Loading...
REVIEW COMMENTS MEMORANDUM ro Mr. James Golden DATK April 18, 1989 "ILK 'ROil Lt. Dale S. Hamnack SU'JKCT Congress lwe Cormnmity Park Per our discussion at the Technical Review Board, I am reccmnending the following. 1. Traffic Control Details including Stop signs and pavement rrarkings. osH: trn ;/DoLJ4-- ~ REC"i1n r~D ,--I .~~.il V .:c AjiR l i?~3 PLANNlhS Dt.t>f. 0" _ /8 MEMORANDUM 18 April 1989 TO: Charlie Frederick Parks and Recreation Director FROM: Tambri J. Heyden Assistant City Planner RE: Congress Avenue community Park Site Plan Staff Comments Please be advised of the Planning Department's comments regarding the above-referenced preliminary site plan. '1. All exotics must be removed; Florida Holly (Brazilian Pepper). Due to the long term completion date of Phase II, it is recommended that the exotics outside of the construction '~imits of Phase I remain until Phase II commences. 2. The existing parking lot is required to be."brought up to code. P.rovide dimensions and layout of the existing lot to enable staff to determine whether it is a nonconforming lot. 3. The typical parking detail shows wheelstops with an 18 foot space and raised continuous curb with a 16 foot space. Eliminate the detail which is not to'be used. 4. Provide a traffic control plan. 5. Provide a lighting plan showing pole locations, height and embedment detail, energy source, wattage, manufacturer's specification and photocell activation. 6. Survey is outdated. 7. Specify materials and colors on building elevations. 8. Provide details for all building and freestanding signs; size, location, height, wording, color, materials, letter size and style. 9. A sidewalk or bike path is recommended on the south side of Charter Drive. TJH/csd cc: Central File J~Q.~~ Tambri J. Heyden /a; Archllecture Landscape Archllecture Urban Design Environmental Planning ~4JII! '/ I 1- ,. - {' t: . /:J<. ~j '-~,~ 6.. .~ I , ,j J (: Lf ... . 'i 4~")'- _.t.-<-. -,- i fJ / -' '7.,., ,7Iwl"~"~';~"_. /'.'.&~~ . WRT lVallacc Roberts & Todd April'18, 1989 RECEIVEn APR 2~ JS8s PLANNING DEPT. ~ Mr. Charles Frederick, Director Recreation & Park Department 211 S. Federal Highway Boynton Beach, Flor~da 33425-0310 Re: Congress Ayenue Community Park Response to city Comments Dear Charlie, .. This letter is written to acknowledge reciept of your April 6 letter. We have provided a response to each item of the letter (attached), followed by responses to Bill DeBeck1s April 10 memo, also attached. Most of the changes required were made in advance of our pre TRB meeting held on April 17. Sheet L-2 (1) will comply (2) will comply (:3 ) will comply (4) While the currently existing pump and well system will be used as the source for work in this phase, the operating time for the additional times will be increased. The effect of longer operation during the day and/or higher rate (electrical) periods should be studied and discussed further. We expect to use lake water and/or an additional well for subsequent phase park improvements. Sheet L-l (1) (2) (3) (4) (5) No specific code items were identified on 4-17-89. will comply. Owner's maintenance,quidelines'will be submitted for review. will specify an 8' height tree. will specify prepared beds for annuals by City. Berm has been ,provided on Sheet C-4. , Lake fill is to be used, unless deleterious material is encountered during excavation. Will comply. (6) 1S1 Giralda Avenue Penthouse Coral Gables, FL 33134 (305) 448-0788 620 WRT Mr. Charles Frederick April 18, 1989 . Page Two Sheet C-4 (1) will comply. (2) will comply. Sheet S-l (1) (a) Will comply (b) will comply (c) will comply to locations ~land #2 for water. (d) Bleacher access is O.K. and seatinSJ c8;paci,ty is -2400 persons. Sheet S-2 ,(1) will comply (2~ (a) will comply. com~liance with this item will add .5' to elevation of awn~ng. (b) We will search catalogues for 13'-14' wide bleacher (c) will comply (d) Will comply by providing junction boxes at location for each scoreboard. As per earlier discussion with City, existing scoreboards will be brought over and lights will be by City parks. (e) Will comply with wood bumper. (f) will comply by providing a written description of the alternate for metal awnings. Sheet E-l (1) will comply (2) will comply Sheet A-l (1-) will compl:\p GENERAL (1) will comply (2) Earthwork calculations are in progress and will be provided to comply. Our responses to Bill DeBeck's April 10 memo. Sheet C-3 - will comply C-4 - will comply C-5 - will modify to clarify detail C-6 - will comply gL/ 'lVRT Mr. Charle Frederick April 18, 1989 Page Three S-l S-3 Note 30 Note 15 S-4 E-1 E-l - will - will Will Will - Will - Will - Will comply comply comply add a note tl15 comply provide on next submittal comply on next submittal Thank you for providing a thorough review of our submittal. S in'cerely , c:/letters/cfred.mm 02~ . " I / CITY of BOYNTON BEACH --_....~ - ..--.-..........-... ......-. - . ~,.. .. 211 South Federal Highway p, O. Box 310 Boynton Beach, Florida 3342S..Q310 (407) 734,8111 APR ' 1\ lQAO RECEIVED April 6. 1989 Mr. Matt Mathis Wallace Roberts & Todd 191 Giralda Avenue Coral Gables, FL 33134 Re: Congress Avenue Community Park Dear Matt, Provided are additional comments and questions relative to the design of the park: o -IRRIGATION (L-2): o o o Ol. F/M.' 2. ,....- /3. V4. o 5. 1. On Sheet L-2 substitute the Hunter PGP Series (full and adjustable. 360 degrees) for the Toro Super 700-C unit. 2. Substitute the Rainbird RC U1260 controller for the Toro U176-56-01. 3. Substitute the Toro 570-C spray head series for the 570 series. 4. Is the current pump and ~ell house system to be utilized for the expa _s~stems1 Does it have the capacity~ t:'t', 0 ~, ;::. ~ 1--f.f=. eN V"t . LANDSCAPING (L-1): Check parking lot code relative to required curbing and landscapin' If the lake is over one-half (1/2) acre in size littoral zone pla are required around fifty percent (507.) of the lake edge. The snail seed as designated (CL) must be eight (8) ft. high if categorized as a tree. If classified and designated as a shrur height is not required. The areas designated for ~idelia adjacent to the shuffleboard make new areas for our "annual" flower planting program. The landscaped area along Congress Avenue should be bermed . additional buffering from traffic, noise and ~ind. Can la} for this? o?3 ~, , , To: Matt Mathis, Wallace Robert~~,Todd Page 2 of 3 ------------------------------------------------------------------------------ ~ w{ Some areas should be changed from seed to sod. This may require adjustments to the irrigation lay-out. v' a. The area north of the new courts along Charter Drive should be sodded to match the area north of the existing courts. Vb. The area on the north side of the eastern shuffleboard courts should be sodded and a reasonable sod strip should be provided on the western side of the west shuffleboard courts and south side of the building (Concept: Sod border around the complex). PAVING AND DRAINAGE (C-4): , ~'~1.~ For Court A, need paving or asphalt for the service garage to the court ~ . as with the existing courts. 2. vi Need adequate service gate area for Court C. TENNIS COURT PLAN 5-1: ~ 1. Stadium Court: ~. Fence: . Ten (10) ft. high and ends ~ith angles corners, provide one side section of ten (10) ft. high and two four (4) ft. high side sections. Use black fence. ~ Too many poles for a stadium court. Recommend four (4) maximum and design accordingly on pole height and number of fixtures. c. Water: o o 1) Need ~ater fountain at the hard courts. 2) Where are spigots for Har-Tru courts? ~ ;e ~ .. .,I~I A -Ir- f4-. d. Bleachers: () ~ ~l) ~ t7 2) Need adequate access to bring in portables or rentals. ~ What's the seating capacity? Z-4o:::> , M/--YJ ' -- .... SHUFFLEBOARD COURTS (S-2): I 1. Maximum line ~idth for in~h. ~'f:;_ - 2. Bleachers: " the shuffleboard court lining detail is one (1) a. Is the site line for the top row of bleachers adequate based on height of the awning? o~....- · &~ , .. To: Matt Mathis, Wallace Roberts & Todd Page 3 of 3 ------------------------------------------------------------------------------ ~ ~f>. o I C;f. d. o e. ~-r- ~~S:~support poles of awning for the hleachers is very tight. Bleachers are fifteen (15) ft. long. No lighting detail provided. 7b (!1& ~ ~ S~, c. Scoreboards are not shown nor the lighting for the boards. Do not recorrunend using "rope" bumper. Two by two inch (i" >: 2") wood bumper recommended. Check with Nidy Company for type of wood, Any "alternate" detail for metal ,a,ins canvas. (~JH... Wvl-'T/ . ELECTRICAL (E-l): f. structure rather than ()~ 1- ~2. v: . . No lighting detail for shuffleboard courts. No lighting detail for parking lot. FLOOR PLAN (A-I): 1.' No window for office on north side for visual control of breezeway, room, etc. cue GENERAL: No survey attached.r;;:) €. ,,1IhL.. ~ Enough fil~-l~o~ lake or site Congress? \ '\ . A1't''- L., f"t '-V . to fill the "hole" and build berm along . Matt, I will.be out of the office on Monday and Tuesday. If you have questions on irrigation or landscaping call John Wildner (738-7443, ext. 357). Questions on any other items call Mark Thompson (738-7440, ext. 356). I haven1t received input from Bill DeBeck yet. Sincerely, CITY OF BOYNTON BEACH ~.,-e.~ . Charles C. Frederick, Director Recreation &,Park D~partment CCF:pb CC: John Wildner Mark Thompson Bill DeBeck 6l.s- , ' MEMORANDUM TO: FROM: DATE: SUBJECT: CHARLES FREDER1CKS BILL De BECK APRIL 10, 1989 NOTES ON CONGRESS AVENUE PAJU~ PARTIAL PLANS C-3 IIExisting" 'Word 'Wrong on 'West shuffle board court C-4 Curb missing - S.~. corner of parking lot . C-5 Storm pipe detail ? No joint in concrete collar - ~~ ~. 10 .S-3 l'E>:isting" 611T W'ny proposed on ever)'thing_ S~ iu.. ...~, ~ <;PffJ Show detail of awning corner post embedment 18" J: 36" ~ ~ Note depth of railing embedment on platform and' s~e~S~J~) 30 Note finish on stairs (no slip aggregate) All steps to have nosing and min 311 non slip return edge S-3 Where iS~ ,":, S-l C-6 S-4 Show slope to drain on 9/5-4 sCv-w ~yl/')'l.J. E-l Details on switch room 01 structure? E-l Show site main conduit runs fMt.e~~ -~.~r~ci1~~. ("~ ,~J (b~ ~~) . tfJaytflk4 gill DeBeck Project Manager BD/jj Gl~ , . . Meeting Notes: 4-17-89 Project: Re: Present: Congress Avenue Community Center Pre TRB Comments TRB staff Parks Staff WRT city Comments - (Follow-up Responsibilitv) site Comments: III (1) stop sign locations and pavement markings on a traffic control plan required by police. (RIM) (2) Parking lot lighting to meet code 5-141(N) recieved at meeting. (LIP) (3) Drainage calculations needed. (RIM) (4) Drainage cloth at inlet not as per FOOT spec. (RIM) (5) Provide barrier free walk access to existing walk at north side of Charter Drive from north west corner of site. (RIM) Sheet C-6 Comments: . (6) (7) (8) Provide reduced back flow prevention at cross connection. (RIM) Provide 2' min. cover over'DIP sanitary line south of community center building. (RIM) Provide cleanouts at 50' c.c. on sanitary line. (RIM) General site Plan (all sheets) (9) Show dumpster at 150 or 300 angle. (WRT) (RIM) (lO)CAB needs color of awnings and samples. (WRT) (ll)Bill DeBeck needs copies of all permits from P.B. Health, L.W.DD & SFWMD. (RIM) (12)Provide lake management specs to owner. (WRT) (13)Identify sign for llcommunity Center" to be redwood to match "Tennis Center" sign. (WRT) (14)Locate sign on lawn (mall) near entry. (WRT) (15)Clarify USTA requirement for asphalt vs. plexi for stadium court. (WRT) (16)All parking lot and site lighting to be photo cell with timer back up/overide. (LIP) (17)Provide one photo cell at one location, not one photo cell at each fixture. (LIP) c:/letters/congave.mm O?~ MEMORANDUM To: Carmen Annunziato, Planning Director~ \ / Ut ili tie s b \J.i7 , From: John A. Guidry, Director of Date: April 19, 1989 Subject: Special TRB Review - Expansion of Teresa Padgett Park Site Plan We offer the following comments on this project: 1. The 6" gate valve and tee shown as existing is not exist- ing. Please specify a tapping tee and a 61\ tapping valve. 2. A reduced pressure backflow preventer is required on the ~ interconnect to the existing irrigation system. This is a serious cross-connection hazard, and must be addressed at this time. . 3. The 611 sanitary service should be lowered to allow suitable clearance from the bottom of the irrigation ditch. Also provide cleanouts at 50' intervals. 4. Indicate the water meter location. dmt bc: Peter Mazzella RECEIVED APR 20 :lS1lt PLANNING DEPT. o.?s> . hO _.. '.. ...--.-- ... -- MEMORANDUM TO James Golden Senior City Planner ! DATr April 18, 1989 "'Lr "..ow Doni Jaeger Site Development Building Department au.nCT SITE PLAN - PROPOSED EXPANSION OF THERESA PADGETT PARK AT SOUTH CONGRESS AVENUE & CHARTER DRIVE I Upon preliminary review of the above referenced site plan, the - following items should be addressed by the design professional: I i 1. IA11 plans submitted for public record by a design professional , !registered in the state of Florida must be signed a~d sealed. 2. iCo1ors of proposed awnings must be provided for Community , ;Appearance Board and City Commission approval. 3. :Handicapped accessibility must be provided for all structures c!nd amenities. 4. Palm Beach County Health Department approval 1's required. ., '5. South Florida Water Management District approval is required. 6. Light poles must be designed to withstand 120 m.p.h. windload in accordance with Chapter 12 of the Standard Building Code, 1985 Edition. D~~dr~ DJ:bh XC: Med Kopczynski 6Ji - - ........ n-.~ .~. -,. - . ~-". , .... ........ I ( !1.E;.MQ.8.li!::!P..w'l'i To: Jim Golden Senior City Planner 04/17/89 From: Vincent A. Finizio Engineering Department Subject: Technical Review Board Comments Congress Avenue Community Park 1. Provi de a pal~~d n~l lot Ii ghti ng pI ~')n consi stent wi th ,the requirements of City of Boynton Beach, Parking Lot Regulations, Article X, section 5-142 (a) lighting and section 5-141 (n) lighting standards inclusive. 2. Provide drainage calculations in accordance with section 5-142 (f). 3.' Provide directional an-ows (pavement mar-kings) and R-l-1 stop signs, at the ingress/egress approach of the existing parking facility and at the intersection of the m~jor driveway with Chart:.er Drive. Section 5-142 (c) traffic control (inl:lusive) " 4. Provide a concrete pedestrian sidewalk (handicap accessible) and associated swale system(s) along Charter Drive. Chapter 22 Streets and sidewalks, section 22-25 sidewalks required. 5. Provide raised continuous concrete curbing consistent with the requirements of section 5-142 (e) curbing and wheel stops. 6. The addition of a parking facility, activates the code requirement to modify the existing parking facility to meet current parking lot regulations and standards. Section 5-138 (a) (c) (f). The e>:istin~~ par-kin~;J 'facility Q.I;.t~~E.-EL9t: COITl~..!...'l. with applicable codes in the following areas: 9.tall stri pi nq end r-j\i s€~fLJ.:orL~j.D.uql-IS_ !';..9nc.r.:(~tt~ curb a. Existing white single striped standard stalls will require restriping to white double striped standard stalls. b. Existing white single striped handicap stalls will require restriping to blue double striped handicap stalls with insignia. Section 5-141 (n) striping standards, Section 5-142 (k) handicap requirements, Section 5-142 (1) parking lot striping c. Install curbing along parking stalls that abut landscaped areas. Section 5-142 (e) curbing and car stops Respectfully submitted, ~b~~__ Vincent A. Finizio LJ ~ I ,"". ---- -- CITY of BOYNTON BEACH 4 211 South Federal Highway P. 0, Box 310 Boynton Beach, Florida 3342S.Q310 (407)734-8111 March 29, 1989 Mr. Matt Mathis Wallace Roberts & Todd 191 Giralda Avenue Coral Gables, FL 33134 Dear Matt, Enclosed is a set of applications which must accompany the plans 'submitted for the formal site plan approval process. If you complete for the pre-Technical Review Board we can review for accuracy then. Also required are 8" x 10" colored photos of the boundaries of the site which show adjacent land users and status. . e, As I mentioned on the phone some items to check on are: c 1. No survey attached to plans. 2. Review parking lot code. Existing parking lot must be brought to code if it is not. (Includes landscaping). 3. 'Park~ng lot lighting not shown. '4.' Elevation plans not complete. ,Need all four (4) elevations, heights,' and,material ,and ,color .selections.. Otherstaff.are still reviewing ,the. plans. and we will ,.fori1ard.' information as soon as possible.. The pre-Technical Review Board has been tentatively scheduled for Monday, April 17, 1989. We will 'take your project third in the ..morning.so you can stay for the afternoon session with the Spillis Candela ,project. .,; ~- If you have any questions ,please call. Sincerely, "CITY .OF :BOYNTON BEACH ~ Charles C. Frederick, Director Recreation'& Park Department CC: Jim Golden Bill DeBeck " John Fernsler, WRT Mark Thompson John Wildner JRlEOB~JN!) ~.AR ~ 11'989 fRJ.!A"NN lUG Cff@[-. CCF:pb - Enclosures 31 --=.