PERMIT DOCUMENTS TURQUOISE Engineering, LLC
Structural Engineering, Design & Testing, CA #28948, NOA #13-0222.02
6915 Washington Rd,West Palm Beach, FL 33405/Phone(561)804-9908/Fax(561)804-9907/e-mail:turginc@aol.com
August 02, 2016
TO: City of Boynton Beach / Building Department
FROM: Riza N. ALTAN, P.E.
SUBJECT: In-Progess Inspection of Flat Re-Roofing
ADDRESS: RAAB Residence / 18 Oaks Ln., Boynton Beach, FL 33436
CONTRACTOR: Robert G Hartmann Inc.
PERMIT: #16-2503
Dear Sir:
The re-roofing of flat area of the subject residence inspected by myself during its in-progress
and final stages. The following observations are made:
The GlasBase base sheet is properly tin-tagged over the re-nailed plywood deck. The 26 Ga.
3"x3" drip edges are overlapped min. 4" and fastened using 11 ga. roofing nails spaced max
at 4" o.c.
It is observed that Flintglas ply sheet and FlintLastic GMS cap sheets are fully hot-mopped as
per CertainTeed Modified Bitumen Roof System over Wood Decks (#FL16709.R3,Table 5, Sys. Type
E, Sys Nc.:W-5, pg. 13/14).
Therefore, this letter is to certify that, during its in-progress; the re-nailing of existing plywood
deck, installations of drip edge and tie-in metals, CertainTeed hot-mopped (#FL16709.R3) •
non-insulated Roof System are observed to be completed conforming to requirements of the
2014 Florida Building Code which specifies 170 MPH ultimate wind speed for Risk Category II
in Exposure C area.
If you have any questions regarding this matter or I may be of further assistance, please do
not hesitate to call me.