DRAWINGSGENERAL ELECTRICAL NOTES - ALL ELECTRICAL WORK PERFORMED UNDER THIS CONTRACT SHALL COMPLY WITH THE NATIONAL ELECTRICAL CODE (NEC) 2008, LOCAL CODES AND ORDINANCES (INCLUDING THE 2010 FLORIDA BUILDING CODE (F.B.C.) WITH LATEST SUPPLEMENTS & AMENDMENTS), AND ALL STANDARDS OF CONSTRUCTION ESTABLISHED BY THE LANDLORD. - PRIOR TO BID, THE CONTRACTOR SHALL VISIT THE JOB SITE AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS. NOTIFY THE ARCHITECT OR ENGINEER OF ANY DISCREPANCIES. THE CONTRACTOR SHALL QUALIFY THE BID ACCORDINGLY. - SUBMIT SHOP DRAWINGS FOR ACCEPTANCE BY THE ARCHITECT AND/OR ENGINEER BEFORE PROCEEDING WITH THE PURCHASE OR INSTALLATION OF THE EQUIPMENT AND MATERIALS. NO FACSIMILES OR FACSIMILE COPIES SHALL BE ACCEPTED. - ALL CONDUCTORS SHALL BE THWN OR THHN COPPER. - ALL OPEN WIRING ABOVE A SUSPENDED CEILING SYSTEM USED AS A RETURN AIR PLENUM SHALL BE RATED FOR USE IN A RETURN AIR PLENUM. ALL CABLING SHALL COMPLY WITH N.F.P.A. STANDARDS. - ALL EXPOSED CONDUITS SHALL BE RUN AS NEAT AS POSSIBLE. P.V.C. CONDUIT SHALL ONLY BE USED IN SLAB OR UNDERGROUND AT A MINIMUM DEPTH OF 24 INCHES.. - ALL UNDERGROUND CONDUIT INSTALLATIONS SHALL COMPLY WITH NEC SECTION 300.5. - ALL UNDERGROUND CONDUITS SHALL BE CONVERTED TO E.M.T. CONDUIT ABOVE SLAB LEVEL, ALL UNDERGROUND ELBOWS SHALL BE R.G.S. CONDUIT. - PROVIDE PULL STRINGS IN ALL EMPTY CONDUITS. - ALLOW NO MORE THAN THE EQUIVALENT OF FOUR QUARTER BENDS (360 DEGREES TOTAL) BETWEEN ALL PULL POINTS, E.G., CONDUIT BODIES AND BOXES AS PER NEC 344.26. - ALL DEDICATED OUTLETS SERVING EQUIPMENT SUCH AS REFRIGERATORS, WATER COOLERS, COPIERS, FAXES, ETC. SHALL HAVE SEPARATE NEUTRAL CONDUCTORS TO EACH DEVICE OR APPLIANCE. - FLEXIBLE CONDUIT SHALL BE USED FOR CONNECTION TO ALL VIBRATING EQUIPMENT SUCH AS MOTORS, ETC. - ALL WIRING DEVICES SHALL BE LEVITON COMMERCIAL GRADE (WHITE DECORA) OR EQUAL AS APPROVED BY ARCHITECT OR ENGINEER. - ALL RECEPTACLES SHALL BE INSTALLED= AT 18" A.F.F. UNLESS OTHERWISE NOTED. - MAINTAIN FIRE RATING IN ALL PENETRATIONS THRU DEMISING AND FIRE RATED WALLS. THIS INCLUDES MAINTAINING A MINIMUM 24" SEPARATION BETWEEN ELECTRICAL DEVICES MOUNTED ON OPPOSITE SIDES OF ALL FIRE RATED PARTITIONS AND WALLS. - ELECTRICAL POWER AND CONTROL WIRING FOR H.V.A.C. AND MECHANICAL EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. - ELECTRICAL CONTRACTOR SHALL VERIFY THE CEILING FINISHES AND SUSPENSION SYSTEMS FOR SELECTION OF THE PROPER TRIM AND SUPPORT ARRANGEMENTS OF ALL ELECTRICAL DEVICES. - PROVIDE ACCESS PANELS AS REQUIRED TO SERVICE ALL ELECTRICAL EQUIPMENT ABOVE HARD CEILINGS. COORDINATE WITH ARCHITECT BEFORE ROUGH INSTALLATION. - ELECTRICAL CONTRACTOR SHALL COORDINATE WORK WITH THE ARCHITECTURAL PLANS BEFORE ROUGH INSTALLATION OF LIGHTS, RECEPTACLES, SWITCHES, AND EQUIPMEG+J.T E 1R EXACT LOCATION. - ELECTRICAL CONTRACTOR SHALL vVERIFY EXACT LOCATION OF ALL EQUIPMENT WITH TENANT PRIOR TO ROUGH INSTALLATION. - ELECTRICAL CONTRACTOR '-SHALL COORDINATE LOCATIONS OF ALL ELECTRICAL WIRING DEVICES (INCLUDING LUMINAIRES, RECEPTACLES, SWITCHES, CONDUITS, WIRING, ETC.) WITH OTHER TRADES TO AVOID CONFLICTS. - ALL ELECTRICAL EQUIPMENT SHALL BE APPROVED AS SAFE FOR USE IN THE U.S. WORKPLACE FOR THE INTENDED APPLICATION, AS DETERMINED BY AN ORGANIZATION CURRENTLY RECOGNIZED BY OSHA (OCCUPATIONAL SAFETY AND HEALTH) AS A NRTL (NATIONALLY RECOGNIZED TEST LABORATORY). (E.G. - UL, CSA, ETC.) - PROVIDE EXPANSION JOINTS WHERE REQUIRED AS PER NEC 300.7(8). - M.C. CABLE SHALL NOT BE USED IN ANY PORTION OF THE INSTALLATION UNLESS PRIOR WRITTEN CONSENT IS OBTAINED FROM THE OWNER, ARCHITECT AND ENGINEER. - AS PER F.B.C. 13-413.ABC.1.1, FEEDER CONDUCTORS SHALL BE SIZED FOR A MAXIMUM VOLTAGE DROP OF,2 PERCENT AT DESIGN LOAD REGARDLESS OF SIZES SHOWN ON PLANS OR PANEL SCHEDULES. - ALL BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED IN ACCORDANCE WITH N.E.C. 210.19 AND FOR A MAXIMUM VOLTAGE DROP OF 3 PERCENT AT DESIGN LOAD AS PER F.B.C. 13-413.ABC.1.2 REGARDLESS OF SIZES SHOWN ON PLANS OR PANEL SCHEDULES. - AS PER F.B.C. 13-413.ABC.2.1, WITHIN 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED BY THE.GENERAL CONTRACTOR TO THE BUILDING OWNER, INCLUDING: 1. A SINGLE -LINE DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND 2. FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL DISTRIBUTION. -- AS PER F.B.C. 13-413.ABC.2.2, THE GENERAL CONTRACTOR SHALL PROVIDE AN OPERATING MANUAL AND MAINTENANCE MANUAL TO THE BUILDING OWNER. THE MANUALS SHALL INCLUDE, AT A MINIMUM, THE FOLLOWING: 1. SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE. 2. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED. 3. NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED SERVICE AGENCY. - IF ANY CONFLICT IS ENCOUNTERED WITHIN THE DESIGN DOCUMENTS, REGARDLESS OF TRADE OR RESPONSIBILITY, THE GREATER SCOPE OF WORK SHALL PREVAIL. - CONTRACTOR SHALL WARRANT ALL WORK TO BE FREE OF DEFECT IN WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER ACCEPTANCE OF THE PROJECT. SCOPE OF WORK THE PURPOSE OF THE PROJECT IS TO UPGRADE THE EXISTING 120/208V 50 AMP CIRCUIT BREAKER PANEL FMC, TO A NEW MAIN LUG ONLY, CIRCUIT BREAKER PANEL TO A 100 AMP OR GREATER BUSS BREAKER PANEL. WITH A 80 AMP FEEDER CIRCUIT. SEE RISER FOR FURTHER DETAILS. CONGRESS AVENUE OVER ALL PLAN N.T.S. P I REVIEWED BY DATE' Structural Electrical. Plum Ing Mechanical LiJ Q P&Z Forester z Fire n, 0 Police V J '"' Other _j Lj��/ Processed by: > All work invoiced on this permit shall conform with all City of Boynton Beach Building Codes Complete Power Systems, LLC 230 N. Esplanade Drive Miami Springs, FL 33166 Michael P. Ashford. Qualifier �J EC#13005707 17 Complete Power Systems, LLC 23o N. Esplanade Dr., Miami Springs F133166 Michael P. Ashford Qualifier EC#: 13005707 * * MY COMMISSION # EE 136608 EXPIRES: October 6i, 2015 B=W,Thru 84d No" Services COMPLETE 1 w1 SYSTEMS LLC. EC# 13005707 MI r IMICHAEL ASHFORD 230 N. ESPLANADE DR MIAMI SPRINGS FLORIDA, 33166 SIGNATURE NOTARY REV I DATE �rrrrr.rr� DRAWN BY: MA CHECKED BY: SCALE: AS NOTED DATE: 05-06--14 PROJECT No. DRAWING No, E of ry LiJ Q n z ( l n, 0 V J '"' V 1 _j Lj��/ l-1- > 7 Q LL 0 LIJ n Z 0 (T U ry 0 T M I-- LLI L L„ I X ry 0 0 M (�� V J 0 0 M (( ll �.�,/ ry U REV I DATE �rrrrr.rr� DRAWN BY: MA CHECKED BY: SCALE: AS NOTED DATE: 05-06--14 PROJECT No. DRAWING No, E of ELECTRICAL FEEDER SCHEDULE 0 NEW 4--#3 & 1-#8 OND THWN CU WIRE IN EXISTING 1.25" C THE WIRE HAS BEEN INCREASED BY ONE SIZE FOR VOLTAGE DROP EQUIPMENT YARD OPTIONAL E3Pj3O0A] STAND BY TGENERATOR I I •-80 kW, 120/248V, 3PHS, 4 W I GENERATOR SHALL BE IN INSTALLED I AS A NON -SEPARATELY DERIVED I GROUNDING SYSTEM, I -559 GALLON SUB -BASE DUAL WALL DIESEL TANK I PROVIDE PLACARD ON GENERATOR I I AS PER N.E.C. 225--37 AND 702-8(a)(b) N.O TE S TO FPL VAULT/MAT NEW 80 AMP MINIMUM SQUARE D PANEL BOARD TO REPLACE EXISTING 50 AMP PANEL BOARD PROVIDE AND INSTALL NEW 80 AMP 3 POLE MAIN BREAKER AND REUSE ALL EXISTING BRANCH CIRCUIT BREAKERS MAIN ELECTRIC ROOM MAIN ELECTRIC ROOM WEST WALL I NORTH WA MAIN ELECTRIC ROOM ALL SWITCHGEAR, BOXES, DEVICES, CONDUIT AND WIRE INDICATED ON THIS PLAN BY A DASHED LINE ARE EXISTING TO REMAIN. ALL DOTTED LINES INDICATE EXISTING EQUIPMENT TO BE REMOVED OR REPLACED. ALL SWITCHGEAR, BOXES, DEVICES, CONDUIT AND WIRE INDICATED ON THIS PLAN BY A SOLID LINE ARE NEW. LL II MAIN ELECTRIC ROOM EAST WALL SOUTH WALL :z]EXISTING XISTING EXISTING PANEL EXISTING DIA.T.S. " `�.S.S "MDS" ( x MAIN Sc.c. I 400A G I EXISTING PANEL EXISTING PANEL EXISTING PANEL EXISTING PANEL EXISTING PANEL I MAIN 5 I 5 OF 5 I I 120/208V I L�� """ .EM" I I� � I� � I (-4RP1A" � I 4 I --- 11 I I I III I( 3 3,0500 IL 120/208V� I I TM.C.B. I I I I� � GENERI AO 150A AVI M.C.B. ANNUCATOR 120/ 8V (120/208 350A _ E 120/208V (A)-(A)- (A)- (A)- (A)- )()()()()().A-A- (C)- (A)•- AL (VIAL 20.1 KVA 76,2 KVA - TOTAL CONNECTED LOAD 76.2 KVA / 208 X �T = 211.6 AMPS (**)- WIRING WILL BE INTEGRAL TO THE NEW T.V.S.S. (***)-THE BUSS OF THIS PANEL HAS BEEN TAPPED FOR AN EXISTING 150A DISCONNECT (****)-THIS RTU IS BE DOWNSIZED FROM 25.92 kVA TO 12.60 kVA BY OTHERS UNDER A SEPARATED PERMIT MAKING FOR A 13.32 kVA (37.0 AMPS) ADDITIONAL SPARE CAPACITY (A) -EXISTING CKT TO REMAIN. (B) -EXISTING CKT & BREAKER TO BE REUSED, PROVIDE NEW BRANCH CONDUIT & WIRE. (C) -NEW CIRCUIT FROM EXISTING PANEL. PROVIDE NEW BREAKER AND WIRE, .(A) (A) (A) -(****) UPS ROOM NORTH WALL EXISTING PANEL 30 KW UPS MAINTENANCE "UPS" IYCABINET I BYPASS PANEL BATTERI I MOA I T' 120/208VS 120/206V NEW ELECTRICAL RISER PANEL FMC TYPE SEE RISER NOTES MAINS : M.L.O. (NEW TO REPLACE EXISTING) MNT : FLUSH a BUS 100A (MINIMUM) 0 LOC TENANT SPACE n < VOLTS 120/208, 3PHS, 4W _n 0 FEEDER SEE RISER V 1 LLJ A.I.C. 10,000 > CKT POLE KVA bESCRIPTION WIRE, C CKT POLE KVA DESCRIPTION WIRE, C 1 1/20 00.90 RECPS. EXISTING 2 1 /20 00.72 RECPS. EXISTING 3 1/20 00.72 RECPS. EXISTING 4 1 /20 p0.50 RECPS. Z EXISTING 5 1/20 00.50 RECPS, EXISTING 6 1/20 00.72 RECPS, EXISTING 7 1/20 00,72 RECPS. EXISTING 8 1/20 00.50 1 RECPS. 0 EXISTING 9 1/20 00.50 RECPS. EXISTING 10 1/20 00.72 RECPS, EXISTING 11 1/20 00.72 RECPS. EXISTING 12 1 1/20 00.72 RECPS. EXISTING 13 1/20 00.72 1 RECPS. EXISTING 14 1/20 00.50 RECPS, EXISTING 15 1 1/20 00.50 RECPS. EXISTING16 1/20 00.72 RECPS. EXISTING 17 1/20 00.72 RECPS. EXISTING 18 1/20 00.50 RECPS. EXISTING 19 1 1/20 00,50 RECPS. EXISTING 1 20 1/20 00.50 RECPS. EXISTING 21 1/20 00,50 RECPS. EXISTING 122 1/20 00.50 RECPS, EXISTING 23 1/20 00.50 RECPS. EXISTING 24 1/20 02.40 RECPS, EXISTING 25 2/30 02.40 UPS EXISTING 26 00.84 FUTURE 27 28 00.84 FUTURE 29 1 00.84 FUTURE 30 00.86 FUTURE TOTAL 10.74 KVA 21.60 KVA / 208 X �_3 - 60 TOTAL 10.86 KVA 21.60 KVA - TOTAL CONNECTED LOAD AMPS z1z zr� Complete Power Systems, LLC 230 N. Esplanade Drive Miami Springs, FL 33166 Michael P. Ashford, Qualifier EC#13005707 14A"Y Complete Power Systems, LLC 23o N. Esplanade Dr., Miami Springs F133166 Michael P. Ashford Qualifier EC#:13005707 TIFFANY K ORTEGA * * MY COMMISSION 0 EE 136608 EXPIRES: October 6 2015 ��9TFOF F10�\OP Bended Tin Budget Notary services COMPLETE (POWER srsrEMs LLC. EC# 13005707 QUALIFIER (MICHAEL ASHFORD 230 N. ESPLANADE DR MIAMI SPRINGS FLORIDA, 33166 SIGNATURE •'C 1 REV I DATE DRAWN BY: MA CHECKED BY: SCALE: AS NOTED DATE: 05-06--14 PROJECT No. DRAWING No. E 2 of Ai 2 a LLJ 0 n < _n 0 M0 V 1 LLJ LLJ L1 > <C 0 LL LII ULJ LLJ Li IIj Lj Lj D Z X Lr0o V) O 0 U REV I DATE DRAWN BY: MA CHECKED BY: SCALE: AS NOTED DATE: 05-06--14 PROJECT No. DRAWING No. E 2 of Ai 2