DRAWINGSINSTALL I NEW STROBE AND I NEW HORN/STROBE i Or; ;; TENANT MODIFICATION, GENERAL_ PROJECT NOTES 1) PROVIDE 120 VOLT DEDICATED CIRCUIT FOR FIRE ALARM SYSTEM BREAKER TO BE MARKED "FIRE ALARM CIRCUIT". BREAKER SHALL BE MARKED IN RED AND MUST HAVE A BREAKER LOCK INSTALLED ON IT. 2) CONDUIT AND BOXES INSTALLED BY ELECTRICAL CONTRACTOR UNDER SEPERATE CONTRACT AND ELECTRICAL PERMIT. 3) FIRE ALARM SYSTEM INSTALLATION IN ACCORDANCE WITH NFPA 72 2007 EDITION, 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN, AND WIRING UNDER NFPA 70. 4) ALL CONDUIT SHALL BE 3/4" UNLESS OTHERWISE NOTED. 5) THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT. 6) THE LIGHT OUTPUT SHALL COMPLY WITH THE POLAR DISPERSION REQUIREMENTS OF ANSI/UL 1971, STANDARD FOR SAFETY SIGNALING DEVICES FOR HEARING IMPAIRED, OR EQUIVALENT. 7) ALL VISUAL NOTIFICATION APPLIANCES MUST BE SYNCHRONIZED IN ACCORDANCE WITH NFPA 72:7.5 8) FIRE ALARM SHOP DRAWINGS ARE BASED ON CONTRACT DRAWINGS DATED 10/14/14. 9) SHADED (GREY) DEVICES ARE EXISTING TO REMAIN. 10) CLASS AND STYLE FOR ALL CIRCUITS ARE AS FOLLOWS: (1) INITIATING DEVICE CIRCUITS - CLASS B, STYLE A (2) SIGNALING LINE CIRCUITS - CLASS B, STYLE 4 (3) NOTIFICATION CIRCUITS - CLASS B, STYLE Y 11) THE CURRENT SYSTEM IS AN EXISTING CENTERAL STATION SERVICE SYSTEM AND DYNAFIRE INC. IS THE CURRENT CERTIFICATE HOLDER. SYM DESCRIPTION EQUIPMENT LEGEND MOUNTING P/N MPP PArW RnY M f1 c-- I i n r, FAoCP ---- -- ----.- �_,,. U.U. Jur-F FIRE ALARM CONTROL PANEL ETR 72" AFF FCI-7100 FCI PROVIDED MANUFACTURER NAC POWER SUPPLY ETR 60" AFF WHEELOCK PS -8 WHEELOCK PROVIDED MANUFACTURER STROBE - WALL MOUNT 80" - 96" TO BOTTOM OF LENS AFF HSR WHEELOCK 4" SQUARE BOX (2-1/8"DEEP) ELECTRICAL STROBE ONLY - WALL MOUNT 80" - 96" TO BOTTOM OF LENS AFF STR WHEELOCK 4" SQUARE BOX (2-1/8" DEEP) ELECTRICAL NAC gHORN :ABLE DESCRIPTION B I NOTIFICATION CIRCUIT CABLE LEGEND MAN WIRP TYPP WINDY CITY WIRE 1 14/2 THHN DRAWING 'IlCit;t FA -1 COVER PAGE & LEGEND FA -2 TENANT IMPROVEMENT AREA FA -3 DETAILS, BATTERY CALCS. z 0 F- W U W W W I- Q 0 W ry z 0 U D F- cf) z O U 0 0 w D d- O N N JOB NUMBER: 3352SVC04 ISSUE DATE: 12/11/2014 DRAWN BY: Joseph Levenson CHECKED BY: Cory Abbott =a 0 75cd 75cd 75cd 75cd 75cd 75cd EOL 1.2 1.2.1 1.2.2 1.2.3 1.2.4 1.2.5 1.2.6 ETR ETR ETR ETR ETR ETR 75cd 75cd 75cd 75cd 75cd 75cd 75cd 75cd p 1.1.1 1.1.2 1.1.3 1.1.4 1.1.5 1.1.6 1.1.7 1.1.8 ._.mma ETR ETR ETR ETR ETR N ETR N ETR NAC SCALE: 1/8" = 1' EOL 1.1 w Q C) W ry z O U ry z O U ry O F -- Li J_ r W M � I (n Q d - Ln O N O \ N r- \ NI\ JOB NUMBER: 3352SVC04 ISSUE DATE: 12/11/2014 DRAWN BY: Joseph Levenson CHECKED BY: Cory Abbott SHOP DRAWING VIN a' U C N FA -l' .� 0 TYPICAL SEQUENCE OF OPERATION I A �A CONDUIT FIRESTOPPING DETAIL System No. W -L-1148 F Ratings -1 and 2 Hr T Rating - 0 Hr SECTION A -A 1. Wall Assembly - The fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual 0300 or U400 Series Wall and Partition Designs in the Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing shall consist of either wood studs or channel shaped steel studs. Wood studs to consist of 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in. wide, fabricated from min 25 MSG galvanized steel, spaced max 24 in. OC. B. Wallboard, Gypsum* - 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, number of layers and sheet orientation shall be as specified in the individual U300 or U400 Series Designs in the UL Fre Resistance Directory. Max diam of opening is 13 in. (BRGU) category in the The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrants - One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within L+ et flhgst,%eMbtift, rfte5/8 in. >-,c- to be n 2ly supported on both sides of the assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe - Nom 8 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 8 in. diam (or smaller) cast or ductile iron pipe. C. Conduit - Nom 4 in. diam (or smaller) steel electrical metallic tubing or steel conduit. 3. Pipe Covering - Nom 2 in. thick hollow cylindrical heavy density (min 3.5 pcf) fiberglass pipe covering with an all -service jacket. Pipe covering material to be min 9 in. long and installed on penetrant to extend 2 in. beyond bath sides of wall surface. Longitudinal joints sealed with metal fasteners or factory -applied self-sealing lap (SSL) tape; The annular space between the pipe covering and periphery of opening shall be min 0 in. (point contact) to max 3/8 in. See Pipe and Equipment Covering -Materials Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. 4. Fill, Void or Cavity Material* - Sealant thickness of fill material applied within annulus flush with both surfaces of wall. In 2 hr assemblies, min 1-1/4 in. thickness of fill material applied within annulus flush with both surfaces of wall. For both 1 and 2 hr assemblies, of point contact location between insulation and gypsum, a min 1/2 in. bead of fill material shall be applied on both sides of wall. FREEWIRE FIRESTOPPING DETAIL System No. W -L-3065 F Ratings --1 and 2 Hr (See Item 1) T Rating -- 0 Hr SECTION A -A 1. Wall Assembly -- The 1 or 2 fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400 or V600 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in . vide and spaced max 24 in. OC. B. Gypsum Board* -- Nom 5/8 in. thick gypsum board, with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300, U400 or V600 Series Design in the UL Fire Resistance Directory. Max diam of opening is 5-1/2 in. when sleeve (item 2) is employed. Max diam of opening is 4 in. when sleeve (item 2) is not employed. The F Rating of the firestop system is equal to the fire rating of the wall assembly. 2. Metallic Sleeve -- (Optional) - Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT) or Schedule 5 (or heavier) steel pipe or min 0.016 in. thick (28 ga) galy steel sleeve installed flush with wall surfaces. The annular space between steel sleeve and periphery of opening shall be min 0 in. (point contact) to max 1 in. When Schedule 5 steel pipe or EMT is used, sleeve may extend up to 18 in. beyond the wall surfaces. 3. Cables -- Aggregate cross-sectional area of cable in opening to be max 45 percent of the cross-sectional area of the opening. The annular space between the cable bundle and the periphery of the opening to be min 0 in. to max 1 in. Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types and sizes of copper conductor cables may be used: A. Max 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket. B. Max 25 pair No. 24 AWG telephone cable with PVC insulation and jacket. C. Type RG/U coaxial cable with polyethylene (PE) insulation and PVC jacket having a max outside diameter of Y in. D. Multiple fiber optical communication cable jacketed with PVC and having a max OD of 5/8 in. E. Through Penetrating Products*-- Max three copper conductor No. 8 AWG . Metal -Clad Cable+. AFC CABLE SYSTEMS INC F. Max 3/C (with ground)(or smaller) No. 8 AWG copper conductor cable with PVC insulation and jacketing. 4. Fill, Void or Cavity Material*-- Sealant-- Fill material applied within the annulus, flush with each end of the steel sleeve or wall surface. Fill material installed symmetrically on both sides of the wall. A min 5/8 in. thickness of sealant is required for the 1 or 2 hr F Rating. An additional 1/2 in. diam bead of fill material shall be applied around the perimeter of sleeve on both sides of the wall when sleeve extends beyond surface of wall. HILTI CONSTRUCTION CHEMCIALS, DIV OF HILTI INC -- CP601S, CP606 or FS -One Sealant *Bearing the UL Classification Mark FIRE PANEL AES RADIO R R R 7.7 m0 -xi 10000 0000 0000 0000 oeoe �' +� � I & I � �ml �m � o I o 0 o I o ii � I H ❑ JO iRCU&E Rfl%Y x� x� J10 CUSS -A CDNYflilp2 MODUIF PRIMER i10 F� Ut_ J2 ❑ ACPOWERPOWER TROUBLE ❑ ALM SUPERVISORY >= RESET SILENCE MODE ego w ❑❑❑❑❑ PH1 o000o FO o J3 01 ❑❑❑❑E PH2 ® = = 0 16v MPUT asTTERY r I N I H ��J9 00 0000 0000 E:IEIEIEIHI CB1 H N G BAiIERY TEsr conREcroR O 0 0 0 mil �.O J11 0 LRL (-) (+)F1 El(-) (+)El El(-) (+) BATTERY BATTERY BATTERY AFI4ECDTRANSF-ER PN %r1w 165VAC iM SMOKE DETECTOR INSTALLATION DETAIL CONTROL UNIT CEILING - 4111;-=-=-=•�i Multiply by 1.2 for saftey margin ANNUNCIATION NOTIFICATION REQUIRED FIRE SAFETY CONTROL SUPPLEMENTARY U) ------------------------------ The maximum current available for aux cp and mastermode sync bus is DETECTOR MUST BEAT For 24 hour standby time, up to .24 amps max using 12 Ahr r- LEAST / FROM WALL, AT For 60 hour standby time , up to .02 amps maximum using 12 1 LEAST 36" FROM ANY AIRDUCT For 72 hour standby time; up to .02 amps maximum using 33 Ahr batteries WALL MOUNTED SMOKE L DETECTOR MUST BEAT The PS -8 will fit 2 12112 Ahr batteries a_ LL ALEAST 4" BELOWL i' 1t9 Z Z � BUT TO TOP OF DETECTOR 91199 Amp OoH 9 t9 ~ O draw CIR 1 CIR 2 O U ~`D~ N 1 SR/SW of 15CD 0.068 0 F- 9 999 Z H 0.094 o z��� Z Z 01.135 5 4 4 SR/SW a 110CD 0.2012 4 U v z a z w a w w of Z O ¢ � a a w z 0.0660..__ U w 6 'SRISW @ 30CD 0.094 O¢ mCDM= ¢ > w Z= = p O (DoO w Y 0 N O ¢ 6.158 Of 0SQJ� w ¢¢ :¢ � z O o z r- HORNISTROBE ....., _. W> z af x z Lu L> moow �cn z cn ¢ LD ¢ X z w L>w U x w X w _ - K a US= ~ O D I=- Q 0.107 O C7 a 0 Z '� Ed cn w 11 SPSR/SPSW 675CD 0.148 J= n. c¢_J w w x of Xz w C7 Of O � z w z O z UOJ O w o ~O¢ Lu O = M ¢ J U w o w K CI] CD w O 13 SPSR/SPSd @15CD 0.0660 m m m ¢ w w ULU ZD 0.094 U¢ U¢¢ 0.158 16 PPR/SR SW 110CD 0.202 w¢ U z p UJ H 1' H Q ip a- - w w cn �- < O Z Z a 1- : � Y w a - 1 Fw- ¢ ¢ ¢ ¢ ¢ ¢ ¢ z ¢ > } - N - U O Y < ¢ w o Y PER CIRCUIT DRAW F= H F¢= p w U U U U U U U P-- x a �. U a z z z J cn r -O � it = z O z AMPS ¢ ¢ ¢ ¢ ¢ ¢ ¢ U O U O ¢ w o r- 1- i- U <n z = INPUTS CIR 1 CIR 8 AMP LOAD 1 MANUAL PULL STATION - FIRST LEVEL 0 0 DISTANCE FROM SOURCE TO EOL 2 AREA SMOKE DETECTOR - FIRST LEVEL 0 0 0 WIRE GUAGE 3 IN -DUCT SMOKE DETECTOR - FIRST LEVEL 1.929 14 0.000 CIRCULAR MIL 4110 0 0 VOLTAGE DROP PERCENTAGE 4 WATERFLOW-FIRST LEVEL 0 0 5 SPRINKLER CONTROL VALVE - FIRST LEVEL 0 AMP LOAD 6 FIRE PUMP RUNNING DISTANCE 7 FIRE PUMP POWER FAILURE/PHASE REVERSAL VDROP 650 VIJRO W IRE GUAGE 8 FIRE PUMP AC POWER FAILURE 1.538 14 0.000 _.............. CIRCULAR MIL 9 FIRE PUMP SYSTEM LOW BATTERY USABLE 4110 USABLE VOLTAGE DROP PERCENTAGE 10 OPEN CIRCUIT 18.362 0.00%0 20.400 11 GROUND FAULT 12 NOTIFICATION APPLIANCE CIRCUIT SHORT 13 ON/OFF OVERRIDE FOR SMOKE EXHAUST IN FIRE COMMAND I A �A CONDUIT FIRESTOPPING DETAIL System No. W -L-1148 F Ratings -1 and 2 Hr T Rating - 0 Hr SECTION A -A 1. Wall Assembly - The fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual 0300 or U400 Series Wall and Partition Designs in the Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing shall consist of either wood studs or channel shaped steel studs. Wood studs to consist of 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in. wide, fabricated from min 25 MSG galvanized steel, spaced max 24 in. OC. B. Wallboard, Gypsum* - 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, number of layers and sheet orientation shall be as specified in the individual U300 or U400 Series Designs in the UL Fre Resistance Directory. Max diam of opening is 13 in. (BRGU) category in the The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrants - One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within L+ et flhgst,%eMbtift, rfte5/8 in. >-,c- to be n 2ly supported on both sides of the assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe - Nom 8 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 8 in. diam (or smaller) cast or ductile iron pipe. C. Conduit - Nom 4 in. diam (or smaller) steel electrical metallic tubing or steel conduit. 3. Pipe Covering - Nom 2 in. thick hollow cylindrical heavy density (min 3.5 pcf) fiberglass pipe covering with an all -service jacket. Pipe covering material to be min 9 in. long and installed on penetrant to extend 2 in. beyond bath sides of wall surface. Longitudinal joints sealed with metal fasteners or factory -applied self-sealing lap (SSL) tape; The annular space between the pipe covering and periphery of opening shall be min 0 in. (point contact) to max 3/8 in. See Pipe and Equipment Covering -Materials Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. 4. Fill, Void or Cavity Material* - Sealant thickness of fill material applied within annulus flush with both surfaces of wall. In 2 hr assemblies, min 1-1/4 in. thickness of fill material applied within annulus flush with both surfaces of wall. For both 1 and 2 hr assemblies, of point contact location between insulation and gypsum, a min 1/2 in. bead of fill material shall be applied on both sides of wall. FREEWIRE FIRESTOPPING DETAIL System No. W -L-3065 F Ratings --1 and 2 Hr (See Item 1) T Rating -- 0 Hr SECTION A -A 1. Wall Assembly -- The 1 or 2 fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400 or V600 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in . vide and spaced max 24 in. OC. B. Gypsum Board* -- Nom 5/8 in. thick gypsum board, with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300, U400 or V600 Series Design in the UL Fire Resistance Directory. Max diam of opening is 5-1/2 in. when sleeve (item 2) is employed. Max diam of opening is 4 in. when sleeve (item 2) is not employed. The F Rating of the firestop system is equal to the fire rating of the wall assembly. 2. Metallic Sleeve -- (Optional) - Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT) or Schedule 5 (or heavier) steel pipe or min 0.016 in. thick (28 ga) galy steel sleeve installed flush with wall surfaces. The annular space between steel sleeve and periphery of opening shall be min 0 in. (point contact) to max 1 in. When Schedule 5 steel pipe or EMT is used, sleeve may extend up to 18 in. beyond the wall surfaces. 3. Cables -- Aggregate cross-sectional area of cable in opening to be max 45 percent of the cross-sectional area of the opening. The annular space between the cable bundle and the periphery of the opening to be min 0 in. to max 1 in. Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types and sizes of copper conductor cables may be used: A. Max 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket. B. Max 25 pair No. 24 AWG telephone cable with PVC insulation and jacket. C. Type RG/U coaxial cable with polyethylene (PE) insulation and PVC jacket having a max outside diameter of Y in. D. Multiple fiber optical communication cable jacketed with PVC and having a max OD of 5/8 in. E. Through Penetrating Products*-- Max three copper conductor No. 8 AWG . Metal -Clad Cable+. AFC CABLE SYSTEMS INC F. Max 3/C (with ground)(or smaller) No. 8 AWG copper conductor cable with PVC insulation and jacketing. 4. Fill, Void or Cavity Material*-- Sealant-- Fill material applied within the annulus, flush with each end of the steel sleeve or wall surface. Fill material installed symmetrically on both sides of the wall. A min 5/8 in. thickness of sealant is required for the 1 or 2 hr F Rating. An additional 1/2 in. diam bead of fill material shall be applied around the perimeter of sleeve on both sides of the wall when sleeve extends beyond surface of wall. HILTI CONSTRUCTION CHEMCIALS, DIV OF HILTI INC -- CP601S, CP606 or FS -One Sealant *Bearing the UL Classification Mark FIRE PANEL AES RADIO R R R 7.7 m0 -xi 10000 0000 0000 0000 oeoe �' +� � I & I � �ml �m � o I o 0 o I o ii � I H ❑ JO iRCU&E Rfl%Y x� x� J10 CUSS -A CDNYflilp2 MODUIF PRIMER i10 F� Ut_ J2 ❑ ACPOWERPOWER TROUBLE ❑ ALM SUPERVISORY >= RESET SILENCE MODE ego w ❑❑❑❑❑ PH1 o000o FO o J3 01 ❑❑❑❑E PH2 ® = = 0 16v MPUT asTTERY r I N I H ��J9 00 0000 0000 E:IEIEIEIHI CB1 H N G BAiIERY TEsr conREcroR O 0 0 0 mil �.O J11 0 LRL (-) (+)F1 El(-) (+)El El(-) (+) BATTERY BATTERY BATTERY AFI4ECDTRANSF-ER PN %r1w 165VAC iM SMOKE DETECTOR INSTALLATION DETAIL DEVICE INSTALLATION DETAIL 44-2-1/8 BOX \ CEILI 44-2-1/8 & PER DRAWINGS BOX CEILING NAG DEVICE FIRE ALARM HORN/STROBE FIRE ALARM ANNUNCIATOR PANEL FIRE ALARM 44-2-1/8MANUAL BOX /`/ PULL STATION 48" TO CENTER FINISHES - FLOOR 80" TO BOTTOM OF LENS TERNALIY WUWED N W&E WRS Stanby current for the PS -8 is .1 0.129 Enter number €zf nxsteunitsonsyncbus..Etter0ifunitisstandalone i Multiply by -006 for each route Sync Bus Total' ?.0065 Enter current di-aw on aux Ifset to MP oxide enter 0 03.000 Aux oversee note 11 0.008 Total 0.1 Multiply by standby hours required 24,60 1 24 Total Standby Amp Flour 3.24 Notification Annlianrpg CEILING 1 3.76 4111;-=-=-=•�i Multiply by 1.2 for saftey margin Total Ahr Deeded NEVER IN THIS AREACEILING i � I MOUNTED SMOKE ST STROBE The maximum current available for aux cp and mastermode sync bus is DETECTOR MUST BEAT For 24 hour standby time, up to .24 amps max using 12 Ahr W�i LEAST / FROM WALL, AT For 60 hour standby time , up to .02 amps maximum using 12 1 LEAST 36" FROM ANY AIRDUCT For 72 hour standby time; up to .02 amps maximum using 33 Ahr batteries WALL MOUNTED SMOKE L DETECTOR MUST BEAT The PS -8 will fit 2 12112 Ahr batteries 811 ALEAST 4" BELOWL i' 1t9 BOYNTON COMMERCE CENTER BUT TO TOP OF DETECTOR DEVICE INSTALLATION DETAIL 44-2-1/8 BOX \ CEILI 44-2-1/8 & PER DRAWINGS BOX CEILING NAG DEVICE FIRE ALARM HORN/STROBE FIRE ALARM ANNUNCIATOR PANEL FIRE ALARM 44-2-1/8MANUAL BOX /`/ PULL STATION 48" TO CENTER FINISHES - FLOOR 80" TO BOTTOM OF LENS TERNALIY WUWED N W&E WRS Stanby current for the PS -8 is .1 0.129 Enter number €zf nxsteunitsonsyncbus..Etter0ifunitisstandalone i Multiply by -006 for each route Sync Bus Total' ?.0065 Enter current di-aw on aux Ifset to MP oxide enter 0 03.000 Aux oversee note 11 0.008 Total 0.1 Multiply by standby hours required 24,60 1 24 Total Standby Amp Flour 3.24 Notification Annlianrpg Enter Alann Time 5 minutes =.083 15 mimutes =. 25 0.25 Total 0.52 Add standby and Alarm Together �! -. 1 3.76 Multiply by 1.2 for saftey margin Total Ahr Deeded FISR !` RO - i E ST STROBE The maximum current available for aux cp and mastermode sync bus is For 24 hour standby time, up to .24 amps max using 12 Ahr batteries For 60 hour standby time , up to .02 amps maximum using 12 Ahr batteries For 72 hour standby time; up to .02 amps maximum using 33 Ahr batteries Note 2 91119 The PS -8 will fit 2 12112 Ahr batteries i' 1t9 BOYNTON COMMERCE CENTER WHEEL CK ISS -8 - P'CLIV ROP 91199 Amp 9 t9 Device type draw CIR 1 CIR 2 9 199 STROBE ONLY -WALL 1 SR/SW of 15CD 0.068 9 999 2 SR/SW @ 30CD _ 0.094 Enter Alann Time 5 minutes =.083 15 mimutes =. 25 0.25 Total 0.52 Add standby and Alarm Together 1 3.76 Multiply by 1.2 for saftey margin Total Ahr Deeded 4.81 Note 1 The maximum current available for aux cp and mastermode sync bus is For 24 hour standby time, up to .24 amps max using 12 Ahr batteries For 60 hour standby time , up to .02 amps maximum using 12 Ahr batteries For 72 hour standby time; up to .02 amps maximum using 33 Ahr batteries Note 2 The PS -8 will fit 2 12112 Ahr batteries BOYNTON COMMERCE CENTER WHEEL CK ISS -8 - P'CLIV ROP Amp Device type draw CIR 1 CIR 2 CIR 3 CIR 4 STROBE ONLY -WALL 1 SR/SW of 15CD 0.068 2 SR/SW @ 30CD _ 0.094 3 SRISW @ 75CD 01.135 5 4 4 SR/SW a 110CD 0.2012 STkbB - CEILING 5 SRISW @ 15CD 0.0660..__ 6 'SRISW @ 30CD 0.094 7 SR/SW a 75CD 6.158 8 SR/SW @ 110CD - 0.202 HORNISTROBE ....., _. 9 SPSR/SPSW @15CD 0.079 _ - 10 SPSRISPS I @3ObD 0.107 . 11 SPSR/SPSW 675CD 0.148 3 2 12 SPSR/SPSV (6110CD 0.212 SPEAKERISTROBE 13 SPSR/SPSd @15CD 0.0660 14 PSR/ PSV/ a@30CD 0.094 15 PSRICPSW @75CD 0.158 16 PPR/SR SW 110CD 0.202 17 SPSRKISPSWK @ 75CD 0.158 - 18 SPSRKISPSWK @ 110CD 0.202 PER CIRCUIT DRAW 1.119 01.836 0 0 TOTAL AMPS ON POKIER SUPPLY 1,955 AMPS VOLTAGE DROP CALCULATIONS CIR 1 CIR 8 AMP LOAD 1.119 0 DISTANCE FROM SOURCE TO EOL 328 VDROP 600 ,DROP_. WIRE GUAGE 14 1.929 14 0.000 CIRCULAR MIL 4110 USABLE 41100 USABLE VOLTAGE DROP PERCENTAGE 146% J 18.471 0.00% 20.400 CIR 2 CIR 4 AMP LOAD 00.8360 DISTANCE 350 VDROP 650 VIJRO W IRE GUAGE 14 1.538 14 0.000 _.............. CIRCULAR MIL 4110 USABLE 4110 USABLE VOLTAGE DROP PERCENTAGE 7.54°la 18.362 0.00%0 20.400 DynaFire DYNAFIRE INC. PHONE (407) 830-6500 - FAX (407) 831-1 47 1098 Concord Drive CASSELBERRY, FLORIDA 32707 E-MAIL: - dyn afireOdyn afire. us Qualifier: STEVEN HATCH STATE LICENCE # EF20000528 Z O I- n U U) LLJ C� LLJ Q LJ Z _O I- U e' F- Z O U 0' OLL_ F - _J � m ::D I C C/) Q Ln O 0 \ N \ N N \ JOB NUMBER: 3352SVC04 ISSUE DATE: 12/11/2014 DRAWN BY: Joseph Levenson CHECKED BY: Cory Abbott SHOP DRAWING U FA - 1 0 SCOPEO �NSTALL I NEW STROBE AND I NEW HORN/STROBE FOR A TENANT i i -r =icAori. BOYNTON TOWN CENTER GENERAL PROJECT NOTES 1) PROVIDE 120 VOLT DEDICATED CIRCUIT FOR FIRE ALARM SYSTEM, BREAKER TO BE MARKED "FIREALARM CIRCUIT". BREAKER SHALL BE MARKED IN RED AND MUST HAVE A BREAKER LOCK INSTALLED ON IT. 2) CONDUIT AND BOXES INSTALLED BY ELECTRICAL CONTRACTOR UNDER SEPERATE CONTRACT AND ELECTRICAL PERMIT. 3) FIRE ALARM SYSTEM INSTALLATION IN ACCORDANCE WITH NFPA 72 2007 EDITION, 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN, AND WIRING UNDER NFPA 70. 4) ALL CONDUIT SHALL BE 3/4" UNLESS OTHERWISE NOTED. 5) THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT. 6) THE LIGHT OUTPUT SHALL COMPLY WITH THE POLAR DISPERSION REQUIREMENTS OF ANSI/UL 1971, STANDARD FOR SAFETY SIGNALING DEVICES FOR HEARING IMPAIRED, OR EQUIVALENT. 7) ALL VISUAL NOTIFICATION APPLIANCES MUST BE SYNCHRONIZED IN ACCORDANCE WITH NFPA 72:15 8) FIRE ALARM SHOP DRAWINGS ARE BASED ON CONTRACT DRAWINGS DATED 10/14/14. 9) SHADED (GREY) DEVICES 'ARE EXISTING TO REMAIN. 10) CLASS AND STYLE FOR ALL CIRCUITS ARE AS FOLLOWS: (1) INITIATING DEVICE CIRCUITS - CLASS B, STYLE A (2) SIGNALING LINE CIRCUITS - CLASS B, STYLE 4 (3) NOTIFICATION CIRCUITS - CLASS B, STYLE Y 11) THE CURRENT SYSTEM IS AN EXISTING CENTERAL STATION SERVICE SYSTEM AND DYINIAFIRE INC. S THE CURRENT CERTIFICATE HOLDER. BOYNTON BEACH FL. SYM DESCRIPTION EQUIPMENT LEGEND MOUNTING P/N B.B. SUPP FACP FIRE ALARM CONTROL PANEL ETR 72" AFF NFS2-3030 NOTIFIER PROVIDED MANUFACTURER NAC NAC POWER SUPPLY ETR 60" AFF FACPS-2458 NOTIFIER PROVIDED MANUFACTURER HORN STROBE WALL MOUNT 80" - 96" TO BOTTOM OF LENS AFF P2R SYSTEM SENSOR 4" SQUARE BOX (2-1/8" DEEP) ELECTRICAL STROBE ONLY WALL MOUNT 80" - 96" TO BOTTOM OF LENS AFF SR SYSTEM SENSOR 4" SQUARE BOX (2-1/8" DEEP) ELECTRICAL >I o o w 0 `r' pq m �0 F- 0 0 C) Z 0 � 0 p:: L- n � � Li ABLE DESCRIPTION CABLE LEGEND MAN WIRE TYPE B NOTIFICATION CIRCUIT WINDY CITY WIRE 14/2 THHN rp, C F!E.S 0 W91 ESE D DEC` 16 2014. DRAW NC INDEXO-FILE COPY<-' BUILDING DIVISION5, FA -1 Dy np Fi re• COVER PAGE & LEGEND FA -2 109B Concord Drive TENANT IMPROVEMENT AREA FA -3 Qualifier: STEVEN HATCH DETAILS, BATTERY CALCS. ct C: o � -0 o C: >I o o w 0 `r' pq m �0 47 LL- Dy np Fi re• DYNAFIRE INC. PHONE (407) 830-6500 — FAX (407) 831-11- 109B Concord Drive CASSELBERRY, FLORIDA 32707 E—MAIL: dynofire@dynafire.us Qualifier: STEVEN HATCH STATE LICENCE # EF20000528 ct C: o � -0 o C: >I o o w 0 `r' pq m �0 F- 0 0 C) Z 0 � 0 p:: L- n � � Li C) U) Lij U) LL -j 0 < 0 C\A LLJ 11,011 Mw JOB NUMBER: 3352SVC04 ISSUE DATE: 12/11/2014 DRAWN BY: Joseph Levenson CHECKED BY: Cory Abbott SHOP DRAWING FA -1 47 LL- m 0 w"bl 75cd 75cd 75cd 75cd 75cd 75cd PHONE (407) 830-6500 — FAX (407) 831-11- 109B Concord Drive ......... .... ............... ........ .... . .................... EOL 1.2 1.2.1 1.2.2 1.2.3 1.2.4 1.2.5 1.2.6 ETR ETR ETR ETR ETR ETR 75cd 75cd 75cd 75cd 750 75cd 75cd 75cd - 0 -----EOL 1.1 1.1.1 1.1.2 1.1.3 1.1.4 1.1.5 1.1.6 1.1.7 1.1.8 ETR ETR ETR ETR ETR N ETR N ETR NAC SCALE: 1/8" = 1' 09, 2-52 60 Ek 0V [R 0 DEC 16 20114 >FIL E COPY --A ISUILMING 0MVISION 47 3 Dy na Fi re• DYNAFIRE INC. PHONE (407) 830-6500 — FAX (407) 831-11- 109B Concord Drive CASSELBERRY, FLORIDA 32707 E—MAIL: dynafireOdynafire.us Qualifier: STEVEN HATCH STATE LICENCE # EF20000528 14 WIN - O ct 4-a C: con 0O � �i �� C: 0 C) C: >1 0 `� pq 0 - C)F- D LL 0 z 0 0 LL - a_ C) Ld W D LLJ 0 LSI KNI''i 21 JOB NUMBER: 3352SVC04 ISSUE DATE: 12/11/2014 DRAWN BY: Joseph Levenson CHECKED BY: Cory Abbott ry SHOP DRAWING FA -1 L 47 3 TYPICAL SEQUENCE OF OPERATION CONDUIT FIRESTOPPING DETAIL System No. W -L-1148 F Ratings -1 and 2 Hr T Rating - 0 Hr F_A 1A 1,6 4 I A SECTION A -A 1. Wall Assembly - The fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual 0300 or U400 Series Wall and Partition Designs in the Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing shall consist of either wood studs or channel shaped steel studs. Wood studs to consist of 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in. wide, fabricated from min 25 MSG galvanized steel, spaced max 24 in. OC. B. Wallboard, Gypsum* - 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, number of layers and sheet orientation shall be as specified in the individual -U300 or U400 Series Designs in the UL Fire Resistance Directory. Max diam of opening is 13 in. (BRGU) category in the The hourly F Rating of the firestop system is equal to the hourly fire rotinQ of the wall assembly in which.4 is installed. 2 1nro;gh Penetrants - One metallic pipe, conduit or tubing to be installed either concentrically; or eccentrically within tiliet fiygstAte3p®*. rliifle5/8 in. conduit or tubing to be rigidly 'supported on both sides of the assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe - Nom 8 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 8 in. diam (or smaller) cast or ductile iron pipe. C. Conduit - Nom 4 in. diom (or smaller) steel electrical metallic tubing or steel conduit. 3. Pipe Covering - Nom 2 in. thick hollow cylindrical heavy density (min 3.5 pcf) fiberglass pipe covering with an all -service jacket. Pipe covering material to be min 9 in. long and installed on penetrant to extend 2 in. beyond both sides of wall surface. Longitudinal joints sealed with metal fasteners or factory -applied self-sealing lop (SSL) tape. The annular space between the pipe covering and periphery of opening shall be min 0 in. (point contact) to max 3/8 in. See Pipe and Equipment Covering-Moterials Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. 4. fill, Void or Cavity Material* - Sealant thickness of fill material applied within annulus flush with both surfaces of wall. In 2 hr assemblies, min 1-1/4 in. thickness of fill material applied within annulus flush with both surfaces of wall. For both 1 and 2 hr assemblies, at point contact location between insulation and gypsum, a min 1/2 in. bead of fill material shall be applied on both sides of wall. FREEWIRE FIRESTOPPING DETAIL System No. W -L-3065 M F Ratings --1 and 2 Hr (See Item 1) 3 T Rating -- 0 Hr F -A 2 1A 2 4 3 ILA 1B SECTION A -A 1. Wall Assembly - The 1 or 2 fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in i the individual U300, U400 or V600 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in . wide and spaced max 24 in. OC. B. Gypsum Board* - Nom 5/8 in. thick gypsum board, with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300, U400 or V600 Series Design in the UL Fire Resistance Directory. Max diam of opening is 5-1/2 in. when sleeve (item 2) is employed. Max diam of opening is 4 in. when sleeve (item 2) is not employed. ' The F Rating of the firestop system is equal to the fire rating of the wall assembly. 2. Metallic Sleeve - (Optional) - Nom 4 in, diam (or smaller) steel electrical metallic tubing (EMT) or Schedule 5 (or heavier) steel pipe or min 0.016 in. thick (28 ga) galy steel sleeve installed flush with wall surfaces. The annular space between steel sleeve and periphery of opening shall be min 0 in. (point contact) to max 1 in. When Schedule 5 steel pipe or EMT is used, sleeve may extend up to 18 in. beyond the wall surfaces. 3. Cables - Aggregate cross-sectional area of cable in opening to be max 45 percent of the cross-sectional area of the opening. The annular space between the cable bundle and the periphery of the opening to be min 0 in, to max 1 in. Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types and sizes of copper conductor cables may be used: A. Max 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket. B. Max 25 pair Nd. 24 AWG telephone cable with PVC insulation and jacket. C. Type RG/U coaxial cable with polyethylene (PE) insulation and PVC jacket having a max outside diameter of % in. D. Multiple fiber optical communication cable jacketed with PVC and having a max OD of 5/8 in. E. Through Penetrating Products*- Max three copper conductor No. 8 AWG . Metal -Clad Cable+. AFC CABLE SYSTEMS INC' F. Max 3/C (with ground)(or smaller) No. 8 AWG copper conductor cable with PVC insulation and jacketing. 4. Fill, Void or Cavity Material*- Sealant - Fill material applied within the annulus, flush with each end of the steel sleeve or wap surface. Fill material installed symmetrically ori both sides of the wall. A min 5/8 in. thickness of sealant is required for the 1 or 2 hr F Rating. An additional 1/2 in. diam bead of fill material shall be applied around the perimeter of sleeve on both sides of the wall when sleeve extends beyond surface of wall HILT[ CONSTRUCTION CHEMCIALS, DIV OF HILTI INC - CP601S, CP606 or FS -One Sealant *Bearing the UL Classification Mark; FIRE PANEL CONTROL UNIT �R = 000 � ANNUNCIATION NOTIFICATION REQUIRED FIRE SAFETY CONTROL SUPPLEMENTARY Power Supervision Relays W = 0 i'CEILING MOUNTED SMOKE DETECTOR t LEAST I• WALL ANDt Auxiliary Current Draw LEAST FROM ANY AIR D H auh WALL • r SMOKE C1A55-A CONVERTER MOOUI�.E DETECTOR MUST BEAT 811 C 1 BELOW CEILING BUT NO LOWER THAN w X 1.318 TO TOP OF DETECTOR 1.318 Z 0 NAC / Output ## 2 1 O ¢ Z . 0.984 O NAC / Output ## 3 ¢ 0 - 0 O 0 NAC / Output ## 4 X _ 0 �SQ ALARIVI LOAD' = 2a 7 J Battery Amp Hour Calculation O ¢ Z 6r EC > W � O of Current (Amps) (Typically 24 or 60 f-In>ats) 0.065 o Z z z J w rl UJ wa o 0 w0 Required Alarm Time Current (Amps) c~n z O o o j w O? g ¢ d Z ¢ o C7 0 c) O U O = CC O- X ¢¢ Z F- cn Z O ~ O Z of cn o cn t -- LTotal Ampm Hours w>> m z of LU= in u) Z CO o < w > w = w J w Amp a a O o w= z Ow o C0 2 w= a D w m 1 ;SRISW @ 15CD 0.066 ¢ w H x z 0 o p p CD a v wLU w 0.158 _ w 4 S R/S W @ 110CD 0.202 o Z J z J o o O¢ t= J LU mU 5 :SR/SW @ 15CD 0.066. 6 "'SR/SW @ 30CD 0.094 p r- V¢ _0.158 _ ww aOw LL LWi z W>go HORN/STROBE O J Q¢ 0.079 r (D OpQ0¢ 0.107_ 11 'SPSR/SPSW @75CD 0.176 LU LU ULI a LU 0.212 Y o Y 13 SPSRISPSW 15CD0.066 F>>>>>> of 0.094 cncn o Y 16 SPSR/SPSW @110CD 0.202 ¢¢ ¢ ¢ FZ Ou)w ¢ ¢ ¢ fQ- Z aTz¢Fn- LU UP 4.202 0 PER CIRCUIT DRAM 1.318 0.984 0 0 u) U O AMPS VOLTAGE DROP CALCULATIONS INPUTS CIR 1 CIR 3 AMP LOAD 1,318 0 DISTANCE FROM SOURCE TO EOL 328 VDROP 600 VDROP 1 MANUAL PULL STATION -FIRST LEVEL 2.272 14 0.000 14 CIRCULAR MIL 10 01 10 • VOLTAGE DROP PERCENTAGE • 2 AREA SMOKE DETECTOR - FIRST LEVEL • • 1 10 • • • • • • 01 10 • 0 • 3 IN -DUCT SMOKE DETECTOR- FIRST LEVEL • • 10 • • • 1 • 01 10 • 4110 • 4 WATERFLOW-FIRST LEVEL • • 10 • • • • 1 • 01 1 10 • • 5 SPRINKLER CONTROL VALVE - FIRST LEVEL • • 1 1 • 6 FIRE PUMP RUNNING • 10 7 FIRE PUMP POWER FAILURE/PHASE REVERSAL • • • • 8 FIRE PUMP AC POWER FAILURE • • • 9 FIRE PUMP SYSTEM LOW BATTERY - • • • 10 OPEN CIRCUIT • • • 11 GROUND FAULT • • • 12 NOTIFICATION APPLIANCE CIRCUIT SHORT • • • 13 ON/OFF OVERRIDE FOR SMOKE EXHAUST IN FIRE COMMAND • CONDUIT FIRESTOPPING DETAIL System No. W -L-1148 F Ratings -1 and 2 Hr T Rating - 0 Hr F_A 1A 1,6 4 I A SECTION A -A 1. Wall Assembly - The fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual 0300 or U400 Series Wall and Partition Designs in the Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing shall consist of either wood studs or channel shaped steel studs. Wood studs to consist of 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in. wide, fabricated from min 25 MSG galvanized steel, spaced max 24 in. OC. B. Wallboard, Gypsum* - 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, number of layers and sheet orientation shall be as specified in the individual -U300 or U400 Series Designs in the UL Fire Resistance Directory. Max diam of opening is 13 in. (BRGU) category in the The hourly F Rating of the firestop system is equal to the hourly fire rotinQ of the wall assembly in which.4 is installed. 2 1nro;gh Penetrants - One metallic pipe, conduit or tubing to be installed either concentrically; or eccentrically within tiliet fiygstAte3p®*. rliifle5/8 in. conduit or tubing to be rigidly 'supported on both sides of the assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe - Nom 8 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 8 in. diam (or smaller) cast or ductile iron pipe. C. Conduit - Nom 4 in. diom (or smaller) steel electrical metallic tubing or steel conduit. 3. Pipe Covering - Nom 2 in. thick hollow cylindrical heavy density (min 3.5 pcf) fiberglass pipe covering with an all -service jacket. Pipe covering material to be min 9 in. long and installed on penetrant to extend 2 in. beyond both sides of wall surface. Longitudinal joints sealed with metal fasteners or factory -applied self-sealing lop (SSL) tape. The annular space between the pipe covering and periphery of opening shall be min 0 in. (point contact) to max 3/8 in. See Pipe and Equipment Covering-Moterials Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used. 4. fill, Void or Cavity Material* - Sealant thickness of fill material applied within annulus flush with both surfaces of wall. In 2 hr assemblies, min 1-1/4 in. thickness of fill material applied within annulus flush with both surfaces of wall. For both 1 and 2 hr assemblies, at point contact location between insulation and gypsum, a min 1/2 in. bead of fill material shall be applied on both sides of wall. FREEWIRE FIRESTOPPING DETAIL System No. W -L-3065 M F Ratings --1 and 2 Hr (See Item 1) 3 T Rating -- 0 Hr F -A 2 1A 2 4 3 ILA 1B SECTION A -A 1. Wall Assembly - The 1 or 2 fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in i the individual U300, U400 or V600 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in . wide and spaced max 24 in. OC. B. Gypsum Board* - Nom 5/8 in. thick gypsum board, with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300, U400 or V600 Series Design in the UL Fire Resistance Directory. Max diam of opening is 5-1/2 in. when sleeve (item 2) is employed. Max diam of opening is 4 in. when sleeve (item 2) is not employed. ' The F Rating of the firestop system is equal to the fire rating of the wall assembly. 2. Metallic Sleeve - (Optional) - Nom 4 in, diam (or smaller) steel electrical metallic tubing (EMT) or Schedule 5 (or heavier) steel pipe or min 0.016 in. thick (28 ga) galy steel sleeve installed flush with wall surfaces. The annular space between steel sleeve and periphery of opening shall be min 0 in. (point contact) to max 1 in. When Schedule 5 steel pipe or EMT is used, sleeve may extend up to 18 in. beyond the wall surfaces. 3. Cables - Aggregate cross-sectional area of cable in opening to be max 45 percent of the cross-sectional area of the opening. The annular space between the cable bundle and the periphery of the opening to be min 0 in, to max 1 in. Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types and sizes of copper conductor cables may be used: A. Max 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket. B. Max 25 pair Nd. 24 AWG telephone cable with PVC insulation and jacket. C. Type RG/U coaxial cable with polyethylene (PE) insulation and PVC jacket having a max outside diameter of % in. D. Multiple fiber optical communication cable jacketed with PVC and having a max OD of 5/8 in. E. Through Penetrating Products*- Max three copper conductor No. 8 AWG . Metal -Clad Cable+. AFC CABLE SYSTEMS INC' F. Max 3/C (with ground)(or smaller) No. 8 AWG copper conductor cable with PVC insulation and jacketing. 4. Fill, Void or Cavity Material*- Sealant - Fill material applied within the annulus, flush with each end of the steel sleeve or wap surface. Fill material installed symmetrically ori both sides of the wall. A min 5/8 in. thickness of sealant is required for the 1 or 2 hr F Rating. An additional 1/2 in. diam bead of fill material shall be applied around the perimeter of sleeve on both sides of the wall when sleeve extends beyond surface of wall HILT[ CONSTRUCTION CHEMCIALS, DIV OF HILTI INC - CP601S, CP606 or FS -One Sealant *Bearing the UL Classification Mark; FIRE PANEL 11 AC POWER ❑ TROUBLE ❑ ALARM ❑ SUPERVISORY RESET SILENCE MODE ❑❑❑❑❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑❑❑❑❑ J4 PRIMER ❑ MODULE F-1 ❑ PHI PH2 OJ9 Cal H N G MM, TETT OONNECTOR 0 0 0 �J7 J11 C....... BATTERY SMOKE DETECTOR INSTALLATION DETAIL �R �R �R = 000 � � 000 0000 0000 0000 0000 0000 1 ••moiNEVER IN THIS AREA Power Supervision Relays X 0.025 = 0 i'CEILING MOUNTED SMOKE DETECTOR t LEAST I• WALL ANDt Auxiliary Current Draw LEAST FROM ANY AIR D H auh WALL • r SMOKE C1A55-A CONVERTER MOOUI�.E 11 AC POWER ❑ TROUBLE ❑ ALARM ❑ SUPERVISORY RESET SILENCE MODE ❑❑❑❑❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑❑❑❑❑ J4 PRIMER ❑ MODULE F-1 ❑ PHI PH2 OJ9 Cal H N G MM, TETT OONNECTOR 0 0 0 �J7 J11 C....... BATTERY SMOKE DETECTOR INSTALLATION DETAIL DEVICE INSTALLATION DETAIL 4x4-2-1/8 BOX 44-2-1/8 BOX 4x4-2-1/8' BOX \\ - PER DRAWINGS CEILING NAG DEVICE FIRE ALARM HORN/STROBE FIRE ALARM ANNUNCIATOR PANEL FIRE ALARM MANUAL PULL STATION 48" TO CENTER FINISHES - FLOOR 80" TO BOTTOM OF LENS 0 A%ECOTIL1NSi0RIAER PM %F16d0 f6.5 VAC dWA ETM- MquNrED iNTROU&EEURER LOAD- = Regulated Load in ALARM Number of Current Total Current, Device Type Devices (Amps) (Amps) Main PC Board without AC 1 411 CEILING = 411 1 ••moiNEVER IN THIS AREA Power Supervision Relays X 0.025 = 0 i'CEILING MOUNTED SMOKE DETECTOR t LEAST I• WALL ANDt Auxiliary Current Draw LEAST FROM ANY AIR D g WALL • r SMOKE from TB4 Terminals 9 & 10 DETECTOR MUST BEAT 811 C 1 BELOW CEILING BUT NO LOWER THAN NAC / Output ##' 1 1 X 1.318 TO TOP OF DETECTOR 1.318 DEVICE INSTALLATION DETAIL 4x4-2-1/8 BOX 44-2-1/8 BOX 4x4-2-1/8' BOX \\ - PER DRAWINGS CEILING NAG DEVICE FIRE ALARM HORN/STROBE FIRE ALARM ANNUNCIATOR PANEL FIRE ALARM MANUAL PULL STATION 48" TO CENTER FINISHES - FLOOR 80" TO BOTTOM OF LENS 0 A%ECOTIL1NSi0RIAER PM %F16d0 f6.5 VAC dWA ETM- MquNrED iNTROU&EEURER LOAD- = Regulated Load in ALARM Number of Current Total Current, Device Type Devices (Amps) (Amps) �(gr . z >11UILE CC)py< UNLDIMG IM90 DynaFire DYNAFIRE INC. PHONE (407) 830-6500 - FAX (407) 831-1 1098 Concord Drive CASSELBERRY, FLORIDA 32707 E-MAIL: dynafire@dynafire.us Qualifier: STEVEN HATCH STATE LICENCE # EF20000528 Z _O I- O D F-- 1110 Z O U IY O 11 C) W D V) O N N JOB NUMBER: 3352SVC04 ISSUE DATE: 12/11/2014 DRAWN BY: Joseph Levenson CHECKED BY: Cory Abbott SHOP DRAWING U C: FA - Main PC Board without AC 1 X 0.145 = 0.145 Power Supervision Relays X 0.025 = 0 Auxiliary Current Draw X g from TB4 Terminals 9 & 10 NAC / Output ##' 1 1 X 1.318 = 1.318 NAC / Output ## 2 1 X 0.984 0.984 NAC / Output ## 3 X - 0 NAC / Output ## 4 X _ 0 ALARIVI LOAD' = 2a 7 Battery Amp Hour Calculation Standby Load Required Standby Time Current (Amps) (Typically 24 or 60 f-In>ats) 0.065 X 24 = 1.56 `AH Alarm Lead Required Alarm Time Current (Amps) (Typically 5 or 10 Minutes) 2.447 X 10 = 0.41 AH Sub Total Standby I Alarm Amp Hours 1.97 AH Multiply by the Derating Factor X LTotal Ampm Hours Requir"e""d3. BO TON COMMERCE CENTER FOPS -24F8 - PCL/VDROP Amp I Device type draw CIR 1 CIR 2 CIR 3 CIR 4 STROBE ONLY -WALL 1 ;SRISW @ 15CD 0.066 2 'SR/SW @ 30CD 0.094 3 SR/SW @ 75CD 0.158 _ 5 4 4 S R/S W @ 110CD 0.202 STROBE -CEILING 5 :SR/SW @ 15CD 0.066. 6 "'SR/SW @ 30CD 0.094 7 SRISW @ 75CD _0.158 _ 8 SRISW @ 11OCD 4.202 HORN/STROBE 9 'SPSR/SPSW @15CD 0.079 10 SPSR/SPSW t@r 30CD 0.107_ 11 'SPSR/SPSW @75CD 0.176 3 2 12 'SPSR/SPSW @110CD 0.212 SPEAKERISTROBE 13 SPSRISPSW 15CD0.066 14 SPSR/SPSW @30CD 0.094 15 SPSR/SPSW @75CD 0.158 16 SPSR/SPSW @110CD 0.202 17 `SPSRKISPSWK @ 75CD 0.158 18 "SPSRKISF'SWK @ 110CD 4.202 PER CIRCUIT DRAM 1.318 0.984 0 0 TOTAL AMPS ON POWER SUPPLY 2,302 AMPS VOLTAGE DROP CALCULATIONS CIR 1 CIR 3 AMP LOAD 1,318 0 DISTANCE FROM SOURCE TO EOL 328 VDROP 600 VDROP WIRE GUAGE 2.272 14 0.000 14 CIRCULAR MIL 4110 USABLE 4110 USABLE VOLTAGE DROP PERCENTAGE 18.128 0.00% 1 20.400 11.14% CIR 2 CIR 4 AMP LOAD 0.984 0 DISTANCE 350 VDROP __. 650 VDROP WIRE GUAGE 14 1.810 14 0.000 CIRCULAR MIL 4110 USABLE 4110 USABLE VOLTAGE DROP PERCENTAGE 8.87a/o 18.590 0.00% 20.400 �(gr . z >11UILE CC)py< UNLDIMG IM90 DynaFire DYNAFIRE INC. PHONE (407) 830-6500 - FAX (407) 831-1 1098 Concord Drive CASSELBERRY, FLORIDA 32707 E-MAIL: dynafire@dynafire.us Qualifier: STEVEN HATCH STATE LICENCE # EF20000528 Z _O I- O D F-- 1110 Z O U IY O 11 C) W D V) O N N JOB NUMBER: 3352SVC04 ISSUE DATE: 12/11/2014 DRAWN BY: Joseph Levenson CHECKED BY: Cory Abbott SHOP DRAWING U C: FA -