DRAWINGSr.Tiz_. F
0
♦
:DOLE
SLAB
ROD COUPLING
ALL THREAD ROD
ADJUSTABLE HANGER
RING (ALUMN. OR
GALVANIZED)
SWIVEL RING
PIPE SIZES 1" TO 4"
PIPE SIZE
ROD SIZE
TYPE OF
FASTENER
MIN. 'C'
DIM.
MAX. 'C'
DIM.
3/4"
3/8"
1-3/8" X 1-17/32"
DROP -IN ANCHOR
1/2"
1-5/8-
-5/8"1"
i 1P
5/8"
1-3/4-
-3/4"1-1/4"
1-1/4"
-13/16-
1 -7/8 -
1-1/2"
15/16"
2-
2-
1-3/16
2-3/8"
2-1/2"
1/2"
1-1/2" X 2-1/32"
DROP -IN ANCHOR
1-7/16"
2-3/4--
3-
1-3/4"
3 -1/4 -
3-1/2"
2"
3-5/8-
4-
5/8"
1-5/8" X 2-15/32"
DROP-IN ANCHOR
2-1/4"
3-7/8"
5"
2-3/4"
4-3/4"
6"
3/4"
1-3/4" X 3-1/4"
DROP -IN ANCHOR
3-5/16"
5 -1/2 -
8"
N/A
N/A
N/A
N/A
Fire Sprinkler Piping Plan
1 1
0
rm�
IE? SCHEDULE
1. NEW MECH TYPE
TEE.
2. EXISTING BRANCHLINE,
3, ARMOVER.*
4. 1" DROP.
** a4RMOVERS GREATER THAN 5. NEW FIRE SPRINKLER HEAD
24 IN LENGTH SHALL BE
SUPPORTED BY A HANGER.
ATTACH COUPONS FOR
FIELD INSPECTOR.
r • r - r. :
•
Obstruction
A
Elevation View
Positioning of Sprinklers to avoid
Obstructions to Discharge (SSU/SSP)
Distance from Sprinklers to
Side of Obstruction (A)
Maximun Allowable Distance
of Deflector above Bottom
of Obstruction (in.) (B)
Less than 1 ft
0
1 ft to less than 1 ft 6 in.
2%
1 ft 6 in. to less than 2 ft
3%
2 ft to less than 2 ft 6 in.
5%
2 ft 6 in. to less than 3 ft
7%
3 ft to less than 3 ft 6 in.
9%
3 ft 6 in. to less than 4 ft
12
4 ft to less than 4 ft 6 in.
14
4 ft 6 in. to less than 5 ft
16%i
5 ft to less than 5 ft 6 in.
18
5 ft 6 in. to less than 6 ft
20
6 ft to less than 6 ft 6 in.
24
6 ft 6 in. to less than 7 ft
30
7 ft to less than 7 ft 6 in.
35
Table 8.6.5.1.2 NFPA 13, ED. 2007
Figure 8.6.5.1.2(a)
NOTE:
FIRE SPRINKLER CUT SHEETS SHALL BE AVAILABLE
ON SITE FOR FIELD FIRE INSPECTOR.
4
5
NOTE:
®
24 IN OLENGTH SH LLRBEAN 4
~- SUPPORTED BY A HANGER.
Relocation Detail
NO SCALE
SCHEDULE
1. EXISTING UPRIGHT FIRE
SPRINKLER HEAD TO BE
REMOVED (UNLESS
WHERE INDICATED TO
BE RELOCATED)
2. NEW 1" ELBOW OR TEE
3. EXISTING 1' NIPPLE
4. EXISTING BRANCHLINE
5. NEW CONCEALED TYPE
SPRINKLER HEAD.
Ceiling or roof
V
Suspended or Floor -Mounted Obstruction
in Light Hazard Occupancies Only (SSU/SSP)
Horizontal distance (A)
Minimun Vertical
Distance below
Deflector (in.) (B)
6 in. or Less
3
More than 6 in. to 9 in.
4
More than 9 in. to 12 in.
6
More than 12 in. to 15 in.
8
More than 15 in. to 18 in.
9%
More than 18 in. to 24 in.
12X
More than 24 in. to 30 in.
15%
More than 30 in.
18
Table 8.6.5.2.2 NFPA 13, ED. 2007
Figure 8.6.5.2.2
CIENERAL_ NC:)TES
®ESCRIPTIC)ili
ALL PIPE TO BE:
CPUC XL 40
X
®ESIC AN CRITERIA
ally/
CLASSIFICATION:
OFFICE
HAZARD:
LIGHT HAZARD
MAX. HEAD COVERAGE:
SCC>PE C:>F= ®RIG
RELOCATED FIRE SPRINKLERS:
225
-
ADDED FIRE SPRINKLERS:
2
OUT PLUGGED:
ri<'LcffiK i e 3 mrv, g! Sa sftEs^t':,7 .,f NpfBy
ALL MATERIALS: HEADS, PIPE AND HANGERS
ARE PER NFPA 13.
L_EC'A*'ENQ
spry 4fWRM &;Sigrt-d for uce iti fighl i -g
EXISTING PIPE
Ordinary hoz4i ,,Qm:s_mWcs up r
:.cess s2}.'_hw.j%&nk3r;...f
NEW PIPE
i frfj?:fkfi V
NEW HANGER
Tf
NEW SPRINKLER
*N
NEW ARMOVER
o R
EXISTING SPRINKLER
E
CHANGE SPRINKLER TO NEW ONE
O CHN
f�� Pd C 6.0
&
%Y�4
O
SCHEDULE
1. EXISTING
DROP TO BE
3 REMOVED.
2. EXISTING BRANCHLINE.
3. 1" ARMOVER.*
4. 1" DROP.
5. NEW FIRE SPRINKLER HEAD
5 ** ARMOVERS GREATER THAN
24 IN LENGTH SHALL BE
® SUPPORTED BY A HANGER. FM
Typical Relocation Detail
NO SCALE
No. Date Revisions By Water Supply Information Design Criteria Sprinklers/ Spacing
1 10-8-13 SUBMIT FOR APPROVAL A.F. Static Pressure - System No. Symbol Qty Size K Temp Description SIN
Residual Pressure - Design Area Area #1 Area #2 O 8 1/2" 5.6 155 TYCO -QUICK RESPONSE WHITE TY -FRB SEMI REC PENDENT TY -3231
Pitot Reading - Density - -
Flow In G.p.m. - Design Area S.f. - -
Date Of Test - Psi Req'd @ City Main - Time Of Test - Gpm Req'd 0 City Main - -
Test Taken By _ Gpm Req'd 0 Basr - -
- No. Spkr. In Dsgn. Area - -
Hydrant Location - Elev. ® Highest Spkr - -
Domestic/outside Hose - -
8 Total This Sheet
- - Z101 .
J
ytdfir, �,.
jr � � b's�rsFf.€adfstu icHf+tat�.rs-fits.F:rsi?a
//%
Series ,, 5.6 K -factor
Uprights Pendent, and Recessed Pendent Sprinklers
Quick R4sp, > Standard coverage
Genera
r
Description
'F,ho TYCO vajfes fY-:FPB qpii*sr:
ond
ally/
t3iMsti.'a f •t 3 ;F v6£i'�f.,i?c3!£.^.£ � i#i iYi?>3 i�f3C-
The- TWO Saf f s Ra FRG6,6 €f facto-,
smen", as zaP .1s ,s,Mh Me- epp&,s_W6
Upright," ' 31,34) and PG•*rd,' z -m
vmdared of the-, 340'rfW Fire %M ^
spfi *J&'s934 r f s, d in lm#u da -:°a sshgAt
6frrs A os. defi3r .; # scid ust} istits-:
ara mri> e p -:Inset `dtaf,,JJxd t.,>3 W014+.3.
d&rd'f t3 ry L'f yr amm,,o,,,has h<3'/irg
ri<'LcffiK i e 3 mrv, g! Sa sftEs^t':,7 .,f NpfBy
%f ri3C1fw[1en, Fall. m ttn'.lk S`_> f7Y y%#i1:'�c'{i
spry 4fWRM &;Sigrt-d for uce iti fighl i -g
thA- Pbe`f.^.f'fYfrirna of u sq. " avwces.
Ordinary hoz4i ,,Qm:s_mWcs up r
:.cess s2}.'_hw.j%&nk3r;...f
TDi�.C�4fu:?
.{TAY A.''✓Oi?,Z>'f�"f�lrYii'f
i frfj?:fkfi V
fYJ thpefr f?tEe 7+GF t" a� FF?7f 2?3YS
Tf
dotd_'_' S e'tEifY.•�!r`i'riy'�•�c'3'Fs?tT'e��`✓.%�FfTf. f
FHSS Pae.dw'33 %0*re irp i 3-
3.e fss#� itef a unaraF fo �zY agnrsf'
?T 3s;71s 3f � fi X .�{z3'Sfi i38 7f.<� $riz�3
trs0 fs i 3 &_12 €0,r fa a r aFP VI'tb a
ally/
fifes �d C ff eg €nis sod ^
rtda
}.l f�'K �s fs2 7rfrs?x �#'s~'tzs tti9 f
yy
F
mm
$
..
l
Y�(
redii:-£fCr..Y 3., f4'�'f'•.3b Yit'
;><•r:
.;.% .'•iii%i.;
}i=l.��£
Ei tei # �r#3i F%t*:srPzs�d
Identificatiot
f �::;:i:::iL'ri.
7� � '
jriwfff
Number (SIMI
A two -pi &yc- 2D Rt- M*Sod//
�AXE
f aiif l ft t� Ft G
z ih {C e ff f� t'
f�� Pd C 6.0
&
%Y�4
0:
f
T�'e
Technical
,Rkx' ,_-;ed 3 tfir 3�rSf3 FL�Cf£3 G•S dti�
3,azufaayt > t'hkll ImefiYi-E£3 $.3r7� dr-"Pi3
Data
f�iivt'F:T�'
'Sprit Malufa dims
},£
tr e iiJf Yr+ st be cut.
&, 0i ,,Fr rn;,-
Plated, Pufrr kFNte fRA1_
fciie rta ata 14,4 vans rsr of SGr.ea
AP} riwa€s
Sizz £a Whft-PA€.� 0.3
TY FPEi ap,,WW539m -w* .4fac;n' ad .3l
L aiid #.,, t L Listed
i.:ee.n,
Te-i'k is.1. 7t.2. 812a�'f Tp -,,57 ?.✓?.i'i-
A %ndWS Appved
Ut rri'{3Yfi PlAt@ , ±'Y".. Brass %Wd
Mer '{4 aM_", dttt",Fit's>;•s3
amf nLM! Data -ShAW T 77_0.
mrFY.3?23um SJ�rf�YS F� : s3 �-5 iiYh-
FraF^� . , s7 nza
1755 ru, ,"#•`.$_,"4 %Ykf'S
, ....
2V3 Psi 117 i afll'
JRslf;; AS.ebFnh,u, . 3 £avu
.
"#''nnf'34 fN'xu'FT. IlZ'Xfvt /�:�„`: nrTS T . �rJ` }i✓
YT >3.32FiYjF1G F-. fts # •fF :f;u tiF%-
3e111 PI'aw
tx3"Yf. ..i^ •:rte
uL. t.,'Y4_Y_;a �S.f L1L. s:%7 ...... 2,4li'f}Te
i4f POPPTdiNT
DiWiasge i fi�4fr £iFet
�•3ifay-3 -94-w to Tw �7ma* -sata
� �,^> a�f11 }•,wi3 � < � e � l.:P.3.r,..af :!,c
Sir -et T>✓b'7rV fir thr, (NSTi`�.f.j ER
SSS#3} FFPi F iYR i£fF'S :
`VARxJ,1PJG that ;:.rnvk--'a_3 ce '3h7�3
Seith-t'E�^.7"..'�£ to hwndGh_,< and
fift<clis3f�4[ si3 r.�.TsSfrkari i�sa?3is and
.}
17P11F' (r't Ci
z.z'f23'�r its f3� {%i3Va 63r'GSST<g41iId
G"i)UIp Sryi"< t`..:.
s> ��,s �,�t,,,^^� afa N�if:r>�r.�•s?:?� c��rr �
r ,s
cr 1t:3 comp. hff;.ts
tai fott to
�
apem, is hn a lira c;tt. iiia<z or cr ztas ,;,
fe rs; ar.,te Exert, i s f
Page i of 4
JA- NUARY 2012
TFP S 72
7950 N.W. 53rd Street #215
Doral, Florida 33166
Ph -Fax -Voice mail: 1.888.351.2672
State Certification # 20775800012010
Project
BOYNTON BEACH MALL
UNIT 879
BOYNTON BEACH, FLORIDA
Contract Ylith:
System No. 1 Date' 10-8-13
Drawn W. AFire Sprinklers Sale: 1/4'= 1'-0"
chWWea By: AFire Sprinklers AW' City of Bo on Beach
Total A/S: 8
Contract No. 2013 FP -1 Of 1