DRAWINGSFAULT CURRENT CULCULATIONS AT TRANSFORMER TRASNOFRMER KVA: 150KVA VOLTAGE EL -L: 48OV, 30 IMPEDANCE Z 3.5x 1 f.l. TRANSFORMER FULL LOAD AMPERS M MULTIPLIER IS.C. TRANSFORMER LET -THROUGH SHORT-CIRCUIT CURRENT 41= KVAx1000 = 150x1000 = 236.7 EL -Lx 1.732 480x1.732 m :� = 3D = 28.6 IS.C= If Lx m = 236.7x28.6 = 6,771 AMPS SHOP DRAWING REQUIREMENTS 1. CONTRACTOR SHALL SUBMIT 6 COPIES OF COMPLETED SHOP DRAWINGS, TOGETHER AT ONE TIME AND MUST COME THROUGH THE ARCHITECT. ALL SUBMITTALS SHALL BE MADE WITHIN 30 DAYS OF NOTICE TO PROCEED. 2. ALL SUBMITTALS MUST CLEARLY INDICATE EXACTLY WHICH ITEMS ARE BEING PROPOSED FOR USE. IF NOT, THE SUBMITTAL SHALL BE REJECTED. 3. SUBSTITUTIONS SHALL BE LIMITED TO ONE OF THE ALTERNATES LISTED IN THE CONSTRUCTION DOCUMENTS. PRODUCTS CONSIDERED TO BE EQUAL SHALL BE REVIEWED AND ACCEPTED BY THE ENGINEER, ARCHITECT AND OWNER (10) DAYS PRIOR TO BID DATE. 4. THE CONTRACTOR ASSUMES ALL DESIGN RESPONSIBILITY AND ALL FINANCIAL RISKS FOR PROCEEDING PRIOR TO SHOP DRAWINGS PROCESSING, AND ON ANY ITEM OR WORK THAT IS AT VARIANCE TO THE CONSTRUCTION DOCUMENTS. 5• SHOP DRAWINGS AND SUBMITTALS FOR EACH ITEM SHALL BE REVIEWED NO MORE THAN TWICE. A THIRD SUBMITTAL ON AN ITEM MUST BE ACCOMPANIED BY A PURCHASE ORDER FROM THE CONTRACTOR OR IT SHALL BE REJECTED. 6. CIRCUMSTANCES NECESSITATING A REVISION TO THE PERMITTED DOCUMENTS NOT PROCESSED PRIOR TO INSTALLATION MAY NOT BE ACCEPTED. IF ACCEPTED IT MUST BE LEGIBLE, ACCURATE AND ACCOMPANIED BY A PURCHASE ORDER ORDER FROM THE CONTRACTOR. THE REVISION SHALL BE CHARGED TO THE CONTRACTOR AND DELIVERED TO HIM ON A C.O.D. BASIS. 7. SUBSTITUTIONS FROM THE BASE DESIGN OR VARIATIONS TO THE PERMITTED CONTRACT DOCUMENTS, WHETHER RESULTING FROM PROCESSED SHOP DRAWINGS OR NOT, THAT RESULT IN REQUIREMENTS IN LETTERS OF AUTHORIZATION AND/OR PERMIT CONTRACT DOCUMENT CHANGES MANDATED BY THE AUTHORITY HAVING JURISDICTION WILL NOT BE MADE BY THIS OFFICE UNLESS ACCOMPANIED BY A PURCHASE ORDER FROM THE CONTRACTOR, AND RELEASED ON A C.O.D. BASIS. 8. CONTRACTOR SHALL SUBMIT 5 COPIES OF EQUIPMENT LAYOUTS OF ALL ELECTRICAL SPACES, ROOMS. ETC. TO THE ENGINEER FOR APPROVAL PRIOR TO ORDERING EQUIPMENT OR INSTALLING CONDUITS. ETC. THE LAYOUTS SHALL CONSIST OF PLAN VIEWS AT A SCALE OF 1/2" - 1'0" AND ELEVATIONS FOR EACH SUCH SPACE OR ROOM, ETC. Mfect ' i - L /O f Plumbing � Forester �- Police s pp S. tmr 4 14 4 A xe� o u or h *\ q\ EXISTING r OVERHEAD PINES \� EXISTING BRANCH �, CIRCUIT WITH 2" EXISTING BRANCH -EXISTING BRANCH PVC, (4)#3/0, (1)#6 , 1 �� , CIRCUIT WITH 3" ; CIRCUIT WITH 11k"GREEN TO I I PRODUCTION ROOM. J ' ; PVC, (3)#4/0, (2)#3 RIGID, (3)#3, (1)#6 ' TO REFRIGERATION GREEN TO VACUUM i COMPRESSOR RACK. PUMP. 1 I r REMOVE 277/480V 200 A. 400 A.* PANEL 400 A. 3 -PH. METER DISC. i 1 DISC. "A" SWITCH_ I I SWITCH I I I I WITH 11 1 1 a I I 11400 AJ I III I 1 1rRi I I a� I IMCB. °II 111 II 5 I� ��---_� it I I 11 11 II 1 I Lr __j EXIST. L? l i ° I f ' - - -1i ° I FPL PULLBOX, PROVIDED BY FPL INSTALLED BY z 3-3/0-2" 75 KVA �`a~�' CONTRACTOR. I I FLEX. 48240 3" PVC. 3E MOVE PVC. COORDINATE WITH FPL �1 REMOVE (2) 2 PVC II �j TO FP&L POWER POLE 111 I - - _j EX. 1)j" PVC. 3#2 , II GRADE ❑ ❑ ❑ ❑ A A1 EXISTING POWER RISER DIAGRAM E1.0 N.T.S. - EXISTING EQUIPMENT TO BE REMOVED - - - - EXISTING EQUIPMENT TO REMAIN NEW EQUIPMENT COORDINATE ALL WORK WITH FPL REPRESENTATIVE 1 y n i National Electrical Code. This approval of the plans shall not prevent the field Inspector from requiring the corrections of errors on such plans when in violation of the FBC or NEC in effect. E S GBANH Ai CIRCUIT WITH 176" ; RIGID, (3)#3, (1)#8� EXISTING BRANCH ; GRD TO j COMPRESSOR CIRCUIT WITH 2" XISTING BRANCH ; A E 1 2 1 PVC, (4)#3/0, (1)#6 CIRCUIT WITH 3" , , EXISTING BRANCH GROUND TO PVC (3)#300 MCM ' CIRCUIT WITH 17i" PRODUCTION ROOM , PANEL (1)#4/0 N.,(1)# 4/0 RIGID, (3)#3, (1)#6 G. TO r , GREEN TO VACUUM i REFRIGERATION PUMP. ' COMPRESSOR RACK. r EXIST. I X400 Aa 11 I�PANEV11NEW 200 A. DISC. 800 AMP " DISCO. I I SWITCH I I I I TH 1 CT'S 1400 AJ I 277/480V,3 I�•� i I 1 OOK. °' ( IMCB. `I 4 I IJP - _ A.I.C. I I 1165 AI9OTED LT � EXIST. I 1 I� °011 ' 75 KVA g-- - - 480 240 3" PVC W/ 1 4- 3-3/0+-2" ; - - 500 MCM-CU p FLEX. 1X1 X8 GUTTER 3R NEW 2 SETS OF 500 MCM USE POLARIS TAP . ,_„,p p GRADE ❑❑ ` EX. 1Ji" PVC.W/3#2 7�L __ EXISTING FPL OVERHEAD LINES 3 J1 I 1AV. METERI M all 1 ? III I FPL PULLBOX, PROVIDED 1 II BY FPL INSTALLED BY 51 11 CONTRACTOR. COORDINATE WITH FPL. z I II I (2) 3r PVC W/4-500 III I ACM -CU EA. U/GROUND (II TO CT's. I I I I I -L-- N__ USE D AND-," �EELECTR�DEOYSTEM AND TO BUILDING TEEL 2 [E10 NEW POWER RISER DIAGRAM UPGRADE TO 800AMP. N.T.S. - - - - EXISTING EQUIPMENT TO REMAIN NEW EQUIPMENT COORDINATE ALL WORK WITH FPL REPRESENTATIVE LOCATION OF EXISTING ELECTRICAL SERVICE AND UTILITY POLE. SEE POWER RISER DIAGRAM zaoTHIS SHEET. N SITE LOCATION PLAN E1.0 N.T.S. ELECTRICAL INDEX 1606X0( GENERAL ELECTRICAL NOTES (GENERAL NOTES ARE PROVIDED AS A BASIC DESCRIPTION OF THE EXTENT AND QUALITY EXPECTED IN THIS PROJECT. IF A CONFLICT EXISTS BETWEEN THESE GENERAL NOTES AND THE REMAINDER OF THE CONTRACT DOCUMENTS THE SPECIFICATIONS, PLANS AND DETAILS WILL GOVERN.) x 1. THE ENTIRE INSTALLATION SHALL BE IN ACCORDANCE WITH THE FOLLOWING CODES AND STANDARDS: 28. ALL CIRCUIT BREAKERS SHALL BE INVERSE TIME TYPE (THERMAL MAGNETIC OR SOLID DATE: 06/08/2016 � C ,� � VS FLOW MA 69NISIPATIYE A-3.012 (FAC) �D 2 STATE AS REQUIRED BY SPECIFICATION). TWO AND THREE POLE CIRCUIT BREAKERS SHALL BE COMMON TRIP. NO TIE HANDLES PERMUTED. FLDMDA STA.IUIE SECTION 633.022 A. NFPA 70: NATIONAL ELECTRICAL CODE (2011 EDITION) 29. ALL FUSES SHALL BE CURRENT LIMITING, PER U.L, RATED 600V., LION. B. NFPA 7Z NATIONAL FIRE ALARM CODE (2010 EDITION) A. NON -TIME DELAY FUSES IN MAIN SWITCHES AND SWITCHES FINDING PANELS. C. NFPA 99: HEALTH CARE FACILITIES (2012 EDITION) B. TIME DELAY FUSES FOR MOTOR AND A/C CIRCUITS. D. NFPA 101: LIFE SAFETY CODE 2012 EDITION) _ AND STANDBY POWER SOW (2010 EDITION) 30• ALL DISCONNECT SWITCHES SHALL BE SIZED BY NEC REQUIREMENTS 70 ACCOMMODATE E NEPA 110: STANDARD FOR F IPPA 780' STANDARD FOR THE INSTALLATION OF LK;IiT" PROTECTION SOW (2011 ON) EQUIPMENT SERVED, INCLUDING REQUIRED FUSES U.O.N. SWITCHES SHALL BE HORSEPOWER RATED FOR MAX. HORSEPOWER, HEAVY DUTY TYPE. IN ADDITION, THE INSIAUATION SHALL ALSO BE IN ACCORDANCE WITH THE FOLLOW G. FLOREA BUILDING CODE 2010 31. CONTRACTOR SHALL VERIFY CIRCUIT PROTECTIVE DEVICE RATING FOR EQUIPMENT PRIOR H. THE GUIDELINES FOR DET9M AND CONSTRUCTION OF HEALTH CARE FACILITIES TO INSTALLATION. (FGA GUIDELINES, 2010 EDITION) 32. FURNISH AND INSTALL DISCONNECT SWITCHES AND WIRING FOR AIR CONDITIONING L FLD FIRE PREVENTION CODE (2D10 EDITION) M SYSTEM AS PER MANUFACTURER RECOMMENDATIONS. CONTROLS ARE TO BE SUPPLIED 2. AS A MINIMUM, ALL EQUIPMENT SHALL MEET APPLICABLE STANDARDS, FOR THE TYPE OF EQUIPMENT AND INTENDED USE, OF THE FOLLOWING: BY AIR CONDITIONING CONTRACTOR AND CONNECTED. PROVIDE ALL CONTROL WIRING FOR A/C SENSORING AND CONTROL UNITS, COORDINATE WITH A/C CONTRACTOR FOR WIRING A. AMERICAN NATIONAL STANDARDS INSTTTUTE (ANSI) DIAGRAMS AND EXACT MOUNTING LOCATIONS. B. ILLUMINATING ENGINEERS SOCIETY (IES) 33. ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT WHERE EXPOSED TO THE WEATHER. C. AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM) ALL FLEX CONDUIT'S CONNECTED TO SUCH EQUIPMENT SHALL BE LIQUID TIGHT. D. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCUITES.(NEMA) E. NOTE- THESE STANDARDS ARE SUBORDINATE TO CODES AND STANDARDS SET BY U.L 34. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND NEMA RATED FOR THE ALL ELECTRICAL EQUIPMENT, DEVICES, WIRE, ETC., SHALL BE LISTED, FOR INTENDED ENVIRONMENT IN WHICH THEY ARE TO BE INSTALLED. USE, WITH UNDERWRITER'S LABORATORIES INC. (U.L). WHERE STANDARDS HAVE BEEN 35, ALL CONNECTIONS TO GROUND RODS SHALL BE MADE WITH U.L APPROVED WELDED ESTABLISHED BY U.L CONNECTIONS, UNLESS NOTED OTHERWISE. THE CONTRACTOR SHALL FORM A 3. CONTRACTOR TO PROVIDE ALL LABOR, MATERIALS AND SUPERVISION NECESSARY TO GROUNDING ELECTRODE SYSTEM AS PER NEC 250-50. ACCOMPLISH THE WORK AS SHOWN AND/OR NOTED ON THE DRAWINGS. 36. OUTLET IN DRY LOCATIONS BOXES SHALL BE PRESSED STEEL, IN WET OR DAMP 4. THE CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL CONDITIONS, LOCATIONS. LOCATIONS SHALL BE CAST ALLOY WEATHER -RESISTANT OUTLET WITH THREADED HUBS DIMENSIONS AND COUNTS AS SHOWN OR NOTED ON THE DRAWINGS, PRIOR TO AND IN OTHER CLASSIFIED AREAS R SHALL BE IN A SPECIAL ENCLOSURE. PROPER SUBMITTING BID. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE ALL LABOR. PLASTER RINGS SHALL BE USED WITH OUTLET BOXES. PROPER COORDINATION BETWEEN ELECTRICAL SUBCONTRACTOR AND GENERAL CONTRACTOR FOR PLASTER RING INITIATION 5. MATERIALS AND SUPERVISION NECESSARY TO ACCOMPLISH THE WORK AS SHOWN WILL BE REQUIRED. NO "GOOF" RINGS SHALL BE ALLOWED. ALL OUTLET BOXES SHALL AND/OR NOTED ON THE PUNS. BE SECURELY FASTENED. 6. ELECTRICAL CONTRACTOR SHALL NOT SCALE DRAWINGS. CONTRACTOR SHALL REFER TO 87, WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE RESISTIVE ASSEMBLIES, ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT LOCATIONS OF ALL EQUIPMENT (CLASSIFIED AS FIRE/SMOKE AND SMOKE PARTITIONS), THEY SHALL BE INSTALLED UNLESS NOTED OTHERWISE. WITHOUT AFFECTING THE FIRE CLASSIFICATION. ALL OF THE FOLLOWING CONDITIONS 7. Tr SHALL BE UNDERSTOOD THAT ALL WORK PERFORMED SHALL BE DONE BY A LICENSED SHALL BE MET' CONTRACTOR AND IN A FIRST-CLASS WORKMANLIKE MANNER. SAID CONTRACTOR SHALL A. ALL ELECTRICAL BOXES SHALL BE METALLIC. MEET ALL REQUIREMENTS SET FORTH BY ANY LOCAL ORDINANCE AND GOVERNING B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE. AUTHORITIES. C. BOX OPENING SHALL NOT EXCEED 10322.56 SQUARE MM (16SQUARE INCHES). 8. THE CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE COMPLETELY FILLED WITH JOINT COMPOUND (OR OTHER APPROVED MATERIAL). 9. CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS E. PROVIDE A WALL AROUND OUTLETS LARGER THAT 1032156 SQUARE MM (16 FOR A PERIOD OF NOT LESS THAN ONE YEAR FROM DATE OF ACCEPTANCE, UNLESS SQUARE INCHES). THE INTEGRITY OF THE WALL RATING SHALL BE MAINTAINED. INDICATED OR SPECIFIED OTHERWISE. F. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 64516 10. IT SHALL NOT BE THE INTENT OF THESE PLANS AND/OR SPECIFICATIONS TO SHOW SQUARE MM (100 SQUARE INCHES) PER 9.29 SQUARE METERS (100 SQUARE FEET). EVERY MINOR DETAIL OF CONSTRUCTION. THE CONTRACTOR SHALL BE EXPECTED TO G. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE RESISTIVE ASSEMBLIES SHALL FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM AND PROVIDE BE SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 609.6MM (24 INCHES). FOR ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER H. OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS. WORKING ORDER. ORIGINAL CONDITIONS. I. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED 3.175MM (1/8 INCH) BETWEEN THE EDGES OF THE OUTLET BOX AND THE EDGES OF 11. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING TO ANY AND ALL DAMAGES TO BUILDING SURFACES, EQUIPMENT, ETC. CAUSED DURING THE THE OPENING. PERFORMANCE OF WORK. 38. SMOKE DETECTORS SHALL BE PROVIDED NO CLOSER THAN 36" FROM SUPPLY AIR 12. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE OR DIFFUSERS. DELAYS AND SWILL INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE 39. CONTRACTOR SHALL PROVIDE A TYPE WRITTEN DIRECTORY OF EACH PANELBOARD. HAND INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY WRITTEN DIRECTORY IS NOT ACCEPTABLE, EXCEPT SPARE AND SPACES SHALL BE 13. FOR ELECTRIC POWER SYSTEM, COORDINATE POWER SERVICE WITH POWER COMPANY, HANDWRITTEN IN PENCIL A. VERIFY LOCATION OF POWER SERVICE TERMINATION WITH POWER COMPANY, PRIOR TO SUBMITTING BID. CONTRACTOR TO VERIFY AVAILABLE SERVICE VOLTAGE AND PHASES 40. PROVIDE A 4" STEEL REINFORCED CONCRETE HOUSEKEEPING PAD UNDER ALL FLOOR WITH POWER COMPANY PRIOR TO BID AND PROVIDE BID ALLOWANCE FOR ALTERNATES. MOUNTED ELECTRICAL EQUIPMENT. B. PROVIDE TEMPORARY ELECTRICAL SERVICE FOR USE BY ALL TRADES DURING 41. A WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH CONSTRUCTION AND REMOVE SAME AT COMPLETION OF PROJECT, NEC 110.26 14. CONTRACTOR SHALL KEEP ALL AREAS IN WHICH WORK IS BEING PERFORMED, FREE B. THE EXCLUSIVELY DEDICATED SPACE EXTENDING FROM FLOOR TO STRUCTURAL FROM DEBRIS AT ALL TIMES AND SAID AREAS SHALL BE LEFT BROOM CLEAN AT THE CEILING WITH A WIDTH AND DEPTH OF THE PANELBOARD OR SWITCHBOARD MUST BE END OF EACH WORKING DAY. CLEAR OF ALL PIPING, DUCTS, EQUIPMENT FOREIGN TO THE ELECTRICAL EQUIPMENT OR 15. CONTRACTOR SHWA PAY FOR ALL PERMITS, FEES. INSPECTIONS, AND TESTING COSTS. ARCHITECTURAL APPURTENANCES IN ACCORDANCE WITH NEC 408. 16. COORDINATE ALL ELECTRICAL SITE WORK WITH ALL OTHER TRADES CONTRACTORS. 42. OAR. HUCO,& LUGS FOR SAME ARE TO NTRACTOR TO VERIFY SPECIFIC BTYPE OFISMETER INSTALLED TO By 17. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR FOR THE ADVANCE WITH F.P.L. PRIOR TO BID. ORDERING OF LONG LEAD ITEMS, AS TO NOT INTERFERE WITH THE PRODUCTION OF OTHER TRADES RESULTING IN ANY DOWN OR LAG TIME. THE CONTRACTOR SHALL NOT 43. A. PROVIDE A PERMANENT SIGN ON THE MAIN ELECTRICAL ROOM DOOR TO THE BLDG. ORDER ANY ITEMS UNTIL APPROVED SHOP DRAWINGS ARE RETURNED TO HIM. STATING THAT THE SERVICE DISCONNECTS ARE LOCATED INSIDE. B. SIGNS SHALL BE PLACED AT THE MAIN DISCONNECT EQUIPMENT INDICATING TYPE AND 18. ELECTRICAL CONTRACTOR SHALL SUBMIT (6 COPIES) EQUIPMENT LAYOUT OF ALL ELECTRICAL SPACES, ROOMS, ETC., TO ENGINEER FOR APPROVAL PRIOR TO ORDERING LOCATION OF ON-SITE EMERGENCY POWER SOURCES. EQUIPMENT OR INSTALLING CONDUITS. ETC. LAYOUT SHALL CONSIST OF PLAN VIEWS - (SCALED AS REQUIRED) . AND ELEVATIONS (DIMENSIONED) FOR EACH SUCH SPACE, 44. THE EQUIPMENT GROUNDING TERMINAL BARS OF THE NORMAL AND EMERGENCY ELECTRICAL SYSTEM PANELBOARDS SERVING THE SAME BUILDING SHALL BE BONDED ROOM, ETC. TOGETHER WITH AN INSULATED, CONTINUOUS, COPPER CONDUCTOR NOT SMALLER THAN 19. CONTRACTOR SHALL SUBMIT AT ONE TIME. SIX (6) SETS OF LOOSE-LEAF BOUND BOOKS, INDEXED WITH ALL PRODUCTS, MATERIALS, LIGHTING FIXTURES.' LAMPS, WIRING 45. NUMBER 6. THE ELECTRICAL CONTRACTOR SHALL FURNISH A COMPLETE SET OF AS -BUILT DEVICES, SWITCHGEAR, ETC. CLEARLY HIGHLIGHTING ALL EQUIPMENT QUANTITIES AND DRAWINGS, SHOWING ALL CHANGES AND DEVIATIONS TO THE ARCHITECT/ENGINEER PRIOR DETAILS. ALL EQUIPMENT SHALL BE AS SPECIFIED ON PLANS: THE RESPONSIBILITY TO TO COMPLETION OF THE PROJECT. ACCEPT OR REJECT ANY PROPOSED SUBSTITUTION REMAINS WITH THE 'PROJECT ENGINEER. THE CONTRACTOR MAY AT HIS JUDGMENT USE ANY ARTICLE, DEVICE, 46. ARCHITECTURAL AND/OR ENGINEERING EXPENSES THAT ARE INCURRED DUE TO EVI IOONNSSOOR SUBSTITUTIONS REQUESTED BY THE CONTRACTOR SHALL BE PAID FOR BY REVISIONS PRODUCT, OR MATERIAL WHICH IN THE JUDGMENT OF THE ENGINEER EXPRESSED IN WRITING ARE EQUAL TO THAT SPECIFIED. 20. ALL CONDUCTORS SHALL BE COPPER, TYPE THHN/THWN EXCEPT WHERE OTHERWISE REQUIRED BY U.L OR CODES. MINIMUM WIRE SIZE SHALL BE #12 AWG. EXCLUDING 47. FOR TELEPHONE SYSTEMS: A PROVIDE GROUNDING FOR ALL TELEPHONE OUTLETS AND EQUIPMENT PER CONTROL WIRING. ALUMINUM CONDUCTORS ARE NOT PERMITTED. REQUIREMENTS OF THE TELEPHONE COMPANY. B. COORDINATE INSTALLATION OF ALL TELEPHONE OUTLETS, RACEWAYS, ENCLOSURES 21. ALL CONDUCTORS SHALL BE IN CONDUITS. ALL CONDUITS SHALL BE GALVANIZED RIGID AND BACKBOARDS WITH TELE. CO. STEEL (GRS) EXCEPT THAT: (a) PVC CONDUITS MAY BE USED UNDERGROUND PROVIDED ELBOWS AND RISERS ARE GALVANIZED RIGID STEEL OR SCHEDULE 80 PVC, WHERE C. VERIFY LOCATION OF TELEPHONE SERVICE WITH TELEPHONE COMPANY. PROVIDE SERVICE CONDUIT TO BLDG. FROM SERVICE POINT PER TELCO. INSTRUCTIONS, INCLUDE SUBJECT TO PHYSICAL DAMAGE (b) ELECTRICAL METALLIC TUBING (EMT) MAY BE USED IN OR ON WALLS OR CEILINGS WHERE NOT SUBJECT TO MECHANICAL DAMAGE, DAMP OR ALL ASSOCIATED COSTS IN BID. D. MARK TERMINATIONS OF TELEPHONE CONDUIT AS DIRECTED BY THE TELEPHONE CORROSIVE CONDITIONS, (c) LIQUID TIGHT FLEXIBLE CONDUIT WHERE REQUIRED, (d) FLEXIBLE METALLIC CONDUIT WHERE REQUIRED IN DRY LOCATIONS ONLY, (e) MC CABLE COMPANY. E VERIFY LOCATION OF TELEPHONE SERVICE WITH TELEPHONE COMPANY PRIOR TO WITH DEDICATED GREEN GROUNDING CONDUCTOR WHERE PERMITTED. ALL CONDUITS IN HAZARDOUS AREAS (PER NEC) SHALL MEET THE REQUIREMENTS OF NEC CHAPTER 5. SUBMITTING BID, INCLUDE ALL ASSOCIATED COSTS IN BID. F. USE EXTERIOR GRADE 3/4" PLYWOOD BACKBOARDS FOR MOUNTING TELEPHONE EQUIPMENT AND TERMINAL STRIPS. PAINT BOARD ON ALT. SIDES AND EDGES WITH TWO 22. FOR UNDERGROUND ELECTRICAL CONDUITS, PROVIDE PULL BOXES, SUCH THAT NO COATS OF FLAT BLACK FIRE RETARDANT PAINT. SINGLE CONDUIT RUN HAS BENDS IN EXCESS OF 360. PULL BOXES ;SHALL BE SUITABLE AND APPROVED FOR THE INTENDED USE. WARNING TAPE WHICH SAYS 48. INDUSTRIAL CONTROL TYPE TRANSFORMERS SHALL BE PROVIDED WITH FINGERSAFE COVERS AND PRIMARY FUSE PROTECTION AS REQUIRED PER NEC 450-3. MOUNT "WARNING BURIED ELECTRIC" SHALL BE PLACED IN TRENCHES ABOVE ALL UNDERGROUND ELECTRIC CONDUITS. WHERE CONDUITS PASS UNDERNEATH PAVED AREAS, THEY SHALL TRANSFORMERS ON 4"X4" JUNCTION BOX ABOVE ACCESSIBLE CEILINGS OR ELECTRICAL BE PVC. WHERE UNDERGROUND CONDUITS ARE NOT EXPOSED TO MECHANICAL DAMAGE ROOMS. OR ARE NOT UNDER PAVED AREAS, THEY SHALL BE SCHEDULE 40 PVC. 49. FOR RESIDENTIAL WORK PROVIDE COMBINATION TYPE ARC -FAULT CIRCUIT INTERRUPTER 23. ALL CONDUIT RUNS ARE SHOWN DIAGRAMMATIC. EXACT ROUTING SHALL BE DETERMINED PROTECTION THROUGHOUT THE DWELLING UNIT, EXCEPT IN KITCHEN BATHROOM, GARAGES AND OUTDOORS. ALL DWELLING UNIT RECEPTACLE OUTLETS MUST BE LISTED 24. IN THE FIELD. UNLESS OTHERWISE NOTED. WIREWAYS SHALL BE SIZED AS REQUIRED. PER NEC, UNLESS OTHERWISE NOTED (UON). TAMPER-RESISTANT. 25. WHERE CORE DRILLING OF FLOOR/WALLS IS REQUIRED, CONTRACTOR SHALL SEAL 50. PROVIDE U.L LISTED COMPOUND APPLIED TO BACK OF "BACK TO BACK" BOXES IN RATED WALLS WHERE THE BOXES ARE LESS THAN 609.6MM (24 INCHES) APART OPENINGS WATERTIGHT AFTER UTILITIES HAVE BEEN INSTALLED. LOCATION OF CORED HOLES SHALL COORDINATE WITH LOCATION OF EQUIPMENT IN A MANNER TO BE CLEAN MEASURED HORIZONTALLY. AND FUNCTIONAL THE CONTRACTOR SHALL INSTALL ONLY ONE CONDUIT PER HOLE AND 51. CONTRACTOR SHALL PROVIDE TYPED -WRITTEN, UPDATED PANEL DIRECTORIES ON ALL SEAL THE OPENING AROUND THE CONDUIT AS SPECIFIED. PANELS THAT ARE AFFECTED AT THE COMPLETION OF THE JOB. 26. PROVIDE FIRE RETARDANT U.L APPROVED SEALANT ON ALL PENETRATIONS OF FIRE RATED PARTITIONS, WALLS AND STRUCTURAL SLABS. CONTRACTOR TO VERIFY, PRIOR TO 52. FOR RECEPTACLES AS ALLWEAPROVIDE ALL 501/..1 AND AND WET 20ARECEPTACLES CONTARE RACTOR SUBMITTING BID, LOCATIONS OF ALL SUCH FIRE RATED PARTITIONS, WALL AND RESISTANT TYPE TO COMPLY WITH NEC ARTICLE 406.8. STRUCTURAL SLABS. 27. UNLESS NOTED AS EXISTING, ALL EQUIPMENT, WIRING, DEVICES. ETC. $HALL BE NEW. FAULT CURRENT CULCULATIONS AT TRANSFORMER TRASNOFRMER KVA: 150KVA VOLTAGE EL -L: 48OV, 30 IMPEDANCE Z 3.5x 1 f.l. TRANSFORMER FULL LOAD AMPERS M MULTIPLIER IS.C. TRANSFORMER LET -THROUGH SHORT-CIRCUIT CURRENT 41= KVAx1000 = 150x1000 = 236.7 EL -Lx 1.732 480x1.732 m :� = 3D = 28.6 IS.C= If Lx m = 236.7x28.6 = 6,771 AMPS SHOP DRAWING REQUIREMENTS 1. CONTRACTOR SHALL SUBMIT 6 COPIES OF COMPLETED SHOP DRAWINGS, TOGETHER AT ONE TIME AND MUST COME THROUGH THE ARCHITECT. ALL SUBMITTALS SHALL BE MADE WITHIN 30 DAYS OF NOTICE TO PROCEED. 2. ALL SUBMITTALS MUST CLEARLY INDICATE EXACTLY WHICH ITEMS ARE BEING PROPOSED FOR USE. IF NOT, THE SUBMITTAL SHALL BE REJECTED. 3. SUBSTITUTIONS SHALL BE LIMITED TO ONE OF THE ALTERNATES LISTED IN THE CONSTRUCTION DOCUMENTS. PRODUCTS CONSIDERED TO BE EQUAL SHALL BE REVIEWED AND ACCEPTED BY THE ENGINEER, ARCHITECT AND OWNER (10) DAYS PRIOR TO BID DATE. 4. THE CONTRACTOR ASSUMES ALL DESIGN RESPONSIBILITY AND ALL FINANCIAL RISKS FOR PROCEEDING PRIOR TO SHOP DRAWINGS PROCESSING, AND ON ANY ITEM OR WORK THAT IS AT VARIANCE TO THE CONSTRUCTION DOCUMENTS. 5• SHOP DRAWINGS AND SUBMITTALS FOR EACH ITEM SHALL BE REVIEWED NO MORE THAN TWICE. A THIRD SUBMITTAL ON AN ITEM MUST BE ACCOMPANIED BY A PURCHASE ORDER FROM THE CONTRACTOR OR IT SHALL BE REJECTED. 6. CIRCUMSTANCES NECESSITATING A REVISION TO THE PERMITTED DOCUMENTS NOT PROCESSED PRIOR TO INSTALLATION MAY NOT BE ACCEPTED. IF ACCEPTED IT MUST BE LEGIBLE, ACCURATE AND ACCOMPANIED BY A PURCHASE ORDER ORDER FROM THE CONTRACTOR. THE REVISION SHALL BE CHARGED TO THE CONTRACTOR AND DELIVERED TO HIM ON A C.O.D. BASIS. 7. SUBSTITUTIONS FROM THE BASE DESIGN OR VARIATIONS TO THE PERMITTED CONTRACT DOCUMENTS, WHETHER RESULTING FROM PROCESSED SHOP DRAWINGS OR NOT, THAT RESULT IN REQUIREMENTS IN LETTERS OF AUTHORIZATION AND/OR PERMIT CONTRACT DOCUMENT CHANGES MANDATED BY THE AUTHORITY HAVING JURISDICTION WILL NOT BE MADE BY THIS OFFICE UNLESS ACCOMPANIED BY A PURCHASE ORDER FROM THE CONTRACTOR, AND RELEASED ON A C.O.D. BASIS. 8. CONTRACTOR SHALL SUBMIT 5 COPIES OF EQUIPMENT LAYOUTS OF ALL ELECTRICAL SPACES, ROOMS. ETC. TO THE ENGINEER FOR APPROVAL PRIOR TO ORDERING EQUIPMENT OR INSTALLING CONDUITS. ETC. THE LAYOUTS SHALL CONSIST OF PLAN VIEWS AT A SCALE OF 1/2" - 1'0" AND ELEVATIONS FOR EACH SUCH SPACE OR ROOM, ETC. Mfect ' i - L /O f Plumbing � Forester �- Police s pp S. tmr 4 14 4 A xe� o u or h *\ q\ EXISTING r OVERHEAD PINES \� EXISTING BRANCH �, CIRCUIT WITH 2" EXISTING BRANCH -EXISTING BRANCH PVC, (4)#3/0, (1)#6 , 1 �� , CIRCUIT WITH 3" ; CIRCUIT WITH 11k"GREEN TO I I PRODUCTION ROOM. J ' ; PVC, (3)#4/0, (2)#3 RIGID, (3)#3, (1)#6 ' TO REFRIGERATION GREEN TO VACUUM i COMPRESSOR RACK. PUMP. 1 I r REMOVE 277/480V 200 A. 400 A.* PANEL 400 A. 3 -PH. METER DISC. i 1 DISC. "A" SWITCH_ I I SWITCH I I I I WITH 11 1 1 a I I 11400 AJ I III I 1 1rRi I I a� I IMCB. °II 111 II 5 I� ��---_� it I I 11 11 II 1 I Lr __j EXIST. L? l i ° I f ' - - -1i ° I FPL PULLBOX, PROVIDED BY FPL INSTALLED BY z 3-3/0-2" 75 KVA �`a~�' CONTRACTOR. I I FLEX. 48240 3" PVC. 3E MOVE PVC. COORDINATE WITH FPL �1 REMOVE (2) 2 PVC II �j TO FP&L POWER POLE 111 I - - _j EX. 1)j" PVC. 3#2 , II GRADE ❑ ❑ ❑ ❑ A A1 EXISTING POWER RISER DIAGRAM E1.0 N.T.S. - EXISTING EQUIPMENT TO BE REMOVED - - - - EXISTING EQUIPMENT TO REMAIN NEW EQUIPMENT COORDINATE ALL WORK WITH FPL REPRESENTATIVE 1 y n i National Electrical Code. This approval of the plans shall not prevent the field Inspector from requiring the corrections of errors on such plans when in violation of the FBC or NEC in effect. E S GBANH Ai CIRCUIT WITH 176" ; RIGID, (3)#3, (1)#8� EXISTING BRANCH ; GRD TO j COMPRESSOR CIRCUIT WITH 2" XISTING BRANCH ; A E 1 2 1 PVC, (4)#3/0, (1)#6 CIRCUIT WITH 3" , , EXISTING BRANCH GROUND TO PVC (3)#300 MCM ' CIRCUIT WITH 17i" PRODUCTION ROOM , PANEL (1)#4/0 N.,(1)# 4/0 RIGID, (3)#3, (1)#6 G. TO r , GREEN TO VACUUM i REFRIGERATION PUMP. ' COMPRESSOR RACK. r EXIST. I X400 Aa 11 I�PANEV11NEW 200 A. DISC. 800 AMP " DISCO. I I SWITCH I I I I TH 1 CT'S 1400 AJ I 277/480V,3 I�•� i I 1 OOK. °' ( IMCB. `I 4 I IJP - _ A.I.C. I I 1165 AI9OTED LT � EXIST. I 1 I� °011 ' 75 KVA g-- - - 480 240 3" PVC W/ 1 4- 3-3/0+-2" ; - - 500 MCM-CU p FLEX. 1X1 X8 GUTTER 3R NEW 2 SETS OF 500 MCM USE POLARIS TAP . ,_„,p p GRADE ❑❑ ` EX. 1Ji" PVC.W/3#2 7�L __ EXISTING FPL OVERHEAD LINES 3 J1 I 1AV. METERI M all 1 ? III I FPL PULLBOX, PROVIDED 1 II BY FPL INSTALLED BY 51 11 CONTRACTOR. COORDINATE WITH FPL. z I II I (2) 3r PVC W/4-500 III I ACM -CU EA. U/GROUND (II TO CT's. I I I I I -L-- N__ USE D AND-," �EELECTR�DEOYSTEM AND TO BUILDING TEEL 2 [E10 NEW POWER RISER DIAGRAM UPGRADE TO 800AMP. N.T.S. - - - - EXISTING EQUIPMENT TO REMAIN NEW EQUIPMENT COORDINATE ALL WORK WITH FPL REPRESENTATIVE LOCATION OF EXISTING ELECTRICAL SERVICE AND UTILITY POLE. SEE POWER RISER DIAGRAM zaoTHIS SHEET. N SITE LOCATION PLAN E1.0 N.T.S. ELECTRICAL INDEX 1606X0( DRA IN x DESIGNED BY: GSJ 1 E1.0 ELECTRICAL INDEX. NOTES. RISERS & SITE PLAN DATE: 06/08/2016 2 E2.0 ELECTRICAL BILL & SCHEDULES 3 E - 0� SCOPE OF WORK FOR THIS PROJECT CONTRACTOR SHALL PERFORM ALL WORK AS SHOWN ON THE POWER RISERS. THE EXISTING MAXIMUM LOAD ON THE SYSTEM HAS RECENTLY EXCEEDED 400AMPS. AND THE SERVICE CONDUCTORS w4VE I�EFvk-GFTiHG WIRY I+OT,-_TNEPEFORE THE SCOPE OF WOR►' IS TO REPLACE THt EXIa"'MG 4Xi%MP. -3ERVIZE WITH A NEW 80OAMP. SERVICE AS SHOWN. Copyright 2011 Material shown Wr64s the Copyrighted Property of Delta G consul! ng Enenecrs,Ync. and shall not be reproduced in whole -- - - - - - - or in nartv&out express written permission. DELTA G CONSULTING ENGINEERS, INC. THE ENGINEERING SPECIALISTS Delta G Consulting Engineers, Inc. 707 N.E. 3rd Ave. Suite 200 Fort Lauderdale, FL 33304 (954) 527-1112 Tel. (954) 524-7505 Fax www.DeltaG.net REVISIONS: QRTC 6.27-16 QRTC 7-12-16 QRTC 8-8-16 s` PROJECT #: 1606X0( PROJECT MANAGER: GSJ DESIGNED BY: GSJ C.A.#: 00009181 DATE: 06/08/2016 8141=1I=T Nn E 1. 0 LOCATION: SEE FLOOR PLAN SPEC:- SQUARE D. 17E, G.E. mFmqmN� mum PRODUCTION PANEL SCHEDULE _--- — LOCATION: SEE FLOOR PLANPANEL 'A' SCHEDULE SQUARE D. ITE . G.E. EXISTING [3 NEIN ® 1606xX �a,PA GSJ DESIGNED BY: • 1 1 • C.A.#: • • VVaii�7:►`LV�►.rW�,�iVd.�llalyi►�I�LLa:.i:"•a.1111!�� 06/08/2016 M TRANSFORMER FOR E©�� E y LOAD DESCRIP71ON PRODUCTION PANEL ©©©®%O%%/////////%% ��EmEm�� N N' %%/O%///////%%%/IrmEm p ®moi O/�%N�////%�///O/�t3'�\/©�t'\�©1��" .7�� KA m ��■m��ooaiiioiiiiaiiiiiiiiiioao���� iiiiioio®iiioiii,.����■■ m ® • • 1 - *45'- 1 •• - VIII,©©©IIIIII✓� iiiii�i���j�//���i•I�©©©1111, IRA - 1 • • - m. m - aril - �©©©m�/���/���/�������������i.��®©©©� m m m �����iiiiiiiiooi iiiiiiiaii,oe����■N •' • - m m o m M --- 111111111�9 mpg m iii//%//%i%%ilii%%iiiii/®� • • maiiiiia,���■■�■�m 0 o CIRCUIT TYPE ARC FAULT -nmE smTcH cmm m s •1 1 s M • . '� IM OGROUNDFAULT @DEDICATED @ISOLA7MGRD. 1 1 a 1 • 1�+��w�►��� i� FEEDERSIZE&� RISER C38USWAY• • f - /q' - MOUNTING: WSURFACE 01111ISH C3 FREE STANDING Q KEYED DOOR BRACING - 65 KAIC NEU7RAL BUS IS- 13HALF SIZE 0 RAI SI • K RAID 71 UO GROUND BAR- M EQUIPMENT C3 ISOLATED :• TH ENCLOSURE ENEMA I M NEMA 311 0 NEMA 4X CLASS( DIV • EASTING 001 a• ► :1 •, X01 1 « •�� CIRCUIT 1ki11ME SVATCHCON7ROL. •, • / / •.. t • - �1��`i7..�hi' i1SHUNT IMP• •. 1 FAULTI° DEDICATED @ ISOLAIED GRD. /ii•iiYYf�1�'i� ' RATEDVOLTAGE- 120/240 VOLTS 3 PHASE M EQPT. GIRD. 0 ISOL ORD. — _��� BRANCH POLM- 42 BRANCH BREAKERS= 42 KAIC KEYED ••• T-71 -— ENCLOSURE11111111111111111111111111111WWWX a « • ti. DIV a�• • a •- : •1116, w ass PANEL TYPE 13FUSED N CB PWG IN 13 CB BOLT IN LOCATION: SEE FLOOR PLANPANEL 'A' SCHEDULE SQUARE D. ITE . G.E. EXISTING [3 NEIN ® 1606xX �a,PA GSJ DESIGNED BY: • 1 1 • C.A.#: • • VVaii�7:►`LV�►.rW�,�iVd.�llalyi►�I�LLa:.i:"•a.1111!�� 06/08/2016 M TRANSFORMER FOR E©�� E y —Sol PRODUCTION PANEL ©©©®%O%%/////////%% ��EmEm�� N N' %%/O%///////%%%/IrmEm p ®moi O/�%N�////%�///O/�t3'�\/©�t'\�©1��" .7�� m ��■m��ooaiiioiiiiaiiiiiiiiiioao���� iiiiioio®iiioiii,.����■■ m IRA ooiiiiiiiiii����m m m m �����iiiiiiiiooi iiiiiiiaii,oe����■N m m o m M --- 111111111�9 m maiiiiia,���■■�■�m 0 o CIRCUIT TYPE ARC FAULT -nmE smTcH cmm m s •1 1 s M • . '� OGROUNDFAULT @DEDICATED @ISOLA7MGRD. 1 1 a 1 • 1�+��w�►��� i� FEEDERSIZE&� RISER C38USWAY• • f - /q' - MOUNTING: WSURFACE 01111ISH C3 FREE STANDING Q KEYED DOOR BRACING - 65 KAIC NEU7RAL BUS IS- 13HALF SIZE 0 RAI SI • K RAID 71 UO GROUND BAR- M EQUIPMENT C3 ISOLATED :• TH ENCLOSURE ENEMA I M NEMA 311 0 NEMA 4X CLASS( DIV • EASTING EXISTING BUILDING LOAD CALCULATION REFRIGERATION RACK PANEL 58.5 KVA PANEL "A" 131.8 KVA TOTAL BUILDING DEMAND LOAD IS 190.3 KVA TO AL BUILDI G LOAD MP 1 28.4 MP NOTE: THIS SHEET WAS CREATED TO SATISFY THE PLAN REVIEWER'S FINAL PERMITTING COMMENTS - - - - Copydght2011 --- - WOW shwrn 7isnx is the Copyrighted Property of Delta G - �Consu�ng Enain6m,lnc. and shall not be reproduced in whole C fh:*' WiMout express written permission. DELTA G CONSULTING ENGINEERS, INC. THE ENGINEERING SPECIALISTS Delta G Consulting Engineers, Inc. 707 N.E. 3rd Ave. Suite 200 Fort Lauderdale, FL 33304 (954) 527-1112 Tel. (954) 524-7505 Fax wrww.DeltaG.net REVISIONS: 9 Z2—\ RTC 7-12-16 ARTC 8-8-16 PROJECT* 1606xX PROJECT MANAGER: GSJ DESIGNED BY: GSJ C.A.#: 00009181 DATE: 06/08/2016 QW1=7 Mn GENERAL ELECTRICAL NOTES (GENERAL NOTES ARE PROVIDED AS A BASIC DESCRIPTION OF THE EXTENT AND QUALITY EXPECTED IN THIS PROJECT. IF A CONFLICT EXISTS BETWEEN THESE GENERAL NOTES AND THE REMAINDER OF THE CONTRACT DOCUMENTS THE SPECIFICATIONS, PLANS AND DETAILS WILL GOVERN.) 1. THE ENTIRE INSTALLATION SHALL BE IN ACCORDANCE WITH THE FOLLOWING CODES AND STANDARDS: ORANIIN CIRCUIT WITH 2" i FLORIDA STATE FIRE MARSHALL'S RULE 69A-3.012 FAC AND 28 ALL CIRCUIT BREAKERS SHALL BE INVERSE TIME TYPE THERMAL MAGNETIC OR SOLID DATE: RULE CHAPTER 6OA-60 FLORIDA ADMINISTRATIVE CODE (FAC) AND CIRCUIT WITH 1X2" STATE AS REQUIRED BY SPECIFICATION). TWO AND THREE POLE CIRCUIT BREAKERS E2.0 ELECTRICAL BILL & SCHEDULES FLORIDA STATUTE SECTION 633.022. RIGID, 3 3 (1)#6 O# SHALL BE COMMON TRIP. NO TIE HANDLES PERMITTED. , A. NFPA 70: NATIONAL ELECTRICAL CODE (2011 EDITION) 29. ALL FUSES SHALL BE CURRENT LIMITING, PER U.L., RATED 60OV., LION. S. NFPA 72: NATIONAL FIRE HARM CODE (2010 EDITION) PUMP. A. NON -TIME DELAY FUSES IN MAIN SWITCHES AND SWITCHES FEEDING PANELS. C. NFPA 99: HEALTH CARE FACILITIES 2012 EDITION) B. TIME DELAY FUSES FOR MOTOR AND A/C CIRCUITS. 0. NFPA 101: LIFE SAFETY CODE (2012 EDITION) E. NFPA 110: STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS (2010 EDITION) 30. ALL DISCONNECT SWITCHES SHALL BE SIZED BY NEC REQUIREMENTS TO ACCOMMODATE F. NFPA 780: STANDARD FOR THE INSTALLATION OF LIGHTNING PROTECTION SYSTEMS (2011 EDITION) EQUIPMENT SERVED, INCLUDING REQUIRED FUSES U.O.N. SWITCHES SHALL BE IN ADDITION, THE INSTALLATION SHALL ALSO BE IN ACCORDANCE WITH THE FOLLOWING: HORSEPOWER RATED FOR MAX. HORSEPOWER, HEAVY DUTY TYPE. G. FLORIDA BUILDING CODE 2010 31. CONTRACTOR SHALL VERIFY CIRCUIT PROTECTIVE DEVICE RATING FOR EQUIPMENT PRIOR H. THE GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES TO INSTALLATION. 2010EDITION (FLORIDA 1. FIREFIRE CODE (2010 EDITION) 32. FURNISH AND INSTALL DISCONNECT SWITCHES AND WIRING FOR AIR CONDITIONING SYSTEM AS PER MANUFACTURER RECOMMENDATIONS. CONTROLS ARE TO BE SUPPLIED 2. AS A MINIMUM, ALL EQUIPMENT SHALL MEET APPLICABLE STANDARDS, FOR THE TYPE OF BY AIR CONDITIONING CONTRACTOR AND CONNECTED. PROVIDE ALL CONTROL WIRING FOR EQUIPMENT AND INTENDED USE, OF THE FOLLOWING: A/C SENSORING AND CONTROL UNITS, COORDINATE WITH A/C CONTRACTOR FOR WIRING A. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) DIAGRAMS AND EXACT MOUNTING LOCATIONS. B. ILLUMINATING ENGINEERS SOCIETY (IES) C. AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM) 33. ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT WHERE EXPOSED TO THE WEATHER. ALL FLEX CONDUITS CONNECTED TO SUCH EQUIPMENT SHALL BE LIQUID TIGHT. D. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATES.(NEMA) E. NOTE: THESE STANDARDS ARE SUBORDINATE TO CODES AND STANDARDS SET BY U.L. 34. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND NEMA RATED FOR THE ALL ELECTRICAL EQUIPMENT, DEVICES, WIRE, ETC., SHALL BE LISTED, FOR INTENDED ENVIRONMENT IN WHICH THEY ARE TO BE INSTALLED. USE, WITH UNDERWRITER'S LABORATORIES INC. (U.L.), WHERE STANDARDS HAVE BEEN 35. ALL CONNECTIONS TO GROUND RODS SHALL BE MADE WITH U.L. APPROVED WELDED ESTABLISHED BY U.L. CONNECTIONS, UNLESS NOTED OTHERWISE. THE CONTRACTOR SHALL FORM A 3. CONTRACTOR TO PROVIDE ALL LABOR, MATERIALS AND SUPERVISION NECESSARY TO GROUNDING ELECTRODE SYSTEM AS PER NEC 250-50. ACCOMPLISH THE WORK AS SHOWN AND/OR NOTED ON THE DRAWINGS. 36• OUTLET IN DRY LOCATIONS BOXES SHALL BE PRESSED STEEL, IN WET OR DAMP 4. THE CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL CONDITIONS, LOCATIONS, LOCATIONS SHALL CAST ALLOY WEATHER -RESISTANT OUTLET WITH THREADED HUBS DIMENSIONS AND COUNTS AS SHOWN OR NOTED ON THE DRAWINGS, PRIOR TO AND IN OTHER CLASSIFIED AREAS IT SHALL BE IN A SPECIAL ENCLOSURE. PROPER SUBMITTING BIO. PLASTER RINGS SHALL BE USED WITH OUTLET BOXES. PROPER COORDINATION BETWEEN 5. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE ALL LABOR, ELECTRICAL SUBCONTRACTOR AND GENERAL CONTRACTOR FOR PLASTER RING INITIATION MATERIALS AND SUPERVISION NECESSARY TO ACCOMPLISH THE WORK AS SHOWN WILL BE REQUIRED. NO "GOOF" RINGS SHALL BE ALLOWED. ALL OUTLET BOXES SHALL AND/OR NOTED ON THE PLANS. BE SECURELY FASTENED. 6. ELECTRICAL CONTRACTOR SHALL NOT SCALE DRAWINGS. CONTRACTOR SHALL REFER TO 37. WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE RESISTIVE ASSEMBLIES, ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT LOCATIONS OF ALL EQUIPMENT (CLASSIFIED AS FIRE/SMOKE AND SMOKE PARTITIONS), THEY SHALL BE INSTALLED UNLESS NOTED OTHERWISE. WITHOUT AFFECTING THE FIRE CLASSIFICATION. ALL OF THE FOLLOWING CONDITIONS 7. IT SHALL BE UNDERSTOOD THAT ALL WORK PERFORMED SHALL BE DONE BY A LICENSED SHALL BE MET: CONTRACTOR AND IN A FIRST-CLASS WORKMANLIKE MANNER. SAID CONTRACTOR SHALL A. ALL ELECTRICAL BOXES SHALL BE METALLIC. MEET ALL REQUIREMENTS SET FORTH BY ANY LOCAL ORDINANCE AND GOVERNING B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE. AUTHORITIES. C. BOX OPENING SHALL NOT EXCEED 10322.56 SQUARE MM (16SQUARE INCHES). 8. THE CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. COMPLETELY FILLED WITH JOINT COMPOUND (OR OTHER APPROVED MATERIAL). 9. CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS E. PROVIDE A WALL AROUND OUTLETS LARGER THAT 10322.56 SQUARE MM (16 FOR A PERIOD OF NOT LESS THAN ONE YEAR FROM DATE OF ACCEPTANCE, UNLESS SQUARE INCHES). THE INTEGRITY OF THE WALL RATING SHALL BE MAINTAINED. INDICATED OR SPECIFIED OTHERWISE. F. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 64516 10. IT SHALL NOT BE THE INTENT OF THESE PLANS AND/OR SPECIFICATIONS TO SHOW SQUARE MM (100 SQUARE INCHES) PER 9.29 SQUARE METERS (100 SQUARE FEET). EVERY MINOR DETAIL OF CONSTRUCTION. THE CONTRACTOR SHALL BE EXPECTED TO G. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE RESISTIVE ASSEMBLIES SHALL FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM AND PROVIDE BE SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 609.6MM (24 INCHES). FOR ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER H. OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS. WORKING ORDER. I. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED 11. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING TO ORIGINAL CONDITIONS, 3.175MM (1/8 INCH) BETWEEN THE EDGES OF THE OUTLET BOX AND THE EDGES OF ANY AND ALL DAMAGES TO BUILDING SURFACES, EQUIPMENT, ETC. CAUSED DURING THE THE OPENING. PERFORMANCE OF WORK. 38. SMOKE DETECTORS SHALL BE PROVIDED NO CLOSER THAN 36" FROM SUPPLY AIR 12. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE OR DIFFUSERS. DELAYS AND SHALL INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 39. CONTRACTOR SHALL PROVIDE A TYPE WRITTEN DIRECTORY OF EACH PANEL.BOARD. HAND WRITTEN DIRECTORY IS NOT ACCEPTABLE, EXCEPT SPARE AND SPACES SHALL BE 13. FOR ELECTRIC POWER SYSTEM, COORDINATE POWER SERVICE WITH POWER COMPANY; HANDWRITTEN IN PENCIL. A. VERIFY LOCATION OF POWER SERVICE TERMINATION WITH POWER COMPANY, PRIOR TO SUBMITTING BIO. CONTRACTOR TO VERIFY AVAILABLE SERVICE VOLTAGE AND PHASES 40. PROVIDE A 4" STEEL REINFORCED CONCRETE HOUSEKEEPING PAD UNDER ALL FLOOR WITH POWER COMPANY PRIOR TO BID AND PROVIDE BID ALLOWANCE FOR ALTERNATES. MOUNTED ELECTRICAL EQUIPMENT. B. PROVIDE TEMPORARY ELECTRICAL SERVICE FOR USE BY ALL TRADES DURING 41. A. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH CONSTRUCTION AND REMOVE SAME AT COMPLETION OF PROJECT, NEC 110.26 14. CONTRACTOR SHALL KEEP ALL AREAS IN WHICH WORK IS BEING PERFORMED, FREE B. THE EXCLUSIVELY DEDICATED SPACE EXTENDING FROM FLOOR TO STRUCTURAL FROM DEBRIS AT ALL TIMES AND SAID AREAS SHALL BE LEFT BROOM CLEAN AT THE CEILING WITH A WIDTH AND DEPTH OF THE PANELBOAROOR SWITCHBOARD MUST BE END OF EACH WORKING DAY. CLEAR OF ALL PIPING, DUCTS, EQUIPMENT FOREIGN TO THE ELECTRICAL EQUIPMENT OR 15. CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES, INSPECTIONS, AND TESTING COSTS. ARCHITECTURAL APPURTENANCES IN ACCORDANCE WITH NEC 408. 16. COORDINATE ALL ELECTRICAL SITE WORK WITH ALL OTHER TRADES CONTRACTORS. 42. METER CANS, HUBS, & LUGS FOR SAME ARE TO BE FURNISHED & INSTALLED BY CONTRACTOR. CONTRACTOR TO VERIFY SPECIFIC TYPE OF METER CAN TO BE USED 17. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR FOR THE ADVANCE WITH F.P.L. PRIOR TO BID. ORDERING OF LONG LEAD ITEMS, AS TO NOT INTERFERE WITH THE PRODUCTION OF OTHER TRADES RESULTING IN ANY DOWN OR LAG TIME. THE CONTRACTOR SHALL NOT 43. A. PROVIDE A PERMANENT SIGN ON THE MAIN ELECTRICAL ROOM DOOR TO THE BLDG. ORDER ANY ITEMS UNTIL APPROVED SHOP DRAWINGS ARE RETURNED TO HIM. STATING THAT THE SERVICE DISCONNECTS ARE LOCATED INSIDE. 18. ELECTRICAL CONTRACTOR SHALL SUBMIT (6 COPIES) EQUIPMENT LAYOUT OF ALL B. SIGNS SHALL BE PLACED AT THE MAIN DISCONNECT EQUIPMENT INDICATING TYPE AND ELECTRICAL SPACES, ROOMS, ETC., TO ENGINEER FOR APPROVAL PRIOR TO ORDERING LOCATION OF ON-SITE EMERGENCY POWER SOURCES. EQUIPMENT OR INSTALLING CONDUITS, ETC. LAYOUT SHALL CONSIST OF PLAN VIEWS 44. THE EQUIPMENT, GROUNDING TERMINAL BARS OF THE NORMAL AND EMERGENCY (SCALED AS REQUIRED) AND ELEVATIONS (DIMENSIONED) FOR EACH SUCH SPACE, ELECTRICAL SYSTEM PANEL.BOARDS SERVING THE SAME BUILDING SHALL BE BONDED ROOM, ETC. TOGETHER WITH AN INSULATED, CONTINUOUS, COPPER CONDUCTOR NOT SMALLER THAN 19. CONTRACTOR SHALL SUBMIT AT ONE TIME, SIX (6) SETS OF LOOSE-LEAF BOUND NUMBER 6. BOOKS, INDEXED WITH ALL PRODUCTS, MATERIALS, LIGHTING FIXTURES, LAMPS, WIRING 45. THE ELECTRICAL CONTRACTOR SHALL FURNISH A COMPLETE SET OF AS -BUILT DEVICES, SWITCHGEAR, ETC. CLEARLY HIGHLIGHTING ALL EQUIPMENT QUANTITIES AND DRAWINGS, SHOWING ALL CHANGES AND DEVIATIONS TO THE ARCHITECT/ENGINEER PRIOR DETAILS. ALL EQUIPMENT SHALL BE AS SPECIFIED ON PLANS: THE RESPONSIBILITY TO TO COMPLETION OF THE PROJECT. ACCEPT OR REJECT ANY PROPOSED SUBSTITUTION REMAINS WITH THE PROJECT ENGINEER. THE CONTRACTOR MAY AT HIS JUDGMENT USE ANY ARTICLE, DEVICE, 46. ARCHITECTURAL AND/OR ENGINEERING EXPENSES THAT ARE INCURRED DUE TO PRODUCT, OR MATERIAL WHICH IN THE JUDGMENT OF THE ENGINEER EXPRESSED IN REVISIONS OR SUBSTITUTIONS REQUESTED BY THE CONTRACTOR SHALL BE PAID FOR BY WRITING ARE EQUAL TO THAT SPECIFIED. THAT CONTRACTOR. 20. ALL CONDUCTORS SHALL BE COPPER, TYPE THHN/THWN EXCEPT WHERE OTHERWISE 47. FOR TELEPHONE SYSTEMS: REQUIRED BY U.L. OR CODES. MINIMUM WIRE SIZE SHALL BE #12 AWG, EXCLUDING A. PROVIDE GROUNDING FOR ALL TELEPHONE OUTLETS AND EQUIPMENT PER CONTROL WIRING. ALUMINUM CONDUCTORS ARE NOT PERMITTED. REQUIREMENTS OF THE TELEPHONE COMPANY. B. COORDINATE INSTALLATION OF ALL TELEPHONE OUTLETS, RACEWAYS, ENCLOSURES 21. ALL CONDUCTORS SHALL BE IN CONDUITS. ALL CONDUITS SHALL BE GALVANIZED RIGID AND BACKBOARDS WITH TELE. CO. STEEL (GRS) EXCEPT THAT: (a) PVC CONDUITS MAY BE USED UNDERGROUND PROVIDED C. VERIFY LOCATION OF TELEPHONE SERVICE WITH TELEPHONE COMPANY. PROVIDE ELBOWS AND RISERS ARE GALVANIZED RIGID STEEL OR SCHEDULE 80 PVC, WHERE SERVICE CONDUIT TO BLDG. FROM SERVICE POINT PER TELCO. INSTRUCTIONS, INCLUDE SUBJECT TO PHYSICAL DAMAGE (b) ELECTRICAL METALLIC TUBING (EMT) MAY BE USED ALL ASSOCIATED COSTS IN BID. IN OR ON WALLS OR CEILINGS WHERE NOT SUBJECT TO MECHANICAL DAMAGE, DAMP OR D. MARK TERMINATIONS OF TELEPHONE CONDUIT AS DIRECTED BY THE TELEPHONE CORROSIVE CONDITIONS, (c) LIQUID TIGHT FLEXIBLE CONDUIT WHERE REQUIRED, (d) COMPANY. FLEXIBLE METALLIC CONDUIT WHERE REQUIRED IN DRY LOCATIONS ONLY, (e) MC CABLE E. VERIFY LOCATION OF TELEPHONE SERVICE WITH TELEPHONE COMPANY PRIOR TO WITH DEDICATED GREEN GROUNDING CONDUCTOR WHERE PERMITTED. ALL CONDUITS IN SUBMITTING BID, INCLUDE ALL ASSOCIATED COSTS IN BID. HAZARDOUS AREAS (PER NEC) SHALL MEET THE REQUIREMENTS OF NEC CHAPTER 5. F. USE EXTERIOR GRADE 3/4" PLYWOOD BACKBOARDS FOR MOUNTING TELEPHONE EQUIPMENT AND TERMINAL STRIPS. PAINT BOARD ON ALL SIDES AND EDGES WITH TWO 22. FOR UNDERGROUND ELECTRICAL CONDUITS, PROVIDE PULL BOXES, SUCH THAT NO COATS OF FLAT BLACK FIRE RETARDANT PAINT. SINGLE CONDUIT RUN HAS BENDS IN EXCESS OF 360. PULL BOXES SHALL BE SUITABLE AND APPROVED FOR THE INTENDED USE. WARNING TAPE WHICH SAYS 48. INDUSTRIAL CONTROL TYPE TRANSFORMERS SHALL BE PROVIDED WITH FINGERSAFE "WARNING BURIED ELECTRIC" SHALL BE PLACED IN TRENCHES ABOVE ALL UNDERGROUND COVERS AND PRIMARY FUSE PROTECTION AS REQUIRED PER NEC 450-3. MOUNT ELECTRIC CONDUITS. WHERE CONDUITS PASS UNDERNEATH PAVED AREAS, THEY SHALL TRANSFORMERS ON 4"X4" JUNCTION BOX ABOVE ACCESSIBLE CEILINGS OR ELECTRICAL BE PVC. WHERE UNDERGROUND CONDUITS ARE NOT EXPOSED TO MECHANICAL DAMAGE ROOMS. OR ARE NOT UNDER PAVED AREAS, THEY SHALL BE SCHEDULE 40 PVC. 49. FOR RESIDENTIAL WORK PROVIDE COMBINATION TYPE ARC -FAULT CIRCUIT INTERRUPTER 23. ALL CONDUIT RUNS ARE SHOWN DIAGRAMMATIC. EXACT ROUTING SHALL BE DETERMINED PROTECTION THROUGHOUT THE DWELLING UNIT, EXCEPT IN KITCHEN BATHROOM, GARAGES IN THE FIELD, UNLESS OTHERWISE NOTED. AND OUTDOORS. ALL DWELLING UNIT RECEPTACLE OUTLETS MUST BE LISTED 24. WIREWAYS SHALL BE SIZED AS REQUIRED, PER NEC, UNLESS OTHERWISE NOTED (LION). TAMPER-RESISTANT. 25. WHERE CORE DRILLING OF FLOOR/WALLS IS REQUIRED, CONTRACTOR SHALL SEAL 50. PROVIDE U.L. LISTED COMPOUND APPLIED TO BACK OF "BACK TO BACK" BOXES IN OPENINGS WATERTIGHT AFTER UTILITIES HAVE BEEN INSTALLED. LOCATION OF CORED RATED WALLS WHERE THE BOXES ARE LESS THAN 609.6MM (24 INCHES) APART HOLES SHALL COORDINATE WITH LOCATION OF EQUIPMENT IN A MANNER TO BE CLEAN MEASURED HORIZONTALLY. AND FUNCTIONAL. THE CONTRACTOR SHALL INSTALL ONLY ONE CONDUIT PER HOLE AND 51. CONTRACTOR SHALL PROVIDE TYPED -WRITTEN, UPDATED PANEL DIRECTORIES ON ALL SEAL THE OPENING AROUND THE CONDUIT AS SPECIFIED. PANELS THAT ARE AFFECTED AT THE COMPLETION OF THE JOB. 26. PROVIDE FIRE RETARDANT U.L. APPROVED SEALANT ON ALL PENETRATIONS OF FIRE RATED PARTITIONS, WALLS AND STRUCTURAL SLABS. CONTRACTOR TO VERIFY, PRIOR TO 52. FOR RECEPTACLES IN DAMP AND WET LOCATIONS THE CONTRACTOR SHALL PROVIDE ALL SUBMITTING BID, LOCATIONS OF ALL SUCH FIRE RATED PARTITIONS, WALL AND 125V. AND 250V., 15A. AND 20A. RECEPTACLES THAT ARE LISTED AS WEATHER STRUCTURAL SLABS. RESISTANT TYPE TO COMPLY WITH NEC ARTICLE 406.8. 27. UNLESS NOTED AS EXISTING, ALL EQUIPMENT, WIRING, DEVICES, ETC. SHALL BE NEW. ALL ELECTRICAL WORK SHALL COMPLY WITH THE 2011 NATIONAL ELECTRICAL CODE. THIS APPROVAL OF THE PLANS SHALL NOT PREVENT THE FIELD INSPECTOR FROM REQUIRING THE CORRECTIONS OF ERRORS ON SUCH PLANS WHEN IN VIOLATION OF THE FBC OR NEC IN EFFECT. GI FAULT CURRENT CULCULATIONS AT TRANSFORMER TRASNOFRIVER KVA: 150KVA VOLTAGE EL -L: 480V, 30 IMPEDANCE Z 3.57a Ifl TRANSFORMER FULL LOAD AMPERS m MULTIPLIER IS.C. TRANSFORMER LET -THROUGH SHORT-CIRCUIT CURRENT 1 KVAx1000 = 1500000 = 236.7 EL -Lx 1.732 4800.732 m =-I 00 = 100 = 28.6 Z 3.5 IS.C- if.,. x m = 236.7x28.6 = 6,771 AMPS SHOP DRAWING REQUIREMENTS 1. CONTRACTOR SHALL SUBMIT 6 COPIES OF COMPLETED SHOP DRAWINGS, TOGETHER AT ONE TIME AND MUST COME THROUGH THE ARCHITECT. ALL SUBMITTALS SHALL BE MADE WITHIN 30 DAYS OF NOTICE TO PROCEED. 2. ALL SUBMITTALS MUST CLEARLY INDICATE EXACTLY WHICH ITEMS ARE BEING PROPOSED FOR USE. IF NOT, THE SUBMITTAL SHALL BE REJECTED. 3. SUBSTITUTIONS SHALL BE LIMITED TO ONE OF THE ALTERNATES LISTED IN THE CONSTRUCTION DOCUMENTS. PRODUCTS CONSIDERED TO BE EQUAL SHALL BE REVIEWED AND ACCEPTED BY THE ENGINEER, ARCHITECT AND OWNER (10) DAYS PRIOR TO BIO DATE. 4. THE CONTRACTOR ASSUMES ALL DESIGN RESPONSIBILITY AND ALL FINANCIAL RISKS FOR PROCEEDING PRIOR TO SHOP DRAWINGS PROCESSING, AND ON ANY ITEM OR WORK THAT IS AT VARIANCE TO THE CONSTRUCTION DOCUMENTS. 5. SHOP DRAWINGS AND SUBMITTALS FOR EACH ITEM SHALL BE REVIEWED NO MORE THAN TWICE. A THIRD SUBMITTAL ON AN ITEM MUST BE ACCOMPANIED BY A PURCHASE ORDER FROM THE CONTRACTOR OR IT SHALL BE REJECTED. 6. CIRCUMSTANCES NECESSITATING A REVISION TO THE PERMITTED DOCUMENTS NOT PROCESSED PRIOR TO INSTALLATION MAY NOT BE ACCEPTED. IF ACCEPTED IT MUST BE LEGIBLE, ACCURATE AND ACCOMPANIED BY A PURCHASE ORDER ORDER FROM THE CONTRACTOR. THE REVISION SHALL BE CHARGED TO THE CONTRACTOR AND DELIVERED TO HIM ON A C.O.D. BASIS. 7. SUBSTITUTIONS FROM THE BASE DESIGN OR VARIATIONS TO THE PERMITTED CONTRACT DOCUMENTS, WHETHER RESULTING FROM PROCESSED SHOP DRAWINGS OR NOT, THAT RESULT IN REQUIREMENTS IN LETTERS OF AUTHORIZATION AND/OR PERMIT CONTRACT DOCUMENT CHANGES MANDATED BY THE AUTHORITY HAVING JURISDICTION WILL NOT BE MADE BY THIS OFFICE UNLESS ACCOMPANIED BY A PURCHASE ORDER FROM THE CONTRACTOR, AND RELEASED ON A C.O.D. BASIS. 8. CONTRACTOR SHALL SUBMIT 5 COPIES OF EQUIPMENT LAYOUTS OF ALL ELECTRICAL SPACES, ROOMS, ETC. TO THE ENGINEER FOR APPROVAL PRIOR TO ORDERING EQUIPMENT OR INSTALLING CONDUITS, ETC. THE LAYOUTS SHALL CONSIST OF PLAN VIEWS AT A SCALE OF 1/2" = 1'0" AND ELEVATIONS FOR EACH SUCH SPACE OR ROOM, ETC. EXISTING BRANCH~ - ORANIIN CIRCUIT WITH 2" i XISTING BRANCH 1!4� EXISTING BRANCH PVC, (4)#3/0, (1)#� DATE: CIRCUIT WITH 3" ' CIRCUIT WITH 1X2" GREEN TO E2.0 ELECTRICAL BILL & SCHEDULES i PVC, (3)#4/0, (2)#3 RIGID, 3 3 (1)#6 O# PRODUCTION ROOM. � , � TO REFRIGERATION GREEN TO VACUUM i COMPRESSOR RACK. i PUMP. r , EXISTING FPL OVERHEAD LINES r REMOVE 277/480V 200 A X400 A PIAN 400 A. 3 -PH. METER DISC. i IIDISC.°II 1`!„„°II SWITCH. i I ISWITCH II IIWITH 11 I 1 11400 A.I I IIMCB. III EXIST. LJ-� / ' 75 KVALL FLEX. -2 48g/240 3" PVC. EMOVE 3" PVC. �• R RR R RSR R RR R •I•_____ __ F - - EX. 1X2" PVC.W/3#2 Z GRADE n n n n n n FPL PULLBOX, PROVIDED BY FPL INSTALLED BY CONTRACTOR. COORDINATE WITH FPL. REMOVE (2) 2" PVC TO FP&L POWER POLE 2 EXISTING POWER RISER DIAGRAM E1.0 N.T.S. max- EXISTING EQUIPMENT TO BE REMOVED - - - - EXISTING EQUIPMENT TO REMAIN NEW EQUIPMENT COORDINATE ALL WORK WITH FPL REPRESENTATIVE LOCATION OF ELECTRICAL t AND UTILITY POWER RISEF THIS SHEET. EX ST G BAN H CIRCUIT WITH 1X2" 3 RIGID, (3)#3, (1)#8 GRD TO COMPRESSOR 2 4 AD E 1 2 1 EXISTING BRANCH EXISTING BRANCH CIRCUIT WITH 1X2" CIRCUIT WITH 3" EXISTING FPL RIGID, (3)#3, (1)#6 PVC, (3)#300 MCM OVERHEAD LINES GREEN TO VACUUM i (1)#4/0 N.,(1)# 4 ' PUMP. G. TO l ; REFRIGERATION OMPRESSOR RAC � l EXISTING BRANCH r n CIRCUIT WITH 2" i PVC, (4)#3/0, (1)#6 GROUND TO PRODUCTION ROOM:j1 PANEL.EXIST. i i 1X4 X400 A� ® I M I 2I�PoANEL'II (DISC. 00 A. ° I) N W LITH I I (SWITCH II 800 MP ETE Is I D400 ISCO 1 11400 A11 I 13 225 277/ OV,3 o III IF 1� IIMCB. �,I-L 11 0- 1 II 1 ' I I CB's ROTED L JI I 100K. I I L -----I 65KAI I II 1 LT _j EXIST I� °C(I A.I.C.° ( FPL PULLBOX, PROVIDED I II ' 75 KVA I BY FPL INSTALLED BY I II 3-3/0-2" 480 2_40 3X" PVC W 4 CONTRACTOR. I FLEX. i 1- 500 MCM-CU 4COORDINATE WITH FPL. I II I 1'X1'X8' GUTTER 3R NEW 2 SETS (2) 3X2 PVC W/4-500 w I I) M S P L IST S. MCM-CU EA. U/GROUND -- ' TO CT'S. (I GRADE ❑❑ X. 1X2" PVC.W/3#2 USE D AND ELECTRODE SYSTEM AND TO BUILDING Zj� STEEL. M10NEW POWER RISER DIAGRAM UPGRADE TO 800AMP. N.T.S. - - - - EXISTING EQUIPMENT TO REMAIN NEW EQUIPMENT COORDINATE ALL WORK WITH FPL REPRESENTATIVE mmi N MSITE LOCATION PLAN E1.0 N.T.S. ELECTRICAL INDEX 1606XX ORANIIN x DESIGNED BY: GSJ 1 E1.0 ELECTRICAL INDEX, NOTES, RISERS & SITE PLAN DATE: 06/08/2016 2 E2.0 ELECTRICAL BILL & SCHEDULES 3 E - SCOPE OF WORK FOR THIS PROJECT CONTRACTOR SHALL PERFORM ALL WORK AS SHOWN ON THE POWER RISERS. THE EXISTING MAXIMUM LOAD ON THE SYSTEM HAS RECENTLY EXCEEDED 400AMPS. AND THE SERVICE CONDUCTORS HAVE BEEN GETTING VERY HOT, THEREFORE THE SCOPE OF WORK IS TO REPLACE THE EXISTING 40OAMP. SERVICE WITH A NEW 80OAMP. SERVICE AS SHOWN. Copyright 2011 Material shown here is the Copyrighted Property of Delta G Consulting Engineers, Inc. and shall not be reproduced in whole or in part without express written permission. DELTA G CONSULTING ENGINEERS, INC. THE ENGINEERING SPECIALISTS Delta G Consulting Engineers, Inc. 707 N.E. 3rd Ave. Suite 200 Fort Lauderdale, FL 33304 (954) 527-1112 Tel. (954) 524-7505 Fax www.Del.taG.net REVISIONS: RTC 6-27-16 QRTC 7-12-16 QRTC 8-8-16 QAS-BUILTS 8-25-16 PROJECT #: 1606XX PROJECT MANAGER: GSJ DESIGNED BY: GSJ C.A.#: 00009181 DATE: 06/08/2016 (ZWI=L=T Kin E1.0 GENERAL ELECTRICAL NOTES (GENERAL NOTES ARE PROVIDED AS A BASIC DESCRIPTION OF THE EXTENT AND QUALITY EXPECTED IN THIS PROJECT. IF A CONFLICT EXISTS BETWEEN THESE GENERAL NOTES AND THE REMAINDER OF THE CONTRACT DOCUMENTS THE SPECIFICATIONS, PLANS AND DETAILS WILL GOVERN.) 1. THE ENTIRE INSTALLATION SHALL BE IN ACCORDANCE WITH THE FOLLOWING CODES AND STANDARDS: 28 ALL CIRCUIT BREAKERS SHALL BE INVERSE TIME TYPE (THERMAL MAGNETIC OR SOLID DESIGNED BY: FLORIDA STATE FIRE MARSHALL'S RULE 69A-3.012 FAC AND RULE CHAPTER 69A-60 FLORIDA ADMINISTRATIVE CODE (FAC) AND C.A.#: STATE AS REQUIRED BY SPECIFICATION LE CIRCUIT BREAKERS ) . TWO AND THREE PO DATE: FLORIDA STATUTE SECTION 633.022. EXISTING FPL SHALL BE COMMON TRIP. NO TIE HANDLES PERMITTED. EXISTING BRANCH , A NEPA 70: NATIONAL ELECTRICAL CODE (2011 EDITION) 29. ALL FUSES SHALL BE CURRENT LIMITING, PER U.L., RATED 60OV., UON. OVERHEAD LINES S. NFPA 72: NATIONAL FIRE ALARM CODE (2010 EDITION) CIRCUIT WITH 2" ;XtSTING A. NON -TIME DELAY FUSES IN MAIN SWITCHES AND SWITCHES FEEDING PANELS. BRANCH C. NFPA 99: HEALTH CARE FACILITIES (2012 EDITION) EXISTING BRANCH B. TIME DELAY FUSES FOR MOTOR AND A/C CIRCUITS. PVC, (4)#3/0, (1)#6 ' GREEN TO 0. NFPA 101: LIFE SAFETY CODE (2012 EDITION) CIRCUIT WITH 3" PVC, (3)#4/0, (2)#3 ' ' CIRCUIT WITH 1X2" RIGID, (3)#3, (1)#6 E. NFPA 110: STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS (2010 EDITION) 30. ALL DISCONNECT SWITCHES SHALL BE SIZED BY NEC REQUIREMENTS TO ACCOMMODATE F. NFPA 780: STANDARD FOR THE INSTALLATION OF LIGHTNING PROTECTION SYSTEMS (2011 EDITION) EQUIPMENT SERVED, INCLUDING REQUIRED FUSES U.O.N. SWITCHES SHALL BE IN ADDITION, THE INSTALLATION SWILL ALSO BE IN ACCORDANCE WITH THE FOLLOWING: TO REFRIGERATION HORSEPOWER RATED FOR MAX. HORSEPOWER, HEAVY DUTY TYPE. GREEN TO VACUUM G. FLORIDA BUILDING CODE 2010 31. CONTRACTOR SHALL VERIFY CIRCUIT PROTECTIVE DEVICE RATING FOR EQUIPMENT PRIOR COMPRESSOR RACK. H. THE GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES PUMP. TO INSTALLATION. 200 A. i (FGA GUIDELINES, 2ENT EDITION) I. FLORIDA FIRE PREVENTION CODE (2010 EDITION) 32. FURNISH AND INSTALL DISCONNECT SWITCHES AND WIRING FOR AIR CONDITIONING f SYSTEM AS PER MANUFACTURER RECOMMENDATIONS. CONTROLS ARE TO BE SUPPLIED 2. AS A MINIMUM, ALL EQUIPMENT SHALL MEET APPLICABLE STANDARDS, FOR THE TYPE OF BY AIR CONDITIONING CONTRACTOR AND CONNECTED. PROVIDE ALL CONTROL WIRING FOR EQUIPMENT AND INTENDED USE, OF THE FOLLOWING: A/C SENSORING AND CONTROL UNITS, COORDINATE WITH A/C CONTRACTOR FOR WIRING A. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) DIAGRAMS AND EXACT MOUNTING LOCATIONS. B. ILLUMINATING ENGINEERS SOCIETY (IES) 33. ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT WHERE EXPOSED TO THE WEATHER. C. AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM) ALL FLEX CONDUITS CONNECTED TO SUCH EQUIPMENT SHALL BE LIQUID TIGHT. D. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATES.(NEMA) E. NOTE: THESE STANDARDS ARE SUBORDINATE TO CODES AND STANDARDS SET BY U.L. 34. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND NEMA RATED FOR THE ALL ELECTRICAL EQUIPMENT, DEVICES, WIRE, ETC., SHALL BE LISTED, FOR INTENDED ENVIRONMENT IN WHICH THEY ARE TO BE INSTALLED. USE, WITH UNDERWRITER'S LABORATORIES INC. (U.L.), WHERE STANDARDS HAVE BEEN 35. ALL CONNECTIONS TO GROUND RODS SHALL BE MADE WITH U.L. APPROVED WELDED ESTABLISHED BY U.L. CONNECTIONS, UNLESS NOTED OTHERWISE. THE CONTRACTOR SHALL FORM A 3. CONTRACTOR TO PROVIDE ALL LABOR, MATERIALS AND SUPERVISION NECESSARY TO GROUNDING ELECTRODE SYSTEM AS PER NEC 250-50. ACCOMPLISH THE WORK AS SHOWN AND/OR NOTED ON THE DRAWINGS. 36 OUTLET IN DRY LOCATIONS BOXES SHALL BE PRESSED STEEL, IN WET OR DAMP 4. THE CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL CONDITIONS, LOCATIONS, LOCATIONS SHALL BE CAST ALLOY WEATHER -RESISTANT OUTLET WITH THREADED HUBS DIMENSIONS AND COUNTS AS SHOWN OR NOTED ON THE DRAWINGS, PRIOR TO AND IN OTHER CLASSIFIED AREAS IT SHALL BE IN A SPECIAL ENCLOSURE. PROPER SUBMITTING BID. PLASTER RINGS SHALL BE USED WITH OUTLET BOXES. PROPER COORDINATION BETWEEN 5. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE ALL LABOR, ELECTRICAL SUBCONTRACTOR AND GENERAL CONTRACTOR FOR PLASTER RING INITIATION MATERIALS AND SUPERVISION NECESSARY TO ACCOMPLISH THE WORK AS SHOWN WILL BE REQUIRED. NO "GOOF" RINGS SHALL BE ALLOWED. ALL OUTLET BOXES SHALL AND/OR NOTED ON THE PLANS. BE SECURELY FASTENED. 6. ELECTRICAL CONTRACTOR SHALL NOT SCALE DRAWINGS. CONTRACTOR SHALL REFER TO 37. WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE RESISTIVE ASSEMBLIES, ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT LOCATIONS OF ALL EQUIPMENT (CLASSIFIED AS FIRE/SMOKE AND SMOKE PARTITIONS), THEY SHALL BE INSTALLED UNLESS NOTED OTHERWISE. WITHOUT AFFECTING THE FIRE CLASSIFICATION. ALL OF THE FOLLOWING CONDITIONS 7. IT SHALL BE UNDERSTOOD THAT ALL WORK PERFORMED SHALL BE DONE BY A LICENSED SHALL BE MET - CONTRACTOR AND IN A FIRST-CLASS WORKMANLIKE MANNER. SAID CONTRACTOR SHALL A. ALL ELECTRICAL BOXES SHALL BE METALLIC. MEET ALL REQUIREMENTS SET FORTH BY ANY LOCAL ORDINANCE AND GOVERNING B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE. AUTHORITIES. C. BOX OPENING SHALL NOT EXCEED 10322.56 SQUARE MM (16SQUARE INCHES). 8. THE CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. COMPLETELY FILLED WITH JOINT COMPOUND (OR OTHER APPROVED MATERIAL). 9. CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS E. PROVIDE A WALL AROUND OUTLETS LARGER THAT 10322.56 SQUARE MM (16 FOR A PERIOD OF NOT LESS THAN ONE YEAR FROM DATE OF ACCEPTANCE,UNLESS SQUARE INCHES). THE INTEGRITY OF THE WALL RATING SHALL BE MAINTAINED. INDICATED OR SPECIFIED OTHERWISE. F. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 64516 10. IT SHALL NOT BE THE INTENT OF THESE PLANS AND/OR SPECIFICATIONS TO SHOW SQUARE MM (100 SQUARE INCHES) PER 9.29 SQUARE METERS (100 SQUARE FEET). EVERY MINOR DETAIL OF CONSTRUCTION. THE CONTRACTOR SHALL BE EXPECTED TO G. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE RESISTIVE ASSEMBLIES SHALL FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM AND PROVIDE BE SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 609.61MM (24 INCHES). FOR ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER H. OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS. WORKING ORDER. I. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED 11. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING TO ORIGINAL CONDITIONS, 3.175MM (1/8 INCH) BETWEEN THE EDGES OF THE OUTLET BOX AND THE EDGES OF ANY AND ALL DAMAGES TO BUILDING SURFACES, EQUIPMENT, ETC. CAUSED DURING THE THE OPENING. PERFORMANCE OF WORK. 38. SMOKE DETECTORS SHALL BE PROVIDED NO CLOSER THAN 36" FROM SUPPLY AIR 12. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE OR DIFFUSERS. DELAYS AND SHALL INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 39. CONTRACTOR SHALL PROVIDE A TYPE WRITTEN DIRECTORY OF EACH PANELBOARD. HAND WRITTEN DIRECTORY IS NOT ACCEPTABLE, EXCEPT SPARE AND SPACES SHALL BE 13. FOR ELECTRIC POWER SYSTEM, COORDINATE POWER SERVICE WITH POWER COMPANY; HANDWRITTEN IN PENCIL. A. VERIFY LOCATION OF POWER SERVICE TERMINATION WITH POWER COMPANY, PRIOR TO SUBMITTING BID. CONTRACTOR TO VERIFY AVAILABLE SERVICE VOLTAGE AND PHASES 40• PROVIDE A 4" STEEL REINFORCED CONCRETE HOUSEKEEPING PAD UNDER ALL FLOOR WITH POWER COMPANY PRIOR TO BID AND PROVIDE BID ALLOWANCE FOR ALTERNATES. MOUNTED ELECTRICAL EQUIPMENT. B. PROVIDE TEMPORARY ELECTRICAL SERVICE FOR USE BY ALL TRADES DURING 41. A. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH CONSTRUCTION AND REMOVE SAME AT COMPLETION OF PROJECT, NEC 110.26 14. CONTRACTOR SHALL KEEP ALL AREAS IN WHICH WORK IS BEING PERFORMED, FREE B. THE EXCLUSIVELY DEDICATED SPACE EXTENDING FROM FLOOR TO STRUCTURAL FROM DEBRIS AT ALL TIMES AND SAID AREAS SHALL BE LEFT BROOM CLEAN AT THE CEILING WITH A WIDTH AND DEPTH OF THE PANELBOARDOR SWITCHBOARD MUST BE END OF EACH WORKING DAY. CLEAR OF ALL PIPING, DUCTS, EQUIPMENT FOREIGN TO THE ELECTRICAL EQUIPMENT OR 15. CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES, INSPECTIONS, AND TESTING COSTS. ARCHITECTURAL APPURTENANCES IN ACCORDANCE WITH NEC 408. 16. COORDINATE ALL ELECTRICAL SITE WORK WITH ALL OTHER TRADES CONTRACTORS. 42. METER CANS, HUBS, & LUGS FOR SAME ARE TO BE FURNISHED & INSTALLED BY CONTRACTOR. CONTRACTOR TO VERIFY SPECIFIC TYPE OF METER CAN TO BE USED 17. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR FOR THE ADVANCE WITH F.P.L. PRIOR TO BID. ORDERING OF LONG LEAD ITEMS, AS TO NOT INTERFERE WITH THE PRODUCTION OF OTHER TRADES RESULTING IN ANY DOWN OR LAG TIME. THE CONTRACTOR SHALL NOT 43. A. PROVIDE A PERMANENT SIGN ON THE MAIN ELECTRICAL ROOM DOOR TO THE BLDG. ORDER ANY ITEMS UNTIL APPROVED SHOP DRAWINGS ARE RETURNED TO HIM. STATING THAT THE SERVICE DISCONNECTS ARE LOCATED INSIDE. 18. ELECTRICAL CONTRACTOR SHALL SUBMIT (6 COPIES) EQUIPMENT LAYOUT OF ALL B. SIGNS SHALL BE PLACED AT THE MAIN DISCONNECT EQUIPMENT INDICATING TYPE AND ELECTRICAL SPACES, ROOMS, ETC., TO ENGINEER FOR APPROVAL PRIOR TO ORDERING LOCATION OF ON-SITE EMERGENCY POWER SOURCES. SHALL CONSIST 017 PLAN -,VIEWS; OR INSTALLING CONDUITS, ETC. LAYOUT44. _ EMERGENCY - THE EQUIPMENT GROUNDING TERMINAL: -BARS OF THE NORMAL AND EMERGENCY (SCALED AS REQUIRED) AND ELEVATIONS (DIMENSIONED) FOR EACH SUCH SPACE, (SCALED ELECTRICAL SYSTEM PANELBOARDS SERVING THE SAME BUILDING SHALL BE BONDED ROOM, ETC. TOGETHER WITH AN INSULATED, CONTINUOUS, COPPER CONDUCTOR NOT SMALLER THAN 19. CONTRACTOR SHALL SUBMIT AT ONE TIME, SIX (6) SETS OF LOOSE-LEAF BOUND NUMBER 6. BOOKS, INDEXED WITH ALL PRODUCTS, MATERIALS, LIGHTING FIXTURES, LAMPS, WIRING 45. THE ELECTRICAL CONTRACTOR SHALL FURNISH A COMPLETE SET OF AS -BUILT DEVICES, SWITCHGEAR, ETC. CLEARLY HIGHLIGHTING ALL EQUIPMENT QUANTITIES AND DRAWINGS, SHOWING ALL CHANGES AND DEVIATIONS TO THE ARCHITECT/ENGINEER PRIOR DETAILS. ALL EQUIPMENT SHALL BE AS SPECIFIED ON PLANS: THE RESPONSIBILITY TO TO COMPLETION OF THE PROJECT. ACCEPT OR REJECT ANY PROPOSED SUBSTITUTION REMAINS WITH THE PROJECT ENGINEER. THE CONTRACTOR MAY AT HIS JUDGMENT USE ANY ARTICLE, DEVICE, 46. ARCHITECTURAL ANO/OR ENGINEERING EXPENSES THAT ARE INCURRED DUE TO PRODUCT, OR MATERIAL WHICH IN THE JUDGMENT OF THE ENGINEER EXPRESSED IN REVISIONS OR SUBSTITUTIONS REQUESTED BY THE CONTRACTOR SHALL BE PAID FOR BY WRITING ARE EQUAL TO THAT SPECIFIED. THAT CONTRACTOR. 20. ALL CONDUCTORS SHALL BE COPPER, TYPE THHN/THWN EXCEPT WHERE OTHERWISE 47. FOR TELEPHONE SYSTEMS: REQUIRED BY U.L. OR CODES. MINIMUM WIRE SIZE SHALL BE #12 AWG, EXCLUDING A. PROVIDE GROUNDING FOR ALL TEIEPHONE OUTLETS AND EQUIPMENT PER CONTROL WIRING. ALUMINUM CONDUCTORS ARE NOT PERMITTED. REQUIREMENTS OF THE TELEPHONE COMPANY. B. COORDINATE INSTALLATION OF ALL TELEPHONE OUTLETS, RACEWAYS, ENCLOSURES 21. ALL CONDUCTORS SHALL BE IN CONDUITS. ALL CONDUITS SHALL BE GALVANIZED RIGID AND BACKBOARDS WITH TELE. CO. STEEL (GRS) EXCEPT THAT: (a) PVC CONDUITS MAY BE USED UNDERGROUND PROVIDED C. VERIFY LOCATION OF TELEPHONE SERVICE WITH TELEPHONE COMPANY. PROVIDE ELBOWS AND RISERS ARE GALVANIZED RIGID STEEL OR SCHEDULE 80 PVC, WHERE SERVICE CONDUIT TO BLDG. FROM SERVICE POINT PER TELCO. INSTRUCTIONS, INCLUDE SUBJECT TO PHYSICAL DAMAGE (b) ELECTRICAL METALLIC TUBING (EMT) MAY BE USED ALL ASSOCIATED COSTS IN BID. IN OR ON WALLS OR CEILINGS WHERE NOT SUBJECT TO MECHANICAL DAMAGE, DAMP OR D. MARK TERMINATIONS OF TELEPHONE CONDUIT AS DIRECTED BY THE TELEPHONE CORROSIVE CONDITIONS, (C) LIQUID TIGHT FLEXIBLE CONDUIT WHERE REQUIRED, (d) COMPANY. FLEXIBLE METALLIC CONDUIT WHERE REQUIRED IN DRY LOCATIONS ONLY, (e) MC CABLE E. VERIFY LOCATION OF TELEPHONE SERVICE WITH TELEPHONE COMPANY PRIOR TO WITH DEDICATED GREEN GROUNDING CONDUCTOR WHERE PERMITTED. ALL CONDUITS IN SUBMITTING BID, INCLUDE ALL ASSOCIATED COSTS IN BID. HAZARDOUS AREAS (PER NEC) SHALL MEET THE REQUIREMENTS OF NEC CHAPTER 5. F. USE EXTERIOR GRADE 3/4" PLYWOOD BACKBOARDS FOR MOUNTING TELEPHONE EQUIPMENT AND TERMINAL STRIPS. PAINT BOARD ON ALL SIDES AND EDGES WITH TWO 22. FOR UNDERGROUND ELECTRICAL CONDUITS, PROVIDE PULL BOXES, SUCH THAT NO COATS OF FLAT BLACK FIRE RETARDANT PAINT. SINGLE CONDUIT RUN HAS BENDS IN EXCESS OF 360. PULL BOXES SHALL BE SUITABLE AND APPROVED FOR THE INTENDED USE. WARNING TAPE WHICH SAYS 48. INDUSTRIAL CONTROL TYPE TRANSFORMERS SHALL BE PROVIDED WITH FINGERSAFE 'WARNING BURIED ELECTRIC' SHALL BE PLACED IN TRENCHES ABOVE ALL UNDERGROUND COVERS AND PRIMARY FUSE PROTECTION AS REQUIRED PER NEC 450-3. MOUNT ELECTRIC CONDUITS. WHERE CONDUITS PASS UNDERNEATH PAVED AREAS, THEY SHALL TRANSFORMERS ON 4"X4" JUNCTION BOX ABOVE ACCESSIBLE CEILINGS OR ELECTRICAL„_„„ BE PVC. WHERE UNDERGROUND CONDUITS ARE NOT EXPOSED TO MECHANICAL DAMAGE ROOMS. OR ARE NOT UNDER PAVED AREAS, THEY SHALL BE SCHEDULE 40 PVC. 49. FOR RESIDENTIAL WORK PROVIDE COMBINATION TYPE ARC -FAULT CIRCUIT INTERRUPTE----- 23. ALL CONDUIT RUNS ARE SHOWN DIAGRAMMATIC. EXACT ROUTING SHALL BE DETERMINED PROTECTION THROUGHOUT THE DWELLING UNIT, EXCEPT IN KITCHEN BATHROOM, GARAGES M IN THE FIELD, UNLESS OTHERWISE NOTED. AND OUTDOORS. ALL DWELLING UNIT RECEPTACLE OUTLETS MUST BE LISTED ----- ----24. 24. WIREWAYS SHALL BE SIZED AS REQUIRED, PER NEC, UNLESS OTHERWISE NOTED (LION). TAMPER-RESISTANT. 25. WHERE CORE DRILLING OF FLOOR/WALLS IS REQUIRED, CONTRACTOR SHALL SEAL 50. PROVIDE U.L. LISTED COMPOUND APPLIED TO BACK OF "BACK TO BACK" BOXES IN - - - OPENINGS WATERTIGHT AFTER UTILITIES HAVE BEEN INSTALLED. LOCATION OF CORED RATED WALLS WHERE THE BOXES ARE LESS THAN 609.6MM (24 INCHES) APART HOLES SHALL COORDINATE WITH LOCATION OF EQUIPMENT IN A MANNER TO BE CLEAN MEASURED HORIZONTALLY. AND FUNCTIONAL. THE CONTRACTOR SHALL INSTALL ONLY ONE CONDUIT PER HOLE AND 51. CONTRACTOR SHALL PROVIDE TYPED -WRITTEN, UPDATED PANEL DIRECTORIES ON ALL SEAL THE OPENING AROUND THE CONDUIT AS SPECIFIED. PANELS THAT ARE AFFECTED AT THE COMPLETION OF THE JOB. - 26. PROVIDE FIRE RETARDANT U.L. APPROVED SEALANT ON ALL PENETRATIONS OF FIRE RATED PARTITIONS, WALLS AND STRUCTURAL SLABS. CONTRACTOR TO VERIFY, PRIOR TO 52. - FOR RECEPTACLES IN DAMP AND WET LOCATIONS THE CONTRACTOR SHALL PROVIDE AI_L_ _ SUBMITTING BID, LOCATIONS OF ALL SUCH FIRE RATED PARTITIONS, WALL AND 125V. AND 250V., 15A. AND 20A. RECEPTACLES THAT ARE LISTED AS WEATHER - STRUCTURAL SLABS. RESISTANT TYPE TO COMPLY WITH NEC ARTICLE 406.8. 27. UNLESS NOTED AS EXISTING, ALL EQUIPMENT, WIRING, DEVICES, ETC. SHALL BE NEW. = FAULT CURRENT CULCULATIONS AT TRANSFORMER TRASNOFRMER KVA: 150KVA VOLTAGE EL -L: 480V, 30 IMPEDANCE Z 3.5% Tfl TRANSFORMER FULL LOAD AMPERS M MULTIPLIER IDC TRANSFORMER LET -THROUGH SHORT-CIRCUIT CURRENT l _ KVAx1000 = 1500000 = 236.7 EL -Lx 1.732 4800.732 m = 100 = 100 = 28.6 Z 3.5 IS.C= If.l. x m = 236.7x28.6 = 6,771 AMPS �� SHOP DRAWING REQUIREMENTS 1. CONTRACTOR SHALL SUBMIT 6 COPIES OF COMPLETED SHOP DRAWINGS, TOGETHER AT ONE TIME AND MUST COME THROUGH THE ARCHITECT. ALL SUBMITTALS SHALL BE MADE WITHIN 30 DAYS OF NOTICE TO PROCEED. 2. ALL SUBMITTALS MUST CLEARLY INDICATE EXACTLY WHICH ITEMS ARE BEING PROPOSED FOR USE. IF NOT, THE SUBMITTAL SHALL BE REJECTED. 3. SUBSTITUTIONS SHALL BE LIMITED TO ONE OF THE ALTERNATES LISTED IN THE CONSTRUCTION DOCUMENTS. PRODUCTS CONSIDERED TO BE EQUAL SHALL BE REVIEWED AND ACCEPTED BY THE ENGINEER, ARCHITECT AND OWNER (10) DAYS PRIOR TO BID DATE. 4. THE CONTRACTOR ASSUMES ALL DESIGN RESPONSIBILITY AND ALL FINANCIAL RISKS FOR PROCEEDING PRIOR TO SHOP DRAWINGS PROCESSING, AND ON ANY ITEM OR WORK THAT IS AT VARIANCE TO THE CONSTRUCTION DOCUMENTS. 5. SHOP DRAWINGS AND SUBMITTALS FOR EACH ITEM SHALL BE REVIEWED NO MORE THAN TWICE. A THIRD SUBMITTAL ON AN ITEM MUST BE ACCOMPANIED BY A PURCHASE ORDER FROM THE CONTRACTOR OR IT SHALL BE REJECTED. 6. CIRCUMSTANCES NECESSITATING A REVISION TO THE PERMITTED DOCUMENTS NOT PROCESSED PRIOR TO INSTALLATION MAY NOT BE ACCEPTED. IF ACCEPTED IT MUST BE LEGIBLE, ACCURATE AND ACCOMPANIED BY A PURCHASE ORDER ORDER FROM THE CONTRACTOR. THE REVISION SHALL. BE CHARGED TO THE CONTRACTOR AND DELIVERED TO HIM ON A C.O.D. BASIS. 7. SUBSTITUTIONS FROM THE BASE DESIGN OR VARIATIONS TO THE PERMITTED CONTRACT DOCUMENTS, WHETHER RESULTING FROM PROCESSED SHOP DRAWINGS OR NOT, THAT RESULT IN REQUIREMENTS IN LETTERS OF AUTHORIZATION AND/OR PERMIT CONTRACT DOCUMENT CHANGES MANDATED BY THE AUTHORITY HAVING JURISDICTION WILL NOT BE MADE BY THIS OFFICE UNLESS ACCOMPANIED BY A PURCHASE ORDER FROM THE CONTRACTOR, AND RELEASED ON A C.O.D. BASIS. 8. CONTRACTOR SHALL SUBMIT 5 COPIES OF EQUIPMENT LAYOUTS OF ALL ELECTRICAL SPACES, ROOMS, ETC. TO THE ENGINEER FOR APPROVAL PRIOR TO ORDERING EQUIPMENT OR INSTALLING CONDUITS, ETC. THE LAYOUTS SHALL CONSIST OF PLAN VIEWS AT A SCALE OF 1/2' = 1'0" AND ELEVATIONS FOR EACH SUCH SPACE OR ROOM, ETC. DISC. I DISC. TH" SWITCH. SWITCH II IIN II 1 11400 A.1I 1 1i I I °'�I I IMCB. °II ILA�f 1 I I II II II 4 EXIST. L - -i j ° 11-- -11 ° I _ 75 KVA FLEX. O-2 489/240 3" PVC. EMOVE 3" PVC. Al FA 1 PVC.W/A GRADE A A A A FPL PULLBOX, PROVIDED BY FPL INSTALLED BY CONTRACTOR. COORDINATE WITH FPL. REMOVE (2) 2" PVC TO FP&L POWER POLE M10EXISTING POWER RISER DIAGRAM N.T.S. �- EXISTING EQUIPMENT TO BE REMOVED - - - - EXISTING EQUIPMENT TO REMAIN NEW EQUIPMENT COORDINATE ALL WORK WITH FPL REPRESENTATIVE EXISTING BRANCH - - - - ------- CIRCUIT WITri--Z"- r r PVC, (4)#3/0'(1)#6 - , Y ' ti_ EXISTING BRANCH GREEN TO - r ;CISIG BRANCH i V V V - - -jk-_--Il C61T WITH 3" --- PRODUCTION -ROOM. Cl CIRCUIT WITH 1Y Vvyv Vvv- PVG,_(3)#4/0, (2)#3 RIGID, (3)#3, (1)# 6 T^ _REERIGERATION GREEN TO VACUUM - - - - Y COMPRESSOR RACK. ; PUMP. f: 71 � EXIST, ' (i DISC. 400 Ae'11 (1P�ANEL 11 NEW 200 A. ; I I SWITCH 11 I I TH I 800 AM P DISCO. i I I 11400 A.1I CT S 1 100K. °' ( IMCB. 9$LL 277/48oV,3 I A.I.C. II IICB' S Fc�, TED J I�65KAIC�I 4 EXIST. ' 75 KVA - - - 48240 3Y2" PVC W/4- 3-3/0-2"500 FLEX. ; 500 MCM- U 1'X1'X8' GUTTER 3R NEW 2 SETS OF 500 MCM USE POLARIS TAP . GRADE ❑❑ `T EX. 1Y2" PVC.W/3#2 A �- �- USE D AND _," -'- CONNECT TO EXISTING GROUNDING ELECTRODE SYSTEM EXISTING FPL OVERHEAD LINES 1) �JR \\ I I ( � IM ETE J' 0 11 VIII I FPL PULLBOX, PROVIDED I II BY FPL INSTALLED BY I II I CONTRACTOR. COORDINATE WITH FPL. z 111 I (2) 3X2" PVC W/4-500 111 ACM -CU EA. U/GROUND w I II TO CT'S. "I eNEW POWER RISER DIAGRAM UPGRADE TO 800AMP. N.T.S. - - - - EXISTING EQUIPMENT TO REMAIN NEW EQUIPMENT COORDINATE ALL WORK WITH FPL REPRESENTATIVE LOCATION OF ELECTRICAL ; AND UTILITY POWER RISEF THIS SHEET. PEPMAIT NO, ALL WORK INVOLVED ON € I l5 �� � I SI OR I u WITH ALL CITY OF BOYNTON BEACH Lv LD Go BODES. Date - I ppm .� $�-�'rl ��� Aa�viun i �� ii SCOPE OF WORK FOR THIS PROJECT CONTRACTOR SHALL PERFORM ALL WORK AS SHOWN ON THE POWER RISERS. THE EXISTING MAXIMUM LOAD ON THE SYSTEM HAS RECENTLY EXCEEDED 40OAMPS. AND THE SERVICE CONDUCTORS HAVE BEEN GETTING VERY HOT, THEREFORE THE SCOPE OF WORK IS TO REPLACE THE EXISTING 40OAMP. SERVICE WITH A NEW 80OAMP. SERVICE AS SHOWN. Copyright 2011 Material shown here is the Copyrighted Property of Delta G Consulting Engineers, Inc. and shall not be reproduced in whole or in part without express written permission. DELTA G CONSULTING ENGINEERS, INC. THE ENGINEERING SPECIALISTS Delta G Consulting Engineers, Inc. 707 N.E. 3rd Ave. Suite 200 Fort Lauderdale, FL 33304 (954) 527-1112 Tel. (954) 524-7505 Fax www. DeltaG. net REVISIONS: QRTC 6-27-16 a _ _ PROJECT* 1606XX PROJECT MANAGER: GSJ DESIGNED BY: 11\ � C.A.#: 00009181 DATE: 06/08/2016 EXISTING FPL \ EXISTING BRANCH , r r OVERHEAD LINES CIRCUIT WITH 2" ;XtSTING BRANCH EXISTING BRANCH PVC, (4)#3/0, (1)#6 ' GREEN TO i CIRCUIT WITH 3" PVC, (3)#4/0, (2)#3 ' ' CIRCUIT WITH 1X2" RIGID, (3)#3, (1)#6 \\ PRODUCTION ROOM. i TO REFRIGERATION GREEN TO VACUUM i COMPRESSOR RACK. PUMP. I 200 A. i X400 A PANEL: � REMOVE 277/480V 400 A. 3 -PH. METER f DISC. I DISC. TH" SWITCH. SWITCH II IIN II 1 11400 A.1I 1 1i I I °'�I I IMCB. °II ILA�f 1 I I II II II 4 EXIST. L - -i j ° 11-- -11 ° I _ 75 KVA FLEX. O-2 489/240 3" PVC. EMOVE 3" PVC. Al FA 1 PVC.W/A GRADE A A A A FPL PULLBOX, PROVIDED BY FPL INSTALLED BY CONTRACTOR. COORDINATE WITH FPL. REMOVE (2) 2" PVC TO FP&L POWER POLE M10EXISTING POWER RISER DIAGRAM N.T.S. �- EXISTING EQUIPMENT TO BE REMOVED - - - - EXISTING EQUIPMENT TO REMAIN NEW EQUIPMENT COORDINATE ALL WORK WITH FPL REPRESENTATIVE EXISTING BRANCH - - - - ------- CIRCUIT WITri--Z"- r r PVC, (4)#3/0'(1)#6 - , Y ' ti_ EXISTING BRANCH GREEN TO - r ;CISIG BRANCH i V V V - - -jk-_--Il C61T WITH 3" --- PRODUCTION -ROOM. Cl CIRCUIT WITH 1Y Vvyv Vvv- PVG,_(3)#4/0, (2)#3 RIGID, (3)#3, (1)# 6 T^ _REERIGERATION GREEN TO VACUUM - - - - Y COMPRESSOR RACK. ; PUMP. f: 71 � EXIST, ' (i DISC. 400 Ae'11 (1P�ANEL 11 NEW 200 A. ; I I SWITCH 11 I I TH I 800 AM P DISCO. i I I 11400 A.1I CT S 1 100K. °' ( IMCB. 9$LL 277/48oV,3 I A.I.C. II IICB' S Fc�, TED J I�65KAIC�I 4 EXIST. ' 75 KVA - - - 48240 3Y2" PVC W/4- 3-3/0-2"500 FLEX. ; 500 MCM- U 1'X1'X8' GUTTER 3R NEW 2 SETS OF 500 MCM USE POLARIS TAP . GRADE ❑❑ `T EX. 1Y2" PVC.W/3#2 A �- �- USE D AND _," -'- CONNECT TO EXISTING GROUNDING ELECTRODE SYSTEM EXISTING FPL OVERHEAD LINES 1) �JR \\ I I ( � IM ETE J' 0 11 VIII I FPL PULLBOX, PROVIDED I II BY FPL INSTALLED BY I II I CONTRACTOR. COORDINATE WITH FPL. z 111 I (2) 3X2" PVC W/4-500 111 ACM -CU EA. U/GROUND w I II TO CT'S. "I eNEW POWER RISER DIAGRAM UPGRADE TO 800AMP. N.T.S. - - - - EXISTING EQUIPMENT TO REMAIN NEW EQUIPMENT COORDINATE ALL WORK WITH FPL REPRESENTATIVE LOCATION OF ELECTRICAL ; AND UTILITY POWER RISEF THIS SHEET. PEPMAIT NO, ALL WORK INVOLVED ON € I l5 �� � I SI OR I u WITH ALL CITY OF BOYNTON BEACH Lv LD Go BODES. Date - I ppm .� $�-�'rl ��� Aa�viun i �� ii SCOPE OF WORK FOR THIS PROJECT CONTRACTOR SHALL PERFORM ALL WORK AS SHOWN ON THE POWER RISERS. THE EXISTING MAXIMUM LOAD ON THE SYSTEM HAS RECENTLY EXCEEDED 40OAMPS. AND THE SERVICE CONDUCTORS HAVE BEEN GETTING VERY HOT, THEREFORE THE SCOPE OF WORK IS TO REPLACE THE EXISTING 40OAMP. SERVICE WITH A NEW 80OAMP. SERVICE AS SHOWN. Copyright 2011 Material shown here is the Copyrighted Property of Delta G Consulting Engineers, Inc. and shall not be reproduced in whole or in part without express written permission. DELTA G CONSULTING ENGINEERS, INC. THE ENGINEERING SPECIALISTS Delta G Consulting Engineers, Inc. 707 N.E. 3rd Ave. Suite 200 Fort Lauderdale, FL 33304 (954) 527-1112 Tel. (954) 524-7505 Fax www. DeltaG. net REVISIONS: QRTC 6-27-16 a _ _ PROJECT* 1606XX PROJECT MANAGER: GSJ DESIGNED BY: GSJ C.A.#: 00009181 DATE: 06/08/2016 SEAL 21AAt a r i517 r"11,01, r" R4�1`11 _�__!'-! , ' a-, ,' '` E1.0 GENERAL ELECTRICAL NOTES SHOP DRAWING REQUIREMENTS 1. CONTRACTOR SHALL SUBMIT 6 COPIES OF COMPLETED SHOP DRAWINGS, TOGETHER AT ONE TIME AND MUST COME THROUGH THE ARCHITECT. ALL SUBMITTALS SHALL BE MADE WITHIN 30 DAYS OF NOTICE TO PROCEED. 2. ALL SUBMITTALS MUST CLEARLY INDICATE EXACTLY WHICH ITEMS ARE BEING PROPOSED FOR USE. IF NOT. THE SUBMITTAL SHALL BE REJECTED. 3. SUBSTITUTIONS SHALL BE LIMITED TO ONE OF THE ALTERNATES LISTED IN THE CONSTRUCTION DOCUMENTS. PRODUCTS CONSIDERED TO BE EQUAL SHALL BE REVIEWED AND ACCEPTED BY THE ENGINEER, ARCHITECT AND OWNER (10) DAYS PRIOR TO BID DATE. 4. THE CONTRACTOR ASSUMES ALL DESIGN RESPONSIBILITY AND ALL FINANCIAL RISKS FOR PROCEEDING PRIOR TO SHOP DRAWINGS PROCESSING, AND ON ANY ITEM OR WORK THAT IS AT VARIANCE TO THE CONSTRUCTION DOCUMENTS. 5. SHOP DRAWINGS AND SUBMITTALS FOR EACH ITEM SHALL BE REVIEWED NO MORE THAN TWICE. A THIRD SUBMITTAL ON AN ITEM MUST BE ACCOMPANIED BY A PURCHASE ORDER FROM THE CONTRACTOR OR Tr SHALL BE REJECTED. 6. CIRCUMSTANCES NECESSITATING A REVISION TO THE PERMITTED DOCUMENTS NOT PROCESSED PRIOR TO INSTALLATION MAY NOT BE ACCEPTED. IF ACCEPTED IT MUST BE LEGIBLE, ACCURATE AND ACCOMPANIED BY A PURCHASE ORDER ORDER FROM THE CONTRACTOR. THE REVISION SHALL BE CHARGED TO THE CONTRACTOR AND DELIVERED TO HIM ON A C.O.D. BASIS. 7. SUBSTITUTIONS FROM THE BASE DESIGN OR VARIATIONS TO THE PERMITTED CONTRACT DOCUMENTS, WHETHER RESULTING FROM PROCESSED SHOP DRAWINGS OR NOT, THAT RESULT IN REQUIREMENTS IN LETTERS OF AUTHORIZATION AND/OR PERMIT CONTRACT DOCUMENT CHANGES MANDATED BY THE AUTHORITY HAVING JURISDICTION WILL NOT BE MADE BY THIS OFFICE UNLESS ACCOMPANIED BY A PURCHASE ORDER FROM THE CONTRACTOR, AND RELEASED ON A C.O.D. BASIS. 8. CONTRACTOR SHALL SUBMIT 5 COPIES OF EQUIPMENT LAYOUTS OF ALL ELECTRICAL SPACES, ROOMS, ETC. TO THE ENGINEER FOR APPROVAL PRIOR TO ORDERING EQUIPMENT OR INSTALLING CONDUITS, ETC. THE LAYOUTS SHALL CONSIST OF PLAN VIEWS AT A SCALE OF 1/2" = 1'0" AND ELEVATIONS FOR EACH SUCH SPACE OR ROOM, ETC. M EXISTING BRANCH �, CIRCUIT WITH 2" ; (GENERAL NOTES ARE PROVIDED AS A BASIC DESCRIPTION OF THE EXTENT AND QUALITY EXPECTED IN THIS PROJECT. IF A CONFLICT EXISTS BETWEEN THESE GENERAL NOTES AND THE REMAINDER OF THE CONTRACT DOCUMENTS THE SPECIFICATIONS, PLANS AND DETAILS WILL GOVERN.) 1. THE ENTIRE INSTALLATION SHAD. BE IN ACCORDANCE WITH THE FOLLOWING CODES AND STANDARDS 28. ALL CIRCUIT L?F?EE'RS SHALL BE INVERSE TIME TYPE (THERMAL MAGNETIC OR SOLID , �_ FLORIDA STATE FIRE MARSHAL'S PILE 69A-3.012 FAC AND RULE CHAPTER 69A-60 FLORIDA witdINISTRATIYE CODE (FAC) AND PVC, (4)#3/0, (1)#6 ° STATE AS REQUIRED ' BY SPECIFICATION). TWO AND THREE POLE CIRCUIT BREAKERS ; FLORIDA STATUTE SECTION 633.022. GREEN TO PRODUCTION ROOM. SHALL BE COMMON TRIP. NO TIE HANDLES PERMITTED. ° A. NFPA 70: NATIONAL ELECTRICAL. CODE (2011 EDITION) 29. ALL FUSES SHALL BE CURRENT LIMITING, PER U.L., RATED 60OV., UON. ° B. NFPA 72 NATIONAL FIS ALARM CODE (2010 EDITION) A. NON -TIME DELAY FUSES IN MAIN SWITCHES AND SWITCHES FEEDING PANELS. i C. NFPA 99: HEALTH CARE FACILITIES (2012 EDITION) ° 200 A. B. TIME DELAY FUSES FOR MOTOR AND A/C CIRCUITS. REMOVE 277/480V 400 A. 3 -PH. METER D. NFPA 101: LIFE SAFEIY CODE (2012 EDITION) E NFPA 110: STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS (2010 EDITION) 30. ALL DISCONNECT SWITCHES SHALL BE SIZED BY NEC REQUIREMENTS TO ACCOMMODATE i ry4tyir# F NFPA 760: STMDARD FOR THE INSTALLATION OF UGRINING PROTEMN SYSTEMS (2011 0110111) EQUIPMENT SERVED, INCLUDING REQUIRED FUSES U.O.N. SWITCHES SHALL BE X400 A. IN ADDITION, THE INSI LIATION SHALL ALSO BE IN ACCORDANCE WITH THE FOLLOWING: EXIST. HORSEPOWER RATED FOR MAX. HORSEPOWER, HEAVY DUTY TYPE. PA I ' II 1`! " " ° II G. FLORIDA BUILDING CODE 2010 31. CONTRACTOR SHALL VERIFY CIRCUIT PROTECTIVE DEVICE RATING FOR EQUIPMENT PRIOR I I SWITCH I I I I y�-TH 11 H. THE GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES DISCO. TO INSTALLATION. 11400 A.II I. (FLORIDA FIRE 2PREV 10 EDITION) COD(2010 EINiION) 32. FURNISH AND INSTALL DISCONNECT SWITCHES AND WIRING FOR AIR CONDITIONING I IIMCB• °II 277/48OV,3 IL JP----' SYSTEM AS PER MANUFACTURER RECOMMENDATIONS. CONTROLS ARE TO BE SUPPLIED 2. AS A MINIMUM, ALL EQUIPMENT SHALL MEET APPLICABLE STANDARDS, FOR THE TYPE OF EXIST. BY AIR CONDITIONING CONTRACTOR AND CONNECTED. PROVIDE ALL CONTROL WIRING FOR EQUIPMENT AND INTENDED USE, OF THE FOLLOWING: 75 KVA A/C SENSORING AND CONTROL UNITS, COORDINATE WITH A/C CONTRACTOR FOR WIRING =_ L�--= --� A. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) � 481240 DIAGRAMS AND EXACT MOUNTING LOCATIONS. 3V' PVC / wCU B. ILLUMINATING ENGINEERS SOCIETY (IES) 33. ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT WHERE EXPOSED TO THE WEATHER. 00 MCM C. AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM) I Ry ALL FLEX CONDUITS CONNECTED TO SUCH EQUIPMENT SHALL BE LIQUID TIGHT. 1'X1'XB' GUTTER 3R NEW 2 D. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATES.(NEMA) E. NOTE: THESE STANDARDS ARE SUBORDINATE TO CODES AND STANDARDS SET BY U.L.. 34. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND NEMA RATED FOR THE OF 500 MCM USE POLARIS ALL ELECTRICAL EQUIPMENT. DEVICES, WIRE, ETC., SHALL BE LISTED, FOR INTENDED GRADE ❑OO❑ ENVIRONMENT IN WHICH THEY ARE TO BE INSTALLED. USE, WITH UNDERWRITER'S LABORATORIES INC. (U.L..), WHERE STANDARDS HAVE BEEN 35. ALL CONNECTIONS TO GROUND RODS SHALL BE MADE WITH U.L APPROVED WELDED ESTABUSHED BY U.L. CONNECTIONS, UNLESS NOTED OTHERWISE. THE CONTRACTOR SHALL FORM A 3. CONTRACTOR TO PROVIDE ALL LABOR, MATERIALS AND SUPERVISION NECESSARY TO GROUNDING ELECTRODE SYSTEM AS PER NEC 250-50. ACCOMPLISH THE WORK AS SHOWN AND/OR NOTED ON THE DRAWINGS. 36. OUTLET IN DRY LOCATIONS BOXES SHALL BE PRESSED STEEL, IN WET OR DAMP 4. THE CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL CONDITIONS, LOCATIONS, LOCATIONS SHALL BE CAST ALLOY WEATHER -RESISTANT OUTLET WITH THREADED HUBS DIMENSIONS AND COUNTS AS SHOWN OR NOTED ON THE DRAWINGS, PRIOR TO AND IN OTHER CLASSIFIED AREAS IT SHALL BE IN A SPECIAL ENCLOSURE. PROPER SUBMITTING BID. PLASTER RINGS SHALL BE USED WITH OUTLET BOXES. PROPER COORDINATION BETWEEN 5. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE ALL LABOR, ELECTRICAL SUBCONTRACTOR AND GENERAL CONTRACTOR FOR PLASTER RING INITIATION LOCATION OF EXISTING MATERIALS AND SUPERVISION NECESSARY TO ACCOMPLISH THE WORK AS SHOWN WILL BE REQUIRED. NO "GOOF" RINGS SHALL BE ALLOWED. ALL OUTLET BOXES SHALL ELECTRICAL SERVICE: AND/OR NOTED ON THE PLANS. BE SECURELY FASTENED. 6. ELECTRICAL CONTRACTOR SHALL NOT SCALE DRAWINGS. CONTRACTOR SHALL REFER TO 37. WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE RESISTIVE ASSEMBUES, POWER RISE. AGRAM ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT LOCATIONS OF ALL EQUIPMENT , (CLASSIFIED AS FIRE/SMOKE AND SMOKE PARTITIONS), THEY SHALL BE INSTALLED UNLESS NOTED OTHERWISE. WITHOUT AFFECTING THE FIRE CLASSIFICATION. ALL OF THE FOLLOWING CONDITIONS 7. IT SHALL BE UNDERSTOOD THAT ALL WORK PERFORMED SHALL BE DONE BY A LICENSED ® SHALL BE MET: CONTRACTOR AND IN A FIRST-CLASS WORKMANUKE MANNER. SAID CONTRACTOR SHALL A. ALL ELECTRICAL BOXES SHALL BE METALLIC. MEET ALL REQUIREMENTS SET FORTH BY ANY LOCAL ORDINANCE AND GOVERNING B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE. AUTHORITIES. C. BOX OPENING SHALL NOT EXCEED 10322.56 SQUARE MM (16SQUARE INCHES). 8. THE CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. COMPLETELY FILLED WITH JOINT COMPOUND (OR OTHER APPROVED MATERIAL). 9. CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS E. PROVIDE A WALL AROUND OUTLETS LARGER THAT 10322.56 SQUARE MM (16 FOR A PERIOD OF NOT LESS THAN ONE YEAR FROM DATE OF ACCEPTANCE, UNLESS SQUARE INCHES). THE INTEGRITY OF THE WALL RATING SHALL BE MAINTAINED. INDICATED OR SPECIFIED OTHERWISE. F. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 64516 10. IT SHALL NOT BE THE INTENT OF THESE PLANS AND/OR SPECIFICATIONS TO SHOW SQUARE MM (100 SQUARE INCHES) PER 9.29 SQUARE METERS (100 SQUARE FEET). EVERY MINOR DETAIL OF CONSTRUCTION. THE CONTRACTOR SHALL BE EXPECTED TO G. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE RESISTIVE ASSEMBLIES SHALL FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM AND PROVIDE BE SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 609.6MM (24 INCHES). FOR ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER H. OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS. WORKING ORDER. 1. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED 11. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING TO ORIGINAL CONDITIONS, 3.175MM (1/8 INCH) BETWEEN THE EDGES OF THE OUTLET BOX AND THE EDGES OF ANY AND ALL DAMAGES TO BUILDING SURFACES, EQUIPMENT, ETC. CAUSED DURING THE THE OPENING. PERFORMANCE OF WORK. 38. SMOKE DETECTORS SHALL BE PROVIDED NO CLOSER THAN 36" FROM SUPPLY AIR 12. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE OR DIFFUSERS. DELAYS AND SHALL INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 39. CONTRACTOR SHALL PROVIDE A TYPE WRITTEN DIRECTORY OF EACH PANELBOARD. HAND WRITTEN DIRECTORY IS NOT ACCEPTABLE, EXCEPT SPARE AND SPACES SHALL BE 13. FOR ELECTRIC POWER SYSTEM, COORDINATE POWER SERVICE WITH POWER COMPANY, HANDWRITTEN 1H',PENCIL. A. VERIFY LOCATION OF POWER SERVICE TERMINATION WITH POWER COMPANY, PRIOR TO SUBMITTING BID. CONTRACTOR TO VERIFY AVAILABLE SERVICE VOLTAGE AND PHASES 40• PROVIDE A 4" STEEL REINFORCED CONCRETE HOUSEKEEPING PAD UNDER ALL FLOOR WITH POWER COMPANY PRIOR TO BID AND PROVIDE BID ALLOWANCE FOR ALTERNATES. MOUNTED ELECTRICAL EQUIPMENT. B. PROVIDE TEMPORARY ELECTRICAL SERVICE FOR USE BY ALL TRADES DURING 41. A. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH CONSTRUCTION AND REMOVE SAME AT COMPLETION OF PROJECT, NEC 110.26 14. CONTRACTOR SHALL KEEP ALL AREAS IN WHICH WORK IS BEING PERFORMED, FREE B. THE EXCLUSIVELY DEDICATED SPACE EXTENDING FROM FLOOR TO STRUCTURAL FROM DEBRIS AT ALL TIMES AND SAID AREAS SHALL BE LEFT BROOM CLEAN AT THE CEILING WITH A WIDTH AND DEPTH OF THE PANELBOARD OR SWITCHBOARD MUST BE END OF EACH WORKING DAY. CLEAR OF ALL PIPING, DUCTS, EQUIPMENT FOREIGN TO THE ELECTRICAL EQUIPMENT OR 15. CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES, INSPECTIONS, AND TESTING COSTS. ARCHITECTURAL APPURTENANCES IN ACCORDANCE WITH NEC 408. 16. COORDINATE ALL ELECTRICAL SITE WORK WITH ALL OTHER TRADES CONTRACTORS. 42. METER CANS, HUBS. & LUGS FOR SAME ARE TO BE FURNISHED & INSTALLED BY CONTRACTOR. CONTRACTOR TO VERIFY SPECIFIC TYPE OF METER CAN TO BE USED 17. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR FOR THE ADVANCE WITH F.P.L. PRIOR TO BID. ORDERING OF LONG LEAD ITEMS, AS TO NOT INTERFERE WITH THE PRODUCTION OF OTHER TRADES RESULTING IN ANY DOWN OR LAG TIME. THE CONTRACTOR SHALL NOT 43. A. PROVIDE A PERMANENT SIGN ON THE MAIN ELECTRICAL ROOM DOOR TO THE BLDG. ORDER ANY ITEMS UNTIL APPROVE) SHOP DRAWINGS ARE RETURNED TO HIM. STATING THAT THE SERVICE DISCONNECTS ARE LOCATED INSIDE. 18. ELECTRICAL CONTRACTOR SHALL SUBMIT (6 COPIES) EQUIPMENT LAYOUT OF ALL B. SIGNS SHALL BE PLACED AT THE MAIN DISCONNECT EQUIPMENT INDICATING TYPE AND LOCATION OF ON-SITE EMERGENCY POWER SOURCES. ELECTRICAL SPACES, ROOMS, ETC., TO ENGINEER FOR APPROVAL PRIOR TO ORDERING EQUIPMENT OR INSTALLING CONDUITS. ETC. LAYOUT SHALL CONSIST OF PLAN VIEWS 44. THE EQUIPMENT GROUNDING TERMINAL BARS OF THE NORMAL AND EMERGENCY (SCALED AS REQUIRED) AND ELEVATIONS (DIMENSIONED) FOR EACH SUCH SPACE, ELECTRICAL SYSTEM"PANELBOARDS' SERVING THE SAME BUILDING SHALL BE BONDED ROOM, ETC. - TOGETHER WITH AN INSULATED, CONTINUOUS, COPPER CONDUCTOR NOT SMALLER THAN 19. CONTRACTOR SHALL SUBMIT AT ONE TIME, SIX (6) SETS OF LOOSE-LEAF BOUND NUMBER 6. BOOKS, INDEXED WITH ALL PRODUCTS, MATERIALS, LIGHTING FIXTURES, LAMPS, WIRING 45. THE ELECTRICAL CONTRACTOR SHALL FURNISH A COMPLETE SET OF AS -BUILT DEVICES, SWITCHGEAR, ETC. CLEARLY HIGHLIGHTING ALL EQUIPMENT QUANTITIES AND DRAWINGS, SHOWING ALL CHANGES AND DEVIATIONS TO THE ARCHITECT/ENGINEER PRIOR DETAILS. ALL EQUIPMENT SHALL BE AS SPECIFIED ON PLANS: THE RESPONSIBILITY TO TO COMPLETION OF THE PROJECT. ACCEPT OR REJECT ANY PROPOSED SUBSTITUTION REMAINS WITH THE PROJECT ENGINEER. THE CONTRACTOR MAY AT HIS JUDGMENT USE ANY ARTICLE, DEVICE, 46. -00 ARCHITECTURAL AND/OR ENGINEERING EXPENSES THAT ARE INCURRED DUE TO PRODUCT, OR MATERIAL WHICH IN THE JUDGMENT OF THE ENGINEER EXPRESSED IN REVISIONS OR SUBSTITUTIONS REQUESTED BY THE CONTRACTOR SHALL BE PAID F BY WRITING ARE EQUAL TO THAT SPECIFIED. THAT CONTRACTOR. 20. ALL CONDUCTORS SHALL BE COPPER, TYPE THHN/THWN EXCEPT WHERE OTHERWISE 47. FOR TELEPHONE SYSTEMS: REQUIRED BY U.L OR CODES. MINIMUM WIRE SIZE SHALL BE #12 AWG, EXCLUDING A. PROVIDE GROUNDING FOR ALL TELEPHONE OUTLETS AND EQUIPMENT P CONTROL WIRING. ALUMINUM CONDUCTORS ARE NOT PERMITTED. REQUIREMENTS OF THE TELEPHONE COMPANY. B. COORDINATE INSTALLATION OF ALL TELEPHONE OUTLETS, RACEWAYS, v CLOSURES 21. ALL CONDUCTORS SHALL BE IN CONDUITS. ALL CONDUITS SHALL BE GALVANIZED RIGID AND BACKBOARDS WITH TELE. CO. STEEL (GRS) EXCEPT THAT. (o) PVC CONDUITS MAY BE USED UNDERGROUND PROVIDED C. VERIFY LOCATION OF TELEPHONE SERVICE WITH TELEPHONE PANY. PROVIDE ELBOWS AND RISERS ARE GALVANIZED RIGID STEEL OR SCHEDULE 80 PVC, WHERE SERVICE CONDUIT TO BLDG. FROM SERVICE POINT PER TELCO STRUCTIONS, INCLUDE SUBJECT TO PHYSICAL DAMAGE (b) ELECTRICAL METALLIC TUBING (EMT) MAY BE USED ALL ASSOCIATE) COSTS IN BID. IN OR ON WALLS OR CEILINGS WHERE NOT SUBJECT TO MECHANICAL DAMAGE, DAMP OR D. MARK TERMINATIONS OF TELEPHONE CONDUIT AS DIREC . BY THE TELEPHONE CORROSIVE CONDITIONS, (c) UQIIID TIGHT FLEXIBLE CONDUIT WHERE REQUIRED, (d) COMPANY. FLEXIBLE METALLIC CONDUIT WHLRE REQUIRED IN DRY LOCATIONS ONLY, (e) MC CABLE E. VERIFY LOCATION OF TELEPHONE SERVICE WITH TE ONE COMPANY PRIOR TO WITH DEDICATED GREEN GROUNDING CONDUCTOR WHERE PERMITTED. ALL CONDUITS IN SUBMITTING BID, INCLUDE ALL ASSOCIATED COSTS I ID. HAZARDOUS AREAS (PER NEC) SHALL MEET THE REQUIREMENTS OF NEC CHAPTER 5. F. USE EXTERIOR GRADE 3/4" PLYWOOD BACK S FOR MOUNTING TELEPHONE EQUIPMENT AND TERMINAL STRIPS. PAINT BO ON ALL SIDES AND EDGES WITH TWO 22. FOR UNDERGROUND ELECTRICAL CONDUITS, PROVIDE PULL BOXES, SUCH THAT NO COATS OF FLAT BLACK FIRE RETARDANT PAI SINGLE CONDUIT RUN HAS BENDS IN EXCESS OF 360. PULL BOXES SHALL BE SUITABLE AND APPROVED FOR THE INTENDED USE. WARNING TAPE WHICH SAYS 48. INDUSTRIAL CONTROL TYPE TRANSFORM SHALL BE PROVIDED WITH FINGERSAFE "WARNING BURIED ELECTRIC" SHALL BE PLACED IN TRENCHES ABOVE ALL UNDERGROUND COVERS AND PRIMARY FUSE PROTECTI AS REQUIRED PER NEC 450-3. MOUNT ELECTRIC CONDUITS. WHERE CONDUITS PASS UNDERNEATH PAVED AREAS, THEY SHALL TRANSFORMERS ON 4"X4" JUNCTION X ABOVE ACCESSIBLE CEUNGS OR ELECTRICAL BE PVC. WHERE UNDERGROUND CONDUITS ARE NOT EXPOSED TO MECHANICAL DAMAGE ROOMS. OR ARE NOT UNDER PAVED AREAS, THEY SHALL BE SCHEDULE 40 PVC. 49. FOR RESIDENTIAL WORK PROVID COMBINATION TYPE ARC -FAULT CIRCUIT INTERRUPTER 23. ALL CONDUIT RUNS ARE SHOWN DIAGRAMMATIC. EXACT ROUTING SHALL BE DETERMINED PROTECTION THROUGHOUT TH WELLING UNIT, EXCEPT IN KITCHEN BATHROOM, GARAGES IN THE FIELD, UNLESS OTHERWISE NOTED. AND OUTDOORS. ALL DWE UNIT RECEPTACLE OUTLETS MUST BE LISTED 24. WIREWAYS SHALL BE SIZED AS REQUIRED, PER NEC, UNLESS OTHERWISE NOTED (LION). TAMPER-RESISTANT. 25. WHERE CORE DRIL LJNG OF FLOOR/WALLS IS REQUIRED, CONTRACTOR SHALL SEAL 50. PROVIDE U.L. LISTED IMPOUND APPLIED TO BACK OF "BACK TO BACK" BOXES IN RATED WALLS WHE HE BOXES ARE LESS THAN 609.6MM (24 INCHES) APART OPENINGS WATERTIGHT AFTER UTILITIES HAVE BEEN INSTALLED. LOCATION OF CORED HOLES SHALL COORDINATE WITH LOCATION OF EQUIPMENT IN A MANNER TO BE CLEAN MEASURED HORIZ ALLY. AND FUNCTIONAL. THE CONTRACTOR SHALL INSTALL ONLY ONE CONDUIT PER HOLE AND 51. CONTRACTOR '` PTROVIDE TYPED -WRITTEN, UPDATED PANE_ DIRECTORIES ON ALL SEAL THE OPENING AROUND THE CONDUIT AS SPECIFIED. PANELS ARE AFFECTED AT THE COMPLETION OF THE JOB. 26. PROVIDE FIRE RETARDANT U.L APPROVED SEALANT ON ALL PENETRATIONS OF FIRE RATED PARTITIONS, WALLS AND STRUCTURAL SLABS. CONTRACTOR TO VERIFY, PRIOR TO 52. FOR ACLES IN DAMP AND WET LOCATIONS THE CONTRACTOR SHALL PROVIDE ALL SUBMITTING BID, LOCATIONS OF ALL SUCH FIRE RATED PARTITIONS. WALL AND 12 AND 2501 15A. AND 20A. RECEPTACLES THAT ARE LISTED AS WEATHER STRUCTURAL SLABS. STANT TYPE TO COMPLY WITH NEC ARTICLE 406.8. 27. UNLESS NOTED AS EXISTING, ALL EQUIPMENT, WIRING. DEVICES, ETC. SHALL BE NEW. SHOP DRAWING REQUIREMENTS 1. CONTRACTOR SHALL SUBMIT 6 COPIES OF COMPLETED SHOP DRAWINGS, TOGETHER AT ONE TIME AND MUST COME THROUGH THE ARCHITECT. ALL SUBMITTALS SHALL BE MADE WITHIN 30 DAYS OF NOTICE TO PROCEED. 2. ALL SUBMITTALS MUST CLEARLY INDICATE EXACTLY WHICH ITEMS ARE BEING PROPOSED FOR USE. IF NOT. THE SUBMITTAL SHALL BE REJECTED. 3. SUBSTITUTIONS SHALL BE LIMITED TO ONE OF THE ALTERNATES LISTED IN THE CONSTRUCTION DOCUMENTS. PRODUCTS CONSIDERED TO BE EQUAL SHALL BE REVIEWED AND ACCEPTED BY THE ENGINEER, ARCHITECT AND OWNER (10) DAYS PRIOR TO BID DATE. 4. THE CONTRACTOR ASSUMES ALL DESIGN RESPONSIBILITY AND ALL FINANCIAL RISKS FOR PROCEEDING PRIOR TO SHOP DRAWINGS PROCESSING, AND ON ANY ITEM OR WORK THAT IS AT VARIANCE TO THE CONSTRUCTION DOCUMENTS. 5. SHOP DRAWINGS AND SUBMITTALS FOR EACH ITEM SHALL BE REVIEWED NO MORE THAN TWICE. A THIRD SUBMITTAL ON AN ITEM MUST BE ACCOMPANIED BY A PURCHASE ORDER FROM THE CONTRACTOR OR Tr SHALL BE REJECTED. 6. CIRCUMSTANCES NECESSITATING A REVISION TO THE PERMITTED DOCUMENTS NOT PROCESSED PRIOR TO INSTALLATION MAY NOT BE ACCEPTED. IF ACCEPTED IT MUST BE LEGIBLE, ACCURATE AND ACCOMPANIED BY A PURCHASE ORDER ORDER FROM THE CONTRACTOR. THE REVISION SHALL BE CHARGED TO THE CONTRACTOR AND DELIVERED TO HIM ON A C.O.D. BASIS. 7. SUBSTITUTIONS FROM THE BASE DESIGN OR VARIATIONS TO THE PERMITTED CONTRACT DOCUMENTS, WHETHER RESULTING FROM PROCESSED SHOP DRAWINGS OR NOT, THAT RESULT IN REQUIREMENTS IN LETTERS OF AUTHORIZATION AND/OR PERMIT CONTRACT DOCUMENT CHANGES MANDATED BY THE AUTHORITY HAVING JURISDICTION WILL NOT BE MADE BY THIS OFFICE UNLESS ACCOMPANIED BY A PURCHASE ORDER FROM THE CONTRACTOR, AND RELEASED ON A C.O.D. BASIS. 8. CONTRACTOR SHALL SUBMIT 5 COPIES OF EQUIPMENT LAYOUTS OF ALL ELECTRICAL SPACES, ROOMS, ETC. TO THE ENGINEER FOR APPROVAL PRIOR TO ORDERING EQUIPMENT OR INSTALLING CONDUITS, ETC. THE LAYOUTS SHALL CONSIST OF PLAN VIEWS AT A SCALE OF 1/2" = 1'0" AND ELEVATIONS FOR EACH SUCH SPACE OR ROOM, ETC. M EXISTING BRANCH �, CIRCUIT WITH 2" ; r r ° U V CIRCUIT WITH 2" __EXISTING BRANCH , �_ EXISTING BRANCH) PVC, (4)#3/0, (1)#6 ° � CIRCUIT WITH 3" ; CIRCUIT WITH 1, "'"' GREEN TO PRODUCTION ROOM. r PVC, (3)#4/0, (2)#3 r ° RIGID, (3)#3; °{ #fi , r TO REFRIGERATION ° GREEN rF ACUUM COMPRESSOR RACK. i PUMPS ° 200 A. 400 A ' PANE ��� REMOVE 277/480V 400 A. 3 -PH. METER DISC. i I `r DISC. ° 11 I I I I SWITCH. I I SWITCH I( f TH I I 11400 A.I I Ir i i I I IMCB. °II ILA___ � Lr __j EXIST. LJ-.-'- -1i ' 75 KVA 2" FLEX.,1111 480 .- " EMOVE 3 PVC. - I' 3" PVC. �• R R R R R A A •1"�--------------------EXISTING 1Nz, PVC. EAD LINES F-1 I I � ( Ij I M ILq I OR. FPL PULLBOX, PROVIDED 111 10 BY FPL INSTALLED BY III I z CONTRACTOR. cn COORDINATE WITH FPL. III x REMOVE (2) 2" PVC I () I w TO FP&L POWER POLE III I I .I I M1OEXISTING POWER RISER DIAGRAM N.T.S. --*--x- EXISTING EQUIPMENT TO BE REMOVED - - - - EXISTING EQUIPMENT TO REMAIN NEW EQUIPMENT COORDINATE ALL WORK WITH FPL REPRESENTATIVE EXISTING BRANCH '� PROJECT MANAGER: GSJ CIRCUIT WITH 2" � „ii"Au 10"t ,C? �A PVC, (4)#3/0, (1)#6 r GREEN ; _EXISTING BRANCH i EXISTING BRANCH PRODUCTION ROOM. , , ° CIRCUIT WITH 3" , CIRCUIT WITH 1V , PVC, (3)#4/0, (2)#3 RIGID, (3)#3, (1) r TO REFRIGERATION GREEN TO VACUO COMPRESSOR RACK. ; PUMP. Zei i ry4tyir# X400 A. EXIST. , PA I ' II 1`! " " ° II NEW 200 A. ° r ' I I SWITCH I I I I y�-TH 11 800 AMP DISCO. 11400 A.II CT's I IIMCB• °II 277/48OV,3 IL JP----' �1 I I II II II EXIST. 75 KVA =_ L�--= --� � 481240 3V' PVC / wCU 2" FLEX. ; 00 MCM I Ry 1'X1'XB' GUTTER 3R NEW 2 SETS `�' R AR fl�fl A AA A •I n OF 500 MCM USE POLARIS TAP . GRADE ❑OO❑ USE NEW 2/0 CU GROUND AND ---- -1- CONNECT TO EXISTING GROUNDING ELECTRODE SYSTEM EXISTING FPL OVERHEAD LINES l� n \\ I I 1N4" I I ® II I ETE 1 M I Lq 0 VIII I FPL PULLBOX, PROVIDED BY FPL INSTALLED BY I I) CONTRACTOR. z I I) COORDINATE WITH FPL. L- (2) 312" PVC W/4-500 1 MCM-CU EA. U/GROUND w II TO CT's. I 1 I M1ONEW POWER RISER DIAGRAM UPGRADE TO 800AMP. N.T.S. - - - - EXISTING EQUIPMENT TO REMAIN NEW EQUIPMENT COORDINATE ALL WORK WITH FPL REPRESENTATIVE CONTRACTOR SHALL PERFORM ALL WORK AS SHOWN ON THE POWER RISERS. THE EXISTING MAXIMUM LOAD ON THE SYSTEM HAS RECENTLY EXCEEDED 400AMPS. AND THE SERVICE CONDUCTORS HAVE BEEN GETTIGN VERY HOT, THEREFOR THE SCOPE OF WORK IS TO REPLACE THE EXISTING 40OAMP. SERVICE WITH A NEW 80OAMP. SERVICE AS SHOWN. Copyright 2011 Material shown here is the Copyrighted Property of Delta G Consulting Engineers, Inc. and shall not be reproduced in whole or in part without express written permission. Delta G Consulting Engineers, Inc. 707 N.E. 3rd Ave. Suite 200 Fort Lauderdale, FL 33304 (954) 527-1112 Tel. (954) 524-7505 Fax www.DeltaG.net '� PROJECT MANAGER: GSJ DESIGNED BY: rp „ii"Au 10"t ,C? �A DATE: 06/08/2016 Zei i ry4tyir# i g n J, t "' LOCATION OF EXISTING ;t ELECTRICAL SERVICE: I 31 AND UTILITY P E' 1 POWER RISE. AGRAM , I THIS SHE -LT•. ® ® I CONTRACTOR SHALL PERFORM ALL WORK AS SHOWN ON THE POWER RISERS. THE EXISTING MAXIMUM LOAD ON THE SYSTEM HAS RECENTLY EXCEEDED 400AMPS. AND THE SERVICE CONDUCTORS HAVE BEEN GETTIGN VERY HOT, THEREFOR THE SCOPE OF WORK IS TO REPLACE THE EXISTING 40OAMP. SERVICE WITH A NEW 80OAMP. SERVICE AS SHOWN. Copyright 2011 Material shown here is the Copyrighted Property of Delta G Consulting Engineers, Inc. and shall not be reproduced in whole or in part without express written permission. Delta G Consulting Engineers, Inc. 707 N.E. 3rd Ave. Suite 200 Fort Lauderdale, FL 33304 (954) 527-1112 Tel. (954) 524-7505 Fax www.DeltaG.net PROJECT #: 1606XX PROJECT MANAGER: GSJ DESIGNED BY: GSJ C.A.ft: 00009181 DATE: 06/08/2016 i n J, t PROJECT #: 1606XX PROJECT MANAGER: GSJ DESIGNED BY: GSJ C.A.ft: 00009181 DATE: 06/08/2016