DRAWINGSRio SCOPE OF WORK This project involves the installation of a new addressable type fire alarm system. The system includes a control panel, manual pull stations, sprinkler system monitoring and notification devices as shown. The control panel and power supply will be installed in a mechanically ventilated space and protected by a smoke detector. Each residential unit will be equipped with notification devices inside the bedrooms. Audio visual notification devices and pull stations will be mounted on the outside of the building as shown on the plans. The system will be monitored by a central station via a wireless transceiver mounted by the pane! The system is to be installed to the current codes and standards. BUILDING DESCRIPTION This is a three story, 32 unit multi -family residential building with individual entrances to each units. GENERAL NOTES 1. ALL WIRE IS "POWER LIMITED." 2. ALL WIRING AS APPLICABLE SHALL BE: 14/2, 18/2, UL, FPLR CABLE. 3. INSTALLATION SHALL COMPLY WITH THE 2010 FLORIDA FIRE PREVENTION CODE (FFPC). 4. INSTALLATION SHALL COMPLY WITH NFPA 72 2007, ALL APPLICABLE CHAPTERS. 5. INSTALLATION SHALL COMPLY WITH NFPA 101, PART OF 2010 FLORIDA FIRE PREVENTION CODE (FFPC). 6. INSTALLATION SHALL COMPLY WITH NEC 2008, ALL APPLICABLE CHAPTERS. 7. CONDUIT AS REQUIRED SHALL BE 1/2" OR 3/4" EMT OR PVC RACEWAY SIZED FOR MAXIMUM OF 40% WIRE FILL, OR WIREMOLD RACEWAY SIZED PER NEC FOR MAXIMUM OF 40% WIRE FILL. 8. SYSTEM SHALL BE GROUNDED PER MANUFACTURERS SPECIFICATION AND THE NEC 2008 ARTICLE 250 9. ALL VISUAL DEVICES SHALL BE MOUNTED @ 80" AFF TO BOTTOM OF LENS PER 2010 FBC, CHAPTER 11 & 2007 NFPA 72. 10. SYSTEM COMPONENTS SHALL BE UL LISTED, COMPATIBLE AND SUITABLE FOR FIRE SERVICE USE. 11. COST OF THE PROJECT IS GREATER THEN $5,000. 12. THE FIRE ALARM EVACUATION SIGNAL SHALL BE PER NFPA 72, 2007 & STATE OF FLORIDA BUILDING CODE 2010 EDITION. 13. ALL FIRE/ SMOKE PARTITION PENETRATION(S) SHALL BE SEALED AS REQUIRED. WITH LISTED APPROVED FIRESTOP COMPOUND, TO MATCH PENETRATED STRUCTURE(S) FIRE RATED. 14. THE NOTIFICATION SYSTEM SHALL BE 75 db MINIMUM OR 15 db ABOVE AMBIENT, WHICHEVER IS GREATER PER NFPA 72. 15. THE NOTIFICATION APPLIANCE CIRCUITS ARE CLASS B- STYLE Y. 16. THE FACP IS ADDRESSABLE AND SUPPORTS A TOTAL OF 60 DEVICES PER SLC CIRCUIT. 17. THIS FIRE ALARM SYSTEM IS CERTIFIED AS "CENTRAL STATION SERVICE" 18. CEILING HEIGHTS ARE LESS THAN 10 FEET UNLESS OTHERWISE NOTED. O SYMBOL LEGEND SYMBOL MODEL DESCRIPTION FACP MIRCOM � O O FX -350 -60 -DR FIRE ALARM CONTROL PANEL 1 FAAP MIRCOM FIRE ALARM ANNUNCIATOR PANEL w/ BB-1001WP H RAM-300-LCDR BACK BOX 1 3030700 DSC 3 11 A ma 3G3070CF WIRELESS COMMUNICATOR 1 [-I MIRCOM y O MIX -3100 SMOKE DETECTOR 1 wp MIRCOM MS-7101DU MANUAL PULLSTATION w/ BB -700 WP BACKBOX 12 AND MIX -101P ® MIRCOM MIX -101P MINI MONITOR MODULE 2 CM MIRCOM 777 4� MIX -100S SUPERVISED CONTROL MODULE 1 SENSOR OSYSTEM B BL -10B FLOW BELL 1 75cd N< MIRCOM WEATHER FHS -340R -WP PROOF HORN/STROBE 1 2 wp MIRCOM MH MH -25W MINI HORN 40 1 EARTHGROUND, NFPA 72. COMPLY WITH NEC CONNECTION TO APPROVED, DEDICATED 120VAC-fi- 120VAC SOURCE DEDICATED BREAKER COMPLY WITH NFPA 72. WITH MINI TAMPER MONITOR MODULE SWITCH (BY OTHERS) 1 WITH MINI FLOW MONITOR MODULE SWITCH (BY OTHERS) 1 WIRE LEGEND 2/18 THHN/THWN SLC INITIATING CABLE FOR PULL STATIONS AND OTHER INITIATING 2/16 AWG L HORN/STROBE THHN/THWN IN CONDUIT 2/1s AWG P FAAP POWER THHN/THWN IN CONDUIT THE ACTIVATION OF THE FIRE ALARM INITIATING DEVICES SHALL AUTOMATICALLY INITIATE THE FUNCTIONS AS ! DETAILED BELOW. A. MANUAL FIRE ALARM PULL STATION - ACTIVATION OF THE MANUAL FIRE ALARM PULL STATION SHALL INITIATE THE FOLLOWING FUNCTIONS: 1. GENERATE AN AUDIBLE SIGNAL AT FIRE ALARM CONTROL PANEL. 2. GENERATE ANAUDIBLE ALARM SIGNAL BY MEANS OF A HORN/STROBE DEVICES ON THE OUTSIDE OF THE BUILDING AND MINI HORNS IN THE INDIVIDUAL UNITS. 3. INDICATE THE ALARMED ZONE ON THE FRCP. 4. TRANSMIT ALARM SIGNAL TO LISTED CENTRAL STATION SERVICE. B. SMOKE DETECTORIHEAT DETECTOR - ACTIVATION OF THE SMOKE DETECTORS SHALL INITIATE THE FOLLOWING FUNCTIONS: 1. GENERATE AN AUDIBLE SIGNAL AT FIRE ALARM CONTROL PANEL. 2. GENERATE AN AUDIBLE ALARM SIGNAL BY MEANS OF A HORN/STROBE DEVICES ON THE OUTSIDE OF THE BUILDING AND MINI HORNS IN THE INDIVIDUAL UNITS. 3. INDICATE THE ALARMED ZONE ON THE FACP. 4. TRANSMIT ALARM SIGNAL TO LISTED CENTRAL STATION SERVICE. C. TROUBLE SIGNAL 1. TROUBLE AND SUPERVISORY DEVICES SHALL NOT ACTIVATE AUDIBLE AND VISIBLE DEVICES, INSTEAD THEY SHOULD SHOW A SUPERVISORY OR TROUBLE INDICATION AT FACP AND REMOTE ANNUNCIATOR IF INSTALLED. A TROUBLE SIGNAL COULD INDICATE A BREAK IN THE CIRCUIT WIRING OR A DETECTOR THAT IS NOT OPERATING PROPERLY. 2. WHEN ALARMED, TRANSMITS A TROUBLE SIGNAL TO THE FACP AND LISTED CENTRAL STATION SERVICE D. TAMPER SWITCHES (VALVE SUPERVISORY SWITCHES) OPERATION: 1. GENERATE AN AUDIBLE SIGNAL AT FIRE ALARM CONTROL PANEL. 2. GENERATE AN AUDIBLE SUPERVISORY SIGNAL 3. INDICATE THE SUPERVISORY ZONE ON THE FACP. 4. TRANSMIT SUPERVISORY SIGNAL TO LISTED CENTRAL STATION SERVICE. A. FLOW SWITCH ACTIVATION 1. GENERATE AN AUDIBLE SIGNAL AT FIRE ALARM CONTROL PANEL. 2. GENERATE AN AUDIBLE ALARM SIGNAL BY MEANS OF A HORN/STROBE DEVICES ON THE OUTSIDE OF THE BUILDING AND MINI HORNS IN THE INDIVIDUAL UNITS. 3. INDICATE THE ALARMED ZONE ON THE FACP. 4. TRANSMIT ALARM SIGNAL TO LISTED CENTRAL STATION SERVICE. 5. ACTIVATE THE FLOW BELL (NON SILENCABLE) B. FLOW BELL OPERATION 1. FLOW BELL SHALL SOUND UPON ACTIVATION OF FLOW SWITCH ONLY. 2. FLOW BELL SHALL SOUND AS LONG AS WATER IS FLOWING. 3. FLOW BELL SHALL NOT BE CAPABLE OF BEING SILENCED FROM FACP. AREA OF WORK -I SITE MAP Bul cling 2307 SL C € 10 II? -Rs .tCT E MMRED: 1N,0Er G 0I?N,D p STEEL GONDING E. All Electrical rshall comply with the 20 u9 National Electrical No. I REVISIONS O Q � O O co c Nil Zw yz Fu u,<3 v� H W f t.Fi, ^ Z o w 3 11 A ma O 04 c p [-I cr) y u O NW 21 PROJECT 777 4� THE ACTIVATION OF THE FIRE ALARM INITIATING DEVICES SHALL AUTOMATICALLY INITIATE THE FUNCTIONS AS ! DETAILED BELOW. A. MANUAL FIRE ALARM PULL STATION - ACTIVATION OF THE MANUAL FIRE ALARM PULL STATION SHALL INITIATE THE FOLLOWING FUNCTIONS: 1. GENERATE AN AUDIBLE SIGNAL AT FIRE ALARM CONTROL PANEL. 2. GENERATE ANAUDIBLE ALARM SIGNAL BY MEANS OF A HORN/STROBE DEVICES ON THE OUTSIDE OF THE BUILDING AND MINI HORNS IN THE INDIVIDUAL UNITS. 3. INDICATE THE ALARMED ZONE ON THE FRCP. 4. TRANSMIT ALARM SIGNAL TO LISTED CENTRAL STATION SERVICE. B. SMOKE DETECTORIHEAT DETECTOR - ACTIVATION OF THE SMOKE DETECTORS SHALL INITIATE THE FOLLOWING FUNCTIONS: 1. GENERATE AN AUDIBLE SIGNAL AT FIRE ALARM CONTROL PANEL. 2. GENERATE AN AUDIBLE ALARM SIGNAL BY MEANS OF A HORN/STROBE DEVICES ON THE OUTSIDE OF THE BUILDING AND MINI HORNS IN THE INDIVIDUAL UNITS. 3. INDICATE THE ALARMED ZONE ON THE FACP. 4. TRANSMIT ALARM SIGNAL TO LISTED CENTRAL STATION SERVICE. C. TROUBLE SIGNAL 1. TROUBLE AND SUPERVISORY DEVICES SHALL NOT ACTIVATE AUDIBLE AND VISIBLE DEVICES, INSTEAD THEY SHOULD SHOW A SUPERVISORY OR TROUBLE INDICATION AT FACP AND REMOTE ANNUNCIATOR IF INSTALLED. A TROUBLE SIGNAL COULD INDICATE A BREAK IN THE CIRCUIT WIRING OR A DETECTOR THAT IS NOT OPERATING PROPERLY. 2. WHEN ALARMED, TRANSMITS A TROUBLE SIGNAL TO THE FACP AND LISTED CENTRAL STATION SERVICE D. TAMPER SWITCHES (VALVE SUPERVISORY SWITCHES) OPERATION: 1. GENERATE AN AUDIBLE SIGNAL AT FIRE ALARM CONTROL PANEL. 2. GENERATE AN AUDIBLE SUPERVISORY SIGNAL 3. INDICATE THE SUPERVISORY ZONE ON THE FACP. 4. TRANSMIT SUPERVISORY SIGNAL TO LISTED CENTRAL STATION SERVICE. A. FLOW SWITCH ACTIVATION 1. GENERATE AN AUDIBLE SIGNAL AT FIRE ALARM CONTROL PANEL. 2. GENERATE AN AUDIBLE ALARM SIGNAL BY MEANS OF A HORN/STROBE DEVICES ON THE OUTSIDE OF THE BUILDING AND MINI HORNS IN THE INDIVIDUAL UNITS. 3. INDICATE THE ALARMED ZONE ON THE FACP. 4. TRANSMIT ALARM SIGNAL TO LISTED CENTRAL STATION SERVICE. 5. ACTIVATE THE FLOW BELL (NON SILENCABLE) B. FLOW BELL OPERATION 1. FLOW BELL SHALL SOUND UPON ACTIVATION OF FLOW SWITCH ONLY. 2. FLOW BELL SHALL SOUND AS LONG AS WATER IS FLOWING. 3. FLOW BELL SHALL NOT BE CAPABLE OF BEING SILENCED FROM FACP. AREA OF WORK -I SITE MAP Bul cling 2307 SL C € 10 II? -Rs .tCT E MMRED: 1N,0Er G 0I?N,D p STEEL GONDING E. All Electrical rshall comply with the 20 u9 National Electrical No. I REVISIONS O Q � O O co c Zw H W Z o w F4 � O 04 z o p [-I cr) E-+ O 0 PROJECT 0 0 co co LL Q � o cocc Orn W cn N z CV a- J �n O J W 00 U_ o =M a W N a N t7 -M W 0 >W OG � W a = a I- LL 'z N 0 i z � r Q00 M QUALIFIER Name: JORGE ALVEREZ License #: EC 13005215 QJ Of Z Q CD Z QU v� � Q M =wLL irz< z:) Z < (DwF� ENGINEER t - Seal Drawn By: A.W Date: 04/07/14 Scale: 1/8"= V-0" nCOV itle: ER SHEET No: Sheel FA -00)] DEN LIVING AND DINING ROOM W.I.0 S1-1 HM MASTER BEDROOM M. BATH CL KITCHEN VZ� LA > 1-.1w p S1-5 F wp 75cd W/D S1-2 BEDROOM MH FRCP W.I.0 BATH 1-1 ELEC RM. S2-W.I.0 BATH , MH BEDROOM LIN F-W�, C 1-2 F A/C Wp LIVING AND DINING ROOM n KITCHEN M. BATH 7�S2-2 MASTER --,BEDROOM CLI I W.I.0 (1 FIRST FLOOR FIRE ALARM PLAN NORTH SCALE: 1/8"=1'-0" S3-13 75cd DICF S4-13 UP 75cd F wP � 1-. 4 ANNUNCIATOR I NEMA -4X ENCLOSURE S3-4 — W.I.0 S1-6 MH HM MASTER DEN DEN MASTER BEDROOM BEDROOM M. BATH M. BATH SCREENED SCREENED F1 PATIO CL CL PATIO UP KITCHEN UP LIVING AND LIVING AND KITCHEN DINING ROOM DINING ROOM CL CL BEDROOM BEDROOM A/C LANG AND A/C S1-9 HM S3-7 DINING ROOM LIVING AND MH DINING ROOM MASTER MASTER :j CL BEDROOM BEDROOM CL S1-10 F 8 � 75cd W/D 75cdVP WP A/C CL oo 7CL A/C II WP S3-8 W/D BEDROOM 1-5 S3-5 S1-7 UN II KITCHEN o0 Oo II UN BEDROOM MH MOO KITCHEN HM BATH Oo i W.I.0 i ' w.I.0 I W.I.0 I W.I.0 I BATH W/D BATH W.LC W.I.0 BATH W/D UN UN W/D UN I I I I I I I I [kUN W/D BATH W.I.0 W.I.0 BATH we -I W.I.0 I I W.LC I I W.I.0 ( I W.I.0 ( BATH e0 S4-5 S2-7 BATH HM BEDROOM MH UN II o0 = = O° II UN BEDROOM KITCHENKITCHEN S2-10 I I A C N 41 CCIL A/C (I 1-7 wp / CL � a, F 75cd W/D W/D 75cd F WP S4-8 1-76 CL L t CL MASTER MASTER r2-9 BEDROOM BEDROOM S4 - MH H LIVING AND A/C BEDROOM A/C DINING ROOM LNG AND BEDROOM DINING ROOM CL CL LANG AND DINING ROOM KITCHEN KITCHEN UP LMNG AND UP DINING ROOM SCREENED CL CL SCREENED L LLLLL PATIO PATIO L LLLL L _rLLLLL JJJL J LLLLLLLL, JJJJJ_ J I " 4JJJJJ�_ 4 M. BATH SCREENED 4-4-44-44-44d- L PATIO SCREENED M. BATH LLLLLLLL PATIOS MH LLLLLLLL JJJJJJJJJ MASTER LLLL JJJJJJJJJ MASTER LLLL JJJJJJJJJ S2-6 BEDROOM LLLL JJJJJ BEDROOM JJJJJ xM JJJJ4 JJ -4J SECOND FLOOR FIRE ALARM PLAN wJ.c CL LLLL JJJJJ CL W.I.0 JJJJJ LLLL NORTH SCALE: 1/8"=1'-0" POWER CONTROL MODULE SUPERVISED FLOW BELL DATA MIX -100S SUPERVISED CONTROL MODULE WIRING DETAIL �� � � `�� - F 2 2014 No. REVISIONS 0 Q Z�- coz O W co CO V z u) ar F= -I H W O U W O z o O z C\2 z PROJECT O CN O co J L.L 0 0 0C Lu o N Q N O J M W "Lj- = OLL C;> O Lu a <-9 N 7' 4 O c.i og z 6 CD wM W 0 >W Qo � =a N o z sz � :z 00 M QUALIFIER Name: JORGE ALVEREZ License #: EC 13005215 J z Z 0, C5 O M wW, W w LL - w (D H o ¢_ (D F-- ENGINEER Seal Drawn By: AMDate: 04/07/14 Scale: 1/8"= 1 0-0" Sheet Title: 1ST & 2ND FL. CTS, ��. `v,owrSheet No: IFA -01 1SLC 1 Sf LC 1SLC 1 SC I L 1 16 wp 1r 1 wP �) 1-14,,p THIRD -FLOOR ------------------------------------------------------------ --- - SECOND FLOOR 1SLC 1SLC 1SLC 1SLC 1-12 wp 1-11 wp 1-10 wp wp F F F F1 -g SECOND FLOOR --------------------------------------------- -- -- FIRST FLOOR 1SLC 1SLC 1SLC 1SLC 1SLC 1SLC 1SLC 1-8 wp 1-7 wp 1-5 1-4 1-3 wp 1-2 wp 1-1 F F MM MM F F g TS FS TRANSCEIVER FOR WIRELESS TRANSMISSION TO THE CENTRAL STATION. 75cd S1-11 S1-12 S1-13 9 r ,A, wP L 75cd S2-11 S2-12 S2-13 9 �z ,A wP 1L 1L --------------------------------------------------------------------------------- 75cd 75cd S1-10 S1-9 S1-8 S1-7 S1-6 S2-10 S2-9 S2-8 S2-7 S2-6 wp A. ,.,, f, l9 _v_ WP a v _sz S7_ 1L ----------------------------------------------- 75cd S1-1 S1-2 S1-3 S1-5 S117-4 9 99 9 - wP 120VAC 3G3070CF MIRCOM FX -350 -60 -DR 120vaC FACP T r1 1SLC+P NEMA 4X 1L ENCLOSURE FAAP ANNUNCIATOR ------------------------------- 75cd S2-1 S2-2 S2-3 S2-4 S2-5 wp MH MH MH MH 24V FLOW BELL r 1 L 1L 75cd S3-1 S3-2 S3-3 ,z �z _v_wP 75cd S4-1 S4-2 S4-3 9 9 _v_wP ---------------------------------------------------------------------------------------------------- 1L 75cd 75cd S3-8 S3-7 S3-6 S3-5 S3-4 S4-8 S4-7 S4-6 S4-5 S4-4 I&wp A 9 9 9 ,A, WP _v_ _�z S7 n L -------------------------------------------- - 1L 75cd S3-9 S3-10 S3-11 S3-12 S3-13 9 9 9 �vl _wP -------------------- 75cd S4-9 S4-10 S4-11 S4-12 S4-13 ri rQ, WP THIRD FLOOR -------------- —1L SECOND FLOOR SECOND -FLOOR FIRST FLOOR I IV „ SEP 2 4 214 --ARE-P COPY S L m PV1si No. REVISIONS O Q z I,-' CO O co CO � z � w w Q � � o � U w � O z o p E—' CO E-, O 0 =PRJECT 0 N O M M J LL Q OC) cf)O W mrn Z N rn Lu 0 O� U) o = w� a- N 08 Z N LO WM W >W Q o "Z N 0 a z a�00 M QUALIFIER Name: JORGE ALVEREZ License #: EC 13005215 Lu o J Z Q Z U Z U o of < M �W U- w �- �M o Q wrl_M ENGINEER Seal Drawn By: AM Date: 04/07/14 Scale: 1/81$=J,—O" Sheet Title: 3RD FL. & RISER Sheet No: FA -02_ Ceiling mounted smoke/heat detector 24' Min handicap bedroom strobe Sycronized more than one appliances in any field of view, spaced a minimum of 55' from each other in rooms 80'x 80' or greater NFPA 72 2007 EDITION SECTION A-4-4.4.1.1(.1) 80' Minimum 6' below ceiling whichever is lower FBC. 11-4.28.3 (4).(6) 3' (Min) Audio/Visual & Visual only devices A/C supply difuser Note: Verify exact mounting requirements Accepted with manufactures data sheets. Manual pull - station 48" Max (ADA) NFPA 72 2007 EDITION (SECTION 2-8.1 ) FBC. 114.28.3 ).(4).(6) Scale: N.T.S System No. W -L-2241 F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 0, 1/4, 1 and 1-3/4 Hr (See Item 2) L Rating At Ambient - Less Than 1 CFM/sq it L Rating At 400 F - Less Than 1 CFM/sq ft r-- A 3 I 2 3 2 I 1 1B L.A Section A -A 1. Wall Assembly -The 1 or 2 hr fire -rated gypsum board /stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design.Diam of opening to be 1 in. to 1-1/8 in. (25 to 29 mm) larger than outside diam of pipe. The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrant - One nonmetallic pipe, conduit or tube to be installed eccentrically or concentrically within the firestop system. Pipe, conduit or tube to be rigidly supported on both sides of the wall assembly. The following types and sizes of nonmetallic pipes, conduits and tubes may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. Annular space shall be min 0 in. ( 0 mm, point contact) to max 1 in. (25 mm). B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) SDR 13.5 or Schedule 80 CPVC pipe for use in closed (process or supply) piping systems. Annular space shall be min 0 in. (0 mm, point contact) to max 1 in. (25 mm). C. Rigid Nonmetallic Conduit+ - Nom 2 in. (51 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with Article 347 of the National Electrical Code (NFPA 70). Annular space shall be min 0 in. ( 0 mm, point contact) to max 1 in. (25 mm). D. Electrical Nonmetallic Tubing+ - Nom 2 in. (51 mm) diam (or smaller) PVC tubing installed in accordance with Article 331 of the National Electrical Code (NFPA 70). Annular space shall be min 0 in. (0 mm, point contact) to max 1 in. (25 mm). E. Cross Linked Polyethylene (PEX) Tubing - Nom 1 in. (25 mm) diam (or smaller) SDR9 PEX tubing for use in dosed (process or supply) piping systems. Annular space shall be min 0 in. ( 0 mm, point contact) to max 1 in. (25 mm). F. Acrylonitrile Butadiene Styrene (ABS) pipe - Nom 1-1/2 in. (38 mm) diam (or smaller) Schedule 40 solid -core or cellular core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. Annular space shall be min 1/4 in. (6 mm) to max 3/4 in. (19 mm). When Item 2A or 2B is used, the T Rating is 1/4 hr. When Item 2C, 2D, or 2E is used, the T Rating is 1 hr and 1-3/4 hr for 1 hr and 2 hr fire rated walls, respectively. When Item 2F is used, T Rating is 0 hr. 3. Fill, Void or Cavity Material* -Sealant -Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of wall assembly. At point contact location, min 1/4 in. (6 mm) diam bead of fill material applied at nonmetallic pipe/gypsum board interface on both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant or Type WF300 Firestop Caulk (for wood studs only) *Bearing the UL Classification Mark Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. u1 STI Created or Revised: June 17, 2010 e ` W -L-224 (800)992-1180 • (908)5268000 • FAX(908)231-8415 - E-MaiCte&wrv@stilimstop.can - Websfte. a .stMmstop.com PAGE ff 1 System No. C -AJ -1353 F Rating - 3 Hr T Rating - 0 Hr L Rating At Ambient - Less Than 1 CFM/Lin Ft L Rating At 400*F - Less Than 1 CFM/Lin Ft ( A 2 4 4B 3 I - A Section A -A 1. Floor or Wall Assembly - Lightweight or normal weight (100-150 pd or 1600-2400 kg/m3) concrete floor or wall. Min thickness of concrete is shown in table in Item 4B. Floor may also be constructed of any min 6 in. (152 mm) thick hollow -core Precast Concrete Units*. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 14 in. (356 mm). Max diam of opening in floors constructed of hollow -core is 7 in. (178 mm). See Concrete Blocks (CAZT) or Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers. 2. Steel Sleeve - (Optional) - Nom 14 in. (356 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe or No. 26 ga (0.022 in. or 0.56 mm thick) sheet steel sleeve with square anchor flange spot welded to the sleeve at approx mid -height. Sleeve cast or grouted in place flush with floor or wall surfaces. Steel pipe sleeve may project a max of 2 in. (51 mm) beyond the floor or wall surfaces. 3. Through Penetrant - One metallic pipe, conduit or tube to be installed eccentrically or concentrically within the firestop system. The annular space between the pipe, conduit or tube and the periphery of the opening shall be min 0 in. ( point contact). The max annular space is 1 in. or 2 in. (25 or 51 mm) as shown in the table in Item 46 . Pipe, conduit or tube to be rigidly supported on both sides of the floor or wall assembly. The following types and sizes of metallic pipes, conduits and tubes may be used: A. Steel Pipe - Nom 12 in. (305 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe - Nom 12 in. (305 mm) diam (or smaller) cast or ductile iron pipe. C. Conduit - Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit, nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing (EMT) or nom 4 in. (102 mm) diam (or smaller) flexible steel conduit. Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: May 26, 2009 SC -AJ -135 STI (800)992-1180 •(908),5268900- FAX(908)231-8415 - E-Mail:tedrserv@sdmstop.com• WebsitamwwStifirestop.wm PAGE Cif 2 5' Never here Wall mounted smoke/heat de OI Finished wall System No. W -J-1098 F Rating - 2 Hr T Ratings - 1/4, 3/4 and 1 Hr (See Item 2) r+A I 3 I 2 I l I-+- A Section A -A 1. Walt Assembly Min 6 in. (152 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 2 in. (51 mm) larger than OD of through penetrant. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names or manufacturers. 2. Through Penetrant One metallic pipe, conduit or tube to be installed eccentrically or concentrically within the firestop 9 PP Y Y e p system. Pipe, conduit or tubing may be installed at an angle not greater than 45 degrees from perpendicular to the wall surface. The annular space between the pipe, conduit or tube and the periphery of the opening shall be min 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe, conduit or tube to be rigidly supported on both sides of the wall assembly. The following types and sizes of metallic pipes, conduits and tubes may be used: A. Steel Pipe Nom 8 in. (203 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Iron Pipe Nom 8 in. (203 mm) diam (or smaller) cast or ductile iron pipe. C. Conduit Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit, nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing (EMT) or nom 4 in. (102 mm) diam (or smaller) flexible steel conduit. D. Copper Pipe Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe. E. Copper Tube Nom 4 in. (102 mm) diam (or smaller) Type L (or heavier) copper tube. Note: Measurements shown are to the closest of the detector 80" A.F.F. OR 6" BELOW CEILING (M) (WHICHEVER IS LOWER) Type of Penetrant Max Diam T Rating Steel or iron pipe, steel conduit or EMT 2 in. (51 mm) 1 hr Steel or iron pipe, steel conduit or EMT 8 in. (203 mm) 3/4 hr Copper pipe or tube 4 in. (102 mm) 1/4 hr 2A. Through Penetrating Product* -Flexible Metal Piping As an alternate to Item 2, one nom 1-1/4 in. (32 mm) diam (or smaller) steel flexible metal pipe to be installed either concentrically or eccentrically within the firestop system. The annular space between the pipe and the periphery of the opening shall be min 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe to be rigidly supported on both sides of the wall assembly. When flexible metal piping is used, T Rating is 1 hr. OMEGA FLEX INC TITEFLEX CORP A BUNDY CO WARD MFG INC 3. Fill Material* -Sealant Min 5/8 tri. 16 mm thickness offill Void or Cavity Mater a ( ) s o I material applied within annulus, flush with both surfaces of wall assembly. At point contact location, min 1/4 in. (6 mm) diam bead of fill material applied at metallic pipe/concrete interface on both surfaces of wall. SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant *Bearing the UL Classification Mark Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. U` STI Created or Revised: September 24, 2004 (800)992.1780 .(908),52&80W•FAX(908)231-6415 • E-Makro&&&@sf estop.am-Websitewww.stifirestop.com PAGE CIF D. Copper Pipe - Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe. E. Copper Tube - Nom 4 in. (102 mm) diam (or smaller) Regular L (or heavier) copper tube. 3A. Through Penetrating Product* - Flexible Metal Piping - As an alternate to Item 3, one nom 2 in. (51 mm) diam (or smaller) flexible steel pipe (with or without plastic jacketing) to be installed either concentrically or eccentrically within the firestop system. The annular space between the pipe, conduit or tube and the periphery of the opening shall be min 0 in. ( 0 mm or point contact). The max annular space is 1 or 2 in. (25 or 51 mm) as shown in the table in Item 4B. Pipe to be rigidly supported on both sides of the floor or wall assembly. OMEGA FLEX INC GASTITE, DIV OF TITEFLEX WARD MFG L L C 4. Firestop System - The firestop system shall consist of the following: A. Packing Material - When required as shown in the table in Item 4B, min 4 pd (64 kg/m3) mineral wool batt insulation compressed and tightly packed to min 2-1/4 in. (57 mm) thickness. Packing material recessed from top surface of floor or both surfaces of wall as required to accommodate fill material (Item 4B). When packing material is shown as being optional, mineral wool or glass fiber insulation or polyethylene foam backer rod may be used as a permanent form to facilitate installation of the fill material. In floors constructed of hollow -core Precast concrete units, packing material to be recessed from both top and bottom surfaces of floor, as required to accommodate fill material (Item 4B). When steel sleeve projects from top of floor or from both sides of wall, the thickness of mineral wool batt packing material should be increased by an amount equal to the distance that the sleeve extends past the floor or wall surface. B. Fill, Void or Cavity Material* - Sealant- Fill material applied within annulus, flush with top surface of floor assembly or top edge of steel sleeve. In walls and in floors constructed from hollow core precast concrete units, fill material applied symmetrically on both sides of assembly flush with wall/floor surfaces or both ends of steel sleeve. At point contact location, apply min 1/4 in. (6 mm) diam bead of fill material at pipe/cencxete interface or pipe/steel sleeve interface on top surface of floor or both surfaces of wall or precast concrete units. The fill material thickness shall be as specified in the following table: Min Concrete Max Min Fill Thickness Steel Annular Space, Packing Material Thickness F Rating in. mm Sleeve in. mm Material in. mm 2-1/2(64) Optional 2 (51) Required 1/4(6) 3 hr 4-1/2(114) Optional 1 (25) Optional 1/2(13) 2 hr SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant *Bearing the UL Classification Mark Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. U STI Created or Revised: May 26, 2009 800 1180 . (908)526 -Bt # FAX(908)2314415 . E o can • webshe:www.stMrestop.com C -A1-135 ( �- dMalae�v�fireSt D� PAGE � 2 STROBE OR HORN/STROBE PULL STATION 48" A F.F. --r- System T ADA HEIGHT REQUIREMENTS Nn CAI F Voltage Drop and Battery Calculations 1 0.2200 0.3800 0.22000 0.38000 S:1 S:2 S:3 S:4 AUX AUX 0.04000 Device Type MilliAmps/Dev 14 0.0006 0.0046 0.00840 0.06440 MIX -3100 Photo Detector Total FHS -340R -WP (75cd mid volume horn/strobe) 220 3 3 3 3 0 0 12 MH-25R/MH-25W Mini Horn 17 10 10 10 10 0 0 40 BL -10B 10" Motorized Bell 20 0 0 0 0 1 0 1 --------------------- 0 0 0 0 0 0 0 0 -------------------- 0 0 0 0 0 0 0 0 -------------------- 0 Total AH =___» 6.22 0 -------------------- 0 -c5 00 0 Total Devices Battery provided may be larger than the size listed Total Current depending on availability at the time of installation. Wire Guage Large batteries may need external battery cabinet. Ohm/K Estimated Length Voltage Drop 13 13 13 13 1 0 53 0.83 0.83 0.83 0.83 0.02 0 3.34 16 16 16 16 1 16 16 4.89 4.89 4.89 4.89 4.89 4.89 300 1 350 1 400 450 0 0 2.44 1 2.84 r 3.25 3.65 N/A 0-00 FX Series Qty IStandbyl Alarm l Standby) Alarm FX -350 -60 -DR/ FX -350 -126 -DR FX -350 -378 -DR 1 0.2200 0.3800 0.22000 0.38000 RAM -300- LCDW/R 00 CO 1 0.0160 0.0400 0.01600 0.04000 MIX -101 P Mini Module 14 0.0006 0.0046 0.00840 0.06440 MIX -3100 Photo Detector Z o 1 0.0004 0.0034 0.00040 0.00340 MIX -100S Supervised Control Module t` O 1 0.0010 0.0010 0.00100 0.00100 N g LO J rn Standby. 24 Hours Totals 0.24580 0.48880 Alarm 5Min!VNACs x Pwr W co O N N 06 4 Z LO 3.340 LO W rn UJ UJ.- Q Totals 0.246 3.829 D_ AH Calculations 5-90 0.32 Total AH =___» 6.22 Derate 1.20 7.46 12 AH Provided 9111.1 A SEP 2 4 2014 UMMiIMO� INo.1 REVISIONS O O Q Z I,- CO O W 00 CO Z M H Z W M z o ww a w O Z o O Z C\2 Z >_4O W t` O O l Z M111 PROJECT QUALIFIER Name: JORGE ALVEREZ License #: EC 13005215 LU N iJ J Q Z C7ZU� 0 U)Q M J IX ILLI W V- W f,'j~� :Z CO C9 W F_ ENGINEER Seal Drawn By: AM Date.- 04/07/14 ate:04/07/14 Scale: 1/8'1=1'-O" !!NOTES t Title: & CALC. Sheet No: FA -03 O C*4 O M M L.L. Oo W t` O Z C � N g LO J rn O -J W " O� Lt- Q = o LO W co O N N 06 4 Z LO LO W rn UJ UJ.- Q o D_ N L O i N Z Q -c5 00 M QUALIFIER Name: JORGE ALVEREZ License #: EC 13005215 LU N iJ J Q Z C7ZU� 0 U)Q M J IX ILLI W V- W f,'j~� :Z CO C9 W F_ ENGINEER Seal Drawn By: AM Date.- 04/07/14 ate:04/07/14 Scale: 1/8'1=1'-O" !!NOTES t Title: & CALC. Sheet No: FA -03