (sheet SP-l).
Received comments from Palm Beach County Traffic Division. Revised
Concurrency Statement has beed provided.
110. According to Chapter 2.5, Section 8.D., areas designated for commercial
activities shall not generally front on exterior or perimeter streets, and shall
be preferably centrally located within the project. The proposed plan would
be in conflict with the aforementioned code. Therefore, an amendment to
the code would be required to allow the project as it is proposed.
Acknowled2ed.
111. The maximum building height in the PUD zoning district is 45 feet. Either
reduce the building height of Building 1 to comply with code or formally
request a height exception pursuant to Chapter 2, Section 4.F.3 of the Land
Development Regulations.
Acknowled2ed, a formal waiver will be submitted by the developer.
112. The site plan should indicate proposed fences and walls, including their
dimensions, setbacks, material, and color(s) pursuant to Chapter 4, Section
7 .B.3. Provide a detail of any walls or fences, including their dimensions,
exterior fmish, and color(s) (Chapter 4, Section 7.D.).
Fence locations and details provided.
113. Will an on-site lift-station be required as a result of this development? If so,
show its location on the site plan (sheet SP-l).
An on-site lift station will not be required. There is an existing lift station
outside the pro.iect boundaries at the NE corner of the site.
114. Abandonment and rededication of easements must be recorded prior to
issuance of a building permit for the project.
Acknowled2ed.
115. The dimensions of the roadway (pavement), drive aisles, back-up areas, and
rights-of-way are subject to the Engineering Division of Public Works'
review and approval.
Acknowledged.
TRC Responses from All Team Members
05/17/05
16
DEPARTMENTS
INCLUDE REJECT
116. The site plan tabular data (sheet SP-l) should accurately indicate the number of required parking
spaces. The required parking projects is as follows:
Proposed Use
Required Parking
Provided
Parkin
24 One-bedroom units
36
124
160
10
48
21
35
434
Use
140
50
21
229
440
Parking spaces required in this ordinance for one use or structure may be allocated in part or in whole for the
required parking spaces of another use or structure if quantitative evidence is provided showing that
parking demand for the different uses or structures would occur on different days of the week or at
different hours. Quantitative evidence shall include estimates for peak hour / peak season demand based
on statistical data furnished by the Urban Land Institute or an equivalent traffic engineering or land
planning and design organization (Chapter 2, Section I1.H.13.). Submit a shared parking analysis prior
to the Technical Review Committee meeting.
117. Please explain the use for the room indicated as "amenity" on the ground
floor plan (sheet A-I) and second floor plan (sheet A-2) of Building 1. Will
it be a gym or racquetball courts?
Amenity space is only on the ground floor of building 1 and is intended as a
building lobby, lounge, mail room, club room and exercise room adjacent to
the common 001 and outdoor atio area.
118. Is an amenity room proposed for Building 2? Is the garage open to below?
Staff recommends creating a recreation deck on the roof of the garage of
building 2 (sheet A-6).
Amenity space in building 1 is for all residents. Note that building 2 only
has 12 total units so any recreational s ace there would be excessive.
119. On the site plan (sheet SP-l), graphically show the building setback
proposed along the south property line.
Acknowledged and depicted on site plan along the south property line.
TRC Responses from All Team Members
05/17/05
17
DEPARTMENTS INCLUDE REJECT
120. On the site plan (sheet SP-l), indicate the number of stories for Building 1
and Building 2.
Acknowledlred and shown on the site olano
121. Are fee-simple townhouses proposed for this project? If so, on the site plan
(sheet SP-l), show the extent of their lot lines.
Yes; lot lines will be depicted 00 plat.
122. Indicate the proposed floor area (expressed in square feet) for the retail area
as shown on second floor plan (sheet A-5).
No actual retail area is intended for the second floor of either building.
Rather, the soace is shown as "double height" in most areas.
123. Staff recommends decreasing the building setback along the east property
line (along Federal Highway) so that buildings would be placed no further
than 10 feet from the property line. The 10- foot front setback of 10 feet
may contain public plazas and landscape material.
There is an existing 20 foot utility easement along the east property line that
contains an existing gravity sewer line and water main that are proposed to
remain.
124. Provide a detail of the security gates, including dimensions, material, and
color.
Acknowledlred and depicted as Dart of the CD phase for Citv's aooronl.
125. Label the clubhouse on the floor plan (sheet A-I) of Building 1.
Acknowledlred and labeled.
126. Label the types of rooms (i.e. bedroom, living room) on all three floors of
the townhouses for Building III and Building VII (sheet A-14).
Acknowledlred and labeled.
127. Provide a west elevation for Building 2 (Chapter 4, Section 7.D.).
See elevations.
128. Provide rear and side elevations of Townhouse Building V (sheet A-2l).
See elevations.
129. All elevation pages shall indicate the exterior fmishes, roof material, paint
manufacturer's name, and color codes. Staff recommends using a color
schedule (Chapter 4, Section 7.D.). Also, provide color swatches and
awning samples.
See elevations and color boards.
130. Include a color rendering of all elevations at the Technical Review
Committee meeting (Chapter 4, Section 7.D.).
Acknowledlred and included for meetinlr. Colored site plan provided.
131. The removal/relocation of landscape material is subject to review and
approval of the City Forester / Environmentalist. The City Forester /
Environmentalist will determine the fate of the existing Black Olive trees
located near the Aphrodites out-parcel.
To be determined.
132. On the landscape plan, ensure that the plant quantities must match between
the tabular data and the graphic illustration. The landscape plan shall
provide total plant material quantities for the following categories: Shade
trees, palm trees, Shrubs / Groundcover.
See plant listl tabular data.
TRC Responses from All Team Members
05/17/05
18
DEPARTMENTS INCLUDE REJECT
133. Fifty percent (50%) of all site landscape materials must be native species
(Chapter 7.5, Article II, Section 5.P). Please categorize as follows: Shade
trees, Palm trees, Shrubs & Groundcover.
Provided.
134. A signature tree (such as a Yellow Elder, Tibouchina Granulsola, or
Bouganvillea) is required at both sides of the project entrances (along U.S. 1
and Old Dixie Highway). The signature trees must have eight (8) feet of
clear trunk if placed within the safe-sight triangle (Chapter 7.5, Article 2,
Section 5.N.). Alternative plant material may be substituted if the above
referenced plant material is not available or undesired. Any substitution of
plant material (for the signature tree requirement) will be subject to the City
Forester / Environmentalist review and approval.
Provided.
135. All trees, if proposed as trees, must be at least 12 feet in height and three (3)
caliper inches at the time of their installation (Chapter 7.5, Article II,
Section 5.C.2.).
Provided.
136. All shrubs and hedges are required to be at minimum 24 inches in height,
24 inches in spread, and planted with tip-to-tip spacing measured
immediately after planting to adequately cover the planted areas on the site
(Chapter 7.5, Article II, Section 5.CA.).
See plant specifications.
137. The palm trees proposed around the townhouse buildings must be installed
at Y2 the building height of the building (Chapter 7.5, Article II, Section
5.M.).
Minimum height 18' OA.
138. All freestanding monument signs shall have colorful groundcover installed
at the base (Chapter 7.5, Article II, Section 5.0).
Provided.
139. What will be the dimensions of the interior and terminal landscape islands?
Provided on site Illan. Minimum width of islands is 10'.
140. All proposed wall signage is subject to the Community Redevelopment
Agency Board and City Commission review and approval. Staff
recommends that you submit a master sign program that shows the number,
location, dimensions, exterior finish, and color(s) of all signs (Chapter 2,
Section 5.H.9.). The sign program would address all types of signs,
including commercial wall signs, identification signs, residential subdivision
signs, freestanding monument signs, canopy signs, way-finding signs,
directional signs, and all other signs as regulated by Chapter 21 of the Land
Development Regulations.
Acknowledged - see site plan for signage criteria.
141. All signage IS subject to review and approval of the Community
Redevelopment Agency Board and City Commission. Provide a detail of
any proposed outdoor freestanding monument signs and indicate their
setback from the property line (minimum 10 feet), and include the sign area,
dimensions, exterior fmish, and letter color(s) (Chapter 4, Section 7.D.).
Acknowledged - see site plan fo.. signage criteria.
, '
\.
TRC Responses from All Team Members
05/17/05
19
1
f1
f-
DEPARTMENTS INCLUDE REJECT
142. Provide a detail of a typical outdoor freestanding lighting fixture. The detail
of the typical freestanding outdoor lighting fixture should include the
overall height, exterior finish, materials used (Le. concrete or aluminum)
and color(s). The lighting fixture height, style, design, and illumination
level shall be compatible with the building design and height and shall
consider safety, function, and aesthetic value (Chapter 9, Section 10.F.1.).
The height of the lighting fixtures should be the same throughout the entire
commercial/mixed-use areas.
AGknowled2ed and included on photometric sheet.
I 1'43. Lighting shall not be of an intensity that produces glare on adjacent property
(Chapter 9, Section 10.F.2.).
..\cknowled2ed.
144. Feature lighting emphasizing plants, trees, barriers, entrances, and exits is
encouraged (Chapter 9, Section 10.F.3.).
Acknowledged and will be incorporated into the project as it develops. See
preliminary 1i2htin2 plan included, see Sheet L-7.
145. Lighting may be used to illuminate a building and its grounds for safety
purposes and to enhance its beauty. However, the visual effect shall be
subtle (Chapter 9, Section 10.Fo4.). Please submit a photometric plan so
that staff can review the photometric levels (footcandles).
Acknowled2ed and included.
146. Lighting shall not be used as a form of advertising in a manner that draws
more attention to the building or grounds at night than in the day (Chapter
9, Section 10.F.5.).
Acknowled2ed.
147. Sculptures, fountains, gardens, pools, trellises an benches shall be
encouraged within the site design (Chapter 9, Section 10.H.). Provide
details of said amenities.
Acknowledged and added. See plans and details on Sheet L-6.
148. Include covered bike racks at intermittent locations throughout the
commercial/public spaces. Also, more attention and detail should made
for a possible location of a bus stop since this location is off of Palm Tran
Route 1.
Acknowled2ed and provided. See site plan.
149. Staff recommends re-orienting the building proposed along Old Dixie
Highway so that the front doors face Old Dixie Highway rather than the
garage doors face Old Dixie Highway. This would help to perpetuate "new
urbanism" principles, in part, by placing importance on the public spaces
(i.e. front doors facing the street) while reducing the amount of impervious
surface (i.e. no need for two driveways to one purpose).
Acknowled2ed and modified, see revised site plan.
150. Staff recommends installing the Royal Palms (proposed along Federal
Highway) at half the height of the adjacent mixed-use buildings.
25' overall, 18' 2reywood provided.
151. Indicate the location of the mailbox kiosk(s) within the townhouse area.
8 kiosks located.
TRC Responses from All Team Members
05/17/05
20
DEPARTMENTS INCLUDE REJECT
152. Rooftops will be treated as part of the building elevation. All rooftop
equipment must be completely screened from view at a minimum
distance of 600 feet.
Acknowled~ed.
153. Additional architectural detail is needed on the parking structure
elevations, in order to be compliant with the eRA design guidelines
Acknowledl!ed; parkinl! l!aral!e will be fnrther developed for the CD set.
154. Indicate the planting of St. Augustine sod in the swale areas with
appropriate irrigation.
Al!reed.
155. Staff suggests that ingress, as well the egress indicated, be provided from
Old Dixie Highway.
Only access to Dixie Hil!hway will be as an exit from the north access road.
156. Will the existing hedge around the southernmost wellhead be retained? If
not, it should be, at a minimum, landscaped to the extent of the one on the
west property line.
Yes.
157. No landscape is depicted on the Landscape Plan around the lift station at the
north property line. It should be heavily landscaped due to its visibility from
Federal Highway.
Landscape provided.
158. A planting scheme involving taller shrub material than the proposed 24 inch
high hedge should be selected for the north property line. Possibly a tiered
landscape approach of different size materials may be more appropriate.
A~reed, see landscape plans.
159. A full-size clubhouse/recreation building should be provided at the pool for
the townhouses.
A structure has been desil!ned to house bathrooms and a l!atherinl! area.
160. The recreation space is not adequate around the pool for the townhouses. A
green, outdoor, play space should be provided to give the residents a park
setting for outdoor activities, since there is not a park in the immediate
vicinity. Staff suggests the elimination of the streets surrounding the pool
area and their conversion to park/green space, since the remainder of the
circulation pattern appears adequate.
Several "green" spaces have been added on adjacent blocks. Although
vehicular circulation still exists, the amount of asphalt has been significantly
reduced. Eliminated road north pool, provided narrower road south of
pool. Please see the updated site plan.
1ST REVIEW COMMENTS
04/22/05
12
v:~ ~ .OS
s.1-'b
DEPARTMENTS INCLUDE REJECT
93. The elevator shall comply with the 2001 FBC, Section 11-4.10.1.
94. Note: If all of the living units are multistory dwelling units (if all the living
space is not on one floor) then these units are not covered by the Florida
Fair Housing Act, the 2001 FBC, Chapter 11 shall apply.
PARKS AND RECREATION
Comments:
95. Impact Feee:
74 single family attached units @ $771.00 each = $57,054
92 multi family units @ $656 each = $60,352
TOTAL $ 1170406
Impact fee is due prior to the issuance of the first applicable permit.
96. Irrigation coverage needs to be 110%
97. Indicate the site triangles at the entrances and exits and assure that
landscaping does not block the line of site.
98. Mark the sodded areas.
FORESTER/ENVIRONMENT ALIST
Comments:
99. Tree Removal Plan-Sheet T-l
The Landscape Architect should tabulate the total number of existing trees on the ~v
site. The plan should indicate where the relocated trees are to be installed
throughout the site. The total diameter inches of trees removed should be shown
as replacement trees on the site landscape plan. These replacement trees should
be shown by a separate symbol on the landscape plan sheet L-5. [Environmental
Regulations, Chapter 7.5, Article I Sec. 7.D.p. 2.]
100. Landscape Plan Sheet L-5
All shade and palm trees on the Plant list must be listed in the specifications /
asa minimum of3" diameter at DBH (4.5' off the ground), 12'-14'
height, and Florida # 1. The height of the trees will be larger than 12' -14' to
meet the 3" diameter requirement. [Environmental Regulations, Chapter
7.5, Article II Sec. 5.C. 2.]
/
101. The details section for the Tree Planting Detail should include a line J
indicating where the height of the tree and the diameter @ DBH (4.5' off
1ST REVIEW COMMENTS
04/22/05
13
DEPARTMENTS INCLUDE REJECT
the ground) will be measured at time of planting and inspection. /
102. The details section for the Palm Planting Detail should include a line /
indicating where the height of the palm, gray wood (GW) and the clear
trunk (C.T.) will be measured at time of planting and inspection
103. The details section for the Shrub and Groundcover Planting Detail should v/
include a line indicating where the height, spread and spacing of the plant
will be measured at time planting and inspection
104. The applicant should add a note indicating that all utility boxes or structures /
(not currently known or shown on the plan) should be screened with Coco
plum hedge plants on three sides
105. The landscape buffer detail should be shown to scale (height and canopy ~
spread) at time of planting and include the height scale of the buildings
106. Irrieation Plan-No Irrieation plan included in the submittal /
The irrigation system design (not included in the plans) should be low
volume water conservation using non-portable water.
107. Turf and landscape (bedding plants) areas should be designed on separate ~
zones and time duration for water conservation.
108. Trees should have separate irrigation bubblers to provide water directly to /
the root ball. [Environmental Regulations, Chapter 7.5, Article II Sec. 5.
C.2.]
PLANNING AND ZONING
Comments:
109. Submit a traffic impact analysis prior to the Technical Review Committee
meeting. The analysis must be approved by the Palm Beach County Traffic
Division for concurrency purposes (Chapter 4. Section 8.F.). The proposed
uses and intensities on the traffic study must be consistent with the proposed
uses and intensities itemized on the site plan (sheet SP-l).
110. According to Chapter 2.5, Section 8.D., areas designated for commercial
activities shall not generally front on exterior or perimeter streets, and shall
be preferably centrally located within the project. The proposed plan would
be in conflict with the aforementioned code. Therefore, an amendment to
the code would be required to allow the project as it is proposed.
111. The maximum building height in the PUD zoning district is 45 feet. Either
reduce the building height of Building 1 to comply with code or formally
request a height exception pursuant to Chapter 2, Section 4.F.3 of the Land
Development Regulations.
112. The site plan should indicate proposed fences and walls, including their
dimensions, setbacks, material, and color(s) pursuant to Chapter 4, Section
7.B.3. Provide a detail of any walls or fences, including their dimensions,
exterior finish, and color{s) (Chapter 4, Section 7.D.).
113. Will an on-site lift-station be required as a result of this development? If so,
.. , . ~~ .,
. ~,tz1AIG~~7<f;tllM- JiM ~,41IJ.i-. /J1o-i-
, jlij/lIA~~~,1 adJ ~~ t .e- ~
~ p-<'VVL -{s'REVIEWCOMMENTS ;J4ci ~
New Site Plan ~f .
Project name: Heritage Club@Boynton Beach ~.... . JI P O~ 1.,/ 1 ~ r
Filenumber:NWSP05-014 -;' ~~ - 1/ Ie-
Reference: 1 streview plans identified as a New Site Plan with a March 23. 2005 Planning ancfJzoning
Department date stamp marking
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments:
1. Prior to permit application contact the Public Works Department (561-742-
6200) regarding the storage and handling of refuse per the CODE, Section
10-26 (a).
2. Indicate by note that the site dumpster enclosures shall be constructed in
accordance with City Standard Drawing G-4.
3. Only two trash enclosures are depicted to service the retaiVoffice/residential
buildings along Federal Highway. This does not appear to be sufficient to
serve the expected waste stream. Please iustifv this decision.
4. Identify if the trash holding areas will be for dumpsters or compactors. If
compactors are to be used the enclosures will need to be enlarged.
Additionally the northernmost holding area will not be accessible for a rear-
loading truck to pick up the container due to the proposed traffic flow along
the north property line.
5. There is a vertical conflict between the dumpster (south of Building 2) and
the existing Black Olives east of the enclosure and the Pigeon Plum on the
west side of the enclosure.
6. There are multiple dead end sections throughout the project that will not be
able to be serviced by our automatic pickup Solid Waste Truck. Please
correct these conditions.
PUBLIC WORKS - Traffic
Comments:
7. Provide a traffic analysis and notice of concurrency (Traffic Performance
Standards Review) from Palm Beach County Traffic Engineering.
8. Dedicate an additional 40-foot of right-of-way or easements to the City of
Boynton Beach along the west property line to allow for a total of 70-foot
total width for public purposes.
9. Reconstruct Old Dixie Hwy. and Gulfstream Blvd. to provide for curb &
gutter, storm sewer, appropriate left turn lanes, striping and landscaped
parkways adjacent to the proposed development. As part of this design the
developer is asked to consider but not required to build a barrier median on
both side of the FECRR/Gulfstream Blvd. crossing with the intent to qualify
this crossing as a Quiet Zone with the Federal Railroad Administration
10. On-street parking shall be public parking and may not be counted towards
1ST REVIEW COMMENTS
04/22/05
7
DEPARTMENTS INCLUDE REJECT
57. Final inspections shall be called only after all construction is completed in
the building or apartment in question.
58. Site addresses and any buildings under construction shall be visible at all
times. Numbers shall be a minimum of six inches high with at least a 1 in
width and shall contrast with the building.
POLICE
Comments:
59. Show direction of traffic on plans.
60. Concern regarding number of gated entries; I.e. police/fire emergency
response.
BUILDING DIVISION
Comments:
61. Please note that changes or revisions to these plans may generate additional
comments. Acceptance of these plans during the TRC process does not /
ensure that additional comments may not be generated by the commission
and at permit review.
62. Indicate within the site data the type of construction of each building as ~ -
defined in 2001 FBC, Chapter 6.
63. Indicate within the site data the occupancy type of each building as defined
in 2001 FBC, Chapter 3. ~
64. The height and area for buildings or structures of the different types of
construction shall be governed by the intended use or occupancy of the /
building, and shall not exceed the limits set forth in Table 500 of the 2001
FBC.
65. Place a note on the elevation view drawings indicating that the exterior wall
openings and exterior wall construction comply with 2001 FBC, Table 600.
Submit calculations that clearly reflect the percentage of protected and V
unprotected wall openings permitted per 2001 FBC, Table 600.
66. Every exterior wall within 15 feet of a property line shall be equipped with
approved opening protectives per 2001 FBC, Section 705.1.1.2. L---
67. Buildings, structures and parts thereof shall be designed to withstand the
minimum wind loads of 140 mph. Wind forces on every building or V /
structure shall be determined by the provisions of ASCE 7, Chapter 6, and
the provisions of 2001 FBC, Section 1606 (Wind Loads). Calculations that
are signed and sealed by a design professional registered in the state of
Florida shall be submitted for review at the time of permit application.
1ST REVIEW COMMENTS
04/22/05
8
DEPARTMENTS INCLUDE REJECT
68. Every building and structure shall be of sufficient strength to support the
loads and forces encountered per the 2001 FBC, Section 1601.2.1 and Table /l.-/
1604.1. Indicate the live load (pst) on the plans for the building design.
69. Buildings three-stories or higher shall be equipped with an automatic
sprinkler system per F.S. 553.895. Fire protection plans and hydraulic
calculations shall be included with the building plans at the time of permit ~
application.
70. At time of permit review, submit signed and sealed working drawings of the ~
proposed construction.
71. On the site plan and floor plan, indicate the number of stories that are in
each building including, where applicable, mezzanines. Indicate the overall V
height of each building.
72. Add to each building that is depicted on the site plan drawing a labeled
symbol that identifies the location of the proposed handicap accessible
units. Add to the drawing the calculations that were used to identify the V
minimum number of required units. Also, state the code section that is
applicable to the computations. Show and label the same units on the
applicable floor plan drawings. Compliance with regulations specified in the
Fair Housing Act is required (Federal Fair Housing Act Design and
Construction Requirements, Title 24 CFR, Part 100.205).
73. At the time of permit review, submit details of reinforcement of walls for
the future installation of grab bars as required by the Federal Fair Housing V
Act Title 24 CFR, Part 100.205, Section 3, Requirement #6. All bathrooms
within the covered dwelling unit shall comply.
74. Add to the drawing the calculations that were used to identify the minimum
number of required handicap accessible parking spaces. ~
75. Add a labeled symbol to the site plan drawing that represents and delineates
the path of travel for the accessible route that is required between the
accessible units and the recreational amenities that are provided for the
project and other common area elements located at the site. The symbol
shall represent the location of the path of travel, not the location of the
detectable warning or other pavement markings required to be installed V
along the path. The location of the accessible path shall not compel the user
to travel in a drive/lane area that is located behind parking vehicles. Identify
on the plan the width of the accessible route. (Note: The minimum width
required by the Code is 44 inches). Add text that would indicate that the
symbol represents the accessible route and the route is designed in
compliance with regulations specified in the Fair Housing Act. Please note
that at time of permit review, the applicant shall provide detailed
documentation on the plans that will verify that the accessible route is in
compliance with the regulations specified m the 2001 FBC. This
1ST REVIEW COMMENTS
04/22/05
9
DEPARTMENTS
documentation shall include, but not be limited to, providing finish grade
elevations along the path of travel.
76. Identify within the site data the finish floor elevation (lowest floor elevation)
that is proposed for the building. Verify that the proposed elevation is in
compliance with regulations of the code by adding specifications to the site
data that address the following issues:
a. The design professional-of-record for the project shall add the
following text to the site data. "The proposed finish floor
elevation _' _ NGVD is above the highest 100-year base
flood elevation applicable to the building site, as determined by
the SFWMD's surface water management construction
development regulations."
b. From the FIRM map, identify in the site data the title of the flood
zone that the building is located within. Where applicable,
specify the base flood elevation. If there is no base flood
elevation, indicate that on the plans.
c. Identify the floor elevation that the design professional has
established for the building within the footprint of the building
that is shown on the drawings titled site plan, floor plan and
paving/drainage (civil plans).
INCLUDE REJECT
~
77. As required by the CBBCO, Part III titled "Land Development
Regulations", submit a site plan that clearly depicts the setback dimensions
from each property line to the leading edge of the buildings. The leading
edge of the buildings begins at the closest point of the overhang or canopy ~
to the property line. In addition, show the distance between all the buildings
on all sides.
78. To properly determine the impact fees that will be assessed for the
clubhouse/recreation building, provide the following:
a. Will the clubhouse/recreation building be restricted to the residents of
the entire project only?
b. Will the residents have to cross any major roads or thoroughfares to get to
the clubhouse/recreation building?
c. Will there be any additional deliveries to the site?
d. Will there be any additional employees to maintain and provide service to
the site?
Please have the applicant provide the City with a copy of the letter that will be
sent to the impact fee coordinator. To allow for an efficient permit review, the
applicant should request that the County send the City a copy of their
determination of what impact fees are required for the clubhouse/recreation
building.
79. Add to the floor plan drawing of the clubhouse/recreation building a
breakdown of the floor area. The area breakdown shall specify the total area
of the building, covered area outside, covered area at the entrances, total
floor area dedicated for the clubhouse/recreation building and other uses
located within the building. Specify the total floor area that is air-
~
,J
/
~
1ST REVIEW COMMENTS
04/22/05
10
DEPARTMENTS INCLUDE REJECT
conditioned. Label the use of all rooms and floor spaces.
80. CBBCPP 3.C.3.4 requires the conservation of potable water. City water may
not, therefore, be used for landscape irrigation where other sources are t/
readily available.
81. A water-use permit from SFWMD is required for an irrigation system that /
utilizes water from a well or body of water as its source. A copy of the
permit shall be submitted at the time of permit application, F.s. 373.216.
82. If capital facility fees (water and sewer) are paid in advance to the City of
Boynton Beach Utilities Department, the following information shall be
provided at the time of building permit application.
d. The full name of the project as it appears on the Development
Order and the
Commission-approved site plan.
a. If the project is a multi-family project, the building number/s
must be provided. The building numbers must be the same as
noted on the Commission-approved site plans.
b. The number of dwelling units in each building. 1/
c. The number of bedrooms in each dwelling unit.
d. The total amount paid and itemized into how much is for water
and how much is for sewer.
(CBBCO, Chapter 26, Article II, Sections 26-34)
At time of permit review, submit separate surveys of each lot, parcel or tract. For
purposes of setting up property and ownership in the City computer, provide a
copy of the recorded deed for each lot, parcel or tract. The recorded deed shall
be submitted at time of permit review.
83. At time of building permit application, submit verification that the City of
Boynton Beach Parks and Recreation Impact Fee requirements have been
satisfied by a paid fee or conveyance of property. The following information
shall be provided:
a. A legal description of the land.
b. The full name of the project as it appears on the Development
Order and the Commission-approved site plan. /
c. If the project is a multi-family project, the building number/s
must be provided. The building numbers must be the same as
noted on the Commission-approved site plans.
d. The number of dwelling units in each building.
e. The total amount being paid.
(CBBCO, Chapter 1, Article V, Section 3(t))
84. Add a general note to the site plan that all plans submitted for permitting V
shall meet the City's codes and the applicable building codes in effect at the
time of permit application.
/
85. Pursuant to approval by the City Commission and all other outside agencies, V
the plans for this project must be submitted to the Building Division for
1ST REVIEW COMMENTS
04/22/05
11
DEPARTMENTS
review at the time of permit application submittal. The plans must
incorporate all the conditions of approval as listed in the development order
and approved by the City Commission.
86. The full address of the project shall be submitted with the construction
documents at the time of permit application submittal. If the project is multi-
family, then all addresses for the particular building type shall be submitted.
The name of the project as it appears on the Development Order must be
noted on the building permit application at the time of application submittal.
87. Show the proposed site lighting on the site and landscape plans. (LDR,
Chapter 4, Section 7.B.4) If possible, provide photo metrics as part of your
TRC plan submittals.
88. The area breakdowns for each unit shall specify the total area of the unit, area
of the balcony, total area that is air-conditioned and, where applicable, total
area of storage and garage space. If the garage and storage areas are not part
of a specific unit, the area shall be included and identified within the area of
the building. Indicate how many of each type of unit will be on each floor
and within the building.
89. Add to the site data the total area under roof of each residential building.
Provide tabular area data for each floor of each building. The breakdown
shall include the following areas and each area shall be labeled on the
applicable floor plan drawing:
a. Common area covered walkways;
b. Covered stairways;
c. Common area balconies;
d. Entrance area outside of a unit;
e. Storage areas (not part of a unit);
f. Garages (not part of a unit);
g. Elevator room;
h. Electrical room;
1. Mechanical room;
j. Trash room;
k. Mailbox pickup and delivery area; and
I. Any other area under roof.
(Chapter 4 - Site Plan Review, Section 7.E.2 and 3)
90. Van accessible parking spaces are required in the parking garages per the
2001 FBC, Section ll-4.1.2(5)(b).
91. Sheet SP-l - Indicate the number of handicapped parking spaces for the retail
area and the residences and the total number of handicapped spaces
provided.
92. Submit a floor plan for the retail, amenity, office, live/work, office/retail
areas.
INCLUDE REJECT
t/
v
v/
L/
v
/
v
..
1ST REVIEW COMMENTS
04/22/05
12
DEPARTMENTS INCLUDE REJECT
93. The elevator shall comply with the 2001 FBC, Section 11-4.10.1. t/
94. Note: If all of the living units are multistory dwelling units (if all the living /
space is not on one floor) then these units are not covered by the Florida V
Fair Housing Act, the 2001 FBC, Chapter 11 shall apply.
PARKS AND RECREATION
Comments:
95. Impact Feee:
74 single family attached units @ $771.00 each = $57,054
92 multi family units @ $656 each = $60,352
TOTAL $ 1170406
Impact fee is due prior to the issuance of the first applicable permit.
96. Irrigation coverage needs to be 110%
97. Indicate the site triangles at the entrances and exits and assure that
landscaping does not block the line of site.
98. Mark the sodded areas.
FORESTER/ENVIRONMENT ALIST
Comments:
99. Tree Removal Plan-Sheet T-l
The Landscape Architect should tabulate the total number of existing trees on the
site. The plan should indicate where the relocated trees are to be installed
throughout the site. The total diameter inches of trees removed should be shown
as replacement trees on the site landscape plan. These replacement trees should
be shown by a separate symbol on the landscape plan sheet L-5. [Environmental
Regulations, Chapter 7.5, Article I Sec. 7.D.p. 2.]
100. Landscape Plan Sheet L-5
All shade and palm trees on the Plant list must be listed in the specifications
as a minimum of3" diameter at DBH (4.5' off the ground), 12'-14'
height, and Florida # 1. The height of the trees will be larger than 12' -14' to
meet the 3" diameter requirement. [Environmental Regulations, Chapter
7.5, Article II Sec. 5.C. 2.]
101. The details section for the Tree Planting Detail should include a line
indicating where the height of the tree and the diameter @ DBH (4.5' off
DEPARTMENT OF PUBLIC WORKS
ENGINEERING DIVISION
MEMORANDUM NO. 05-048
TO:
Ed Breese, Principal Planner, Planning and Zoning
FROM:
laurinda logan, P.E., Senior Engineer
DATE:
April 19, 2005
RE:
Review Comments
New Site Plan - 1st Review
Heritage Club at Boynton Beach
File No, NWSP 05-014
The above referenced Site Plans, received on March 25, 2005, was reviewed for Public Works,
Engineering, and Utilities against the requirements outlined in the City of Boynton Beach Code of
Ordinances. Following are our comments with the appropriate Code and land Development Regulations
(lDR) referenced.
PUBLIC WORKS - GENERAL
1. Prior to permit application contact the Public Works Department (561-742-6200) regarding the
storage and handling of refuse per the CODE, Section 10-26 (a).
2. Indicate by note that the site dumpster enclosures shall be constructed in accordance with City
Standard Drawing G-4.
3. Only two trash enclosures are depicted to service the retail/office/residential buildings along Federal
Highway. This does not appear to be sufficient to serve the expected waste stream. Please justify
this decision.
4. Identify if the trash holding areas will be for dumpsters or compactors. If compactors are to be used
the enclosures will need to be enlarged. Additionally the northernmost holding area will not be
accessible for a rear-loading truck to pick up the container due to the proposed traffic flow along the
north property line.
5. There is a vertical conflict between the dumpster (south of Building 2) and the existing Black Olives
east of the enclosure and the Pigeon Plum on the west side of the enclosure.
6. There are multiple dead end sections throughout the project that will not be able to be serviced by
our automatic pickup Solid Waste Truck. Please correct these conditions.
PUBLIC WORKS - TRAFFIC
7. Provide a traffic analysis and notice of concurrency (Traffic Performance Standards Review) from
Palm Beach County Traffic Engineering.
8. Dedicate an additional 40-ft. of right-of-way or easements to the City of Boynton Beach along the
west property line to allow for a total of 70-ft. total width for public purposes.
"'I
Department of Public Works/Engineering Division Memo No. 05-048
Re: Heritage Club at Boynton Beach, New Site Plan 1 sl Review
April 19, 2005
Page 2
9. Reconstruct Old Dixie Hwy. and Gulfstream Blvd. to provide for curb & gutter, storm sewer,
appropriate left turn lanes, striping and landscaped parkways adjacent to the proposed development.
As part of this design the developer is asked to consider but not required to build a barrier median on
both side of the FECRR/Gulfstream Blvd. crossing with the intent to qualify this crossing as a Quiet
Zone with the Federal Railroad Administration.
10. On-street parking shall be public parking and may not be counted towards internal parking
requirements.
11. Live Oaks proposed along the west property line may conflict with parallel parking.
12. The proposed diagonal parking adjacent to the main entry off Federal Highway will create a traffic
hazard for westbound entering vehicles and vehicles exiting eastbound from the Building Two
parking structure. Staff recommends either eliminating this parking or specifying parallel parking.
13. Delineate and stripe 12-ft.x35-ft. loading zones for the retail buildings; include a pavement message
in yellow indicating "No Parking - Loading Zone".
14. Reference City Standard Drawings "K" Series for striping details.
15. Clearly identify the location of gates and indicate their accessibility for Fire/Rescue and Solid Waste.
16. Place "One-Way Only" signs across from the westbound egress driveways onto Federal Highway.
17. The two-way north-south roadway in the northwest corner of the development is less than 24-ft. in
width. Please correct this condition.
18. Accommodate the need to turn around if the gate fails on the one-way north-south roadway or the
gate should be designed with battery backup capability to automatically open the gate in the event of
a power failure.
19. The driveway at the northeast corner of the development is less than 24-ft. in width. Please correct
this condition.
20. Delete the two diagonal parking spaces at the southwest of the pool area due to safety concerns of
backing into a four-way intersection.
ENGINEERING
21, Permits required from other permitting agencies such as Florida Department of Transportation
(FOOT), South Florida Water Management District (SFWMD), Lake Worth Drainage District (LWDD),
Florida Department of Environmental Protection (FDEP), Palm Beach County Health Department
(PBCHD), Palm Beach County Engineering Department (PBCED), Palm Beach County Department
of Environmental Resource Management (PBCDERM) and any others, shall be included with the
permit request.
22. All comments requiring changes and/or corrections to the plans shall be reflected on all appropriate
sheets.
~
Department of Public Works/Engineering ~ivision Memo No. 05-048
Re: Heritage Club at Boynton Beach, New Site Plan 1 sl Review
April 19, 2005
Page 3
23. Please note that changes or revIsions to these plans may generate additional comments.
Acceptance of these plans during the TRC process does not ensure that additional comments may
not be generated by the Commission and at permit review.
24. Provide written and graphic scales on all sheets.
25. Show proposed site lighting on the Site and Landscape plans (LOR, Chapter 4, Section 7.B.4.) The
lighting design shall provide a minimum average light level of one foot-candle. On the Lighting Plan,
specify that the light poles shall withstand a 140 MPH wind load (LOR, Chapter 23, Article II, Section
A.1.a and Florida Building Code). Provide a note that the fixtures shall be operated by photo-
electrical control and are to remain on until 2:00 a.m. (LOR, Chapter 23, Article II, Section A.1.a.)
Include pole wind loading, and pole details in conformance with the LOR, Chapter 6, Article IV,
Section 11, Chapter 23, Article I, Section 5.B.7 and Chapter 23, Article II, Section A on the Lighting
Plan. Glare which is readily perceptible at any point at or beyond the property on which the use is
located is prohibited (LOR, Chapter 2, Section 4.N.7). Lighting shall be directed away from any
residential uses (LOR, Chapter 2, Section 4.N.7). If possible please provide photometrics as part of
your TRC plan submittals - it is much easier to identify and correct any deficiencies now than while
you are waiting on a permit!
26. It may be necessary to replace or relocate large canopy trees adjacent to light fixtures to eliminate
future shadowing on the parking surface (LOR, Chapter 23, Article II, Section A.1.b).
27. Show sight triangles on the Landscape plans (LOR, Chapter 7.5, Article II, Section 5.H.). Reference
FOOT Standard Index 546 for the sight triangles along Federal Highway. Use 35-ft. sight triangles
for Gulfstream Boulevard and Old Dixie Highway.
28. Indicate, by note on the Landscape Plan, that within the sight triangles there shall be an unobstructed
cross-visibility at a level between 2.5' and 8' above the pavement (LOR, Chapter 7.5, Article II,
Section 5.H.).
29. Landscaped areas shall be protected from vehicular encroachment by a continuous, raised curb
(LOR, Chapter 7.5, Article II, Section 5.A. and Chapter 22, Article II, Section E.)
30. Per the LOR, Chapter 7.5, Article II, Section 5.C.2. Ficus species are not permitted. Please
substitute another species.
31. The proposed Royal Palms along the east property line may conflict with existing power lines.
Please correct.
32. Phoenix Oactylifera and other plantings are proposed within the center median at the main entrance
off Federal Highway. A portion of these plantings and the island fall within the Federal Highway right-
of-way and will not be permitted.
33. The medians on Federal Highway have existing irrigation and plant material belonging to the City of
Boynton Beach. Any damage to the irrigation system and/or plant material as a result of the
contractor's operations shall be repaired or replaced to the equivalent or better grade, as approved
by the City of Boynton Beach, and shall be the sole responsibility of the developer. Please
acknowledge this notice in your comments response and add a note to the plans with the above
stated information.
'4irt,jj"
Department of Public Works/Engineering Division Memo No. 05-048
Re: Heritage Club at Boynton Beach, New Site Plan 1 sl Review
April 19, 2005
Page 4
34. Sidewalks adjacent to parking lots shall be continuous through all driveways and shall be 6 in. thick
within driveways (LDR, Chapter 23, Article II, Section P).
35. Provide an engineer's certification on the Drainage Plan as specified in LDR, Chapter 4, Section
7.F.2.
36. Full drainage plans, including drainage calculations, in accordance with the LDR, Chapter 6, Article
IV, Section 5 will be required at the time of permitting.
37. Paving, Drainage and Site details will not be reviewed for construction acceptability at this time. All
engineering construction details shall be in accordance with the applicable City of Boynton Beach
Standard Drawings and the "Engineering Design Handbook and Construction Standards" and
will be reviewed at the time of construction permit application.
UTILITIES
38. Please provide a timeline that clearly illustrates when water and sewer services will be required to
serve the proposed project. Your starting date for the timeline should be the date of City Commission
approval. Also provide milestone dates for permit application, the start of construction, and the setting
of the first water meter. This timeline will be used to determine the adequacy of water and
wastewater treatment capacity for your project upon the project's completion, so please be as
accurate as possible.
39. All utility easements and utility lines shall be shown on the Site plan and Landscape plans (as well as
the Water and Sewer Plans) so that we may determine which appurtenances, trees or shrubbery may
interfere with utilities. In general, palm trees will be the only tree species allowed within utility
easements. Canopy trees may be planted outside of the easement so that roots and branches will
not impact those utilities within the easement in the foreseeable future. The LDR, Chapter 7.5,
Article I, Section 18.1 gives public utilities the authority to remove any trees that interfere with utility
services, either in utility easements or public rights-of-way.
40. Palm Beach County Health Department permits will be required for the water and sewer systems
serving this project (CODE, Section 26-12).
41. Fire flow calculations will be required demonstrating the City Code requirement of 1,500 g.p.m. (500
g.p.m. some residential developments) with 20 p.s.i. residual pressure as stated in the LDR, Chapter
6, Article IV, Section 16, or the requirement imposed by insurance underwriters, whichever is greater
(CODE, Section 26-16(b)).
42. The LOR, Chapter 6, Article IV, Section 16 requires that all points on each building will be within 200
feet of an existing or proposed fire hydrant. Please demonstrate that the plan meets this condition,
by showing all hydrants.
43. The CODE, Section 26-34(E) requires that a capacity reservation fee be paid for this project either
upon the request for the Department's signature on the Health Department application forms or within
seven (7) days of site plan approval, whichever occurs first. This fee will be determined based upon
final meter size, or expected demand.
"
Department of Public Works/Engineering Division Memo No. 05-048
Re: Heritage Club at Boynton Beach, New Site Plan 1st Review
April 19, 2005
Page 5
44. Comprehensive Plan Policy 3.C.3.4. requires the conservation of potable water. As other sources
are readily available City water shall not be allowed for irrigation.
45. This office will not require surety for installation of the water and sewer utilities, on condition that the
systems be fully completed, and given to the City Utilities Department before the first permanent
meter is set. Note that setting of a permanent water meter is a prerequisite to obtaining the
Certificate of Occupancy.
46. A building permit for this project shall not be issued until this Department has approved the plans for
the water and/or sewer improvements required to service this project, in accordance with the CODE,
Section 26-15.
47. The City currently has sufficient water and sewer capacity to service this project, which will have an
estimated demand of approximately 36,000 gpd for potable water and sanitary sewer. Our current
capacities and commitments are as follows:
a. Potable water capacity = 27 MGD
Demand and commitments = 21.4 MGD
b. Sanitary sewer capacity = 12 MGD
Demand and commitments = 11.76
48. Improvements to the existing water and sewer infrastructure will be required as follows:
a. The on-site lift station must be upgraded or replaced so as to accommodate the added demand
and the constraints imposed by site changes. Existing gravity and pressure flows to the station
must be accommodated in the design.
b. The water system must be connected to the existing 8-in. water main located on the east side of
Federal Highway. In addition, an 8-in. water main connection must be established from the 12-in.
water main located on the west side of Seacrest Boulevard, to the existing 8-in. line that
terminates on SE 34th Ave. in the vicinity of SE 3rd Court; or an alternate route may be considered
to establish an 8-in. water main connection to the 12-in. main on Seacrest Boulevard. The intent
of the design is to establish an 8-in. loop from Federal Highway to Seacrest Blvd., thereby
assuring adequate fire protection and domestic supply.
49. PVC material is not permitted on the City's water system. All lines shall be DIP (one spur line
between building types IV & VIII reflect a PVC water line.)
50. Appropriate backflow preventer(s) will be required on the domestic water service to the buildings, and
the fire sprinkler line(s) if there are any, in accordance with the CODE, Section 26-207.
51. The LDR, Chapter 3, Article IV, Section 3(P) requires a statement be included that utilities are
available and will be provided by all other appropriate agencies. This statement is lacking on the
submitted plans.
'"
Department of Public Works/Engineering Division Memo No. 05-048
Re: Heritage Club at Boynton Beach, New Site Plan 15t Review
April 19, 2005
Page 6
52. Utility construction details will not be reviewed for construction acceptability at this time. All utility
construction details shall be in accordance with the Utilities Department's "Utilities Engineering
Design Handbook and Construction Standards" manual (including any updates); they will be
reviewed at the time of construction permit application.
LUck
Cc: Jeffrey R. Livergood, P.E., Director, Public Works (via e-mail)
Peter V. Mazzella, Deputy Utility Director, Utilities
H. David Kelley, Jr., P.E./ P.S.M., City Engineer, Public Works/Engineering (via e-mail)
Glenda Hall, Maintenance Supervisor, Public Works/Forestry & Grounds Division
Larry Quinn, Solid Waste Manager, Public Works/Solid Waste
Kenneth Hall, Engineering Plans Analyst, Public Works/Engineering (via e-mail)
File
S:\Engineering\Kribs\heritage Club @ Boynton Beach, New Site Plan 1st Rev..doc
A-q -
]lUrJ cUQucJ ({\-' \/'J~ Il ~Droc.lq Ckfj
~~L)j <t'P1(if' - ctrttS1ccl/\A'
~/\ (,\i\ \"j crt k VII \ &y1JLIJ1 C~(l
_ jlfl L L>"\ &y0 yjV'\ ~ "ill c ~ ~ lA/YI It C (I'l/\.
"\;'\c-d ~ c, ~"- . lV~~di/'\ elM D dL
---
\
[J{Ul k {J{UJ
1ST REVIEW COMMENTS
04/22/05
18
DEPARTMENTS INCLUDE REJECT
151. Indicate the location of the mailbox kiosk(s) within the townhouse area.
152. Rooftops will be treated as part of the building elevation. All rooftop
equipment must be completely screened from view at a minimum
distance of 600 feet.
153. Additional architectural detail is needed on the parking structure
elevations, in order to be compliant with the eRA design guidelines
154. Indicate the planting of St. Augustine sod in the swale areas with
appropriate irrigation.
155. Staff suggests that ingress, as well the egress indicated, be provided from
Old Dixie Highway.
156. Will the existing hedge around the southernmost wellhead be retained? If
not, it should be, at a minimum, landscaped to the extent of the one on the
west property line.
157. No l~dscape is depicted on the Landscape Plan around the lift station at the
north property line. It should be heavily landscaped due to its visibility from
Federal Highway.
158. A planting scheme involving taller shrub material than the proposed 24 inch
high hedge should be selected for the north property line. Possibly a tiered
landscape approach of different size materials may be more appropriate.
159. A full-size clubhouse/recreation building should be provided at the pool for
the townhouses.
160. The recreation space is not adequate around the pool for the townhouses. A
green, outdoor, play space should be provided to give the residents a park
setting for outdoor activities, since there is not a park in the immediate
vicinity. Staff suggests the elimination of the streets surrounding the pool
area and their conversion to park/green space, since the remainder of the
circulation pattern appears adequate.
MWRIsc
S:\Planning\SHARED\WP\PROJECTS\Heritage Club @ Boynton Beach\NWSP 05-014\1ST REVIEW COMMENTS.doc
d
~
.....
t)
~
:Ii
e5
I
:b
.....
.....
;g
o
~
o
~
-I
o
-I
~en
~~
~
m
:::0
Qo
en
m
~
m
:::0
c
m
3:
~tn
-
'1J
:::0
2
mw
OCXl
-I~
..a.
<::)
$It
..a.
Co
Cl)
...a. ......
CoCo
NN
00
....
..co
<::)
..a.
C1l
...a. ......
CoCo
NN
00
tn
o
CD
:::::
~
iil
::J
C')
CD
t7'
;;tJ
S
g
c:
~
:::r
-I
o
-I
~en
~~
~CD
me-
:::00
Qo-
en
m
~
m
:::0
c
m
3:0
~~
ctn
::0
:::0
2......
m~
ON
-I~
...a. ......
-:.....~
COCXl
cnm
...a. ......
:.:.".!:>.
NN
U)co
oc)
'TIa
::!!oc:::
OCD
m"O
~
~
~
~
CD
-
I:b
~
......
o
o
-I
S
~o--1
cOO
<::l:.E
.....c.:J
~O::T
m g
:::0 CIl
Qo CD
en~
mW
~O
me;)
:::of:
co
m)>
3:-<
~
c
-
'1J
:::0
o
c..
m
0-....1
-10
ww
00
~.....
00
00
co
~
...a. ......
w W
~~
U1tn
:::0
m
en
o
m
z
-I
)>
r
C
Z
=i
~
::J
:;.
en
c:
iii'
CIl
-
I:b
o
::J
8'
::J
I:b
CD
CIl
C')
:::r
o:::o:::oc:::o::x:
'TImmZmCD
'TI -I en =i en :::1.
n~~ Bat
mrc mCD
z
~ ::iQ
z )>5.
-I r..,-
CIl
-
I:b
o
::s
8'
::J
-I
S
~eneneno--1
c.c.c CD 0 0
<CCOl::l:.E
:J:-oOlOl-c.::l
-I CD CD Os
me-e- C
:::000 CIl
Qo__ CD
en ~
m ~
~ e;)
m )>
:::0 C
C 0
~oo ~
~;:;);:;)m
ctntnO
-
'1J
:::0
o
c..mco
~~~~......
-I~~tn~
..., ......-....1
...a. ......0......
WCXl:"'o,w
CO......CXlOCXl
o CXl-....l 0 0
~~
............ ......
oOO)co
ooo~
w ......w
N ON
:... 0) coo,:...
Ntn~ON
...a.~coo......
c:
z
=4
)>~
I)>
1-1
Om
0;::0
~."
_I
00
Z~
c:Z
zO
=40
en."
"lJ
-.,,~O
(;)1)>-1
"lJO-l)>
C<mDJ
-<;::01
m
)>
I
I." en
O,m
OO~
~~m
- ;::0
o
z
_."en
(;),m
"lJ0~
C<m
-<;::0
)>
z
::t
(")
-
"tJ
~
m
c
~
~
m
AJ
)>
Z
C
tn
m
~
m
AJ
C
m
!:
)>
z
C
tn
...
PLANNING AND ZONING
MEMORANDUM
TO: Sherie Coale, Senior Office Assistant
FROM: Ed Breese, Principal Planner
DATE: April 22, 2005
SUBJECT: Heritage Club (NWSP 05-014)
Please include the following comments in the TRC reVIew of the above-mentioned
proj ect:
1. Rooftops will be treated as part of the building elevation. All rooftop equipment
must be completely screened from view at a minimum distance of 600 feet.
2. Additional architectural detail is needed on the parking structure elevations, in
order to be compliant with the CRA design guidelines.
3. Indicate the planting of St. Augustine sod in the swale areas with appropriate
irrigation.
4. Staff suggests that ingress, as well the egress indicated, be provided from Old
Dixie Highway.
5. Will the existing hedge around the southernmost wellhead be retained? If not, it
should be, at a minimum, landscaped to the extent of the one on the west property
line.
6. No landscape is depicted on the Landscape Plan around the lift station at the north
property line. It should be heavily landscaped due to its visibility from Federal
Highway.
7. A planting scheme involving taller shrub material than the proposed 24 inch high
hedge should be selected for the north property line. Possibly a tiered landscape
approach of different size materials may be more appropriate.
8. A full-size clubhouse/recreation building should be provided at the pool for the
townhouses.
9. The recreation space is not adequate around the pool for the townhouses. A green,
outdoor, play space should be provided to give the residents a park setting for
outdoor activities, since there is not a park in the immediate vicinity. Staff
suggests the elimination of the streets surrounding the pool area and their
conversion to park/green space, since the remainder of the circulation pattern
appears adequate.
Page 1 of 1
Hudson, Dick (Orran)
From: Rumpf, Michael
Sent: Tuesday, May 10, 200512:14 PM
To: 'mweiner@zonelaw.com'
Cc: Greene, Quintus; Breese, Ed; Hudson, Dick (Orran)
Subject: RE: Gulfstream Mall-Code amendment
Mike,
Your client has this schedule but I wanted to supply it to you as well along with explanation of the time constraints,
and schedule/processing requirements.
Pre-Commission review - June 7th
CRA - project and code review - July 12th [there would not be adequate time to totally prepare the
amendment for the June CRA meeting which has been moved to June 9th].
P&D - Code review - July 26th [given the possible impact outside of the CRA jurisdication, the P&D Board
would have to review the code item. If not, the schedule could be adjusted 2 weeks].
>>processing requirements skip a CC meeting coming from the Boards<<
Commission - Public Hearing & 1 st Reading of ordinances - August 16th (August 2nd if P&D review not
required).
Commission - 2nd Reading - September 6th (August 16th if P&D review not required).
Mike, at this time, without knowing details of the amendment, I must assume that a review by the P&D Board will
be required.
Mike
-----Original Message-----
From: Michael Weiner [mailto:mweiner@zonelaw.com]
Sent: Friday, May 06,20056:13 PM
To: rumpfm@ci.boynton-beach.fl.us
Cc: RMath ias@NewCenturyCompanies.com
Subject: Gulfstream Mall
Mike:
I spoke to Quintus. He said that we might be able to address the Gulfstream Mall project administratively.
Can we meet to discuss this?
If I cannot move forward with the site plan, there is a good chance the deal will not go through.
Considering that we have a consensus on a great project, I would hate to see it disappear because of a
timing problem.
Lets meet and see what we can do to keep this one going. I really think we have our "gateway". I just
need to keep it on track. The meeting will not be long
Thanks.
Michael Weiner
5/17/2005
Page 1 of2
Coale, Sherie
From: Jason Mankoff [JMankoff@zonelaw.com]
Sent: Tuesday, April 19, 20059:47 AM
To: 'Coale, Sherie'
Cc: RMathias@NewCenturyCompanies.com; Ashlee Vargo; Michael
Subject: RE: Gulfstream Townhomes
After speaking to Sherri, she believes that as a result of the meeting last week, the plans are currently being
revised to reflect the changes discussed, including enlarging the right of way for Dixie. She is thus under the
assumption that the TRC comments will not be sent out until the revisions are submitted.
Robert, are your professionals currently revising plans as a result of this meeting?
Jason S. Mankoff, Esq.
Weiner & Aronson, P.A.
102 N. Swinton Avenue
Delray Beach, FL 33444
561.265.2666 x 303
561.272.6831 (fax)
imankoff@zonelaw.com
From: Jason Mankoff [mailto:JMankoff@zonelaw.com]
Sent: Tuesday, April 19, 2005 9:36 AM
To: 'Coale, Sherie'
Cc: 'RMathias@NewCenturyCompanies.com'; Ashlee Vargo; Michael
Subject: RE: Gulfstream Townhomes
Yes, that is the project I am referring to. Do you know what the major issues were? Thanks.
Jason S. Mankoff, Esq.
Weiner & Aronson, P.A.
102 N. Swinton Avenue
Delray Beach, FL 33444
561.265.2666 x 303
561.272.6831 (fa>:)
imankoff@zonelaw.com
From: Coale, Sherie [mailto:CoaleS@ci.boynton-beach.fl.us]
Sent: Tuesday, April 19, 2005 9:31 AM
To: 'JMankoff@zonelaw.com'
Subject: RE: Gulfstream Townhomes
Jason, do you mean Heritage Club at Gulfstream Mall? I know there was a meeting last week regarding that
project, there were some major issues that would probably invalidate the existing plans that were reviewed.
-----Original Message-----
From: Jason Mankoff [mailto:JMankoff@zonelaw.com]
Sent: Tuesday, April 19, 2005 9:30 AM
To: RMathias@NewCenturyCompanies.com; mweiner@zonelaw.com; 'Coale, Sherie'; Ashlee Vargo
Subject: RE: Gulfstream Townhomes
Sherie, Do you know when the comments for the above will be available?
Thanks,
4/1912005
FIRE & LIFE SAFETY DIVISION
0..-'
:/;ft\(
. "" "
MISSION STATEMENT
To prevent fires that result in loss of life, serious injury,
excessive property loss and business interruption; to be diligent
stewards of the resources provided; to fairly and consistently
enforce the statutes of the city and state; and to represent the
city with the utmost integrity, honor, and professionalism.
TO:
Ed Breese, Principal Planner
FROM:
Rodger W. Kemmer, Deputy Chief/Fire Marshal
DATE:
April 5, 2005
SUBJECT: NWSP 05-012
NWSP 05-013
NWSP 05-014
NWSP 05-015
Grove Plaza Parcel "B"
Peninsula
Heritage Club
Deliverance Church
The Fire Department expects to be able to maintain an adequate level of service
for the subject projects, with current or anticipated staffing. Infrastructure
requirements such as hydrants and roadways will be addressed during plan
reviews and the permitting process.
CC: Chief Bingham
F&LS Staff
File
Ci'fY OF BOYNTON BEACH, FLoRIn1\.
INTER-OFFICE MEMORANDUM
TO:
Ed Breese,
Principal Planner
DATE:
March 31, 2005
FILE: NWSP 05-014
FROM:
John Huntington, Officer
Crime Prevention Unit
SUBJECT:
REFERENCES:
Heritage Club @ Boynton Beach
Impacts of Proposed Site Plan Upon City
Services
ENCLOSURES:
I have reviewed the impact for services for the proposed project at Heritage Club @ Boynton Beach located at
3600 South Federal Hwy. (Gulf Stream Mall)
With the projected development throughout the city, an increase of 28% in population can be expected. Total
police calls for service have increased 66.8 % from 1990 - 2000.
For the purpose of this study, a statistical analysis was completed to show the percentage of increase of police
calls for service for the selected project area. A crime analysis for 2004 shows that there have been 9,814 calls
for service for zone 5 and represents 14.4% of total calls for service. There are no other existing developments
to use as a comparison for this assessment. It must be noted that this project is one of six mixed-use projects
planned for completion.
This project calls for 166 multi-family dwelling units and 19,538 sq. feet of retail, restaurant and office space.
This mixed-use project will have a direct impact on providing an adequate level of public service to this area.
The need for additional officers in Zone 5 is evident by the high percentage of calls for service that one officer
is currently handling. Due to new development throughout the city, all city services will be affected. An
increase of 12% of total calls for service can be expected due to proposed city wide growth.
Service requirements for the police department will be impacted greatly and the demand for more police
personnel and equipment will be needed to balance the increase in population.
~~["" r-, -_
{S' /rl 1[, r: :,', -.-:-'-_.'
~!i"'!,:
n I[ . ----'1' /
II! : I !Jr, : '
li \.' I -.r-
'I i '
~Ii.,_
.
o p \ i
~. J\r, TM[NT 0>. , , '
~:!:.~i
,.'~..'~.".....'
\ :-.
, . - - ~
I ,... '
(.J, j
The City of Boynton Beach
DEVELOPMENT DEPARTMENT
PLANNING AND ZONING DIVlSON
100 E. Boynton Beach Boulevard
P.O. Box 310
Boynton Beach, Florida 33425-0310
TEL: 561-742-6260
FAX: 561-742-6259
www.boynton-beach.org
To: Peter Mazzella, Assistant Director, Utilities
Nem Gomez, Interim Director of Utilities
Marshall Gage, Police Chief
Rodger Kemmer, Deputy Chief / Fire Marshal
Jody Rivers, Parks Superintendent
Cc: William Bingham, Fire Chief
Wally Majors, Parks Director
Laurinda Logan, Civil Engineer
Rick Lee, Fire Protection Analysist
John Huntington, Police Officer
From: Ed Breese, Principal Planner U!3;
Date: 3/24/05
Re: Impacts of proposed site plan upon City facilities and services
Project: Heritage Club @ Boynton Beach
File Number: NWSP 05-014
MEMORANDUM
As part of the City's concurrency requirements, the City Commission directed the Planning & Zoning
Division to report whether or not the City could maintain an adequate level of service with current
infrastructure and / or staffing levels in order to support the proposed development.
Plans for the above-mentioned project have been forwarded to your department's TRC
representative for their technical review and comment. We are requesting that you review the
proposed project for anticipated impacts to your department's level of service (as requested by the
City Commission) and provide us with your comments for direct insertion into our staff report, In
the past, you have sent us something that indicates your current staff / infrastructure would either
be able to support the proposed project or what would be reqUired to meet the adopted level of
service, Please respond no later than 2 weeks from today, Also, any recommendations that
you believe that would enhance the project are certainly welcomed, I thank you for your assistance
in this matter, Should you have any questions regarding the requested information, please do not
hesitate to call me at 742-6260.
S:\PIannlng\SHARED\ WP\AGENDAS\ TRC\correspondence\Impact Analysls.doc
Heritage Club at Boynton Beach - Gulf Steam Mall Zone 5
Report Executed By: HUNTJOHN On: 03/31/05
Records Found: 9814
i_freptname Count Percent
573 5.8%
ABANDON VEHICLE/COV 6 0.1%
ACCIDENT DUI RELATED 1 0.0%
ACCIDENT HIT & 1 0,0%
ACCIDENT HIT & RUN 17 0.2%
ACCIDENT INJURIES 2 0.0%
ACCIDENT LONG FORM 17 0.2%
ACCIDENT SHORT 8 0.1%
ACCIDENT SHORT FORM 347 3.5%
ACCIDENTAL DAMAGE 6 0.1%
ACCIDENTAL INJURY 4 0.0%
AGG. ASSAULT CUTTING 2 0.0%
AGG. ASSAULT FIREARM 3 0.0%
AGG. ASSAULT GENERAL 8 0.1%
AGG. BATTERY CUTTING 3 0.0%
AGG. BATTERY GENERAL 4 0.0%
ALARM BUS CANCELLED 6 0.1%
ALARM BUS. WEATHER 15 0.2%
ALARM BUSINESS 2 0.0%
ALARM BUSINESS FALSE 312 3.2%
ALARM RES CANCELLED 10 0.1%
ALARM RESID. WEATHER 8 0.1%
ALARM RESIDENT 3 0.0%
ALARM RESIDENT FALSE 309 3.1%
ALARM VEH GENERAL 3 0.0%
ANIMAL BITE NEIGHBOR 3 0.0%
ANIMAL COMPLAIN 1 0.0%
ANIMAL COMPLAINT 54 0.6%
ASSAULT THREAT 2 0.0%
ASST AND/OR SERV NEE 18 0.2%
ASST MTRST/TRF COMPL 127 1.3%
ATTEMPT CONTACT 5 0.1%
ATTEMPT LOC PERSON 4 0.0%
ATTEMPT LOC VEHICLE 10 0.1%
ATTEMPTED AUTO THEFT 1 0.0%
BAKER ACT 59 0.6%
BARKING DOG 16 0.2%
BURG FENCED COMPOUND 2 0.0%
BURGLARY ATTEMP 1 0.0%
BURGLARY ATTEMPT 13 0.1%
BURGLARY AUTO 104 1.1%
BURGLARY OTHER 4 0.0%
BURGLARY STRUCTURE 7 0.1%
BUS NON-FORCE ENTRY 9 0.1%
BUS SMASH & GRAB 4 0.0%
BUSINESS FORCE ENTRY 8 0.1%
CALL TAKER HAND 33 0.3%
CARJACKING 3 0.0%
CARRY CONCEAL FIREAR 2 0.0%
CARRY CONCEAL WEAPON 3 0.0%
CASE# PULLED IN 6 0.1%
CAT TYPE 10 0.1%
CHILD ABUSE 3 0.0%
CHILD NEGLECT 6 0.1%
CHILD SEXUAL BATTERY 2 0.0%
CITY ORD VIOL/OTHER 15 0.2%
CIVIL ASSIST 86 0.9%
COUNTERFEITED MONEY 2 0.0%
DEATH - DR WILL SIGN 2 0.0%
DEATH - M.E. CASE 2 0.0%
DELIVER MESSAGE 1 0.0%
DISORDERLY CONDUCT 2 0.0%
DISORDERLY INTOX 2 0.0%
DISTURB LNDLRD/TENAN 8 0.1%
DISTURBANCE CUSTOMER 29 0.3%
DISTURBANCE FIGHT 1 0.0%
DISTURBANCE JUV 1 0.0%
DISTURBANCE JUVENILE 72 0.7%
DISTURBANCE NEIGHBOR 14 0.1%
DISTURBANCE OTH 2 0.0%
DISTURBANCE OTHER 219 2.2%
DOMESTIC DISPUT 9 0.1%
DOMESTIC DISPUTE 239 2.4%
DOMESTIC VIOLEN 3 0.0%
DOMESTIC VIOLENCE 45 0.5%
ELDERLY ABUSE/NEGLEC 5 0.1%
ELDERLY FRAUD 1 0.0%
EXTRA PATROL 567 5.8%
FAIL STOP F/OFF 1 0.0%
FAIL STOP F/OFFICER 12 0.1%
FALSE IMPRISONMENT 1 0.0%
FILE FALSE REPORT 1 0.0%
FORGERY GENERAL USE 2 0.0%
FOUND PROPERTY 42 0.4%
FRAUD GENERAL 36 0.4%
GRAFFITI 1 0.0%
HOME INVASION 1 0.0%
LOITER & PROWL ADULT 2 0.0%
LOST PROPERTY 102 1. 0%
MARCHMAN ACT 7 0.1%
MISS/ADLT/ENDAG 1 0.0%
MISS/ADLT/ENDAG/SUSP 18 0.2%
MISSING JUVENILE 1 0.0%
NARCOTICS OTHER 11 0.1%
NO OFFENSE DEFINED 9 0.1%
NOISE DISTURBANCE 178 1.8%
OBSCENE GENERAL USE 1 0.0%
OBSCENE PHONE CALL 5 0.1%
OPEN CONTAINER 10 0.1%
OPEN DOOR BUSINESS 30 0.3%
OPEN DOOR RESIDENCE 14 0.1%
PHONE THREATS 18 0.2%
POLICE ASSIST - 2 0.0%
POLICE ASSIST - 911 235 2.4%
POLICE ASSIST DCF 84 0.9%
POLICE ASSIST 0 15 0.2%
POLICE ASSIST OTHER 939 9.6%
POLICE ASSIST STANDB 30 0.3%
POLICE INC REPORT 2 0.0%
POSS CONTRABAND 58 0.6%
POSS NARCOTIC PARAPH 13 0.1%
POSS/ALCOHOL MINOR 1 0.0%
PROSTITUTION OTHER 2 0.0%
PROWLER COMPLAINT 1 0.0%
R/A WITH VIOLENCE 1 0.0%
R/A WITHOUT VIOLENCE 22 0.2%
REC STOLEN PROPERTY 6 0.1%
REC VEH/OTHER JURIS 19 0.2%
REFER OTHER CAS 5 0.1%
REFER OTHER CASE 219 2.2%
RES FORCE ENTRY DAY 10 0.1%
RES FORCE ENTRY NIGH 5 0.1%
RESD NON-FORCE ENTRY 12 0.1%
RESIDENCE - DEL 2 0.0%
RESIDENCE - DELAYED 38 0.4%
ROBBERY ATTEMPT 2 0.0%
ROBBERY OTHER 3 0.0%
ROBBERY STRONGARM 17 0.2%
ROBBERY THREAT WEAPO 2 0.0%
ROBBERY/CUT INSTRUME 1 0.0%
ROBBERY/FIREARM 9 0.1%
RUNAWAY JUVENILE 23 0.2%
SALE/CONTRABAND 2 0.0%
SEIZURE OF LIC TAG 2 0.0%
SELECTIVE ENFORCEMEN 93 0.9%
SEX CRIME 3 0.0%
SEX OFF VST CNT 2 0.0%
SEX OFFNDR VST ATMPT 4 0.0%
SEX OFFNDR VST CNTCT 1 0.0%
SEX OTHER 1 0.0%
SEXUAL BATTERY 5 0.1%
SHOPLIFTING 106 1.1%
SIMPLE ASSAULT/VERBA 2 0.0%
SIMPLE BATTERY 80 0.8%
SOLICIT FOR PROSTITU 2 0.0%
STANDBY FOR FD 11 0.1%
STOLEN VEHICLE 65 0.7%
STOPPED FOR DUI 35 0.4%
SUSP DRUG ACTIVITY 1 0.0%
SUSP INCIDENT 388 4.0%
SUSP PHONE CALL 10 0.1%
SUSPICIOUS PERS 8 0.1%
SUSPICIOUS PERSON 576 5.9%
SUSPICIOUS VEHI 8 0.1%
SUSPICIOUS VEHICLE 237 2.4%
THEFT ATTEMPT 1 0.0%
THEFT AUTO ACCESSORI 45 0.5%
THEFT OF BOAT 1 0.0%
THEFT OTHER 195 2.0%
THEFT SRVC/DEFRD INN 8 0.1%
THREAT/DESTRCT DEVIC 2 0.0%
THREATS OTHER 3 0.0%
TOOK PROPERTY UNDER 1 0.0%
TRAFFIC COMPL 0 6 0.1%
TRAFFIC COMPL OTHER 470 4.8%
TRAFFIC STOP MO 17 0.2%
TRAFFIC STOP MO CODE 1153 11.7%
TRESPASS PROPERTY 7 0.1%
TRESPASS STRUCTURE 7 0.1%
TRESPASS WARNIN 1 0.0%
TRESPASS WARNING 129 1.3%
TRF COMP/RECLAS 1 0.0%
TRF COMP/RECLAS ACCI 33 0.3%
TRF COMPL/VEH TOWED 11 0.1%
UNWANTED GUEST 2 0.0%
UTTER FORGED INSTRUC 9 0.1%
VANDALISM BUSINESS 13 0.1%
VANDALISM RESIDENCE 15 0.2%
VANDALISM/ AUTO 58 0.6%
VANDALISM/OTHER 25 0.3%
VICE CONFIDENTIAL 5 0.1%
VIOL LIQUOR LICENSE 1 0.0%
VIOLATION OF CURFEW 2 0.0%
WAR BK PCKUP ATTEMPT 19 0.2%
WARRANT ADULT 96 1. 0%
WARRANT/PU JUVENILE 3 0.0%
WEAPONS OTHER 1 0.0%
WELFARE CHECK 33 0.3%
Johnson, Eric
From:
Sent:
To:
Subject:
Hudson, Dick (Orran)
Tuesday, March 29, 2005 9:20 AM
Johnson, Eric
RE: office or retail
Since we are not encouraging a large commercial node in that area, I don't care. I would expect that not all the
commercial space will be converted to office uses, but there are some office uses that could be better served in a ground
floor location.
From:
Sent:
To:
Cc:
Subject:
Johnson, Eric
Tuesday, March 29, 2005 8:41 AM
Hudson, Dick (Orran)
Breese, Ed
office or retail
Dick,
I'm reviewing Heritage Club. They are proposing a small office (1,380 square feet) on the ground floor. I know Mixed-Use
districts discourage and maybe even prohibit office uses on 1 st floor, but PUD doesn't regulate it. Do we care if office is
proposed on 1 st floor for this project? Speak now or forever hold your peace. Thanks, Eric
1