REVIEW COMMENTS
ENGINEERING DIVISION
.5M~
() J11 0-& /~ ~G'V/tJ
l' uti ''R-.
TO:
TART MEMBERS: (Hand delivered) C.
Ed Breese, Senior Planner / Kevin Hallahan, Forester/Environmentalist
John Huntington, Sergeant, Police Department
H. David Kelley Jr., City Engineer
Rick Lee, Fire Plans Reviewer
Timothy K. Large, Building Code Administrator
Lourinda Logan, Senior Engineer (including stormwater management plan).
Jody Rivers, Parks Superintendent
Date: September 13, 2005
FROM: Ken Hall, Engineering Plans AnalYStllnSpecto@
RE: Plat Review - Knollwood PUD
Here is your copies of the plat, survey and construction plans for the subject development.
Please send me your comments (or lack thereof) by September 28. As always, we
appreciate your timely response.
c: Jeffrey Livergood. Public Works Director. (memo only)
DEVELOPMENT DEPARTMENT
PLANNING AND ZONING DIVISION
MEMORANDUM NO. PZ 05-194
TO:
Ken Hall
Engineering Technician
Michael W. Rumpfi' 0 V'
Planning and Zoning Director
Ed Breese ~
Principal Planner
THROUGH:
FROM:
DATE:
September 28, 2005
SUBJECT:
Knollwood PUD - Plat Comments
I have reviewed the above referenced plat and have the following comment:
1. Plat (Sheet 4) - Remove the roadway terminus between Lots 30 & 31 to avoid encroachment into the
10 foot Landscape Buffer Easement (L.B.E.) along the east plat line against Nautica PUD, consistent
with the approved site plan.
2. Plat (Sheet 4) - Remove the roadway terminus between Lots 42 & 43 to avoid encroachment into the
10 foot Landscape Buffer Easement (L.B.E.) along the south plat line against Sunup Grove
Subdivision, consistent with the approved site plan.
3. The existing 20 foot ingress/egress easement between Lots 33 & 34 of Sunup Grove Subdivision that
provided access to the five (5) acre tract that was added to Knollwood Groves to create the
Knollwood PUD, would now terminate at the rear of Lot 38 of the Knollwood PUD Plat. Is there
some mechanism to abandon this easement?
4. Condition of Approval (COA) # 40 for the Knollwood PUD requires conversion of the landscape
"easements" to "tracts" to ensure appropriate maintenance by the HOA. On Sheet 1 of the Plat, Item
10 listed under "Description, Dedication and Reservation", there is language discussing HOA
responsibility with regard to this issue. Is this sufficient?
~
Development Department
Memorandum
To:
Ken Hall
Engineering Technician
\<~*
From:
Kevin John Hallahan, Forester / Environmentalist
Subj ect:
Knollwood PUD-Plat comments
Lake Management Plan (Upland and Littoral plantings)
Incorporation into HOA documents
Date:
October 11, 2005
Tracts L-l and L-2 Narrative comment #2
The applicant should provide a copy of the Lake Maintenance Plan document. This document
should be referenced in the HOA documents in the section pertaining to proper maintenance of
the lake. This document is referenced in the plat narrative in the tract pertaining to maintenance
ofthe lake.
xc: Kjh
G file / Eng.
xc: kjh
7.E.l
KNOLL WOOD II (NWSP 05-017)
NEW SITE PLAN
DEVELOPMENT DEPARTMENT
PLANNING AND ZONING DIVISION
MEMORANDUM NO. PZ 05-110
STAFF REPORT
FROM:
Chair and Members
Planning and Development Board and
Mayor and City Commission
Eric Lee Johnson, AICP y Y
Planner 1J
Michael W. Rumpf
Director of Planning and Zoning
TO:
THROUGH:
DATE:
June 23, 2005
PROJECT NAME /
NUMBER:
Knollwood PUD / NWSP 05-017
REQUEST:
New site plan approval to construct 148 single-family homes on a 36.17-
acre parcel in the PUD Planned Unit Development zoning district
PROJECT DESCRIPTION
Property Owner: Multiple owners
Applicant! Agent: DRHI, Inc. / Julian Bryan & Associates, Inc.
Location: Southwest corner of the intersection of Lawrence Road and the LWDD L-20
Canal (Approximately 1 mile south of Hypoluxo Road) (Exhibit "A'')
Parcel Size: 36.17 acres
Existing Land Use: Low Density Residential (LDR)
Existing Zoning: PUD Planned Unit Development
Proposed Use: 148 single-family homes
Adjacent Uses:
North:
Right-of-way of the LWDD L-20 Canal then single family residential
development (Lawrence Oaks) designated Low Density Residential and
zoned PUD Planned Unit Development;
South:
To the southwest, developed residential property lying in unincorporated
Palm Beach County designated LR-3 (3 du/ac with PUD zoning) and zoned
AR Agricultural Residential. To the southeast, developed single family
residential (Nautica) designated Low Density Residential and zoned PUD
Planned Unit Development;
Staff Report - Knollwood PUD (NWSP 05-017)
Memorandum No PZ 05-110
Page 2
East: Right-of-way of Lawrence Road then single family residential development
(Citrus Glen) designated Low Density Residential and zoned PUD Planned
Unit Development; and
West: To the northwest, vacant land in unincorporated Palm Beach County
designated MR-5 Single Family Residential (5 dujac) and zoned AR-
Agricultural Residential. To the southwest, single family residential
development (Sunset Cay) also located in unincorporated Palm Beach
County, designated RTU Residential Transitional Urban district.
BACKGROUND
Site Characteristic: According to the survey, the subject property is comprised of two (2) lots and is
the site of the Knollwood Groves orange grove. The parcel contains several
buildings and respective parking areas. Currently, Miner Road terminates at
Lawrence Road; however, the County's Long-Range Transportation Improvement
Plan calls for a right-of-way of 110 feet along the north boundary of the subject
property. In deference to that plan, the developers have set aside a 110-foot wide
strip of property along the north boundary of the parcel. The survey shows a large
pond is located at the northeast corner of the property. The highest elevation is
18.4 feet above sea level, located at the center of the property. A four (4)-foot tall
chain link fence runs along the east property line.
Proposal:
Mr. Julian Bryan, agent for the property owners, proposes to develop the subject
property with 148 (Zero Lot Line) single-family dwelling units on 36.17 acres. A
large portion of the property (+j- 30 acres) had already been approved for Low
Density Residential (LDR) land use and PUD Planned Unit Development zoning.
The developer is proposing to annex (ANEX 05-002) an additional 5 acres of land
and rezone (LUAR 05-006) it to PUD to accommodate additional units. Single-
family homes are permitted uses in the PUD zoning district. The maximum density
allowed by the Low Density Residential (LDR) land use classification is 4.84 dujac,
which would provide the developer a maximum of 175 units. The project would be
built in one (1) phase.
ANALYSIS
Concurrency:
Traffic:
A traffic impact analysis was sent to the Palm Beach County Traffic Division for
concurrency review in order to ensure an adequate level of service. On April 12,
2005, the Palm Beach County Traffic Division determined that the proposed
residential development meets the Traffic Performance Standards of Palm Beach
County, upon provision of an exclusive left-turn northbound lane on Lawrence
Road. The County approved the site for 146 units but the site plan proposes 148
units. Therefore, no building permits would be issued until the applicant submits a
revised analysis and the County reviews and approves the additional two (2) units
(see Exhibit "C" - Conditions of Approval).
Utilities:
The City/s water capacity, as increased through the purchase of up to 5 million
Staff Report - Knollwood PUD (NWSP 05-017)
Memorandum No PZ 05-110
Page 3
gallons of potable water per day from Palm Beach County Utilities, would meet the
projected potable water needs for this project. Local piping and infrastructure
improvements may be required for the project, dependent upon the final project
configuration and fire-flow demands. These local improvements would be the
responsibility of the site developer and would be reviewed at the time of
permitting. Sufficient sanitary sewer and wastewater treatment capacity is
currently available to serve this project, subject to the applicant making a firm
reservation of capacity, following approval of the site plan.
Police/Fire: Staff reviewed the site plan and determined that current staffing levels would be
sufficient to meet the expected demand for services.
Drainage: Conceptual drainage information was provided for the City's review. The
Engineering Division has found the conceptual information to be adequate and is
recommending that the review of specific drainage solutions be deferred until time
of permit review. All South Florida Water Management District permits and other
drainage related permits must be submitted at time of building permit (see Exhibit
"C" - Conditions of Approval).
School: The School District of Palm Beach County must approve the project for school
concurrency prior to the issuance of any building permits (see Exhibit "C" -
Conditions of Approval).
Driveways: The plans show that one (1) point of ingress I egress is proposed at the southeast
corner of the property, connecting with Lawrence Road. The County is requiring a
deceleration lane on southbound Lawrence Road. The entrance lane into the
development would be 22 feet in width. The exit lane would be 15 feet in width
and they would be separated by a 10-foot wide landscaped median. The exit lane
would only allow for right-turn only traffic movements onto Lawrence Road.
According to the Typical Road Section shown on sheet 2 of 4, the private rights-of-
way, internal to the development would be 40 feet in width. Each side (or half) of
this right-of-way would consist of 11 feet of asphalt, two (2) feet of valley gutter
(for drainage purposes), a three (3)-foot wide swale (grassy area), and a four (4)-
foot wide pedestrian sidewalk. The plans proposed a gated entrance. Further
details of the gate would be required at the time of permitting (see Exhibit "C" -
Conditions of Approval). The plans show a 20-foot wide stabilized emergency
access point is also proposed along Lawrence Road. This access point would be
used for emergency purposes only, and only if the main entrance is obstructed.
Parking Facility: Two, three, four, and five bedroom dwelling units require two (2) parking spaces
per unit. The project proposes 148 residential units and therefore, would require
296 parking spaces. Each unit would have a two (2)-car garage. According to the
floor plan (sheet A-l), the garages would be dimensioned a minimum 19 feet in
width by 19 feet in depth, large enough to accommodate two (2) vehicles. This
provision equals the required parking. Also, the "Typical Lot Detail" (sheet 1 of 1)
indicates that the driveways in front of each unit would also accommodate two (2)
parked cars. The detail shows the driveways would be dimensioned 18 feet in
width by 22.5 feet in depth. The plan would provide a total of 612 parking spaces.
Staff Report - Knollwood PUD (NWSP 05-017)
Memorandum No PZ 05-110
Page 4
Landscaping:
Nearly two (2) acres of the subject property would be set aside for buffer and open
spaces. The landscape data on sheet 7 of 10 indicates that the project would have
a total of 1,234 trees and 15,360 shrubs I groundcover. Over 50% or 8,056 of the
15,360 shrubs I groundcover would be native. The landscape plan indicates that
62% or 767 of the trees would be native (see Exhibit"C" - Conditions of Approval).
A total of 60 existing trees would be relocated elsewhere on-site. They include the
following species: Gumbo Limbo, Sausage Tree, Live Oak, Laurel Oak, African
Trumpet tree, and Cabbage palm trees.
The plans proposed landscape buffers around the entire development. In order to
ensure proper maintenance of the buffer areas, staff recommends converting them
from landscape "easements" to "tracts" that would be owned and maintained by
the Home Owners' Association (see Exhibit "C" - Conditions of Approval). The
east (front) landscape buffer along Lawrence Road would be 30 feet in width. A
decorative wall is proposed within the center of this landscape buffer. It would be
comprised of three (3) different parts, namely, a concrete-block-steel portion, a
decorative stone finish portion, and a black picket fence portion. An assortment of
trees and shrubs are proposed along both sides of the wall. They include the
following: Ligustrum Tree, Live Oak, Royal palm, Bismark palm, Cabbage palm,
Dwarf Yaupon Holly, Snow Bush, Redtip Cocoplum, Dwarf Podocarpus, Crinum Lily,
and annuals.
The north (side) landscape buffer proposed along the 110-foot set aside for the
planned Miner Road extension would be 20 feet in width. The landscape plan
(sheets 2, 3 of 10) shows a chain link fence and a row of Redtip Cocoplum are
proposed along the northern edge of this buffer. The species of trees would
include the following: Sweet Mahogany, Dahoon Holly, Cabbage palm, Gumbo
Limbo, and Live Oak. Staff recommends that where possible, the shade tree
spacing shall be no more than one (1) tree per 25 lineal feet. The area set aside
for the Miner Road extension would be sodded and irrigated until the time the
County makes the necessary improvements (see Exhibit "C" - Conditions of
Approval).
The west (rear) and south (side) landscape buffers would be 10 feet in width. A
row of trees is proposed within these buffers. They include the following: Gumbo
Limbo, Sweet Mahogany, and Cabbage palm. Likewise, a row of Redtip Cocoplum
is proposed along the west and south property lines. To provide immediate
buffering, staff recommends that these perimeter landscaped buffers utilize taller,
more mature canopy trees behind all two story models, to soften the height against
abutting single story residences. For example, the trees should be installed at 16
feet in height where two (2) story buildings are constructed (see Exhibit "C" -
Conditions of Approval). The City's PUD regulations require that "peripheral yards
abutting other zoning districts shall be the same as required in the abutting zone".
The southwest edge of the subject project abuts an existing, older residential
neighborhood built under the County's AR zoning district regulations. These
existing properties are larger than the proposed yards, with rear yard setbacks that
vary between approximately 26 feet to 40 feet (estimated). Therefore, increased
Staff Report - Knollwood PUD (NWSP 05-017)
Memorandum No PZ 05-110
Page 5
compatibility with the adjacent properties (where abutting AR zoning district) is
required. This can be accomplished by either increasing the building setbacks of
the abutting lots (Lots 31 through 42), increase the size of the buffer width (from
20 feet to 25 feet), and I or significantly increase the plant material proposed
within the 10-foot wide landscape buffer (i.e. variety of canopy trees spaced no
greater than 20 feet apart combined with lower vegetation to buffer heights from
(four) 4 feet to six (6) feet (see Exhibit "C" - Conditions of Approval).
Varying planting schemes are proposed and the scheme is dependent upon the
style of the house proposed on each lot. The Typical Unit Landscape Plan (sheet 8
of 10) indicates that each unit would have a Live Oak planted within the front yard.
A row of Viburnum hedges would screen the air conditioner units, which are
proposed along the sides of the houses. The Landscape Quantities Table indicates
the following species: Live Oak, Queen palm, Alexander palm, Pygmy Date palm,
Florida Royal palm, Montgomery palm, Foxtail palm, Silver Buttonwood, Redtip
Cocoplum, Red Crinum Lily, Japanese Fern, Pink Ixora Jatropha, and Ligustrum.
Building and Site: As previously mentioned, the maximum density allowed by the Low Density
Residential (LDR) land use classification is 4.84 dwelling units per acre, which
translates to a maximum of 175 units. The site plan proposes a total of 148 zero-
lot line units. The site plan tabular data (sheet 1 of 4) indicates that the lots would
account for 49% of the entire property. The private roads would account for 14%
of the site. Nearly five and one-half (5112) acres are set aside for potential future
right-of-way purposes. The development's recreation area would account for 2%
of the site. This 0.75-acre recreation area would accommodate swimming pool, a
1,797 square foot cabana I veranda facility, and a tot-lot. Two (2) large lake I
water management tracts are proposed, in part, for storm water retention areas.
These tracts would account for 14% or 4.93 acres of the entire site.
The Typical Lot Details indicate that the proposed lots would be 45 feet in width.
The interior lots would be 105 feet deep and perimeter lots would be 115 feet
deep. The proposed building setbacks are as follows: Front - 22.5 feet minimum,
25 feet maximum, Side - 10 feet and zero (0) feet on the other side. The rear
building setback would be 10 feet for interior lots and 20 feet for lots proposed
along the perimeter. The proposed building setbacks are consistent and
comparable with the building setbacks in the adjacent Planned Unit Development
(PUD) residential communities.
The Typical Lot Details illustrate the proposed placement of the house within each
respective lot. The applicant informed staff that the "building envelope" as
illustrated on the detail would not represent the walls of each home. Rather, the
"building envelope" only depicts each lot's minimum setback requirements.
Therefore, the proposed houses, which would be smaller than the "building
envelope", would be placed further away from the property lines, such as long as
its placement would meet all other minimum setbacks. For the perimeter lots, the
detail shows that the 20-foot wide rear building setback would consist of a 10-foot
wide landscape easement (where the buffer trees are proposed).
Staff Report - Knollwood PUD (NWSP 05-017)
Memorandum No PZ 05-110
Page 6
The applicant is requesting provisions for swimming pools and screened-roof
enclosures within the rear yard. No solid-roof enclosures are proposed outside the
building envelope. Staff has no objection the allowance of pools and screened
rooms provided that the landscape buffer would remain intact. Staff would object
to solid-roof screened enclosures that encroach into the minimum rear setback.
Staff recommends that the height of the screen enclosures be limited to the mean
height of the house on which the structure is proposed (see Exhibit "C" -
Conditions of Approval). The elevations show that the mean height of the two (2)
story homes would be 25 feet - seven (7) inches tall and the peak of the roof
would be 29 feet - two (2) inches tall. The maximum height in all residential
zoning districts except R-3 Multi-family Residential is 30 feet. On interior lots,
screened enclosures would have a five (5) foot rear setback and swimming pools
would have a seven (7) foot rear setback. On perimeter lots, screened-enclosures
would have the same rear setbacks (from each individual rear lot line) but would be
further separated from the perimeter (of the entire PUD) by a 10-foot wide
landscape buffer.
Design:
The City has reviewed and approved many different residential projects over the
past several years (i.e. Anderson PUD, Serrano PUD, The Harbors, Villas at
Quantum Lakes, Arbolata, Jefferson at Boynton Beach, Kensington Place). With
the exception of Anderson and Serrano, most of the newer projects have been
townhouse developments. Associated with the proposed type of single-family
residential development are a wide variety of possible building designs (i.e.
contemporary, traditional, Spanish-Mediterranean, etc.). This project would be
considered as more of a mixture of "contemporary and Mediterranean"
architectural style, similar to many zero-lot line communities throughout South
Florida. The homes would be either one (1) or two (2) stories tall. The proposed
roofing material would be Spanish S-tile roof. The elevations show that the
exterior finish of the walls would be textured stucco. The applicant is proposing a
variety of colors schemes. The colors are as follows:
Scheme Body Color Trim Color Front Door Color
1 Restorative CW025W Spicenut 8755A Winestain 8386N
lR Spicenut 8755N Restorative CW025W Winestain 8386N
2 Tequilla 8672W Wood let 8685D Mansard Stone
8635D
2R Wooldet 8685D Tequilla 8672W Mansard Stone
8635D
3 Stucco Greige 8693M Floral White CW033W Black Metal 8796N
3R Floral White CW033W Stucco Greige 8693M Black Metal 8796N
4 Desert Tumbleweed Moose Paint 8715D Wayfarer Grey 8535D
8723M
4R Moose Paint 8715D Desert Tumbleweed Wayfarer Grey 8535D
8723M
5 Desert Fawn 8222W Beaver Creek 8765D Dark Colossus 8526A
5R Beaver Creek 8765D Desert Fawn 8222W Dark Colossus 8526A
6 Saltbush 8183M Weaverbird 7760W Manganese 8826N
6R Weaverbird 7760W Saltbush 8183M Manganese 8826N
Staff Report - Knollwood PUD (NWSP 05-017)
Memorandum No PZ 05-110
Page 7
The project proposes a variety of house style types, ranging from three (3) to five
(5) bedrooms with air-conditioned living areas ranging from 1,952 square feet to
3,054 square feet. Staff has no objections to the proposed building colors,
architectural style, or roof types.
Signage:
Project development signs are proposed on each side of the main entrance. The
ledger-sized page of the sign shows that it would be 20.25 square feet in area and
multi-colored. Its colors would be consistent with the building colors proposed
throughout the community. The sign face would be placed in between two (2)
decorative columns on the C.B.S. wall proposed within the front (east) landscape
buffer.
RECOMMENDATION:
Staff has reviewed this request for new site plan approval and recommends approval, contingent upon the
approval of the corresponding petitions for annexation (ANEX 05-002) and rezoning to PUD (LUAR 05-
006), and also subject to satisfying all comments indicated in Exhibit "C" - Conditions of Approval. Any
additional conditions recommended by the Board or City Commission shall be documented accordingly in
the Conditions of Approval.
S:\Planning\SHARED\WP\PROJECTS\Knollwood Groves PUD\NWSP 05-017\Staff Report.doc
""',. '., ,"
,...-c.t',.-....
~ ~ "'~..- .,' ." .",...." ..N.:,~....;
'. ~ =.., ,..~.!,..".._.. ,.. .,.;o,_.~...~=.."':...r,-,~....,.'-..e.- ...~_,"" .~,!'''7'' ~. 9'~
"~
Knollwood Grovect PUD
Exhibit A
n,
-..L.W.Y
~ J=
...
- ...,
..., ~~ 5
-
::J~ I-
r
--'I~__r-).(
~~
< ~ ~
~ H ~
/111111 III It! ~
"\
/"'-.
"
co
.M~I
1'-'......
t-"\. I 'I 'I .
Z -""Ll
i- ~ ~ ~
'.-
IH_TaII .00UI&A
---
A II
11111111
~
r==
- -
,:: L
=1
~ -:j ~ "'\..l
l ~~~I~
TH A ~
.m I I
-"ig m ~~
L~1 _, ~.~ "~~
~
rrrn ~u ~q
yo
Ir-
'-'
~
~
.Im..... .
I U-~
t-..
t-
OTH
II 11--1
II LjJ JE:!:4I.
/Il Till II~R
II 111111 7
KDlaKILL ~D ""
-=, .....,.,.;,l~ +
AA08 M'fIUCUlIC
....-.- .-.-.-.-.
~~-
1=1= ~.... ~
t:::~ ...& 1
- Jn~
~tIt In
)'f~! ..., 7
~ \..... R I
~ llij =
II I
/1111111: II
IUN TOP
~
.....
11..1..1.
I I
'f
~
'" Ie:
:-'=
-
_n..
......... .....: "'8'"
,
"'" ,II/lIT
-S 1=
II JIl{' I I I I 1/ 1 "lIl
1,100
650
o
1,100 Feet
--.......-
. .....&_........,...---...._....._......._....-.........~_.._-_..................
--....1.. ...... .....-......_____.0#_........ ...............
)..
aull TIUI&
IUN
f
I II
N
A
--..
41
40
39
Ul 38
C
Z
C 37
-u
Co 36
Z::o
::00 35
"'<
8'" 34
::oUl
Oc 33
"'co
~o 32
:::;
Ul 31
0 30
Z
29
EXHIBIT B
SKETCH AND LEGAL DESCRIPTION
(NOT A SURVEY)
z
~ -z- ~
o \.fl ~ '-J lOo
()l 0"-
()l (J t'l \.fl ~ (Jl
c.ii ~~ ~1O
N 0- eN c;j
-z-:>> -z- --t::::
..->% <:
vi-:=:'" <:
I:>>
~~
I
K-::::
~K-
f'Tl
'-J
-"
'-J
-"
-"
NOOO 34'2S"E
28 332.99'
)>-4-
-40?
-i-l&;
II -
Ui"'I
-U",S
O)>C
Z~Ul
-4
-UZ
"
)>r:::
-IZ
'"
o
Z
'"
tf)
(Xl
-"to
~ 0
O()l
!'JtO
(J)-
'-Jt.N
-.j::.
- -,
II
I
;3 II
fi II
-4 I
:iE c:i II
II
II
~I
TRACT "8"
UNPLATTED
OOOTOS"W
961.74'
628.00'
"0-8"
101
II 100
~ II 99
! ~ 1198
i 111 97
: ~II 96 _;::
I 111 95 ~~
~ : III 94 ~::o
~:1 III 93 ~b
~ ~ III 92 ~ ~
~q 11191 ~~
~~ 11190 ~~
~ r1 III 89 ~ .j>.
,. I 88
q "I 87
. III
N () II 86
~ ~ 11185
:--J)> II'
~ '1 III
, III
: enlll 81
I ~1I1 80
: :;;:11-7-9
I :vII 78
: :11: 77
r ~II 76
, 0 I
i :r.1I1 75
, ~1'174
II 73
11172
11171
11170
,,169
11.68
II 67
1166
jl165
~1164
~1163
91162
111 TRACT "R-l"
ACT "P 3"
~-z-
O~
..--\-
--- :>> -z-
0%
-z- ~
"->:>>..-7
~t'\
K-
0'::::
~K-
~
~-z-
(J-':::::"
.-\ t'l..-7
O~
-z-~
:>>
~~
I
K-"->
0'-
IK-
K-
~
Z
,
z
'"
Ul
'"
o
-I
o
Z
GJ
,
.j>.
[Jl
.j>.
tv
40'
.j::.
o
E.LiNE SECTION "13-45"-42
502003'29"W
lAWRrnC~ROAD- --
JOB NO.
04174
c::o
.,
"'::;;
"'1J""1J""TI-O"""U-OO$:rr
. 0. . . . . o. .
Vi- CDmOO::OZl/)CD
~ ;> OCDCD
';J
C:::lJQ:I-o-o-o-o-o-oos::::rr
-I.......... :::0)>)>100110--
-C1S::::00il>--IlZ0n
rIl>"TlfTl$:--1ZZ-CfTlfT1
---l-ofTl -l-lOS:::ZZ
----l1""TIf./) corn -[Tllf)(/)
-<Orr1(/1 fTlOOOl>ZfTTrrl
11::0- :1>011",-100
fTll 0 ();::":
l>::E Z :r: ()co::o ViCD
lIi)>)> QrTlfTl CC
fTl-< r () s::::c>o ::Olf)
;:: 0 ;::-0 <-
fT1 l/) C fTlZ::O rrlZ
Z C Z zzo -<ro1
--I ::0 --I n-Vl 0(1)
< -< f'TlZ ::O(j)
'" ;::C>CD
-< ::0 fT1 0
o fTl Z 0
:::0 n -I ^
o
::0
o
Vl
E. L1NES(C"TION" 12-45:42 -"
Proj ect Nome. KNOLL WOOD
OVERALL PROPERTY
JSH
JS
SCALE. 1"-400'
DATE. 4/05/2005
no )>
~~ OJ
. ;> OJ
:::0
m
<
)>
-i
o
noZ
~~ en
zn
"'::0
::OfTl
-4
'"
SHEET 2 OF 2
g~ ~~~ m ~~~~~ i ~~~j ~
~~ ~~~ ~ ~~~!~ ~ ~II~ ~
Ii ~! I ~h~ ~ ~~i~ rn
L o !!I ~~~~ ill~~';; (")
8i ~fll ~~j~ ~..~~ ~
i~ Sill io~j ~~~ -i
;~ ~~ - ~~iz ~flll 0
~i bo ~~~ ~~ z
~~ ~.~ !l
j ~~ ~~~~ ~~~
E~~! s~si fll!lb
5~. - ~o ..~
~~ m8 ~b~ ~b~
~= ~~ ~~i~ ~~~
~ S~ gO m gzj
z ~~ ~~~ ~M
"''l ~ ~ ~~
% - ~~
nn~ ~~
~~~~. b ~
" ~ q .. .; ~~
~ n ~ Z .. t
"t..,... "l;;: ~t
, I
~ ~ '4 ~ liS ~i
.... ""..... 0"
~ '"' ~ ~ ~ ;::~ ~
il "~
~~
~~ ~i ~~ ~~ ~
~~ ~I<: ~~ 1Ii~
~~ r>j;;l ~~ Rl~
i~ ~g ~ ~~
1Ii~ c~ ~~ ~.
~~ ~~ ~~ ~~
~: ~~ ~~ ~~
~rll ~~ ~.. ~~
~~ ~~ ~~ ~
~~ ~~ ~~ ~~
~il ~~ ~: ~~
!ii! ~ -II: ii:....
~,~ e M
~ ~~ S ~~
; ~~ r: ~
~ ~ \1
~
~
~ I
II ,p
~ ~~I ~~
~ ~I ~~
I ~, ~q <l'
~ ~~ ~~
S~ S
~'
......
0 ~ ~. ; ~! :.:~
." ii' .
~
EXHIBIT B
ac!:B>~~:IIb!!!
~~!6?;t"T1~~~nl
Pi~!l!~~~
m~i;lOn~~
U" ~ ~ ~i'i!Jl
~U~q~1
Ii 0 !l! .
.. ~ g ~ g
.. ~ ~
.. ~
.m
~ - ~ !:1 ~ J! !:1::i "
~i~~~~i@~
~~~~~~~~
~
:"II>>>
~~~
'IIQ~
"'0"
ij10m
c:
II.
=J
"
'"
" 3~
lJlill~:'
~;;;~~
~m!l!_:S
2i:
"
l!
~; ""
i
~
o
S
o
..
iii
"
'"
~
....
:JI o:u
tlLu~P
is~il~
~~~_il
::ti:
"
l!
;~ ~~ ~j ~n~~ ~~~~n ~ ~ 2l1~
,,~ :!;" mO r <z_C 6m:tm" z 'l! ~ Ii ~
::l~ ~~ ~~ :Ii ~~~"a~ Q r- I!l 2J (;)
~E ~! g51 ~~~ g~1;~m i 15 0 0
a~ ~: ~g ~j!!m ill~~~"~ ~ ;;j ~ ~m
~% 3m 0: mz~ g:S i g m ~
"6 3~ 1aiil ~f~ ~~5;!~!i1 !!l !!l
~~ fR~ ii ~~m oljOm"n ~ i ~
:S ~ ~~6 ~~;!;!;8 ill z z
lilm ~ gz-g ii m-8 5>:~:U" CO) Q
:u ~8z iil5m~
~ ~ ~~ 8~" "~~~~
:if Jit i~ o!~ Q8:::1 (') ~ 51! ~ ~ ~ ,.. :"'" ~ pi ~ i';
o c em ~~~ Q.!!:!i~!D ... l!S E ti t 8 f: 01 8 ~ :u
~ ~ ~~ >m~ ~~~~. i ~ ! ~ ~ ~ ~ l; ~ ~ ~ Dl
nt iit 0 ~~"' G ~ a m
~ ~ i~ ~.~ ~~~~ ~ N~
~ ~ ~~ ~~8! ~~
m () gO ?iffi ~ ~~m
m ~ ~~ ::10 i ~""
s ~ ~ ~ ~~
~ ~ ~ ~~~~J~jj~ ~
Q
J B A Julian Bryan & Associates u<t>_n d_.'"n .._ "'_nnln.. ..-zon'n.. "~,,.._ _n_'"",_ m_""_< "-_.'blll", "o_~~_n_' ..~~_In"
MASTER PLAN I SITE PLAN fTTT111ITiiiI
BOYNTONBEACH,FLORIDA KNOLLWOOD GROVES P.U.D. D.R HORTON HOME ~
- . . --' ,...,...;;,'f"
a ~! en ~s ~~
~ z nt ~ ~~ ~~
~~~~~ ~~
E )>
li ,..-I
~ )>
~
~~ U
o 0 ~ ~
ji!llzz
21 M ~ Q
N ~ !i1 ~
~o~c
~ ~ ,. ~
'"
l~: ~ ii J
~6~i!ij;l~~!Si
o:U-=a~8:~~
~ !II j:D r-z E r;
: () C'l ~~l5 ~
~ g g!:"TI fit
liB~~
<
S~~
_gt
~~~ ~
"os ~
;1 r-
~~ ~ ~
~l:l ~ ~
~. "
s:~ 11
~~ ~
~~ z
~~
~:
~~
~
~
I~ ~~,
~.
~ t!l
~ z
~~~
aJ"'F
~ ..
~ ~
pl
II I~ !!li!I!!i i ~ I
i~ ;llulm~i ~ ! ~
~ Qe ~Q'Q~~i~~ I ~ 0
I, ;~ 111111;11 i ; ~
~ ~~~~15j~i i
I i Ilhll!l .
! ~ Id~U~iii
i ~ I~ud~
i i Jdl~M
I I ~~Idin
II~nl~
iB"
iB"
.~~~: ROAD ,
-- '''''"'''',:
\
~;,
j I:
~ i'
II!
Ii
-I;
Iii
!;
:j
EXHIBIT B
~
o
r,
,OJ:
I."
.'1
~ :J
;,c"
I
I
___________J
CIVTe SITE
,:
',I.
n
;'::
,;:
~11
-J
r;,
.:1;
o
~ ~n
~~~~
,:.~~~
~~l~
~
~
>
n
I
,..;,
Ii
; ~;
'Ii
"I'
.:.'~!
" :~
t j;
;:;~;(
,
,
~ <<
~ ""l@'
:;I 0.<'(/$~~
.: ~h'Y.X. ~
;;: !!I ),)f~>i(h:0
a ~~~~'\'7~
:!j ~
..
ell
!;;
l~:~
.
~
J B A Julian Bry-an & Associates urban d__lgn _tte planning .--zoning property _n_I~I_ rn_rtc-t; .......lblll'ty go....--rnrn_nt.l proce.aalnQ
I>) ;h.:~
0 ~~. A
"T1 ~,.,
.j>.
SITE PLAN
BOYNTON BEACH FlORJDA KNOLLWOOD GROVES P.U.D.
O.R HORTON HOME
Ii ~
I I ~
i I
.
gg
l!Il
4 I
~ ~ ~. 4
I ~
@ J
\ \
011
P Il..
t @Il..
't
~
,
,
I I
I '
I II~ ~ ~
:1 ;U
~ ttt ~
~
,!I@
'Il.. liP ~ ~
I sllll
~ I II ;
,Id
~ ;, ,~
~ ~ ~
,
" I 1
't I'
J ~ l
~! irrrr'lr!ll I". 'I r 1D<lIIlI~ ILIWoTICNI ~Ii I II!!
In!!1 · > !ij~
n.. P
t
'.
'&
EXHIBIT B
EXHIBIT B
..- It
I I~
I 'I
I III;;;
I II ~ ....
N' I' ~
I'd I ~~
5~ B I
I
@)i I
....
~< ~~
n> I !.~
-f I
~ I
,
I '
: DE[j II ~
I ! I' ~~
U ,
I "i H
~II
j\
H
t !tt t
' " I~
,I II~ II II :1
,I , " I~
, I I
H
'~
i ~ i
I I I
" : ~
!1 ~l> 1 .... ~
ICID~ ~
... j
'm
~ i ~ l
a : N ~ I
Z rn
I
I@ , ....
,
.... I~~
.... "
il ,~
II
@ .
~! irrrr'!!'! II IIUIl.DtO UVATICINI ~nl I~
~g
I ~i)
,
I I ~ II u ~
I ,
: , 0 I1IIII
, ,
, ,
1-----::-----1 :' . II ; EE
,
r I ~ ~ ~~ I 'I ~
< I ' 011I I' d 0 gEE
)>, ~ ~
-f'
o I OEm gEE
z'
i {1 o. ~@ 01:0
, '
r--u- ; ~I
D_ O
I CD
OEm I ~,
~ I~I ,
I;~ < I
)>, Ii
! -f I
,0 , CD
~ Z I
I ,
I, ,
Ii
'~
! '.
~
)> ~ ~ ~CID
< ,~
)>
!::::! I II I
l~ ~ 1 ~c&J
I oEm .~~
fI I
l~
1110.
' "
I II
, ~
I
tl imrll!'!l! I". 'I r I~
In!!1 · > !ii~
nil P
J>
EXHIBIT B
___ ___--J
l$
~--t~~~i
^
m
-<
;:
l>
"0
~~: ~
~ 1: ~
~,;~
~ .~
~&\i~
~WJ ~
I
HH~ ~
tiW~ -1
HH~w
'i;!~ ~
hH~~
,l! 0
jg
~~i~~~
~! i t! ~
iciJ; I
1"'101 , I,
!~!;!~~:i!j
f.;::
l!
~ :j'l II:; ~~-'-----'!
,.;.; '.:~;~'~'==i...'.c~.~.'.jllll r :II~~.. . ~~ll
~'" I 1 01 I l t ~ I
~==-=-" . :'~111' I,: ' 1
~ co ______J::--~-~u ..::;;-. :~;-._~-----=-..___ -
-~~ ~--;;:~:.~l~ [f-~~.r-=~=T I[
~ .1:11 Ii'.
~li i','.
~ - f"-Hli li~~:~:=~~~
---=--- - ~:ti IiI" i I
I", }1 i'"., : I
~1'1 IL\-- '~l:1
~..';.'\111; t~.. '. "" I
I:Hi Ir"~---l
~+~jl r t, II
i'-~r~ill!~o\'r' _~
i ..1.;1
-'~'i~1
,'.'1 ill
LUI
; t'
-~---.. -,~
I-IC~
-----liJ
=----r!;.t I
~~ I : d
.< ~I
- 'I}
'-,~:,o''l ~y
,_11. !
I'
.;: I
.......... '
:... I
~-~
-------------------- ;: :
':rJ
I ',:-':
/.
-~)
!~
(3 ~~
~ ;: ~
;~
,p
@
--=~
J3!'~~ :.
:;:t~~~ t: I ..
'-'lif: "
J!=:: I
, "
I,
"
"
"
"
"
:'
,
"
"
,
"
,
,
, "
"
"
"
"
"
,
"
I
,
,
I
I
I
,
)
l
I
)
,
,
,
,
i
,
,
I
,
,
,
,
I
-'. _ _ ~ J.
lAWRENCE ROAD
, .'-~!':_!:;; -'~,~;'''
Kno//wood Groves P. U. D.
~i~r
~~ ~
m :to 0
j2~ CD 0
I !l~
D.R. HORTON HOMES
Boyton Beach Florida
~ @ EXHlBl
1 ~ J ~ r~
- --
)(~"
I~ I ;~:;
1...-: I' @ . I
1"-- J( -- o.
It: ·
..--~- }--li f-----~ ~':"-
............- . - -f--M-
Ci ~~'Ir""
~ --:-)-T.T >C ~~@
-j. ~~! T--~
~ '-, JI ,> >, ~~
n ' J io
IL Il ):~-! ~~
;-:1 I;:: ~~~
r j ~;' ljl"~
n: ' ! It:: @;'
iii'! __..J, I ~ \ ~r;t;,Q :;-
};~'., - In ~rt
!j~<-- j It ~
~r ~-~'i ! Ic \-,
.', i' )2
g ", I?;
-t ' I~):
1~~Lm ,II;: ~
I::'~ E ~r>~ r'
Leu; I ,~ ~
~ft ~ ~
" 'f y
111 ~ J ~ ~,
IllrT--! 1~~
~: ,- -----~ "- ~-
ftt I P
I[?~, ~ ;~I:
It:. L_~ ,",--v i
I 'y ! -
ji, ! ; ~) r$ ~
,~~:- ,~. \~-;j h " ~
I ~\""n- -j=L}~ @ ;
, . ~ i ~ ~j9~
- - " . ,.....,----- ,-.,,.... "IC' ( , i~ 0
" ' ~ ", ' . '- un' u} un "-- ':T ,< _
! : I :: D ~,~ (
i ,rD--
i r$l.."-:; .:"
-- ~~:\\ :c
;:V( ~
, '- "",:Dc
, "'D
>
~~ ~
~ l! SHEE;' . i (
____________________ :1 I --1--;H;e;;-
111 ~
i;: ~D
" ,
p ;D@ ".c'~
p ~<I
,
/ ~:~ @~ ~ i 01\ I Y
~ ~ /'-,,);~. Jr ~ L ~ ~I
~'I-'-.~ r' -i'- =-'7'-\;:
T T ~:rr- _",', _ I,''',' I
) ~:i I:fJ -" i~~ ~ I
) lit~ _~J
:f)':_~- ~~+_~.i .;i~::..~ .:"~:n_~ ",Z.__.1.. ~.;:::..::' ~:-_~ -1;,._;~,-
(~j ~~G ~
',-^-- "
I Q ,
~I
--8 '--"-./__
A,
~
i
,
'\
'\
"",,' ,"""
I
".h
~ ~"-
! , ~ I
i., 11 r.1-- i.------ i
.:L:..l.)L ...,.~..~.,' ''''''' " .. .".j, .
"--J~,"-~'-.../
, i !
I
1
I'-;j
- . '
: ;~
.
-- . ~
p-'{~~~ r~~;='~-'f~~~.-, '-jc-~-'"'1'~ ~:~~~'~-r-;~ ~ -~1'''a~J~
, , ) j , : !I " I' ~ I ':1," ~. i,1
- ------.f~tll!F I I I~
~ .~ i. I I I __ r11
be : i ~f ;:-Lt ", 1 J 1 l____ -~:,l!
L t-I~ 1-:1 j I I "ti,
~--~ -1 I! I .----- I~l ~ I -- --~-- I -
ii" -,-' 1;'1 .. ~I
,.', l - ~ 1.1,' 1- ;__._~..~ "/".. ' '. f, : ,}"
~ I I ~~ I :-'1 ' ~ - ,._-:. - --- ~ - - ~~ ~!
j: J t~ Ittt-"c,; " .- ""'- . 1 .
;~e ! --: r ft<,:-J,-J - ",--:!,' j ',;,~ i di
~ i~ -- -- _Y-2i ~ i j ,~!
~-~~ l~ ..-1-' 'rJ ,_ _ ~ ~ ~ tj
I~~ J,W Wit ---"-i- :< ~; :{ -~.J"=-~'-"11
T' : ti-+~,L__~ \ i IOUI i : ~l
). ; .l.~. ~'_I- - f ~____{ t~j
L ____.J:.{ H: I ; "~ '. I t 'JoJ
J! ! "; [f~+~, I. ._,;.:;. - - - -. -~,~ : C ~I
,I ; .,,~ l,~.' "'I~C:-_' '. t~ r-----t,'_ ",J
;L_; -:i~l I'~" ~- - r\4Xj : or I: /~ ~.. -_--~ I ; ,,~~ ~!
)i J) ; ( ~' : i~ I 0,..0 ': ~-- f,.,.~, J!'I'
L-------l: ~: 1 -i ._y_ < ; I ~~ / ~
L~+J~cS:_)c~':,,2~7~~ ~t;;::(( ~\ ,-+J
I I'ltj! I .. .....~ ... D~~~~r)\ ;--------i<.i:1
I _____(:) '~.-::- :r----."'.-"~,._" I'.""'~"~'''''''.':'"~,,, '\.' \ ,,~ ,~"
: f"Tjl tf.;~,;~l~:~:-~1-i(;:=-l.:'''.~~}) 11~~~JI
~~---------I" + 1,. ~ Iff Iii: i r~~~",' ~,': .i.JII"1 [.1l(8 ! ; U ;~ 1~-(!1
JI I .;. I' I '" ~ ;,. lV'; ,
~I ." 'T,' ~1..J I :J:i: 1 i- Ii I.
L.R-~-~ ~: J ~ r L- :,.....,' I ~~ i I:~ t: I
~ ~'.I IT" ~ ~ I ~ ' ~. , ;..I"il i!):f-~ ---., -ill
_~. --- ----1- /: I ~ +~ : -~L t~ t ~~~ i I :!
~ E~ / ~@ ~ : J, .1'; ;Tl ~t'd" i ~ ~ ";'1
~~. 1\ VI ie.'.!j !,., .. tC "."1
: ~ I f)i ! ': II ~i.:, ',- . ~----.J ,- J/:~
I \ - , . '.' '. - - . - ~ '~<,4
I I ./ @j ,: If,: ;r! '''"cc_c;"",:,''''''--'-+:'''T :",-,0:-5...
en .~ ~! ['!ll.:cl.- -.-- €
iii -"'--'--+1.. ' " ~~--..~ .-.,--j-- -.+--_..
~ ~-~ j ~r-~:,,,-~=ldl (~/ -=~-~~t ,. - '
'" ,,-- :tI<;' I 'rP' ~I. t,(-~"r! L.,
. '. I "', " , ! .,
,,'I iri ,,'ll 1'0 L" .' j",,;
---~.~:." I : q ~ I ~-~' ';, ' '71'
,,>, I; I, I .~' '
,.r If , ;' ''il I~' L...... c ,--' ;L. ,----
---0-t I ~'--;'[l. I; ~ ~ - / i
I i{ Th1 : c~~ ~ f:' -r--I / .r;- ~
: ' l + "'~ .~. :I!' jl .'er ~-~~--
- .:...~( .r 5 - -u-~I'.~Ai! ,~, ,(r '
, : . /! ! ; n li'Lr~~~
---7-;-~ "\:i;i i.. ,-:11 f~ .: " ,I (
I ;: _~~ - 'r; It- I' 'r~~-----~-
ctj :~'i . , . : ~I 1)';"1' :
-- .~. i-<- .. --";, n! '" !1: , '
SHEET 2: ~; i )f _____J:.:tH~) ~~-~-_-~---;z--...., -
--;;;-E~T-3~2~1 j--- i --~, n : I(~+_'-j--=-=-=-~~
------:--:1 \1 .., ~i.~~l 11 ~'I ., i
'! ( : : ~l i'i~'--' l
T~! :t==---~ i:~l--1
: I' "I-----r\.,:;l 1i-1
: , ! I: 1,---,
! ---------M--~-~--
/
I........ i
I__~ ~~_
1 ~:~E
~ - - --<:'fI~-
I -:N
I
;>;
m
-<
3:
)>
"
II Hi'
X' ~.
ill
CD
~
~
~"
@ 1i
~"
I
I
~ j'
~-'
~
~
-
-
II
~
C)
z&\
~WJ
(" E'~l' 2: ~
I
1B
-~
.....
. - lL_:.u
. !-'-. .-.- ..-..
!: I
~:;.-~,.I
Kno//wood Groves P.U.O.
11!1!~
Hi 0
ii:
~~~m
.~! ~~~i
I I "I i I
III ill
i.I,I.! ! I.
\~i~i~~ljlf
,
j
o'
D.R. HORTON HOMES
Boyton Beach Florida
!~
Wf
~~ ~
H~ ::r:CJ 0
F- (1) 0
~ j OJ .......
Ii: ~ ~-
~ · 5,(1)
!. ~ C
J · (rQ "'"'
-:..~,<,,~~,!:
~~ i
h;'I
',I] I t Ii i i
~' ~. .ll-~~ -; -7.J'~-~~1~~\~~~~:._
, 'Ii ~~. 0 _.- .;'- .-, ~L_.,~ - cb-~", - .-. - --"
r~1 l '" _ _ ~
_ _ =~:.Tl_ _ _..: _ _ _~~~.._ __ ___~ _=-~_-=-_ ~ _-=_ ~__ _ =- _ _ _ _ _..,
I
~- ;:t:~~': ~ . __.:t?,~:..- ".
.-."""""l( -
~) :_- ""-
LAWRENCE ROAD
))
- '" -;'-. t-!HL ;~> 7
;>;
m
-<
:s:
:>>
'0
(j) .,:; ~
r.
OJ
iD ~I
-
w ~
q @
1 ~
~
~
~= ~
!f ~f~ ~
IHH~
t"' l~ ~
.,.,! -
lii~l ~
,II 0
iH
'HiP
~!W~
i ! tj i i
Ii II i i
I; 1 i i!
15:ii51 ! !~
1~lfl~~ljij
Kno//wood Groves P. U. D.
;;
;~
D.R. HORTON HOMES
Boyton Beach, Florida
~~ Ul
-;-'ii
:;;"l<t
if
;'~
~~
I ::cn 0
('DO
~,;;
:JC
00.....
EXHIBIT "C"
Conditions of Approval
Project name: Knollwood
File number: NWSP 05-016
Reference: 2nd review plans identified as a New Site Plan with an May 24, 2005 Planning; and Zoning;
Department date stamp marking
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments: None
PUBLIC WORKS - Traffic
Comments:
1. The Palm Beach County Traffic Division determined that the proposed
project meets the Traffic Performance Standards (TPS) of Palm Beach
County, upon provision of an exclusive north-bound lane along Lawrence
Road onto the project main access driveway.
ENGINEERING DIVISION
Comments:
2. Per the LDR, Chapter 7.5, Article II, Section 5.C.2. Ficus species are not
permitted.
3. Live Oaks are proposed within the utility easement on the east side of the
recreation area. Canopy trees are not allowed within utility easements.
Please replace with a different species.
4. Full drainage plans, including drainage calculations, in accordance with the
LDR, Chapter 6, Article IV, Section 5 will be required at the time of
permitting.
5. Paving, Drainage and Site details will not be reviewed for construction
acceptability at this time. All engineering construction details shall be in
accordance with the applicable City of Boynton Beach Standard Drawings
and the "Engineering Design Handbook and Construction Standards" and
will be reviewed at the time of construction permit application.
UTILITIES
Comments:
6. Palm Beach County Health Department permits will be required for the water
and sewer systems serving this project (CODE, Section 26-12).
7. Fire flow calculations will be required demonstrating the City Code
COA.doc
06/23/05
2
DEPARTMENTS INCLUDE REJECT
requirement of 1,500 g.p.m. (500 g.p.m. some residential developments) with
20 p.s.i. residual pressure as stated in the LDR, Chapter 6, Article IV, Section
16, or the requirement imposed by insurance underwriters, whichever is
greater (CODE, Section 26-16(b)).
8. The CODE, Section 26-34(E) requires that a capacity reservation fee be paid
for this project either upon the request for the Department's signature on the
Health Department application forms or within seven (7) days of site plan
approval, whichever occurs first. This fee will be determined based upon
final meter size, or expected demand.
9. A building permit for this project shall not be issued until this Department has
approved the plans for the water and/or sewer improvements required to
service this project, in accordance with the CODE, Section 26-15.
10. Utility construction details will not be reviewed for construction acceptability
at this time. All utility construction details shall be in accordance with the
Utilities Department's "Utilities Engineering Design Handbook and
Construction Standards" manual (including any updates); they will be
reviewed at the time of construction permit application.
FIRE
Comments: None
POLICE
Comments: None
BUILDING DIVISION
Comments:
11. Indicate within the site data the type of construction of each building as
defined in 2001 FBC, Chapter 6.
12. Buildings, structures and parts thereof shall be designed to withstand the
minimum wind loads of 140 mph. Wind forces on every building or structure
shall be determined by the provisions of ASCE 7, Chapter 6, and the
provisions of 2001 FBC, Section 1606 (Wind Loads). Calculations that are
signed and sealed by a design professional registered in the state of Florida
shall be submitted for review at the time of permit application.
13. At time of permit review, submit signed and sealed working drawings of the
proposed construction.
14. CBBCPP 3.C.3.4 requires the conservation of potable water. City water may
not, therefore, be used for landscape irrigation where other sources are readily
COA.doc
06/23/05
3
DEPARTMENTS INCLUDE REJECT
available.
15. A water-use permit from SFWMD is required for an irrigation system that
utilizes water from a well or body of water as its source. A copy of the permit
shall be submitted at the time of permit application, F.S. 373.216.
16. If capital facility fees (water and sewer) are paid in advance to the City of
Boynton Beach Utilities Department, the following information shall be
provided at the time of building permit application:
a. The full name of the project as it appears on the Development Order and
the Commission-approved site plan.
b. If the project is a multi-family project, the building number/s must be
provided. The building numbers must be the same as noted on the
Commission-approved site plans.
c. The number of dwelling units in each building.
d. The number of bedrooms in each dwelling unit.
e. The total amount paid and itemized into how much is for water and how
much is for sewer.
(CBBCO, Chapter 26, Article II, Sections 26-34)
17. At time of permit review, submit separate surveys of each lot, parcel or tract.
For purposes of setting up property and ownership in the City computer,
provide a copy of the recorded deed for each lot, parcel or tract. The recorded
deed shall be submitted at time of permit review.
18. At time of building permit application, submit verification that the City of
Boynton Beach Parks and Recreation Impact Fee requirements have been
satisfied by a paid fee or conveyance of property. The following information
shall be provided:
a. A legal description of the land.
b. The full name of the project as it appears on the Development Order and
the Commission-approved site plan.
c. If the project is a multi-family project, the building number/s must be
provided. The building numbers must be the same as noted on the
Commission-approved site plans.
d. The number of dwelling units in each building.
e. The total amount being paid.
(CBBCO, Chapter 1, Article V, Section 3(f))
19. Pursuant to approval by the City Commission and all other outside agencies,
the plans for this project must be submitted to the Building Division for
review at the time of permit application submittal. The plans must incorporate
all the conditions of approval as listed in the development order and approved
by the City Commission.
PARKS AND RECREATION
COA.doc
06/23/05
4
DEPARTMENTS INCLUDE REJECT
Comments:
20. The recreation impact fee will be:
148 single-family, detached homes @ 940.00 each = $139,120.00
The impact fee is due prior to issuance of the "first application permit".
FORESTERlENVIRONMENT ALIST
Comments:
21. The applicant should amend the note indicating that all utility boxes or
structures (not currently known or shown on the plan) should be screened
with Coco plum hedge plants on three sides.
22. At the time of permitting, the applicant must submit an updated Lake
Management Plan document for the lakes.
23. Irrigation Plan-No Irrigation plan included in the submittal
The irrigation system design (not included in the plans) should be low volume
water conservation using non-portable water.
24. Trees should have separate irrigation bubblers to provide water directly to the
root ball (Chapter 7.5, Article II Sec. 5. C.2.).
PLANNING AND ZONING
Comments:
25. Approval of this site plan is contingent upon the accompanying request for
annexation (ANEX 05-002) and corresponding land use / rezonmg
applications (LUAR 05-001 and LUAR 05-006). This includes the proposed
project density.
26. The Palm Beach County Traffic Division approved the project for 146 single-
family dwelling units. The site plan proposes 148 dwelling units. At the time
of permitting, revise the site plan by deleting two (2) units or provide an
updated Traffic Performance Standards Review letter from the County that
approves the project for the additional two (2) units.
27. A unity of title will be required at the time ofoermitting.
28. The School District of Palm Beach County must approve the project for
school concurrency purposes prior to the issuance of a building permit.
29. Increased compatibility with the adjacent properties (where abutting AR
zoning district) is required. This can be accomplished by either increasing the
building setbacks of the abutting lots (Lots 31 through 42), increase the size
COA.doc
06/23/05
5
DEPARTMENTS INCLUDE REJbCT
of the buffer width (from 20 feet to 25 feet), and / or significantly increase the
plant material proposed within the 10-foot wide landscape buffer (i.e. variety
of canopy trees spaced no greater than 20 feet apart combined with lower
vegetation to buffer heights from four (4) feet to six (6) feet
30. At the time of permitting, provide a detail of the front entry gates, including
its dimensions, material, and color(s) (Chapter 4, Section 7.D.).
31. Fifty percent (50%) of all site landscape materials must be native species
(Chapter 7.5, Article II, Section 5.P). On the landscape plan plant list (sheet
7 of 10), indicate by asterisk, the native species to ensure that at least 50% of
landscape material is native. Separate and indicate the proposed plant
material into the following categories: Shade Trees, Palm Trees, Shrubs /
Hedges, and Groundcover. Please tabulate the amount of native material in
each plant category.
32. On the landscape plan, ensure that the plant quantities must match between
the tabular data and the graphic illustration.
33. The landscape plan (sheet 9 of 10) shows a Unit 2110 but there is no
corresponding floor plan. At the time of permitting, revise this sheet to
exclude this unit or provide all corresponding information for the unit.
34. At the time of permitting, revise the landscape plan to include the following:
The 110 foot strip along the north side of the property between the 20 foot
landscape buffer and the LWDD canal R-O-W should be sodded, irrigated,
and maintained by the developer / HOA like all other common areas within
the site.
35. The master plan / site plan will dictate the applicable setbacks for amenities
such as swimming pools and screened-roof enclosures. There IS a
discrepancy between a note that references city regulations for pool setbacks
and the minimum dimension shown on the typical lot drawing. Therefore, at
time of permitting, on the site plan (sheet 1 of 4), eliminate the note that reads
"Pools and Jacuzzi's may be permitted provided they meet City of Boynton
Beach code requirements", or change the dimension on the typical lot
drawing to be consistent with city setback regulations.
36. At the time of permitting, provide Home Owners' Association documents to
verify necessary maintenance of common areas and landscape buffers.
37. On the Typical Lot Details as shown on the site plan, indicate "Minimum"
rear and side building setbacks rather than "TYP" rear and side building
setbacks.
38. Building heights proposed on the subject property (Lots 31 through 60) are
partially defined and impacted by the ground elevation of the adjacent
properties (if they are lower ground elevation). Therefore, two (2) story
houses built along the perimeter of the subi ect property may be in jeopardy of
COA.doc
06/23/05
6
DEPARTMENTS INCLUDE REJECT
exceeding the maximum building height (proposed as per this site plan).
Therefore, at the time of permitting, provide updated ground elevations of the
adjacent property to ensure compliance and consistency.
39. On the site plan, correct the label "Nautica Sound PUD" to read "Nautica
PUD".
40. In order to ensure proper maintenance of the buffer areas, staff recommends
converting them from landscape "easements" to "tracts" that would be owned
and maintained by the Home Owners' Association.
41. Staff recommends that the height of the screen enclosures be limited to the
mean height of the house on which the structure is proposed.
42. Staff recommends that where possible, the shade tree spacing within the north
landscape buffer shall be no more than one (1) tree per 25 lineal feet
43. Staff recommends the perimeter landscaped buffers utilize taller, more mature
canopy trees behind all two story models, to soften the height against abutting
single story residences. For example, the trees should be installed at 16 feet
in height where two (2) story buildings are constructed.
44. A six (6) foot tall black vinyl coated chain link fence is proposed along the
southern property line of Lots 1 through 3 and half-way through Lot 4. Staff
recommends extending the fence westward so that it terminates along the
west property line of Lot 4.
ADDITIONAL PLANNING & DEVELOPMENT BOARD COMMENTS:
Comments:
45. To be determined.
ADDITIONAL CITY COMMISSION COMMENTS:
Comments:
46. To be determined.
MWR/elj
S:\Planning\SHARED\WP\PROJECTS\Knollwood Groves PUD\NWSP 05-017\COA.doc
Johnson, Eric
From:
Sent:
To:
Subject:
Johnson, Eric
Thursday, June 23, 2005 11 :59 AM
Rumpf, Michael; Breese, Ed
Proposed setbacks Knollwood
Mike,
Do you want me to make a recommendation to increase the rear setback for the units proposed along the south property
line, adjacent to the County AR parcels? If so, by how much? From 20 to 25 feet?
Thanks,
Eric
1
Johnson, Eric
From:
Sent:
To:
Subject:
Rumpf, Michael
Thursday, June 23,20054:18 PM
Johnson, Eric
RE: Proposed setbacks Knollwood
I think the optional comment is best which calls out the issue, and gives them options for addressing the potential
incompatibility of the existing and proposed neighborhoods. To read as follows (clean up as desired):
The City's PUD regulations require that "peripheral yards abutting other zoning districts shall be the same as required in
the abutting zone". The southwest edge of the project abuts an older neighborhood built under the County's AR zoning
district. These lots are larger than the proposed yards, with rear yard setbacks that vary between approximately 26 feet to
40 feet (estimated). Increase compatibility with adjacent properties (where abutting AR zoning district) by 1) increasing
setbacks of abutting lots; 2) increasing adjacent buffer width; and/or 3) by significantly increasing the buffer vegetation (i.e.
variety of canapy trees spaces no greater than 20 feet combined with lower vegation to buffer heights from 4 feet to 6 feet.
-----Original Messagemn
From: Johnson, Eric
Sent: Thursday, June 23,200511:59 AM
To: Rumpf, Michael; Breese, Ed
Subject: Proposed setbacks Knollwood
Mike,
Do you want me to make a recommendation to increase the rear setback for the units proposed along the south
property line, adjacent to the County AR parcels? If so, by how much? From 20 to 25 feet?
Thanks,
Eric
1
Johnson, Eric
Page 1 of 1
From: Main, Karen
Sent: Thursday, June 23, 2005 1 :38 PM
To: Johnson, Eric; Rumpf, Michael
Subject: Nautica
Rear setback for bldgs along the community's 25' buffer easement is 25
Rear setback for lots on the 5' buffer easements (lakes, parks & preserves) is 10'
6/2312005
o
'" "-/)
~)
.---\ 5'
3
>
Johnson, Eric
From:
Sent:
To:
Subject:
Rumpf, Michael
Thursday, June 23, 2005 12:26 PM
Johnson, Eric
RE: Your comments
-----Original Message-----
From: Johnson, Eric
Sent: Thursday, June 23, 2005 11:06 AM
To: Rumpf, Michael
Subject: Your comments
Mike,
These are your comments that were written down on the little sheets. Let me know what you think. I didn't make a
condition regarding the park. Make changes as you see fit. Thanks,
The landscape plan (sheet 9 of 10) shows a Unit 2110 but there is no corresponding floor plan. At the time of permitting, revise
this sheet to exclude this unit or provide all corresponding information for the unit.
The master plan/site plan will dicate the applicable setbacks for amenities such as swimming pools and screened-roof
enclosures. There is a descrepancy between a note that references city regulations for pool setbacks and the minimum
dimension shown on the typical lot drawing. Therefore, at time of permitting, on the site plan (sheet 1 of 4), eliminate the note
that reads "Pools and Jacuzzi's may be permitted provided they meet City of Boynton Beach code requirements", or change the
dimension on the typical lot drawing to be consistent with city setback regulations.
In order to ensure proper maintenance of the buffer areas, staff recommends converting them from landscape easements" to
"tracts" that would be owned and maintained by the Home Owners' Association.
At the time of permitting, provide Home Owners' Association documents to verify necessary maintenance of common areas and
landscape buffers.
Builidng heights proposed on the subject property (Lots 31 through 60) are partially defmed and impacted by the ground elevation
of the adjacent properties (if they are lower ground elevation). Therefore, two (2) story houses built along the perimeter of the
subject property may be in jeopardy of exceeding the maximum building height (proposed as per this site plan). Therefore, at the
time of permitting, provide updated ground elevations of the adjacent propety to ensure compliance and consistency.
On the Typical Lot Details as shown on the site plan, indicate "Minimum" rear and side building setbacks rather than "TYP" rear
and side building setbacks.
On the site plan, correct the label "Nautica Sound PUD" to read "Nautica PUD".
1
1 s. REVIEW' RESPONSES, 5-~-i~05
New Site Plan
jI,\ . ~
t 0JY'Y "
Project name: Knollwood
File number: NWSP 05-016
Reference: 1 Sl review plans identified as a New Site Plan with an April 6, 2005 Planning and Zoning
Department date stamp marking
I II
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments:
1. Prior to permit application contact the Public Works Department (561-742- /
6200) regarding the storage and handling of refuse per the CODE, Section
10-26 (a).
No resoonse required.
PUBLIC WORKS - Traffic
Comments:
2. Provide a traffic analysis and notice of concurrency (Traffic Performance /
Standards Review) from Palm Beach County Traffic Engineering.
A traffic analysis has been submitted.
3. Staff strongly recommends moving the main entrance to the north property
line, by extending Miner Rd. from Lawrence Rd. west to the easterly north-
south roadway. The proposed location of the main entry off Lawrence Rd.
will conflict with the planned park entry to the Civic Site south of
Knollwood Groves PUD. Additionally the proposed main entry has only one
egress lane that will not efficiently allow both northbound and southbound t/
turning movements.
The entry location has been the topic of meetings with both Palm Beach
County and City professionals. For reasons too numerous to list in this
response the entry will remain in it's general location. County staffwill require
extending the existing median in front of the entrance thereby only allowing
for a rif!ht in and rif!ht out of the community.
4. Retain a secondary emergency access on the east property line onto
Lawrence Rd. V-
A second means of emergency access onto Lawrence Road has been added to
the site plan.
5. Show all required off-site improvements. Extend Miner Rd. west from
Lawrence Rd. approximately 600-ft. The typical section should provide a V
minimum of two 12-ft. lanes, widening to three 12- ft. lanes at the
intersection of Miner and Lawrence to allow for left turn movements.
Please see response #3 above.
6. Coordinate with Palm Beach County Traffic Engineering to upgrade the V
signals at Miner Rd. and Lawrence Rd.
The aoolicant has met with Palm Beach County traffic and roadwav
comment response.052405
OS/24/05
2
I II
DEPARTMENTS INCLUDE REJECT
production. Warrants necessary for upgrading the signal do not exist at this
time.
7. Extend the center median on Lawrence Rd. south of Miner Rd. {//
approximately 70-ft. north.
The center median has been extended north as requested.
ENGINEERING DIVISION
Comments:
8. All comments requiring changes and/or corrections to the plans shall be /
reflected on all appropriate sheets.
All corrections have been shown on all sheets
9. Please note that changes or revisions to these plans may generate additional /
comments. Acceptance of these plans during the TRC process does not
ensure that additional comments may not be generated by the Commission
and at permit review.
Acknowled(!ed
10. Show proposed site and street lighting on the Site and Landscape plans ~
(LDR, Chapter 4, Section 7.B.4.) Lighting will be required for the parking
area adjacent to the recreation area.
Lif!htinf! has been added to all aoolicable plans.
II. The two Live Oaks located in Lots 96 and 97 (either side of the drainage
easement) are placed too close together for their mature size. Staff
recommends that the cultivars "Highrise" or "Cathedral" be used for Live V
Oaks, particularly where called out along rear property lines.
Response: One of the proposed Live Oaks has been removed from the
landscape plan, as requested. "Highrise" species have been designated
throughout the project. Please see revised landscape plan included herein.
12. All trees and palms should be placed a minimum of five feet off the
property lines and away from driveways, sidewalks and curbs to allow for
future growth and prevent heaving of the aforementioned structures. ~ ~
Response: All street trees have been placed at least 5 feet from drives,
sidewalks and curbs. Please see landscape plans, prepared by Cotleur &
Hearing, Inc., and included herein.
13. Wild Date Palm/Sylvester specified within the entryway median does not
have adequate clear trunk specified for vehicle clearance due to the large
size (length) of the fronds which will hang into traffic. ~ --
Response: The Wild Date Palm/Sylvester has been replaced with Royal Palms.
Please see revised plans prepared by Cotleur & Hearing, Inc.
14. The Shrub/Groundcover Planting Detail on Typical Unit Landscape Plan
Sheet 2 of 2 depicts planting for a tree. Please correct. ~
Response: The Planting Detail, referred to above, identifies a shrub.
Please refer to landscape plans, included herein.
comment response.052405
OS/24/05
3
DEPARTMENTS
15. It may be necessary to replace or relocate large canopy trees adjacent to
light fixtures to eliminate future shadowing on the parking surface (LOR,
Chapter 23, Article II, Section A.l.b).
Response: This has been noted in the General Notes on the
landscape plan. The proposed trees have been adjusted per the
lighting plan. Please see revised plans, included herein.
16. Show sight triangles on the Landscape plans (LOR, Chapter 7.5, Article II,
Section 5.H.). Reference FOOT Standard Index 546 for the sight triangles
along Lawrence Road. Use a minimum 25-f1. site triangle for interior
development intersections (revise the note on Landscape Plan Sheet I of 5.)
Response: The required safe sight triangles have been included on
the landscape plans.
17. Per the LOR, Chapter 7.5, Article II, Section 5.C.2. Ficus species are not
permitted.
Response: The ficus shrub located in the green island has been
replaced with a Carissa "Green island". Please refer to revised
landscape plans.
18. Provide a legend for the plant symbols.
Response: All plants are denoted and tagged on the landscape
plans with letter symbols, which correlate to the comprehensive
plant list included within the landscape plan package. Please refer
to landscape plans, included herein, for further clarification.
19. Live Oaks are proposed within the utility easement on the east side of the
recreation area. Canopy trees are not allowed within utility easements.
Please replace with a different species.
Response: All canopy trees have been pulled to a location behind
the easement. Royals have been identified around the perimeter of
the recreation area.
INCLUOE REJECT
/
/'
20. Full drainage plans, including drainage calculations, in accordance with the
LOR, Chapter 6, Article IV, Section 5 will be required at the time of ./
permitting. V
Acknowledged. See Site Grading Note #8 on Sheet 2 of the Preliminary
Enflineerinf! Plans.
21. Paving, Drainage and Site details will not be reviewed for construction
acceptability at this time. All engineering construction details shall be in
accordance with the applicable City of Boynton Beach Standard Drawings
and the "Engineering Design Handbook and Construction Standards"
and will be reviewed at the time of construction pemlit application.
Acknowledged.
22. Upon Commission approval of the site plan schedule a pre-application
meeting with the Engineering Division to begin the plat process.
v
t/
~
~
/'
comment response.052405
OS/24/05
4
DEPARTMENTS
Acknowled~ed.
UTILITIES
Comments:
.~ ' Please provide a timeline that clearly illustrates when water and sewer
services will be required to serve the proposed project. Your starting date
for the timeline should be the date of City Commission approval. Also
provide milestone dates for permit application, the start of construction,
and the setting of the first water meter. This timeline will be used to
determine the adequacy of water and wastewater treatment capacity for
your project upon the project's completion, so please be as accurate as
possible.
We expect water and sewer service will be required 12 months after the City
Commission approval.
City Commission Approval - Month 0
Permit Application - Month 2
Start of Construction - Month 7
FustWarerMerer-Monffl12
24. All utility easements and utility lines shall be shown on the Site plan and
Landscape plans (as well as the Water and Sewer Plans) so that we may
determine which appurtenances, trees or shrubbery may interfere with
utilities. In general, palm trees will be the only tree species allowed within
utility easements. Canopy trees may be planted outside of the easement so
that roots and branches will not impact those utilities within the easement
in the foreseeable future. The LOR, Chapter 7.5, Article I, Section 18.1
gives public utilities the authority to remove any trees that interfere with
utility services, either in utility easements or public rights-of-way.
Most all water and sewer has been shown in the road R/W which will also be a
utility easement to the City. A 10 foot general utility easement has been shown
adjacent to the road RJW. Utility easements outside the road R/W have been
shown. All easements will be dedicated bv olat.
25. Palm Beach County Health Department permits will be required for the
water and sewer systems serving this project (CODE, Section 26-12).
Acknowledged.
26. Fire flow calculations will be required demonstrating the City Code
requirement of 1,500 g.p.m. (500 g.p.m. some residential developments)
with 20 p.s.i. residual pressure as stated in the LOR, Chapter 6, Article IV,
Section 16, or the requirement imposed by Insurance underwriters,
whichever is greater (CODE, Section 26-16(b )).
Fire Flow calculations will be provided at the time of permit application.
27. The LOR, Chapter 6, Article IV, Section 16 requires that all points on each
building will be within 200 feet of an existing or proposed fire hydrant.
INCLUDE REJECT
/
v/
v
~
/
t/
comment response.052405
OS/24/05
5
DEPARTMENTS
Numerous lots are not covered by this requirement; lots not covered are: 9,
10 partially, 31 partially, 40 partially, 51 partially, 52, 53, 54, 65, 66, 67,
79 partially, 80, 81, 82 partially, 87, 88, 89, 90 partially, Ill, 112, 113, 120
partially, 127 partially, 128, 135, 136, 137, 147 partially, 148, and 149.
Reconfigure fire hydrant locations to meet this code requirement.
This code section also provides for an exception to the above requirement for
one and two story residential project with a density of less than 10 units
per acre which this project qualifies. We believe the plan meets the
exception reauirements.
28. The CODE, Section 26-34(E) requires that a capacity reservation fee be
paid for this project either upon the request for the Department's signature
on the Health Department application forms or within seven (7) days of site
plan approval, whichever occurs first. This fee will be detemlined based
upon final meter size, or expected demand.
Acknowled~ed.
29. Water and sewer lines to be owned and operated by the City shall be
included within utility easements. Please show all proposed easements on
the engineering drawings, using a minimum width of 12 feet. The
easements shall be dedicated via separate instrument to the City as stated in
CODE Sec. 26-33(a).
See response to item 24.
30. This office will not require surety for installation of the water and sewer
utilities, on condition that the systems be fully completed, and given to the
City Utilities Department before the first permanent meter is set. Note that
setting of a permanent water meter is a prerequisite to obtaining the
Certificate of Occupancy.
Acknowled~ed.
31. A building permit for this project shall not be issued until this Department
has approved the plans for the water and/or sewer improvements required
to service this project, in accordance with the CODE, Section 26-15.
Acknowledged. See Fire and Life Safety notes on Sheet 2 of the Preliminary
En~ineerin~ Plans.
32. Appropriate backflow preventer(s) will be required on the domestic water
service to the dwellings as well as the recreational building, and the fire
sprinkler line if there is one, in accordance with the CODE, Section 26-
207.
Acknowled~ed.
33. The LDR, Chapter 3, Article IV, Section 3(P) requires a statement be
included that support utilities are available and will be provided by all
other appropriate agencies. This statement is lacking on the submitted
plans.
INCLUDE
/
,/
REJECT
/
/
/
/
/
comment response.052405
OS/24/05
6
I ~
DEPARTMENTS INCLUDE REJECT
See General Note Ion Sheet 2 of the Preliminary EnKineerillJ! Plans.
34. Utility construction details will not be reviewed for construction
acceptability at this time. All utility construction details shall be in /
accordance with the Utilities Department's "Utilities Engineering Design
Handbook and Construction Standards" manual (including any
updates); they will be reviewed at the time of construction permit
application.
Acknowled1!ed.
FIRE
Comments:
35. All entrance gates to construction area shall have a Knox lock system that
will also open in case of electrical power failure. All gates shall be a t/'
minimum of 20' wide. Fire Department apparatus shall be able to turn into
the construction site in one turn.
Acknowledged, a knox box will be provided to activate the entrance gates. All
Kates will ooen to provide a 20' clear open inK.
36. The construction site access roads shall be maintained free of obstructions /
at all times.
A cknowledJ!ed
37. All required fire hydrants, standpipes or sprinkler systems shall be in place
before going vertical. Vertical construction shall be protected by standpipes V
and the sprinkler system to one level below the highest level of V
construction throughout the building.
AcknowledKed. No fire sorinkler systems are allticioated in this oro;ect.
38. Any cost of damage to Fire Department vehicles because of improperly
stabilized roads or any towing fees if a vehicle becomes stuck will be the
responsibility of the contractor. A minimum of 32 tons is required for ~ /"
ground stabilization.
AcknowledKed.
39. Adequate Fire Department vehicle turn around space shall be provided in c./ v/
the construction area.
AcknowledJ!ed.
POLICE
Comments: NONE
BUILDING DIVISION
Comments:
comment response.052405
OS/24/05
-.,
/
DEPARTMENTS
40. Please note that changes or revisions to these plans may generate additional
comments. Acceptance of these plans during the TRC process does not
ensure that additional comments may not be generated by the commission
and at permit review.
No reSDonse required.
41. Indicate within the site data the type of construction of each building as
defined in 200 I FBC, Chapter 6.
A note has been added to the site plan regarding the use of CBS Masonry
construction
43. At time of permit review, submit signed and sealed working drawings of
the proposed construction.
Acknowledeed
44 Identify within the site data the finish floor elevation (lowest floor
elevation) that is proposed for the building. Yerify that the proposed
elevation is in compliance with regulations of the code by adding
specifications to the site data that address the following issues:
a. The design professional-of-record for the project shall add the following
text to the site data. "The proposed finish floor elevation ~. ~ NGYD
is above the highest 100-year base flood elevation applicable to the
building site, as determined k;.by the SFWMD's surface water
management construction development regulations."
b. From the FIRM map, identify in the site data the title of the flood zone
that the building is located within. Where applicable, specify the base
flood elevation. If there is no base flood elevation, indicate that on the
plans.
c. Identify the floor elevation that the design professional has established
for the building within the footprint of the building that is shown on the
drawings titled site plan, floor plan and paving/drainage (civil plans).
See Site Grading Notes on Sheet 2 of the Preliminary Engineering Plans.
Notes have also been added to the site plans.
45. Add to the submittal a partial elevation view drawing of the proposed
perimeter wall/fence. Identify the type of wall/fence material and the
type of material that supports the wall/fence, including the typical
distance between supports. Also, provide a typical section view drawing
of the wall/fence that includes the depth that the wall/fence supports are
below finish grade and the height that the wall/fence is above finish
grade. The location and height of the wall/fence shall comply with the
wall/fence regulations specified in the Zoning Code.
Wall and fence details will be provided with the next resubmittal for staff
review.
46.
CBBCPP 3.C.3.4 requires the conservation of potable water. City water
may not, therefore, be used for landscape irrigation where other sources
are readily available.
INCLUDE REJECT
/v
/
L7
/
/
~
/
comment response.052405
OS/24/05
8
I II
DEPARTMENTS INCLUDE REJECT
It is anticipated that the source of irrigation water shall be groundwater from
the lake.
47. A water-use permit from SFWMD is required for an irrigation system /
that utilizes water from a well or body of water as its source. A copy of
the permit shall be submitted at the time of permit application, F.S.
373.216.
Acknowledged.
48. If capital facility fees (water and sewer) are paid in advance to the City
of Boynton Beach Utilities Department, the following information shall
be provided at the time of building permit application:
a. The full name of the project as it appears on the Development Order and
the Commission-approved site plan. /
b. If the project is a multi-family project, the building number/s must be
provided. The building numbers must be the same as noted on the
Commission-approved site plans.
c. The number of dwelling units in each building.
d. The number of bedrooms in each dwelling unit.
e. The total amount paid and itemized into how much is for water and how
much is for sewer.
(CBBCO, Chapter 26, Article II, Sections 26-34)
Acknowledged.
49. At time of permit review, submit separate surveys of each lot, parcel or
tract. For purposes of setting up property and ownership in the City /
computer, provide a copy of the recorded deed for each lot, parcel or
tract. The recorded deed shall be submitted at time of permit review.
Acknowledged
50. At time of building permit application, submit verification that the City
of Boynton Beach Parks and Recreation Impact Fee requirements have
been satisfied by a paid fee or conveyance of property. The following
information shall be provided: /
a. A legal description of the land.
b. The full name of the project as it appears on the Development Order and
the Commission-approved site plan.
c. If the project is a multi-family project, the building numberls must be
provided. The building numbers must be the same as noted on the
Commission-approved site plans.
d. The number of dwelling units in each building.
e. The total amount being paid.
(CBBCO, Chapter 1, Article V, Section 3(t))
Acknowledged
51. Add a general note to the site plan that all plans submitted for permitting /
shall meet the City's codes and the applicable building codes in effect at
the time of permit application.
A note has been added to the site vlan
comment response.052405
OS/24/05
9
I II
I
DEP ARTMENTS INCLUDE REJECT
52. Pursuant to approval by the City Commission and all other outside
agencies, the plans for this project must be submitted to the Building v
Division for review at the time of permit application submittal. The plans /
must incorporate all the conditions of approval as listed 10 the
development order and approved by the City Commission.
Acknowledged
53. Sheet 2 of 4. Indicate on the plans that light poles comply withy 200 I
FBC, Section 1606 for compliance with 140mph windload. Design ~
calculations by a design professional registered in the State of Florida
shall be submitted at time of permit application.
Acknowledged
P ARKS AND RECREATION
Comments:
54. Landscaping notes should indicate a 110% irrigation coverage. /
Response: A note has been added to the landscape plan. Please see revised
plan included herein.
55. A six (6) foot black, vinyl coated chain link fence should be installed /
between the development and the civic area to the south.
Response: A note has been added to the landscape plan for reference. Please
see revised plans, included herein.
56. The recreation impact fee will be : /
152 single-family, detached homes @ 940.00 each = $142,880.00
The impact fee is due prior to issuance of the "first application permit".
Acknowledged
FORESTER/ENVIRONMENTALIST
Comments:
57. The Landscape Architect should indicate and tabulate the total number 1/
of existing trees on the site. The tabular data should show the individual
species of trees proposed to remain in place, be relocated throughout the
site, or removed / replaced on site. All desirable species of existing trees
must be relocated rather than removed if the trees are in good health.
These trees should be shown by a separate symbol on the landscape plan
sheet LP5. fEnvironmental Regulations, Chapter 7.5, Article I Sec.
comment response.052405
OS/24/05
10
I II
DEPARTMENTS INCLUDE REJECT
7.D.p.2.]
Response: The total number of on-site trees have been tabulated for the site. A
Mitigation, Relocation and Preservation Chart has been added to the
landscape plan package which identifies all trees to be mitigated, to be re-
located off site and to be re-located on site. All high quality, native trees have
been saved or re-located to the greatest extent possible, including
approximately 60 sabal palms.
58. Landscape Plan
Sheet 5 of 5. 1 of 1 ( Lakes) /
All shade and palm trees on the Plant list must be listed in the
specifications as a minimum of 3" diameter at DBH (4.5' off the
ground), 12'-14' height minimum and Florida #1. The height of the
trees will be larger than 12'-14' to meet the 3" diameter requirement.
[Environmental Regulations, Chapter 7.5, Article II Sec. 5.C. 2.]
Response: The plant list has been revised as requested. Please see revised plant
list included in the revised landscape plan package.
59. The details section for the Tree and Palm Planting Detail should include -:/
a line indicating where the height of the tree will be measured at time of
planting and inspection.
Response: The detail has been revised accordingly. Please see revised plan
included herein.
60. All groundcover / vine plantings should have a height and spread /
measurement.
Response: The plant list has been revised to reflect this information. Please see
revised plans prepared by Cotleur & Hearing, Inc.
61. The applicant should amend the note indicating that all utility boxes or
structures (not currently known or shown on the plan) should be /
screened with Coco plum hedge plants on three sides.
Response: The Applicant has amended the platz accordingly. Please see
updated note on revised landscape plans.
62. The applicant must submit a Lake Management Plan document for the
lakes. t/
A management plan will be submitted to the City prior to request for lake
excavation oermits.
63. Irri2ation Plan-No Irri2ation plan included in the submittal
The irrigation system design (not included in the plans) should be low /-
volume water conservation using non-portable water.
Response: An irrigation plan has been included within this re-submittal. The
irrigation is drawing from the on-site lake.
64. Turf and landscape (bedding plants) areas should be designed on ./
separate zones and time duration for water conservation.
Resoonse: The Aoolicant acknowledKes this comment but would like to note
comment response.052405
OS/24/05
11
DEPARTMENTS
INCLUDE REJECT
that this is not a costs effective option, and is not being proposed for this
site. Separate zoned for turf and landscape areas would require a
complicated zone layout that would not be most effective for this plan and
would increase irrigation costs by at least 40%.
65. Trees should have separate irrigation bubblers to provide water directly
to the root ball. [Environmental Regulations, Chapter 7.5, Article II Sec.
5. C.2.]
Response: Separate irrigation bubblers are typically not required for every tree.
The Applicant is not proposing separate irrigation bubblers at this time,
because it is not cost-effective and is unnecessary. The developer will use
water trucks on site until the trees are established, approximately 30 days.
PLANNING AND ZONING
Comments:
66.
At the technical advisory reVIeW team meeting, provide written
responses to all staffs comments and questions. Submit 12 sets of
revised plans. Each set should be folded and stapled.
At the technical advisory review team meeting, provide a full set of
drawings, sized 8Yz inches by 11 inches of each plan. Save each plan to
a compact disk and submit that to staff as well.
E"\.eIAWC;
Approval of this site plan is contingent upon the accompanying request
for land use / rezoning application (LUAR 05-00 I). This includes the
proposed project density. Include a note regarding LUAR 05-001 on the
site plan / master plan (sheet I of 4).
owled ed, a note has also been added to the site Ian.
According to Chapter 2.5, Section 9.B., when rezoning a property, no
minimum lot size or minimum yard shall be required; provided however,
that PUD frontage on dedicated public roads shall observe front yard
requirements in accordance with the zoning district the PUD use most
closely resembles and that peripheral yards abutting other zoning
districts shall be the same as required in the abutting zone. The abutting
properties to the west are zoned County Agricultural Residential (AR)
and County Residential Transitional Urban District (RTU). The RTU
zoning district requires a 20-foot rear setback. The Typical Perimeter
Lot Detail indicates a 20-foot rear dimension. This is acceptable.
of title will be re uired.
/
t./
J
L/
v
comment response.052405
OS/24/05
12
DEPARTMENTS
Acknowledged
On the site plan (sheet I of 4), name this sheet as both the "Master Plan"
and "Site Plan" since it will serve as both according to Chapter 2.5,
Section 10.A.3.d.
Revised as requested on the site plan
,~....."~<,,
2. e Palm Beach County Traffic Division shall approve the Traffic
Impact Statement / Study. (Chapter 4. Section 8.F.).
ck owled ed
73. The School District of Palm Beach County must approve the project for
school concurrency purposes. Please provide evidence of their approval
prior to the technical advisory review team meeting.
School Board will be provided prior to the Development
Include a color rendering of all four (4) elevations at the Technical
Review Committee meeting (Chapter 4, Section 7.0.).
Color renderings will be provided by the developer at the meeting.
>(
The ledger-sized color rendering of Model 2510 does not match its
respective elevations with regard to house style, window openings, and
architectural enhancements. Also, no color renderings were submitted
for Model 1952 and 3054. Renderings were submitted for Model 3080
and 3135, but no elevations were provided.
Correct renderings of each model will be provided at the TRC meeting.
Provide paint swatches for the elevations (Chapter 4, Section 7.0.).
rovided at the meetin .
The elevations shall indicate the exterior finish, paint manufacturer's
name, and color codes. Staff recommends using a color schedule that
corresponds with the graphic illustration (Chapter 4, Section 7.0.).
Color swatches will reflect the exact colors proposed. Architectural renderings
rely on commercially available art markers for renderings. On some occasions
they are not exactly the same a paint manufacturers swatches.
/(
INCLUDE
~
/
~
REJECT
v
t/
v/
v
comment response.052405
OS/24/05
13
DEPARTMENTS
(Chapter 4, Section 7.0.).
Building heights are shown on the elevations and in a table on the site plan.
t(
Provide a floor plan and elevation of the cabana building (Chapter 4,
Section 7.0.). Staff recommends constructing a clubhouse building (w
A/C) rather than a small cabana building in order to provide a place
where owner association meetings home can occur.
Plans of the cabana building are included in this resubmittal. The applicant
does not feel that a clubhouse with meeting facilities is necessary.
8
All signage is subject to review and approval of the Planning &
Development Board and City Commission. Is there an entrance sign
proposed for the project? If so, on the site plan (sheet I of 4), indicate its
location and provide a detail of the sign area, including the dimensions,
exterior finish, and letter color(s) (Chapter 4, Section 7.D.).
Entry sign details will bf5s~mi~~r~r;,.~Xhe next TAC meeting.
r\
I~
Are screened roofs or solid-roof enclosures proposed at the rear of each
house? According to Chapter 16 of the 200 I Florida Building Code, a
concrete slab is required at the base of screen enclosures. Indicate the
impervious area should all homeowners choose to build a screen or
solid-roof enclosure at the rear of their unit.
A note has been added to the site plan reflecting the maximum impervious area
with tMe largest home footprint and deck area.
y
A note on the site plan (sheet I of 4) indicates that swimming pools are
permitted such as long as they meet City of Boynton Beach Code
requirements. Indicate their proposed location, configuration, and
setback within the Typical Lot Details. Also, indicate the impervious
area should all homeowners choose to improve their lots with swimming
pools. Please note that setbacks for swimming pools should be greater
than setbacks for screened-roof enclosures.
INCLUDE
Notes have been added to the typical lot details reflecting pool and screen I
enclosure setbacks.
83. On the site plan (sheet 1 of 4), revise the note that currently reads,
"Covered patios (including roofed screened enclosures) shall be
restricted to within building envelope" to read as follows: Covered
patios (including solid-roof screened enclosures) shall be restricted to
within building envelope.
REJECT
comment response.052405
OS/24/05
14
DEPARTMENTS
The width of the roadway (pavement) is subject to the Engineering
Division of Public Works' review and approval.
4?
Acknowledged, this width is exactly the same as the developers last six
communities in the Ci .
85. The site plan / master plan tabular data (sheet 1 of 4) should indicate the
square footage and percentage distribution of the total project site,
including area proposed for landscaped open space, vehicular use areas,
other paved areas, and building coverage and total lot coverage (Chapter
4, Section 7.EA.). R ~~
'he site tabular data table re ects a breakdown 0 all re uired in ormation.
The site plan / master plan tabular data (sheet I of 4) should indicate the number
and ratio of required and provided off-street parking spaces (Chapter 4, Section
7.E.5).
1;
re uirements are shown in the site data table on the site Ian.
The site plan / master plan tabular data (sheet 1 of 4) should indicate the
height of buildings (Chapter 4, Section 7.E.7.).
ildin hei hts table has been added to the site Ian.
Provide a detail of the fence proposed around the pool/clubhouse area,
including its dimensions, material, and color (Chapter 4, Section 7.0.).
tail will be resubmitted with the next series 0 revisions.
Provide a detail of the proposed buffer wall, including its dimensions,
materi~l, ~d color (Chapter 4, S~ction 7.0.). . t L j....
~~ ~R.-f.A ~4' ~~~ (~ L 6/ 4- a~~t, f IfU--
etail will be resubmitted with the next series 0 revisions.
Provide a detail of the entry gates proposed at the development's front
entrance, as well as proposed entry features denoted on the plans.
nclude its di nsions, material, and color(s) (Chapter 4, Section 7.0.).
ail will be resubm ed with the next series 0 revisions.
Will a lift station be required? If so, where would it be located?
The removal/relocation of landscape material is subject to review and
approval of the City Forester / Environmentalist.
On the landscape plan, ensure that the plant quantitIes must match
between the tabular data and the ra hic illustration.
INCLUDE
v
v
./
REJECT
L/
~
v
v
v
~
comment response.052405
OS/24/05
15
DEP ARTMENTS
Response: All quantities have been thorough(v reviewed to ensure consistency
between the tabular data and the graphic illustration.
All plant material shown on the landscape plan (sheet 3 of 5), in
particular within the landscape buffer, must be identified with a symbol
and its corresponding quantity.
Response: All plant material is identified and tagged with a symbol and
label. Please see attached landscape plan.
~5. A signature tree (such as a Yellow Elder, Tibouchina Granulsola, or
<' '\ Bouganvillea) is required at both s;des of each project entrance I exit
The signature trees must have 6 feet of clear trunk if placed within the
safe-sight triangle (Chapter 7.5, Article 2, Section 5.N.). Alternative
plant material may be substituted if the above referenced plant material
is not available or undesired. Any substitution of plant material (for the
signature tree requirement) will be subject to the City Landscaper /
Environmentalist review and approval.
Response: Tibouchina Granulsola has been proposed on both sides of the
project entrance, as recommended by the City of Boynton Beach.
lIe on s eet 0 i
q\4aHtltIes OR sh0€t t1 gf51 --tfriOl, provide an overalI plant list that
accurately identifies all (total) plant material provided.
Response: An overall plant list has been provided. Please refer to revised
landscape plans prepared by Cotleur & Hearing, Inc.
~ All trees are required to be at least 12 feet overall height and three (3)
./\ caliper inches at the time of installation (Chapter 7.5, Article II, Section
5.C.2.). This would apply to the Bougainvillea, Silver Buttonwood,
Hibiscus, and Ligustrum.
Response: No Silver Buttonwood are proposed on-site. All Bougainvillea,
Hibiscus and Ligustrums, due to the fact they are omamental trees and are
not available in the minimum size identified above, have been moved to the
large shrub category.
INCLUDE
J
REJ ECT
/'
/
/
comment response.052405
OS/24/05
16
DEPARTMENTS
{' . Indicate the ten (10) foot wide landscape buffers on the landscape plan
(sheets 2,3 of 5). Also, indicate any other proposed easements or land
dedications on the landscape plans.
Response: All landscape buffers, easements and land dedications have
been indicated on the revised landscape plan. Please see revised plans,
included herein.
~ On the landscape plan (sheet 3 of 5), indicate the type of trees proposed
/\ at the northeast comer of the property.
Response: The trees at the northeast corner of the property have been
appropriately labeled. Please see landscape plan included herein, as
prepared by Cotleur & Hearing, Inc.
(j
i 100. All shrubs and hedges are required to be at minimum 24 inches in
eight, 24 inches in spread, and planted with tip-to-tip spacing measured
immediately after planting to adequately cover the planted areas on the
site (Chapter 7.5, Article II, Section 5.CA.).
Response: The Applicant acknowledges this comment and has provided the
appropriate shrubs and hedges on the site.
~ Place a note on the landscape plan that all above ground mechanical
equipment such as exterior utility boxes, meters, transformers, and back-
flow preventers shall be visually screened (Chapter 9, Section 10.CA.).
Response: A note has been added to the landscape plan identifying that all
above ground mechanical equipment will be visually screened from view to
the greatest extent possible an in conformance with Chapter 9, Section
lO.C.4.
~
! ( 1 02~ Was the landscape material proposed on the Typical Unit plans
Onciuded within the overall landscape plan plant list?
Response: Only trees proposed at each of the units were included in the
overall landscape plan plant list, as these are easily identifiable as one (1)
street tree per unit. Shrubs and groundcover shown on the typical unit
plans are not included in the overall plant list.
~ .MM ~-\~ib\ ~~/ ~ ~,J) ~. /
~-(
INCLUDE
/
ct
REJECT
v/
v
~
l
comment response.052405
OS/24/05
17
DEP ARTMENTS
. ~aff recommends installing a hedge on the outside of the fence that is
/S- .req~ired around the pool area.
Response: A hedge has been added along the outside perimeter of the
required fence. Please see revised landscape plans, included herein.
104. With nO parks in the immediate vicinity, consider elimination of lots
138-140 to create a cohesive, unified park/open space area. The
proposed open space around the entry gates is disjointed from the other
recreational facilities proposed with the development and not safe for
kids running back and forth across the road.
105. The fence along the north side of 20 foot landscape buffer should be
moved further south to provide a dense/lush landscape theme on the
outside of the fence, visible from outside the development.
Response: The Applicant is not proposing to move the fence further
south, as there is ample existing vegetation on the north side of the
fence, which has been enhanced by additional cluster plantings
proposed by the Applicant. Together, these create a dense/lush
landscape theme on the outside (north side) of the fence.
r o~ ) The 110 foot strip along the north side of the property between the 20
000t landscape buffer and the LWDD canal R-O-W, should be sodded,
irrigated and maintained by the developer/HOA like all other common
areas within the site.
Noted
~taff recommends utilizing larger, Canary Island Date Palms in the
.~ entry drive median.
Response: Royal Palms have been used in lieu of Canary Island Date
Palms in the entry drive median. Please see revised plan, included herein.
~~
(~~lt ktaff recommends the perimeter landscaped buffers utilize taller, more I
Vature canopy trees behind all two story models, to soften the height
against abutting single story residences.
Response: Oaks have been proposed behind all two story models to soften
the height. Please see landscape plans, prepared by Cotleur & Hearing,
Inc., and included herein.
wt '-Sf ,'I +r~~0 C),~Q t~ 'R~ ttf {b~
INCLUDE REJECT
~
v
1..-/
/
comment response.052405
OS/24/05
18
"?
I II
DEPARTMENTS INCLUDE REJECT
~taff recommends the use of a decorative opaque gate at the fire
emergency access.
Response: A note has been added on the landscape plan, identifying the
location of a decorative opaque gate at the fire emergency access. Please
see revised landscape plan, included herein.
tJeeiA~.
110. The site data does not agree between the site plan (sheet I of 4) and the
landscape plan (sheet 5 of 5). Please correct.
Response: The site data has been revised to ensure consistency among all
plans. Please see revised plans, included herein.
K~~
MWR/sc
S:\Planning\SHARED\WP\PROJECTS\Knollwood Groves PUD\NWSP 05-017\ 1 ST REVIEW COMMENTS.doc
.
'3y YV-\tJA.\.f
- ~\{2/ '( It 0-0 .~<;
-~~
~ Str toc~ I ~ '1J S1~
__ ~ 1~0cJj ~ cll-{~h~
,
- R-e ~dJ Z{~ 7 ( ) ,
,-M-! aP fJfr ?; to iF ~r~ ~ /Vl~(J/
v:[1 -
.
~ 5t~ 2-?J 4- ~20c ~ .vAX;, ~__ ~
O~VHVJ 0'. I w~ ~
~e~ D\M at Cd;&~<< 1+( '.
~~ 1?ic[ I 7Lf:l- Ce'33~ ~ li q
I'- \ j.l \'.. e f\~ (
~\,cJJ7 tJuf~ tIt\ '?W7"'j [0 ~54 ~~.;t 1+ lOb.
.- 't>~ 1 '(:;:;el.O(-rh~ offA'fr'L JoJe {rl>'wt tIt~Tl&1
~ 1~ l ~ ~ ilf' 1\Jcf& ~ S{~ cjf?-~ /VO o~/J-t}f
t9~cf) ~.
-- ?lAtve'1
~
r--
~
.:S--
~
Johnson, Eric
From:
Sent:
To:
Cc:
Subject:
Logan, Laurinda
Friday, June 17, 2005 10:01 AM
Johnson, Eric
Livergood, Jeffrey; Kelley, David
RE: Knollwood Groves PUD
#1. Yes
#2. You'll have to ask him, but I think so.
#3. Prior to issuance of final CO.
#4. Developer
p.s. PBC permits required for work on Lawrence.
-----Original Message-----
From: Johnson, Eric
Sent: Friday, June 17, 20059:56 AM
To: Logan, Laurinda
Subject: Knollwood Groves PUD
Laurinda,
Masoud Atefi with Palm Beach County Traffic Division approved the Knollwood project for traffic concurrency purposes
but had the following comment regarding Lawrence Road:
"The Palm Beach County Traffic Division determined that the proposed project meets the Traffic Performance Standards
(TPS) of Palm Beach County, upon provision of an exclusive north-bound lane along Lawrence Road onto the project
main access driveway" .
In preparing the staff report and because my memory fails me, I wanted to confirm with you that...
#1. Our city Engineering Division was aware of this County requirement;
#2. The applicant (Julian Bryan) is aware of this County requirement;
#3. When will this northbound lane be constructed? During the permitting process? Land development permit
process? Platting process?
#4 Who is paying for this? I am thinking it is the responsiblity of the developer, correct?
Thanks for shedding some light on the situation.
Eric
1
. #
1st REVIEW RESPONSES, 5-24-05
New Site Plan bJ1Lv/~ Ar~~ '-V/,j~
Project name: Knollwood C-:ot4.D fi7()JJ~l A J ~
File number: NWSP 05-016 S 1-"11 o~ -r:; ~ f?
Reference: I slreview plans identified as a New Site Plan with an April 6. 2005 Planning a d Zoning (5 -
Department date stamp marking.
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments:
1. Prior to permit application contact the Public Works Department (561-742-
6200) regarding the storage and handling of refuse per the CODE, Section
10-26 (a).
No response required.
PUBLIC WORKS - Traffic
Comments:
2. Provide a traffic analysis and notice of concurrency (Traffic Performance
Standards Review) from Palm Beach County Traffic Engineering.
A traffic analvsis has been submitted.
3. Staff strongly recommends moving the main entrance to the north property
line, by extending Miner Rd. from Lawrence Rd. west to the easterly north-
south roadway. The proposed location of the main entry off Lawrence Rd.
will conflict with the planned park entry to the Civic Site south of
Knollwood Groves PUD. Additionally the proposed main entry has only one
egress lane that will not efficiently allow both northbound and southbound
turning movements.
The entry location has been the topic of meetings with both Palm Beach
County and City professionals. For reasons too numerous to list in this
response the entry will remain in it's general location. County stajJwill require
extending the existing median in front of the entrance thereby only allowing
for a ri/[ht in and ri/[ht out of the communitv.
4. Retain a secondary emergency access on the east property line onto
Lawrence Rd.
A second means of emergency access onto Lawrence Road has been added to
the site olano
5. Show all required off-site improvements. Extend Miner Rd. west from
Lawrence Rd. approximately 600- ft. The typical section should provide a
minimum of two 12-ft. lanes, widening to three 12- ft. lanes at the
intersection of Miner and Lawrence to allow for left turn movements.
Please see resoonse #3 above.
6. Coordinate with Palm Beach County Traffic Engineering to upgrade the
signals at Miner Rd. and Lawrence Rd.
The aoplicant has met with Palm Beach Countv traffic and roadway
cominent response.052405
OS/24/05
6
DEPARTMENTS INCLUDE REJECT
See General Note Ion Sheet 2 of the Preliminary Enf(ineerinf( Plans.
34. Utility construction details will not be reviewed for construction
acceptability at this time. All utility construction details shall be in
accordance with the Utilities Department's "Utilities Engineering Design
Handbook and Construction Standards" manual (including any
updates); they will be reviewed at the time of construction permit
application.
Acknowledf(ed.
FIRE
Comments:
35. All entrance gates to construction area shall have a Knox lock system that
will also open in case of electrical power failure. All gates shall be a
minimum of20' wide. Fire Department apparatus shall be able to turn into
the construction site in one turn.
Acknowledged, a knox box will be provided to activate the entrance gates. All
f(ates will open to provide a 20' clear ooeninf(.
36. The construction site access roads shall be maintained free of obstructions
at all times.
Acknowledf(ed
37. All required fire hydrants, standpipes or sprinkler systems shall be in place
before going vertical. Vertical construction shall be protected by standpipes
and the sprinkler system to one level below the highest level of
construction throughout the building.
Acknowledf(ed. No fire sprinkler svstems are anticipated in this proiect.
38. Any cost of damage to Fire Department vehicles because of improperly
stabilized roads or any towing fees if a vehicle becomes stuck will be the
responsibility of the contractor. A minimum of 32 tons is required for
ground stabilization.
Acknowledf(ed.
39. Adequate Fire Department vehicle turn around space shall be provided in
the construction area.
Acknowledf(ed.
POLICE
Comments: NONE
BUILDING DIVISION
Comments:
comment response.052405
OS/24/05
7
DEPARTMENTS
40. Please note that changes or revisions to these plans may generate additional
comments. Acceptance of these plans during the TRC process does not
ensure that additional comments may not be generated by the commission
and at permit review.
No response required.
41. Indicate within the site data the type of construction of each building as
defined in 2001 FBC, Chapter 6.-
A note has been added to the site plan regarding the use of CBS Masonry
construction
43. At time of permit review, submit signed and sealed working drawings of
the proposed construction.
Acknowledged
44 Identify within the site data the finish floor elevation (lowest floor
elevation) that is proposed for the building. Verify that the proposed
elevation is in compliance with regulations of the code by adding
specifications to the site data that address the following issues:
a. The design professional-of-record for the project shall add the following
text to the site data. "The proposed finish floor elevation _' _ NGVD
is above the highest 100-year base flood elevation applicable to the
building site, as determined k;.by the SFWMD's surface water
management construction development regulations."
b. From the FIRM map, identify in the site data the title of the flood zone
that the building is located within. Where applicable, specify the base
flood elevation. If there is no base flood elevation, indicate that on the
plans.
c. Identify the floor elevation that the design professional has established
for the building within the footprint of the building that is shown on the
drawings titled site plan, floor plan and paving/drainage (civil plans).
See Site Grading Notes on Sheet 2 of the Preliminary Engineering Plans.
Notes have also been added to the site plans.
45. Add to the submittal a partial elevation view drawing of the proposed
perimeter wall/fence. Identify the type of wall/fence material and the
type of material that supports the wall/fence, including the typical
distance between supports. Also, provide a typical section view drawing
of the wall/fence that includes the depth that the wall/fence supports are
below finish grade and the height that the wall/fence is above finish
grade. The location and height of the wall/fence shall comply with the
wall/fence regulations specified in the Zoning Code.
Wall and fence details will be provided with the next resubmittal for staff
review.
46. CBBCPP 3.C.3.4 requires the conservation of potable water. City water
may not, therefore, be used for landscape irrigation where other sources
are readily available.
INCLUDE REJECT
/
v
11
v
t:-//'
.)
.
comment response.052405
OS/24/05
8
, II
DEPARTMENTS INCLUDE REJECT
It is anticipated that the source of irrigation water shall be groundwater from
the lake.
47. A water-use permit from SFWMD is required for an irrigation system /
that utilizes water from a well or body of water as its source. A copy of ~
the permit shall be submitted at the time of permit application, F.S.
373.216.
AcknowledJ!ed.
48. If capital facility fees (water and sewer) are paid in advance to the City
of Boynton Beach Utilities Department, the following information shall
be provided at the time of building permit application:
a. The full name of the project as it appears on the Development Order and /
the Commission-approved site plan.
b. If the project is a multi-family project, the building number/s must be
provided. The building numbers must be the same as noted on the
Commission-approved site plans.
c. The number of dwelling units in each building.
d. The number of bedrooms in each dwelling unit.
e. The total amount paid and itemized into how much is for water and how
much is for sewer.
(CBBCO, Chapter 26, Article II, Sections 26-34)
AcknowledJ!ed.
49. At time of permit review, submit separate surveys of each lot, parcel or
tract. For purposes of setting up property and ownership in the City /
computer, provide a copy of the recorded deed for each lot, parcel or ~/
tract. The recorded deed shall be submitted at time of permit review.
A cknowledlled
50. At time of building permit application, submit verification that the City
of Boynton Beach Parks and Recreation Impact Fee requirements have
been satisfied by a paid fee or conveyance of property. The following
information shall be provided:
a. A legal description of the land.
b. The full name of the project as it appears on the Development Order and
the Commission-approved site plan. ~
c. If the project is a multi-family project, the building number/s must be
provided. The building numbers must be the same as noted on the
Commission-approved site plans.
d. The number of dwelling units in each building.
e. The total amount being paid.
(CBBCO, Chapter 1, Article V, Section 3(f))
AcknowledJ!ed 1/
5L Add a general note to the site plan that all plans submitted for permitting /
shall meet the City's codes and the applicable building codes in effect at
the time of permit application.
A note has been added to the site plan
coriiment response.052405
OS/24/05
9
DEPARTMENTS INCLUDE .1
52. Pursuant to approval by the City Commission and all other outside
agencies, the plans for this project must be submitted to the Building
Division for review at the time of permit application submittal. The plans /
must incorporate all the conditions of approval as listed In the V/
development order and approved by the City Commission.
Acknowledl!ed
53. Sheet 2 of 4. Indicate on the plans that light poles comply withy 200 I
FBC, Section 1606 for compliance with 140mph windload. Design /
calculations by a design professional registered in the State of Florida
shall be submitted at time of permit application.
Acknowledged
PARKS AND RECREATION
Comments:
54. Landscaping notes should indicate a 110% irrigation coverage.
Response: A note has been added to the landscape plan. Please see revised
plan included herein.
55. A six (6) foot black, vinyl coated chain link fence should be installed
between the development and the civic area to the south.
Response: A note has been added to the landscape plan for reference. Please
see revised plans, included herein.
56. The recreation impact fee will be :
152 single-family, detached homes @ 940.00 each = $142,880.00
The impact fee is due prior to issuance of the "first application permit".
AcknowledJ!ed
FORESTER/ENVIRONMENTALIST
Comments:
57. The Landscape Architect should indicate and tabulate the total number
of existing trees on the site. The tabular data should show the individual
species of trees proposed to remain in place, be relocated throughout the
site, or removed / replaced on site. All desirable species of existing trees
must be relocated rather than removed if the trees are in good health.
These trees should be shown by a separate symbol on the landscape plan
sheet LP5. rEnvironmental Regulations, Chapter 7.5, Article I Sec.
-~
1 st REVIEW COMMENTS
New Site Plan
Project name: Knollwood
File number: NWSP 05-016
Reference: 1 slreview plans identified as a New Site Plan with an April 6. 2005 Planning and Zoning
Department date stamp marking
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments:
1. Prior to permit application contact the Public Works Department (561-742-
6200) regarding the storage and handling of refuse per the CODE, Section
10-26 (a).
PUBLIC WORKS - Traffic
Comments:
2. Provide a traffic analysis and notice of concurrency (Traffic Performance
Standards Review) from Palm Beach County Traffic Engineering.
3. Staff strongly recommends moving the main entrance to the north property
line, by extending Miner Rd. from Lawrence Rd. west to the easterly north-
south roadway. The proposed location of the main entry off Lawrence Rd.
will conflict with the planned park entry to the Civic Site south of Knollwood
Groves PUD. Additionally the proposed main entry has only one egress lane
that will not efficiently allow both northbound and southbound turning
movements.
4. Retain a secondary emergency access on the east property line onto Lawrence
Rd.
5. Show all required off-site improvements. Extend Miner Rd. west from
Lawrence Rd. approximately 600-ft. The typical section should provide a
minimum of two 12-ft. lanes, widening to three 12-ft. lanes at the intersection
of Miner and Lawrence to allow for left turn movements.
6. Coordinate with Palm Beach County Traffic Engineering to upgrade the
signals at Miner Rd. and Lawrence Rd.
7. Extend the center median on Lawrence Rd. south of Miner Rd. approximately
70-ft. north.
ENGINEERING DIVISION
Comments:
8. All comments requiring changes and/or corrections to the plans shall be
reflected on all appropriate sheets.
9. Please note that changes or revisions to these plans may generate additional
...
1ST REVIEW COMMENTS
04/28/05
4
DEPARTMENTS INCLUDE REJECT
on the Health Department application forms or within seven (7) days of site
plan approval, whichever occurs first. This fee will be determined based
upon final meter size, or expected demand.
29. Water and sewer lines to be owned and operated by the City shall be
included within utility easements. Please show all proposed easements on
the engineering drawings, using a minimum width of 12 feet. The
easements shall be dedicated via separate instrument to the City as stated in
CODE Sec. 26-33(a).
30. This office will not require surety for installation of the water and sewer
utilities, on condition that the systems be fully completed, and given to the
City Utilities Department before the first permanent meter is set. Note that
setting of a permanent water meter is a prerequisite to obtaining the
Certificate of Occupancy.
31. A building permit for this project shall not be issued until this Department
has approved the plans for the water and/or sewer improvements required to
service this project, in accordance with the CODE, Section 26-15.
32. Appropriate backflow preventer(s) will be required on the domestic water
service to the dwellings as well as the recreational building, and the fire
sprinkler line if there is one, in accordance with the CODE, Section 26-207.
33. The LDR, Chapter 3, Article IV, Section 3(P) requires a statement be
included that support utilities are available and will be provided by all other
appropriate agencies. This statement is lacking on the submitted plans.
34. Utility construction details will not be reviewed for construction
acceptability at this time. All utility construction details shall be in
accordance with the Utilities Department's "Utilities Engineering Design
Handbook and Construction Standards" manual (including any updates);
they will be reviewed at the time of construction permit application.
FIRE
Comments:
35. All entrance gates to construction area shall have a Knox lock system that
will also open in case of electrical power failure. All gates shall be a V
minimum of 20' wide. Fire Department apparatus shall be able to turn into
the construction site in one turn.
36. The construction site access roads shall be maintained free of obstructions at t/
all times.
37. All required fire hydrants, standpipes or sprinkler systems shall be in place V
before going vertical. Vertical construction shall be protected by standpipes
.
1ST REVIEW COMMENTS
04/28/05
5
DEPARTMENTS INCLUDE REJECT
and the sprinkler system to one level below the highest level of construction V-
throughout the building.
38. Any cost of damage to Fire Department vehicles because of improperly
stabilized roads or any towing fees if a vehicle becomes stuck will be the V
responsibility of the contractor. A minimum of 32 tons is required for
ground stabilization.
39. Adequate Fire Department vehicle turn around space shall be provided in
the construction area. V--.
POLICE
Comments: NONE
BUILDING DIVISION
Comments:
40. Please note that changes or revisions to these plans may generate additional
comments. Acceptance of these plans during the TRC process does not
ensure that additional comments may not be generated by the commission
and at permit review.
41. Indicate within the site data the type of construction of each building as
defined in 2001 FBC, Chapter 6.
42. Buildings, structures and parts thereof shall be designed to withstand
the minimum wind loads of 140 mph. Wind forces on every building or
structure shall be determined by the provisions of ASCE 7, Chapter 6, and
the provisions of 2001 FBC, Section 1606 (Wind Loads). Calculations that
are signed and sealed by a design professional registered in the state of
Florida shall be submitted for review at the time of permit application.
43. At time of permit review, submit signed and sealed working drawings of the
proposed construction.
44. Identify within the site data the finish floor elevation (lowest floor elevation)
that is proposed for the building. Verify that the proposed elevation is in
compliance with regulations of the code by adding specifications to the site
data that address the following issues:
a. The design professional-of-record for the project shall add the following
text to the site data. "The proposed finish floor elevation _' _ NGVD
is above the highest 100-year base flood elevation applicable to the
building site, as determined by the SFWMD's surface water management
construction development regulations."
b. From the FIRM map, identify in the site data the title of the flood zone
that the building is located within. Where applicable, specify the base
flood elevation. If there is no base flood elevation, indicate that on the
1 ST REVIEW COMMENTS
04/28/05
7
*
DEPARTMENTS INCLUDE REJECT
c. If the project is a multi-family project, the building number/s must be
provided. The building numbers must be the same as noted on the
Commission-approved site plans.
d. The number of dwelling units in each building.
e. The total amount being paid.
(CBBCO, Chapter 1, Article V, Section 3(t))
51. Add a general note to the site plan that all plans submitted for permitting
shall meet the City's codes and the applicable building codes in effect at the
time of permit application.
52. Pursuant to approval by the City Commission and all other outside agencies,
the plans for this project must be submitted to the Building Division for
review at the time of permit application submittal. The plans must
incorporate all the conditions of approval as listed in the development order
and approved by the City Commission.
53. Sheet 2 of 4. Indicate on the plans that light poles comply withy 2001 FBC,
Section 1606 for compliance with 140mph windload. Design calculations
by a design professional registered in the State of Florida shall be submitted
at time of permit application.
PARKS AND RECREATION
Comments:
54. Landscaping notes should indicate a 110% irrigation coverage. /
55. A six (6) foot black, vinyl coated chain link fence should be installed ./
between the development and the civic area to the south.
t~ -(0 140 uPrf$ - /tJ~ W ID ~ev( ~(; CA-lC.
56. The recreation impact fee will be : ~
152 single-family, detached homes @ 940.00 each = $142,880.00
The impact fee is due prior to issuance of the "first application permit".
FORESTER/ENVIRONMENT ALIST
Comments:
57. The Landscape Architect should indicate and tabulate the total number of
existing trees on the site. The tabular data should show the individual
species of trees proposed to remain in place, be relocated throughout the
site, or removed / replaced on site. All desirable species of existing trees
must be relocated rather than removed if the trees are in good health. These
5!~\06
if!.
r)
V-~ ~ /
,-\_0)
5. ~
1ST REVIEW COMMENTS
04/28/05
8
DEPARTMENTS INCLUDE REJECT
trees should be shown by a separate symbol on the landscape plan sheet ~
LP5. [Environmental Regulations, Chapter 7.5, Article I Sec. 7.D.p. 2.]
58. Landscape Plan
Sheet 5 of 5.1 of 1 ( Lakes)
All shade and palm trees on the Plant list must be listed in the specifications
as a minimum of3" diameter at DBH (4.5' off the ground), 12'.14' height 1.-----'"
minimum and Florida # 1. The height of the trees will be larger than 12' -14'
to meet the 3" diameter requirement. [Environmental Regulations, Chapter
7.5, Article IT Sec. 5.C. 2.]
59. The details section for the Tree and Palm Planting Detail should include a
line indicating where the height of the tree will be measured at time of ~
planting and inspection.
60. All groundcover / vine plantings should have a height and spread ~
measurement.
61. The applicant should amend the note indicating that all utility boxes or
structures (not currently known or shown on the plan) should be screened /
with Coco plum hedge plants on three sides.
62. The applicant must submit a Lake Management Plan document for the V
lakes.
63. Irrieation Plan-No Irrieation plan included in the submittal V
The irrigation system design (not included in the plans) should be low
volume water conservation using non-portable water.
64. Turf and landscape (bedding plants) areas should be designed on separate V
zones and time duration for water conservation.
65. Trees should have separate irrigation bubblers to provide water directly to
the root ball. [Environmental Regulations, Chapter 7.5, Article IT Sec. 5. ~
C.2.]
PLANNING AND ZONING
Comments:
66. At the technical advisory review team meeting, provide written responses to
all staff's comments and questions. Submit 12 sets of revised plans. Each
set should be folded and stapled.
67. At the technical advisory review team meeting, provide a full set of
drawings, sized 8Y2 inches by 11 inches of each plan. Save each plan to a
compact disk and submit that to staff as well.
...,.
""'
1 ~~REVIEW RESPONSES, 5-24-05
New Site Plan
l _ !
.I.V'
i'- .1
Project name: Knollwood
File number: NWSP 05-016
Reference: 1 st review plans identified as a New Site Plan with an April 6, 2005 Planning and Zoning
Department date stamp marking.
DEPARTMENTS INCLUDE REJECT
PUBLIC WORKS - General
Comments:
1. Prior to permit application contact the Public Works Department (561-742-
6200) regarding the storage and handling of refuse per the CODE, Section
10-26 (a). "'I-,
No response required.
PUBLIC WORKS - Traffic
-
Comments: .
2. Provide a .trttffie-tmalysisand notice of concurrency (Traffic Performance
Standards Review) from Palm Beach County Traffic Engineering. ").:"
A traffic ana(ysis has been submitted.
3. Staff strongly recommends moving the main entrance to the north property
line, by extending Miner Rd. from Lawrence Rd. west to the easterly north-
south roadway. The proposed location of the main entry off Lawrence Rd.
will conflict with the planned park entry to the Civic Site south of
Knollwood Groves PUD. Additionally the proposed main entry has only one
egress lane that will not efficiently allow both northbound and southbound
turning movements. ~"" '
The entry location has been the topic of meetings with both Palm Beach
County and City professionals. For reasons too numerous to list in this
response the entry will remain in it's general location. County staffwill require
extending the existing median in front of the entrance thereby only allowing
for a right in and right out of the community.
4. Retain a secondary emergency access on the east property line onto
Lawrence Rd.
I
A second means of emergency access onto Lawrence Road has been added to
the site plan.
5. Show all required off-site improvements. Extend Miner Rd. west from
Lawrence Rd. approximately 600-ft. The typical section should provide a
mInImUm of two 12- ft. lanes, widening to three 12- ft. lanes at the
intersection of Miner and Lawrence to allow for left turn movements. '.
Please see response #3 above.
6. Coordinate with Palm Beach County Traffic Engineering to upgrade the
signals at Miner Rd. and Lawrence Rd. "
The applicant has met with Palm Beach County traffic and roadway
...
comment response.052405
OS/24/05
2
DEPARTMENTS INCLUDE REJECT
production. Warrants necessary for upgrading the signal do not exist at this
time.
7. Extend the center median on Lawrence Rd. south of Miner Rd.
approximately 70-ft. north. ,...
The center median has been extended north as requested.
ENGINEERING DIVISION
Comments:
8. All comments requiring changes and/or corrections to the plans shall be
reflected on all appropriate sheets.
All corrections have been shown on all sheets
9. Please note that changes or revisions to these plans may generate additional
comments. Acceptance of these plans during the TRC process does not
ensure that additional comments may not be generated by the Commission .
and at permit review.
Acknowled!!ed
10. Show proposed site and street lighting on the Site and Landscape plans
(LDR, Chapter 4, Section 7.BA.) Lighting will be required for the parking
area adjacent to the recreation area. l
Lif!htinf! has been added to all applicable plans.
11. The two Live Oaks located in Lots 96 and 97 (either side of the drainage
easement) are placed too close together for their mature size. Staff
recommends that the cultivars "Highrise" or "Cathedral" be used for Live
Oaks, particularly where called out along rear property lines. '''.,,,
Response: One of the proposed Live Oaks has been removed from the
landscape plan, as requested. "Highrise" species have been designated
throughout the project. Please see revised landscape plan included herein.
12. All trees and palms should be placed a minimum of five feet off the
property lines and away from driveways, sidewalks and curbs to allow for
future growth and prevent heaving of the aforementioned structures.
Response: All street trees have been placed at least 5 feet from drives,
sidewalks and curbs. Please see landscape plans, prepared by Cotleur &
Hearing, Inc., and included herein.
13. Wild Date Palm/Sylvester specified within the entryway median does not
have adequate clear trunk specified for vehicle clearance due to the large
size (length) of the fronds which will hang into traffic. "
Response: The Wild Date Palm/Sylvester has been replaced with Royal Palms.
Please see revised plans prepared by Cotleur & Hearing, Inc.
14. The Shrub/Groundcover Planting Detail on Typical Unit Landscape Plan
Sheet 2 of 2 depicts planting for a tree. Please correct.
Response: The Planting Detail, referred to above, identifies a shrub.
Please refer to landscape plans, included herein.
comment response.052405
OS/24/05
3
DEPARTMENTS
15. It may be necessary to replace or relocate large canopy trees adjacent to
light fixtures to eliminate future shadowing on the parking surface (LDR,
Chapter 23, Article II, Section A.1.b).
Response: This has been noted in the General Notes on the
landscape plan. The proposed trees have been adjusted per the
lighting plan. Please see revised plans, included herein.
16. Show sight triangles on the Landscape plans (LDR, Chapter 7.5, Article II,
Section 5.H.). Reference FDOT Standard Index 546 for the sight triangles
along Lawrence Road. Use a minimum 25-ft. site triangle for interior
development intersections (revise the note on Landscape Plan Sheet 1 of 5.)
Response: The required safe sight triangles have been included on
the landscape plans.
17. Per the LDR, Chapter 7.5, Article II, Section 5.C.2. Ficus species are not
permitted.
Response: The ficus shrub located in the green island has been
replaced with a Carissa "Green island". Please refer to revised
landscape plans.
18. Provide a legend for the plant symbols.
Response: All plants are denoted and tagged on the landscape
plans with letter symbols, which correlate to the comprehensive
plant list included within the landscape plan package. Please refer
to landscape plans, included herein, for further clarification.
19. Live Oaks are proposed within the utility easement on the east side of the
recreation area. Canopy trees are not allowed within utility easements.
Please replace with a different species.
Response: All canopy trees have been pulled to a location behind
the easement. Royals have been identified around the perimeter of
the recreation area.
Acknowledged. See Site Grading Note #8 on Sheet 2 of the Preliminary
En1!ineerinJ! Plans.
21. Paving, Drainage and Site details will not be reviewed for construction
acceptability at this time. All engineering construction details shall be in
accordance with the applicable City of Boynton Beach Standard Drawings
and the "Engineering Design Handbook and Construction Standards"
and will be reviewed at the time of construction permit application.
Acknowledged.
22. Upon Commission approval of the site plan schedule a pre-application
meeting with the Engineering Division to begin the plat process.
INCLUDE REJECT
'.
comment response.052405
OS/24/05
4
DEPARTMENTS
Acknowledged.
UTILITIES
Comments:
:2.). Please provide a time line that clearly illustrates when water and sewer
services will be required to serve the proposed project. Your starting date
for the timeline should be the date of City Commission approval. Also
provide milestone dates for permit application, the start of construction,
and the setting of the first water meter. This timeline will be used to
determine the adequacy of water and wastewater treatment capacity for
your project upon the project's completion, so please be as accurate as
possible.
We expect water and sewer service will be required 12 months after the City
Commission approval.
City Commission Approval - Month 0
Permit Application - Month 2
Start of Construction - Month 7
First Water Meter-Month 12
24. All utility easements and utility lines shall be shown on the Site plan and
Landscape plans (as well as the Water and Sewer Plans) so that we may
determine which appurtenances, trees or shrubbery may interfere with
utilities. In general, palm trees will be the only tree species allowed within
utility easements. Canopy trees may be planted outside of the easement so
that roots and branches will not impact those utilities within the easement
in the foreseeable future. The LDR, Chapter 7.5, Article I, Section 18.1
gives public utilities the authority to remove any trees that interfere with
utility services, either in utility easements or public rights-of-way.
Most all water and sewer has been shown in the road R/W which will also be a
utility easement to the City. A 10 foot general utility easement has been shown
adjacent to the road RIW. Utility easements outside the road R/W have been
shown. All easements will be dedicated by plat.
25. Palm Beach County Health Department permits will be required for the
water and sewer systems serving this project (CODE, Section 26-12).
A cknowledf(ed.
26. Fire flow calculations will be required demonstrating the City Code
requirement of 1,500 g.p.m. (500 g.p.m. some residential developments)
with 20 p.s.i. residual pressure as stated in the LDR, Chapter 6, Article IV,
Section 16, or the requirement imposed by insurance underwriters,
whichever is greater (CODE, Section 26-16(b)).
Fire Flow calculations will be provided at the time of permit application.
27. The LDR, Chapter 6, Article IV, Section 16 requires that all points on each
building will be within 200 feet of an existing or proposed fire hydrant.
INCLUDE REJECT
comment response.052405
OS/24/05
5
DEPARTMENTS
INCLUDE REJECT
Numerous lots are not covered by this requirement; lots not covered are: 9,
10 partially, 31 partially, 40 partially, 51 partially, 52, 53, 54, 65, 66, 67,
79 partially, 80, 81, 82 partially, 87, 88, 89, 90 partially, Ill, 112, 113, 120
partially, 127 partially, 128, 135, 136, 137, 147 partially, 148, and 149.
Reconfigure fire hydrant locations to meet this code requirement.
"
This code section also provides for an exception to the above requirement for
one and two story residential project with a density of less than 10 units
per acre which this project qualifies. We believe the plan meets the
exception requirements.
28. The CODE, Section 26-34(E) requires that a capacity reservation fee be
paid for this project either upon the request for the Department's signature
on the Health Department application forms or within seven (7) days of site
plan approval, whichever occurs first. This fee will be determined based
upon final meter size, or expected demand.
Acknowledf(ed.
29. Water and sewer lines to be owned and operated by the City shall be
included within utility easements. Please show all proposed easements on
the engineering drawings, using a minimum width of 12 feet. The
easements shall be dedicated via separate instrument to the City as stated in
CODE Sec. 26-33(a).
See response to item 24.
30. This office will not require surety for installation of the water and sewer
utilities, on condition that the systems be fully completed, and given to the
City Utilities Department before the first permanent meter is set. Note that
setting of a permanent water meter is a prerequisite to obtaining the
Certificate of Occupancy.
Acknowledf(ed.
31. A building permit for this project shall not be issued until this Department
has approved the plans for the water and/or sewer improvements required
to service this project, in accordance with the CODE, Section 26-15. .
Acknowledged. See Fire and Life Safety notes on Sheet 2 of the Preliminary
Enf(ineerinf( Plans.
32. Appropriate backflow preventer(s) will be required on the domestic water
service to the dwellings as well as the recreational building, and the fire
sprinkler line if there is one, in accordance with the CODE, Section 26-
207.
Acknowledf(ed.
33. The LDR, Chapter 3, Article IV, Section 3(P) requires a statement be
included that support utilities are available and will be provided by all
other appropriate agencies. This statement is lacking on the submitted
plans.
comment response.052405
OS/24/05
6
DEPARTMENTS INCLUDE REJECT
See General Note 1 on Sheet 2 of the Preliminary Engineering Plans.
34. Utility construction details will not be reviewed for construction
acceptability at this time. All utility construction details shall be in
accordance with the Utilities Department's "Utilities Engineering Design
Handbook and Construction Standards" manual (including ;
any ,
;;
updates); they will be reviewed at the time of construction permit
application.
Acknowledged.
FIRE
Comments:
35. All entrance gates to construction area shall have a Knox lock system that
will also open in case of electrical power failure. All gates shall be a
minimum of 20' wide. Fire Department apparatus shall be able to turn into
the construction site in one turn.
Acknowledged, a knox box will be provided to activate the entrance gates. All
gates will open to provide a 20' clear opening.
36. The construction site access roads shall be maintained free of obstructions
at all times.
Acknowledged
37. All required fire hydrants, standpipes or sprinkler systems shall be in place
before going vertical. Vertical construction shall be protected by standpipes
and the sprinkler system to one level below the highest level of
construction throughout the building.
Acknowledged. No fire sprinkler systems are anticipated in this proJect.
38. Any cost of damage to Fire Department vehicles because of improperly
stabilized roads or any towing fees if a vehicle becomes stuck will be the
responsibility of the contractor. A minimum of 32 tons is required for
ground stabilization.
Acknowledged.
39. Adequate Fire Department vehicle turn around space shall be provided in
the construction area.
Acknowledged.
POLICE
Comments: NONE
BUILDING DIVISION
Comments:
.~ '01; r
. <n;lO ;108 III 1 .
. -;lOlm::c )>
:~ ! ~ <:l < ~ -l '. ~ 1 ~
,:C'l e I .:,~ i Cr ~ 1.
f~a~m ~ , :
,(1) ~<n .
:..... trim ] "
j ~ . .
~i'~!~1!
'".' ."'~'_tl':.:~~~l~"
:",~ - ..
~~~:~~: I
. ~;.ii:.=- .'
.1~... .. I.~.
!.I", ,,_:. ;e. I .
.~::::. :.;
~~,:,:' 1.::.ii:.1
11 . . I.......
'. . I::;,~~"
:J :~'..::.::~, ..:~ii:c,
-~..'.-.... . I~~
. . '. '. .' ',..... ..,;~
,.... . t:....
...-.:JI" I ~.:.::.::: ".::~;,r"
--, : I . . . " _
~."".4 ..... ....., ~::::~. ~:.:...
' ;.... '............................ ~.... ~':liil
','. .......... · .......... · ........ .. ".:.:., ~::'l!i
:~.:............... .. .. . :::::' ..:::: l:':.
............. ....'~-'=H
.. .i. . ....
m~rl::~~m ~~Ii.
.... ..... ..... ...... Je..iI......
:......, , '.:. O....i:t
-. ."". ::.'.- '.-- '... .. "'0 to',." 'e:'::.:.' -~..." !
::.:. ~.:.:: \M . ~
....: . .' ':'. ITl -< '::.a
:.::.~.,.::.:.):> I~..:~!I
.:-....-,.;c.-.: ("') z ...
":.:..:.. ... """0' ;::~~
t;i ::m; ~ z :r-f.:...~.'~..,...:... :.!
:'.:. ....:. ~
.::.:: .::.: ::~:..~
:..:., .:.:. .....
.::.: .:.: :.t:..~
:.... ..... '41"'*'_
· "..:' ":...-.-. i. ....ii,'. . .....
· · · · · · '. · .... .... 00;........ r. . '. .
... ............ ............ ......:.. ....:~.~.........'-. '.'~.. '
,.......0... ...... .......... .......: ~.
............... .
~..!".!_.&.- ..... ,.
,
~
- -
'..,
,...
F
, I
f
.,
~, ~,.;
to"~$V
,/ ~ ..
~\9 "il, 10/
"'0.> ~O /
~.>
(/)
~'"
'-~
v..
~O
....
1\)\1' l\l ::u
00 2 ....
o tIl . I...
.,. . .... ....VI
O~NN"""'"
~ CD ~(I)
N f!'h
T
.1'11 +
.
)>
;e
CD
o
-<
Z
.--1
o
Z
J,
\::
"
.
./
..
f1"1
)>
(")
:I:
:1
')
'"
.,:'1:!'!
:=8'
'b I 't
~;c;i~ _t
,r-Il
J I I I -~,:,~8
) bo....1 ~~ :s ~-o ~ a7 ~
P ..n Ci) ".. <f ~ I
Ie I ,-.,.... 0 I U) 0 -I -II
I!I;' f t!~~~ ~ Cr
- '~ ~ (n OJ ·
< c.nm _.
,~ .
~Ii .. ..,
I. I ii."'
t .~
,---- .
" W, 'e,.:.,,:.'.,
~ ~.; I . f!.~'.~~.j!t.
_ ~ "'.'---'. ' -----r;:.,
· · I ~'~:;::~:: l:~:::"
. ? -.to I ..,.., ~~.~~. I....,
fIII'tiI 'r;-:.-~.. I.~.
I I 1.:.:.: I:::
~ .~.:.:. j.:"
~il I I. :~~~~~~ \;:2
.J..L',.,:. . I: ,F.:::::., I::z~;ri
· l.........~.'i.~.'..
C4_',__"_". ",,'"'' .......-. .::::.-: 1.-';-;"\
..'.---.".'..1..... I' .... .'.'.: .; . .la, 'e~.:.,,"
,.1'....1'.1, I, 1,..',..',',............',..: I: .:.:, ;.:.:fli
.',..',',............'1. It..'..~... ........ 1:.:.:-\ }-. e,';,.
. . . i .....; r..'~.'.i
:::::."::::: ~:~z.~
.......:...... \e..,~:iI
............ '.:.,:~\
::::: ~:::: ;:,;.:,::~..'..
:.:.'.'" ..:.... C...~~-
. . . . ....,.'
. . .", .. ..... ..'........'.::
.:.:-:'" .:.:.:. ~:.'~i1
........~:,: IL..--...... ....~.~'..',;,'~
. . :' Ii . . ~'.H.!'~-',.
.....,.." ~......; ,.., &:I :-.',:4J~(" .
.....-'" "'....' t.N 0 E'..t~~~'
. ..-- __.. ._ '. I
............ 111 . .... ..--Wl.ri
..... ...... ):)- -<..~-~,
~~~~~; ~.~~~; ~ O~. ~;:;~
.:...:,~ ..!..... ':::;I'~!
...:.:,:"'- "'..:.: ~ .. '
.....- '..... .:::Iii- :e:.:' I
.....':,~ ..... .....1
. . ..."', .. r-.-.
.....:,.. .... .. . -I
.....::! ..... I.......,
.....' .... ...~
t...' ..... .... ....;-~
I. · · .....~~...................I.:.:.-:_ -.:.:_ . .:.-:~a
.........0.""'..... .'. 1'1 ......-' .. '... i.. ....v.~
'_' . .. ......... 1'-',-, . . . .: >
:.".',,:...,,:...,:,'.!__~;;"'.., .,' ,',~. ~""'''i'~i'!'" ~,..,. :~,,:~,
r
, I
I.
...
~ ~~.~
A" 'V....
r.. .~
,/ .. It.. ...
~\9 ~V.. .10
"'0 & 7/
>0
~.>
a~
~I:""
&>
17 "
&>0
I\l\ ....
0'" ""::0
00 0....
.01 ~
ow -.j.:a.~
. - NN ~
N CD ~cn
N ~A
.'
--!~
.
G)l;' .r
Gl 1 '
]:>> ,
~ 1 ~'
~ 1 .
1 :
L?
.
J
.
.
,
_ oJ
m
o
-<
Z
'--I
o
Z
L""
"..
. .
",
.
(D
fF1
)>
o
::I:
i.....~.._.. -.'."'~-
'.. .. ,_"e".
:..:..:r......;'.....".. ~.!.
~.:~~ .,j: ~<,:
..
Ie ...
I....;
, . .
1:.:.,
f. .
. .
'.:-.'.1
I- . ..-0'
I....,..
I... ,.....':'.....)..
..... --c!
I...',
.
L.~
!~..
.
.~
:l
?
v:
'r I:
I
I
!
I
:11 !
li~
III
!
~.
i
I
!'
( J 'iI'flj
, lrfl,.,
e '1 ~ flliil!
1-( 11111:j
~d i i J iiI/fir
.~ ~ r ljllil
I
~,.~
. ~,.:. >.
. 'If \ .:~~' ' , ! ': Ii , .
.. '1 .,
M , ~ . 't . z.: i , . ~~~ I'
... I ,\ ..., ;~l~: I~'
. ,I!' ~ I . . ,. 0. .
...~ 'I", 'I II . .~ r' --- "'" -..
-~\ 1;... \ ~ ,/-;-~t. .
!.I....:il.i.i.'vdfL.,; I." 1',:11""'"
....~ \.' ~.I:"i~'!' '
I .'. l:lati ._' _I
d:. 1"_''#''/1
if"'''',
i . l, , , ~.
, . 11'1,. -I if : , " '. I
. . iii- '!'~~ i \.:!
i : '0 , ' ,: ?'ii
i : I!!~ JJL.:t>,., z.~
il ' "A, , ,Eil":Xl. 9i'
, !t/,>"^r'r.(: f
. I-~ 1 ",/ , ~ -1115: I 1: I~
: ~:Hi t "ijr , :'
'I ',',. , I;"!'" ".',1
. ~ : ~ J ': :il..
.:~.::
!ij~
.: rill
~~.
~r
n~= ~
!
~H~i
, +.,
: I~'.
F-
Ui' ~M.
I
'.
: U!~:
p
,:\f'
.
. .
I~~
~ ~
, I
i~i~
=~~
(f)
fT1
Ii!
.='
~,
:i
Ij~!!lIi~ III T :,:!! Tlil'l~m.,,~ l:'
I:~ ~ ~ !~.. I I!;h .
'l;';~:"i'!'" .'
,'. ~lL. .
I" H:. i;;:!j , 1] ! l H;Q! "!
m. "1~li: ,'" I
-.. 10 II,~N :qq.
~:~I l~ '1m '
Inm.mg : : J<
.! "
i
-.t.. :!j
i !jl~
I
,
I
I
~,~y
.(
; ~_:.~i~
iii,
=~J
u!~
I:E:C
."
H~~
jfT1
..,
Facsimile
TRANSMITTAL
CITY OF BOYNTON BEACH
100 E. BOYNTON BEACH BOULEVARD
P.O. BOX 310
BOYNTON BEACH, FLORIDA 33425-0310
FAX: (561) 742-6259
PLANNING AND ZONING DIVISION
to: Chip Bryan
fax #: fIR/ 3C1/ ' 3~d~
date: April 28, 2005
from: Sherie Coale
re: 1 ST REVIEW COMMENTS FOR Knollwood
Please find attached the first review comments for your project. To stay on the
current review schedule, please do the following steps listed below, and bring all
documents to the Technical Application Review Team who will meet on Tuesday,
May 17,2005.
1. Revise your plans incorporating all comments listed herein, including the addition of
notes on plans to confirm response to general statements/ comments, and bring 12 copies
to the TART meeting (full sets including all pages originally submitted);
2. Submit the additional information as requested within the attached comments; ( i.e. traffic
analysis, engineering certification, etc.)
3. Prepare a written response (7 copies) consisting of a list briefly summarizing how each
comment has been addressed on the revised plans or with the supplemental information
including location on the plans (this promotes an expeditious 2n review by staff and your
project representatives during the TART meeting );and
4.
Submit reductions (8 ~ X 11) and in digital
format (JPEG) for the proposed site plans,
elevations and landscaping plan (this is required
for the final report and public presentation).
Planning and Zoning Division
City of Boynton Beach
Boynton Beach, Florida 33425
742-6260
Fax: 742-6259
~
The applicant should not attend a second review meeting until all documents have been revised
and copied for staff review. Ifplans will not be fully revised and brought to the scheduled
meeting, contact Ed Breese in this office by the Thursday prior to the scheduled meeting date.
Projects deviating from the original schedule are eligible for review at subsequent meetings,
which are held every Tuesday. To reschedule, contact Sherie Coale, by the Thursday prior to the
Tuesday meeting that you desire to attend. The remainder of the review schedule will be
adjusted accordingly. If you have questions on the attached comments, please contact the
respective reviewer using the attached list of review representatives.
If the plans are reasonably complete and all significant comments are addressed following 2nd
review, the project is forwarded to the Planning and Development Board meeting that falls
approximately 2 to 3 weeks following the TART meeting. An "*,, by any comment identifies a
comment that must be addressed prior to moving forward to the Planning and Development
board.
Note: Items recognized by staff as typically outstanding at this point include a traffic report
and/or confirmation ofthe traffic concurrency approval from the Palm Beach County
drainage certification by a licensed engineer, signed "Rider to Site Plan Application"
form and colored elevations of the proposed project. This information is necessary for
the project to proceed. If you have submitted this information, please disregard this note.
DEPARTMENT REPRESENTATIVE REPRESENT A TIVES' PHONE FAX
DESIGNEE
Engineering Dave Kelley Laurinda Logan 742-6482 742-6485
Building Don Johnson Timothy Large 742-6352 742-6352
Fire Department Rodger Kemmer Rick Lee 742-6753 742-6357
Police Department Marshall Gage John Huntington 737-6167 737-3136
Utilities Pete Mazzella H. David Kelley Jr. 742-6401 742-6485
Public Works-General Larry Quinn Laurinda Logan 742-6482 742-6485
Public W orks- Traffic Jeffrey Livergood Laurinda Logan 742-6482 742-6485
Parks & Recreation Jody Rivers 742-6227 742-6233
Forester/Environmentalist Kevin Hallahan Kevin Hallahan 742-6267 742-6259
Planning & Zoning Michael Rumpf, Ed Breese 742-6262 742-6259
CHAIRMAN
REVISED 4/12/05
S:IPlanningISHAREDlWPIPROJECTSlKnollwood Groves PUDINWSP 05-01711s1 Review comments FAX COVERdoc
TRC COMMENTS
PROJECT:
FILE #
TYPE OF PROJECT:
SIZE OF PROJECT:
CAPACITY:
KNOLLWOOD
NWSP 05-017
RESIDENCES
36.17 ACRES
152 SINGLE FAMILY RESIDENCES WITH CLUB
HOUSE
COMMENTS
1. All entrance gates to construction area shall have a Knox lock
system that will also open in case of electrical power failure. All
gates shall be a minimum of 20' wide. Fire Department apparatus
shall be able to turn into the construction site in one turn.
2. The construction site access roads shall be maintained free of
obstructions at all times.
3. All required fire hydrants, standpipes or sprinkler systems shall be in
place before going vertical. Vertical construction shall be protected
by standpipes and the sprinkler system to one level below the
highest level of construction throughout the building.
4. Any cost of damage to Fire Department vehicles because of
improperly stabilized roads or any towing fees if a vehicle becomes
stuck will be the responsibility of the contractor. A minimum of 32
tons is required for ground stabilization.
5. Adequate Fire Department vehicle turn around space shall be
provided in the construction area.
6. The finished roof height is very close to the 30' mark. The height of
the buildings will be measured and if they exceed 30' they will be
required to install a fire sprinkler system.
../
DEPARTMENT OF PUBLIC WORKS
ENGINEERING DIVISION
MEMORANDUM NO. 05-050
TO:
Ed Breese, Principal Planner, Planning and Zoning
FROM:
Laurinda Logan, P.E., Senior Engineer
DATE:
April 25, 2005
RE:
Review Comments
New Site Plan - 1 st Review
Knollwood Groves PUD
File No. NWSP 05-017
The above referenced Site Plans, received on April 18, 2005, were reviewed for Public Works,
Engineering, and Utilities against the requirements outlined in the City of Boynton Beach Code of
Ordinances. Following are our comments with the appropriate Code and Land Development Regulations
(LDR) referenced.
PUBLIC WORKS - GENERAL
1. Prior to permit application contact the Public Works Department (561-742-6200) regarding the
storage and handling of refuse per the CODE, Section 10-26 (a).
PUBLIC WORKS - TRAFFIC
2. Provide a traffic analysis and notice of concurrency (Traffic Performance Standards Review) from
Palm Beach County Traffic Engineering.
3. Staff strongly recommends moving the main entrance to the north property line, by extending Miner
Rd. from Lawrence Rd. west to the easterly north-south roadway. The proposed location of the main
entry off Lawrence Rd. will conflict with the planned park entry to the Civic Site south of Knollwood
Groves PUD. Additionally the proposed main entry has only one egress lane that will not efficiently
allow both northbound and southbound turning movements.
4. Retain a secondary emergency access on the east property line onto Lawrence Rd.
5. Show all required off-site improvements. Extend Miner Rd. west from Lawrence Rd. approximately
600-ft. The typical section should provide a minimum of two 12-ft. lanes, widening to three 12-ft.
lanes at the intersection of Miner and Lawrence to allow for left turn movements.
6. Coordinate with Palm Beach County Traffic Engineering to upgrade the signals at Miner Rd. and
Lawrence Rd.
7. Extend the center median on Lawrence Rd. south of Miner Rd. approximately 70-ft. north
'" "'
Department of Public Works/Engineering Division Memo No. 05-050
Knollwood Groves PUD, New Site Plan 1st Review
April 25, 2005
Page 2
ENGINEERING
8. All comments requiring changes and/or corrections to the plans shall be reflected on all appropriate
sheets.
9. Please note that changes or reVISions to these plans may generate additional comments.
Acceptance of these plans during the TRC process does not ensure that additional comments may
not be generated by the Commission and at permit review.
10. Show proposed site and street lighting on the Site and Landscape plans (LDR, Chapter 4, Section
7.B.4.) Lighting will be required for the parking area adjacent to the recreation area.
11. The two Live Oaks located in Lots 96 and 97 (either side of the drainage easement) are placed too
close together for their mature size. Staff recommends that the cultivars "Highrise" or "Cathedral" be
used for Live Oaks, particularly where called out along rear property lines.
12. All trees and palms should be placed a minimum of five feet off the property lines and away from
driveways, sidewalks and curbs to allow for future growth and prevent heaving of the aforementioned
structures.
13. Wild Date Palm/Sylvester specified within the entryway median does not have adequate clear trunk
specified for vehicle clearance due to the large size (length) of the fronds which will hang into traffic.
14. The Shrub/Groundcover Planting Detail on Typical Unit Landscape Plan Sheet 2 of 2 depicts planting
for a tree. Please correct.
15. It may be necessary to replace or relocate large canopy trees adjacent to light fixtures to eliminate
future shadowing on the parking surface (LDR, Chapter 23, Article II, Section A.1.b).
16. Show sight triangles on the Landscape plans (LDR, Chapter 7.5, Article II, Section 5.H.). Reference
FDOT Standard Index 546 for the sight triangles along Lawrence Road. Use a minimum 25-ft. site
triangle for interior development intersections (revise the note on Landscape Plan Sheet 1 of 5.)
17. Per the LDR, Chapter 7.5, Article II, Section 5.C.2. Ficus species are not permitted.
18. Provide a legend for the plant symbols.
19. Live Oaks are proposed within the utility easement on the east side of the recreation area. Canopy
trees are not allowed within utility easements. Please replace with a different species.
20. Full drainage plans, including drainage calculations, in accordance with the LDR, Chapter 6, Article
IV, Section 5 will be required at the time of permitting.
21. Paving, Drainage and Site details will not be reviewed for construction acceptability at this time. All
engineering construction details shall be in accordance with the applicable City of Boynton Beach
Standard Drawings and the "Engineering Design Handbook and Construction Standards" and
will be reviewed at the time of construction permit application.
Department of Public Works/Engineering Division Memo No. 05-050
Knollwood Groves PUD, New Site Plan 1st Review
April 25, 2005
Page 3
UTILITIES
22. Please provide a timeline that clearly illustrates when water and sewer services will be required to
serve the proposed project. Your starting date for the timeline should be the date of City Commission
approval. Also provide milestone dates for permit application, the start of construction, and the setting
of the first water meter. This timeline will be used to determine the adequacy of water and
wastewater treatment capacity for your project upon the project's completion, so please be as
accurate as possible.
23. All utility easements and utility lines shall be shown on the Site plan and Landscape plans (as well as
the Water and Sewer Plans) so that we may determine which appurtenances, trees or shrubbery may
interfere with utilities. In general, palm trees will be the only tree species allowed within utility
easements. Canopy trees may be planted outside of the easement so that roots and branches will
not impact those utilities within the easement in the foreseeable future. The LDR, Chapter 7.5,
Article I, Section 18.1 gives public utilities the authority to remove any trees that interfere with utility
services, either in utility easements or public rights-of-way.
24. Palm Beach County Health Department permits will be required for the water and sewer systems
serving this project (CODE, Section 26-12).
25. Fire flow calculations will be required demonstrating the City Code requirement of 1,500 g.p.m. (500
g.p.m. some residential developments) with 20 p.s.i. residual pressure as stated in the LDR, Chapter
6, Article IV, Section 16, or the requirement imposed by insurance underwriters, whichever is greater
(CODE, Section 26-16(b)).
26. The LDR, Chapter 6, Article IV, Section 16 requires that all points on each building will be within 200
feet of an existing or proposed fire hydrant. Numerous lots are not covered by this requirement; lots
not covered are: 9, 10 partially, 31 partially, 40 partially, 51 partially, 52, 53, 54, 65, 66, 67, 79
partially, 80, 81, 82 partially, 87, 88, 89, 90 partially, 111, 112, 113, 120 partially, 127 partially, 128,
135, 136, 137, 147 partially, 148, and 149. Reconfigure fire hydrant locations to meet this code
requirement.
27. The CODE, Section 26-34(E) requires that a capacity reservation fee be paid for this project either
upon the request for the Department's signature on the Health Department application forms or within
seven (7) days of site plan approval, whichever occurs first. This fee will be determined based upon
final meter size, or expected demand.
28. Water and sewer lines to be owned and operated by the City shall be included within utility
easements. Please show all proposed easements on the engineering drawings, using a minimum
width of 12 feet. The easements shall be dedicated via separate instrument to the City as stated in
CODE Sec. 26-33(a).
29. This office will not require surety for installation of the water and sewer utilities, on condition that the
systems be fully completed, and given to the City Utilities Department before the first permanent
meter is set. Note that setting of a permanent water meter is a prerequisite to obtaining the
Certificate of Occupancy.
.
Department of Public Works/Engineering Division Memo No. 05-050
Knollwood Groves PUD, New Site Plan 1 sl Review
April 25, 2005
Page 4
30. A building permit for this project shall not be issued until this Department has approved the plans for
the water and/or sewer improvements required to service this project, in accordance with the CODE,
Section 26-15.
31. Appropriate backflow preventer(s) will be required on the domestic water service to the dwellings as
well as the recreational building, and the fire sprinkler line if there is one, in accordance with the
CODE, Section 26-207.
32. The LDR, Chapter 3, Article IV, Section 3(P) requires a statement be included that support utilities
are available and will be provided by all other appropriate agencies. This statement is lacking on the
submitted plans.
33. Utility construction details will not be reviewed for construction acceptability at this time. All utility
construction details shall be in accordance with the Utilities Department's "Utilities Engineering
Design Handbook and Construction Standards" manual (including any updates); they will be
reviewed at the time of construction permit application.
LUck
Cc: Jeffrey R. Livergood, P.E., Director, Public Works (via e-mail)
Peter V. Mazzella, Deputy Utility Director, Utilities
H. David Kelley, Jr., P.E./ P.S.M., City Engineer, Public Works/Engineering (via e-mail)
Glenda Hall, Maintenance Supervisor, Public Works/Forestry & Grounds Division
Larry Quinn, Solid Waste Manager, Public Works/Solid Waste
Kenneth Hall, Engineering Plans Analyst, Public Works/Engineering (via e-mail)
File
S:\Engineering\Kribs\Knollwood Groves PUD, New Site Plan 1st Review.doc
/"
Plannine Memorandum: Forester / Environmentalist
To:
Ed Breese, Principal Planner
From:
Kevin J. Hallahan, Forester / Environmentalist
Subject:
Knollwood
New Site Plan - 1 st Review
NWSP 05-017
Date:
April 25, 2005
Existine Trees Manaeement Plan
The Landscape Architect should indicate and tabulate the total number of existing trees on
the site. The tabular data should show the individual species of trees proposed to remain in
place, be relocated throughout the site, or removed / replaced on site. All desirable species of
existing trees must be relocated rather than removed if the trees are in good health. These
trees should be shown by a separate symbol on the landscape plan sheet LP5.
[Environmental Regulations, Chapter 7.5, Article I Sec. 7.D.p. 2.]
Landscaoe Plan
Sheet 5 of 5.1 of 1 (Lakes)
1. All shade and palm trees on the Plant list must be listed in the specifications as a
minimum of3" diameter at DBH (4.5' off the ground), 12'-14' height minimum and
Florida #1. The height of the trees will be larger than 12'-14' to meet the 3" diameter
requirement. [Environmental Regulations, Chapter 7.5, Article II Sec. S.C. 2.]
2. The details section for the Tree and Palm Planting Detail should include a line
indicating where the height of the tree will be measured at time of planting and
inspection.
3. All groundcover / vine plantings should have a height and spread measurement.
4. The applicant should amend the note indicating that all utility boxes or structures (not
currently known or shown on the plan) should be screened with Coco plum hedge plants
on three sides.
5. The applicant must submit a Lake Management Plan document for the lakes.
..
Irrieation Plan-No Irrieation plan included in the submittal
1. The irrigation system design (not included in the plans) should be low volume water
conservation using non-portable water.
2. Turf and landscape (bedding plants) areas should be designed on separate zones and time
duration for water conservation.
3. Trees should have separate irrigation bubblers to provide water directly to the root ball.
[Environmental Regulations, Chapter 7.5, Article II Sec. 5. C.2.]
Kjh
------
CITY OF BOYNTON BEACH, FLORIDA
INTER-OFFICE MEMORANDUM
TO:
Ed Breese,
Principal Planner
DATE:
April 22, 2005
FILE: NWSP 05-017
FROM:
Off. John Huntington
Police Department
CPTED Practitioner
SUBJECT: Knollwood
REFERENCES: Site Plan
ENCLOSURES:
I have viewed the above building plans and have the following comments:
No Comments.
./
Rivers, Jody
To:
Subject:
Breese, Ed; Coale, Sherie
Site Plan Review - Knollwood
Project:
File No.:
Knollwood
NWSP 05-017
1 . Landscaping notes should indicate a 110% irrigation coverage.
2. A 6' black, vinyl coated chain link fence should be installed between the development and the civic area to the
south.
3. The recreation impact fee will be:
152 single-family, detacted homes @ $940.00 each = $142,880.00
The impact fee is due prior to issuance of the "fist application permit."
J ovi.lj T.;;:Lve v:;
Parks Superintendent
City of Boynton Beach
100 E. Boynton Beach Blvd.
Boynton Beach, FL 33425
(561) 742-6226
(561) 742-6233 (fax)
1
~
The City of Boynton Beach
DEVELOPMENT DEPARTMENT
PLANNING AND ZONING DIVISON
100 E. Boynton Beach Boulevard
P.O. Box 310
Boynton Beach, Florida 33425-0310
TEL: 561-742-6260
FAX: 561-742-6259
~~'~l'
" \
!
~ /
, " /
'c"'''~ .-.- "'""" ~
I '>J'
www.boynton-beach.org
To: Peter Mazzella, Assistant Director, Utilities
Kofi Boatang, Director of Utilities
Marshall Gage, Police Chief
Rodger Kemmer, Deputy Chief / Fire Marshal
Jody Rivers, Parks Superintendent
Cc: William Bingham, Fire Chief
Wally Majors, Parks Director
Laurinda Logan, Civil Engineer
Rick Lee, Fire Protection Analysist
John Huntington, Police Officer
Ed Breese, Principal Planner 4t:7J
From:
Date:
Re:
4/15/05
Impacts of proposed site plan upon City facilities and services
Project: Knollwood PUD
File Number: NWSP 05-016
MEMORANDUM
As part of the City's concurrency requirements, the City Commission directed the Planning & Zoning
Division to report whether or not the City could maintain an adequate level of service with current
infrastructure and I or staffing levels in order to support the proposed development.
Plans for the above-mentioned project have been forwarded to your department's representative
for their technical review and comment. We are requesting that you review the proposed project for
anticipated impacts to your department's level of service (as requested by the City Commission) and
provide us with your comments for direct insertion into our staff report. In the past, you have sent
us something that indicates your current staff I infrastructure would either be able to support the
proposed project or what would be required to meet the adopted level of service. Please respond
no later than 2 weeks from today. Also, any recommendations that you believe that would
enhance the project are certainly welcomed. I thank you for your assistance in this matter. Should
you have any questions regarding the requested information, please do not hesitate to call me at
742-6260.
5: \Planning\SHARED\ WP\AGENDAS\ TRC\correspondence\lmpact Analysis.doc
-----
.'
FROM: Timothy K. Larg
TRC Member/Bu
Ll1W"6f Acronvms/Abbreviations:
ASCE - American Society of Civil
Engineers
CBB - City of Boynton Beach
CBBA - Boynton Beach Amendments
CBBCO - City of Boynton Beach
Code of Ordinances
CBBCPP - City of Boynton Beach
Comprehensive Plan Policy
CFR - Code of Federal Regulations
EPA - Environment Protection Agency
FBC - Florida Building Code
FIRM - Flood Insurance Rate Map
F .S. - Florida Statutes
LOR - Land Development Regulations
NEC - National Electric Code
NFPA - National Fire Prevention Assn
NGVD - National Geodetic Vertical
Datum of 1929
_ SFWMD - South Florida Water
Management District
FFPC - Florida Fire Prevention Code
DEPARTMENT OF DEVELOPMENT
BUILDING DIVISION
MEMORANDUM NO. 05-076
TO: Ed Breese
Principal Planner
DATE: April 26, 2005
SUBJECT: Project-~ ~(lwvo~
File No. - NWSP 05-017 - 1::;1 review
We have reviewed the subject plans and recommend that the request be forwarded for Board
review with the understanding that all remaining comments will be shown in compliance on the
working drawings submitted for permits.
Buildino Division (Site Specific and Permit Comments) - Timothv K. Laroe (561) 742-6352
1 Please note that changes or revisions to these plans may generate additional comments.
Acceptance of these plans during the TRC process does not ensure that additional comments may
not be generated by the commission and at permit review.
2 Indicate within the site data the type of construction of each building as defined in 2001 FBC,
Chapter 6.
3 Buildings, structures and parts thereof shall be designed to withstand the minimum wind loads of
140 mph. Wind forces on every building or structure shall be determined by the provisions of ASCE
7, Chapter 6, and the provisions of 2001 FBC, Section 1606 (Wind Loads). Calculations that are
signed and sealed by a design professional registered in the state of Florida shall be submitted for
review at the time of permit application.
4 At time of permit review, submit signed and sealed working drawings of the proposed construction.
5 Identify within the site data the finish floor elevation (lowest floor elevation) that is proposed for the
building. Verify that the proposed elevation is in compliance with regulations of the code by adding
specifications to the site data that address the following issues:
a. The design professional-of-record for the project shall add the following text to the site data.
"The proposed finish floor elevation _' _ NGVD is above the highest 100-year base flood
elevation applicable to the building site, as determined by the SFWMD's surface water
management construction development regulations."
b. From the FIRM map, identify in the site data the title of the flood zone that the building is located
within. Where applicable, specify the base flood elevation. If there is no base flood elevation,
indicate that on the plans.
c. Identify the floor elevation that the design professional has established for the building within the
footprint of the building that is shown on the drawings titled site plan, floor plan and
paving/drainage (civil plans).
S:\Development\Building\ TRC\ TRC 2005\Citrus Cay
Page 1 of 2
6 Add to the submittal a partial elevation view drawing of the proposed perimeter wall/fence. Identify
the type of wall/fence material and the type of material that supports the wall/fence, including the
typical distance between supports. Also, provide a typical section view drawing of the wall/fence
that includes the depth that the wall/fence supports are below finish grade and the height that the
wall/fence is above finish grade. The location and height of the wall/fence shall comply with the
wall/fence regulations specified in the Zoning Code.
7 CBBCPP 3.C.3.4 requires the conservation of potable water. City water may not, therefore, be used
for landscape irrigation where other sources are readily available.
8 A water-use permit from SFWMD is required for an irrigation system that utilizes water from a well
or body of water as its source. A copy of the permit shall be submitted at the time of permit
application, F.S. 373.216.
9 If capital facility fees (water and sewer) are paid in advance to the City of Boynton Beach Utilities
Department, the following information shall be provided at the time of building permit application:
a. The full name of the project as it appears on the Development Order and the Commission-
approved site plan.
b. If the project is a multi-family project, the building number/s must be provided. The building
numbers must be the same as noted on the Commission-approved site plans.
c. The number of dwelling units in each building.
d. The number of bedrooms in each dwelling unit.
e. The total amount paid and itemized into how much is for water and how much is for sewer.
(CBBCO, Chapter 26, Article II, Sections 26-34)
10 At time of permit review, submit separate surveys of each lot, parcel or tract. For purposes of setting
up property and ownership in the City computer, provide a copy of the recorded deed for each lot,
parcel or tract. The recorded deed shall be submitted at time of permit review.
11 At time of building permit application, submit verification that the City of Boynton Beach Parks and
Recreation Impact Fee requirements have been satisfied by a paid fee or conveyance of property.
The following information shall be provided:
a. A legal description of the land.
b. The full name of the project as it appears on the Development Order and the Commission-
approved site plan.
c. If the project is a multi-family project, the building number/s must be provided. The building
numbers must be the same as noted on the Commission-approved site plans.
d. The number of dwelling units in each building.
e. The total amount being paid.
(CBBCO, Chapter 1, Article V, Section 3(f))
12 Add a general note to the site plan that all plans submitted for permitting shall meet the City's codes
and the applicable building codes in effect at the time of permit application.
13 Pursuant to approval by the City Commission and all other outside agencies, the plans for this
project must be submitted to the Building Division for review at the time of permit application
submittal. The plans must incorporate all the conditions of approval as listed in the development
order and approved by the City Commission.
14 Sheet 2 of 4. Indicate on the plans that light poles comply withy 2001 FBC, Section 1606 for
compliance with 140mph windload. Design calculations by a design professional registered in the
State of Florida shall be submitted at time of permit application.
bf
S:\Development\Building\ TRC\ TRC 2005\Citrus Cay
Page 2 of 2
r'
~
FIRE & LIFE SAFETY DIVISION
TO:
Ed Breese, Principal Planner
FROM:
Rodger W. Kemmer, Deputy Chief/Fire Marshal
DATE:
April 20, 2005
SUBJECT: NWSP 05-016
NWSP 05-017
Knollwood PUD
High Ridge New Urban Community
The Fire Department expects to be able to maintain an adequate level of service
for the subject projects, with current or anticipated staffing. Infrastructure
requirements such as hydrants and roadways will be addressed during plan
reviews and the permitting process. It must be noted however, that the Multi-
family units of High Ridge NUC is in an area with significant growth in the past
year. We support this project with the understanding that Fire Station NO.5 will
be available when these structures are ready for occupancy.
Any additional commercial occupancies that require periodic fire inspections will
require additional inspection staff.
CC: Chief Bingham
F&LS Staff
File