DRAWINGSALL MATERIAL APPLICABLE TO THIS PROJECT WILL
BE INDICATED WITH A (Q� )
❑ ALL PLASTIC PIPE 3/4" THROUGH 2YE" SHALL BE UL LISTED OR FM APPROVED CPVC MANUFACTURED IN
ACCORDANCE WITH ASTM F-442.
❑ ALL PLASTIC FITTINGS SHALL BE UL LISTED OR FM APPROVED CPVC MANUFACTURED IN ACCORDANCE
WITH ASTM F438, ASTM F439 OR ASTM F1970.
ALL CPVC PIPE AND FITTINGS SHALL BE ASSEMBLED USING 'ONE STEP' 500 CEMENT.
❑ CPVC PIPE SHALL BE ALLOWED TO BE USED IN ORDINARY HAZARD ROOMS OF 400 SQUARE FEET OR
LESS OF OTHERWISE LIGHT HAZARD OCCUPANCIES (NFPA 13 SECTION 6.3.6.2 OR NFPA 13R SECTION
5.2.2.3).
F-� ALL 1" TO 2" THREADED BLACK STEEL PIPE SHALL BE UL LISTED/FM APPROVED AND MANUFACTURED
IN ACCORDANCE WITH ASTM A-135 OR A-795. ACCEPTABLE PIPE BRANDS ARE WHEATLAND
'MEGATHREAD', ALLIED 'DYNATHREAD', BULL MOOSE TUBE 'EDDYTHREAD' AND WELDED TUBE -BERKELEY
'STEADY -THREAD'. ALL PIPE SHALL BE CPVC COMPATIBLE.
ALL 1' TO 2" THREADED GALVANIZED PIPE WILL BE SCHEDULE 40 HOT DIPPED GALVANIZED
MANUFACTURED IN ACCORDANCE WITH ASTM A-795 OR ASTM A-53.
ALL 1' TO 2" THREADED BLACK STEEL PIPE SHALL BE SCHEDULE 40 UL LISTED/FM APPROVED AND
MANUFACTURED IN ACCORDANCE WITH ASTM A-795. ACCEPTABLE PIPE MANUFACTURERS ARE
WHEATLAND, ALLIED, BULL MOOSE TUBE AND WELDED TUBE -BERKELEY. ALL PIPE SHALL BE CPVC
COMPATIBLE.
❑ ALL 11'4" TO 4" GROOVED BLACK STEEL PIPE SHALL BE UL LISTED/FM APPROVED AND MANUFACTURED
IN ACCORDANCE WITH ASTM A795. ACCEPTABLE BRANDS ARE BULL MOOSE 'EDDYFLOW', WHEATLAND
'MEGA -FLOW', ALLIED 'DYNA-FLOW' AND WELDED TUBE -BERKELEY 'STEADY -FLOW'. ALL PIPE SHALL BE
CPVC COMPATIBLE.
ALL IY4" TO 4" GROOVED BLACK STEEL PIPE SHALL BE SCHEDULE 10, UL LISTED/FM APPROVED AND
MANUFACTURED IN ACCORDANCE WITH ASTM A-795. ACCEPTABLE MANUFACTURERS ARE BULL
MOOSE, WHEATLAND, ALLIED AND WELDED TUBE -BERKELEY. ALL PIPE SHALL BE CPVC COMPATIBLE.
ALL GROOVED STEEL PIPE 6" AND LARGER SHALL BE UL LISTED/FM APPROVED SCHEDULE 10 AND
MANUFACTURED IN ACCORDANCE WITH ASTM A-135.
❑ ALL GROOVED STEEL PIPE IY4" AND LARGER SHALL BE SCHEDULE 10 HOT DIPPED GALVANIZED AND
MANUFACTURED IN ACCORDANCE WITH ASTM A-795.
ALL STEEL PIPE SHALL HAVE A CORROSION RESISTANCE RATIO (CRR) OF NOT LESS THAN 1.0 PER
WAFS STANDARDS.
ALL BLACK THREADED FITTINGS SHALL BE DUCTILE IRON CLASS 150 OR CLASS 300 ANSI B15.3, CAST
IRON CLASS 125 OR CLASS 250 ANSI BIBA OR MALLEABLE IRON CLASS 150 OR CLASS 300 ANSI
616.3.
F-] ALL GALVANIZED THREADED FITTINGS SHALL BE MALLEABLE IRON CLASS 150 OR CLASS 300 ANSI
816.3 WITH GALVANIZED COATING IN ACCORDANCE WITH ASTM A-153.
F-1 ALL WELDED OUTLETS SHALL BE UL LISTED OR FM APPROVED AND MANUFACTURED IN ACCORDANCE
WITH ANSI B16.11.
F-] GROOVED FITTINGS SHALL BE UL LISTED OR FM APPROVED AND MANUFACTURED IN ACCORDANCE WITH
ASTM A-536 FOR DUCTILE IRON OR ASTM A-47 FOR MALLEABLE IRON.
❑ ALL GALVANIZED GROOVED FITTINGS SHALL BE UL LISTED OR FM APPROVED AND MANUFACTURED IN
ACCORDANCE WITH ASTM A-536 FOR DUCTILE IRON OR ASTM A-47 FOR MALLEABLE IRON.
GALVANIZED COATING SHALL BE IN ACCORDANCE WITH ASTM A-153.
ALL GROOVED STEEL PIPE SHALL BE ROLL GROOVED PER PIPE MANUFACTURER REQUIREMENTS.
PIPE AND FMI46.S SAL RTES
SCALE, NONE
Rr. Bpr0 No Ino,
WAFS POLICY ON REUSING SPRINKLERS
NFPA 13 STATES THAT ONLY NEW SPRINKLERS SHALL BE INSTALLED,
WAFS POLICY IS TO REPLACE ANY SPRINKLER THAT HAS BEEN REMOVED
FROM THE FITTING TO WHICH IT WAS ATTACHED, IF DURING THE COURSE
OF SERVICE OR REPAIR TO THE FIRE SPRINKLER SYSTEM THE SPRINKLER
REMAINS IN THE FITTING TO WHICH IT WAS INSTALLED AND THE
SPRINKLER IS PROTECTED FROM DAMAGE THROUGHOUT THE ADJUSTMENT
PROCESS, THAT SPRINKLER MAY REMAIN,
HANGER INSTALLATION NOTES
1. ONE HANGER FOR EACH SECTION OF PIPE.
1.1. WHERE SPRINKLERS ARE SPACED LESS THAN 6'
APART, HANGERS SPACED UP TO A MAXIMUM OF
12' SHALL BE PERMITTED.
1.2. STARTER LENGTHS LESS THAN 6' SHALL NOT
REQUIRE A HANGER, UNLESS ON THE END LINES
OF A SIDEFEED SYSTEM OR WHERE AN
INTERMEDIATE CROSS MAIN HANGER HAS BEEN
OMITTED.
2. CLEARANCE BETWEEN A HANGER AND THE
CENTERLINE OF AN UPRIGHT SPRINKLER SHALL NOT .BE
LESS THAN 3".
3. THE UNSUPPORTED LENGTH BETWEEN THE END
SPRINKLER AND THE LAST HANGER ON THE LINE
SHALL NOT BE GREATER THAN 35" FOR 1 -IN. PIPE, 48"
FOR 1 -IN. PIPE, AND 60" FOR 1 -IN. OR LARGER PIPE.
WHERE THESE LIMITS ARE EXCEEDED, THE PIPE SHALL
BE EXTENDED BEYOND THE END SPRINKLER AND
SHALL BE SUPPORTED BY AN ADDITIONAL HANGER.
4. ARM -OVERS SHALL HAVE A HANGER WHEN THE
CUMULATIVE HORIZONTAL PIPE IS MORE THAN 24".
USE A TRAPEZE HANGER WHEN NECESSARY.
S. MAX HANGER SPACING:
5.1. STEEL PIPE: 1" - 1-1/4" (121, 1-1/2" - 4" (16)
5.2. THREADED LIGHTWALL: 1" - 3" (121
SEE NOTE 1.2
SEE NOTE 3 70TE 4 v -� v
SEE NOTE 5
SEE NOTE 1.1
STEEL PIPE HANGER SPACING
PRESSURE UNDER 1OOPS1
SCALD NONE
Automtic Fire SprWere, km
Il..:l:
• DESIGN AND INSTALLATION TO BE IN ACCORDANCE WITH 2010 EDITION OF NFPA 13.
1r DESIGN AND INSTALLATION TO BE IN ACCORDANCE WITH ALL APPLICABLE LOCAL AND
STATE CODES.
• ALL PIPE AND FITTINGS USED ON THIS PROJECT TO BE IN ACCORDANCE WITH APPLICABLE
CODES AND WAFS STANDARDS. SEE PIPE AND FITTINGS GENERAL NOTES (WAFS DETAIL
#00593N).
• ALL HANGERS AND ANY REQUIRED BRACING SHALL BE DESIGNED AND INSTALLED IN
ACCORDANCE WITH NFPA 13, MANUFACTURER'S INSTRUCTIONS AND THEIR LISTING.
• ALL PENETRATIONS THROUGH RATED BUILDING ASSEMBLIES SHALL BE SEALED WITH FIRE
CAULK IN ACCORDANCE WITH DETAILS PROVIDED. WAFS POLICY IS TO USE HILTI FS ONE OR
STI LCL
• UNDERGROUND MAINS AND LEAD-INS SHALL BE FLUSHED AND SIGNED TEST CERTIFICATES
PROVIDED BEFORE A CONNECTION IS MADE TO THE SYSTEM.
r ALL PIPING SHALL BE INSPECTED AND APPROVED BY PROPER AUTHORITIES PRIOR TO
COVERING WITH DRYWALL. COPIES OF SIGNED TEST CERTIFICATES ARE TO BE FORWARDED
TO THE PROPER RECIPIENTS.
• ALL SYSTEMS SHALL BE TESTED FOR 2 HOURS AT 200 PSI OR 50 PSI GREATER THAN
MAXIMUM SYSTEM WORKING PRESSURE, WHICHEVER IS GREATER.
• ALL SOFFITS REQUIRED TO CONCEAL SPRINKLER PIPING ARE BY OTHERS.
• ALL WIRING OF DEVICES (FLOW SWITCHES, TAMPER SWITCHES, COMPRESSORS, ETC) IS BY
OTHERS.
• CONNECTION OF SPRINKLER DEVICES TO THE BUILDING ALARM OR MONITORING SYSTEM IS BY
OTHERS.
• ALL PAINTING OF PIPE AS REQUIRED IS BY OTHERS.
(r ALL INSULATION REQUIRED FOR FREEZE PROTECTION OF SPRINKLER SYSTEM IS BY OTHERS.
• HEATING OF ROOMS TO MAINTAIN TEMPERATURES OF 40 DEGREES OR GREATER IS BY
OTHERS.
8 FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED NOT LESS THAN IB" AND NOT MORE
THAN 46" ABOVE THE LEVEL OF THE ADJACENT GRADE.
• QUICK RESPONSE SPRINKLERS SHALL BE USED IN ALL LIGHT HAZARD AREAS.
• SPARE SPRINKLERS OF EACH TYPE (EXCLUDING DRY) SHALL BE PROVIDED ON THE PREMISES
AS FOLLOWS:
o LESS THAN 300 - 6 SPRINKLERS
0 300 TO 1000 - 12 SPRINKLERS
o OVER 1000 - 24 SPRINKLERS
• REFER TO SPACING NOTES ON PLANS FOR MAXIMUM CALCULATED SPACING ALLOWANCES.
4, SPRINKLERS SHALL BE INSTALLED IN ALL AREAS EXCEPT AS FOLLOWS:
o ANY PORCHES, BALCONIES OR OVERHANGS THAT ARE NON-COMBUSTIBLE AND ARE NOT
USED FOR STORAGE.
o CORRIDORS THAT ARE NON-COMBUSTIBLE IN CONSTRUCTION AND AT LEAST 509 OPEN.
o AT THE TOP OF ALL ELEVATOR SHAFTS WHERE THE CAR ENCLOSURE MEETS THE
REQUIREMENTS OF ASME A17.1.
o AT THE BOTTOM OF ENCLOSED NON COMBUSTIBLE ELEVATOR SHAFTS THAT DO NOT
CONTAIN COMBUSTIBLE HYDRAULIC FLUID.
• WAFS TO PROVIDE ALL REQUIRED SIGNAGE PER NFPA 13 INCLUDING BUT NOT LIMITED TO
VALVES, HYDRAULIC PLACARDS, AND INSPECTION TAGS AS REQUIRED BY FS 633.
NFPA 13 20110 SAL NOTES
SCALE, NONE
P" sp rlkl.r., km
00859N 00686N
CEILING
TYPICAL STANDARD
SPRAY PENDENT
SPRINKLER
TYPICAL STANDARD
SPRAY UPRIGHT
SPRINKLER
B�-
- A -----
TYPICAL
OBSTRUCTION
CEILING
TYPICAL
OBSTRUCTION
DISTANCE FROM
SPRINKLER TO SIDE
OF OBSTRUCTION (A)
MAXIMUM ALLOWABLE DISTANCE
OF DEFLECTOR ABOVE BOTTOM
OF OBSTRUCTION (IN.) (B)
LESS THAN 1 FT.
0
1 FT, TO LESS THAN 1 FT, 6 IN,
Mercantile
1 FT, 6 IN, TO LESS THAN 2 FT,
3
2 FT, TO LESS THAN 2 FT. 6 IN,
5
2 FT, 6 IN, TO LESS THAN 3 FT,
7
3 FT, TO LESS THAN 3 FT, 6 IN,
9
3 FT, 6 IN, TO LESS THAN 4 FT,
12
4 FT, TO LESS THAN 4 FT, 6 IN,
14
4 FT, 6 IN, TO LESS THAN 5 FT,
16h
5 FT, AND GREATER
18
NFPA 13 TABLE 8,6,512
NFPA 13 SPRINKLER CLEARANCE W/ OBSTRUCTION
(STANDARD SPRAY LIPRWT / STANDARD SPRAY PENDENT)
SCALED NONE
FMe Sprinkbre, hm.
00610N
SPRINKLER HEAD
FIRE SPRINKLER DETAILS
DESIGN CRITERIA
ALL PIPE TO BES
❑ SCH. 7 ❑ SCH, 30 ❑ GALV,
❑ SCH. 10 dSCH, 40 ❑ CPVC
CLASSIFICATION;
Mercantile
HAZARD;
Ordinary Hazard Group II
MAX, HEAD COVERAGE:
130 SQ,FT,
SCOPE OF WORK
NUMBER OF RELOCATED SPRINKLER HEADS;
13
NUMBER OF ADDED SPRINKLER HEADSi
5
NUMBER OF PLUGGED SPRINKLER HEADS
N
ALL FIRE SPRINKLER SYSTEM
MATERIALS (HEADS, PIPES AND
HANGERS) ARE PERI
❑ NFPA 13 2002 EDITION
❑ NFPA 13 2007 EDITION
If NFPA 13 2010 EDITION
SCOPE OF WORK DETAILS/NOTES:
Relocate (13), add (5) & plug (lU) fire sprinkler heads to accommodate
tenant remodel shown per plan,, Owner will be removing all coolers and
freezers. W,A,F,S, to remove dry pendents and replace w/ new uprights
at deck level to assure proper sprinkler coverage, Only areas
indicating fire sprinkler work will be in W,A,F,S scope of work,
LEGEND
EXISTING PIPE
— — — — —
NEW PIPE
DOMESTIC DEMAND I -
NEW HANGER
Z
MECHANICAL, TEE
MT
NEW SPRINKLER HEAD
A*
RELOCATED SPRINKLER HEAD
R*
PLUGGED EXISTING SPRINKLER HEAD
-E
NOT IN�SCOPE OF CONTRACT
T— QUANTITY SPRINKLERS
BW
SPRINKLER HEAD C
STEEL PIPE
HANGER RING
TABLE 3 - MAXIMUM SUPPORT SPACING
NOM. PIPE
SIZE
A
BA
C
1'
3'-0' MAX.
12'-0' MAX,
3' MIN,
lye
4'-0' MAX,
12'-0' MAX.
3' MIN,
1W TO 8'
5'-0' MAX.
15'-0' MAX,
3' MIN,
WMAXIMUM SUPPORT SPACING FOR STEEL PIPE
STEEL PIPE HALER SPACE
7WWARMW SCALE, NONE
Firs Spr4ddere, Inc.
C
DESIGNER
REFERENCE
DETAIL VIEW -
ALL THREAD ROD
' FOR -'TO4'
WFOR 5'TO8'
TOP BEAM CLAMP
` FOR 9/4' TO 4' PIPE
' FOR 5' TO 8' PIPE
� mn�u, luny
(SIZED TO PIPE)
LOCKNUT (INCLUDED
W/ CLAMP) HAND #01
RING HANGER FOR 3/47 TO B" PIPE (BAR .DIST)
SCALE, NONE
Fin Sp 0 dit bw 00198N
NOTES=
1. ALL AREAS OUTSIDE OF SCOPE OF WORK IS NOT IN CONTRACT
WITH WAYNE AUTOMATIC FIRE SPRINKLERS.
2. ENTIRE EXISTING BUILDING IS A FULLY SPRINKLER BUILDING.
3. HYDRAULIC CALCULATION IS NOT REQUIRED AS NEW DESIGN
LAYOUT MATCHES EXISTING ORDINARY HAZARD II LAYOUT,
CLASSIFICATION DOES NOT CHANGE.
i
0
IMP4119
ORTANT OWNER INFORMATION
THIS DRAWING IS BASED ON THE DWNER'S ACCEPTANCE OF THE CURRENTLY ADOPTED EDITION (EITHER STATE OR LOCAL) OF NFPA 25 AS
THE APPLICABLE STANDARD FOR THE INSPECTION, TESTING AND MAINTENANCE OF WATER BASED FIRE PROTECTION SYSTEMS, PER SECTION 4,L
THE RESPONSIBILITY FOR PROPERLY MAINTAINING A WATER BASED FIRE PROTECTION SYSTEM SHALL BE THAT OF THE OWNER. IF THE
BUILDING OWNER HAS NOT RECEIVED A COPY OF THIS PAMPHLET AND/OR IS NOT FAMILIAR WITH THE OPERATION AND MAINTENANCE OF THIS
SYSTEM, PLEASE CONTACT THE NEAREST OFFICE OF WAYNE AUTOMATIC FIRE SPRINKLERS, INC.
TOTAL A/SI
CPVC COMPATIBILITY NOTICE
CPVC FIRE SPRINKLER PIPING SYSTEMS HAVE BEEN USED SUCCESSFULLY FOR MORE THAN 20 YEARS IN NEW CONSTRUCTION, RE -PIPE AND
REPAIR. CPVC PRODUCTS ARE IDEALLY SUITED FOR THESE APPLICATIONS DUE TO THEIR OUTSTANDING CORROSION RESISTANCE.
OCCASIONALLY, HOWEVER CPVC CAN BE DAMAGED BY CONTACT WITH CHEMICALS FOUND IN SOME CONSTRUCTION MATERIALS QED SOME WIRES,
FLUX, PETROLEUM BASED PRODUCTS, ETC.) AND ANCILLARY PRODUCTS SUCH AS THREAD SEALANTS, LEAK DETECTORS, FIRESTOPS, ETC. ANY
PRODUCT THAT COMES IN CONTACT WITH CPVC SPRINKLER PIPE MUST BE EVALUATED IN ACCORDANCE WITH THE SYSTEM COMPATIBILITY
PROGRAM AS FOUND AT WWW.SYSTEMCOMPATIBLE.COM
COPYRIGHT
ALL DOCUMENTS, INCLUDING ORIGINAL DRAWINGS, SPECIFICATIONS, FIELD NOTES, ESTIMATES AND DATA, INCLUDING COMPUTER
PROGRAMS PURSUANT TO THIS PROJECT ARE AND WILL REMAIN THE PROPERTY OF WAYNE AUTOMATIC FIRE SPRINKLERS, INC.
(WAFS) AS INSTRUMENTS OF SERVICE. THEY ARE NOT INTENDED NOR REPRESENTED TO BE SUITABLE FOR RE -USE BY THE CLIENT,
OR OTHERS, ON EXTENSION OF THIS PROJECT, OR FOR ANY OTHER PROJECT. ANY REUSE, OR ADAPTATION OF THE INFORMATION
CONTAINED HEREIN, WITHOUT SPECIFIC WRITTEN PERMISSION FROM WAFS WILL BE AT THE CLIENTS SOLE RISK, WITHOUT
LIABILITY, OR LEGAL EXPOSURE TO WAFS, AND WILL ENTITLE WAFS TO FURTHER COMPENSATION AT RATES TO BE AGREED ON
BETWEEN WAFS AND THE CLIENT. THE CLIENT SHALL ALSO INDEMNIFY AND HOLD WAFS HARMLESS FROM ANY AND ALL CLAIMS,
DAMAGES, LOSSES AND EXPENSES, INCLUDING ATTORNEYS FEES RESULTING FROM ANY SUCH PERMISSIONS.
DATE,
GRAPHICS ELEMENTS NOTE
FIRE SPRINKLER CONSTRUCTION DRAWINGS AND SHOP DRAWINGS MAY INCLUDE BACKGROUND DRAWINGS OR GRAPHICS BORROWED
FROM THE ARCHITECTURAL, CIVIL, STRUCTURAL. OR MEP DRAWINGS. THESE REFERENCE BACKGROUND ELEMENTS ARE FOR
GENERAL INFORMATION OR CONTEXT ONLY AND THE FIRE SPRINKLER ENGINEER DOES NOT ACCEPT ANY RESPONSIBILITY FOR
THESE ELEMENTS. THE FIRE SPRINKLER ENGINEER IS ONLY RESPONSIBLE FOR THOSE PORTIONS OF THE FIRE SPRINKLER
DRAWINGS DEPICTING FIRE SPRINKLER SCOPES OF WORK. REFER TO APPROVED ARCHITECTURAL, STRUCTURAL. MEP OR CIVIL
DRAWINGS FOR AUTHORITATIVE EXPRESSIONS OF BACKGROUND INFORMATION THAT MAY BE UTILIZED IN FIRE SPRINKLER
\ DRAWINGS OR DETAILS
WATER SUPPLY INFORMATION
MUL9UH1 UR
ACTUAL EXTRAPOLATED FIRE PUMP -
STATIC PRESSURE SIZE, GPM E PSI -
HYDRANT ELEV. -
RESIDUAL PRESSURE DATE OF TEST-
FLOV IN GPM - - TIME OF TEST -
PITOT READING - MAW OF PORTS FLOWED -
TEST PROVIDED BY --
OLE N
it CONTRACT #
DESIGN CRITERIA
SYSTEM / DESIGN AREA # -
HAZARD CLASS -
# IF SPRINO.ERS IN DEM AREA -
MINIMUM DENSITY -
DESIGN AREA S.F. -
PSI REQ'D 2 BR -
GPM REQ'D 2 BR -
PSI REQ'D @ TEST -
GPM REQ'D 2 TEST -
OIVATHN ! HDIEST SPRINKLER -
HOSE INSIDE/OUTSIDE I -
DOMESTIC DEMAND I -
SPRINKLERS SPACING
SYMBOL MAXIMUM MINIMUM COMMENTS
I
i
T— QUANTITY SPRINKLERS
SYMB. IST 2ND 3RD 4TH SIN SIZE K TEMP MODEL
l
ii
i'.
i
i
i
�I
i
j - - - - TOTAL PER FLOOR
- TOTAL THIS SHEET
DATE SUBMITTALS By
P
I
NO. DATE REVISIONS BY
l XX/XX/XX -- -
I�
i
WWAYNE-
i!
i! Automatic Fire Sprinklers, Inc.
MAIN OFFICE — ORLANDO, FLORIDA
EM CAPITOL COURT OCOM FLOMA 34761
PHONE (40" 866-3030 FAX:
JACK80N4L= FL
MES DISTRB)TION AVE WEST
JACKSONVLFL WES8-2745
LE
PHONE (804) 288-3030
FAX ()04) 288-0724
TAMPA, FL
3228 CHERRY PALM ORME
TAMPA. FL 33816.9337
PHONE (82) 830 -OM3
FAX (90 63D-0312
POI, AM BEAAX PL
30 NW )S})( TERRACE
POWAND BEACK FL 33084-,408
PHONE MA) W-3030
FAX (854) W-8424
FT MYEW FL
4883 LAHEDO AVE
Fr. MYEM FL 33806-4924
PHONE (239) 433-3090
CONCOFD NC
4370 LMTDRSPORT DRVE
CONCORD, NC 28027-8977
PHONE (704) 782-3032
STATE LICB�
NC SPF&*aJR 28748
NC ALARM ROM SP LV
ED SPFRAaR mg
FAX (M) 433-328:1 FAX VO4) 796-8838 SC ALARM 3385
IhIED BY . ---
Winn Dixie #259
620 S. Federal Hwy
Boynton yon Beach, Florida 33435
Winn Dixie Maintenance
1141 SW 12th Ave
- Pompano Beach, FL 33069 FEB 0'
SHEET TITLE, I Notes & Details
DRAWN BYI
Michael Crawford
TOTAL A/SI
18
DATE,
1/29/2015
AHJI
City of Boynton Beach
it CONTRACT #
#9595
CENTER OF TILE
JOB? [:] YES gffNO
CENTER
ON FIXTURES JOB? F_j YES aND
j SHEET #
FP1
CONSTRUCTION TYPE,
IIB
OCCUPANCY,
M
N
c. �'•1•'G'• . AREA 01
SCALE: 1/8" 1 = -0
4' 2' 1' 0 8' 16'
III
SCALE 1/8' = 1'
AREA 02
V-0))
SCALE: 1/8
VV
• AL •
1*4ifil,
AREA #3 /
SCALE: 1/8" = 1'-0"
4' 2' 1' 0 8' 16'
III
i
SCALE 1/8' = 1'
Mal AND DRW
TD PROVIDE PROPER
R
JL .I
X
mou
co
I�
c
BY
S. FEDERAL HWY
SITE PLAN
V_V
IMPORTANT OWNER INFORMATION
THIS DRAWING IS BASED ON THE OWNER'S ACCEPTANCE OF THE CURRENTLY ADOPTED EDITION (EITHER STATE OR LOCAL) OF NFPA 25 AS
THE APPLICABLE STANDARD FOR THE INSPECTION, TESTING AND MAINTENANCE OF WATER BASED FIRE PROTECTION SYSTEMS. PER SECTION 41
THE RESPONSIBILITY FOR PROPERLY MAINTAINING A WATER BASED FIRE PROTECTION SYSTEM SHALL BE THAT OF THE OWNER. IF THE
BUILDING OWNER HAS NOT RECEIVED A COPY OF THIS PAMPHLET AND/OR IS NOT FAMILIAR WITH THE OPERATION AND MAINTENANCE OF THIS
SYSTEM, PLEASE CONTACT THE NEAREST OFFICE OF WAYNE AUTOMATIC FIRE SPRINKLERS, INC.
CPVC COMPATIBILITY NOTICE
CPVC FIRE SPRINKLER PIPING SYSTEMS HAVE BEEN USED SUCCESSFULLY FOR MORE THAN 20 YEARS IN NEW CONSTRUCTION, RE -PIPE AND
REPAIR. CPVC PRODUCTS ARE IDEALLY SUITED FOR THESE APPLICATIONS DUE TO THEIR OUTSTANDING CORROSION RESISTANCE.
OCCASIONALLY, HOWEVER, CPVC CAN BE DAMAGED BY CONTACT WITH CHEMICALS FOUND IN SOME CONSTRUCTION MATERIALS 00 SOME WIRES,
FLUX, PETROLEUM BASED PRODUCTS, ETC.) AND ANCILLARY PRODUCTS SUCH AS THREAD SEALANTS, LEAK DETECTORS, FIRESTOPS, ETC, ANY
PRODUCT THAT COMES IN CONTACT WITH CPVC SPRINKLER PIPE MUST BE EVALUATED IN ACCORDANCE WITH THE SYSTEM COMPATIBILITY
PROGRAM AS FOUND AT WWW.SYSTEMCGMPATIBLE.COM
COPYRIGHT
ALL DOCUMENTS, INCLUDING ORIGINAL DRAWINGS, SPECIFICATIONS, FIELD NOTES, ESTIMATES AND DATA, INCLUDING COMPUTER
PROGRAMS PURSUANT TO THIS PROJECT ARE AND WILL REMAIN THE PROPERTY OF WAYNE AUTOMATIC FIRE SPRINKLERS, INC.
(WAFS) AS INSTRUMENTS OF SERVICE. THEY ARE NOT INTENDED, NOR REPRESENTED TO BE SUITABLE FOR RE -USE BY THE CLIENT,
OR OTHERS, ON EXTENSION OF THIS PROJECT, OR FOR ANY OTHER PROJECT. ANY REUSF, OR ADAPTATION OF THE INFORMATION
CONTAINED HEREIN, WITHOUT SPECIFIC WRITTEN PERMISSION FROM WAFS WILL BE AT THE CLIENTS SOLE RISK, WITHOUT
LIABILITY, OR LEGAL EXPOSURE TO WAFS, AND VILL ENTITLE WAFS TO FURTHER COMPENSATION AT RATES TO BE AGREED ON
BETWEEN WAFS AND THE CLIENT. THE CLIENT SHALL ALSO INDEMNIFY AND HOLD WAFS HARMLESS FROM ANY AND ALL CLAIMS,
DAMAGES, LOSSES AND EXPENSES, INCLUDING ATTORNEYS FEES RESULTING FROM ANY SUCH PERMISSIONS.
GRAPHICS ELEMENTS NOTE
FIRE SPRINKLER CONSTRUCTION DRAWINGS AND SHOP DRAWINGS MAY INCLUDE BACKGROUND DRAWINGS OR GRAPHICS BORROWED
FROM THE ARCHITECTURAL CIVIL, STRUCTURAL OR MEP DRAWINGS. THESE REFERENCE BACKGROUND ELEMENTS ARE FOR
GENERAL INFORMATION OR CONTEXT ONLY AND THE FIRE SPRINKLER ENGINEER DOES NOT ACCEPT ANY RESPONSIBILITY FOR
THESE ELEMENTS. THE FIRE SPRINKLER ENGINEER IS ONLY RESPONSIBLE FOR THOSE PORTIONS OF THE FIRE SPRINKLER
DRAWINGS DEPICTING FIRE SPRINKLER SCOPES OF WORK, REFER TO APPROVED ARCHITECTURAL, STRUCTURAL, MEP OR CIVIL
DRAWINGS FOR AUTHORITATIVE EXPRESSIONS OF BACKGROUND INFORMATION THAT MAY BE UTILIZED IN FIRE SPRINKLER
DRAWINGS OR DETAILS
WATER SUPPLY
INFORMATION
•
REQ!
SIZEi GPM a PSI -
/0'
`
HYDRANT ELEV. -
. Ia-
99.1-M.im .971F13 -11M,
OF TEST_
IN GPM - -
TIME OF TEST -
�FLOW
I PITOT READING -
KMBOt OF PORTS FLOM -
TEST PROVIDED BY --
PjEkOCATIUN
ID
• �.
•
SYSTEM / DESIGN AREA # -
- - -
HAZARD CLASS -
# IF SPRINID.ERS IN DESIGNI AREA -
MINIMUM DENSITY -
10
- -31
10
PSI REQ'D @ BR -
GPM REQ'D E BR -
PSI REQ'D 2 TEST -
GPM REQ'D 2 TEST -
SHATDN a HOEST SPRDJW -
HOSE INSIDE/OUTSIDE -
DOMESTIC DEMAND -
alw ICOI TO K MOM it ]'
PRE—FAB MEAT
-
p
MEAT COOLER
N
c. �'•1•'G'• . AREA 01
SCALE: 1/8" 1 = -0
4' 2' 1' 0 8' 16'
III
SCALE 1/8' = 1'
AREA 02
V-0))
SCALE: 1/8
VV
• AL •
1*4ifil,
AREA #3 /
SCALE: 1/8" = 1'-0"
4' 2' 1' 0 8' 16'
III
i
SCALE 1/8' = 1'
Mal AND DRW
TD PROVIDE PROPER
R
JL .I
X
mou
co
I�
c
BY
S. FEDERAL HWY
SITE PLAN
V_V
IMPORTANT OWNER INFORMATION
THIS DRAWING IS BASED ON THE OWNER'S ACCEPTANCE OF THE CURRENTLY ADOPTED EDITION (EITHER STATE OR LOCAL) OF NFPA 25 AS
THE APPLICABLE STANDARD FOR THE INSPECTION, TESTING AND MAINTENANCE OF WATER BASED FIRE PROTECTION SYSTEMS. PER SECTION 41
THE RESPONSIBILITY FOR PROPERLY MAINTAINING A WATER BASED FIRE PROTECTION SYSTEM SHALL BE THAT OF THE OWNER. IF THE
BUILDING OWNER HAS NOT RECEIVED A COPY OF THIS PAMPHLET AND/OR IS NOT FAMILIAR WITH THE OPERATION AND MAINTENANCE OF THIS
SYSTEM, PLEASE CONTACT THE NEAREST OFFICE OF WAYNE AUTOMATIC FIRE SPRINKLERS, INC.
CPVC COMPATIBILITY NOTICE
CPVC FIRE SPRINKLER PIPING SYSTEMS HAVE BEEN USED SUCCESSFULLY FOR MORE THAN 20 YEARS IN NEW CONSTRUCTION, RE -PIPE AND
REPAIR. CPVC PRODUCTS ARE IDEALLY SUITED FOR THESE APPLICATIONS DUE TO THEIR OUTSTANDING CORROSION RESISTANCE.
OCCASIONALLY, HOWEVER, CPVC CAN BE DAMAGED BY CONTACT WITH CHEMICALS FOUND IN SOME CONSTRUCTION MATERIALS 00 SOME WIRES,
FLUX, PETROLEUM BASED PRODUCTS, ETC.) AND ANCILLARY PRODUCTS SUCH AS THREAD SEALANTS, LEAK DETECTORS, FIRESTOPS, ETC, ANY
PRODUCT THAT COMES IN CONTACT WITH CPVC SPRINKLER PIPE MUST BE EVALUATED IN ACCORDANCE WITH THE SYSTEM COMPATIBILITY
PROGRAM AS FOUND AT WWW.SYSTEMCGMPATIBLE.COM
COPYRIGHT
ALL DOCUMENTS, INCLUDING ORIGINAL DRAWINGS, SPECIFICATIONS, FIELD NOTES, ESTIMATES AND DATA, INCLUDING COMPUTER
PROGRAMS PURSUANT TO THIS PROJECT ARE AND WILL REMAIN THE PROPERTY OF WAYNE AUTOMATIC FIRE SPRINKLERS, INC.
(WAFS) AS INSTRUMENTS OF SERVICE. THEY ARE NOT INTENDED, NOR REPRESENTED TO BE SUITABLE FOR RE -USE BY THE CLIENT,
OR OTHERS, ON EXTENSION OF THIS PROJECT, OR FOR ANY OTHER PROJECT. ANY REUSF, OR ADAPTATION OF THE INFORMATION
CONTAINED HEREIN, WITHOUT SPECIFIC WRITTEN PERMISSION FROM WAFS WILL BE AT THE CLIENTS SOLE RISK, WITHOUT
LIABILITY, OR LEGAL EXPOSURE TO WAFS, AND VILL ENTITLE WAFS TO FURTHER COMPENSATION AT RATES TO BE AGREED ON
BETWEEN WAFS AND THE CLIENT. THE CLIENT SHALL ALSO INDEMNIFY AND HOLD WAFS HARMLESS FROM ANY AND ALL CLAIMS,
DAMAGES, LOSSES AND EXPENSES, INCLUDING ATTORNEYS FEES RESULTING FROM ANY SUCH PERMISSIONS.
GRAPHICS ELEMENTS NOTE
FIRE SPRINKLER CONSTRUCTION DRAWINGS AND SHOP DRAWINGS MAY INCLUDE BACKGROUND DRAWINGS OR GRAPHICS BORROWED
FROM THE ARCHITECTURAL CIVIL, STRUCTURAL OR MEP DRAWINGS. THESE REFERENCE BACKGROUND ELEMENTS ARE FOR
GENERAL INFORMATION OR CONTEXT ONLY AND THE FIRE SPRINKLER ENGINEER DOES NOT ACCEPT ANY RESPONSIBILITY FOR
THESE ELEMENTS. THE FIRE SPRINKLER ENGINEER IS ONLY RESPONSIBLE FOR THOSE PORTIONS OF THE FIRE SPRINKLER
DRAWINGS DEPICTING FIRE SPRINKLER SCOPES OF WORK, REFER TO APPROVED ARCHITECTURAL, STRUCTURAL, MEP OR CIVIL
DRAWINGS FOR AUTHORITATIVE EXPRESSIONS OF BACKGROUND INFORMATION THAT MAY BE UTILIZED IN FIRE SPRINKLER
DRAWINGS OR DETAILS
WATER SUPPLY
INFORMATION
DR13"T UR -
ACTUAL EXTRAPOLATED FIRE PUMPca
REQ!
SIZEi GPM a PSI -
STATIC PRESSURE - _
HYDRANT ELEV. -
RESIDUAL PRESSURE - -DATE
OF TEST_
IN GPM - -
TIME OF TEST -
�FLOW
I PITOT READING -
KMBOt OF PORTS FLOM -
TEST PROVIDED BY --
PjEkOCATIUN
DESIGN
CRITERIA
SYSTEM / DESIGN AREA # -
HAZARD CLASS -
# IF SPRINID.ERS IN DESIGNI AREA -
MINIMUM DENSITY -
DESIGN AREA S,F. -
PSI REQ'D @ BR -
GPM REQ'D E BR -
PSI REQ'D 2 TEST -
GPM REQ'D 2 TEST -
SHATDN a HOEST SPRDJW -
HOSE INSIDE/OUTSIDE -
DOMESTIC DEMAND -
SPRINKLERS
SPACING
SYMBOL MAXIMUM MINIMUM
COMMENTS
Q 15'-0' 6'-0'
130 SQ.FT. MAX COVERAGE
�I
'l
0
r— QUANTITY SPRINKLERS
YMB. IST 2ND I 3RD 4TH SIN SIZE K TEMP MODEL
)R 13 TY3111 1/2' 5.6 155' RELocATEO TYCO TY -L A BRASS UPF
5—A 5 TY3111 1/2' 5.6 155' ADDED TYCO TY -L ,SR, BRASS UPRIGHT
WSTD(G UPRIGHT TO BE REMDIM
TOTAL PER FLOOR
18 TOTAL THIS SHEET
'E SUBMITTAIS
l• — I — I — I
III /1\ I XX/XX/XX I -- I - I
W WAYNE
Automatic Fire Sprinklers, Inc.
MAIN OFFICE — ORLANDO. FLORIDA
222 CAPITOL COURT OCOE -_ FLOWA 34761
PHONE (4077 666-3030 FAX: ( 866-8026
,u►CanWu a R. TAWA. R. R76F MM WAM R.
11326 011 AVE WEST 3226 amy PALM DIM 30 NW 16TH TINFACE
JAQXSONVLLE FL 32256-2746 TAMPA, FL 338 7 POWANO BEACH. FL 33084 -MOB
PHONE (804) 268-3030 PHONE (813) 830-0303 PHONE O)64) 99-3030
FAX: (904) 288-0724 FAX (818) 830 -OM FAX (864) BO' -8424
FT. mym R. COBS IAC STATE UC06M
4883 LQ:EDO AVE 4370 MOTORSPORT DAM NC SPRNO.m 28745
FT. MYM FL 33805-4824 CONCORD, NO 28027 77 NC ALARM 29M SP LV
PHONE MM) 433-303D PHONE (704) 782-3032 ec elm 116
FAX (238) 433-3283 FAX (704) 786-6839 SC ALARM 3386
Winn Dixie #259
1620 S. Federal Hwy
Boynton Beach, Florida 33435
Winn Dixie Maintenance
1141 SW 12th Ave
Pompano Beach, FL 33069
SHEET TITLE,
Notes &Details
DRAWN BY, Michael Crawford
TOTAL A/S, 18
DATE, 1/29/2015
AHJ, City of Boynton Beach
CONTRACT # #9595
CENTER OF TILE JOB? [-] YES NO CENTER ON FIXTURES JOB? ❑ YES QTNO
SHEET # CONSTRUCTION TYPD
IS
FP2 OCCUPANCYi
M r