DRAWINGSGENERAL NOTES:
1. ALL MECHANICAL SYSTEMS ARE TO BE INSTALLED IN ACCORDANCE WITH ALL
APPLICABLE SECTIONS OF THE NFPA STANDARDS, ANSI STANDARDS, THE LOCAL
BUILDING CODE, NOISE & HEIGHT ORDINANCES, PLANS AND SPECIFICATIONS.
2. ALL MATERIALS SHALL BE NEW AND ALL WORKMANSHIP AND MATERIALS SHALL BE
W STRICT ACCORDANCE WITH APPLICABLE LOCAL CODES, PRODUCT APPROVAL,
RULES AND ORDINANCES, ANY DAMAGED EQUIPMENT SHALL BE REPLACED OR
RESTORED TO ORIGINAL CONDITION.
3. THE CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, ACCESS
PANELS, CONTROL SYSTEMS, DEVICES, PERMITS AND SERVICES NECESSARY FOR
FURNISHING AND INSTALLING A COMPLETE OPERABLE MECHANICAL SYSTEM.
4. ALL LOUVERS, GRILLES, PIPING, ETC. SHALL BE PAINTED TO MATCH
SURROUNDING COLOR AND TEXTURES AS REQUIRED BY ARCHITECT. VERIFY COLOR
AND TEXTURE WITH ARCHITECT. PAINT ALL EXPOSED MECHANICAL EQUIPMENT
WITH BENJAMIN MOORE EPDXY ENAMEL 182.
5. ALL CUTTING, PATCHING, STRUCTURAL STEEL, WEATHER PROOFING, PAINTING,
AND WALL OPENINGS SHALL BE BY THE GENERAL CONTRACTOR.
6. ALL OPENINGS IN BUILDING STRUCTURE, FOR DUCTWORK, PIPING, ETC. TO BE
1/2" LARGER (ON ALL SIDES) THEN THE OUTSIDE DIMENSIONS. FILL VOIDS
WITH FIRE RETARDANT SILICONE FOAM (I.E. CHASE -FOAM CTC PR -855 BY CHASE
TECHNOLOGY CORP.).
7. SHOP DRAWINGS: CONTRACTORS SHALL SUBMIT FOR APPROVAL, WITHIN 30 DAYS
AFTER SIGNING CONTRACT, A MINIMUM OF FIVE COPIES OF FULLY DESCRIPTIVE
LITERATURE, INCLUDING BUT NOT LIMITED TO: AIR CONDITIONING UNITS, FANS AND
AIR OUTLETS. NO WORK SHALL PROCEED WITHOUT APPROVAL OF THESE SUBMITTALS.
8. PROVIDE FLEXIBLE DUCT CONNECTORS, RATED AS REQUIRED, TO ALL FANS, A/C
UNITS, OR MECHANICAL EQUIPMENT.
9. PROVIDE MAINTENANCE AND OPERATION MANUAL ON ALL MECHANICAL EQUIPMENT
OR SYSTEMS. PROVIDE 5 SETS OF SUBMITTALS ON ALL HVAC EQUIPMENT.
SUBMITTALS SHALL HAVE A SUMMARY SHEET SHOWING ALL SCHEDULED
INFORMATION.
10. HVAC CONTRACTOR WILL WARRANTY ALL MECHANICAL SYSTEMS, DUCTWORK,
THERMOSTATS, AND ALL OTHER EQUIPMENT,PARTS AND LABOR UNDER THESE
DRAWINGS AND SPECIFICATIONS FOR A PERIOD OF ONE (1) YEAR AFTER C.O. OF
BUILDING. ANY REPAIRS REQUIRING SYSTEM SHUT DOWN WELL BE DONE DURING
NON OPERATIONAL PERIODS. HVAC CONTRACTOR SHALL COORDINATE WITH ALL
OTHER TRADES PRIOR TO BIDDING AND PURCHASING ANY EQUIPMENT.
11. AIR QUALITY SHOULD BE TESTED BEFORE OCCUPANCY AND SHOULD BE INSTRUMENTED
AND MONITORED THEREAFTER, OR AT LEAST AT REGULAR INTERVALS
12. GENERAL CONTRACTOR TO PROVIDE FINAL TEST AND BALANCE PER NEW DESIGN LAYOUT.
MECHANICAL EQUIPMENT NOTES:
1. ALL MECHANICAL EQUIPMENT SHALL BE ARI & U.L. LISTED WHERE APPLICABLE
AND RATED FOR THE REQUIRED SERVICE, PRESSURES, TEMPERATURES, AND SHALL
BE PROVIDED WITH ALL NECESSARY TRANSFORMERS, SEALS, VALVES,
CONNECTIONS, ETC. TO FUNCTION PROPERLY.
2. PROVIDE VIBRATION ISOLATORS ON ALL MECHANICAL EQUIPMENT AS CALLED FOR
IN THE SPECIFICATIONS. IF NOT SPECIFIED, AS RECOMMENDED BY
MANUFACTURER FOR QUIET OPERATION (WITH 99% ISOLATION EFFICIENCY).
3. INDEPENDENT CONTRACTOR SHALL TEST AND BALANCE ALL MECHANICAL EQUIPMENT
AIR DEVICES, EXTRACTORS, DAMPERS, AHU'S & FAN RATES, ETC. TO PROVIDE
THE DESIGN QUANTITIES AS SHOWN ON THE PLANS OR SCHEDULES. PROVIDE T&B
REPORT IN ACCORDANCE WITH THE AIR BALANCE COUNCIL STANDARDS, SIGNED
AND SEALED BY A REGISTERED FLORIDA ENGINEER. PROVIDE FINAL BALANCING
FOR ALL SYSTEMS TO SATISFACTION OF OWNER AND ENGINEER. T&B CONTRACTOR
SHALL VISIT JOB SITE DURING CONSTRUCTION TO ENSURE THAT ALL DUCTS,
DAMPERS, ETC. ARE INSTALLED FOR PROPER AND QUIET'AIRDELIVERY.
4. THERMOSTAT LOCATION SHALL BE APPROVED BY OWNER AND ENGINEER BEFORE
INSTALLATION.
5. ALL INSULATION WILL HAVE FIRE/SMOKE RATING LESS THAN 25/50.
6. FILTERS SHALL BE IN PLACE DURING CONSTRUCTION. PROVIDE A NEW SET
PRIOR TO TEST AND BALANCE AND A FINAL SET AT THE END OF ONE YEAR
SERVICE PERIOD.
AIR DISTRIBUTION / DUCTWORK NOTES
1. REFER TO ARCHITECTURAL PLANS FOR CEILING TYPE.
2. PROVIDE OFF WHITE FINISH (SUBJECT TO ARCHITECT'S APPROVAL).
3. ALL DUCTWORK WHERE ALLOWED BY LOCAL CODES AND AND CEILING RATING SHALL
BE 1" LOW PRESSURE DUCT, SEAL CLASS "C" AND AS FOLLOWS:
A. S/A & R/A - 1-1/2" THICK FIBERGLASS DUCT BOARD WITH VAPOR BARRIER (R-6 MIN.)
B. EXHAUST AIR DUCTWORK - GALVANIZED SHEETMETAL
B. OUTSIDE AIR DUCTWORK - INSULATED GALVANIZED SHEETMETAL
4. ALL DUCTWORK AND DIFFUSERS SHALL BE RATED FOR THE USE, PRESSURE AND
TEMPERATURE SPECIFIED AND AS REQUIRED BY THE CEILING SYSTEM RATING.
5. ALL DUCTWORK SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH
"SMACNA" STANDARDS AND LOCAL BUILDING CODES.
6. ALL DUCT SIZES ARE CLEAR INSIDE DIMENSIONS.
7. SEAL ALL DUCTS, JOINTS AND SEAMS IN AN APPROVED MANNER AND INSURE
AGAINST LEAKAGE.
8. PROVIDE ACCESS DOORS AS REQUIRED FOR ALL MECHANICAL EQUIPMENT TO
SERVICE AND VISUALLY CHECK ROTATION OF FANS AND MOTORS, POSITION OF
DAMPERS, REPLACE FIRE DAMPER LINKS, ADJUST OR REPLACE CONTROLS, ETC.
9. PROVIDE VANED ELBOWS IN ALL CASES, SPLITTER DAMPERS WHERE INDICATED
ON DRAWINGS AND VOLUME CONTROL DAMPERS IN ALL BRANCH DUCTS OR DIFFUSER
CONNECTIONS.
10. TERMINAL AIR DISTRIBUTION DEVICES SHALL BE AS FOLLOWS:
CEILING DIFFUSER: EQUIV. TO TITUS MODEL TDC-AA
WALL DIFFUSER: EQUIV. TO TITUS MODEL 300 FL
RETURN REGISTER: EQUIV. TO TITUS MODEL 350 FL
GENERAL NOTE:
CONTRACTOR TO COORDINATE DUCTWORK LAYOUT WITH EXISTING
ELECTRICAL CONDUITS, ETC. REROUTE EXISTING DUCTWORK AS
NESSESARY. NOTIFY OWNER, ARCHITECT AND ENGINEER OF ANY
CONFLICT WITH EXISTING CONDITIONS TO PROVIDE SOLUTIONS.
CONTRACTOR SHALL VISIT JOB SITE PRIOR TO BID. T&B CONTRACTOR
SHALL PROVIDE A FINAL TEST AND BALANCE REPORT WITHIN SCOPE
OF WORK TO PROVIDE THE DESIGNED QUANTITIES SHOWN ON PLANS.
PROVIDE T&B REPORT IN ACCORDANCE WITH THE AIR BALANCE COUNCIL
STANDARDS, SIGNED AND SEALED BY A REGISTER ENGINEER.
-
LEGEND
NEW SUPPLY DIFFUSER
NEW RETURN AIR GRILLE
MANUAL VOLUME DAMPER
(T PROVIDE PROGRAMABLE T -STAT.
NEW FLEXIBLE DUCT, U.L. CLASS 1 (R-6)
NEW DUCT WITH R=4.2 INSULATION.
OUTSIDE AIR
CALCULATIONS
(AS PER
ASHRAE 62.1-2010)
APPLICATION
#OF PEOPLE
CFM/PERSON
NET FLOOR AREA
CFM/SF
O.A. CFM
O.A. PROVIDED
A/C#1
14
5
580
0.06
104,
125
NOTES:
4-WAYSUPPLY
1. CALCULATIONS ARE BASED ON ESTIMATED
DESIGN OCCUPANCY RATES
PSR ARCHITECTURAL PLANS AND VENTILATION RATES PER ASHRAE.
--WALL CAP WITH
- BUILT-IN DAMPER
WALL CAP DETAIL
NOT TO SCALE
WALL
CEILING GRILL WITH OBD DAMPER
NOTE: BOLT CONDENSING UNITS
TO CONC. PAD TO WITHSTAND
150 MPH HURRICANE FORCE
WANDS PER FBC 301.12.
CONDENSING UNIT
2" X 2" X 3/16" STEEL ANGLE
WITH 3/8" BOLTS TO BASE OF
UNIT AND 3/8" RED HEAD ANCHOR
INTO CONCRETE PAD. (TYPICAL
TWO SIDES)
PROVIDE 4" PVC SLEEVE AT
PENETRATION AND SEAL ENDS
WATERTIGHT
REFRIGERANT LINES METAL
STRAPS SECURED TO
BUILDING WALL
PROTECTIVE METAL JACKET.
PAINT TO MATCH ARCH.
NEOPRENE VIBRATION ISOLATORS
6" PREFAB PAD
CONDENSING UNIT MOUNTING DETAIL-
N.T.S.
NOTE:
HANG DUCTS ACCORDING
TO SMACNA STANDARDS
TYPICAL Z BAR
AND WIRE DUCT
HANGING DETAIL
TYPICAL HANGING -
STRAP AND SADDLE
HANGING DETAIL
10"0 MAX.
METHODS
OD
DUCTS DETAIL
SECURE WIRE
AIR DISTRIBUTION DEVICE
SCHEDULE
UNITUNITSELECTION
SERVICE
AIR HANDLING
NECK
SIZE
REMARK
Na
SYSTEM DATA
BASED ON
MODEL
CFM
aZ
A
CEILING
SUPPLY
TITUS TDC AA
WT
PLANS
4-WAYSUPPLY
GENERAL NOTE:
ELECTRICAL
COMPRESSOR
NO NEW LOADS (CFM) WERE
ADDED TO THIS PROJECT,
ALL EXISTING LOAD WAS
REBALANCE PER NEW DESIGN LAYOUT.
REF. LINES
Al
M
Elm
TOILET
Reinaldo A. Gomez
Architect
AR# 0013736
16047 SW 68 ST
MIAMI,FLORIDA 33193
Phone: 786-261-9551
REVISIONS
10/1/15 FIELD GOND.
SPLIT
SYSTEM
SCF-IJEDUILE
AIR HANDLING
UNIT
AIR COOLED CONDENSING UNIT
SYSTEM DATA
MARK
MODEL
CFM
aZ
FAN
HEATER
WT
MARK
MODEL
WT
ELECTRICAL
COMPRESSOR
UNIT
MAX
CAPACITY
j
REF. LINES
N0.
Q
ESP
N0.
LBS
VOLTS -PH -HZ
MCA
FUSE
S
SEER
LL0
TOTAL
OA
HP
KW
STEP
LBS
QTY.
TONS
TMBH
SMBH
SUCTION
I LIQUID
AHU-1
RH1T24
600
104
0.5
1/3
2.8
1
1..
95
CU -1
13AJN18
187
208-1-60
1
1.5
14
20
23.8
17.7
13
AS PER A4ANUF. RECORlMND
SPLIT SYSTEM NOTES:
r
4. PROVIDE PROPER VIBRATION ISOLATORS AS PER ISOLATION
1. OUTSIDE AIR DESIGN CONDITIONS: 91°FDB - 79°FDB.
MANUFACTURER'S RECOMMENDATIONS.
PROVIDE FILTER RACK UNDER
2 PROVIDE A/C UNIT WITH PROGRAMMABLE HEATING AND COOLING
THERMOSTAT WITH
AHU. RETURN AIR THRU LOUVERED DOOR UNLESS OTHERWISE NOTED.
ON-OFF SWITCH SUB -BASE. (WIRED AND INSTALLED
BY ELECTRICAL
CONTRACTOR)
5. INSULATE REFRIGERANT SUCTION LINE
WITH 3/4" FIRE
3. SIZE AND RUN REFRIGERANT PIPING AS
MANUFACTURER'S
RETARDANT ARMAFLEX.
PUBLISHED RECOMMENDATIONS.
6. PROVIDE BUILT-IN DISCONNECT WITH
ALL AIR HANDLING UNITS.
Al
M
Elm
TOILET
Reinaldo A. Gomez
Architect
AR# 0013736
16047 SW 68 ST
MIAMI,FLORIDA 33193
Phone: 786-261-9551
REVISIONS
10/1/15 FIELD GOND.
3-
L GM
i o 00
wah
n -rt~. IIII,I -
MECHANICAL FLOOR PLAN_
NEW WORK KEY NOTES
O NEW HORIZONTAL AHU TO BE LOCATED ABOVE THE CEILING.
O G.C. TO PROVIDE 0/A MOTORIZED DAMPERS IN THIS AREA
AS REQUIRED. MOTORIZED DAMPERS 120V/1/60 TO BE
INTERCONNECTED WITH (AHU) RESPECTIVELY AND SHUT
DOWN WHEN AC IS NOT OPERATING.
O3 LOCATE NEW CAP FOR AIR INTAKE IN THIS AREA AS REQUIRED.
LOCATE NEW CU' -1 IN ROOF IN TtiIS AREA AS REQUIRED.
GENERAL NOTE_
EXISTING AC -1 AND AC -2 ARE BOTH 5TON UNITS
RATED 208V/1/60 60,OOOBTUH MODEL# LCMC9260SO02
BY GRENADA. BOTH A/C UNITS WILL BE REUSED AS
PART OF THIS PROJECT.
GUIROLA & ASSOCIATES P.A
CONSULTING ENGINEERS
David Guirola PE
P.E. No 57468
tIA NW72nd AVE,
MIAMI. FLORIDA 3312&126
PH 1
CA ODOD9112 EMAIL G
PERMIT NO.
ALL WORK INVOLVED ON THIS PERMIT SMALL CONFORM
WITH ALL CITY OF BOYNTON BEACH BUILDING CODES.
NIP
By: Date:A
14
EC HAN I CAL
FLOOR PLAN
DATE: PREPARED REVIEWED
BY: BY:
4/15/15 JM JM
SHEET: OF:
OVIED M-1 1
®. 4n4r
W
W
0
aZ
W
CL
Q
Q
Q
0
j
�
Z
Q
0
UL
W
=
S
LL0
z
0
4
0
�-
MW
W
o
Icad.
W
oZ
3:
0
W
1..
J
r
00
�0
U) IM
r
3-
L GM
i o 00
wah
n -rt~. IIII,I -
MECHANICAL FLOOR PLAN_
NEW WORK KEY NOTES
O NEW HORIZONTAL AHU TO BE LOCATED ABOVE THE CEILING.
O G.C. TO PROVIDE 0/A MOTORIZED DAMPERS IN THIS AREA
AS REQUIRED. MOTORIZED DAMPERS 120V/1/60 TO BE
INTERCONNECTED WITH (AHU) RESPECTIVELY AND SHUT
DOWN WHEN AC IS NOT OPERATING.
O3 LOCATE NEW CAP FOR AIR INTAKE IN THIS AREA AS REQUIRED.
LOCATE NEW CU' -1 IN ROOF IN TtiIS AREA AS REQUIRED.
GENERAL NOTE_
EXISTING AC -1 AND AC -2 ARE BOTH 5TON UNITS
RATED 208V/1/60 60,OOOBTUH MODEL# LCMC9260SO02
BY GRENADA. BOTH A/C UNITS WILL BE REUSED AS
PART OF THIS PROJECT.
GUIROLA & ASSOCIATES P.A
CONSULTING ENGINEERS
David Guirola PE
P.E. No 57468
tIA NW72nd AVE,
MIAMI. FLORIDA 3312&126
PH 1
CA ODOD9112 EMAIL G
PERMIT NO.
ALL WORK INVOLVED ON THIS PERMIT SMALL CONFORM
WITH ALL CITY OF BOYNTON BEACH BUILDING CODES.
NIP
By: Date:A
14
EC HAN I CAL
FLOOR PLAN
DATE: PREPARED REVIEWED
BY: BY:
4/15/15 JM JM
SHEET: OF:
OVIED M-1 1
®. 4n4r
0J SCALE: 1/4"=1'-O'
LEt�ND
DUPLEX RECEPTACLE @ 12" AFF, U.O.N.
LIGHTING SWITCH {s 48" AFF.
3
3 -WAY LIGHTING SWITCH @ 48" AFF.
ELECTRIC PANEL
FAN/LIGHT COMBINATION
FLUORESCENT LIGHT
EMERGENCY LiGHT 120V WITH BATTERY
CONNECTED AHEAD OF ANY SWITCH
SELECTED BY ARCH/OWNER
2 SETS 4#600 THWN
+1#1/0(GND) IN 3/4" C EACH
EXISTING
ELECTRICAL BUILDING WALL
EXISTING
30800
7
120/208V
EXISTING
MAIN
BREAKER 30
200A
AND METER
EXISTING
EXISTING 1# 3/0 (GND) IN 3/4" C
FPL
EXISTING ELECTRICAL RISER
NTS
SUITE 104
EXISTING
PANEL A
200 A
120/208V 30
EXISTING
4#3/0 THWN + 1 # 6 (GND)
IN 2" C
1
DEMAND NO DEN. CONDUIT WIRE TRI' POLES LOAD DESCRIPTION CKT
LOAD VA LOAD VA SIZE AMP AND REMARKS NO.
A-25 A-13,15
1030
NF
WP WP
Lj
112
112
112
112
112
112
112
112
112
112
112
112
12
12
12
12
12
12
12
12
12
12
12
12
20
20
20
20
20
20
25
20
20
20
20
20
1-
1-
1-
1-
1-
1-
2-
2-
1-
1-
1-
1-
EXISTING DISPLAY REC.
-1
-3
-5
-7
-9
-11
-13
-15
-17
-19
-21
-23
-25
-27
-29
-31
-33
-35
-37
-39
-41
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
2-
4-
6-
8-
10-
12-
W
16-
18-
20-
22-
24-
26-
28-
30-
32-
34-
36-
38-
40-
42-
EXISTING SPARE
FEC
EC
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
12
12
12
12
12
12
12
112
112
1/2
112
1/2
112
112
0
0
0
1165
1165
0
560
280
0
0
0
0
900
0
900
900
280
560
-
DISPLAY
EXISTING SPARE
EXISTING DISPLAY REG.
EXISTING SPARE
NEW OFFICE REC.
NEW CIU
EXISTING BATH REC.
OFFICE
EXISTING SPARE
EXISTING SPARE
NEW AHU
NEW DISPLAYS LIGHTS
LL
A-7
EXISTING 220V OUTLET
EXSTING SPAFE
_
EXISTING SPARE
A-5
EXISTING SPARE
EXISTING SPARE
EXISTING SPARE
EXISTING RECEPfACLEGFI
EXISTING NE OUTLET
A-1 A-3
EXISTING SPARE
SPACE
EXISTING WEST OUTLET
SPACE
EXISTING EAST OUTLET
SPACE
EXISTING SPARE
SPACE
EXISTING SPARE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
0 8514 = SUB - TOTALS
EXIST. TOILET
SUB - TOTALS = 6710 0
0 VA : TOTAL DEMAND LOAD (2)
LOAD PER PHASE
7797 VA PHASE"A"
4415 VA PHASE "B"
3012 VA PHASE "C'
TOTAL PANEL AMPS =VA /VOLT = 42 AMP
1. PROV IDE GROU DING BAR KiT
2_ APPLYING DEMAND AS PER NEC TABLE 220-44.
'A"
PANOA"
0 VA: 2506 CONTINOUS LIGHT
0 VA : 25% LARGEST MOTOR
15224 TOTAL LOAD
A 9
EXISTING WAREHOUSE
pp POWER PLAN
0 SCALE:1 /4"=V-0"
-0"
SERVICE 3PH, 4W, 60HZ TYPE SI ENS
VOLTAGE 120 / 208 V. EXISTING PANEL "A" MOD.
MAIN BUS: 225 AMP
MAINS: 200
DEMAND NO DEN. CONDUIT WIRE TRI' POLES LOAD DESCRIPTION CKT
LOAD VA LOAD VA SIZE AMP AND REMARKS NO.
PHASE
A B C
CKT LOAD DESCR 91ON POLES TRI' WARE CONDUIT NO DEM. DEMAND
NO: AND REMARKS AMP SIZE LOAD VA LOAD VA
=
720
540
720
720
180
0
1820
1820
832
832
150
0
180
0
112
112
112
112
112
112
112
112
112
112
112
112
12
12
12
12
12
12
12
12
12
12
12
12
20
20
20
20
20
20
25
20
20
20
20
20
1-
1-
1-
1-
1-
1-
2-
2-
1-
1-
1-
1-
EXISTING DISPLAY REC.
-1
-3
-5
-7
-9
-11
-13
-15
-17
-19
-21
-23
-25
-27
-29
-31
-33
-35
-37
-39
-41
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
2-
4-
6-
8-
10-
12-
W
16-
18-
20-
22-
24-
26-
28-
30-
32-
34-
36-
38-
40-
42-
EXISTING SPARE
-1
-1
-1
-2
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
12
12
12
12
12
12
12
112
112
1/2
112
1/2
112
112
0
0
0
1165
1165
0
560
280
0
0
0
0
900
0
900
900
280
560
-
EXISTING DISPLAY FEC.
EXISTING SPARE
EXISTING DISPLAY REG.
EXISTING SPARE
NEW OFFICE REC.
NEW CIU
EXISTING BATH REC.
EXISTING SPARE
EXISTING SPARE
NEW AHU
NEW DISPLAYS LIGHTS
LL
NEIN OFFICE LiGHT
EXISTING 220V OUTLET
EXSTING SPAFE
_
EXISTING SPARE
NEW FANLIGHT BATH
EXISTING SPARE
EXISTING SPARE
EXISTING SPARE
EXISTING RECEPfACLEGFI
EXISTING NE OUTLET
EXISTING VVEST FAN
EXISTING SPARE
SPACE
EXISTING WEST OUTLET
SPACE
EXISTING EAST OUTLET
SPACE
EXISTING SPARE
SPACE
EXISTING SPARE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
0 8514 = SUB - TOTALS
D.F_ = 0.50
SUB - TOTALS = 6710 0
0 VA : TOTAL DEMAND LOAD (2)
LOAD PER PHASE
7797 VA PHASE"A"
4415 VA PHASE "B"
3012 VA PHASE "C'
TOTAL PANEL AMPS =VA /VOLT = 42 AMP
1. PROV IDE GROU DING BAR KiT
2_ APPLYING DEMAND AS PER NEC TABLE 220-44.
15224 VA : TOTAL NO DEMAND LOAD
0 VA: 2506 CONTINOUS LIGHT
0 VA : 25% LARGEST MOTOR
15224 TOTAL LOAD
ELECTF#CAL SPECRCAMNS
PART 1- GENERAL
A.- Overall Installation: The installation shall comply with the Latest
edition of Electrical Code (NEC), the Florida Building Code (FBC), and
any other applicable Federal, State and Local codes.
B.- Conductor Calculations: Conductor calculations are based on 75 'C.
1. General: The General and Special Conditions and Requirements of
the Contract and Specifications as well as plans and specifications
of other disciplines and trades shall be a part of the work hereby
specified. These specifications and accompanying plans are intended
to provide for the complete furnishing and installation of the elec-
trical systems. To provide means to furnish and install.
2. Compliance: Workmanship, materials and installation shall be in strict
accordance with the applicable edition of the NEC,NFPA,NEMA,ASTM,
OSHA, HRS health agencies, and other applicable national, state, and
local codes and pertaining regulations established by the ruling
authority having jurisdiction.
Contractors shall also meet the requirements of other standards
where such requirements are more strict than those standards
cited above.
3. Workmanship: All work shall be performed by contractors licensed
in their respective discipline. Work shall be done in a first class
manner, fully operative, and to the acceptance of the Architect and
the Engineers. Contractor shall provide for all necessary labor and
material required for the completion of the work including but not
limited to related work such as connection of existing systems, exca-
vations and back filling.
4. Materials: Contractor shall provide all new materials of American ma-
nufacture, bearing the Underwriter's Laboratory (UL) label as appli-
cable. Materials shall be new, suitable for the application and above
standard quality normally used for the purpose as called for on plans.
Supplemental materials, products and components necessary to comply
with the intent of the Contract drawings and/or specifications, but
not noted or specified on these sections, shall be provided by the
Contractor as required for the completion of the work at no additio-
nal cost to the Owner. Contractor shall be responsible for provisions
and coordination of delivery of materials.
Equipment marred during shipment or installation shall be touched up
and refinished to factory finish, replaced where not acceptable.
5.- Permits and Insurance: Contractor shall secure and pay for all
permits, fees, taxes, inspections, tests, fines and other items as
required for the installation of the complete electrical systems as
outlined herein and shown on plans.
Contractor shall provide all required insurance for protection against
public liability and property damage for the duration of the work.
6.- Existing conditions: Before bidding, the contractor shall visit the job
site and ascertain all existing conditions which will affect his work.
Failure to do so will not be accepted as a reason for requesting
extra pay where the existing conditions result in extra materials or labor
Any existing conditions found by the Contractor which will adversely
affect the work shall be immediately be brought to the attention of
the Architect/Engineer. Correction of any defects shall be completely
without additional charge and shall include replacements or repair of
any other phase of the installation which may have been damaged thereby.
7.- Plans: Drawings are basically diagrams intended to depict approximately
equipment locations and arrangements, not to show every minor detail.
Plans shall not be scaled to determine exact location and dimensions.
8.- Interference: The Contractor shall coordinate his work with other
trades so that interference with existing conditions, conduits, piping,
equipment, architectural and structural members be avoided.
J.- Substitutions: Products and materials called out by trade name and/or
catalog numbers establish a standard of quality, appearance, perfor-
mance and dimension. Contractors shall base his proposal on those
items as they shall be considered as a standard basis of bidding.
Requests for substitution shall be submitted in writing to the Archi-
tect/Engineer, demonstrating that product is of comparable and basic
design, construction, standards and warranties, dimensions to fit wi-
thout change, and does not cause extra work to other trades.
Contractor shall be responsible for providing equality of substitution:
Architect/Engineer will, under no circumstances, be required to prove
such item is or is not of equal quality to the specified item. Archi-
tect/Engineer expenses incurred due to Contractor's requested revi-
sions or substitutions shall be paid by the Contractor.
10. -Record Drawings: Maintain a complete set of prints for indicating
all changes. Use colored pens to mark changes at the time of exe-
cution and deliver the set to the Architect/Engineer upon completion.
Contractor shall stamp "As Built" on prints and plans, date and sign
in ink.
11. -The Contractor shall, and hereby does, warrant all labor and material
free from defects for a period of one (1) year from the date of
acceptance or beneficial use by the owner, whichever is earlier and
shall, upon notification during this period promptly repair or replace
any defective items or material or equipment at no cost to the owner.
SCOPE OF WORK
1- THE SCOPE OF WORK IS A NEW OFFICE SPACE
IN EXISTING WAREHOUSE. REST OF EXISTING
WAREHOUSE AREA POWER AND LIGHTING EXISTING TO
REMAIN.
GUIROLA & ASSOCIATES P.A.
CONSULTING ENGINEERS
David Guirola PE
P.E. No 57468
A NW 72nd AVE, S-451
MI
- M1AM1,1=LORIDA 3312126
P.H: (305) 513 665
CA 00009112 EMAIL: GUIRO 56MAOL.COM
M
Reinaldo A. Gomez
Architect
AR# 0013736
16047 SW 68 ST
MIAMI,FLORIDA 33193
Phone: 786-261-9551
1010/1/15 FiELD COND.
ELECTRICAL
PLAN
DATE:
W
REVIEWED
W
=
BY:
U
YG
DG
Q
OF:
E-1
aW
Q
Q
0
J
-
Z
CO)
LL
W
M
_
LL
z
U
Q
0
_
W
o
W
�Z0
H�
J
r
00
so
In
r
wm
ELECTRICAL
PLAN
DATE:
PREPARED
REVIEWED
BY:
BY:
4/15/15
YG
DG
SHEET:
OF:
E-1
1
EXIST, 1HR DEMISING WALL TO
OCCUPANT LOAD CALCULATION:
BASE ON FLORIDA BUILDING CODE / LIFE SAFETY CODE
BUSINESS) =588 SF /100 = 6 OCCUPANTS
WAREHOUSE) =3925 SF /500 = 8 OCCUPANTS ;
TOTAL OCCUPANCY = 14 OCCUPANTS
REQUIRED PROVIDED
MINIMUM NUMBER OF EXITS 2 2
MINIMUM WIDTH OF EXIT CORRIDORS 0.2(110) 22" 72"
MAXIMUM TRAVEL DISTANCE TO EXIT 150' 98'
EMAIN
2x4
.ELEV. +16'-0"
`�' EXIST. EXPOSED
STRUCTURE
OFFICE
F
WALL ASSEMBLY
INSULATION
FIRECODE COMPOI
PENETRATION
Fire Stop—lHr Wal
D I 11 SCALE: NTS
WAREHOUSE
V '
W
SCOPE: EXISTING AUTOBODY/AUTO
REPAIR SHOP TO HAVE PORTION IN
THE FRONT TO BE REMODELED INTO
NEW OFFICE FOR SHOP.
OCCUPATIONAL USE OF SPACE TO
REMAIN THE SAME.
REFLECTED CEILING PLANSCALD 1/8' = V-0' —4)I
NOTES:
1. NOTE: REFER TO MECHANICAL DRAWINGS FOR LOCATION
SUPPLY AND RETURN AIR DIFFUSER AND GRILLS.
2. REFER TO ELECTRICAL DRAWINGS FOR LIGHTING FIXTURE
SPECIFICATIONS AND ADDITIONAL INFORMATION.
PER NFPA 101 OCCUPANCY CLASSIFICATION OF DISPLAY/OFFICE IS BUISNESS
PER NFPA 101 OCCUPANCY CLASSIFICATION OF WAREHOUSE IS STORAGE
PER NFPA 101 BUISNESS OCCUPANCY IS ORDINARY HAZARD
_ WAREHOUSE STORAGE IS LOW HAZARD
BOTTOM OF
STRUCT. DECKt
4:
PROVIDE FASTENER
0 24" O.C. max
(HILTI X—ZF-20THP) _ '' _
ALL JOINTS & SCREW
HEADS ON OUTER LAYER
TO HAVE TWO COATS
DRY OR PRE MIXED
JOINT COMPOUND. 2" W—
PERF. PAPER TAPE OVER
ALL JOINTS, EMBEDDED—
IN
MBEDDEDIN 1ST COAT.
TYPICAL NOTE:
PROVIDE 1-1/2" x
1/2" CHANNEL
LATERAL STUD
BRACING EVERY
4'-6" MAX. ATTAC
TO EACH VERT.
STUD W/ CLIP ANG
& 4 FRAMING
SCREWS
1
7
Penetration
1/2" MAX
F.B.C. 2010
BUILDING IS TYPE 11 CONSTRUCTION
ALTERATION LEVEL 2
CONSTRUCTION TYPE 11
SCOPE OF WORK
1. ALL INTERIOR - NO BUILDING ENVELOPE WORK. NO STRUCTURAL MODIFICATIONS.
COORDINATE. RELOCATION OF OUTLETS & LIGHTING W/ EXISTING CIRCUITS.
NO ADDITIONAL ELECTRICAL LOAD.
GE14ERAL NOTES:
1. PR IDE ALL
TO HIS SPACE LABOR,
DAT EQUIPMENT, 662AND SOUTHTCOIALS NGRESSQUIRTO COMPLETE A EED PALM SPRINGS, THE
FLOR FLORIDAIMPROVEMENTS
2. L WORK TOCOMPLY IN ALL
ORDINANCES, PECTS WITH REGULATIONS. LAWSAAND CODES LE (Le. NATIONAL FIRECOUNTY NO
CODE,
DE,
R LOCAL STATUES,
NFPA 101 LIFE SAFETY CODE AND THE 2010 EDITION OF THE FLORIDA BUILDING CODE).
CONTRACTOR OCCUPATIO ALM LICENSE LWITHINEDHE CITY OF IN THE STATE
PALM FLORIDA SPRINGS.
AND SHALL OBTAIN AN
4. CONTRACTOR SHALL CONTACT ARCHITECT IMMEDIATELY UPON DISCOVERY OF ANY UNFORESEEN
CONDITIONS. NO CUTTING SHALL BE DONE TO ANY STRUCTURAL MEMBERS EXCEPT
WHEN/IF SHOWN ON THE DRAWINGS.
6. EXISTING CONDITIONS: CONTRACTOR TO NOTIFY ARCHITECT IMMEDIATELY IF EXISTING
CONDITIONS ARE NOT IN AGREEMENT WITH INFORMATION AND DETAILS SHOWN ON DRAWINGS.
5. CONTRACTORS SHALL VERIFY ALL CONDITIONS AND DIMENSIONS AT THE JOBSITE.
6. HE
INCLUDING WORK OF OTHER
CONTRACTOR RESPONSIBLE
WHERFOR
AFFECT COORDINATION OF ALL TRADES AND WORK,
8. IT IS THE GENERAL CONTRACTOR'S
S EL OR RESPONSIBILITY
TO KEEP CHANGES THE
CITY
OAFFECM SPRINGS
UPDATED ON ANY ADDENDUM, OR PLAN
THE PERMIT APPROVED SET OF PLANS.
9. ALL MATERIALS USED IN THE PERMANENT CONSTRUCTION OF THE WORK SHALL BE NEW
AND UNUSED, FIRST QUALITY AND FREE FROM DEFECTS AND INSTALLED AS PER MANUR
RECOMMENDED
PROFESSIONAL L HE APPLICATIONLIAT HAND. ALL WORKMANSHIP SHALL
EO
10. THE CONTRACTOR SHALL MAINTAIN A FULL SET OF COMPLETE AND CURRENT DRAWINGS
AVAILABLE FOR REVIEW AT THE JOBSITE AT ALL TIMES. ALL FIELD MODIFICATIONS TO
THE ORIGINAL DRAWINGS SHALL BE NOTED AND MAINTAINED FOR THE OWNER'S RECORD
COPY.
*CONTRACTOR TO VERIFY ALL EXISTING EGRESS DOORS HAVE ADA COMPLIANT PUSHPULL DEVICES AND CLOSENS,
3/8" CONTINUOUS FIRE RATED
SEALANT TYP. TOP & BOT.
SEAL ALL PENETRATIONS W/
FIRE RATED SEALANT
CEILING LINE
METAL STUD BRACING
0 CEILING LINE
BATT INSULATION
WHERE SHOWN ON PLAN
SELF TAPPING BUGLE HEAD
-SCREWS TYPE S-12 ® 12" O.C..
1" LONG
3-5/8" 20 GA MTL
STUDS SPACED 0 16"O.C.
"
5/8TYPE 'X' DRYWALL
1 hr = 1 LAYER EACH
SIDE
NON-BEARING WALL
BRATED 1 HRS
; I JUL DESIGN No. U419
PROVIDE FASTENERS
® 24" O.C. max
(HILTI X—ZF-20THP)
3-5/8" STEEL RUNNER
CHANNEL TOP & BOTTOM
SCALE 3"=1'-0"
IDE OTES NEW 3 1/2' :
DS AT 24"O.C. FRONC. SLAB ABOVE W/
D. EACH SIDE FROM F
ABOVE FINISH CEILING
EXISTING STRUCTURE
ICAL CEILING TILE
ND CLASSIFICATION "C"
BRACING (TYP)
Reineldo A. Gomez
Architect
AR# 0013736
16047 SW 68 ST
MIAMI,PLOMDA 33193
Phone: 786-261-9551
REVISIONS
6/20/15
9/17/2015
10/12/2015
W
Class A Locations
W
Criteria
a
Light (Low) Hazard
Occupancy.
Minimum Rated single
extinguisher 2-A
J
OC
za
Maximum floor area
Maximum floor area
per unit of A 3,000
for extinguisher
sgft
11,250 sgft
wn
Moll
Maximum travel distance to extinguisher
75 ft
FLOOR
PLAN
w
usQ
SCALES 1/8" = V-0"
O
W
OCCUPANCY CLAWF'ICr►'TI ON
0
w!-
OCCUPANCY CATEGORY
P.
MIXED USE
W
CONSTRUCTION TYPE TYPE it -B (NO
SPRINKLER
AREA TABULATION:
BUSINESS
588 SQ. FT.
WAREHOUSE
3337 SQ. FT.
TOTAL
3925 SQ. FT.
OCCUPANT LOAD CALCULATION:
BASE ON FLORIDA BUILDING CODE / LIFE SAFETY CODE
BUSINESS) =588 SF /100 = 6 OCCUPANTS
WAREHOUSE) =3925 SF /500 = 8 OCCUPANTS ;
TOTAL OCCUPANCY = 14 OCCUPANTS
REQUIRED PROVIDED
MINIMUM NUMBER OF EXITS 2 2
MINIMUM WIDTH OF EXIT CORRIDORS 0.2(110) 22" 72"
MAXIMUM TRAVEL DISTANCE TO EXIT 150' 98'
EMAIN
2x4
.ELEV. +16'-0"
`�' EXIST. EXPOSED
STRUCTURE
OFFICE
F
WALL ASSEMBLY
INSULATION
FIRECODE COMPOI
PENETRATION
Fire Stop—lHr Wal
D I 11 SCALE: NTS
WAREHOUSE
V '
W
SCOPE: EXISTING AUTOBODY/AUTO
REPAIR SHOP TO HAVE PORTION IN
THE FRONT TO BE REMODELED INTO
NEW OFFICE FOR SHOP.
OCCUPATIONAL USE OF SPACE TO
REMAIN THE SAME.
REFLECTED CEILING PLANSCALD 1/8' = V-0' —4)I
NOTES:
1. NOTE: REFER TO MECHANICAL DRAWINGS FOR LOCATION
SUPPLY AND RETURN AIR DIFFUSER AND GRILLS.
2. REFER TO ELECTRICAL DRAWINGS FOR LIGHTING FIXTURE
SPECIFICATIONS AND ADDITIONAL INFORMATION.
PER NFPA 101 OCCUPANCY CLASSIFICATION OF DISPLAY/OFFICE IS BUISNESS
PER NFPA 101 OCCUPANCY CLASSIFICATION OF WAREHOUSE IS STORAGE
PER NFPA 101 BUISNESS OCCUPANCY IS ORDINARY HAZARD
_ WAREHOUSE STORAGE IS LOW HAZARD
BOTTOM OF
STRUCT. DECKt
4:
PROVIDE FASTENER
0 24" O.C. max
(HILTI X—ZF-20THP) _ '' _
ALL JOINTS & SCREW
HEADS ON OUTER LAYER
TO HAVE TWO COATS
DRY OR PRE MIXED
JOINT COMPOUND. 2" W—
PERF. PAPER TAPE OVER
ALL JOINTS, EMBEDDED—
IN
MBEDDEDIN 1ST COAT.
TYPICAL NOTE:
PROVIDE 1-1/2" x
1/2" CHANNEL
LATERAL STUD
BRACING EVERY
4'-6" MAX. ATTAC
TO EACH VERT.
STUD W/ CLIP ANG
& 4 FRAMING
SCREWS
1
7
Penetration
1/2" MAX
F.B.C. 2010
BUILDING IS TYPE 11 CONSTRUCTION
ALTERATION LEVEL 2
CONSTRUCTION TYPE 11
SCOPE OF WORK
1. ALL INTERIOR - NO BUILDING ENVELOPE WORK. NO STRUCTURAL MODIFICATIONS.
COORDINATE. RELOCATION OF OUTLETS & LIGHTING W/ EXISTING CIRCUITS.
NO ADDITIONAL ELECTRICAL LOAD.
GE14ERAL NOTES:
1. PR IDE ALL
TO HIS SPACE LABOR,
DAT EQUIPMENT, 662AND SOUTHTCOIALS NGRESSQUIRTO COMPLETE A EED PALM SPRINGS, THE
FLOR FLORIDAIMPROVEMENTS
2. L WORK TOCOMPLY IN ALL
ORDINANCES, PECTS WITH REGULATIONS. LAWSAAND CODES LE (Le. NATIONAL FIRECOUNTY NO
CODE,
DE,
R LOCAL STATUES,
NFPA 101 LIFE SAFETY CODE AND THE 2010 EDITION OF THE FLORIDA BUILDING CODE).
CONTRACTOR OCCUPATIO ALM LICENSE LWITHINEDHE CITY OF IN THE STATE
PALM FLORIDA SPRINGS.
AND SHALL OBTAIN AN
4. CONTRACTOR SHALL CONTACT ARCHITECT IMMEDIATELY UPON DISCOVERY OF ANY UNFORESEEN
CONDITIONS. NO CUTTING SHALL BE DONE TO ANY STRUCTURAL MEMBERS EXCEPT
WHEN/IF SHOWN ON THE DRAWINGS.
6. EXISTING CONDITIONS: CONTRACTOR TO NOTIFY ARCHITECT IMMEDIATELY IF EXISTING
CONDITIONS ARE NOT IN AGREEMENT WITH INFORMATION AND DETAILS SHOWN ON DRAWINGS.
5. CONTRACTORS SHALL VERIFY ALL CONDITIONS AND DIMENSIONS AT THE JOBSITE.
6. HE
INCLUDING WORK OF OTHER
CONTRACTOR RESPONSIBLE
WHERFOR
AFFECT COORDINATION OF ALL TRADES AND WORK,
8. IT IS THE GENERAL CONTRACTOR'S
S EL OR RESPONSIBILITY
TO KEEP CHANGES THE
CITY
OAFFECM SPRINGS
UPDATED ON ANY ADDENDUM, OR PLAN
THE PERMIT APPROVED SET OF PLANS.
9. ALL MATERIALS USED IN THE PERMANENT CONSTRUCTION OF THE WORK SHALL BE NEW
AND UNUSED, FIRST QUALITY AND FREE FROM DEFECTS AND INSTALLED AS PER MANUR
RECOMMENDED
PROFESSIONAL L HE APPLICATIONLIAT HAND. ALL WORKMANSHIP SHALL
EO
10. THE CONTRACTOR SHALL MAINTAIN A FULL SET OF COMPLETE AND CURRENT DRAWINGS
AVAILABLE FOR REVIEW AT THE JOBSITE AT ALL TIMES. ALL FIELD MODIFICATIONS TO
THE ORIGINAL DRAWINGS SHALL BE NOTED AND MAINTAINED FOR THE OWNER'S RECORD
COPY.
*CONTRACTOR TO VERIFY ALL EXISTING EGRESS DOORS HAVE ADA COMPLIANT PUSHPULL DEVICES AND CLOSENS,
3/8" CONTINUOUS FIRE RATED
SEALANT TYP. TOP & BOT.
SEAL ALL PENETRATIONS W/
FIRE RATED SEALANT
CEILING LINE
METAL STUD BRACING
0 CEILING LINE
BATT INSULATION
WHERE SHOWN ON PLAN
SELF TAPPING BUGLE HEAD
-SCREWS TYPE S-12 ® 12" O.C..
1" LONG
3-5/8" 20 GA MTL
STUDS SPACED 0 16"O.C.
"
5/8TYPE 'X' DRYWALL
1 hr = 1 LAYER EACH
SIDE
NON-BEARING WALL
BRATED 1 HRS
; I JUL DESIGN No. U419
PROVIDE FASTENERS
® 24" O.C. max
(HILTI X—ZF-20THP)
3-5/8" STEEL RUNNER
CHANNEL TOP & BOTTOM
SCALE 3"=1'-0"
IDE OTES NEW 3 1/2' :
DS AT 24"O.C. FRONC. SLAB ABOVE W/
D. EACH SIDE FROM F
ABOVE FINISH CEILING
EXISTING STRUCTURE
ICAL CEILING TILE
ND CLASSIFICATION "C"
BRACING (TYP)
Reineldo A. Gomez
Architect
AR# 0013736
16047 SW 68 ST
MIAMI,PLOMDA 33193
Phone: 786-261-9551
REVISIONS
6/20/15
9/17/2015
10/12/2015
rPSUM BOARD
015
) SELECT BASF N1�1��)t�� 'z k
eOEI) SELECT TILE
REf E E] t
QUI 0ING D � V i S OK_
130�NT F
TYP. INTERIOR PARTITON
FLAME 'SPREAD CLASSIFICATION "C" - UNSPRINKLERED BUILDING
ALIGN N AND SECURE TOP AND BOTTOM RUNNERS AT 24" O.C. WITH .145" DIAMETER LOW-VELOCITY POWER DRIVEN FASTENERS WITH 1'/" PENETRATION.
P. PARTITION DETAIL 3/4"=1'-O„
DATE: PREPARED REVIEWED
BY: BY:
4/30/15 RG RG
SHEET: OF:
A-1 1
W
W
Z
a
IL
Q
0
J
OC
za
o
11=
wn
Moll
Emit
X
Uj
w
usQ
O
W
0
w!-
CZ
0
P.
"'
O
W
coo,
rPSUM BOARD
015
) SELECT BASF N1�1��)t�� 'z k
eOEI) SELECT TILE
REf E E] t
QUI 0ING D � V i S OK_
130�NT F
TYP. INTERIOR PARTITON
FLAME 'SPREAD CLASSIFICATION "C" - UNSPRINKLERED BUILDING
ALIGN N AND SECURE TOP AND BOTTOM RUNNERS AT 24" O.C. WITH .145" DIAMETER LOW-VELOCITY POWER DRIVEN FASTENERS WITH 1'/" PENETRATION.
P. PARTITION DETAIL 3/4"=1'-O„
DATE: PREPARED REVIEWED
BY: BY:
4/30/15 RG RG
SHEET: OF:
A-1 1
EXIST. 1HR DEMISING WALL TO RE
BASE ON FLORIDA BUILDING CODE / LIFE SAFETY CODE
BUSINESS) =588 SF /100 = 6 OCCUPANTS
WAREHOUSE) =3925 SF /500 = 8 OCCUPANTS
TOTAL OCCUPANCY = 14 OCCUPANTS
REQUIRED PROVIDED
MINIMUM NUMBER OF EXITS 2 2
MINIMUM WIDTH OF EXIT CORRIDORS 0.2(110) 22" 72"
MAXIMUM TRAVEL DISTANCE TO EXIT 150' 98'
LAIN
(0
w
LL_
I®
ELEV. +16'-0"
EXIST. DCPOSED
STRUCTURE
•a .
0
REFLECTED CEILING P
SCALEt 1/8' = 1'-0'
0
WALL ASSEMBLY
INSULATION
FIRECODE COMPOI
PENETRATION
EXIST.
Fire Stop—lHr Wall Penetration
SCALE: NTS
F.B.C. 2010
BUILDING IS TYPE II CONSTRUCTION
ALTERATION LEVEL 2
CONSTRUCTION TYPE II
PE OF WORK
1. ALL INTERIOR - NO BUILDING ENVELOPE WORK. NO STRUCTURAL MODIFICATIONS.
COORDINATE RELOCATION OF OUTLETS & LIGHTING W/ EXISTING CIRCUITS.
NO ADDITIONAL ELECTRICAL LOAD.
GE14ERAL NOTES:
1. PR DE ALL LABOR, EQUIPMENT, AND MATERIALS REQUIRED TO COMPLETE THE IMPROVEMENTS
TO IS SPACE LOCATED AT 1662 SOUTH CONGRESS AVE., PALM SPRINGS, FLORIDA
2. WORK TO COMPLY IN ALL RESPECTS WITH APPLICABLE FEDERAL, STATE, COUNTY AND/
R LOCAL STATUES, ORDINANCES, REGULATIONS, LAWS AND CODES (i.e. NATIONAL FIRE CODE,
TO
101 LIFE SAFETY CODE AND THE 2010 EDITION OF THE FLORIDA BUILDING CODE).
CONTRACTOR MUST BE LICENSED IN THE STATE OF FLORIDA AND SHALL OBTAIN AN
OCCUPATIONAL LICENSE WITHIN THE CITY OF PALM SPRINGS.
CONTRACTOR SHALL CONTACT ARCHITECT IMMEDIATELY UPON DISCOVERY OF ANY UNFORESEEN
CONDITIONS. NO CUTTING SHALL BE DONE TO ANY STRUCTURAL MEMBERS EXCEPT
WHEN/IF SHOWN ON THE DRAWINGS.
6. EXISTING CONDITIONS: CONTRACTOR TO NOTIFY ARCHITECT IMMEDIATELY IF EXISTING
CONDITIONS ARE NOT IN AGREEMENT WITH INFORMATION AND DETAILS SHOWN ON DRAWINGS.
5. CONTRACTORS SHALL VERIFY ALL CONDITIONS AND DIMENSIONS AT THE JOBSITE.
6. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF ALL TRADES AND WORK,
INCLUDING WORK OF OTHERS WHERE AFFECTED.
8. IT IS THE GENERAL CONTRACTOR'S SOLE RESPONSIBILITY TO KEEP THE CITY OF PALM SPRINGS
UPDATED ON ANY ADDENDUM, CHANGE ORDER, OR PLAN CHANGES THAT WILL AFFECT
THE PERMIT APPROVED SET OF PLANS.
9. ALL MATERIALS USED IN THE PERMANENT CONSTRUCTION OF THE WORK SHALL BE NEW
AND UNUSED, FIRST QUALITY AND FREE FROM DEFECTS AND INSTALLED AS PER MANUF.
RECOMMENDED PROCEDURES FOR THE APPLICATION AT HAND. ALL WORKMANSHIP SHALL
BE OF FIRST CLASS PROFESSIONAL QUALITY.
10. THE CONTRACTOR SHALL MAINTAIN A FULL SET OF COMPLETE AND CURRENT DRAWINGS
AVAILABLE FOR REVIEW AT THE JOBSITE AT ALL TIMES. ALL FIELD MODIFICATIONS TO
THE ORIGINAL DRAWINGS SHALL BE NOTED AND MAINTAINED FOR THE OWNER'S RECORD
COPY.
DOOR
Class A
Locations
V
Criteria
PROVIDE FASTENER
\-3/8-
0 24" O.C. max
Light <Low) Hazard
Occupancy
(HILTI X—ZF-20THP)
Minimum
Rated single
extinguisher 2-A
SEAL ALL PENETRATIONS W/
a
-
Maximum
floor area
per unit of A 3,000
sqft
z
CEILING LINE
Maximum
floor area
for extinguisher
11,250 sqft
C
Maximumtravel
distance to extinguisher
75 ft
FLOOR PLAN
0
Q
SCALEi 1/8' = 1'-0'
W
1-
m
OCCUPANCY CLAS81F7CATM
CO)d.
W
oZ
�' o
�=
J
3:
O
OCCUPANCY CATEGORY
MIXED USE
no
CONSTRUCTION TYPE TYPE II -B (NO SPRINKLER )
M
Co
qFM
(0M
AREA TABULATION•
BUSINESS 588 SQ. Ff.
WAREHOUSE 3337 SQ. FT.
TOTAL 3925 SQ. FT.
OCCUPANT LOAD CALCULATION:
BASE ON FLORIDA BUILDING CODE / LIFE SAFETY CODE
BUSINESS) =588 SF /100 = 6 OCCUPANTS
WAREHOUSE) =3925 SF /500 = 8 OCCUPANTS
TOTAL OCCUPANCY = 14 OCCUPANTS
REQUIRED PROVIDED
MINIMUM NUMBER OF EXITS 2 2
MINIMUM WIDTH OF EXIT CORRIDORS 0.2(110) 22" 72"
MAXIMUM TRAVEL DISTANCE TO EXIT 150' 98'
LAIN
(0
w
LL_
I®
ELEV. +16'-0"
EXIST. DCPOSED
STRUCTURE
•a .
0
REFLECTED CEILING P
SCALEt 1/8' = 1'-0'
0
WALL ASSEMBLY
INSULATION
FIRECODE COMPOI
PENETRATION
EXIST.
Fire Stop—lHr Wall Penetration
SCALE: NTS
F.B.C. 2010
BUILDING IS TYPE II CONSTRUCTION
ALTERATION LEVEL 2
CONSTRUCTION TYPE II
PE OF WORK
1. ALL INTERIOR - NO BUILDING ENVELOPE WORK. NO STRUCTURAL MODIFICATIONS.
COORDINATE RELOCATION OF OUTLETS & LIGHTING W/ EXISTING CIRCUITS.
NO ADDITIONAL ELECTRICAL LOAD.
GE14ERAL NOTES:
1. PR DE ALL LABOR, EQUIPMENT, AND MATERIALS REQUIRED TO COMPLETE THE IMPROVEMENTS
TO IS SPACE LOCATED AT 1662 SOUTH CONGRESS AVE., PALM SPRINGS, FLORIDA
2. WORK TO COMPLY IN ALL RESPECTS WITH APPLICABLE FEDERAL, STATE, COUNTY AND/
R LOCAL STATUES, ORDINANCES, REGULATIONS, LAWS AND CODES (i.e. NATIONAL FIRE CODE,
TO
101 LIFE SAFETY CODE AND THE 2010 EDITION OF THE FLORIDA BUILDING CODE).
CONTRACTOR MUST BE LICENSED IN THE STATE OF FLORIDA AND SHALL OBTAIN AN
OCCUPATIONAL LICENSE WITHIN THE CITY OF PALM SPRINGS.
CONTRACTOR SHALL CONTACT ARCHITECT IMMEDIATELY UPON DISCOVERY OF ANY UNFORESEEN
CONDITIONS. NO CUTTING SHALL BE DONE TO ANY STRUCTURAL MEMBERS EXCEPT
WHEN/IF SHOWN ON THE DRAWINGS.
6. EXISTING CONDITIONS: CONTRACTOR TO NOTIFY ARCHITECT IMMEDIATELY IF EXISTING
CONDITIONS ARE NOT IN AGREEMENT WITH INFORMATION AND DETAILS SHOWN ON DRAWINGS.
5. CONTRACTORS SHALL VERIFY ALL CONDITIONS AND DIMENSIONS AT THE JOBSITE.
6. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF ALL TRADES AND WORK,
INCLUDING WORK OF OTHERS WHERE AFFECTED.
8. IT IS THE GENERAL CONTRACTOR'S SOLE RESPONSIBILITY TO KEEP THE CITY OF PALM SPRINGS
UPDATED ON ANY ADDENDUM, CHANGE ORDER, OR PLAN CHANGES THAT WILL AFFECT
THE PERMIT APPROVED SET OF PLANS.
9. ALL MATERIALS USED IN THE PERMANENT CONSTRUCTION OF THE WORK SHALL BE NEW
AND UNUSED, FIRST QUALITY AND FREE FROM DEFECTS AND INSTALLED AS PER MANUF.
RECOMMENDED PROCEDURES FOR THE APPLICATION AT HAND. ALL WORKMANSHIP SHALL
BE OF FIRST CLASS PROFESSIONAL QUALITY.
10. THE CONTRACTOR SHALL MAINTAIN A FULL SET OF COMPLETE AND CURRENT DRAWINGS
AVAILABLE FOR REVIEW AT THE JOBSITE AT ALL TIMES. ALL FIELD MODIFICATIONS TO
THE ORIGINAL DRAWINGS SHALL BE NOTED AND MAINTAINED FOR THE OWNER'S RECORD
COPY.
DOOR
SCHEDULE
V
aZ
PROVIDE FASTENER
\-3/8-
0 24" O.C. max
CONTINUOUS FIRE RATED
(HILTI X—ZF-20THP)
SEALANT TYP. TOP & BOT.
mi
'-
SEAL ALL PENETRATIONS W/
a
-
T__
r' FIRE RATED SEALANT
�
*CONTRACTOR TO VERIFY ALL EXISTING EGRESS DOORS HAVE ADA COMPLIANT PUSHPULL DEVICES AND CLOSERS.
ot BOTTOM OF
STRUCT. DECK
W
V
aZ
PROVIDE FASTENER
\-3/8-
0 24" O.C. max
CONTINUOUS FIRE RATED
(HILTI X—ZF-20THP)
SEALANT TYP. TOP & BOT.
mi
'-
SEAL ALL PENETRATIONS W/
a
-
T__
r' FIRE RATED SEALANT
�
z
CEILING LINE
NOTES:
1. NOTE: REFER TO MECHANICAL DRAWINGS FOR LOCATION
SUPPLY AND RETURN AIR DIFFUSER AND GRILLS.
2. REFER TO ELECTRICAL DRAWINGS FOR LIGHTING FIXTURE
SPECIFICATIONS AND ADDITIONAL INFORMATION.
PER NFPA 101 OCCUPANCY CLASSIFICATION OF DISPLAY/OFFICE IS BUISNESS
PER NFPA 101 OCCUPANCY CLASSIFICATION OF WAREHOUSE IS STORAGE
PER NFPA 101 BUISNESS OCCUPANCY IS ORDINARY HAZARD
WAREHOUSE STORAGE IS LOW HAZARD
ALL JOINTS & SCREW
HEADS ON OUTER LAYER
TO HAVE TWO COATS
DRY OR PRE MIXED
JOINT COMPOUND. 2" W—
PERF. PAPER TAPE OVER
ALL JOINTS, EMBEDDED
IN 1ST COAT.
TYPICAL NOTE:
PROVIDE 1-1/2" x
1/2" CHANNEL
LATERAL STUD
BRACING EVERY
4'-6" MAX. ATTAC
TO EACH VERT.
STUD W/ CLIP ANG
& 4 FRAMING
SCREWS
METAL STUD BRACING
® CEILING LINE
BATT INSULATION
WHERE SHOWN ON PLAN
SELF TAPPING BUGLE HEAD
SCREWS TYPE S-12 0 12" O.C..
1" LONG
3-5/8" 20 GA MTL
STUDS SPACED 0 16"o.c.
" TYPE 'X' DRYWALL
= 1 LAYER EACH
NON-BEARING WALL
BRATED MRS
IUL DESIGN No. U419
VIDE FASTENERS
4" O.C. max
TI X—ZF-20THP)
/8" STEEL RUNNER
NNEL TOP & BOTTOM
SCALE 3"=1'-0"
DOTES NEW 3 1/2'
S DS AT E O.C. FRO!
NC. SLAB ABOVE W/
D. EACH SIDE FROM F
ABOVE FINISH CEILING
EXISTING STRUCTURE
TICAL CEILING TILE
:AD CLASSIFICATION "C"
BRACING (TYP)
'SUM BOARD
SELECT BASE
SELECT TILE
Reinaido A. Gomez
Architect
AR# 0013736
16047 SW 68 ST
MIAMI,IPLOMDA 33193
Phone: 786-2614MS1
FIEVRIONS
6/20/15
9/17/2015
W
W
V
aZ
aW
cc
a
C'
mi
'-
Z
a
-
O
1=
�
CO
lion
LL.
X
C
_
Wun
0
Q
W
1-
m
�
O
CO)d.
W
oZ
�' o
�=
J
3:
O
W
H
no
M
M
Co
qFM
(0M
TYP. INTERIOR PARTITON
FLAME SPREAD CLASSIFICATION "C" - UNSPRINKLERED BUILDING DATE: PREPARED BBEVIEwED
4/30/15 RG RG
ALIGN AND SECURE TOP AND BOTTOM RUNNERS AT 24" O.C. WITH .145" DIAMETER LOW-VELOCITY POWER DRIVEN FASTENERS WITH 1%" PENETRATION.
SHEET: OF:
TYP. PARTITION DETAIL 3/4"= 1'-O" A=1 1
a
DENOTES NEW 1 5/8" 24 GA. MR.
STUDS AT 16"OC. 'fid/ Z" GYP, WALI
BD. INTERIOR SIDE SECURED TO
EXISTING WALL WITH DRfWALL
SCREWS 0 16" O.C. W/ DRYWALL
►' FASTNERS W/ I " PENETRATION
y INTO CMU 0 TOP INTERMEDIATE AN
BOTTOM CHANNELS
4 HORIZONTAL BRACING (TYP)
EXISTING 8' CMU
y R-4.1 FOIL INSULATION AT EXTERIi
WALL
sr
EXISTING WALL (CMU AT EXTERIOR
CONDITION)
r
! PAINTED G'fPSUM BOARD
-BASE RUNNER
ALIGN AND SECURE BOTTOM RUNNERS AT 24" O.C. NTH .145"
DIAMETER LOW-tVELOCITY POWER DRNEN FASTENERS WITH 1 �"
PENETRATION.
, C- FRAMING DETAIL
EXIST. 1HR DEMISING WALL TO REME
Class A Locations
Criteria
Light (Low) Hazard occupancy
Minimum Rated single extinguisher 2-A
Maximum floor area per unit of A 3,000 sgft
Maximum ftoor area for extinguisher 11,250 sgft
Maximum travel distance to extinguisher75 ft
FLOOR PLAN
SCALE, 1/8'
pCCUPAMY CLMSIFICATION
OCCUPANCY CATEGORY MIXED USE
CONSTRUCTION TYPE TYPE 11-B (NO SPRINKLER )
AREA TABULATION:
BY:
BUSINESS 588 SQ. FT.
WAREHOUSE 3337 SQ. FT.
4/30/15
JPREPARED
RG
TOTAL 3925 SQ. Ff.
SHEET:
OF:
OCCUPANT LOAD CALCULATION:
1
��e�r
ry
BASE ON FLORIDA BUILDING CODE / LIFE SAFETY CODE
,^1�iLIC'(i�t"tel
d
BUSINESS) =588
SF /100 =
6 OCCUPANTS
WAREHOUSE) =3925 SF /500 =
8 OCCUPANTS
= 14 OCCUPANTS
TOTAL OCCUPANCY
REQUIRED
PROVIDED
MINIMUM NUMBER OF EXITS
2
2
MINIMUM WIDTH OF EXIT CORRIDORS 0.2(110)
22"
72"
MAXIMUM TRAVEL DISTANCE TO EXIT
150'
98'
41.
EMAIN
W
FIR
ELEV. 9'-0'
2x4 A TILE
ELEY. +1+16_-0"
V EXIST. DCPOSED
STRUCTURE
WAREHOUSE
49
OFFICE
REFLECTED CEILING PLANS
EXIST.
NOTES:
1. NOTE: REFER TO MECHANICAL DRAWINGS FOR LOCATION
SUPPLY AND RETURN AIR DIFFUSER AND GRILLS.
2. REFER TO ELECTRICAL DRAWINGS FOR LIGHTING FIXTURE
SPECIFICATIONS AND ADDITIONAL INFORMATION.
PER NFPA 101 OCCUPANCY CLASSIRCATION OF DISPLAY/OFFICE IS BUISNESS
PER NFPA 101 OCCUPANCY CLASSIFICATION OF WAREHOUSE IS STORAGE
PER NFPA 101 BUISNESS OCCUPANCY IS ORDINARY HAZARD
WAREHOUSE STORAGE IS LOW HAZARD
WALL ASSEMBLY
INSULATION
"RECODE COMPOI
PENETRATION
Fire Stop-1Hr Wall Penetration
SCALE: NTS
F.B.C. 2010
BUILDING IS TYPE II CONSTRUCTION
ALTERATION LEVEL 2
CONSTRUCTION TYPE 11
S\COPE OF WORK
1. ALL INTERIOR - NO BUILDING ENVELOPE WORK. NO STRUCTURAL MODIFICATIONS.
COORDINATE RELOCATION OF OUTLETS & LIGHTING W/ EXISTING CIRCUITS.
NO ADDITIONAL ELECTRICAL LOAD.
GE ERAL NOTES:
1. PR IDE ALL LABOR, EQUIPMENT, AND MATERIALS REQUIRED TO COMPLETE THE IMPROVEMENTS
TO HIS SPACE LOCATED AT 1662 SOUTH CONGRESS AVE., PALM SPRINGS. FLORIDA
2. WORK TO COMPLY IN ALL RESPECTS WITH APPLICABLE FEDERAL, STATE, COUNTY AND/
NFPA0101 LIFE�SAFETY ORDINANCES,
00 LAND REGULATIONS,
EDITION OF THE FLORIDA BUILDING CODE)i.e. NATIONAL FIRE CODE,
CONTRACTOR MUST BE LICENSED IN THE STATE OF FLORIDA AND SHALL OBTAIN AN
OCCUPATIONAL LICENSE WITHIN THE CITY OF PALM SPRINGS.
CONTRACTOR SHALL CONTACT ARCHITECT IMMEDIATELY UPON DISCOVERY OF ANY UNFORESEEN
CONDITIONS. NO CUTTING SHALL BE DONE TO ANY STRUCTURAL MEMBERS EXCEPT
WHEN/IF SHOWN ON THE DRAWINGS.
6. EXISTING CONDITIONS: CONTRACTOR TO NOTIFY ARCHITECT IMMEDIATELY IF EXISTING
CONDITIONS ARE NOT IN AGREEMENT WITH INFORMATION AND DETAILS SHOWN ON DRAWINGS.
5. CONTRACTORS SHALL VERIFY ALL CONDITIONS AND DIMENSIONS AT THE JOBSITE.
6. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF ALL TRADES AND WORK,
INCLUDING WORK OF OTHERS WHERE AFFECTED -
8. IT IS UPDATED GENERAL ON ANY ADDENDUM,,OR'S SOLE CHANGE ORDER,OORIBILITY TO KEEP THE CITY PLAN CHANGES THAT W OAFFECT SPRINGS
THE PERMIT APPROVED SET OF PLANS.
9. ALL MATERIALS USED IN THE PERMANENT CONSTRUCTION OF THE WORK SHALL BE NEW
AND UNUSED, FIRST QUALITY AND FREE FROM DEFECTS AND INSTALLED AS PER MANUR
RECOMMENDED PROCEDURES FOR THE APPLICATION AT HAND. ALL WORKMANSHIP SHALL
BE OF FIRST CLASS PROFESSIONAL QUALITY.
10. THE CONTRACTOR SHALL MAINTAIN A FULL SET OF COMPLETE AND CURRENT DRAWINGS
AVAILABLE FOR REVIEW AT THE JOBSITE AT ALL TIMES, ALL FIELD MODIFICATIONS TO
THE ORIGINAL DRAWINGS SHALL BE NOTED AND MAINTAINED FOR THE OWNER'S RECORD
COPY.
BOTTOM OF
STRUCT. DECK
PROVIDE FASTENERS
0 24" O.C. max
(HILTI X-ZF-20THP)
ALL JOINTS & SCREW
HEADS ON OUTER LAYER
TO HAVE TWO COATS
DRY OR PRE MIXED
JOINT COMPOUND. 2" W -
PERF. PAPER TAPE OVER
ALL JOINTS, EMBEDDED—
IN
MBEDDEDIN 1ST COAT.
TYPICAL NOTE:
PROVIDE 1-1/2' x
1/2- CHANNEL
LATERAL STUD
BRACING EVERY
4'-6' MAX. ATTA
TO EACH VERT.
STUD W/ CLIP ANG
& 4 FRAMING
SCREWS
1/2' MAX
`----3/8" CONTINUOUS FIRE RATED
SEALANT TYP. TOP & BOT.
SEAL ALL PENETRATIONS W/
FIRE RATED SEALANT
i- CEILING LINE
METAL STUD BRACING
® CEILING LINE
BATT INSULATION
WHERE SHOWN ON PLAN
SELF TAPPING BUGLE HEAD
SCREWS TYPE S-12 ® 12" O.C..
1" LONG
3-5/8' 20 GA MTL
STUDS SPACED ® 16"o.c.
5/8' TYPE 'X' DRYWALL I
I hr = 1 LAYER EACH
SIDE
NON-BEARING WALL
\ g RATED 1HRS
\ A-1
UL DESIGN No. U41
PROVIDE FASTENERS
® 24" O.C. max
(HILTI X-ZF-20THP)
3-5/8" STEEL RUNNER
CHANNEL TOP & BOTTOM
SCALE 3"=1'-0"
aTES NEW 3 1/27.
toOS AT 24 O.C. FROI
C. SLAB ABOVE W/
EACH SIDE FROM F
ABOVE FINISH CEILING
EXISTING STRUCTURE
[CAL CEILING TILE
AD CLASSIFICATION 'C"
m AL
Reinaido A. Gomez
Architect
AR# 0013736
16047 SW 68 ST
MUU1141.11FLOMDA 33193
Phone: 786-261-9551
REVISIONS
6/20/15
9/17/2015
W
W 0
v Z
' a W
a> a
0 J p�
> Z O
low DC LA,
X w
W
Oz Q
W
E- i- d. m
CO)
pZ
> O o
� � W
'j o
no
Cq
TYP. INTERIOR PARTITON
FLAME SPREAD CLASSIFICATION "C" - UNSPRINKLERED BUILDING
ALIGN AND SECURE TOP AND BOTTOM RUNNERS AT 24" O.C. WITH .145" DIAMETER LOW-VELOCITY POWER DRIVEN FASTENERS WITH 1%" PENETRATION.
TYP. PA ITDETAIL 3/4"=1'-O"
DATE:
BRACING (TYP)
BY:
BY:
4/30/15
JPREPARED
RG
RG
SHEET:
OF:
1
tjd i. `�
i 21.+ E!t�i'3—
1
��e�r
ry
,^1�iLIC'(i�t"tel
d
n
L13JI,157
!-ire
potice
(PSUM BOARD
other
SELECT BASE
L
PP� tnii shaii c�tllaFt'Fr �t�#t a4t to -
SELECT TILEcoy
�,t � � , ��ro4 re on ti3�
{
TYP. INTERIOR PARTITON
FLAME SPREAD CLASSIFICATION "C" - UNSPRINKLERED BUILDING
ALIGN AND SECURE TOP AND BOTTOM RUNNERS AT 24" O.C. WITH .145" DIAMETER LOW-VELOCITY POWER DRIVEN FASTENERS WITH 1%" PENETRATION.
TYP. PA ITDETAIL 3/4"=1'-O"
DATE:
REVIEWED
BY:
BY:
4/30/15
JPREPARED
RG
RG
SHEET:
OF:
A-1
1
EXIST, 1HR DEMISING WALL TO R
OCCUPANT LOAD CALCULATION:
BASE ON FLORIDA BUILDING CODE / LIFE SAFETY CODE
BUSINESS) =588 SF /100 = 6 OCCUPANTS
WAREHOUSE) =3925 SF /500 = 8 OCCUPANTS
TOTAL OCCUPANCY
MINIMUM NUMBER OF EXITS
MINIMUM WIDTH OF EXIT CORRIDORS 0.2(110)
MAXIMUM TRAVEL DISTANCE TO EXIT
= 14 OCCUPANTS
REQUIRED PROVIDED
2 2
22" 72"
150' 98'
AIN
SCHEDULE
Class A
Locations
Criteria
"
SEALANT TYP. TOP & BOT.
SEAL ALL PENETRATIONS W/
Light (Low) Hazard
Occupancy
ELEV. 9'-0"
Minimum
Rated single
extinguisher 2-A
+9 0
Maximum
floor area
per unit of A 3,000
sgft
Maximum
floor area
for extinguisher
11,250 sgft
FLOOR
P
Maximum
travel distance to extinguisher
75 ft
EXIST. EXPOSED
STRUCTURE
SCALES 1/8' = 1'-0'
WAREHOUSE
U
OCCUPANCY CLMIFICATION
OCCUPANCY CATEGORY
MIXED USE
CONSTRUCTION TYPE TYPE II -B (NO
SPRINKLER
AREA TABULATION:
BUSINESS
588 SQ. FT.
WAREHOUSE
3337 SQ. FT.
TOTAL
3925 SQ. FT.
OCCUPANT LOAD CALCULATION:
BASE ON FLORIDA BUILDING CODE / LIFE SAFETY CODE
BUSINESS) =588 SF /100 = 6 OCCUPANTS
WAREHOUSE) =3925 SF /500 = 8 OCCUPANTS
TOTAL OCCUPANCY
MINIMUM NUMBER OF EXITS
MINIMUM WIDTH OF EXIT CORRIDORS 0.2(110)
MAXIMUM TRAVEL DISTANCE TO EXIT
= 14 OCCUPANTS
REQUIRED PROVIDED
2 2
22" 72"
150' 98'
AIN
REFLECTED CEILING P
SCALES 1/8' = 1'-0'
i
WALL ASSEMBLY
INSULATION
FIRECODE COMPOL
PENETRATION
Fire Stop—lHr Wc
SCALE: NTS
BOTTOM OF
STRUCT. DECK
PROVIDE FASTENERS
® 24" O.C. max
(HILTI X-ZF-20THP)
ALL JOINTS & SCREW
HEADS ON OUTER LAYER
TO HAVE TWO COATS
DRY OR PRE MIXED
JOINT COMPOUND. 2" W -
PERF. PAPER TAPE OVER
ALL JOINTS, EMBEDDED
IN 1ST COAT.
NOTES:
1. NOTE: REFER TO MECHANICAL DRAWINGS FOR LOCATION
SUPPLY AND RETURN AIR DIFFUSER AND GRILLS.
2. REFER TO ELECTRICAL DRAWINGS FOR LIGHTING FIXTURE
SPECIFICATIONS AND ADDITIONAL INFORMATION.
PER NFPA 101 OCCUPANCY CLASSIFICATION OF DISPLAY/OFFICE IS BUISNESS
PER NFPA 101 OCCUPANCY CLASSIFICATION OF WAREHOUSE IS STORAGE
PER NFPA 101 BUISNESS OCCUPANCY IS ORDINARY HAZARD
WAREHOUSE STORAGE IS LOW HAZARD
TYPICAL NOTE:
PROVIDE 1-1/2" x
1/2" CHANNEL
LATERAL STUD
BRACING EVERY
4'-6" MAX. ATTAC
TO EACH VERT.
STUD W/ CLIP ANG
& 4 FRAMING
SCREWS
Penetration
F.B.C. 2010
BUILDING IS TYPE 11 CONSTRUCTION
ALTERATION LEVEL 2
CONSTRUCTION TYPE 11
SCOPE OF WORK
1. ALL INTERIOR - NO BUILDING ENVELOPE WORK. NO STRUCTURAL MODIFICATIONS.
COORDINATE RE_OCATION OF OUTLETS & LIGHTING W/ EXISTING CIRCUITS.
NO ADDITIONAL ELECTRICAL LOAD.
GE EML NOTES:
1. PR IDE ALL LABOR, EQUIPMENT, AND MATERIALS REQUIRED TO COMPLETE THE IMPROVEMENTS
TO HIS SPACE LOCATED AT 1662 SOUTH CONGRESS AVE., PALM SPRINGS, FLORIDA
2. L WORK TO COMPLY IN ALL RESPECTS WITH APPLICABLE FEDERAL, STATE, COUNTY AND/
RLOCAL STATUES, ORDINANCES, REGULATIONS, LAWS AND CODES (i.e. NATIONAL FIRE CODE,
NFPA 101 LIFE SAFETY CODE AND THE 2010 EDITION OF THE FLORIDA BUILDING CODE).
CONTRACTOR MUST BE LICENSED IN THE STATE OF FLORIDA AND SHALL OBTAIN AN
OCCUPATIONAL LICENSE WITHIN THE CITY OF PALM SPRINGS.
4. CONTRACTOR SHALL CONTACT ARCHITECT IMMEDIATELY UPON DISCOVERY OF ANY UNFORESEEN
CONDITIONS. NO CUTTING SHALL BE DONE TO ANY STRUCTURAL MEMBERS EXCEPT
WHEN/IF SHOWN ON THE DRAWINGS.
6. EXISTING CONDITIONS: CONTRACTOR TO NOTIFY ARCHITECT IMMEDIATELY IF EXISTING
CONDITIONS ARE NOT IN AGREEMENT WITH INFORMATION AND DETAILS SHOWN ON DRAWINGS.
5. CONTRACTORS SHALL VERIFY ALL CONDITIONS AND DIMENSIONS AT THE JOBSITE.
6. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF ALL TRADES AND WORK,'
INCLUDING WORK OF OTHERS WHERE AFFECTED.
8. IT IS THE GENERAL CONTRACTOR'S SOLE RESPONSIBILITY TO KEEP. THE CITY OF PALM SPRINGS
UPDATED ON ANY ADDENDUM, CHANGE ORDER, OR PLAN CHANGES THAT WILL AFFECT
THE PERMIT APPROVED SET OF PLANS.
9. ALL MATERIALS USED IN THE PERMANENT CONSTRUCTION OF THE WORK SHALL BE NEW
AND UNUSED, FIRST QUALITY AND FREE FROM DEFECTS AND INSTALLED AS PER MANUF.
RECOMMENDED PROCEDURES FOR THE APPLICATION AT HAND. ALL WORKMANSHIP SHALL
BE OF FIRST CLASS PROFESSIONAL QUALITY.
10. THE CONTRACTOR SHALL MAINTAIN A FULL SET OF COMPLETE AND CURRENT DRAWINGS
AVAILABLE FOR REVIEW AT THE JOBSITE AT ALL TIMES. ALL FIELD MODIFICATIONS TO
THE ORIGINAL DRAWINGS SHALL BE NOTED AND MAINTAINED FOR THE OWNER'S RECORD
COPY.
Iii'
SCHEDULE
1/2" MAX
1
ate■■■■ ■■■■
"
SEALANT TYP. TOP & BOT.
SEAL ALL PENETRATIONS W/
}.`..
FIRE RATED SEALANT
ELEV. 9'-0"
OFFICE
����� ■moo
2x4 AC TILE
+9 0
X4T LE
XIST. TOILET
EXIST. EXPOSED
STRUCTURE
Cp
WAREHOUSE
U
W
REFLECTED CEILING P
SCALES 1/8' = 1'-0'
i
WALL ASSEMBLY
INSULATION
FIRECODE COMPOL
PENETRATION
Fire Stop—lHr Wc
SCALE: NTS
BOTTOM OF
STRUCT. DECK
PROVIDE FASTENERS
® 24" O.C. max
(HILTI X-ZF-20THP)
ALL JOINTS & SCREW
HEADS ON OUTER LAYER
TO HAVE TWO COATS
DRY OR PRE MIXED
JOINT COMPOUND. 2" W -
PERF. PAPER TAPE OVER
ALL JOINTS, EMBEDDED
IN 1ST COAT.
NOTES:
1. NOTE: REFER TO MECHANICAL DRAWINGS FOR LOCATION
SUPPLY AND RETURN AIR DIFFUSER AND GRILLS.
2. REFER TO ELECTRICAL DRAWINGS FOR LIGHTING FIXTURE
SPECIFICATIONS AND ADDITIONAL INFORMATION.
PER NFPA 101 OCCUPANCY CLASSIFICATION OF DISPLAY/OFFICE IS BUISNESS
PER NFPA 101 OCCUPANCY CLASSIFICATION OF WAREHOUSE IS STORAGE
PER NFPA 101 BUISNESS OCCUPANCY IS ORDINARY HAZARD
WAREHOUSE STORAGE IS LOW HAZARD
TYPICAL NOTE:
PROVIDE 1-1/2" x
1/2" CHANNEL
LATERAL STUD
BRACING EVERY
4'-6" MAX. ATTAC
TO EACH VERT.
STUD W/ CLIP ANG
& 4 FRAMING
SCREWS
Penetration
F.B.C. 2010
BUILDING IS TYPE 11 CONSTRUCTION
ALTERATION LEVEL 2
CONSTRUCTION TYPE 11
SCOPE OF WORK
1. ALL INTERIOR - NO BUILDING ENVELOPE WORK. NO STRUCTURAL MODIFICATIONS.
COORDINATE RE_OCATION OF OUTLETS & LIGHTING W/ EXISTING CIRCUITS.
NO ADDITIONAL ELECTRICAL LOAD.
GE EML NOTES:
1. PR IDE ALL LABOR, EQUIPMENT, AND MATERIALS REQUIRED TO COMPLETE THE IMPROVEMENTS
TO HIS SPACE LOCATED AT 1662 SOUTH CONGRESS AVE., PALM SPRINGS, FLORIDA
2. L WORK TO COMPLY IN ALL RESPECTS WITH APPLICABLE FEDERAL, STATE, COUNTY AND/
RLOCAL STATUES, ORDINANCES, REGULATIONS, LAWS AND CODES (i.e. NATIONAL FIRE CODE,
NFPA 101 LIFE SAFETY CODE AND THE 2010 EDITION OF THE FLORIDA BUILDING CODE).
CONTRACTOR MUST BE LICENSED IN THE STATE OF FLORIDA AND SHALL OBTAIN AN
OCCUPATIONAL LICENSE WITHIN THE CITY OF PALM SPRINGS.
4. CONTRACTOR SHALL CONTACT ARCHITECT IMMEDIATELY UPON DISCOVERY OF ANY UNFORESEEN
CONDITIONS. NO CUTTING SHALL BE DONE TO ANY STRUCTURAL MEMBERS EXCEPT
WHEN/IF SHOWN ON THE DRAWINGS.
6. EXISTING CONDITIONS: CONTRACTOR TO NOTIFY ARCHITECT IMMEDIATELY IF EXISTING
CONDITIONS ARE NOT IN AGREEMENT WITH INFORMATION AND DETAILS SHOWN ON DRAWINGS.
5. CONTRACTORS SHALL VERIFY ALL CONDITIONS AND DIMENSIONS AT THE JOBSITE.
6. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF ALL TRADES AND WORK,'
INCLUDING WORK OF OTHERS WHERE AFFECTED.
8. IT IS THE GENERAL CONTRACTOR'S SOLE RESPONSIBILITY TO KEEP. THE CITY OF PALM SPRINGS
UPDATED ON ANY ADDENDUM, CHANGE ORDER, OR PLAN CHANGES THAT WILL AFFECT
THE PERMIT APPROVED SET OF PLANS.
9. ALL MATERIALS USED IN THE PERMANENT CONSTRUCTION OF THE WORK SHALL BE NEW
AND UNUSED, FIRST QUALITY AND FREE FROM DEFECTS AND INSTALLED AS PER MANUF.
RECOMMENDED PROCEDURES FOR THE APPLICATION AT HAND. ALL WORKMANSHIP SHALL
BE OF FIRST CLASS PROFESSIONAL QUALITY.
10. THE CONTRACTOR SHALL MAINTAIN A FULL SET OF COMPLETE AND CURRENT DRAWINGS
AVAILABLE FOR REVIEW AT THE JOBSITE AT ALL TIMES. ALL FIELD MODIFICATIONS TO
THE ORIGINAL DRAWINGS SHALL BE NOTED AND MAINTAINED FOR THE OWNER'S RECORD
COPY.
Iii'
SCHEDULE
1/2" MAX
1
ate■■■■ ■■■■
"
SEALANT TYP. TOP & BOT.
SEAL ALL PENETRATIONS W/
}.`..
FIRE RATED SEALANT
CEILING LINE
����� ■moo
*CONTRACTOR TO VERIFY ALL EXISTING EGRESS DOORS HAVE: ADA COMPLIANT PUSHPULL DEVICES AND CLOSERS.
'\
NON-BEARING WALL
g RATED 1HRS
JUL DESIGN No. 0419
METAL STUD BRACING
® CEILING LINE
BATT INSULATION
WHERE SHOWN ON PLAN
SELF TAPPING BUGLE HEAD
SCREWS TYPE S-12 ® 12" O.C..
1" LONG
3-5/8" 20 GA MTL
STUDS SPACED ® 16"o.c.
5/8" TYPE 'X' DRYWALL
1 hr = 1 LAYER EACH
SIDE
PROVIDE FASTENERS
® 24" O.C. max
(HILTI X—ZF-20THP)
3-5/8" STEEL RUNNER
CHANNEL TOP & BOTTOM
SCALE 3"=1'-0"
EXISTING STRUCTURE
to
0 OTES NEW 3 1/2" 24 GA. MTL
S DS AT 24"O.C. FROM FLOOR TO
tNC. SLAB ABOVE W/ r GYP. WALL
D. EACH SIDE FROM FLOOR TO 6"
ABOVE FINISH CEILING
2X4 ACOUSTICAL CEILING TILE
FLAME SPREAD CLASSIFICATION "C"
HORIZONTAL BRACING (TYP)
PAINTED GYPSUM BOARD
OWNER TO SELECT BASE
OWNER TO SELECT TILE
TYP. INTERIOR PARTITON
FLAME SPREAD CLASSIFICATION "C" - UNSPRINKLERED BUILDING
ALIGN AND SECURE TOP AND BOTTOM RUNNERS AT 24" O.C. WITH .145" DIAMETER LOW-VELOCITY POWER DRIVEN FASTENERS WITH 11/x" PENETRATION.
TYP. PARTITION DETAIL 3/4" =1'-0"
Reinaldo A. Gomez
Architect
AR# 0013736
16047 SW 68 ST
MIAMIlFLORIDA 33193
Phone: 786-261-0551
REVISIONS
6/20/15
9/17/2015
: —
a
;ab
PATE: PREPARED REVIEWED
BY: BY:
4/30/15 RG RG
ww
<C Z
am
cc> Q
4 p
(5 J
Z o
tW J
F -LL
w
U,
Q
0 Q
w
aZ
0 w0
w
J p !�
M 00
Cam
SHEET:
OF:
1/2" MAX
1
3/8 CONTINUOUS FIRE RATED
"
SEALANT TYP. TOP & BOT.
SEAL ALL PENETRATIONS W/
}.`..
FIRE RATED SEALANT
CEILING LINE
NON-BEARING WALL
g RATED 1HRS
JUL DESIGN No. 0419
METAL STUD BRACING
® CEILING LINE
BATT INSULATION
WHERE SHOWN ON PLAN
SELF TAPPING BUGLE HEAD
SCREWS TYPE S-12 ® 12" O.C..
1" LONG
3-5/8" 20 GA MTL
STUDS SPACED ® 16"o.c.
5/8" TYPE 'X' DRYWALL
1 hr = 1 LAYER EACH
SIDE
PROVIDE FASTENERS
® 24" O.C. max
(HILTI X—ZF-20THP)
3-5/8" STEEL RUNNER
CHANNEL TOP & BOTTOM
SCALE 3"=1'-0"
EXISTING STRUCTURE
to
0 OTES NEW 3 1/2" 24 GA. MTL
S DS AT 24"O.C. FROM FLOOR TO
tNC. SLAB ABOVE W/ r GYP. WALL
D. EACH SIDE FROM FLOOR TO 6"
ABOVE FINISH CEILING
2X4 ACOUSTICAL CEILING TILE
FLAME SPREAD CLASSIFICATION "C"
HORIZONTAL BRACING (TYP)
PAINTED GYPSUM BOARD
OWNER TO SELECT BASE
OWNER TO SELECT TILE
TYP. INTERIOR PARTITON
FLAME SPREAD CLASSIFICATION "C" - UNSPRINKLERED BUILDING
ALIGN AND SECURE TOP AND BOTTOM RUNNERS AT 24" O.C. WITH .145" DIAMETER LOW-VELOCITY POWER DRIVEN FASTENERS WITH 11/x" PENETRATION.
TYP. PARTITION DETAIL 3/4" =1'-0"
Reinaldo A. Gomez
Architect
AR# 0013736
16047 SW 68 ST
MIAMIlFLORIDA 33193
Phone: 786-261-0551
REVISIONS
6/20/15
9/17/2015
: —
a
;ab
PATE: PREPARED REVIEWED
BY: BY:
4/30/15 RG RG
ww
<C Z
am
cc> Q
4 p
(5 J
Z o
tW J
F -LL
w
U,
Q
0 Q
w
aZ
0 w0
w
J p !�
M 00
Cam
SHEET:
OF:
A-1
1
EXIST. 1HR DEMI
SCALES 1/8' = 1'-0'
OCCUPANCY CLASSIFICATION
OCCUPANCY CATEGORY
CONSTRUCTION TYPE TYPE it -B (NO SPRINKLER )
AREATABULATION:
BUSINESS 588 SQ. FT.
WAREHOUSE 3337 SQ. FT.
TOTAL 3925 SQ. FT.
Ctass A Locations
A-
R
R DEMISING WAL
TRATIONS)
EXIST. EXIT
Criteria
Light (Low) Hazard Occupancy
Minimum Rated single extinguisher 2-A
Maximum floor area per unit of A 3,000 sgft
Maximum floor area for extinguisher 11,250 sgft
Maximum travel distance to extinguisher75 ft
MIXED USE
OCCUPANT LOAD CALCULATION:
BASE ON FLORIDA BUILDING CODE / LIFE SAFETY CODE
BUSINESS) =588 SF /100 = 6 OCCUPANTS
WAREHOUSE) =3925 SF /500 = 8 OCCUPANTS
TOTAL OCCUPANCY
MINIMUM NUMBER OF EXITS
MINIMUM WIDTH OF EXIT CORRIDORS 0.2(110)
MAXIMUM TRAVEL DISTANCE TO EXIT
REQUIRED
2
22"
150'
= 14 OCCUPANTS
PROVIDED
2
72"
98'
I inja a I ga :Ib- I �re 11
-1 111151 ca I I
SCALES 1/8' = 1'-0'
NOTES:
1. NOTE: REFER TO MECHANICAL DRAWINGS FOR LOCATION OF
SUPPLY AND RETURN AIR DIFFUSER AND GRILLS.
2. REFER TO ELECTRICAL DRAWINGS FOR LIGHTING FIXTURE
SPECIFICATIONS AND ADDITIONAL INFORMATION.
PER NFPA 101 OCCUPANCY CLASSIFICATION OF DISPLAY/OFFICE IS BUISNESS
PER NFPA 101 OCCUPANCY CLASSIFICATION OF WAREHOUSE IS STORAGE
PER NFPA 101 BUISNESS OCCUPANCY IS ORDINARY HAZARD
WAREHOUSE STORAGE IS LOW HAZARD
WALL ASSEMBLY
INSULATION
FIRECODE COMPOI
PENETRATION
Stor)—lHr Wo
SCALE: NTS
BOTTOM OF
STRUCT. DECK
PROVIDE FASTENERS
0 24" O.C. max
(HILTI X—ZF-20THP)
ALL JOINTS & SCREW
HEADS ON OUTER LAYER
TO HAVE TWO COATS
DRY OR PRE MIXED
JOINT COMPOUND. 2" W—
PERF. PAPER TAPE OVER
ALL JOINTS, EMBEDDED
IN 1ST COAT.
EA
TYPICAL NOTE:
PROVIDE 1-1/2" x
1/2" CHANNEL
LATERAL STUD
BRACING EVERY
4'-6" MAX. ATTAC
TO EACH VERT.
STUD W/ CLIP ANG
& 4 FRAMING
SCREWS
Penetration
1/2" MAX
F.B.C. 2010
BUILDING IS TYPE II CONSTRUCTION
ALTERATION LEVEL 2
CONSTRUCTION TYPE II
SCOPE OF WORK
1. ALL INTERIOR - NO BUILDING ENVELOPE WORK. NO STRUCTURAL MODIFICATIONS.
2. COORDINATE RELOCATION OF OUTLETS & LIGHTING W/ EXISTING CIRCUITS.
NO ADDITIONAL ELECTRICAL LOAD.
GENERAL NOTES:
1. PROVIDE ALL LABOR, EQUIPMENT, AND MATERIALS REQUIRED TO COMPLETE THE IMPROVEMENTS
TO THIS SPACE LOCATED AT 1662 SOUTH CONGRESS AVE., PALM SPRINGS, FLORIDA
2. ALL WORK TO COMPLY IN ALL RESPECTS WITH APPLICABLE FEDERAL, STATE, COUNTY AND/
OR LOCAL STATUES, ORDINANCES, REGULATIONS, LAWS AND CODES (i.e. NATIONAL FIRE CODE,
NFPA 101 LIFE SAFETY CODE AND THE 2010 EDITION OF THE FLORIDA BUILDING CODE).
3. CONTRACTOR MUST BE LICENSED IN THE STATE OF FLORIDA AND SHALL OBTAIN AN
OCCUPATIONAL LICENSE WITHIN THE CITY OF PALM SPRINGS.
4. CONTRACTOR SHALL CONTACT ARCHITECT IMMEDIATELY UPON DISCOVERY OF ANY UNFORESEEN
CONDITIONS. NO CUTTING SHALL BE DONE TO ANY STRUCTURAL MEMBERS EXCEPT
WHEN/IF SHOWN ON THE DRAWINGS.
6. EXISTING CONDITIONS: CONTRACTOR TO NOTIFY ARCHITECT IMMEDIATELY IF EXISTING
CONDITIONS ARE NOT IN AGREEMENT WITH INFORMATION AND DETAILS SHOWN ON DRAWINGS.
5. CONTRACTORS SHALL VERIFY ALL CONDITIONS AND DIMENSIONS AT THE JOBSITE.
6. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF ALL TRADES AND WORK,
INCLUDING WORK OF OTHERS WHERE AFFECTED.
8. IT IS THE GENERAL CONTRACTOR'S SOLE RESPONSIBILITY TO KEEP THE CITY OF PALM SPRINGS
UPDATED ON ANY ADDENDUM, CHANGE ORDER, OR PLAN CHANGES THAT WILL AFFECT
THE PERMIT APPROVED SET OF PLANS.
9. ALL MATERIALS USED IN THE PERMANENT CONSTRUCTION OF THE WORK SHALL BE NEW
AND UNUSED, FIRST QUALITY AND FREE FROM DEFECTS AND INSTALLED AS PER MANUF.
RECOMMENDED PROCEDURES FOR THE APPLICATION AT HAND. ALL WORKMANSHIP SHALL
BE OF FIRST CLASS PROFESSIONAL QUALITY.
10. THE CONTRACTOR SHALL MAINTAIN A FULL SET OF COMPLETE AND CURRENT DRAWINGS
AVAILABLE FOR REVIEW AT THE JOBSITE AT ALL TIMES. ALL FIELD MODIFICATIONS TO
THE ORIGINAL DRAWINGS SHALL BE NOTED AND MAINTAINED FOR THE OWNER'S RECORD
COPY.
DOOR
SCHEDULE
REMARKS
������r� ■�^
*CONTRACTOR TO VERIFY ALL EXISTING EGRESS DOORS HAVE ADA COMPLIANT PUSHPULL DEVICES AND CLOSERS.
-3/8" CONTINUOUS FIRE RATED
SEALANT TYP. TOP & BOT.
SEAL ALL PENETRATIONS W/
FIRE RATED SEALANT
CEILING LINE
METAL STUD BRACING
0 CEILING LINE
BATT INSULATION
WHERE SHOWN ON PLAN
SELF TAPPING BUGLE HEAD
-SCREWS TYPE S-12 0 12" O.C..
1" LONG
NON-BEARING WALL
RATED 1 HRS
3-5/8" 20 GA MTL
STUDS SPACED ® 16"o.c.
5/8" TYPE 'X' DRYWALL
1 hr = 1 LAYER EACH
SIDE
PROVIDE FASTENERS
0 24" O.C. max
(HILTI X—ZF-20THP)
3-5/8" STEEL RUNNER
CHANNEL TOP & BOTTOM
IUL DESIGN
SCALE 3"=1'-0"
No. U419
EXISTING STRUCTURE
is
DENOTES NEW 3 1/2" 24 GA. MTL
STUDS AT 24'0.C. FROM FLOOR TO
CONC. SLAB ABOVE W/ 4' GYP. WALL
BD. EACH SIDE FROM FLOOR TO 6"
ABOVE FINISH CEILING
2X4 ACOUSTICAL CEILING TILE
FLAME SPREAD CLASSIFICATION "C"
HORIZONTAL BRACING (TYP)
PAINTED GYPSUM BOARD
OWNER TO SELECT BASE
OWNER TO SELECT TILE
TYP. INTERIOR PARTITON
FLAME SPREAD CLASSIFICATION "C" - UNSPRINKLERED BUILDING
ALIGN AND SECURE TOP AND BOTTOM RUNNERS AT 24" O.C. WITH .145" DIAMETER LOW-VELOCITY POWER DRIVEN FASTENERS WITH 1%" PENETRATION.
NP. PARTITION DETAIL 3/4"= 1'-0"
FIAG
Reinaido A. Gomez
Architect
AR# 0013736
16047 SW 68 ST
MIAMI,FLORIDA 33193
Phone: 786-261-8551
REVISIONS
6/20/15
7/20/15
JUL 20115
DATE: PREPARED REVIEWED
BY: BY:
4/30/15 RG RG
SHEET: OF:
A-1 1
A-14
DISPLAY) I I THY I OFFICE
EXIST. \TOILET
A-21
EXISTING WAREHOUSE I PANEL "A" iiiiiI I I
ILLUMINATION PLAN
SCALE: 1/4"= V-0"
LEGEND
!91:= DUPLEX RECEPTACLE @ 12" AFF, U.O.N.
LIGHTING SWITCH 0 48" AFF.
3
3—WAY LIGHTING SWITCH C➢ 48" AFF.
® ELECTRIC PANEL
FAN/LIGHT COMBINATION
FLUORESCENT LIGHT
EMERGENCY LIGHT 120V WITH BATTERY
CONNECTED AHEAD OF ANY SWITCH
SELECTED BY ARCH/OWNER
2 SETS 4#600 THWN
+1#1/0(GND) IN 3/4" C EACH
E iX STIN
.ELECTRICAL BUILDING WALL
EXISTING
30800
8W
120/208V
EXISTING
MAIN
BREAKER 30
200A
AND METER
EXISTING
EXISTING 1 # 3/0 (GND) IN 3/4" C
FPL
EXISTING ELECTRICAL RiSER
NTS
ROOF
A-13,15
WP10NO
WP
A-25
ROOF SECTION PLAN
SCALE:1 /4'=1 '-0"
SUITE 104
EXISTING
PANEL A
200 A
120/208V 30
EXISTING
4#3/0 THWN + 1 # 6 (GND)
IN 2" C
rVWCK MAN
SCALE:1 /4"=1'-0"
SERVE 3PH, 4W, 60HZ TYPE SIA34S
VOLTAGE 120 / 208 V. EXISTING PANEL "A" MOU
MAIN BUS: 225 AMP
MAINS: 200
DEMAND NO DEM. CONDUIT WIRE TRIP POLES LOAD DESCRIPTION CKT
LOAD VA LOAD VA SIZE AMP AND REMARKS NO.
PHASE
ABC
CKT LOAD DESCRIPTION POLES TRIP WiRE CONDUIT NO DEM DEMAND
NO. AND REMARKS AMP SIZE LOAD VA LOAD VA
720
540
720
720
180
0
1820
1820
832
832
150
0
180
0
1/2
1/2
1/2
1/2
1/2
112
1/2
1/2
1/2
112
1/2
1/2
12
12
12
12
12
12
12
12
12
12
12
12
20
20
20
20
20
20
25
20
20
20
20
20
1-
1-
1-
1-
1-
1-
2-
2-
1-
1-
1-
1-
EXISTING DISPLAY REC.
EEC
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
2-
4-
6-
8-
10-
12-
14-
16-
18-
20-
22-
24-
26-
28-
30-
32-
34-
36-
38-
40-
42-
EXISTING SPARE
-1
-1
-1
-2
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
DISPLAY
1/2
112
1/2
1/2
1/2
1/2
112
0
0
0
1165
1165
0
560
280
0
0
0
0
900
0
900
900
280
560
EXIST DISPLAY REC.
EXISTING SPARE
EXISTING DISPLAY REC.
OFFICE
NEW OFFICE REC.
NEW CIU
EXISTING BATH REC.
EXISTING SPARE
A-7
NEWAHU
NEW DISPLAYS LIGHTS
NEW OFFICE LiGHT
A-5
EXSiiNG SPARE
EXISTING SPARE
NEW FAIWLIGHT BATH
EXISTING SPARE
A-1 A-3
EXISTING SPARE
EXISTING RECEPTACLE GFI
EXISTING NE OUTLET
BUSTING WEST FAN
EXISTING SPARE
SPACE
EXISTING WEST OUTLET
SPACE
\1114 P
SPACE
EXISTING SPARE
SPACE
EXISTING SPARE
SPACE
SPACE
EXIST. TOILET
SPACE
SPACE
SPACE
0 8514 = SUB - TOTALS
0 A 9
0
SUB - TOTALS = 6710 0
0
VA : TOTAL DEMAND LOAD (2)
LOAD PER PHASE
7797 VA PHASE "A"
4415 VA PHASE"B"
3012 VA PHASE "C'
EXISTING WAREHOUSE
PANEL A"
15224 VA : TOTAL NO DEMAND LOAD
0 VA: 25% CONTINOUS LIGHT
rVWCK MAN
SCALE:1 /4"=1'-0"
SERVE 3PH, 4W, 60HZ TYPE SIA34S
VOLTAGE 120 / 208 V. EXISTING PANEL "A" MOU
MAIN BUS: 225 AMP
MAINS: 200
DEMAND NO DEM. CONDUIT WIRE TRIP POLES LOAD DESCRIPTION CKT
LOAD VA LOAD VA SIZE AMP AND REMARKS NO.
PHASE
ABC
CKT LOAD DESCRIPTION POLES TRIP WiRE CONDUIT NO DEM DEMAND
NO. AND REMARKS AMP SIZE LOAD VA LOAD VA
720
540
720
720
180
0
1820
1820
832
832
150
0
180
0
1/2
1/2
1/2
1/2
1/2
112
1/2
1/2
1/2
112
1/2
1/2
12
12
12
12
12
12
12
12
12
12
12
12
20
20
20
20
20
20
25
20
20
20
20
20
1-
1-
1-
1-
1-
1-
2-
2-
1-
1-
1-
1-
EXISTING DISPLAY REC.
-1
-3
-5
-7
-9
-11
-13
-15
-17
-19
-21
-23
-25
-27
-29
-31
-33
-35
-37
-39
-41
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
2-
4-
6-
8-
10-
12-
14-
16-
18-
20-
22-
24-
26-
28-
30-
32-
34-
36-
38-
40-
42-
EXISTING SPARE
-1
-1
-1
-2
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
-1
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
12
12
12
12
12
12
12
1/2
112
1/2
1/2
1/2
1/2
112
0
0
0
1165
1165
0
560
280
0
0
0
0
900
0
900
900
280
560
EXIST DISPLAY REC.
EXISTING SPARE
EXISTING DISPLAY REC.
EXISTING SPARE
NEW OFFICE REC.
NEW CIU
EXISTING BATH REC.
EXISTING SPARE
EXISTING SPARE
NEWAHU
NEW DISPLAYS LIGHTS
NEW OFFICE LiGHT
EXISTING 220V OUTLET
EXSiiNG SPARE
EXISTING SPARE
NEW FAIWLIGHT BATH
EXISTING SPARE
EXISTING SPARE
EXISTING SPARE
EXISTING RECEPTACLE GFI
EXISTING NE OUTLET
BUSTING WEST FAN
EXISTING SPARE
SPACE
EXISTING WEST OUTLET
SPACE
EXISTING EAST OUTLET
SPACE
EXISTING SPARE
SPACE
EXISTING SPARE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
0 8514 = SUB - TOTALS
D.F. = 0.50
SUB - TOTALS = 6710 0
0
VA : TOTAL DEMAND LOAD (2)
LOAD PER PHASE
7797 VA PHASE "A"
4415 VA PHASE"B"
3012 VA PHASE "C'
TOTAL PANEL AIM'S =VA /VOLT = 42 AMP
1. PROVIDE GROUNDING BAR KTT
2. APPLYING DEMAND AS PER NEC TABLE 220-44.
15224 VA : TOTAL NO DEMAND LOAD
0 VA: 25% CONTINOUS LIGHT
0 VA: 25% LARGEST MOTOR
15224 TOTAL LOAD
ELECTRICAL SPECOCATKOIS
PART 1— GENERAL
A.— Overall installation: The installation shall comply with the Latest
edition of Electrical Code (NEC), the Florida Building Code (FBC), and
any other applicable Federal, State and Local codes.
B.— Conductor Calculations: Conductor calculations are based on 75 'C.
1. General: The General and Special Conditions and Requirements of
the Contract and Specifications as well as plans and specifications
of other disciplines and trades shall be a part of the work hereby
specified. These specifications and accompanying plans are intended
to provide for the complete furnishing and installation of the elec—
trical systems. To provide means to furnish and install.
2. Compliance: Workmanship, materials and installation shall be in strict
accordance with the applicable edition of the NEC,NFPA,NEMA,ASTM,
OSHA, HRS health agencies, and other applicable national, state, and
local codes and pertaining regulations established by the ruling
authority having jurisdiction.
Contractors shall also meet the requirements of other standards
where such requirements are more strict than those standards
cited above.
3. Workmanship: All work shall be performed by contractors licensed
in their respective discipline. Work shall be done in a first class
manner, fully operative, and to the acceptance of the Architect and
the Engineers. Contractor shall provide for all necessary labor and
material required for the completion of the work including but not
limited to related work such as connection of existing systems, exca—
vations and back filling.
4. Materials: Contractor shall provide all new materials of American ma—
nufacture, bearing the Underwriter's Laboratory (UL) label as appli—
cable. Materials shall be new, suitable for the application and above
standard quality normally used for the purpose as called for on plans.
Supplemental materials, products and components necessary to comply
with the intent of the Contract drawings and/or specifications, but
not noted or specified on these sections, shall be provided by the
Contractor as required for the completion of the work at no additio—
nal cost to the Owner. Contractor shall be responsible for provisions
and coordination of delivery of materials.
Equipment marred during shipment or installation shall be touched up
and refinished to factory finish, replaced where not .acceptable.
5.— Permits and Insurance: Contractor shall secure and pay for all
permits, fees, taxes, inspections, tests, fines and other items as
required for the installation of the complete electrical systems as
outlined herein and shown on plans.
Contractor shall provide all required insurance for protection against
public liability and property damage for the duration of the work.
6.— Existing conditions: Before bidding, the contractor shall visit the job
site and ascertain all existing conditions which will affect his work.
Failure to do so will not be accepted as a reason for requesting
extra pay where the existing conditions result in extra materials or labor
Any existing conditions found by the Contractor which will adversely
affect the work shall be immediately be brought to the attention of
the Architect/Engineer. Correction of any defects shall be completely
without additional charge and shall include replacements or repair of
any other phase of the installation which may have been damaged thereby.
7.— Plans: Drawings are basically diagrams intended to depict approximately
equipment locations and arrangements, not to show every minor detail.
Plans shall not be scaled to determine exact location and dimensions.
8.— Interference: The Contractor shall coordinate his work with other
trades so that interference with existing conditions, conduits, piping,
equipment, architectural and structural members be avoided.
9.— Substitutions: Products and materials called out by trade name and/or
catalog numbers establish a standard of quality, appearance, perfor—
mance and dimension. Contractors shall base his proposal on those
items as they shall be considered as a standard basis of bidding.
Requests for substitution shall be submitted in writing to the Archi—
tect/Engineer, demonstrating that product is of comparable and basic
design, construction, standards and warranties, dimensions to fit wi—
thout change, and does not cause extra work to other trades.
Contractor shall be responsible for providing equality of substitution:
Architect/Engineer will, under no circumstances, be required to prove
such item is or is not of equal quality to the specified item. Archi—
tect/Engineer expenses incurred due to Contractor's requested revi—
sions or substitutions shall be paid by the Contractor.
10.—Record Drawings: Maintain a complete set of prints for indicating
all changes. Use colored pens to mark changes at the time of exe—
cution and deliver the set to the Architect/Engineer upon completion.
Contractor shall stamp "As Built" on prints and plans, date and sign
in ink.
11.—The Contractor shall, and hereby does, warrant all labor and material
free from defects for a period of one (1) year from the date of
acceptance or beneficial use by the owner, whichever is earlier and
shall, upon notification during this period promptly repair or replace
any defective items or material or equipment at no cost to the owner.
COPE OF WORK
1— THE SCOPE OF WORK IS A NEW OFFICE SPACE
iN EXISTING WAREHOUSE. REST OF EXISTING
WAREHOUSE AREA POWER AND LIGHTING EXISTING TO
REMAIN.
}
t'
GUIROLA & ASSOCIATES P.A.
CONSULTING ENGINEERS
David Guirola PE
P.E. No 57468
1150 NW 72nd AVE, 5-451
MIAMI, FLORIDA 33126
P,H: (305)513.96&5
CA 00009112 EMAIL: GUIRO 5@,AOL.COM
Reinafdo A. Gomez
Architect
AR# 0013736
16047 SW 68 ST
MIAMI,FLORiDA 33193
Phone: 786-261-9551
� W_
aZ
o. LU
Coll Q Q
0 J
Z
LL
h
W D _
LLo
0 z <t
W
=W �Z
O 0
�_ 3: W
J r- 1—
�0
00
ELECTRICAL
PLAN
DATE: PREPARED REVIEWED
BY: 13Y.
4/15/15 YG DG
SHEET: OF:
E-1 1
GENERAL NOTES:
1. ALL MECHANICAL SYSTEMS ARE TO BE INSTALLED IN ACCORDANCE WITH ALL
APPLICABLE SECTIONS OF THE NFPA STANDARDS, ANSI STANDARDS, THE LOCAL
BUILDING CODE, NOISE & HEIGHT ORDINANCES, PLANS AND SPECIFICATIONS.
2. ALL MATERIALS SHALL BE NEW AND ALL WORKMANSHIP AND MATERIALS SHALL BE
IN STRICT ACCORDANCE WITH APPLICABLE LOCAL CODES, PRODUCT APPROVAL,
RULES AND ORDINANCES, ANY DAMAGED EQUIPMENT SHALL BE REPLACED OR
RESTORED TO ORIGINAL CONDITION.
3. THE CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, ACCESS
PANELS, CONTROL SYSTEMS, DEVICES, PERMITS AND SERVICES NECESSARY FOR
FURNISHING AND INSTALLING A COMPLETE OPERABLE MECHANICAL SYSTEM.
4. ALL LOUVERS, GRILLES, PIPING, ETC. SHALL BE PAINTED TO MATCH
SURROUNDING COLOR AND TEXTURES AS REQUIRED BY ARCHITECT. VERIFY COLOR
AND TEXTURE WITH ARCHITECT. PAINT ALL EXPOSED MECHANICAL EQUIPMENT
WITH BENJAMIN MOORE EPDXY ENAMEL 182.
5. ALL CUTTING, PATCHING, STRUCTURAL STEEL, WEATHER PROOFING, PAINTING,
AND WALL OPENINGS SHALL BE BY THE GENERAL CONTRACTOR.
6. ALL OPENINGS IN BUILDING STRUCTURE, FOR DUCTWORK, PIPING, ETC. TO BE
1/2" LARGER (ON ALL SIDES) THEN THE OUTSIDE DIMENSIONS. FILL VOIDS
WITH FIRE RETARDANT SILICONE FOAM (I.E. CHASE -FOAM CTC PR -855 BY CHASE
TECHNOLOGY CORP.).
7. SHOP DRAWINGS: CONTRACTORS SHALL SUBMIT FOR APPROVAL, WITHIN 30 DAYS
AFTER SIGNING CONTRACT, A MINIMUM OF FIVE COPIES OF FULLY DESCRIPTIVE
LITERATURE, INCLUDING BUT NOT LIMITED TO: AIR CONDITIONING UNITS, FANS AND
AIR OUTLETS. NO WORK SHALL PROCEED WITHOUT APPROVAL OF THESE SUBMITTALS.
8. PROVIDE FLEXIBLE DUCT CONNECTORS, RATED AS REQUIRED, TO ALL FANS, A/C
UNITS, OR MECHANICAL EQUIPMENT.
9. PROVIDE MAINTENANCE AND OPERATION MANUAL ON ALL MECHANICAL EQUIPMENT
OR SYSTEMS. PROVIDE 5 SETS OF SUBMITTALS ON ALL HVAC EQUIPMENT.
SUBMITTALS SHALL HAVE A SUMMARY SHEET SHOWING ALL SCHEDULED
INFORMATION.
10. HVAC CONTRACTOR WILL WARRANTY ALL MECHANICAL SYSTEMS, DUCTWORK,
THERMOSTATS, AND ALL OTHER EQUIPMENT,PARTS AND LABOR UNDER THESE
DRAWINGS AND SPECIFICATIONS FOR A PERIOD OF ONE (1) YEAR AFTER C.O. OF
BUILDING. ANY REPAIRS REQUIRING SYSTEM SHUT DOWN WILL BE DONE DURING
NON OPERATIONAL PERIODS. HVAC CONTRACTOR SHALL COORDINATE WITH ALL
OTHER TRADES PRIOR TO BIDDING AND PURCHASING ANY EQUIPMENT.
11. AIR QUALITY SHOULD BE TESTED BEFORE OCCUPANCY AND SHOULD BE INSTRUMENTED
AND MONITORED THEREAFTER, OR AT LEAST AT REGULAR INTERVALS
12. GENERAL CONTRACTOR TO PROVIDE FINAL TEST AND BALANCE PER NEW DESIGN LAYOUT.
MECHANICAL EQUIPMENT NOTES:
1. ALL MECHANICAL EQUIPMENT SHALL BE ARI & U.L. LISTED WHERE APPLICABLE
AND RATED FOR THE REQUIRED SERVICE, PRESSURES, TEMPERATURES, AND SHALL
BE PROVIDED WITH ALL NECESSARY TRANSFORMERS, SEALS, VALVES,
CONNECTIONS, ETC. TO FUNCTION PROPERLY.
2. PROVIDE VIBRATION ISOLATORS ON ALL MECHANICAL EQUIPMENT AS CALLED FOR
IN THE SPECIFICATIONS. IF NOT SPECIFIED, AS RECOMMENDED BY
MANUFACTURER FOR QUIET OPERATION (WITH 99% ISOLATION EFFICIENCY).
3. INDEPENDENT CONTRACTOR SHALL TEST AND BALANCE ALL MECHANICAL EQUIPMENT
AIR DEVICES, EXTRACTORS, DAMPERS, AHU'S & FAN RATES, ETC. TO PROVIDE
THE DESIGN QUANTITIES AS SHOWN ON THE PLANS OR SCHEDULES. PROVIDE T&B
REPORT IN ACCORDANCE WITH THE AIR BALANCE COUNCIL STANDARDS, SIGNED
AND SEALED BY A REGISTERED FLORIDA ENGINEER. PROVIDE FINAL BALANCING
FOR ALL SYSTEMS TO SATISFACTION OF OWNER AND ENGINEER. T&B CONTRACTOR
SHALL VISIT JOB SITE DURING CONSTRUCTION TO ENSURE THAT ALL DUCTS,
DAMPERS, ETC. ARE INSTALLED FOR PROPER AND QUIET AIR. DELIVERY.
4. THERMOSTAT LOCATION SHALL BE APPROVED BY OWNER AND ENGINEER BEFORE
INSTALLATION.
5. ALL INSULATION WILL HAVE FIRE/SMOKE RATING LESS THAN 25/50.
6. FILTERS SHALL BE IN PLACE DURING CONSTRUCTION. PROVIDE A NEW SET
PRIOR TO TEST AND BALANCE AND A FINAL SET AT THE END OF ONE YEAR
SERVICE PERIOD.
AIR DISTRIBUTION Z DUCTWORK NOTES T
1. REFER TO ARCHITECTURAL PLANS FOR CEILING TYPE.
2. PROVIDE OFF WHITE FINISH (SUBJECT TO ARCHITECT'S APPROVAL).
3. AL1._ DUCTWORK WHERE ALLOWED BY LOCAL CODES AND AND CEILING RATING SHALL
BE 1" LOW PRESSURE DUCT, SEAL CLASS "C" AND AS FOLLOWS:
A. S/A & R/A - 1-1/2" THICK FIBERGLASS DUCT BOARD WITH VAPOR BARRIER (R-6 MIN.)
B. EXHAUST AIR DUCTWORK - GALVANIZED SHEETMETAL
B. OUTSIDE AIR DUCTWORK - INSULATED GALVANIZED SHEETMETAL
4. ALL DUCTWORK AND DIFFUSERS SHALL BE RATED FOR THE USE, PRESSURE AND
TEMPERATURE SPECIFIED AND AS REQUIRED BY THE CEILING SYSTEM RATING.
5. ALL DUCTWORK SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH
"SMACNA" STANDARDS AND LOCAL BUILDING CODES.
6. ALL DUCT SIZES ARE CLEAR INSIDE DIMENSIONS.
7. SEAL ALL DUCTS, JOINTS AND SEAMS IN AN APPROVED MANNER AND INSURE
AGAINST LEAKAGE.
8. PROVIDE ACCESS DOORS AS REQUIRED FOR ALL MECHANICAL EQUIPMENT TO
SERVICE AND VISUALLY CHECK ROTATION OF FANS AND MOTORS, POSITION OF
DAMPERS, REPLACE FIRE DAMPER LINKS, ADJUST OR REPLACE CONTROLS, ETC.
9. PROVIDE VANED ELBOWS IN ALL CASES, SPLITTER DAMPERS WHERE INDICATED
ON DRAWINGS AND VOLUME CONTROL DAMPERS IN ALL BRANCH DUCTS OR DIFFUSER
CONNECTIONS.
10. TERMINAL AIR DISTRIBUTION DEVICES SHALL BE AS FOLLOWS:
CEILING DIFFUSER: EQUIV. TO TITUS MODEL TDC-AA
WALL DIFFUSER: EQUIV. TO TITUS MODEL 300 FL
RETURN REGISTER: EQUIV. TO TITUS MODEL 350 FL
GENERAL NOTE:
CONTRACTOR TO COORDINATE DUCTWORK LAYOUT WITH EXISTING
ELECTRICAL CONDUITS, ETC. REROUTE EXISTING DUCTWORK AS
NESSESARY. NOTIFY OWNER, ARCHITECT AND ENGINEER OF ANY
CONFLICT WITH EXISTING CONDITIONS TO PROVIDE SOLUTIONS.
CONTRACTOR SHALL VISIT JOB SITE PRIOR TO BID. T&B CONTRACTOR
SHALL PROVIDE A FINAL TEST AND BALANCE REPORT WITHIN SCOPE
OF WORK TO PROVIDE THE DESIGNED QUANTITIES SHOWN ON PLANS.
PROVIDE T&B REPORT IN ACCORDANCE WITH THE AIR BALANCE COUNCIL
STANDARDS, SIGNED AND SEALED BY A REGISTER ENGINEER.
SEAL JOINT W
EPDXY & DUCT
TAPE
AIR FLOW
lu
INSULATE TOP OF -
ALL AIR TERMINALS
DIFFU
AIR DUCT (SEE PLAN VIEW)
SPIN TAP FITTING
AIR FLOW
METAL ROUND SCOOP FITTING
INSULATED FLEX.. DUCT
SEAL JOINT WITH EPDXY
AND DUCT TAPE
NOTE:
HANG DUCTS ACCORDING
TO SMACNA STANDARDS
FLEXIBLE DUCT CONNECTION DETAIL
N.T.S.
LEGEND
MNEW SUPPLY DIFFUSER
NEW RETURN AIR GRILLE
J MANUAL VOLUME DAMPER
O PROVIDE PROGRAMABLE T -STAT.
NEW FLEXIBLE DUCT, U.L. CLASS 1 (R-6)
NEW DUCT WITH R=4.2 INSULATION.
OUTSIDE AIR
CALCULATIONS
(AS PER
ASHRAE 62.1-2010)
APPLICATION
#OF PEOPLE
CFM/PERSON
NET FLOOR AREA
CFM/SF
O.A. CFM
O.A. PROVIDED
A/C#1
14 '`
5
580
0.06
104
125
NOTES:
4 -WAY SUPPLY
1. CALCULATIONS ARE BASED ON ESTIMATED
DESIGN OCCUPANCY RATES
PER ARCHITECTURAL PLANS AND VENTILATION RATES PER ASHRAE.
WALL CAP DETAIL
NOT TO SCALE
WALL CAP WITH
BUILT-IN DAMPER
WALL
ROOF FLOOR PLAN
SCALEi 1/8' = V-0'
NOTE:
HANG DUCTS ACCORDING
TO SMACNA STANDARDS
TYPICAL HANG
STRAP AND S
HANGING DETA
1
OF
DETAIL
SECURE WIRE
AIR DISTRIBUTION DEVICE
SCHEDULE
UNIT UNIT
SERVICE
SELECTION
AIR HANDLING
NECK
REMARK
NO.
SYSTEM DATA
BASED ON
MODEL
SIZE
A
CEILING
SUPPLY
TITUS TDC AA
WT
SEE
PLANS
4 -WAY SUPPLY
GENERAL NOTE:
ELECTRICAL
COMPRESSOR
NO NEW LOADS (CFM) WERE
ADDED TO THIS PROJECT,
ALL EXISTING LOAD WAS
REBALANCE PER NEW DESIGN LAYOUT.
REF. LINES
MECHANICAL FLOOR PLAN
SCALEi 1/8' = 1'-0'
NEW WORK KEY NOTES
O NEW HORIZONTAL AHU TO BE LOCATED ABOVE THE CEILING.
O G.C_ TO PROVIDE 0/A MOTORIZED DAMPERS IN THIS AREA
AS REQUIRED. MOTORIZED DAMPERS 120V/1/60 TO BE
INTERCONNECTED WITH (AHU) RESPECTIVELY AND SHUT
DOWN WHEN AC IS NOT OPERATING.
Q3 LOCATE NEW CAP FOR AIR INTAKE IN THIS AREA AS REQUIRED.
® LOCATE NEW CU -1 IN ROOF IN THIS AREA AS REQUIRED.
GENERAL NOTE:
EXISTING AC -1 AND AC -2 ARE BOTH 5TON UNITS
RATED 208V/1/60 60,OOOBTUH MODEL# LCMC9260SO02
BY GRENADA. BOTH A/C UNITS WILL BE REUSED AS
PART OF THIS PROJECT.
GUIROLA & ASSOCIATES P.A.
CONSULTING ENGINEERS
David Guirola PE
P.E. No 57468
451
MLAMI, FLOM AVE,126
MIAINi, FLOPoOA 33128
P.H: (305) 5139665
CA 00009112 EMAIL GUIRO 5@AOL.COM
,RAG
Reinaldo A. Gomez
Architect
AR# 0013736
16047 SW 68 ST
MIAMI,FLORIDA 33193
Phone: 786-261 9551
PEVISI)VS
W W
Q
� W
Q
a o
Z Q
Z
J
U.
w
W _
L 0 U
0 a
L W
co
W OZ
O O
W
M no
T- (j)M
SrPLIT
S"Y"STEM
S
AIR HANDLING
UNIT
AIR COOLED CONDENSING UNIT
SYSTEM DATA
MARK
MODEL
CFM
FAN
HEATER
WT
MARK
MODEL
WT
ELECTRICAL
COMPRESSOR
UNIT
MAX
CAPACITY
REF. LINES
N0.
NO.
N0.
LBS
VOLTS -PH -HZ
MCA
FUSE
SEER
TOTAL
OA
HP
KW
STEP
LBS
QTY.
TONS
TMBH
SMBN
SUCTION
I LIQUID
AHU-1
RH1T24
600
104
0.5
1/3
2.8
1
95
CU -1
13AJN18
187
208-1-60
1
1.5
14
20
23.8
17.7
13
AS PER MANUF. RECOMMND
SPLIT SYSTEM NOTES:
4. PROVIDE PROPER VIBRATION ISOLATORS AS PER ISOLATION
1. OUTSIDE AIR DESIGN CONDITIONS: 91'FDB - 79°FDB.
MANUFACTURER'S RECOMMENDATIONS.
PROVIDE FILTER RACK UNDER
2. PROVIDE A/C UNIT WITH PROGRAMMABLE HEATING AND COOLING
THERMOSTAT WITH
AHU. RETURN AIR THRU LOUVERED DOOR UNLESS OTHERWISE NOTED.
ON-OFF SWITCH SUB -BASE. (WIRED AND INSTALLED
BY ELECTRICAL
CONTRACTOR)
5. INSULATE REFRIGERANT SUCTION LINE
WITH 3/4" FIRE
3. SIZE AND RUN REFRIGERANT PIPING AS
MANUFACTURER'S
RETARDANT ARMAFLEX.
PUBLISHED RECOMMENDATIONS.
6. PROVIDE BUILT-IN DISCONNECT WITH
ALL AIR HANDLING UNITS.
MECHANICAL FLOOR PLAN
SCALEi 1/8' = 1'-0'
NEW WORK KEY NOTES
O NEW HORIZONTAL AHU TO BE LOCATED ABOVE THE CEILING.
O G.C_ TO PROVIDE 0/A MOTORIZED DAMPERS IN THIS AREA
AS REQUIRED. MOTORIZED DAMPERS 120V/1/60 TO BE
INTERCONNECTED WITH (AHU) RESPECTIVELY AND SHUT
DOWN WHEN AC IS NOT OPERATING.
Q3 LOCATE NEW CAP FOR AIR INTAKE IN THIS AREA AS REQUIRED.
® LOCATE NEW CU -1 IN ROOF IN THIS AREA AS REQUIRED.
GENERAL NOTE:
EXISTING AC -1 AND AC -2 ARE BOTH 5TON UNITS
RATED 208V/1/60 60,OOOBTUH MODEL# LCMC9260SO02
BY GRENADA. BOTH A/C UNITS WILL BE REUSED AS
PART OF THIS PROJECT.
GUIROLA & ASSOCIATES P.A.
CONSULTING ENGINEERS
David Guirola PE
P.E. No 57468
451
MLAMI, FLOM AVE,126
MIAINi, FLOPoOA 33128
P.H: (305) 5139665
CA 00009112 EMAIL GUIRO 5@AOL.COM
,RAG
Reinaldo A. Gomez
Architect
AR# 0013736
16047 SW 68 ST
MIAMI,FLORIDA 33193
Phone: 786-261 9551
PEVISI)VS
W W
Q
� W
Q
a o
Z Q
Z
J
U.
w
W _
L 0 U
0 a
L W
co
W OZ
O O
W
M no
T- (j)M
MECHANICAL
FLOOR PLAN
DATE: PREPARED I REVIEWED
BY: BY:
4/15/15 JM JM
SHEET: OF:
M-1 1
(�4
1
4
�
MECHANICAL
FLOOR PLAN
DATE: PREPARED I REVIEWED
BY: BY:
4/15/15 JM JM
SHEET: OF:
M-1 1