Loading...
DRAWINGSPROJECT TABULATION DISCIPLINE REQUIRED PROVIDED EXISTING BUILDING TYPE EXISTING TYPE VB (7,750 S. -F.) BUILDING "B" OCCUPANCY BUSINESS (GROUP "B") SQUARE FEET 600 S.F. OFFICES TRAVEL DISTANCE 200 FT SEE LIFE SAFETY PLAN INTERIOR FINISH SEE NOTE THIS SHEET TENANT SEPARATION EXISTING 1 HR. OCCUP. LOAD 1/100 S.F. 6 PEOPLE EXIT REQUIREMENT 0.2"/PERSON .80 LIN. FT. 16.98 FT. BUILDING IS NOT SPRINKLED LEVEL -2 ALTERATION BLDG CODE USD F.B.C. 2014 FIFTH EDITION ALL FLOOR FINISHES ARE TO BE COORDINATED WITH THE TENANT EXIT REQUIREMENTS: EGRES WIDTH AS PER TABLE 7.3.3.1 LIFE SAFETY CODE 0.5 600 S.F. / 100 = 6 PEOPLE 6 X 0.5 / 12 = .25 LIN. FT. EXIT REQUIRED ( 5.66 LIN. FT. TOTAL PROVIDED) EXISTING EXIT TO ------ .®.®. ®. ®, BUILDING EXTERIOR iII! � II} 9 II { III { I II I I \ I \. I� � II} II} { III C INTERIOR WALLS AND CEILING FINISHES: INTERIOR WALLS AND CEILING FINISH COMPLYING WITH 10.2.3 SHALL BE II { CLASS "A" OR CLASS "B" IN ALL CORRIDORS AND LOBBIES AND SHALL BE CLASS "A" IN ENCLOSED STAIRWAYS. SHALL ALSO BE CLASS "A" OR "B" II IN GENERAL ASSEMBLY AREAS. I) { INTERIOR FLOOR FINISHES: II { INTERIOR FLOOR FINISH COMPLYING WITH 10.2.7 SHALL BE CLASS I OR CLASS II IN CORRIDORS AND EXITS. CLASS "A" INTERIOR WALL AND CEILING FINISH: { { FLAME SPREAD 0-25 SMOKE DEVELOPMENT 0-450 CLASS "B" INTERIOR WALL AND CEILING FINISH: FLAME SPREAD 26-75 SMOKE DEVELOPMENT 0-450 I CLASS "C" INTERIOR WALL AND CEILING FINISH: { II FLAME SPREAD 76-200 SMOKE DEVELOPMENT 0-450 !IIS ALL INSULATION MATERIAL TO HAVE A FLAME SPREAD INDEX II OF NOT MORE THAN 25 AND A SMOKE DEVELOPMENT INDEX OF NOT MORE THAN 450 FABRICS AND FILMS USED FOR DECORATIVE PURPOSE, ALL DRAPERIES AND CURTAINS II AND SIMILAR LOOSELY HANGING FURNISHINGS SHALL MEET THE FLAME PROPAGATION PERFORMANCE CRITERIA CONTAINED IN NFPA-701, STANDARD METHOD OF FIRE TEST II { FOR FLAME PROPAGATION OF TEXTILES AND FILMS (NFPA-101.12.2.7.4 AND 10.3.1 { �� IIS NOTE: III 1. FIRE EXTINGUISHERS SHALL HAVE A MINUMUM RATING OF 2A 2013C MOUNTED 48" A.F.F. TO THE TOP { OF THE HANDLE. TRAVEL DISTANCE SHALL NOT EXCEED 75 FEET, AND THEY ARE TO BE CURRENTLY 'll{ TAGGED BY A LICENSED FIRE EQUIPMENT COMPANY. (1 PROVIDED) ! II 2• ADDITIONAL EXIT AND EMERGENCY LIGHTS MAY BE REQUIRED { BY THE FIELD FIRE INSPECTOR AT THE TIME OF THE FIRE FINAL. 3. ALL JOINTS AT THE FIRE RATED PARTITIONS ARE TO BE PROTECTED BY AN APPROVED FIRE RESISTANT JOINT SYSTEM �- TO RESIST ONE HOUR RATING. THE FIRE RESISTANT JOINTS SHALL BE SECURLY { INSTALLED IN OR AT THE JOINT FOR ITS ENTIRE LENGTH, SO AS NOT TO DISLODGE. \ 4. ADDITIONAL EXIT AND EMERGENCY LIGHTS MAY BE REQUIRED \ BY THE FIELD FIRE INSPECTOR AT THE TIME OF THE FIRE FINAL. I \ II � IIS i IIS I II } I II I uj wwCD IEXISTlNG i I o0 \ METER ROOM i \ I TO REMAIN I zo o ELECT PNL. TO REMAIN > _ { FIELD VERIFY PROPER , Cl 01 = { CLEARANCE FROM NEW I w CD w I EXISTING 8" BLOCK WALL PARTITION J{ D Eo 0 L._._._._._._._._._ ._._._. ---- o0:: EXISTING DOOR i �� -�` .�� ~ mw N C7U d Z TO REMAIN I I NZ � C3 I I wp • (8'-0") w U \ • B H.C. TOILET ��. II I DRYER II I • WASHER • � i� I I II I STOCK ROOM II I I (3'—O' II I j 1 I : I— I L/ li Www J � � Z I I e I oo� & I I II >_ I li . C., i- xZoe w I w cn�N H Y I{ O I I oo Wim, m l FE I I z� o� co I I I I wC) o� Q Of wN { I {} CD o US{ { T CD 57< I I o II I i II Q I I II I I II Q I I II Lu z I (10'-011) II Z i v I I1 i ! 34" HIGH COUNTER } (BY OTHERS) 'o I I/ I I II Y-1 I CLOTH DROP OFF II I I II I i � � II EXISTING STOREFRONT DOOR AND WINDOWS \ EXISTING EXIT TO TO REMAIN BUILDING EXTERIOR EXISTING ROOFED WALKWAY i LIFE E03AFETY PLAN i SCALE: 1/4"=1'-0" BAY - 10 DOOR SCHEDULE 10 3'-0" X 6'-8" S.C. DOOR WITH LEVERED HANDLE AND AUTOMATIC CLOSER COORDINATE HARDWARE WITH THE OWNER 3'-0" X 6'-8" S.C. DOOR 20 WITH LEVERED HANDLE NO LOCK PROVIDED ALL DOOR HARDWARE SHALL COMPLY WITH NFPA 101 CHAPTER 7 ALL DOOR TO BE OPERABLE WITH NOT MORE THAN ONE SINGLE RELEASING OPERATION. GENERAL DEMOLITION NOTES 1. THE CONTRACTOR SHALL OBTAIN ALL PERMITS REQUIRED FOR HAULING AND LEGALLY DISPOSING OF MATERIALS REMOVED IN DEMOLITION WORK. 2. THE CONTRACTOR SHALL VISIT THE SITE OF THE WORK AND EXAMINE THE PLANS AND IT WILL BE ASSUMED THAT THE CONTRACTOR HAS INVESTIGATED AND IS FULLY INFORMED OF THE CONDITIONS AND MATERIALS TO BE ENCOUNTERED AS TO CHARACTER, QUALITY AND QUANTITIES OF WORK TO BE PERFORMED AND MATERIALS TO BE FURNISHED AND AS TO THE REQUIREMENTS OF THE PLANS. 3. THE CONTRACTOR SHALL REMOVE ALL SPECIFIC ITEMS INDICATED ON THESE DRAWINGS AND ALSO REMOVE ANY OTHER ITEMS OR CONSTRUCTION AS REQUIRED TO ACCOMPLISH ALL NEW WORK TO AREAS SHOWN 4. ALL DIMENSIONS SHOWN ARE TO BE VERIFIED IN THE FIELD AND ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT BEFORE PROCEEDING WITH THE WORK. 5. BUILDING CONTRACTOR TO CUT OUT AND REMOVE EXISTING WALLS END SLAB AS INDICATED. 6. THE AMOUNT OF DUST RESULTING FROM DEMOLITION SHALL BE CONTROLLED TO PREVENT THE SPREAD OF DUST TO AVOID CREATION OF A NUISANCE IN THE SURROUNDING AREA. USE OF WATER WILL NOT BE PERMITTED WHEN IT WILL RESULT IN, OR CREATE, HAZARDOUS OR OBJECTIONABLE CONDITIONS SUCH AS FLOODING AND POLLUTION. 7. ALL EXISTING SURFACES SUCH AS WALLS, FLOORS, CEILINGS, BASES, ETC. THAT ARE AFFECTED BY THESE ALTERATIONS ARE TO HAVE NEW MATERIAL AND FINISH AS REQUIRED TO MATCH ALL ADJACENT EXISTING FINISHES 8. GENERAL CONTRACTOR SHALL DO ALL CUTTING AND PATCHING OF EXISTING CONCRETE SLABS, PARTITIONS, ETC ... AS MAY BE REQUIRED FOR ALL TRADES TO ACCOMPLISH ALL WORK REQUIRED BY THESE CONTRACT DOCUMENTS. CONTRACTOR SHALL DO ALL PATCHING AND PROVIDE NEW FINISHES TO MATCH EXISTING SO AS TO MAKE THE "PATCHED AREA" INDISCERNIBLE FROM THE EXIST. ADJACENT AREA. 9. UTILITY SERVICES: MAINTAIN EXISTING UTILITIES INDICATED TO REMAIN, KEEP IN SERVICE, AND PROTECT AGAINST DAMAGE DURING DEMOLITION OPERATIONS. U.O.N. 10. PRIOR TO DEMOLITION, VERIFY THE SCOPE OF WORK W/THE TENANT AND DISPOSITION OF ANY REMOVED ITEMS. 11. REMOVE ALL SPECIFIC ITEMS INDICATED ON THESE DRAWINGS AND ALSO REMOVE ANY OTHER ITEMS OR CONSTRUCTION AS REQ'D. TO ACCOMPLISH ALL NEW WORK TO AREAS SHOWN. 12. PATCH CONC. SLAB TO MATCH EXISTING STRUCTURE, AFTER NEW PLUMBING FIXTURES HAS BEEN LOCATED. 13. ALL REMOVED ITEMS IF ANY SHALL BECOME THE PROPERTY OF THE CONTRACTOR WITH THE APPROVAL OF THE OWNER, AND SHALL BE REMOVED FROM THE SITE. NEW 3000 PSI CONC. W 6X6 W1.4XW1.4 W.W.M. EXISTING CONC. SLAB 0 6 MILL W.P MEMBRANE AND MESH TO REMAIN AT NEW SLAB OPENINGS • ®. _ —X — X---{ —X—X —X—X— {— X— X SLAB CUT REMIDIAL DETAIL N.T.S. NON STRUCTURAL SLABS TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED TERMITICIDES OR OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED FOR USE AS A PREVENTIVE TREATMENT TO NEW CONSTRUCTION. TO BE DONE PRIOR TO ANY CONSTRUCTION. A PERMANENT SIGN, WHICH IDENTIFIES THE TERMITE TREATMENT PROVIDER AND NEED FOR RE -INSPECTION AND TRATMENT CONTRACT RENUAL, SHALL BE PROVIDED. THE SIGN SHALL BE POSTED NEAR THE WATER HEATER OR ELECTRICAL PANEL. EMERGENCY LIGHT FIXTURE WITH BATTERY BACH-UP WIRED TO UNSWITCHED LEG L1600 N. FEDERAL HWY e EXIT LIGHT FIXTURE WITH BATTERY BACH-UP WIRED TO UNSWITCHED LEG NOT MORE THAN 5W PER FACE FE FIRE EXTINGUISHER USE FEDERAL HIGH Ay (US STATE ROA® 5 i i n a I{ �I I EXISTING I \ R i \ TO REMAIN ,\ I ELECT PNL. I { TO REMAIN � L EXISTING 8" BLOCK WALL EXISTING DOOR I . I TO REMAINo. IlI EXISTING DOOR AND �� / LLA { PARTITION TO BE REMOVED L -�' - - - :.l { F_ i, ---- I I I I EXISTING TOILET ROOM TO BE REMOVED AS REQUIRED } { HARD CAPP ALL NOT USED i HOT AND COLD WATER LINES. I I Ii I I II I I Ii I I II ww I { I I oo • opo I j II >_ clf i II I • ca � w o> o YI i 1i ooW U F N I { I I � 5� 00 SO cy wUof� Y J . o wl � ll w 6 Y-10 II z Lu Z z i ALL EXISTING 2X4 SUSP. I Q { CEILING, TO BE REMOVED I I o I ALL EXISTING FLOOR i I I FINISH, TO BE REMOVED I , ..... ....... - -- ------ I { II I { II EXISTING STOREFRONT DOOR AND WINDOWS \ II TO REMAIN EXISTING ROOFED WALKWAY -._._._.-.-.-._._.-._.-. I DEMU'L I SCALE: 1/4"=1'-0" BAY - 10 - • - • - • - EXISTING WALLS AND ITEMS TO REMAIN - - - - - PARTITIONS AND ITEMS TO BE REMOVED e&,rnd I �t1t tri o �aA6"004 u aVAE-+d�'x�� t7 U5 voa � AW w �W � rr�w oa Hnio WAvWi���ja+�Zw zw O rx Or� w w� .. Amo A o� AC��wQ�aW�"FHH �..WpWq�EEEOWW x W ¢EnAaa., E�zQPEZZE--..4;!, :p. :a } ) t I -4- CHECKED DRAWN DATE 8-4-2015 COMM. NO. 15-145 w A w 0 9 0 u O O 0 M M o a 0 i!In g a • W i LL UJ co i <"z z 0 W o • � � w O #z co? :a } ) t I -4- CHECKED DRAWN DATE 8-4-2015 COMM. NO. 15-145 w A w 0 9 0 u O O M M 0 � O N • .� W o C) � � w O M M u W m �b � IC :a } ) t I -4- CHECKED DRAWN DATE 8-4-2015 COMM. NO. 15-145 w A w 0 9 0 u C Li J J EXISTING STL BAR JOIST STRUCTURE ABOVE CONT. GALV. MTL, RUNNERS I STRUCTU'REEAT 36"CK RO.C. TO z NEW 2X4 SUSP. ACOUST CEILING MATCH EXISTING PREVIOUS SUSP. CEILING 3.1/2" BATT. INSULATION THRU-OUT CONT. GALV. METAL RUNNER W/ 1/8" 1" LONG POWDER ACTUATED FASTNERS AT 24" O.C. ONE HOUR CONSTRUCTION NOTE ONE LAYER 5/8" TYPE "X" GYP. WALLBOARD APPLIED AT RIGHT ANGLES OR PARALLEL TO EA. SIDE OF MIN. 3-1/2" METAL STUDS, MIN. NO. 20 GSG. GALV. STEEL @ 16" O.C. W/ SELF -TAPPING BUGLE HEAD SHEET STEEL TYPE, SPACED 12" O.C. TYPE S-12 BY 1" LONG. STUDS ATTACHED TO FLOOR AND CEILING TRACKS W/ 1/2" LONG TYPE S-12 PAN HEAD SELF -TAPPING STEEL SCREWS ON BOTH SIDES OF STUDS. (GLASS FIBER OR MINERAL WOOL BATT. MATERIAL BEARING THE UL CLASSIFICATION MARKING AS TO FIRE RESISTANCE OF A THICKNESS TO COMPLETELY FILL STUD CAVITY SEE PTN. TYPE FOR LOCATION OF BATT INSULATION.) UL. #U425 ` EXISTING CONC. SLAB 1 HR. FIRE RATED ENCLuouRE SCALE 3/4"=1'-0" EXISTING STL BAR JOIST STRUCTURE ABOVE PROVIDE 3.5/8" 20 GA. MTL STUD BRACING AT 48" O.C. THRU-OUT NEW 2X4 SUSP. ACOUST CEILING MATCH EXISTING PREVIOUS SUSP. CEILING CONT. GALV. MET, FIRE STOP @ CLG. LEVEL W/ TECK SCREWS TO CLG. SYSTEM AT 36" O.C. 5/8" GYP. BD. ON 25 GA. 3.5/8" METAL STUDS @ 24" Q.C. GALV. METAL RUNNER W/ 1" LONG POWER ACTUATED FASTNERS AT 24" O.C. EXIST. CONC. SLAB TYPICAL INTERIOR PARTITION SCALE 3/4"=1'-0" WASHABLE EPDXY PAINT ON ALL 4 WALLS 42" 12 = I GRAB BAR FLOOR 11LES TO BE VCT, (VINYL COMPOSITE TILES) TYPICAL TOILET ROOM ELEVATIONS 16"x30" MIRROR 36" (TYP) 6" GRAB BAR = _ E\ i 15 CF N 18" 3'-6" CLR. SUPPLY ALL HANICAP LAVATORIES WITH UNDER COUNTER GUARDS , THERE SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER LAVS. VERIFY THAT ALL TOILET FLUSH HANDLES TO BE MOUNTED ON THE WIDE SIDE OF TOILET AREAS. CONTRACTOR TO FIELD VERIFY THAT TOILET ROOMS MEET A.D.A. REQUIREMENTS ALL GRAB BARS TO BE SECURED TO SUPPORT 250 LBF IN ALL DIRECTIONS. (GRAB BARS SHALL NOT ROTATE WITHIN THEIR FITTINGS) I 7'-2" m TOILET ROOM PLAN SCALE: 1/4"=1'-0" 30"X48" CLEAR CLEAR FLOOR SPACE AT LAVATORY GENERAL NOTES 1. THE CONTRACTOR SHALL VISIT THE SITE OF THE WORK AND EXAMINE THE PLANS AND IT WILL BE ASSUMED THAT THE CONTRACTOR HAS INVESTIGATED AND IS FULLY INFORMED AS TO THE CONDITIONS AND MATERIALS TO BE ENCOUNTERED AS TO CHARACTER, QUALITY AND QUANTITIES OF WORK TO BE PERFORMED AND MATERIALS TO BE FURNISHED AND AS TO THE REQUIREMENTS OF THE PLANS. 2. THE CONTRACTOR SHALL FIELD CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AND BE RESPONSIBLE FOR SAME. DISCREPANCIES BETWEEN FIELD AND DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT. 3. DO NOT SCALE DRAWINGS. 4. CONTRACTOR WILL GUARANTEE IN WRITING ALL MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE OWNER AND WILL, AT HIS OWN COST, REPAIR OR REPLACE ALL WORK OR DAMAGES CAUSED BY WORK WHICH BECOMES DEFECTIVE DURING THE TERM OF THE GUARANTEE. 5. CONTRACTOR SHALL COORDINATE AND SUPERVISE HIS WORK AND WORK BY SUBCONTRACTORS. 6. THESE PLANS ARE THE PROPERTY OF THE ARCHITECT AND SHALL NOT BE USED, REPRODUCED, OR CHANGED IN ANY WAY WITHOUT THE EXPRESSED WRITTEN CONSENT OF THE ARCHITECT, 7. ALL MATERIALS AND WORK TO CONFORM TO LATEST GOVERNING BUILDING CODES AND REGULATIONS. 8. ALL COUNTERS AND CABINETS ARE BY OTHERS 9• ARCHITECTS ERRORS OR OMISIONS DO NOT RELIEVE THE CONTRACTORS FROM COMPLING WITH THE LATEST EDITION OF THE FL. BLDG. CODE 10. THE ARCHITECT IS NOT RESPONSIBLE FOR ANY PRESENT OR PRE-EXISTING CODE VIOLATIONS THAT MAY EXIST ON THE EXISTING SITE OR BUILDING. 11. ALL WORK IS TO BE DONE IN STRICT COMPLIANCE WITH THE FLORIDA BLDG. CODE 2014 FIFTH EDITION AND ANY OTHER LOCAL GOVERNING AUTHORITIES. 12. IF REQUIRED CONTRACTOR TO PROVIDE COMPLETE SET OF SHOP DRAWING FOR ALL REQUIRED FIRE ALARMS AND/OR FIRE PROTECTION DEVICES WICH SHALL BE APPROVED AND ACCEPTED BY THE LOCAL ATHORITIES, TO INCLUDE LAY -OUT, LOCATIONS, CONNECTIONS AND ANY REQUIRED CALCULATIONS. 13. ALL FINISHES ARE TO BE COORDINATED WITH THE OWNER. 14. ALL DRAWINGS UNDER THIS SET OF PLANS ARE TO BE SUBMITTED TO ALL THE PROPER AUTHORITIES AND BUILDING DEPTS. FOR REVIEW AND PROCESSING. NO WORK IS TO BE STARTED UNTILL ALL PROPER PERMITS ARE ISSUED. 15, FOR STEEL STUD PARTITIONS.: STEEL STUDS SUPPORTING WALL HUNG PLUMBING FIXTURES SHALL BE DOUBLED OR NOT LESS THAN 20 GAGE WITH A MIN. EFFECTIVE MOMENT OF INERTIA EQUAL TO 0.864 IN. SUCH STUDS SHALL BE RIGIDLY CONNECTED TOP AND BOTTOM TO PREVENT SIGNIFICANT END ROTATION OR DISPLACEMAT. A HORIZONTAL MEMBER SECURELY FASTENED TO NOT LESS THAN TWO STUDS SHALL BE INSTALLED FOR THE ATTACHMENT OF EACH WALL HUNG PLUMBING FIXTURE. WHERE LATH ON VERTICAL SURFACES EXTENDS BETWEEN RAFTERS OR OTHER SIMILAR PROJECTING MEMBERS, SOLID BACKING SHALL BE INSTALLED TO PROVIDE SUPPORT FOR LATH AND ATTACHMENTS. 16. ALL DIMENSIONS ARE TO BE VERIFIED WITH ACTUAL EQUIPMENT SIZES 1-2 HR. FIRE RATED GYP. WALL BRD. STEEL STUD 1/4" (6mm)MIN. DIAMETER BEAD OF 3M "FIRE BARRIER CP 25N/S CAULK". METALLIC PIPE OR CONDUIT CP 25N/S CAULK PENETRATION FIRESTOP FOR METAL PIPE/CONDUIT THROUGH GYPSUM WALL BOARD la—SYSTEM #WL1001 PLUMBING PENETRATION THRU ONE HOUR RATED PARTITION TO BE PROTECTED AS FOLLOWS: PVC: U.L. NO. W -L-2148 CPUC PIPE NOM. 2" OR SMALLER. COPPER: U.L. NO. W -L-1039 COPPER TUBING 4" DIA. OR SMALLER �e«ma+�►. e....-s...�e...�r � .� � �... � �. �„e�...p«�A,�p®....t+�a.d..A�a�.s�.r�.a.....�.+.�.a�a�.a.�=«.-r..«A..-.. a.�em..s�. A 6! ft 0 0 , II asLLI uj uj a- ep L {t ]/ a 8 II p t t i �Y II rEXISTING 19 METER ROOM TO REMAIN ' z o� o ELECT PNL, TO REMAIN > _ = II 6 FIELD VERIFY PROPER I Q o CLEARANCE FROM NEW o i II EXISTING 8" BLOCK WALL PARTITION A¢ pa ¢@p ;- d e 8m. A a:am 0 _va. a wwme0 .rm. 0 vms. 0 em.m 8 +rm+u / -+•m. a «meu ammm 0 .wee A +� 0 mv. 0 +sn 4 w.v 4 ..mm. i � _ � ~ N ' IIS a u_j z + EXISTING DOOR Li N II TO REMAIN z ' a. 1 , .. _...... H.C. TOILET 1oaa ~ 6 2 » . ...........Ie...+I ....Jq DRYER O ' WASHER A STOCK ROOM p p pq Yg t o t e o t a w E i e a N a s (o I I � g+ SII L0= ! t 2 as wa.. W W C.9 IIS o9i: ooQ� tl II ' P/'1 W A t[t 8{a 1— f� y o 0 6 6 Z Lo_� g8a 11 0 � 9 . CD C9 to i= C. U- alll W 1 w 9f No0 ia C f oo� A il� m 1 mciv w� p (I fe p O F..� a a - W a C' 0 ! Ie e LIN 00 Z y = r tg0 tlp0 t— 3aA 8 6 A@ W + + V 0 0 p� BAY--' 1 � I � CLOTH DROP OFF v I'I 34" HIGH COUNTER (BY OTHERS) IIIc � � II A 9'-0"AA a a 3-4 �€ � : _ : _ : ..... ..._ ..._ .. _ ...._ ...6 ..._ a 9 + + / et `� 12$-4" ... _...... . Ln _t `1:,,�...._.... ..............-. A t ...� a ....,. a ..,.. a .�.,. a;AL4— \ \ EXISTING STOREFRONT .. DOOR AND WINDOWS \ II TO REMAIN \ II EXISTING ROOFED WALKWAY 0 i _ , _ . _ . — . _ , _ . _ . _ . _ . II i Ili SCALE: 1/4"=1'-0" BAY - 10 GROUP "B" BUSINESS CODE USED F.B.C. 2014 FIFTH EDITION ALL DIMENSIONS ARE TO BE FIELD VERIFIED DO NOT SCALE DRAWINGS EXISTING WALLS AND ITEMS TO REMAIN a NEW NON RATED PARTITIONS - =M= NEW ONE HOUR RATED PARTITIONS DOOR SCHEDULE 3'-0O WITH "LEVERED LEVERED AND AUTOMATIC CLOSER COORDINATE HARDWARE WITH THE OWNER 3'-0" X 6'-8" S.C. DOOR 2� WITH LEVERED HANDLE NO LOCK PROVIDED ALL DOOR HARDWARE SHALL COMPLY WITH NFPA 101 CHAPTER 7 ALL DOOR TO BE OPERABLE WITH NOT MORE THAN ONE SINGLE RELEASING OPERATION. o 4�A RU¢<w�F x8w�zza<z A za o QHOt oxw'AAE.F"�Z5 0U< MAAv�vaFQw QM���aO�W�O��FFA �]WE+P"�WE-EW.f�.1UE+W�xF" V 0 0 cn M 0 N Q 5 :..._ . O_ a N m TOILET ROOM PLAN SCALE: 1/4"=1'-0" 30"X48" CLEAR CLEAR FLOOR SPACE AT LAVATORY GENERAL NOTES 1. THE CONTRACTOR SHALL VISIT THE SITE OF THE WORK AND EXAMINE THE PLANS AND IT WILL BE ASSUMED THAT THE CONTRACTOR HAS INVESTIGATED AND IS FULLY INFORMED AS TO THE CONDITIONS AND MATERIALS TO BE ENCOUNTERED AS TO CHARACTER, QUALITY AND QUANTITIES OF WORK TO BE PERFORMED AND MATERIALS TO BE FURNISHED AND AS TO THE REQUIREMENTS OF THE PLANS. 2. THE CONTRACTOR SHALL FIELD CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AND BE RESPONSIBLE FOR SAME. DISCREPANCIES BETWEEN FIELD AND DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT. 3. DO NOT SCALE DRAWINGS. 4. CONTRACTOR WILL GUARANTEE IN WRITING ALL MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE OWNER AND WILL, AT HIS OWN COST, REPAIR OR REPLACE ALL WORK OR DAMAGES CAUSED BY WORK WHICH BECOMES DEFECTIVE DURING THE TERM OF THE GUARANTEE. 5. CONTRACTOR SHALL COORDINATE AND SUPERVISE HIS WORK AND WORK BY SUBCONTRACTORS. 6. THESE PLANS ARE THE PROPERTY OF THE ARCHITECT AND SHALL NOT BE USED, REPRODUCED, OR CHANGED IN ANY WAY WITHOUT THE EXPRESSED WRITTEN CONSENT OF THE ARCHITECT, 7. ALL MATERIALS AND WORK TO CONFORM TO LATEST GOVERNING BUILDING CODES AND REGULATIONS. 8. ALL COUNTERS AND CABINETS ARE BY OTHERS 9• ARCHITECTS ERRORS OR OMISIONS DO NOT RELIEVE THE CONTRACTORS FROM COMPLING WITH THE LATEST EDITION OF THE FL. BLDG. CODE 10. THE ARCHITECT IS NOT RESPONSIBLE FOR ANY PRESENT OR PRE-EXISTING CODE VIOLATIONS THAT MAY EXIST ON THE EXISTING SITE OR BUILDING. 11. ALL WORK IS TO BE DONE IN STRICT COMPLIANCE WITH THE FLORIDA BLDG. CODE 2014 FIFTH EDITION AND ANY OTHER LOCAL GOVERNING AUTHORITIES. 12. IF REQUIRED CONTRACTOR TO PROVIDE COMPLETE SET OF SHOP DRAWING FOR ALL REQUIRED FIRE ALARMS AND/OR FIRE PROTECTION DEVICES WICH SHALL BE APPROVED AND ACCEPTED BY THE LOCAL ATHORITIES, TO INCLUDE LAY -OUT, LOCATIONS, CONNECTIONS AND ANY REQUIRED CALCULATIONS. 13. ALL FINISHES ARE TO BE COORDINATED WITH THE OWNER. 14. ALL DRAWINGS UNDER THIS SET OF PLANS ARE TO BE SUBMITTED TO ALL THE PROPER AUTHORITIES AND BUILDING DEPTS. FOR REVIEW AND PROCESSING. NO WORK IS TO BE STARTED UNTILL ALL PROPER PERMITS ARE ISSUED. 15, FOR STEEL STUD PARTITIONS.: STEEL STUDS SUPPORTING WALL HUNG PLUMBING FIXTURES SHALL BE DOUBLED OR NOT LESS THAN 20 GAGE WITH A MIN. EFFECTIVE MOMENT OF INERTIA EQUAL TO 0.864 IN. SUCH STUDS SHALL BE RIGIDLY CONNECTED TOP AND BOTTOM TO PREVENT SIGNIFICANT END ROTATION OR DISPLACEMAT. A HORIZONTAL MEMBER SECURELY FASTENED TO NOT LESS THAN TWO STUDS SHALL BE INSTALLED FOR THE ATTACHMENT OF EACH WALL HUNG PLUMBING FIXTURE. WHERE LATH ON VERTICAL SURFACES EXTENDS BETWEEN RAFTERS OR OTHER SIMILAR PROJECTING MEMBERS, SOLID BACKING SHALL BE INSTALLED TO PROVIDE SUPPORT FOR LATH AND ATTACHMENTS. 16. ALL DIMENSIONS ARE TO BE VERIFIED WITH ACTUAL EQUIPMENT SIZES 1-2 HR. FIRE RATED GYP. WALL BRD. STEEL STUD 1/4" (6mm)MIN. DIAMETER BEAD OF 3M "FIRE BARRIER CP 25N/S CAULK". METALLIC PIPE OR CONDUIT CP 25N/S CAULK PENETRATION FIRESTOP FOR METAL PIPE/CONDUIT THROUGH GYPSUM WALL BOARD la—SYSTEM #WL1001 PLUMBING PENETRATION THRU ONE HOUR RATED PARTITION TO BE PROTECTED AS FOLLOWS: PVC: U.L. NO. W -L-2148 CPUC PIPE NOM. 2" OR SMALLER. COPPER: U.L. NO. W -L-1039 COPPER TUBING 4" DIA. OR SMALLER �e«ma+�►. e....-s...�e...�r � .� � �... � �. �„e�...p«�A,�p®....t+�a.d..A�a�.s�.r�.a.....�.+.�.a�a�.a.�=«.-r..«A..-.. a.�em..s�. A 6! ft 0 0 , II asLLI uj uj a- ep L {t ]/ a 8 II p t t i �Y II rEXISTING 19 METER ROOM TO REMAIN ' z o� o ELECT PNL, TO REMAIN > _ = II 6 FIELD VERIFY PROPER I Q o CLEARANCE FROM NEW o i II EXISTING 8" BLOCK WALL PARTITION A¢ pa ¢@p ;- d e 8m. A a:am 0 _va. a wwme0 .rm. 0 vms. 0 em.m 8 +rm+u / -+•m. a «meu ammm 0 .wee A +� 0 mv. 0 +sn 4 w.v 4 ..mm. i � _ � ~ N ' IIS a u_j z + EXISTING DOOR Li N II TO REMAIN z ' a. 1 , .. _...... H.C. TOILET 1oaa ~ 6 2 » . ...........Ie...+I ....Jq DRYER O ' WASHER A STOCK ROOM p p pq Yg t o t e o t a w E i e a N a s (o I I � g+ SII L0= ! t 2 as wa.. W W C.9 IIS o9i: ooQ� tl II ' P/'1 W A t[t 8{a 1— f� y o 0 6 6 Z Lo_� g8a 11 0 � 9 . CD C9 to i= C. U- alll W 1 w 9f No0 ia C f oo� A il� m 1 mciv w� p (I fe p O F..� a a - W a C' 0 ! Ie e LIN 00 Z y = r tg0 tlp0 t— 3aA 8 6 A@ W + + V 0 0 p� BAY--' 1 � I � CLOTH DROP OFF v I'I 34" HIGH COUNTER (BY OTHERS) IIIc � � II A 9'-0"AA a a 3-4 �€ � : _ : _ : ..... ..._ ..._ .. _ ...._ ...6 ..._ a 9 + + / et `� 12$-4" ... _...... . Ln _t `1:,,�...._.... ..............-. A t ...� a ....,. a ..,.. a .�.,. a;AL4— \ \ EXISTING STOREFRONT .. DOOR AND WINDOWS \ II TO REMAIN \ II EXISTING ROOFED WALKWAY 0 i _ , _ . _ . — . _ , _ . _ . _ . _ . II i Ili SCALE: 1/4"=1'-0" BAY - 10 GROUP "B" BUSINESS CODE USED F.B.C. 2014 FIFTH EDITION ALL DIMENSIONS ARE TO BE FIELD VERIFIED DO NOT SCALE DRAWINGS EXISTING WALLS AND ITEMS TO REMAIN a NEW NON RATED PARTITIONS - =M= NEW ONE HOUR RATED PARTITIONS DOOR SCHEDULE 3'-0O WITH "LEVERED LEVERED AND AUTOMATIC CLOSER COORDINATE HARDWARE WITH THE OWNER 3'-0" X 6'-8" S.C. DOOR 2� WITH LEVERED HANDLE NO LOCK PROVIDED ALL DOOR HARDWARE SHALL COMPLY WITH NFPA 101 CHAPTER 7 ALL DOOR TO BE OPERABLE WITH NOT MORE THAN ONE SINGLE RELEASING OPERATION. o 4�A RU¢<w�F x8w�zza<z A za o QHOt oxw'AAE.F"�Z5 0U< MAAv�vaFQw QM���aO�W�O��FFA �]WE+P"�WE-EW.f�.1UE+W�xF" V 0 0 cn M Q 5 O_ N e ON1 0 ^H Q � ° Z c CHECKED DRAWN DATE 8-4-2015 CONW. NO. 15-148A 51 01A 0 cn M Q O_ N e ON1 0 o � u c o� W o" a � W H to CHECKED DRAWN DATE 8-4-2015 CONW. NO. 15-148A 51 01A WASHER %• ® COLO I SOV 3/4"SOV' 3/4" N.T.S. CONNECT TO EXISTING COLD WATER LINES SAME LOCATIOM S.O.V. 1/2" W.C. CONNECT TO EXISTING VENT SAME LOCATION 2® " DOMESTIC 1 2 W.C. 3" WASHER 3" 33" 3" "®" LAV EXISTING 3" SANITARY LINE AT PREVIOUS EXISTING TOILET ROOM C.O. 3" N2"C.O. .rj lam; Alm" N.T.S. SLOPE AT 1/4" PER FOOT. CQNNECT TO EXISTING 3' SANITARY LINE AT PREVIOUS TOILET SAME LOCATION 1. ALL WORK SHALL BE DONE IN ACCORDANCE THE FLORIDA BUILDING CODE AN ALL OTHER LOCAL CODES AND ORDINANCES IN A FIRST CLASS MANNER. 2. THESE DRAWINGS ARE DIAGRAMATIC, THEY ARE NOT INTENDED TO SHOW A COMPLETE WORKING SYSTEM. ITEMS REASONABLY INFERED AS NECESSARY TO PROVIDE A COMPLETE AND FUNCTIONAL SYSTEM SHALL BE PROVIDED WHETHER SPECIFICALLY SHOWN OR NOT. ANY DISCREPANCIES OR OMISSIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT BEFORE THE BID. 3. THE CONTRACTOR IS RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED FOR THE COMPLETION OF THE WORK. 4. ALL MATERIALS SHALL BE NEW AND BEAR UNDERWRITERS LABELS WHERE APPLICABLE. 5. THE CONTRACTOR SHALL PROVIDE AND INSTALL ALL NEW WORK AS INDICATED ON THE PLANS. IF PROBLEMS OR OMISSIONS ARE ENCOUNTERED IN FOLLOWING THE DRAWINGS, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT AS SOON AS POSSIBLE AND STOP ALL WORK ON THAT PORTION OF THE WORK UNTILL NEW DIRECTIONS ARE GIVEN. 6. THE CONTRACTOR SHALL VISIT THE JOB SITE AND FAMILIARIZE HIMSELF WITH ALL CONDITIONS. ALL EXISTING MECHANICAL EQUIPMENT (WHETHER INDICATED ON THE DRAWINGS OR NOT) ARE TO BE VERIFIED AS EXISTING AND IN GOOD WORKING ORDER, IF THEY ARE TO BE USED . 7. PROVIDE CLEANOUT AT THE BASE OF EACH SOIL AND WASTE STACK. 8. IF APPLICABLE, ALL PENETRATIONS THRU RATED WALLS OR FLOORS SHALL BE PROTECTED WITH EQUALLY FIRE RATED FOAM, CAULK OR PUTTY. 9. THE CONTRACTOR IS TO FAMILIARIZED HIMSELF FULLY WITH ALL OF THE EXISTING CONDITIONS INCLUDING DETERMINATION OF ALL EXISTING PIPING SYSTEMS. INCLUDING BUT NOT LIMITED TO SANITARY, DOMESTIC WATER AND STORM DRAINAGE. 10. PROVIDE DIELECTRIC FITTINGS BETWEEN ALL DISSIMILAR PIPING CONNECTIONS. 11. ALL FIXTURES ARE TO BE SUPPLIED WITH APPROVED WATER HAMMER ARRESTORS. 12. ALL HOT WATER PIPING SHALL BE INSULATED WITH 1" ARMAFLEX OR APPROVED EQUAL. 13. ALL BATHROOM OR TOILET ROOM FLOORS AND BASE SHALL BE OF NON SKID CER. TILES. COORDINATE STYLE AND MNFGR WITH THE OWNER. 14. PROVIDE SHUT-OFF VALVES AT EACH FIXTURE WATER SUPPLY PROVIDE A MIN. PITCH OF 1/8" FOR 3" OR LARGER PIPES AND 1/4" PITCH FOR PIPES LESS THAN 3". 15. A WATER HAMMER ARRESTOR SHALL BE INSTALLED WHERE QUICK CLOSING VALVES ARE UTILIZED.THE ARRESTOR SHALL BE LOCATED WITHIN AN EFFECTIVE RANGE OF THE QUICK CLOSING VALVE. ACCESS SHALL BE PROVIDED TO THE WATER HAMMER ARRESTOR. 16. NO HOT WATER WITH A TEMPERATURE HIGHER THAN 140 DEGRES TO DISCHARCH INTO SANITARY SYSTEM. ALL FIXTURES USING HOT WATER TO LIMIT FLOW TO 0.5 GPM. 17. THE TOTAL LENGTH OF HOT WATER PIPES FROM THE SOURCE OF THE HOT WATER SUPPLY TO THE NEAREST FIXTURE SHALL BE LESS THAN 100 FEET. 18. THE HOT WATER SUPPLY LINE TO ANY FIXTYRE REQUIRING HOT WATER SHALL BE INSTALLED ON THE LEFT SIDE OF THE FIXTURE. 19. ALL TOILETS ARE TO BE H.C. ACCESSIBLE AND THE ELONGATED TYPE. 22. EACH NEW OR REPLACED FIXTURE, SHALL HAVE SEPERATE VALVES.. 23. REPLACED TOILET FLANGE TO BE RAISED TO MATCH ANY NEW FINISHED FLOOR HEIGHT. 24. ALL FIXTURES ARE TO MEET THE MAX. FLOW RATES AS INDICATED ON TABLE P2903.2A (RES) OR 604.4 (BLDG.) 1. PROVIDE MODEL 653-B (3/4" HIP) WATER HAMMER ARRESTORS BY HYDRA RESTOR OR EQUAL TO BE PROVIDED WHERE QUICK CLOSING VALVES ARE UTILIZED. 2. PROVIDE SHUT-OFF VALVES AT EACH FIXTURE WATER SUPPLY 3. ALL BATHROOM FLOORS AND BASE SHALL BE OF NON SKID CER. TILES. COORDINATE STYLE AND MNFGR WITH THE OWNER. 4. EACH NEW OR REPLACED FIXTURE, SHALL HAVE SEPERATE VALVES.. 5. REPLACED TOILET FLANGE TO BE RAISED TO MATCH ANY NEW FINISHED FLOOR HEIGHT. 6. ALL FIXTURES ARE TO MEET THE MAX. FLOW RATES AS INDICATED ON TABLE P2903.2A (RES) OR 604.4 (BLDG.) TABLE P2903.2A MAXIMUM FLOW RATES AND CONSUMPTION FOR PLUMBING FIXTURES, FIXTURE FITTINGS AND APPLIANCES PLUMBING FIXTURE OR PLUMBING FIXTURE OR FIXTURE FITTING FIXTURE FITTING MAXIMUM FLOW RATE (B) LAVATORY FAUCET 1.5 GPM AT 60 PSI WATER CLOSET 1.28 GALLONS PER FLUSHING CYCLE 1 GALLON = 3.785 L 1 GALLON PER MINUTE = 3.785 L/M 1 POUND PER SQUARE INCH = 6.895 KPA (A) A HANDHELD SHOWER SPRAY IS A SHOWERHEAD (B) CONSUMPTION TOLERANCES SHALL BE DETERMINED FROM REFERENCED STANDARDS (C) WATER FACTOR IN GALLONS PER CYCLE PER CUBIC FOOT NOTE:ALL REFERENCED FIXTURES SHALL 1 BE PROVIDED ACCORDNLY TO THE STANDARDS AS PER F.P.C. 2014 FIFTH EDITION ------ ------ _._._._._._.� �._.® II 11 I E)(I NG I MM ROOM I \ ! TO REMAIN i li I IL._._._._._._._._._._._._._._._._.J I EXISTING DOOR I I TO REMAIN -j �•_•-• . W.C. EXISTING 3" SANITARY LINE H.C. TOILET 3" \ ! AT PREVIOUS EXISTING TOILET ROOM 3" -,-m-. "-m-"- 2" I I I DRYERX I i 311 LAV. X I j WASHER < Lr I i TANKLESS i I I i STOCK ROOM W.H. I I II i I II i II J 9i I iw w 0 C M I jO ca z I <n J W J I I YI U i. H ml � °O I I Woo o I 4' wl C I jz CD i wI I I I I I I _ N O M 0 M I w i 0 I o i. H p � I Woo Z 4' C I M CD i fi i z z CD con ca W a kn 1.0 I I o ° III I U I II II II II II II II II II II II II II Y-1 i CLOTH DROP OFF II I i II 134" HIGH COUNTER I I (BY OTHERS) II i I II I i II I II •� II \ II EXISTING ROOFED WALKWAY (-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•-•- - - r L z 0 14 4 mG]QdgFR:�a R x U o10g0W vi 5�2 0go ca x ox z F00a0a'C4 E,� wr, 0o a wA q4u E.�sHAWWE"�UCx7 � do°AA�a2Ex- Z�0�-�z���3� U z WWz 0 w 0 O U CHECKED DRAWN DATE 8-4-2015 COMM. No. 15-148A 21 w A w a x 0 u 0 0 u 0 O M 0 M i 0 N i. H p � Woo O 4' � M CD Z fi z con ca CHECKED DRAWN DATE 8-4-2015 COMM. No. 15-148A 21 w A w a x 0 u 0 0 u 0 O M M 0 N H p � Woo O H N � M M con a W a kn 1.0 CHECKED DRAWN DATE 8-4-2015 COMM. No. 15-148A 21 w A w a x 0 u 0 0 u TYPE SERVICE 120/208V -3P-4 WIRES MOUNTING POLES 30 NEW ELECT. PANEL "A" IN THE SAME PREVIOUS LOCATION FIELD VERIFY PROPER CLEARANCE FROM NEW PARTITION MAIN BUS 100AMPS NEUTRAL FULL MAINS MLO DEM. KVA NO DEM KVA TRIP/ POLE CON- DUIT WIRE 75 % C COPPER DESCRIPTION CIRC. NO. DISCONNECT SWITCHES SHALL BE H.P. RATED, HEAVY DUTY, QUICK -MADE, CIRC. NO. DESCRIPTION WIRE 75 % C COPPER CON- DUIT TRIP/ POLE NO DEM KVA DEM. KVA 10.0 FOR A COMPLETE ELECTRICAL SYSTEM AND PROVIDE ALL REQUIREMENTS NECESSARY �.:. FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER. EXISTING A/C 1 Eo 2 ELECT OUTLETS 12 1/2 20/1 10. 1.2 3 CLASS WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE. 4 ELECT OUTLETS 12 1/2 20/1 CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM 1.2 5 6 LIGHTS 12 1/2 20/1 1.2 0.8 ALL REQUIRED INSURANCE SHALL BE PROVIDED FOR PROTECTION AGAINST PUBLIC 20/1 1/2 12 CASH REGISTER 7 THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD REQUIREMENTS OF POWER 8 TANKLESS W.H. 6 CU 1" 60/2 ALL RACEWAYS UNDERGROUND SHALL BE A MINIMUM OF 3/4" CONDUIT. 8.5 0.8 20/1 1/2 12 EXH FAN TOILET RM 9 P4 10 FAILURE OF NOTIFYING DISCREPANCIES. 22. ELECTRICAL CONTRACTOR TO VERIFY ALL EQUIPMENT ELECTRICAL REQUIREMENTS WITH a MANUFACTURER INCLUDING CONNECTIONS, WIRE SIZES AND VOLTAGES REQUIREMENTS. 11 NOTIFY THE ARCHITECT WITH ANY DISCREPANCIES PRIOR TO CONSTRUCTION. 12 DRYER 10 CU 1" 30/2 NOTIFY THE ARCHITECT IN CASE OF DISCREPANCIES PRIOR TO CONSTRUCTION. 5.0 ALL SMOKE DETECTORS MUST BE COMBINATION SMOKE / CARBON MONOXIDE ALARM DETECTORS THEY MUST BE (120V) HARD WIRED, INTERCONNECTED WITH A BATTERY BACKUP AND AT LEAST 4 INCHES AWAY FROM THE NEAREST 13 1 14 NO CLOSER THAN 3 FEET TO A FAN AND OR AIR CONDITIONING DUCT OUTLET. IF DETECTORS ARE NOT MOUNTED ON A SIDEWALL, THEY MUST BE LOCATED BETWEEN 4 AND 12 INCHES FROM THE CEILING TO THE TOP 15 EDGE OF THE DETECTORS. ALL DETECTORS SHALL BE LISTED OR LABELED 16 WASHER 12 1/2 20/1 INTERCONNECTED IN NUMBERS THAT EXCEED THE MNFGRS RECOMENDATIONS. IN NO 1.5 CASE SHALL MORE THAN 18 INITIATING DEVICES BE INTERCONNECTED, OF WHICH 12 CAN BE SMOKE ALARMS, WHERE THE INTERCONNECTING MEANS IS NOT SUPERVISED) 17 18 ELECT OUTLETS GFI 12 1/2 20/1 0.4 19 20 21 22 23 24 25 26 27 28 29 30 11.6 PROVIDE AS PER NAME PLATE 30.6 = 85 AMPS 360 NEW 1ODA 30 CIRC. CIRC. BRKR PNL "A" 3 #3 THWN CU T --------AND #8 CU. GROUND IN 1 1/2 COND. EXISTING F' 100A DISC. ' L.1 J 3 #3 THWN CU --'AND #8 CU. GROUND IN 1 1/2 COND. L� �-1 EXISTING METER T EXISTING WIREWAY _ EXIST. ELECT. RISER DIAGRAM NTS IN METER ROOM m 1. DO NOT SCALE ELECTRICAL DRAWINGS. 2. COORDINATE ALL LIGHT SWITCHES AND TELEPHONE JACK LOCATIONS AND QUANTITIES WITH THE OWNER. 3. PROVIDE TAMPER RESISTANT RECEPTACLES FOR ALL 15 AND 20 AMP RECEPTACLES 4. OUTLET BOXES SHALL BE PRESSED STEEL OR PLASTIC, IN DRY LOCATIONS. CAST ALLOY WITH THREADED HUBS IN WET OR DAMP LOCATIONS AND SPECIAL ENCLOSURES O FOR OTHER CLASSIFIED AREAS. 5. DISCONNECT SWITCHES SHALL BE H.P. RATED, HEAVY DUTY, QUICK -MADE, QUICK -BREAK ENCLOSURES AS REQUIRED BY EXPOSURE. 6. ALL TELEPHONE LINE LOCATION AND QUANTITIES SHALL BE VERIFIED WITH THE OWNER. 7. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM AND PROVIDE ALL REQUIREMENTS NECESSARY �.:. FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER. 8. ELECTRICAL SYSTEM SHALL BE COMPLETE AND EFFECTIVELY GROUNDED AS REQUIRED Eo BY THE LATEST EDITION OF THE N.E.C. 9. ALL MATERIALS SHALL BE NEW AND BEAR UNDERWRITERS' LABELS WHERE APPLICABLE. 10. ALL WORK SHALL BE PERFORMED BY LICENSED ELECTRICAL CONTRACTOR IN A FIRST s CLASS WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE. 11. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE #: WITH THE PROCESS OF CONSTRUCTION. 12. CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FROM A PERIOD OF NOT LESS THAN ONE YEAR FROM DATE OF ACCEPTANCE. 13. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 14. ALL REQUIRED INSURANCE SHALL BE PROVIDED FOR PROTECTION AGAINST PUBLIC M M LIABILITY OF PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 15. CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES, INSPECTIONS, AND TESTING. 16. THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD REQUIREMENTS OF POWER tn AND TELEPHONE COMPANIES. 17. PROVIDE GROUNDS FOR ALL CIRCUITS. 18. ALL RACEWAYS UNDERGROUND SHALL BE A MINIMUM OF 3/4" CONDUIT. 19, ALL CIRCUIT BREAKERS, TWO AND THREE POLE, TO BE COMMON TRIP. NO TIE HANDLES, OR TANDEMS WILL BE ACCEPTED. 20. PANELBOARDS SHALL BE PROVIDED WITH COPPER BUS AND GROUNDING BARS. 21. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES P4 ON DRAWINGS. THE CONTRACTOR SHALL BE RESPONSIBLE OF ANY CHANGES DUE TO FAILURE OF NOTIFYING DISCREPANCIES. 22. ELECTRICAL CONTRACTOR TO VERIFY ALL EQUIPMENT ELECTRICAL REQUIREMENTS WITH a MANUFACTURER INCLUDING CONNECTIONS, WIRE SIZES AND VOLTAGES REQUIREMENTS. NOTIFY THE ARCHITECT WITH ANY DISCREPANCIES PRIOR TO CONSTRUCTION. 23, ELECTRICAL CONTRACTOR TO FIELD VERIFY ALL EXISTING ELECTRICAL SERVICE AND CONDITIONS, TO INCLUDE EXISTING POWER PHASE, VOLTAGE AND CAPACITY AND NOTIFY THE ARCHITECT IN CASE OF DISCREPANCIES PRIOR TO CONSTRUCTION. 24. ALL SMOKE DETECTORS MUST BE COMBINATION SMOKE / CARBON MONOXIDE ALARM DETECTORS THEY MUST BE (120V) HARD WIRED, INTERCONNECTED WITH A BATTERY BACKUP AND AT LEAST 4 INCHES AWAY FROM THE NEAREST SIDEWALL TO THE EDGE OF THE DETECTOR. DERECTORS CAN BE NO 1 CLOSER THAN 3 FEET TO THE DOOR OF ANY BATHROOM OR KITCHEN, AND NO CLOSER THAN 3 FEET TO A FAN AND OR AIR CONDITIONING DUCT OUTLET. IF DETECTORS ARE NOT MOUNTED ON A SIDEWALL, THEY MUST BE LOCATED BETWEEN 4 AND 12 INCHES FROM THE CEILING TO THE TOP EDGE OF THE DETECTORS. ALL DETECTORS SHALL BE LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING LABORATORY. (AS PER NFPA 72 11.8.2.2 SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE INTERCONNECTED IN NUMBERS THAT EXCEED THE MNFGRS RECOMENDATIONS. IN NO CASE SHALL MORE THAN 18 INITIATING DEVICES BE INTERCONNECTED, OF WHICH 12 CAN BE SMOKE ALARMS, WHERE THE INTERCONNECTING MEANS IS NOT SUPERVISED) 25.A.H.U. TO HAVE FACTORY DISCONNECTS WATER HEATER TO HAVE DISCONNECT AND DIRECT WIRED 26, ALL CEILING FANS TO BE ON RHEOSTAT COORDINATE ANY OTHER RHEOSTAT LOCATIONS WITH THE OWNER. 27, ALL EXTERIOR LIGHTS TO BE WHITE LIGHT AND GLARE SHALL NOT SPILL OVER TO ADJACENT PROPERTIES. 28. COORDINATE ALL TELEPHONE, ALARM SYSTEM, INTERCOME , CEILING FANS AND LIGHT SWITCHES LOCATIONS AND QUANTITIES WITH THE OWNER. 29, CLOTHES DRYER TRANSITION DUCT TO THE APPLIANCE TO BE A LISTED LABLED. ALL CLOTHES DRYER EXHAUST DUCTS SHALL BE A MINIMUM OF 4" ROUND AND 26 GA. METAL PIPE. DRYER DUCTS SHALL HAVE A SMOOTH INTERIOR SURFACE, AND NOT EXCEED THE MAXIMUM ALLOWABLE LENGTH AS PER CODE. 30. CLOTHES DRYER TRANSITION DUCTS USED TO CONNECT THE APPLIANCE TO THE EXHAUST DUCT SYSTEM SHALL BE LIMITED TO LENGTHS NOT TO EXCEED 8 FEET FOR ELECTRICAL APPLIANCES OR 6 FEET FOR GAS APPLIANCES AND SHALL BE LISTED OR LABLED FOR THE APPLICATION. 31. EXHAUST DUCTS FOR DOMESTIC CLOTHES DRYERS SHALL BE A MIN OF 4" ROUND AND 26 GAGE METAL PIPE. AND SHALL HAVE A SMOOTH INTERIOR FINISH AND THE MAXIMUM DEVELOPMENT LENGHT SHALL NOT EXCEED 25 FEET. 32. AS PER F.B.C. 2007 ALL MTL FRAME PARTITION SECTIONS ARE TO BE GROUNDED WITH #6 CU. GROUND WIRE IN 3/4" COND. CONNECTED TO A MTL ELECTRICAL OUTLET BOX. 33. AS PER N.E.C. 408.4 ALL CIRCUITS AND CIRCUIT MODIFICATIONS SHALL BE LEGIBLY IDENTIFIED AS TO PURPOSE OR USE ON THE CIRCUIT DIRECTORY LOCATED ON THE FACE OF THE INSIDE OF THE PANEL DOOR IN CASE OF A PANELBOARD, AND AT EACH SWITCH ON THE SWITCHBOARD. !------- E)(ISnNG ! I METER ROOM ! TO REMAIN j Ij ! fL._._._._._. -.-.-.-._._._._._._._.J !I cn Li ! INEW EXH. FAN A-6 ® _11 -CONNECT TO THE w ! f B A -g ' ` EXISTING ROOF OPENING Ofo A-6 I ! IN THE SAME LOCATION E, w o I t �� r� !j ! fj ! fj ! j 3 /A- tm. ®.-._._._. .-.-.. .®.®. EXTERIOR LIGHTS ON HOUSE PANEL TIMER NOTE: THE ELECTRICAL CONTRACTOR IS TO VERIFY AND PROVIDE ALL ELECTRICAL REQUIREMENTS TO INCLUDE BUT NOT LIMITED TO ALL FUSE AND WIRE SIZES AS PER EACH MACHINES AND LIGHTS INDIVIDUAL NAME PLATE REQUIREMENTS , MANFGRS INSTALATION MANUAL AND SPECIFICATIONS. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL EQUIPMENTS SPEC SHEETS AND INSTALLATION MANUALS AND SHALL ALSO COORDINATE AND INSURE THAT ALL EQUIPMENT WILL BE PROVIDED IN PROPER WORKING ORDER. NOTIFY THE ARCHITECT IN CASE OF ANY DISCREPANCIES BETWEEN THE PLANS AND EACH MACHINE REQUIREMENTS PRIOR TO ANY CONSTRUCTION. THE CONTRACTOR IS TO COORDINATE AND RECEIVE ALL EQUIPMENT SPECS FROM THE OWNER. I I SCALE: 1/4"=1'-0" BAY - 10 ,COUST CEILING REVIOUS SUSP. CEILING 'K7 S7 EMERGENCY LIGHT FIXTURE WITH BATTERY BACH-UP WIRED TO UNSWITCHED LEG p EXIT LIGHT FIXTURE WITH BATTERY BACH-UP V WIRED TO UNSWITCHED LEG NOT MORE THAN 5W PER FACE LIGHT SWITCHES p 2' X 4' ACCOST FLUORECENT LIGHT FIXTURES ------------------------------------------ II !! f --------------------------------- UISTING! I MM ROOM f � ! TO REMAIN j ELECT PNL. TO REMAIN ! • FIELD VERIFY PROPER f j ! PARTITION E FROM NEW f jL._._._._.-._.-.-.-. ._.-.-.- EXISTING DOOR ! F._•-•-•®•®�®•®•®- VT- ®t- - TO REMAIN j II ! H.C. TOILET ! j DRYER ! j A 12-14 A-18 FI X ! A-2 A ! jQ: WASHER ` j ! j A-8,10 TANKLESS W.H. ! j STOCK ROOM ! ! !! f j II '- •• . W, u A-2 . . Y a i ! o ! !! � .. N w Y j A-2 A-2 ! ! v C3f .. m• ! f! co w ! !! w w! ! !! ! j Y-10 !! CLOTH DROP OFF j ! j A-4 A-4 ! I ! !! i f A -Z 34" HIGH COUNTER f ! f� (BY OTHERS) II f ! !! ! f !! ! ! A-4 I f HIGH OUTLET A-4! ! ! SHOW WINDOW I ! � II EXISTING ROOFED WALKWAY SCALE: 1/4"=1'-0" BAY - 10 11 OV DUPLEX ELECT. OUTLETS - . - • - . - EXISTING WALLS AND ITEMS TO REMAIN x X x X NEW ONE HOUR RATED PARTITIONS 0 E h A W Z - u l gz FWOQ�Q�a�� 0 O � a�vww z z� �z O� vSz DO� un od E E x E O w' 04wA o pA��aWQW,�a•'Ew�woz �EE� WUW aaw.Qc4� �F10, x ar�AwEZ�E-+ZE.a7w3a. w x E A zz rJ DATE 8 -4 -2 - COMM. NO. 15=148 n C! 0 O M M d' Illi co �.:. wN :.., Eo L_jL j, O LL i s u #: °� C kn z kO co DATE 8 -4 -2 - COMM. NO. 15=148 n C! 0 O M M d' wN ^ O O ON1 u a °� C kn kO M M tn W a E-' P4 W a CHE���' DRAWN 1 DATE 8 -4 -2 - COMM. NO. 15=148 n C! H . V. A. C. GENERAL NOTES: ALL WORK SHALL CONFORM WITH THE FLORIDA BUILDING, NFPA, NEC, AND ALL OTHER APPLICABLE FEDERAL, STATE AND LOCAL REGULATIONS AND ORDINANCES. CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, TAXES, INSPECTIONS, TESTS, PERFORMANCE BONDS, FINES AND OTHER ITEMS AS REQUIRED FOR THE INSTALLATION OF THE COMPLETE MECHANICAL SYSTEMS, AND SHALL BE RESPONSIBLE FOR OBTAINING HIS OWN PERMIT. CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. ALSO VERIFY EXISTING CONDITIONS BEFORE START THE JOB. SUBMIT SHOP DRAWING OF ALL MATERIALS AND EQUIPMENT FOR APPROVAL PRIOR TO FABRICATION. MEHCANICAL PLANS ARE DIAGRAMATIC,AND MAY CHANGE DUE TO FIELD CONDITIONS. VENTILATION DUCTWORK MATERIAL ARE SPECIFY ON MECHANICAL PLANS, DUCT CONSTRUCTION, BRACING AND SUSPENSION IN ACCORDANCE WITH THE RECOMMENDATIONS SET FORTH IN THE LATEST EDITION OF THE A.S.H.R.A.E. GUIDE AND S.M.A.C.N.A. STANDARDS. DUCT SIZES SHOWN ARE "INSIDE" DIMENSIONS. VERIFY EXACT LOCATION OF DUCT WITH RESPECT TO STRUCTURE BEFORE FABRICATION. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE PROGRESS OF CONSTRUCTION AND IN STRICT COMPLIANCE WITH ALL APPLICABLE CODES AND STANDARDS. SUBMIT SHOP DRAWING OF ALL MATERIALS AND EQUIPMENT FOR APPROVAL PRIOR TO FABRICATION. GENERAL/MECHANICAL CONTRACTOR SHALL BE VERIFY ALL INSULATION VALUE USED FOR CALCUALTUIONS IN ENERGY AND/OR HEAT LOAD PROVIDED BY MECHANICAL ENGINEER. CUT ALL OPENINGS AND CHASES REQUIRED TO ACCOMODATE THE WORK UNDER THIS DIVISION, AND REPAIR ALL FLOORS, WALLS, ETC., DAMAGED BY SUCH CUTTINGS. ALL WORK DONE UNDER THIS HEADING MUST CONFORM IN EVERY RESPECT TO FINISH AND QUALITY OF MATERIALS AND WORKMANSHIP SPECIFIED UNDER APPROPIATE SECTIONS FOR THE BUILDING. ALL DUCTWORK SHALL CONFORM TO SMACNA STANDARDS. ALL DUCTWORK SIZES ARE INSIDE DIMENSIONS. ALL VENTILATION DUCTWORK SHALL BE GALVANIZED SHEETMETAL OR THERMOFIN. ALL AIR CONDITIONING DUCTWORK SHALL BE FIBERGLASS BOARD OR FLEX MIN R-6 INSU; ATION, MUST CONFORM WITH ALL LOCAL CODES, UNLESS OTHERWISE NOTED. ALL ELBOW SHALL BE PROVIDED WITH TURNING VENTS. MECHANICAL CONTRACTOR SHALL BE RESPONSABLE FOR AIR BALANCE ACORDING WITH PLAN. ALL DUCTWORK RUNNING IN CONDITIONED SPACE COULD BE R-4 AND DUCTWORK RUNNING IN UNCONDITIONED SPACE SHALL BE R-6 MIN INSUATION. PROVIDE 1" UNDERCUT AT ALL INTERIOR DOORS. TEST AND BALANCE REPORT ARE REQUIRED BY INDEPENDENT PROFESIONAL ENGINEER FOR FINAL INSPECTION AS PER FBC REQUIRED. STANDARD 3" WIDE HANGERS Honget extension to be the sum of the distances between the hanging ....r"c and +hn duct size. ID fSmacnal Maximum Hanger Duct size, Inches LOW VELOCITY RETURN 48: Wide or grater 4 ft AIR DUCT (SEE PIAN fift and less than 48" VIEW) deep Width between 28" FLEXBLE DUCT INSTALLATION AND SUPPORT. FLEXIBLE DUCTS SHALL BE CONFIGURED AND SUPPORTED SO AS TO BEI.LMOUTH X PREVENT THE USE OF EXCESS DUCT MATERW, PREVENT DUCT SPIN cOLIAR FITTING WITH EXTRACTOR AND VOLUME DAMPER. QUADRANT {16" Less depth o�d?ess DISLOCATION OR DAMAGE, AND PREVENT CONSTRICTION OF THE DUCT BELOW THE RATED DUCT DIAMETER IN ACCORDANCE WITH THE FOLLOWING TO BE OUTSIDE INSULATION. PROVIDE X REQUIREMENTS: INSULATION GUARD WHERE NECASSARY. X 1. DUCTS SHALL BE INSTALLED FULLY EXTENDED. THE TOTAL EXTENDED LENGTH OF DUCT MATERIAL SHALL NOT EXCEED 5 PERCENT WQmp AIR FLOW OF THE MINIMUM REQUIRED LENGTH FOR THAT RUN. DUCT CONNECTION SHALL BE AT THE TOP OR SIDE OF PLENUM AS SPACE Q 2. BENDS SHALL MAINTAIN A CENTER UNE RADIUM OF N0T LESS THAN CONDITIONS PERM INSULATED FLEX DUCE ONE DUCT DIAMETER. 3. TERMINAL DEVICES SHALL BE SUPPORTED INDEPENDENTLY OF W m SEAL JOINT WITH DUCT THE FLEXIBLE DUCT. 3. HORIZONTAL DUCT SHALL BE SUPPORTED AT INTERNALS NOT SEALER do TAPE GREATER THAN 5 FEET. DUCT SAG BETWEEN SUPPORTS SHALL NOT ry W w EXCEED 1/2 INCH PER FOOT OF LENGTH. SUPPORTS SHALL BE CD C.0 11-- Z PROVIDED WITHIN 1.5 FEET OF INTERMEDIATE FITTINGS AND / INSULATED PLENUM BETWEEN INMEDIATE FITTINGS AND BENDS. CEILING JOISTS o Z AND RIGID DUCTS OR EQUIPMENT SHALL BE CONSIDERED TO BE SUPPOiS STANDARD 3" WIDE HANGERS Honget extension to be the sum of the distances between the hanging ....r"c and +hn duct size. ID fSmacnal Maximum Hanger Duct size, Inches Spacing 48: Wide or grater 4 ft Less the 48 wide fift and less than 48" X deep Width between 28" fift & 48" and greater X than deep X�' {16" Less depth o�d?ess 8ft i6" X CHANNEL SECTION If Total Minimum Minimum Extension is Channel Channel not greater than: Gauge Profile 5. VERTICAL DUCT SHALL BE STABILIZED WiTH SUPPORT STRAPS AT 6" 24 3" X 1.5" INTERVALS NOT GREATER THAN 6 FEET. "--CEIUNG DIFFUSER 18" 22 3" X 2" 6. HANGERS, SADDLES AND OTHER SUPPORTS SHALL MEET THE DUCT 30" 18 3" X 2" MANUFACTURER'S RECOMMENDATIONS AND SHALL BE OF SUFFICIENT WIDTH TO PREVENT RESTRICTION OF THE INTERNAL DUCT DIAMETER. IN NO CASE SHALL THE MATERIAL SUPPORTING FLEXIBLE DUCT THAT FLEXIBLE DUCT CONNECTIONS DET (TYPICAL) USE of 2" WIDE IN DIRECT CONTACT WiTH IT BE LESS THAN 1/2 INCHES WIDE. NTS 22 gauge 2'x 1.5" hangers may be substituted MAXIMUM LENGTH OF FLEXIBLE DUCT for 3" hangers for ducts with widths not over 48" RUNOUT TO DIFFUSER TO BE 10 FEET and depths not over 24" provided that not more than one joint occurs between hangers and the maximum hanger spacing 4ft. Exception: When duct perimeter is 80" or less and does not require reinforcement two joints are permitted between hangers MECHANICAL SCOPE OF WORK: THIS IS AN EXISTING BAY UNDER TENANTS IMPROVEMENT. (NOT CHANGE OF USE) - THE EXISTING A/C EQUIPMENT AND MAIN DUCT RIGID DUCT WILL REMAIN. - IS LIMITED TO INSTALL NEW BRANCHS DUCTS AND VENTILATION FOR DRYER AS SPECIFY IN THIS PLAN A/C GRILLE` SPECS. A 24X24 LAY -IN SUPPLY GRILLE TITUS MODEL: TMSA-AA or similar B 24X24 LAY -IN SUPPLY GRILLE TITUS MODEL: 250 -AA or similar HVAC DESIGN REQUIRES YES NO DUCT SMOKE DETECTOR X FIRE DAMPER(S)/ RADIANT X SMOKE DAMPER(S) X FIRE RATED ENCLOSURE M X FIRE RATED ROOF CEILING ASSEMBLY X�' X FIRE STOPPING L L X SMOKE CONTROL m-' X PROVIDE W/P CAP LOW PROFILE B.D.D. AT TOP, BASE SEAL TO ROOF. BATHROOM PROVIDE WITH CORROSIVE RESISTANT SCREEN, —DRYER. NO SCREEN, CLG. MIN 8" —�--- EXHAUST DUCT DUCT FROM UNIT: —BATH EXHAUST/ 04" galv. M+I, duct 30GA —DRYER EXHAUST/ 04" gals. Mtl. duct 26GA TYPICAL ROOF/ WALL CAP DETAIL @ DRYER AND./OR TOILET EXH. N.7.S. DUSTING METER ROOM TO REMAIN EXISTING DOOR TO REMAIN STOCK ROOM EXIST TO REMAIN 2.5 TON PACKAGE UNIT ON ROOF MODEL: GPC 1330H21AB 1000 CFM J 0 w 0 0 C ' CD z F - x w 0l ";'X24" e ;urn grille J I flex 08" EXIST EXH'- TO REMAIN TOILET ROOM DRYER WASHER DRYER EXH 04" metal pipe 26ga Vent thru Roof I 16X8 R/A on top of UPIN m ,A 20QQX CI flex 08" gr? g 0 V) 11J ,1; O$ ff M MAIN TRUNK TO REMAIN oreillleg flex 08" flex 08 0 34" HIGH COUNTER A' geil� n BAY -1 0 CLOTH DROP OFF EXISTING ROOFED WALKWAY MECHANICAL PLAN SCALE: 1/4"44' EXISTING MAIN DUCT RIGID DUCT WILL REMAIN. SUSPENDED ACUSTICAL CEILING Z 14 aw Az oLIQ pq tiW 0 UA�A7�ya6rn � Q�wcGFQ-dH�z��� Z L�> Wow .4 `�� C O Q� H A W w Z ZpO SUAwwwOpWpv,F 7 W Z H O O x x A A F x > VIUpAw pAA`W Cjw`��'Q+`ry'Zww zxwO O 0 C a��aop4a��av�HU aW¢�o�oao��� d�Aa�i-+Z�r�nZNa�3a. I Z O o Q M ry X�' M L L oo zm m-' o WQmp � Q ry —I z Z . W m __�_3oo ry W w M I L.! CD C.0 11-- Z F- � r4O o Z Q 0° O N O M M o Q � O 0 �Q w o N w � r4O � Q a � a 16.t z 00 Q M a+ � �b O U V N Cn C�1 �M 2 � W W a A A CHECKED a DRAWN DATE 8-4-2015 COMM. NO. 15-14$ a U