DRAWINGSINSTALL I NEW STROBE AND
I NEW HORN/STROBE i Or; ;;
TENANT MODIFICATION,
GENERAL_ PROJECT NOTES
1) PROVIDE 120 VOLT DEDICATED CIRCUIT FOR FIRE ALARM SYSTEM BREAKER TO BE MARKED "FIRE ALARM CIRCUIT". BREAKER SHALL BE MARKED IN RED AND
MUST HAVE A BREAKER LOCK INSTALLED ON IT.
2) CONDUIT AND BOXES INSTALLED BY ELECTRICAL CONTRACTOR UNDER SEPERATE CONTRACT AND ELECTRICAL PERMIT.
3) FIRE ALARM SYSTEM INSTALLATION IN ACCORDANCE WITH NFPA 72 2007 EDITION, 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN, AND WIRING UNDER NFPA 70.
4) ALL CONDUIT SHALL BE 3/4" UNLESS OTHERWISE NOTED.
5) THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT.
6) THE LIGHT OUTPUT SHALL COMPLY WITH THE POLAR DISPERSION REQUIREMENTS OF ANSI/UL 1971, STANDARD FOR SAFETY SIGNALING DEVICES FOR HEARING
IMPAIRED, OR EQUIVALENT.
7) ALL VISUAL NOTIFICATION APPLIANCES MUST BE SYNCHRONIZED IN ACCORDANCE WITH NFPA 72:7.5
8) FIRE ALARM SHOP DRAWINGS ARE BASED ON CONTRACT DRAWINGS DATED 10/14/14.
9) SHADED (GREY) DEVICES ARE EXISTING TO REMAIN.
10) CLASS AND STYLE FOR ALL CIRCUITS ARE AS FOLLOWS:
(1) INITIATING DEVICE CIRCUITS - CLASS B, STYLE A
(2) SIGNALING LINE CIRCUITS - CLASS B, STYLE 4
(3) NOTIFICATION CIRCUITS - CLASS B, STYLE Y
11) THE CURRENT SYSTEM IS AN EXISTING CENTERAL STATION SERVICE SYSTEM AND DYNAFIRE INC. IS THE CURRENT CERTIFICATE HOLDER.
SYM DESCRIPTION
EQUIPMENT LEGEND
MOUNTING P/N
MPP PArW RnY
M f1 c-- I i n r,
FAoCP
---- -- ----.- �_,,. U.U. Jur-F
FIRE ALARM CONTROL PANEL ETR 72" AFF FCI-7100 FCI PROVIDED MANUFACTURER
NAC POWER SUPPLY ETR 60" AFF WHEELOCK PS -8 WHEELOCK PROVIDED MANUFACTURER
STROBE - WALL MOUNT 80" - 96" TO BOTTOM OF LENS AFF HSR WHEELOCK 4" SQUARE BOX (2-1/8"DEEP) ELECTRICAL
STROBE ONLY - WALL MOUNT 80" - 96" TO BOTTOM OF LENS AFF STR WHEELOCK 4" SQUARE BOX (2-1/8" DEEP) ELECTRICAL
NAC
gHORN
:ABLE DESCRIPTION
B I NOTIFICATION CIRCUIT
CABLE LEGEND
MAN WIRP TYPP
WINDY CITY WIRE 1 14/2 THHN
DRAWING 'IlCit;t
FA -1 COVER PAGE & LEGEND
FA -2 TENANT IMPROVEMENT AREA
FA -3 DETAILS, BATTERY CALCS.
z
0
F-
W
U
W
W
W
I-
Q
0
W
ry
z
0
U
D
F-
cf)
z
O
U
0
0
w
D
d-
O
N
N
JOB NUMBER: 3352SVC04
ISSUE DATE: 12/11/2014
DRAWN BY: Joseph Levenson
CHECKED BY: Cory Abbott
=a 0
75cd
75cd
75cd
75cd
75cd
75cd
EOL 1.2
1.2.1
1.2.2
1.2.3
1.2.4
1.2.5
1.2.6
ETR
ETR
ETR
ETR
ETR
ETR
75cd
75cd
75cd
75cd
75cd
75cd 75cd
75cd
p
1.1.1
1.1.2
1.1.3
1.1.4
1.1.5
1.1.6 1.1.7
1.1.8
._.mma ETR
ETR
ETR
ETR
ETR
N ETR
N
ETR NAC
SCALE: 1/8" = 1'
EOL 1.1
w
Q
C)
W
ry
z
O
U
ry
z
O
U
ry
O F --
Li J_
r
W M
� I
(n Q
d -
Ln
O
N O
\ N
r- \
NI\
JOB NUMBER: 3352SVC04
ISSUE DATE: 12/11/2014
DRAWN BY: Joseph Levenson
CHECKED BY: Cory Abbott
SHOP DRAWING
VIN
a'
U
C
N
FA -l' .�
0
TYPICAL SEQUENCE OF OPERATION
I A
�A
CONDUIT FIRESTOPPING DETAIL
System No. W -L-1148
F Ratings -1 and 2 Hr
T Rating - 0 Hr
SECTION A -A
1. Wall Assembly - The fire -rated gypsum wallboard/stud wall assembly
shall be constructed of the materials and in the manner specified in the
individual 0300 or U400 Series Wall and Partition Designs in the Fire
Resistance Directory and shall include the following construction features:
A. Studs - Wall framing shall consist of either wood studs or channel
shaped steel studs. Wood studs to consist of 2 by 4 in. lumber spaced
16 in. OC. Steel studs to be min 2-1/2 in. wide, fabricated from min
25 MSG galvanized steel, spaced max 24 in. OC.
B. Wallboard, Gypsum* - 5/8 in. thick, 4 ft wide with square or tapered
edges. The gypsum wallboard type, number of layers and sheet
orientation shall be as specified in the individual U300 or U400 Series
Designs in the UL Fre Resistance Directory. Max diam of opening is 13
in. (BRGU) category in the
The hourly F Rating of the firestop system is equal to the hourly fire
rating of the wall assembly in which it is installed.
2. Through Penetrants - One metallic pipe, conduit or tubing to be installed
either concentrically or eccentrically within L+ et flhgst,%eMbtift, rfte5/8 in.
>-,c- to be n 2ly supported on both sides of the assembly.
The following types and sizes of metallic pipes, conduits or tubing may
be used:
A. Steel Pipe - Nom 8 in. diam (or smaller) Schedule 10 (or heavier)
steel pipe.
B. Iron Pipe - Nom 8 in. diam (or smaller) cast or ductile iron pipe.
C. Conduit - Nom 4 in. diam (or smaller) steel electrical metallic tubing
or steel conduit.
3. Pipe Covering - Nom 2 in. thick hollow cylindrical heavy density (min
3.5 pcf) fiberglass pipe covering with an all -service jacket. Pipe covering
material to be min 9 in. long and installed on penetrant to extend 2 in.
beyond bath sides of wall surface. Longitudinal joints sealed with metal
fasteners or factory -applied self-sealing lap (SSL) tape; The annular space
between the pipe covering and periphery of opening shall be min 0 in.
(point contact) to max 3/8 in.
See Pipe and Equipment Covering -Materials
Building Materials Directory for names of manufacturers. Any pipe
covering material meeting the above specifications and bearing the
UL Classification Marking with a Flame Spread Index of 25 or less and
a Smoke Developed Index of 50 or less may be used.
4. Fill, Void or Cavity Material* - Sealant
thickness of fill material applied within annulus flush with both surfaces
of wall. In 2 hr assemblies, min 1-1/4 in. thickness of fill material
applied within annulus flush with both surfaces of wall. For both 1 and
2 hr assemblies, of point contact location between insulation and
gypsum, a min 1/2 in. bead of fill material shall be applied on both sides
of wall.
FREEWIRE FIRESTOPPING DETAIL
System No. W -L-3065
F Ratings --1 and 2 Hr (See Item 1)
T Rating -- 0 Hr
SECTION A -A
1. Wall Assembly -- The 1 or 2 fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in
the individual U300, U400 or V600 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following
construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in.
OC. Steel studs to be min 2-1/2 in . vide and spaced max 24 in. OC.
B. Gypsum Board* -- Nom 5/8 in. thick gypsum board, with square or tapered edges. The gypsum board type, thickness, number of layers,
fastener type and sheet orientation shall be as specified in the individual U300, U400 or V600 Series Design in the UL Fire Resistance
Directory. Max diam of opening is 5-1/2 in. when sleeve (item 2) is employed. Max diam of opening is 4 in. when sleeve (item 2) is not
employed.
The F Rating of the firestop system is equal to the fire rating of the wall assembly.
2. Metallic Sleeve -- (Optional) - Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT) or Schedule 5 (or heavier) steel pipe or min 0.016
in. thick (28 ga) galy steel sleeve installed flush with wall surfaces. The annular space between steel sleeve and periphery of opening shall be min
0 in. (point contact) to max 1 in. When Schedule 5 steel pipe or EMT is used, sleeve may extend up to 18 in. beyond the wall surfaces.
3. Cables -- Aggregate cross-sectional area of cable in opening to be max 45 percent of the cross-sectional area of the opening. The annular space
between the cable bundle and the periphery of the opening to be min 0 in. to max 1 in. Cables to be rigidly supported on both sides of the wall
assembly. Any combination of the following types and sizes of copper conductor cables may be used:
A. Max 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket.
B. Max 25 pair No. 24 AWG telephone cable with PVC insulation and jacket.
C. Type RG/U coaxial cable with polyethylene (PE) insulation and PVC jacket having a max outside diameter of Y in.
D. Multiple fiber optical communication cable jacketed with PVC and having a max OD of 5/8 in.
E. Through Penetrating Products*-- Max three copper conductor No. 8 AWG . Metal -Clad Cable+.
AFC CABLE SYSTEMS INC
F. Max 3/C (with ground)(or smaller) No. 8 AWG copper conductor cable with PVC insulation and jacketing.
4. Fill, Void or Cavity Material*-- Sealant-- Fill material applied within the annulus, flush with each end of the steel sleeve or wall surface. Fill
material installed symmetrically on both sides of the wall. A min 5/8 in. thickness of sealant is required for the 1 or 2 hr F Rating. An additional 1/2
in. diam bead of fill material shall be applied around the perimeter of sleeve on both sides of the wall when sleeve extends beyond surface of wall.
HILTI CONSTRUCTION CHEMCIALS, DIV OF HILTI INC -- CP601S, CP606 or FS -One Sealant
*Bearing the UL Classification Mark
FIRE PANEL AES RADIO
R R R
7.7
m0 -xi 10000 0000 0000 0000 oeoe
�' +� � I & I � �ml �m � o I o 0 o I o ii � I H ❑ JO iRCU&E Rfl%Y
x� x� J10
CUSS -A CDNYflilp2 MODUIF
PRIMER
i10 F� Ut_
J2 ❑ ACPOWERPOWER TROUBLE
❑ ALM SUPERVISORY
>= RESET SILENCE MODE
ego w ❑❑❑❑❑ PH1
o000o FO
o
J3 01 ❑❑❑❑E PH2 ® = = 0 16v MPUT asTTERY r I N I H
��J9 00 0000 0000
E:IEIEIEIHI
CB1 H N G BAiIERY TEsr conREcroR
O 0 0 0 mil �.O
J11 0
LRL
(-) (+)F1 El(-) (+)El El(-) (+)
BATTERY BATTERY BATTERY
AFI4ECDTRANSF-ER
PN %r1w
165VAC iM
SMOKE DETECTOR INSTALLATION DETAIL
CONTROL UNIT
CEILING
-
4111;-=-=-=•�i
Multiply by 1.2 for saftey margin
ANNUNCIATION
NOTIFICATION
REQUIRED FIRE SAFETY CONTROL
SUPPLEMENTARY
U)
------------------------------
The maximum current available for aux cp and mastermode sync
bus is
DETECTOR MUST BEAT
For 24 hour standby time, up to .24 amps max using 12 Ahr
r-
LEAST / FROM WALL, AT
For 60 hour standby time , up to .02 amps maximum using 12
1
LEAST 36" FROM ANY AIRDUCT
For 72 hour standby time; up to .02 amps maximum using 33 Ahr batteries
WALL MOUNTED SMOKE
L
DETECTOR MUST BEAT
The PS -8 will fit 2 12112 Ahr batteries
a_
LL
ALEAST 4"
BELOWL
i' 1t9
Z
Z �
BUT
TO TOP OF DETECTOR
91199
Amp
OoH
9 t9
~ O
draw
CIR 1 CIR 2
O
U
~`D~
N
1 SR/SW of 15CD
0.068
0
F-
9 999
Z H
0.094
o z���
Z
Z
01.135
5 4
4 SR/SW a 110CD
0.2012
4 U
v z a z w a w w
of Z O ¢
� a a w
z
0.0660..__
U
w
6 'SRISW @ 30CD
0.094
O¢ mCDM=
¢ > w Z= = p O
(DoO
w Y 0
N O ¢
6.158
Of
0SQJ� w ¢¢
:¢
� z O o z
r-
HORNISTROBE ....., _.
W> z af x z Lu
L> moow �cn
z
cn ¢ LD ¢ X
z w L>w
U x w
X
w
_
-
K a US= ~ O D I=- Q
0.107
O C7 a 0
Z
'� Ed
cn
w
11 SPSR/SPSW 675CD
0.148
J= n. c¢_J w w x
of Xz
w C7
Of
O � z w z O z UOJ O w o
~O¢ Lu
O
=
M
¢ J U w o w
K CI]
CD
w
O
13 SPSR/SPSd @15CD
0.0660
m m m
¢ w w
ULU ZD
0.094
U¢ U¢¢
0.158
16 PPR/SR SW 110CD
0.202
w¢ U z p
UJ H
1' H Q ip a-
-
w
w cn �- < O Z Z
a 1- : � Y
w
a
-
1 Fw-
¢ ¢ ¢ ¢ ¢ ¢ ¢
z
¢
>
} - N - U O Y
< ¢ w o
Y
PER CIRCUIT DRAW
F= H F¢= p w
U U U U U U U P-- x a
�.
U
a z z z J cn r -O
� it = z
O
z
AMPS
¢ ¢ ¢ ¢ ¢ ¢ ¢ U O U O
¢
w
o r- 1- i- U <n z
=
INPUTS
CIR 1
CIR 8
AMP LOAD
1 MANUAL PULL STATION - FIRST LEVEL
0
0
DISTANCE FROM SOURCE TO EOL
2 AREA SMOKE DETECTOR - FIRST LEVEL
0
0 0
WIRE GUAGE
3 IN -DUCT SMOKE DETECTOR - FIRST LEVEL
1.929
14 0.000
CIRCULAR MIL
4110
0
0
VOLTAGE DROP PERCENTAGE
4 WATERFLOW-FIRST LEVEL
0
0
5 SPRINKLER CONTROL VALVE - FIRST LEVEL
0
AMP LOAD
6 FIRE PUMP RUNNING
DISTANCE
7 FIRE PUMP POWER FAILURE/PHASE REVERSAL
VDROP
650 VIJRO
W IRE GUAGE
8 FIRE PUMP AC POWER FAILURE
1.538
14 0.000
_.............. CIRCULAR MIL
9 FIRE PUMP SYSTEM LOW BATTERY
USABLE
4110 USABLE
VOLTAGE DROP PERCENTAGE
10 OPEN CIRCUIT
18.362
0.00%0 20.400
11 GROUND FAULT
12 NOTIFICATION APPLIANCE CIRCUIT SHORT
13 ON/OFF OVERRIDE FOR SMOKE EXHAUST IN FIRE COMMAND
I A
�A
CONDUIT FIRESTOPPING DETAIL
System No. W -L-1148
F Ratings -1 and 2 Hr
T Rating - 0 Hr
SECTION A -A
1. Wall Assembly - The fire -rated gypsum wallboard/stud wall assembly
shall be constructed of the materials and in the manner specified in the
individual 0300 or U400 Series Wall and Partition Designs in the Fire
Resistance Directory and shall include the following construction features:
A. Studs - Wall framing shall consist of either wood studs or channel
shaped steel studs. Wood studs to consist of 2 by 4 in. lumber spaced
16 in. OC. Steel studs to be min 2-1/2 in. wide, fabricated from min
25 MSG galvanized steel, spaced max 24 in. OC.
B. Wallboard, Gypsum* - 5/8 in. thick, 4 ft wide with square or tapered
edges. The gypsum wallboard type, number of layers and sheet
orientation shall be as specified in the individual U300 or U400 Series
Designs in the UL Fre Resistance Directory. Max diam of opening is 13
in. (BRGU) category in the
The hourly F Rating of the firestop system is equal to the hourly fire
rating of the wall assembly in which it is installed.
2. Through Penetrants - One metallic pipe, conduit or tubing to be installed
either concentrically or eccentrically within L+ et flhgst,%eMbtift, rfte5/8 in.
>-,c- to be n 2ly supported on both sides of the assembly.
The following types and sizes of metallic pipes, conduits or tubing may
be used:
A. Steel Pipe - Nom 8 in. diam (or smaller) Schedule 10 (or heavier)
steel pipe.
B. Iron Pipe - Nom 8 in. diam (or smaller) cast or ductile iron pipe.
C. Conduit - Nom 4 in. diam (or smaller) steel electrical metallic tubing
or steel conduit.
3. Pipe Covering - Nom 2 in. thick hollow cylindrical heavy density (min
3.5 pcf) fiberglass pipe covering with an all -service jacket. Pipe covering
material to be min 9 in. long and installed on penetrant to extend 2 in.
beyond bath sides of wall surface. Longitudinal joints sealed with metal
fasteners or factory -applied self-sealing lap (SSL) tape; The annular space
between the pipe covering and periphery of opening shall be min 0 in.
(point contact) to max 3/8 in.
See Pipe and Equipment Covering -Materials
Building Materials Directory for names of manufacturers. Any pipe
covering material meeting the above specifications and bearing the
UL Classification Marking with a Flame Spread Index of 25 or less and
a Smoke Developed Index of 50 or less may be used.
4. Fill, Void or Cavity Material* - Sealant
thickness of fill material applied within annulus flush with both surfaces
of wall. In 2 hr assemblies, min 1-1/4 in. thickness of fill material
applied within annulus flush with both surfaces of wall. For both 1 and
2 hr assemblies, of point contact location between insulation and
gypsum, a min 1/2 in. bead of fill material shall be applied on both sides
of wall.
FREEWIRE FIRESTOPPING DETAIL
System No. W -L-3065
F Ratings --1 and 2 Hr (See Item 1)
T Rating -- 0 Hr
SECTION A -A
1. Wall Assembly -- The 1 or 2 fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in
the individual U300, U400 or V600 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following
construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in.
OC. Steel studs to be min 2-1/2 in . vide and spaced max 24 in. OC.
B. Gypsum Board* -- Nom 5/8 in. thick gypsum board, with square or tapered edges. The gypsum board type, thickness, number of layers,
fastener type and sheet orientation shall be as specified in the individual U300, U400 or V600 Series Design in the UL Fire Resistance
Directory. Max diam of opening is 5-1/2 in. when sleeve (item 2) is employed. Max diam of opening is 4 in. when sleeve (item 2) is not
employed.
The F Rating of the firestop system is equal to the fire rating of the wall assembly.
2. Metallic Sleeve -- (Optional) - Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT) or Schedule 5 (or heavier) steel pipe or min 0.016
in. thick (28 ga) galy steel sleeve installed flush with wall surfaces. The annular space between steel sleeve and periphery of opening shall be min
0 in. (point contact) to max 1 in. When Schedule 5 steel pipe or EMT is used, sleeve may extend up to 18 in. beyond the wall surfaces.
3. Cables -- Aggregate cross-sectional area of cable in opening to be max 45 percent of the cross-sectional area of the opening. The annular space
between the cable bundle and the periphery of the opening to be min 0 in. to max 1 in. Cables to be rigidly supported on both sides of the wall
assembly. Any combination of the following types and sizes of copper conductor cables may be used:
A. Max 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket.
B. Max 25 pair No. 24 AWG telephone cable with PVC insulation and jacket.
C. Type RG/U coaxial cable with polyethylene (PE) insulation and PVC jacket having a max outside diameter of Y in.
D. Multiple fiber optical communication cable jacketed with PVC and having a max OD of 5/8 in.
E. Through Penetrating Products*-- Max three copper conductor No. 8 AWG . Metal -Clad Cable+.
AFC CABLE SYSTEMS INC
F. Max 3/C (with ground)(or smaller) No. 8 AWG copper conductor cable with PVC insulation and jacketing.
4. Fill, Void or Cavity Material*-- Sealant-- Fill material applied within the annulus, flush with each end of the steel sleeve or wall surface. Fill
material installed symmetrically on both sides of the wall. A min 5/8 in. thickness of sealant is required for the 1 or 2 hr F Rating. An additional 1/2
in. diam bead of fill material shall be applied around the perimeter of sleeve on both sides of the wall when sleeve extends beyond surface of wall.
HILTI CONSTRUCTION CHEMCIALS, DIV OF HILTI INC -- CP601S, CP606 or FS -One Sealant
*Bearing the UL Classification Mark
FIRE PANEL AES RADIO
R R R
7.7
m0 -xi 10000 0000 0000 0000 oeoe
�' +� � I & I � �ml �m � o I o 0 o I o ii � I H ❑ JO iRCU&E Rfl%Y
x� x� J10
CUSS -A CDNYflilp2 MODUIF
PRIMER
i10 F� Ut_
J2 ❑ ACPOWERPOWER TROUBLE
❑ ALM SUPERVISORY
>= RESET SILENCE MODE
ego w ❑❑❑❑❑ PH1
o000o FO
o
J3 01 ❑❑❑❑E PH2 ® = = 0 16v MPUT asTTERY r I N I H
��J9 00 0000 0000
E:IEIEIEIHI
CB1 H N G BAiIERY TEsr conREcroR
O 0 0 0 mil �.O
J11 0
LRL
(-) (+)F1 El(-) (+)El El(-) (+)
BATTERY BATTERY BATTERY
AFI4ECDTRANSF-ER
PN %r1w
165VAC iM
SMOKE DETECTOR INSTALLATION DETAIL
DEVICE INSTALLATION DETAIL
44-2-1/8
BOX \
CEILI
44-2-1/8 & PER DRAWINGS
BOX CEILING NAG DEVICE
FIRE ALARM
HORN/STROBE
FIRE ALARM
ANNUNCIATOR
PANEL
FIRE ALARM
44-2-1/8MANUAL
BOX /`/ PULL STATION
48" TO CENTER
FINISHES
- FLOOR
80" TO
BOTTOM
OF LENS
TERNALIY WUWED
N W&E WRS
Stanby current for the PS -8 is .1 0.129
Enter number €zf nxsteunitsonsyncbus..Etter0ifunitisstandalone i
Multiply by -006 for each route Sync Bus Total' ?.0065
Enter current di-aw on aux Ifset to MP oxide enter 0 03.000
Aux oversee note 11 0.008
Total 0.1
Multiply by standby hours required 24,60 1 24
Total Standby Amp Flour 3.24
Notification Annlianrpg
CEILING
1 3.76
4111;-=-=-=•�i
Multiply by 1.2 for saftey margin
Total Ahr Deeded
NEVER IN THIS AREACEILING
i
� I
MOUNTED SMOKE
ST STROBE
The maximum current available for aux cp and mastermode sync
bus is
DETECTOR MUST BEAT
For 24 hour standby time, up to .24 amps max using 12 Ahr
W�i
LEAST / FROM WALL, AT
For 60 hour standby time , up to .02 amps maximum using 12
1
LEAST 36" FROM ANY AIRDUCT
For 72 hour standby time; up to .02 amps maximum using 33 Ahr batteries
WALL MOUNTED SMOKE
L
DETECTOR MUST BEAT
The PS -8 will fit 2 12112 Ahr batteries
811
ALEAST 4"
BELOWL
i' 1t9
BOYNTON COMMERCE CENTER
BUT
TO TOP OF DETECTOR
DEVICE INSTALLATION DETAIL
44-2-1/8
BOX \
CEILI
44-2-1/8 & PER DRAWINGS
BOX CEILING NAG DEVICE
FIRE ALARM
HORN/STROBE
FIRE ALARM
ANNUNCIATOR
PANEL
FIRE ALARM
44-2-1/8MANUAL
BOX /`/ PULL STATION
48" TO CENTER
FINISHES
- FLOOR
80" TO
BOTTOM
OF LENS
TERNALIY WUWED
N W&E WRS
Stanby current for the PS -8 is .1 0.129
Enter number €zf nxsteunitsonsyncbus..Etter0ifunitisstandalone i
Multiply by -006 for each route Sync Bus Total' ?.0065
Enter current di-aw on aux Ifset to MP oxide enter 0 03.000
Aux oversee note 11 0.008
Total 0.1
Multiply by standby hours required 24,60 1 24
Total Standby Amp Flour 3.24
Notification Annlianrpg
Enter Alann Time 5 minutes =.083 15 mimutes =. 25 0.25
Total 0.52
Add standby and Alarm Together
�! -.
1 3.76
Multiply by 1.2 for saftey margin
Total Ahr Deeded
FISR !` RO -
i
E
ST STROBE
The maximum current available for aux cp and mastermode sync
bus is
For 24 hour standby time, up to .24 amps max using 12 Ahr
batteries
For 60 hour standby time , up to .02 amps maximum using 12
Ahr batteries
For 72 hour standby time; up to .02 amps maximum using 33 Ahr batteries
Note 2
91119
The PS -8 will fit 2 12112 Ahr batteries
i' 1t9
BOYNTON COMMERCE CENTER
WHEEL CK ISS -8 - P'CLIV ROP
91199
Amp
9 t9
Device type
draw
CIR 1 CIR 2
9 199
STROBE ONLY -WALL
1 SR/SW of 15CD
0.068
9 999
2 SR/SW @ 30CD _
0.094
Enter Alann Time 5 minutes =.083 15 mimutes =. 25 0.25
Total 0.52
Add standby and Alarm Together
1 3.76
Multiply by 1.2 for saftey margin
Total Ahr Deeded
4.81
Note 1
The maximum current available for aux cp and mastermode sync
bus is
For 24 hour standby time, up to .24 amps max using 12 Ahr
batteries
For 60 hour standby time , up to .02 amps maximum using 12
Ahr batteries
For 72 hour standby time; up to .02 amps maximum using 33 Ahr batteries
Note 2
The PS -8 will fit 2 12112 Ahr batteries
BOYNTON COMMERCE CENTER
WHEEL CK ISS -8 - P'CLIV ROP
Amp
Device type
draw
CIR 1 CIR 2
CIR 3 CIR 4
STROBE ONLY -WALL
1 SR/SW of 15CD
0.068
2 SR/SW @ 30CD _
0.094
3 SRISW @ 75CD
01.135
5 4
4 SR/SW a 110CD
0.2012
STkbB - CEILING
5 SRISW @ 15CD
0.0660..__
6 'SRISW @ 30CD
0.094
7 SR/SW a 75CD
6.158
8 SR/SW @ 110CD -
0.202
HORNISTROBE ....., _.
9 SPSR/SPSW @15CD
0.079
_
-
10 SPSRISPS I @3ObD
0.107
.
11 SPSR/SPSW 675CD
0.148
3 2
12 SPSR/SPSV (6110CD
0.212
SPEAKERISTROBE
13 SPSR/SPSd @15CD
0.0660
14 PSR/ PSV/ a@30CD
0.094
15 PSRICPSW @75CD
0.158
16 PPR/SR SW 110CD
0.202
17 SPSRKISPSWK @ 75CD
0.158
-
18 SPSRKISPSWK @ 110CD
0.202
PER CIRCUIT DRAW
1.119 01.836
0 0
TOTAL AMPS ON POKIER SUPPLY
1,955
AMPS
VOLTAGE DROP CALCULATIONS
CIR 1
CIR 8
AMP LOAD
1.119
0
DISTANCE FROM SOURCE TO EOL
328
VDROP
600 ,DROP_.
WIRE GUAGE
14
1.929
14 0.000
CIRCULAR MIL
4110
USABLE
41100 USABLE
VOLTAGE DROP PERCENTAGE
146%
J 18.471
0.00% 20.400
CIR 2
CIR 4
AMP LOAD
00.8360
DISTANCE
350
VDROP
650 VIJRO
W IRE GUAGE
14
1.538
14 0.000
_.............. CIRCULAR MIL
4110
USABLE
4110 USABLE
VOLTAGE DROP PERCENTAGE
7.54°la
18.362
0.00%0 20.400
DynaFire
DYNAFIRE INC.
PHONE (407) 830-6500 - FAX (407) 831-1 47
1098 Concord Drive
CASSELBERRY, FLORIDA 32707
E-MAIL: - dyn afireOdyn afire. us
Qualifier: STEVEN HATCH
STATE LICENCE # EF20000528
Z
O
I-
n
U
U)
LLJ
C�
LLJ
Q
LJ
Z
_O
I-
U
e'
F-
Z
O
U
0'
OLL_ F -
_J
� m
::D I
C
C/) Q
Ln
O 0
\ N
\ N
N \
JOB NUMBER: 3352SVC04
ISSUE DATE: 12/11/2014
DRAWN BY: Joseph Levenson
CHECKED BY: Cory Abbott
SHOP DRAWING
U
FA -
1
0
SCOPEO
�NSTALL I NEW STROBE AND
I NEW HORN/STROBE FOR A
TENANT i i -r =icAori.
BOYNTON TOWN CENTER
GENERAL PROJECT NOTES
1) PROVIDE 120 VOLT DEDICATED CIRCUIT FOR FIRE ALARM SYSTEM, BREAKER TO BE MARKED "FIREALARM CIRCUIT". BREAKER SHALL BE MARKED IN RED AND
MUST HAVE A BREAKER LOCK INSTALLED ON IT.
2) CONDUIT AND BOXES INSTALLED BY ELECTRICAL CONTRACTOR UNDER SEPERATE CONTRACT AND ELECTRICAL PERMIT.
3) FIRE ALARM SYSTEM INSTALLATION IN ACCORDANCE WITH NFPA 72 2007 EDITION, 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN, AND WIRING UNDER NFPA 70.
4) ALL CONDUIT SHALL BE 3/4" UNLESS OTHERWISE NOTED.
5) THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT.
6) THE LIGHT OUTPUT SHALL COMPLY WITH THE POLAR DISPERSION REQUIREMENTS OF ANSI/UL 1971, STANDARD FOR SAFETY SIGNALING DEVICES FOR HEARING
IMPAIRED, OR EQUIVALENT.
7) ALL VISUAL NOTIFICATION APPLIANCES MUST BE SYNCHRONIZED IN ACCORDANCE WITH NFPA 72:15
8) FIRE ALARM SHOP DRAWINGS ARE BASED ON CONTRACT DRAWINGS DATED 10/14/14.
9) SHADED (GREY) DEVICES 'ARE EXISTING TO REMAIN.
10) CLASS AND STYLE FOR ALL CIRCUITS ARE AS FOLLOWS:
(1) INITIATING DEVICE CIRCUITS - CLASS B, STYLE A
(2) SIGNALING LINE CIRCUITS - CLASS B, STYLE 4
(3) NOTIFICATION CIRCUITS - CLASS B, STYLE Y
11) THE CURRENT SYSTEM IS AN EXISTING CENTERAL STATION SERVICE SYSTEM AND DYINIAFIRE INC. S THE CURRENT CERTIFICATE HOLDER.
BOYNTON BEACH FL.
SYM DESCRIPTION
EQUIPMENT LEGEND
MOUNTING P/N
B.B. SUPP
FACP
FIRE ALARM CONTROL PANEL ETR
72" AFF
NFS2-3030
NOTIFIER
PROVIDED
MANUFACTURER
NAC
NAC POWER SUPPLY ETR
60" AFF
FACPS-2458
NOTIFIER
PROVIDED
MANUFACTURER
HORN STROBE WALL MOUNT
80" - 96" TO BOTTOM OF LENS AFF
P2R
SYSTEM SENSOR
4" SQUARE BOX (2-1/8" DEEP)
ELECTRICAL
STROBE ONLY WALL MOUNT
80" - 96" TO BOTTOM OF LENS AFF
SR
SYSTEM SENSOR
4" SQUARE BOX (2-1/8" DEEP)
ELECTRICAL
>I o o w
0 `r' pq
m �0
F-
0
0
C)
Z
0
�
0
p::
L-
n
�
�
Li
ABLE DESCRIPTION
CABLE LEGEND
MAN WIRE TYPE
B NOTIFICATION CIRCUIT WINDY CITY WIRE 14/2 THHN
rp, C F!E.S 0 W91 ESE D
DEC` 16 2014.
DRAW NC INDEXO-FILE COPY<-'
BUILDING DIVISION5,
FA -1
Dy np Fi re•
COVER PAGE & LEGEND
FA -2
109B Concord Drive
TENANT IMPROVEMENT AREA
FA -3
Qualifier: STEVEN HATCH
DETAILS, BATTERY CALCS.
ct
C:
o �
-0 o
C:
>I o o w
0 `r' pq
m �0
47
LL-
Dy np Fi re•
DYNAFIRE INC.
PHONE (407) 830-6500 — FAX (407) 831-11-
109B Concord Drive
CASSELBERRY, FLORIDA 32707
E—MAIL: dynofire@dynafire.us
Qualifier: STEVEN HATCH
STATE LICENCE # EF20000528
ct
C:
o �
-0 o
C:
>I o o w
0 `r' pq
m �0
F-
0
0
C)
Z
0
�
0
p::
L-
n
�
�
Li
C)
U)
Lij
U)
LL -j
0
<
0
C\A
LLJ
11,011 Mw
JOB NUMBER: 3352SVC04
ISSUE DATE: 12/11/2014
DRAWN BY: Joseph Levenson
CHECKED BY: Cory Abbott
SHOP DRAWING
FA -1
47
LL-
m 0
w"bl
75cd
75cd
75cd
75cd
75cd
75cd
PHONE (407) 830-6500 — FAX (407) 831-11-
109B Concord Drive
.........
.... ...............
........ ....
. .................... EOL 1.2
1.2.1
1.2.2
1.2.3
1.2.4
1.2.5
1.2.6
ETR
ETR
ETR
ETR
ETR
ETR
75cd
75cd
75cd
75cd
750
75cd
75cd 75cd
-
0 -----EOL 1.1
1.1.1
1.1.2
1.1.3
1.1.4
1.1.5
1.1.6
1.1.7 1.1.8
ETR
ETR
ETR
ETR
ETR
N
ETR N
ETR NAC
SCALE: 1/8" = 1'
09, 2-52 60 Ek 0V [R 0
DEC 16 20114
>FIL E COPY --A
ISUILMING 0MVISION
47
3
Dy na Fi re•
DYNAFIRE INC.
PHONE (407) 830-6500 — FAX (407) 831-11-
109B Concord Drive
CASSELBERRY,
FLORIDA 32707
E—MAIL:
dynafireOdynafire.us
Qualifier: STEVEN HATCH
STATE LICENCE # EF20000528
14 WIN -
O
ct
4-a
C:
con
0O
�
�i
��
C:
0
C)
C:
>1
0
`� pq
0
-
C)F-
D
LL
0
z
0
0
LL -
a_
C)
Ld
W
D
LLJ
0
LSI
KNI''i 21
JOB NUMBER: 3352SVC04
ISSUE DATE:
12/11/2014
DRAWN BY: Joseph Levenson
CHECKED
BY: Cory Abbott
ry
SHOP DRAWING
FA -1
L
47
3
TYPICAL SEQUENCE OF OPERATION
CONDUIT FIRESTOPPING DETAIL
System No. W -L-1148
F Ratings -1 and 2 Hr
T Rating - 0 Hr
F_A
1A
1,6
4
I A
SECTION A -A
1. Wall Assembly - The fire -rated gypsum wallboard/stud wall assembly
shall be constructed of the materials and in the manner specified in the
individual 0300 or U400 Series Wall and Partition Designs in the Fire
Resistance Directory and shall include the following construction features:
A. Studs - Wall framing shall consist of either wood studs or channel
shaped steel studs. Wood studs to consist of 2 by 4 in. lumber spaced
16 in. OC. Steel studs to be min 2-1/2 in. wide, fabricated from min
25 MSG galvanized steel, spaced max 24 in. OC.
B. Wallboard, Gypsum* - 5/8 in. thick, 4 ft wide with square or tapered
edges. The gypsum wallboard type, number of layers and sheet
orientation shall be as specified in the individual -U300 or U400 Series
Designs in the UL Fire Resistance Directory. Max diam of opening is 13
in. (BRGU) category in the
The hourly F Rating of the firestop system is equal to the hourly fire
rotinQ of the wall assembly in which.4 is installed.
2 1nro;gh Penetrants - One metallic pipe, conduit or tubing to be installed
either concentrically; or eccentrically within tiliet fiygstAte3p®*. rliifle5/8 in.
conduit or tubing to be rigidly 'supported on both sides of the assembly.
The following types and sizes of metallic pipes, conduits or tubing may
be used:
A. Steel Pipe - Nom 8 in. diam (or smaller) Schedule 10 (or heavier)
steel pipe.
B. Iron Pipe - Nom 8 in. diam (or smaller) cast or ductile iron pipe.
C. Conduit - Nom 4 in. diom (or smaller) steel electrical metallic tubing
or steel conduit.
3. Pipe Covering - Nom 2 in. thick hollow cylindrical heavy density (min
3.5 pcf) fiberglass pipe covering with an all -service jacket. Pipe covering
material to be min 9 in. long and installed on penetrant to extend 2 in.
beyond both sides of wall surface. Longitudinal joints sealed with metal
fasteners or factory -applied self-sealing lop (SSL) tape. The annular space
between the pipe covering and periphery of opening shall be min 0 in.
(point contact) to max 3/8 in.
See Pipe and Equipment Covering-Moterials
Building Materials Directory for names of manufacturers. Any pipe
covering material meeting the above specifications and bearing the
UL Classification Marking with a Flame Spread Index of 25 or less and
a Smoke Developed Index of 50 or less may be used.
4. fill, Void or Cavity Material* - Sealant
thickness of fill material applied within annulus flush with both surfaces
of wall. In 2 hr assemblies, min 1-1/4 in. thickness of fill material
applied within annulus flush with both surfaces of wall. For both 1 and
2 hr assemblies, at point contact location between insulation and
gypsum, a min 1/2 in. bead of fill material shall be applied on both sides
of wall.
FREEWIRE FIRESTOPPING DETAIL
System No. W -L-3065
M
F Ratings --1 and 2 Hr (See Item 1) 3
T Rating -- 0 Hr
F -A 2 1A
2 4
3
ILA 1B
SECTION A -A
1. Wall Assembly - The 1 or 2 fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in i
the individual U300, U400 or V600 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following
construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in.
OC. Steel studs to be min 2-1/2 in . wide and spaced max 24 in. OC.
B. Gypsum Board* - Nom 5/8 in. thick gypsum board, with square or tapered edges. The gypsum board type, thickness, number of layers,
fastener type and sheet orientation shall be as specified in the individual U300, U400 or V600 Series Design in the UL Fire Resistance
Directory. Max diam of opening is 5-1/2 in. when sleeve (item 2) is employed. Max diam of opening is 4 in. when sleeve (item 2) is not
employed. '
The F Rating of the firestop system is equal to the fire rating of the wall assembly.
2. Metallic Sleeve - (Optional) - Nom 4 in, diam (or smaller) steel electrical metallic tubing (EMT) or Schedule 5 (or heavier) steel pipe or min 0.016
in. thick (28 ga) galy steel sleeve installed flush with wall surfaces. The annular space between steel sleeve and periphery of opening shall be min
0 in. (point contact) to max 1 in. When Schedule 5 steel pipe or EMT is used, sleeve may extend up to 18 in. beyond the wall surfaces.
3. Cables - Aggregate cross-sectional area of cable in opening to be max 45 percent of the cross-sectional area of the opening. The annular space
between the cable bundle and the periphery of the opening to be min 0 in, to max 1 in. Cables to be rigidly supported on both sides of the wall
assembly. Any combination of the following types and sizes of copper conductor cables may be used:
A. Max 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket.
B. Max 25 pair Nd. 24 AWG telephone cable with PVC insulation and jacket.
C. Type RG/U coaxial cable with polyethylene (PE) insulation and PVC jacket having a max outside diameter of % in.
D. Multiple fiber optical communication cable jacketed with PVC and having a max OD of 5/8 in.
E. Through Penetrating Products*- Max three copper conductor No. 8 AWG . Metal -Clad Cable+.
AFC CABLE SYSTEMS INC'
F. Max 3/C (with ground)(or smaller) No. 8 AWG copper conductor cable with PVC insulation and jacketing.
4. Fill, Void or Cavity Material*- Sealant - Fill material applied within the annulus, flush with each end of the steel sleeve or wap surface. Fill
material installed symmetrically ori both sides of the wall. A min 5/8 in. thickness of sealant is required for the 1 or 2 hr F Rating. An additional 1/2
in. diam bead of fill material shall be applied around the perimeter of sleeve on both sides of the wall when sleeve extends beyond surface of wall
HILT[ CONSTRUCTION CHEMCIALS, DIV OF HILTI INC - CP601S, CP606 or FS -One Sealant
*Bearing the UL Classification Mark;
FIRE PANEL
CONTROL UNIT
�R
=
000 �
ANNUNCIATION
NOTIFICATION
REQUIRED FIRE SAFETY CONTROL
SUPPLEMENTARY
Power Supervision Relays
W
=
0
i'CEILING MOUNTED SMOKE
DETECTOR t
LEAST I• WALL ANDt
Auxiliary Current Draw
LEAST FROM ANY AIR D
H
auh
WALL • r SMOKE
C1A55-A CONVERTER MOOUI�.E
DETECTOR MUST BEAT
811
C 1 BELOW CEILING
BUT NO LOWER THAN
w
X 1.318
TO TOP OF DETECTOR
1.318
Z 0
NAC / Output ## 2 1
O ¢ Z
.
0.984
O
NAC / Output ## 3
¢ 0
-
0
O
0
NAC / Output ## 4
X
_
0
�SQ
ALARIVI LOAD'
=
2a 7
J
Battery Amp Hour Calculation
O ¢
Z 6r EC
> W �
O of
Current (Amps)
(Typically 24 or 60 f-In>ats)
0.065
o Z z
z J w rl
UJ
wa
o 0
w0
Required Alarm Time
Current (Amps)
c~n
z O o
o
j w O?
g ¢ d
Z ¢ o
C7 0 c) O
U O = CC
O- X ¢¢
Z
F- cn
Z O
~
O Z of cn
o
cn
t --
LTotal Ampm
Hours
w>>
m z of LU= in
u) Z CO
o <
w > w
= w J
w
Amp
a a
O o w=
z
Ow o
C0 2
w=
a D
w
m
1 ;SRISW @ 15CD
0.066
¢
w
H x
z 0 o
p
p CD
a
v wLU
w
0.158 _
w
4 S R/S W @ 110CD
0.202
o Z J
z J o o
O¢
t=
J
LU
mU
5 :SR/SW @ 15CD
0.066.
6 "'SR/SW @ 30CD
0.094
p
r-
V¢
_0.158 _
ww
aOw
LL LWi
z
W>go
HORN/STROBE
O J
Q¢
0.079
r
(D
OpQ0¢
0.107_
11 'SPSR/SPSW @75CD
0.176
LU LU ULI
a
LU
0.212
Y
o Y
13 SPSRISPSW 15CD0.066
F>>>>>>
of
0.094
cncn
o
Y
16 SPSR/SPSW @110CD
0.202
¢¢ ¢ ¢
FZ Ou)w
¢ ¢ ¢
fQ-
Z
aTz¢Fn-
LU
UP
4.202
0
PER CIRCUIT DRAM
1.318 0.984 0 0
u) U O
AMPS
VOLTAGE DROP CALCULATIONS
INPUTS
CIR 1
CIR 3
AMP LOAD
1,318
0
DISTANCE FROM SOURCE TO EOL
328
VDROP 600 VDROP
1 MANUAL PULL STATION -FIRST LEVEL
2.272 14 0.000
14
CIRCULAR MIL
10 01 10
•
VOLTAGE DROP PERCENTAGE
•
2 AREA SMOKE DETECTOR - FIRST LEVEL
• •
1 10 • • • •
•
• 01 10
•
0
•
3 IN -DUCT SMOKE DETECTOR- FIRST LEVEL
• •
10 • • •
1
• 01 10
•
4110
•
4 WATERFLOW-FIRST LEVEL
• •
10 • • • •
1
• 01 1 10
•
•
5 SPRINKLER CONTROL VALVE - FIRST LEVEL
• •
1
1
•
6 FIRE PUMP RUNNING
•
10
7 FIRE PUMP POWER FAILURE/PHASE REVERSAL
• •
• •
8 FIRE PUMP AC POWER FAILURE
• •
•
9 FIRE PUMP SYSTEM LOW BATTERY -
• •
•
10 OPEN CIRCUIT
• •
•
11 GROUND FAULT
• •
•
12 NOTIFICATION APPLIANCE CIRCUIT SHORT
• •
•
13 ON/OFF OVERRIDE FOR SMOKE EXHAUST IN FIRE COMMAND
•
CONDUIT FIRESTOPPING DETAIL
System No. W -L-1148
F Ratings -1 and 2 Hr
T Rating - 0 Hr
F_A
1A
1,6
4
I A
SECTION A -A
1. Wall Assembly - The fire -rated gypsum wallboard/stud wall assembly
shall be constructed of the materials and in the manner specified in the
individual 0300 or U400 Series Wall and Partition Designs in the Fire
Resistance Directory and shall include the following construction features:
A. Studs - Wall framing shall consist of either wood studs or channel
shaped steel studs. Wood studs to consist of 2 by 4 in. lumber spaced
16 in. OC. Steel studs to be min 2-1/2 in. wide, fabricated from min
25 MSG galvanized steel, spaced max 24 in. OC.
B. Wallboard, Gypsum* - 5/8 in. thick, 4 ft wide with square or tapered
edges. The gypsum wallboard type, number of layers and sheet
orientation shall be as specified in the individual -U300 or U400 Series
Designs in the UL Fire Resistance Directory. Max diam of opening is 13
in. (BRGU) category in the
The hourly F Rating of the firestop system is equal to the hourly fire
rotinQ of the wall assembly in which.4 is installed.
2 1nro;gh Penetrants - One metallic pipe, conduit or tubing to be installed
either concentrically; or eccentrically within tiliet fiygstAte3p®*. rliifle5/8 in.
conduit or tubing to be rigidly 'supported on both sides of the assembly.
The following types and sizes of metallic pipes, conduits or tubing may
be used:
A. Steel Pipe - Nom 8 in. diam (or smaller) Schedule 10 (or heavier)
steel pipe.
B. Iron Pipe - Nom 8 in. diam (or smaller) cast or ductile iron pipe.
C. Conduit - Nom 4 in. diom (or smaller) steel electrical metallic tubing
or steel conduit.
3. Pipe Covering - Nom 2 in. thick hollow cylindrical heavy density (min
3.5 pcf) fiberglass pipe covering with an all -service jacket. Pipe covering
material to be min 9 in. long and installed on penetrant to extend 2 in.
beyond both sides of wall surface. Longitudinal joints sealed with metal
fasteners or factory -applied self-sealing lop (SSL) tape. The annular space
between the pipe covering and periphery of opening shall be min 0 in.
(point contact) to max 3/8 in.
See Pipe and Equipment Covering-Moterials
Building Materials Directory for names of manufacturers. Any pipe
covering material meeting the above specifications and bearing the
UL Classification Marking with a Flame Spread Index of 25 or less and
a Smoke Developed Index of 50 or less may be used.
4. fill, Void or Cavity Material* - Sealant
thickness of fill material applied within annulus flush with both surfaces
of wall. In 2 hr assemblies, min 1-1/4 in. thickness of fill material
applied within annulus flush with both surfaces of wall. For both 1 and
2 hr assemblies, at point contact location between insulation and
gypsum, a min 1/2 in. bead of fill material shall be applied on both sides
of wall.
FREEWIRE FIRESTOPPING DETAIL
System No. W -L-3065
M
F Ratings --1 and 2 Hr (See Item 1) 3
T Rating -- 0 Hr
F -A 2 1A
2 4
3
ILA 1B
SECTION A -A
1. Wall Assembly - The 1 or 2 fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in i
the individual U300, U400 or V600 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following
construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in.
OC. Steel studs to be min 2-1/2 in . wide and spaced max 24 in. OC.
B. Gypsum Board* - Nom 5/8 in. thick gypsum board, with square or tapered edges. The gypsum board type, thickness, number of layers,
fastener type and sheet orientation shall be as specified in the individual U300, U400 or V600 Series Design in the UL Fire Resistance
Directory. Max diam of opening is 5-1/2 in. when sleeve (item 2) is employed. Max diam of opening is 4 in. when sleeve (item 2) is not
employed. '
The F Rating of the firestop system is equal to the fire rating of the wall assembly.
2. Metallic Sleeve - (Optional) - Nom 4 in, diam (or smaller) steel electrical metallic tubing (EMT) or Schedule 5 (or heavier) steel pipe or min 0.016
in. thick (28 ga) galy steel sleeve installed flush with wall surfaces. The annular space between steel sleeve and periphery of opening shall be min
0 in. (point contact) to max 1 in. When Schedule 5 steel pipe or EMT is used, sleeve may extend up to 18 in. beyond the wall surfaces.
3. Cables - Aggregate cross-sectional area of cable in opening to be max 45 percent of the cross-sectional area of the opening. The annular space
between the cable bundle and the periphery of the opening to be min 0 in, to max 1 in. Cables to be rigidly supported on both sides of the wall
assembly. Any combination of the following types and sizes of copper conductor cables may be used:
A. Max 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket.
B. Max 25 pair Nd. 24 AWG telephone cable with PVC insulation and jacket.
C. Type RG/U coaxial cable with polyethylene (PE) insulation and PVC jacket having a max outside diameter of % in.
D. Multiple fiber optical communication cable jacketed with PVC and having a max OD of 5/8 in.
E. Through Penetrating Products*- Max three copper conductor No. 8 AWG . Metal -Clad Cable+.
AFC CABLE SYSTEMS INC'
F. Max 3/C (with ground)(or smaller) No. 8 AWG copper conductor cable with PVC insulation and jacketing.
4. Fill, Void or Cavity Material*- Sealant - Fill material applied within the annulus, flush with each end of the steel sleeve or wap surface. Fill
material installed symmetrically ori both sides of the wall. A min 5/8 in. thickness of sealant is required for the 1 or 2 hr F Rating. An additional 1/2
in. diam bead of fill material shall be applied around the perimeter of sleeve on both sides of the wall when sleeve extends beyond surface of wall
HILT[ CONSTRUCTION CHEMCIALS, DIV OF HILTI INC - CP601S, CP606 or FS -One Sealant
*Bearing the UL Classification Mark;
FIRE PANEL
11 AC POWER ❑ TROUBLE
❑ ALARM ❑ SUPERVISORY
RESET SILENCE MODE
❑❑❑❑❑
❑ ❑ ❑ ❑ ❑
❑ ❑ ❑ ❑ ❑
❑❑❑❑❑
J4
PRIMER
❑
MODULE
F-1 ❑
PHI
PH2
OJ9
Cal H N G MM, TETT OONNECTOR
0 0 0 �J7 J11 C.......
BATTERY
SMOKE DETECTOR INSTALLATION DETAIL
�R �R
�R
=
000 �
� 000 0000 0000 0000 0000 0000
1 ••moiNEVER IN THIS AREA
Power Supervision Relays
X 0.025
=
0
i'CEILING MOUNTED SMOKE
DETECTOR t
LEAST I• WALL ANDt
Auxiliary Current Draw
LEAST FROM ANY AIR D
H
auh
WALL • r SMOKE
C1A55-A CONVERTER MOOUI�.E
11 AC POWER ❑ TROUBLE
❑ ALARM ❑ SUPERVISORY
RESET SILENCE MODE
❑❑❑❑❑
❑ ❑ ❑ ❑ ❑
❑ ❑ ❑ ❑ ❑
❑❑❑❑❑
J4
PRIMER
❑
MODULE
F-1 ❑
PHI
PH2
OJ9
Cal H N G MM, TETT OONNECTOR
0 0 0 �J7 J11 C.......
BATTERY
SMOKE DETECTOR INSTALLATION DETAIL
DEVICE INSTALLATION DETAIL
4x4-2-1/8
BOX
44-2-1/8
BOX
4x4-2-1/8'
BOX \\
- PER DRAWINGS
CEILING NAG DEVICE
FIRE ALARM
HORN/STROBE
FIRE ALARM
ANNUNCIATOR
PANEL
FIRE ALARM
MANUAL
PULL STATION
48" TO CENTER
FINISHES
- FLOOR
80" TO
BOTTOM
OF LENS
0
A%ECOTIL1NSi0RIAER
PM %F16d0
f6.5 VAC dWA
ETM- MquNrED
iNTROU&EEURER
LOAD- =
Regulated Load in ALARM
Number of Current Total Current,
Device Type Devices (Amps) (Amps)
Main PC Board without AC 1
411 CEILING
=
411
1 ••moiNEVER IN THIS AREA
Power Supervision Relays
X 0.025
=
0
i'CEILING MOUNTED SMOKE
DETECTOR t
LEAST I• WALL ANDt
Auxiliary Current Draw
LEAST FROM ANY AIR D
g
WALL • r SMOKE
from TB4 Terminals 9 & 10
DETECTOR MUST BEAT
811
C 1 BELOW CEILING
BUT NO LOWER THAN
NAC / Output ##' 1 1
X 1.318
TO TOP OF DETECTOR
1.318
DEVICE INSTALLATION DETAIL
4x4-2-1/8
BOX
44-2-1/8
BOX
4x4-2-1/8'
BOX \\
- PER DRAWINGS
CEILING NAG DEVICE
FIRE ALARM
HORN/STROBE
FIRE ALARM
ANNUNCIATOR
PANEL
FIRE ALARM
MANUAL
PULL STATION
48" TO CENTER
FINISHES
- FLOOR
80" TO
BOTTOM
OF LENS
0
A%ECOTIL1NSi0RIAER
PM %F16d0
f6.5 VAC dWA
ETM- MquNrED
iNTROU&EEURER
LOAD- =
Regulated Load in ALARM
Number of Current Total Current,
Device Type Devices (Amps) (Amps)
�(gr . z
>11UILE CC)py<
UNLDIMG IM90
DynaFire
DYNAFIRE INC.
PHONE (407) 830-6500 - FAX (407) 831-1
1098 Concord Drive
CASSELBERRY, FLORIDA 32707
E-MAIL: dynafire@dynafire.us
Qualifier: STEVEN HATCH
STATE LICENCE # EF20000528
Z
_O
I-
O
D
F--
1110
Z
O
U
IY
O
11
C)
W
D
V)
O
N
N
JOB NUMBER: 3352SVC04
ISSUE DATE: 12/11/2014
DRAWN BY: Joseph Levenson
CHECKED BY: Cory Abbott
SHOP DRAWING
U
C:
FA -
Main PC Board without AC 1
X 0.145
=
0.145
Power Supervision Relays
X 0.025
=
0
Auxiliary Current Draw
X
g
from TB4 Terminals 9 & 10
NAC / Output ##' 1 1
X 1.318
=
1.318
NAC / Output ## 2 1
X 0.984
0.984
NAC / Output ## 3
X
-
0
NAC / Output ## 4
X
_
0
ALARIVI LOAD'
=
2a 7
Battery Amp Hour Calculation
Standby Load
Required Standby Time
Current (Amps)
(Typically 24 or 60 f-In>ats)
0.065
X
24 = 1.56 `AH
Alarm Lead
Required Alarm Time
Current (Amps)
(Typically 5 or 10 Minutes)
2.447
X
10 = 0.41 AH
Sub Total Standby I Alarm Amp Hours 1.97 AH
Multiply by the Derating Factor X
LTotal Ampm
Hours
Requir"e""d3.
BO TON COMMERCE CENTER
FOPS -24F8 - PCL/VDROP
Amp
I
Device type
draw
CIR 1 CIR 2 CIR 3 CIR 4
STROBE ONLY -WALL
1 ;SRISW @ 15CD
0.066
2 'SR/SW @ 30CD
0.094
3 SR/SW @ 75CD
0.158 _
5 4
4 S R/S W @ 110CD
0.202
STROBE -CEILING
5 :SR/SW @ 15CD
0.066.
6 "'SR/SW @ 30CD
0.094
7 SRISW @ 75CD
_0.158 _
8 SRISW @ 11OCD
4.202
HORN/STROBE
9 'SPSR/SPSW @15CD
0.079
10 SPSR/SPSW t@r 30CD
0.107_
11 'SPSR/SPSW @75CD
0.176
3 2
12 'SPSR/SPSW @110CD
0.212
SPEAKERISTROBE
13 SPSRISPSW 15CD0.066
14 SPSR/SPSW @30CD
0.094
15 SPSR/SPSW @75CD
0.158
16 SPSR/SPSW @110CD
0.202
17 `SPSRKISPSWK @ 75CD
0.158
18 "SPSRKISF'SWK @ 110CD
4.202
PER CIRCUIT DRAM
1.318 0.984 0 0
TOTAL AMPS ON POWER SUPPLY
2,302
AMPS
VOLTAGE DROP CALCULATIONS
CIR 1
CIR 3
AMP LOAD
1,318
0
DISTANCE FROM SOURCE TO EOL
328
VDROP 600 VDROP
WIRE GUAGE
2.272 14 0.000
14
CIRCULAR MIL
4110
USABLE 4110 USABLE
VOLTAGE DROP PERCENTAGE
18.128 0.00% 1 20.400
11.14%
CIR 2
CIR 4
AMP LOAD
0.984
0
DISTANCE
350
VDROP __. 650 VDROP
WIRE GUAGE
14
1.810 14 0.000
CIRCULAR MIL
4110
USABLE 4110 USABLE
VOLTAGE DROP PERCENTAGE
8.87a/o
18.590 0.00% 20.400
�(gr . z
>11UILE CC)py<
UNLDIMG IM90
DynaFire
DYNAFIRE INC.
PHONE (407) 830-6500 - FAX (407) 831-1
1098 Concord Drive
CASSELBERRY, FLORIDA 32707
E-MAIL: dynafire@dynafire.us
Qualifier: STEVEN HATCH
STATE LICENCE # EF20000528
Z
_O
I-
O
D
F--
1110
Z
O
U
IY
O
11
C)
W
D
V)
O
N
N
JOB NUMBER: 3352SVC04
ISSUE DATE: 12/11/2014
DRAWN BY: Joseph Levenson
CHECKED BY: Cory Abbott
SHOP DRAWING
U
C:
FA -