The City of Boynton Beach
DEVELOPMENT DEPARTMENT
PLANNING AND ZONING DIVISON
100 E. Boynton Beach Boulevard
P.O. Box 310
Boynton Beach, Florida 33425-0310
TEL: 561-742-6260
FAX: 561-742-6259
www.boynton-beach.org
May 22, 2006
Mr. Dominic Merelli
RAV Millwork & Supply
1015 NW 17th Avenue
Delray Beach, FL 33445
Re: RAV Millwork & Supply
MMSP 06-028
Dear Mr. Merelli:
In response to your request dated May 4, 2006 for the
administrative review and approval of the modifications proposed to
the above-referenced approved site plan, depicting the following:
. Addition of a retaining wall along the western edge of the
property (as depicted on the attached plan) .
Please be informed that the proposed changes on the revised
date stamped 5/8/06 are "minor" as defined within the
Development Regulations, Chapter 4 Si te Plan Review.
project may continue to be processed by the Building Division
permit application, subject to the following conditions:
plan
Land
This
as a
1. Sheet A-1 - Detail A/A.1 refers to FBC 2504.2.2. There is no such
Section in the 2004 Edition. Please correct this detail on the
permit plans.
2. Sheet A.1 - Detail A/A.1 calls out 5/8" stucco and masonry. Note #2
calls out 7/8". Please correct this detail and note on the permit
plans.
3. All portions of the proposed retaining wall shall be contained
within the property line.
4. Caution shall be used in working around the existing water meter.
It shall remain in a grassy (non-surfaced) area. Contact the City
of Boynton Beach Utilities Dept. if a change in grade is required
for the meter.
5. Per the LDR, Chapter 7.5, Article II, Section 5.C.2. Ficus species
are not permitted. Please substitute an acceptable hedge material,
meeting all of the code requirements for height and spacing, on the
revisions to the permit plans.
6. Provide written and graphic scales on all sheets.
7. Provide a north arrow on the plan.
8. Paving, drainage and site details will not be reviewed for
construction acceptability at this time. All engineering
construction details shall be in accordance with the applicable
'.-
. Page 2
City of Boynton Beach Standard Drawings and the
Handbook and Construction Standardsll and will
time of construction permit application.
9. All comments requiring changes and/or corrections to the plans
shall be reflected on all appropriate sheets.
10. Signed and sealed plans shall be submitted to the Building
Division with a Permit Application for this work.
11.Please note that changes or revisions to these plans may generate
additional comments. Acceptance of these plans during the Minor
Site Plan Modification process does not ensure that additional
comments may not be generated at permit review.
May 22, 2006
IIEngineering Design
be reviewed at the
Be advised that the proposed changes may require a modification to
the building permit. Please contact me at (561) 742-6260 if you
have additional questions.
Sincerely,
Ed Breese, Principal Planner
Cc: Karen Main, Plan Review Analyst
Laurinda Logan, Senior Engineer
Tim Large, Building Codes Administrator
Kevin Hallahan, City Forester
TO:
Page 1 of2
Breese, Ed
From: Coale, Sherie
Sent: Monday, May 22,200611 :20 AM
To: Breese, Ed
Subject: FW: MMSP RAV Millwork
-----Original Message-----
From: Rosado, Maibet
Sent: Monday, May 22, 2006 11:19 AM
To: Livergood, Jeffrey; Hall, Ken; Kelley, David
Cc: Coale, Sherie
Subject: MMSP RAV Millwork
TO:
Ed Breese, Principal Planner, Planning and Zoning
FROM:
Laurinda Logan, P.E., Senior Engineer
DATE:
May 22, 2006
RE:
Review Comments
Minor Site Plan Modification - 1 st Review
RA V Millwork
File No. MMSP 06-028
The above referenced minor modification, received on May 10, 2006, was reviewed for Public Works,
Engineering, and Utilities against the requirements outlined in the City of Boynton Beach Code of
Ordinances. This modification is for the addition of a retaining wall to correct a change in grade
between the public sidewalk and the property. The change in grade is causing washing of soils off the
property and into the public right-of-way. Following are our comments with the appropriate Code and
Land Development Regulations (LOR) referenced.
PUBLIC WORKS - GENERAL
No comments at this time.
PUBLIC WORKS - TRAFFIC
No comments at this time.
ENGINEERING
1. All comments requiring changes and/or corrections to the plans shall be reflected on all appropriate
sheets.
2. Please note that changes or revIsions to these plans may generate additional comments.
Acceptance of these plans during the Technical Advisory Review Team (TART) process does not
ensure that additional comments may not be generated by the Commission and at permit review.
3. Provide written and graphic scales.
4. Provide a north arrow on the plan.
5/2212006
TO:
Page 2 of2
5. Per the LOR, Chapter 7.5, Article II, Section 5.C.2. Ficus species are not permitted.
6. All portions of the proposed retaining wall shall be contained within the property line.
7. Paving, drainage and site details will not be reviewed for construction acceptability at this time. All
engineering construction details shall be in accordance with the applicable City of Boynton Beach
Standard Drawings and the "Engineering Design Handbook and Construction Standards" and
will be reviewed at the time of construction permit application.
UTILITIES
8. Caution shall be used in working around the existing water meter. It shall remain in a grassy (non-
surfaced) area. Contact the City of Boynton Beach Utilities Dept. if a change in grade is required
for the meter.
LL/mr
Cc: Jeffrey R. Livergood, P.E., Director, Public Works (via e-mail)
Peter V. Mazzella, Deputy Utility Director, Utilities
H. David Kelley, Jr., P.E./ P.S.M., City Engineer, Public Works/Engineering (via e-mail)
Glenda Hall, Forestry & Grounds Manager, Public Works/Forestry & Grounds Division
Larry Quinn, Solid Waste Manager, Public Works/Solid Waste
Kenneth Hall, Engineering Plans Analyst, Public Works/Engineering (via e-mail)
File
S:\Engineering\Logan\MMSP RAV Millwork.doc
512212006
DEPARTMENT OF PUBLIC WORKS
ENGINEERING DIVISION
MEMORANDUM NO. 06-052
FROM:
Ed Breese, Principal Planner, Planning and Zoning
---
Laurinda Logan, P.E., Senior Engineer
WI ~ (fl ~ n \YI rr:
-~__u._._I__._.
i MAY 2 3 Ll
L ~
OEPARTMENT OF OEVElOPM E N i
;",J
TO:
DATE:
May 22,2006
RE:
Review Comments
Minor Site Plan Modification -1st Revl
RAV Millwork
File No. MMSP 06-028
The above referenced minor modification, received on May 10, 2006, was reviewed for Public Works,
Engineering, and Utilities against the requirements outlined in the City of Boynton Beach Code of
Ordinances. This modification is for the addition of a retaining wall to correct a change in grade between
the public sidewalk and the property. The change in grade is causing washing of soils off the property
and into the public right-of-way. Following are our comments with the appropriate Code and Land
Development Regulations (LOR) referenced.
PUBLIC WORKS - GENERAL
No comments at this time.
PUBLIC WORKS - TRAFFIC
No comments at this time.
ENGINEERING
1. All comments requiring changes and/or corrections to the plans shall be reflected on all appropriate
sheets.
2. Please note that changes or reVISions to these plans may generate additional comments.
Acceptance of these plans during the Technical Advisory Review Team (TART) process does not
ensure that additional comments may not be generated by the Commission and at permit review.
3. Provide written and graphic scales.
4. Provide a north arrow on the plan.
5. Per the LOR, Chapter 7.5, Article II, Section 5.C.2. Ficus species are not permitted.
6. All portions of the proposed retaining wall shall be contained within the property line.
7. Paving, drainage and site details will not be reviewed for construction acceptability at this time. All
engineering construction details shall be in accordance with the applicable City of Boynton Beach
Standard Drawings and the "Engineering Design Handbook and Construction Standards" and
will be reviewed at the time of construction permit application.
Dept. of Public Works, Engineering Division Memo No. 06-052
RE: RA V Milwork - 1 st Review, NWSP 06-052
May 22,2006
Page 2
UTILITIES
8. Caution shall be used in working around the existing water meter. It shall remain in a grassy (non-
surfaced) area. Contact the City of Boynton Beach Utilities Dept. if a change in grade is required for
the meter.
LLlmr
Cc: Jeffrey R. Livergood, P.E., Director, Public Works (via e-mail)
Peter V. Mazzella, Deputy Utility Director, Utilities
H. David Kelley, Jr., P.E./ P.S.M., City Engineer, Public Works/Engineering (via e-mail)
Glenda Hall, Forestry & Grounds Manager, Public Works/Forestry & Grounds Division
Larry Quinn, Solid Waste Manager, Public Works/Solid Waste
Kenneth Hall, Engineering Plans Analyst, Public Works/Engineering (via e-mail)
File
S:\Engineering\Logan\MMSP RAV Millwork.doc
DEPARTMENT OF DEVELOPMENT
BUILDING DIVISION
MEMORANDUM NO. 05-087
TO:
FROM:
Sherie Coale
Application Technician
Timothy K. Larg~
TRC Member/Building Division
DATE:
May 12, 2006
SUBJECT:
Project - RA V Supply - QP & Village North Commercial
File No. - MMSP 06-028
1) Sheet A-1 - Detail A1A.1 refers to FBC 2504.2.2. There is no such Section in the
2004 Edition.
2) Sheet A.1 - Detail AlA. 1 calls out 5/8" stucco and masonry. Note #2 calls out 7/8".
Clarify.
3) Signed and sealed plans shall be submitted to the Building Division with a Permit
Application for this work.
tkl:bf
S:\Development\Building\ TRC\ TRC 2006\RA V Supply-QP & Village North Commercial
Page 1 of 1
Standard review comments for new site plan, major site plan modification and conditional... Page 1 of2
Breese, Ed
From: Coale, Sherie
Sent: Wednesday, May 17, 2006 12:12 PM
To: Breese, Ed
Subject: RAV Supply-OP & Village North Commercial MMSP 06-028
DEPARTMENT OF DEVELOPMENT
BUILDING DIVISION
MEMORANDUM NO. 05-087
TO: Sherie Coale
Application Technician
FROM: Timothy K. Large
TRC Member/Building Division
DATE: May 12,2006
SUBJECT: Project - RAV Supply - QP & Village North Commercial
File No. - MMSP 06-028
1) Sheet A-1 - Detail A/A.1 refers to FBC 2504.2.2. There is no such Section in the 2004
Edition.
2) Sheet A.1 - Detail A/A.1 calls out 5/8" stucco and masonry. Note #2 calls out 7/8".
Clarify.
3) Signed and sealed plans shall be submitted to the Building Division with a Permit
Application for this work.
5/1812006
May 4, 2006
MAY - 8 LOUD
'l' "
~_.._..~-' ~.-
J
City of Boynton Beach
Planning, Zoning & Permits
Dear Sir or Madam:
Please find four copies of a rroposed retaining wall to be constructed on the west side of
our building at 3210 SW14t Place Boynton Beach. The reason for this is because the
building is elevated from the street, so all the soil runs to the sidewalk when it rains. We
plan to landscape around it with numerous ficus trees and plants.
Attached is a $100.00 check for the fee.
Please note that we have a current permit open #0500007138
Sincerely,
Dominic Merelli
President
Wood Manufacturers Inc
dlb/a RA V Millwork & Supply
561-441-0806
Formica, Cabinet Supplies & Hardwood Mouldings · Radius Mouldings
1015 N.W. 17th Ave.. Delray Beach, FL 33445. (561) 276-7720. (Fax) 276-7141 · (800) 336-1994
..
PROJECT NAME: RA V Supply Inc.
LOCATION: 3210 SW 14th Place
PCN:
I FILE NO.: MMSP 06-028 II TYPE OF APPLICATION: I
AGENT/CONTACT PERSON: OWNER:
Dominic Merelli ADDRESS:
ADDRESS:
FAX: FAX:
PHONE: 561-441-0806 PHONE:
E-Mail:
SUBMITTAL / RESUBMITT AL 5/8/06
1 ST REVIEW COMMENTS DUE:
PUBLIC lIP ARC NOTICE:
TART MEETING:
LAND DEVELOPMENT SIGNS POSTED
(SITE PLANS):
LEGAL AD:
PLANNING & DEVELOPMENT BOARD
MEETING:
COMMUNITY REDEVELOPMENT
AGENCY BOARD
CITY COMMISSION MEETING:
COMMENTS:
S:\Planning\SHARED\WP\PROJECTS\Rav Millwork & Supply\MMSP 06-028\2006 PROJECT TRACKING INFO,doc