DRAWINGSGENERAL NOTES
1) The fire alarm system is U.L. Listed as POWER LIMITED &
of the general alarm type per NEPA 72, 2002 edition.
All equipment is compatible and Listed for its intended use.
2) The fire alarm panel is provided with standby battery
per NFPA 72 4.4.1.5.3.1 with 24 hours standby and 5 minutes
alarm. Should loss of normal 120VAC operating power occur,
the fire alarm panel will automatically transfer to the
standby battery.
3) A break in any field wiring or grounding of any
conductor will result in the activation of the fire alarm
panel trouble buzzer, which can be silenced by operating
the "Trouble Silence" button on the fire alarm panel.
4) Pull stations to be mounted at 48" AFF per the ADA code.
5) Ceiling mounted smoke detectors shall not be located in
a direct airflow, nor closer than 3 feet from an air
supply diffuser. NFPA 72 A.5.7.4.1 (2002) I
6) Power up and power down of the fire alarm panel must
be done in the proper sequence:
Power Down: Disconnect battery and then turn
off the AC power at the breaker.
Power Up: Turn on the AC power at the breaker
and then connect the battery.
NOTE: Do NOT disconnect the AC power feed from
the terminal block to disconnect power.
7) The 120VAC power feed for the fire panel and booster
power supplies must be from a dedicated emergency
panel breaker, and the breaker must be identified
as "FIRE ALARM CIRCUIT".
8) The control (relay) module for AHU shutdown shall be
located within three (3) feet of the device being
controlled. NEPA 101 A-7-6.5.5 (2003) The control module
shall be located such that the front mounted LED is
visible upon entry into mechanical room. The relay
contacts have a MAXIMUM capability of 1.0 amps @ 24v
and 0.3 amps @ 120VAC. Contractor must verify that the
shutdown circuit does NOT exceed these maximum current
ratings.
9) The installing contractor shall set the device address
as identified on the installation wiring disgrams
10) Wall Mounted Horns and strobes to be at 80" to bottom
or 6" from ceiling which ever is lower.
11) Notification Appliance Circuit will be "Class B - Style Y"
12) Signaling line circuits (SLC) Circuit will be "Class B - Style 4"
13) ALL DEVICES ARE COMPATIBLE
14) All duct detectors will send -a supervisory
signal to fire alarm panel.
15) Conduit shall not exceed 40% of conduit capacity.
16) Maximum number devices of slc circuit is 198 devices
17) The design installation complies with FBC 11-4.28.3
18) All audible devices shall be 3 PULSE temporal.
19) All strobe light shall be synchronized.
AREA OF "NORK
SITE KEY
TOTAL CIRCUIT AMP DRAW `lr\uu" '
Psi 0
DEVICE
DEVICE COUNT
DEVICE AMP DRAW
TOTAL DEVICE AMP
DRAW
MAX AMP 2.5
P2R 75CD
1
.157
0.157
ALARM
SR 75CD
4
.158
0.474
1#12 AWG THHN WIRE FOR GROUND CONNECTION
GREEN
GREEN
CURRENT
2#12 AWG THHN WIRE FOR POWER SUPPLY AND
AND PANEL TO 120 VOLT POWER
TOTAL CIRCUIT DRAW
��
STANDBY
CURRENT
WWW.FIRECONTROLSMET
TOTAL 0.6311
DEVICE LEGEND
NOTIFIER NBGX-12LX PULL STATION
NOTIFIER FSP -851 PHOTO SMOKE SENSOR
NOTIFIER FSD-751 DUCT HOUSING
SYSTEM SENSOR (P2R) MULTI -CANDELA HORN/STROBE
SYSTEM SENSOR (SR) 1 MULTI -CANDELA SERIES STROBE
FU SYSTEM SENSOR (RTS151) REMOTE TEST STATION MTD. 0 48" A.F.F.
= FCI GFPS-9 REMOTE POWER BOOSTER
D90;O ; F o
\i ;
N
RTI
M03
ER
D91
O_
N F
10
n.
FIRE DEPARTMENT NOTICE:
BOYNTON BEACH CITY ORDINANCE
CH. 9 FIRE PROTECTION AND PREVENTION
SEC. 9-33 DUCT DETECTOR ANNUNCIATION
(b) UNLESS PART OF AN ENGINEERED SMOKE
CONTROL SYSTEM, ALL HVAC SYSTEMS
IN A FIRE AREA SHALL SHUT DOWN WHEN
ANY DUCT DETECTOR ACTIVATES.
PENETRATIONS AND DOORS
Pentrations through rated walls and doors
in rated walls shall be protected using
materials that will maintain the fire rating of
the wall. Doors in rated walls shall be
rated for that wall. This includes frames,
door closers and hardware. A label from a
recognized door testing agency shall be
afixed to the hing side of the door, confirming
its rating. Pipe penetration material shall have
its data available for inspection also.
TOTAL CIRCUIT AMP DRAW ` INUU1 I ht L
Psi 0
DEVICE
DEVICE COUNT
DEVICE AMP DRAW
TOTAL DEVICE AMP
DRAW
MAX AMP 2.5
P21? 75CD
2
.157
0.314
ALARM
SR 75CD
3
.158
0.474
1#12 AWG THHN WIRE FOR GROUND CONNECTION
GREEN
GREEN
CURRENT
2#12 AWG THHN WIRE FOR POWER SUPPLY AND
AND PANEL TO 120 VOLT POWER
TOTAL CIRCUIT DRAW
TOTAL 0,788
AMPS PER OUTPUT CIRCUIT 3.0 9.0
AMPS TOTAL
A
16-2 FPL WIRE FOR HORNS AND STROBES
DESCRIPTION
STANDBY
B
QTY
RED
TOTAL
ALARM
18-2 FPL 24V POWER PANEL TRIP
QTY
ORANGE
TOTAL
1#12 AWG THHN WIRE FOR GROUND CONNECTION
GREEN
GREEN
CURRENT
2#12 AWG THHN WIRE FOR POWER SUPPLY AND
AND PANEL TO 120 VOLT POWER
13 4
��
STANDBY
CURRENT
WWW.FIRECONTROLSMET
CM
ALARM
is
Intertek
PER UNIT
PER UNIT
CURRENT
PER UNIT
PER UNIT
WIRELESS 0 L
CURRENT
CURRENT
Inc. are altered in any manner by owner,
(AMPS)
Office j,
(AMPS)
Womens
PER ITEM
(AMPS)
ITEM
(AMPS)
f
i (AMPS)
or in part, related to the project and
(AMPS)
that the owner and its agents indemnify
and holds harmless Fire Controls Inc. for
any and all acts related to the project.
(AMPS)
This concept drawings are for information
(AMPS)
Contractor shall field verify all
1
F.C.1 GFPS-9 POWER SUPPLY
0.075
X
1
=
0.075
-0.175
X
1
=
0.175
X
1
2
CIRCUIT #1
0.0
X
1
=
0.0
0.631
X
1
=
0.631
X
2
3
CIRCUIT #2
0.0
X
1
=
0.0
0.788
X
1
=
0.788
X
7
4
CIRCUIT #3
0.0
X
1
=
0.0
0.0
X
1
=
0.0
X
28
5
CIRCUIT #4
0.0
X
1
=
0.0
0.0
X
1
=
0.0
X
2
=
TOTAL SYSTEM
TOTAL SYSTEM
6
SYS SENSOR (RTS151) TEST STATION
0.0
X
STANDBY CURRENT (AMPS)
0'075
ALARM CURRENT (AMPS)
1.594
X
REQUIRED OPERATING TIME OF SECONDARY POWER SOURCE FROM NFPA 72 4.4.1.5.3.1
STANDBY: 24 HOURS ALARM: 5 MINUTES X 1/60 = .083 HOURS
REQUIRED TOTAL SYSTEM
i -�
REQUIRED
REQUIRED
EXISTING CIRCUIT #1
TOTAL SYSTEM
X
REQUIRED
=
STANDBY STANDBY
0.892
STANDBY
ALARM
=
ALARM
ALARM
8
TIME CURRENT
0.0
CAPACITY
TIME
=
CURRENT
1.292
CAPACITY
1
(HOURS) (AMPS)
1.292
(AMP -HOURS)
(HOURS)HO(AMPS)
9
EXISTING CIRCUIT #3
0.0
(AMP -URS)
1
24 X 0.075
=
1.8
.083
1 X
1.594
=
0.1324
-
REQUIRED
EXISTING CIRCUIT #4
REQUIRED
X
REQUIRED
=
DERATING
0.95
MINIMUM MINIMUM
STANDBY
=
ALARM
h all
AMPERE HOUR
.o
FACTOR @
TOTAL SYSTEM
AMP -HOUR 7 AHR
CAPACITY
REVISION:
CAPACITY
REVISION:
BATTERY
REVISION:
1.2
°'1904
BATTERY BATTERY
(AMP -HOURS)
(AMP -HOURS)
STANDBY. 24 HOURS ALARM: 5 MINUTES X 1/60 = .083 HOURS
SHEET NO.
REQUIRED
FA1 OF 1
TOTAL SYSTEM
REQUIRED WILL BE
REQUIRED
REQUIRED
TOTAL SYSTEM
REQUIRED
PROVIDED
STANDBY
STANDBY
ALARM
1.9324
X
1.2
=
2.4
FIRE ALARM BATTERY CALCULATIONS
-
PSI 2
NEW F.C.I. GFPS-9 POWER SUPPLY
CAPACITY
r = XI INN" D EVIICi� �
i I NOTIFIER AFP -200
1 20VJ
NO , .= AF -P-200
EXISTING
CP1
12-2-1 12-2-2
A 75cd 75cd
°QUI ami
N N
12-2-3 12-2-4 12-2-5
75cd 75cd 75cd
�nl,()( E 0 L
N N N
ELECTRIC, 190M. TIOht
RE q poRED:
Uffi)E
ROURD
STEEL ElhD8 6
t T,, Q.. . Y
alwo,
Y
NEW CIRCUIT #2
12-1-1 12-1-2 12-1-3 12-1-4
A 75cd 75cd 75cd 75cd
`' ;c: 1,w- EOL EXISTING CIRCUIT #1
E E E E
PS 12
F.C.I
D GFPS-9 POWER SUPPLY
NEW
":'"n" KELLY FALLICA
Notary Public - State of Florida
my Comm. Expires Jan 31, 2016
';9 F Commission # EE 165129
JOB COST UND
GREGORY LA
EF20000663
SWORN TO AND SUBSCRIBED BEFORE
cont Is Inc. ME ON THIS OF ' . = 2014
BY GREGORY LANE WHO N PERSONALLY
KNOWNTO,
OTARY
WIRE LEGEND
SYMBOL WIRE TYPE AND DESCRIPTION LABELED WARE COLOR
COLOR
A
16-2 FPL WIRE FOR HORNS AND STROBES
BROWN
BROWN
B
18-2 WIRE FPL FOR DATA COMMUNICATION
RED
RED
C
18-2 FPL 24V POWER PANEL TRIP
ll"dG_
ORANGE
D
1#12 AWG THHN WIRE FOR GROUND CONNECTION
GREEN
GREEN
E
2#12 AWG THHN WIRE FOR POWER SUPPLY AND
AND PANEL TO 120 VOLT POWER
13 4
��
NOTE: WIRE COLORS ARE FOR RISER REFERENCE ONLY,
AND DO NOT REFLECT ACTUAL FIELD COLORS.
f
r a fes.
f �!
H PS12
o " D91
/ @ f
i \��
N Pil l !
f ,r
%N f
fi>> Office
i
� � f
r Office
f i
r! t F
r t
,� f<
3 f��
l
f` f
.` 12-2-5
ER 75cd
F
I, G? EOLf
f
ER
M03� ,-
ptf
ITEM
DESCRIPTION
STANDBY
QTY
TOTAL
ALARM
%pontrols Inc
QTY
Trusted Brands/ Onnovative Solutions
TOTAL
2721 NW 19TH STREET
POMPANO BEACH, FLORIDA 33069
CURRENT
LIC 9 EF 20000663
STANDBY
CURRENT
WWW.FIRECONTROLSMET
CM
ALARM
is
Intertek
PER UNIT
CURRENT
PER UNIT
WIRELESS 0 L
If any document prepared by Fire Control
CURRENT
Inc. are altered in any manner by owner,
its agents or by any third party if
Office j,
(AMPS)
Womens
Mens
PER
ITEM
(AMPS)
f
or in part, related to the project and
(AMPS)
that the owner and its agents indemnify
and holds harmless Fire Controls Inc. for
any and all acts related to the project.
This concept drawings are for information
(AMPS)
Contractor shall field verify all
information contained on these drawings
and is responsible for design and
1
NOTIFIER (AFP -200) ANALOG FIRE PANEL
.185
X
1
=
0.185
.236
X
1
=
0.236
applicable N.F.P.A. codes in effect at the
2
NOTIFIER (FSP -851) PHOTO SMOKE SENSOR
.00025
X
2
=
0.00050
.00025
X
2
=
0.00050
O
3
NOTIFIER (FSD-751) DUCT HOUSING
.000375
X
7
=
0.00263
.000375
X
7
=
0.00263
CZm
4
NOTIFIER NBGX-12LX PULL STATION
.000375
X
28
=
0.0105
.000375
X
28
=
0.0105
O CZ d- m
5
NOTIFIER MMX -101 MONITOR MODULE
.000375
X
2
=
0.00075
.000375
X
2
=
0.00075
6
SYS SENSOR (RTS151) TEST STATION
0.0
X
2
-
0.0
0.012
X
2
=
0.024
i -�
7
EXISTING CIRCUIT #1
0.0
X
1
=
0.0
0.892
X
1
=
0.892
8
EXISTING CIRCUIT #2
0.0
X
1
=
0.0
1.292
X
1
=
1.292
9
EXISTING CIRCUIT #3
0.0
X
1
=
0.0
1.449
X
1
=
1.449
Other
-
10
EXISTING CIRCUIT #4
0.0
X
1
=
0.0
0.95
X
}
=
0.95
h all
DRA tY or o
.o
TOTAL SYSTEM
G.o
TOTAL SYSTEM
REVISION:
REVISION:
REVISION:
STANDBY CURRENT (AMPS)
°'1904
ALARM CURRENT (AMPS)
4.85s
REQUIRED OPERATING TIME OF SECONDARY POWER SOURCE FROM NFPA 72 4.4.1.5.3.1
STANDBY. 24 HOURS ALARM: 5 MINUTES X 1/60 = .083 HOURS
SHEET NO.
REQUIRED
FA1 OF 1
TOTAL SYSTEM
REQUIRED
REQUIRED
TOTAL SYSTEM
REQUIRED
STANDBY
STANDBY
STANDBY
ALARM
ALARM
ALARM
TIME
CURRENT
CAPACITY
TIME
CURRENT
CAPACITY
(HOURS)
(AMPS)
(AMP -HOURS)
(HOURS)
(AMPS)
(AMP -HOURS)
24
X
0.1994
=
4.786
.083
X
4.858
=
0.4032
REQUIRED
REQUIRED
REQUIRED
DERATING
MINIMUM MINIMUM
STANDBY
ALARM
AMPERE HOUR
FACTOR @
AMP -HOUR 7 AHR
CAPACITY
CAPACITY
BATTERY
1.2
BATTERY BATTERY
(AMP -HOURS)
(AMP -HOURS)
REQUIRED WILL BE
PROVIDED
4.786
+
0.,
=.1
5.1892
X 1
1.2
=
6.228
EIRE ALARM BATTERY CALCULATIONS
CP1
EXISTING NOTIFIER AEP -200 EIRE PANEL
f
r a fes.
f �!
H PS12
o " D91
/ @ f
i \��
N Pil l !
f ,r
%N f
fi>> Office
i
� � f
r Office
f i
r! t F
r t
,� f<
3 f��
l
f` f
.` 12-2-5
ER 75cd
F
I, G? EOLf
f
ER
M03� ,-
ptf
f�
F777
%pontrols Inc
Trusted Brands/ Onnovative Solutions
2721 NW 19TH STREET
POMPANO BEACH, FLORIDA 33069
(954)958®9111 (954)958®9933 FAX
LIC 9 EF 20000663
z ,
WWW.FIRECONTROLSMET
CM
is
Intertek
WIRELESS 0 L
If any document prepared by Fire Control
f
Inc. are altered in any manner by owner,
its agents or by any third party if
Office j,
construction is not in accordance with
Womens
Mens
/f
Controls Inc. then it is understood that
f
or in part, related to the project and
,
that the owner and its agents indemnify
and holds harmless Fire Controls Inc. for
any and all acts related to the project.
This concept drawings are for information
only to potential system arrangement.
N jl 75cd f', ��\ N f
12-2-1 12-2-3
` 12-2-2 75cd B r
f
Office ✓ ' 75�d
N E
I
D90
�G
12-2-4 °C
ER Open Area 75cd ,N
Office Office Office
FIR 't" A LA 7? M FL 0 0 OR P LA N
1::8 NORTH
f�
F777
%pontrols Inc
Trusted Brands/ Onnovative Solutions
2721 NW 19TH STREET
POMPANO BEACH, FLORIDA 33069
(954)958®9111 (954)958®9933 FAX
LIC 9 EF 20000663
ETL 1 0101197ATL-001
WWW.FIRECONTROLSMET
CM
is
Intertek
WIRELESS 0 L
If any document prepared by Fire Control
Inc. are altered in any manner by owner,
its agents or by any third party if
construction is not in accordance with
unaltered documents prepared by Fire
Controls Inc. then it is understood that
Fire Controls Inc. has no liability in whole
or in part, related to the project and
that the owner and its agents indemnify
and holds harmless Fire Controls Inc. for
any and all acts related to the project.
This concept drawings are for information
only to potential system arrangement.
Contractor shall field verify all
information contained on these drawings
and is responsible for design and
installation of the system in accordance
with the specs.
To the best of our knowledge the
drawings and specifications submitted
herewith, comply with existing
interpretations and previsions of the
applicable N.F.P.A. codes in effect at the
date shown below. No warranty express
or implied is hereby given.
DATE: 09/22/2014
SCALE: AS NOTED
W
O
-1--i
Z3
T
V J! d'
�m M
CZm
>M
C_ U
��41
E a)
CZCZ
O CZ d- m
L � T
' > CU ' O
C;CZ
O
LU(DTM�O/'�
T �r■
CZ
^C
W
I
LICENSED ENGINEER.
i -�
REVIEWED BY DAT
Structural
Electrical
Plumbing
Mechanical
P&Z
Forester
Fire
�j
!
Police
Other
-
Processed
by:
II conform
h all
DRA tY or o
.o
G. L.
G.o
REVISION:
REVISION:
REVISION:
SHEET TITLE
Fire Alarm Floor Plan
Notes, Riser & Calc's
SHEET NO.
FA1 OF 1