DRAWINGSNOTE:
ARMOVERS GREATER THAN 24"
IN LENGTH SHALL BE
SUPPORTED BY A HANGER
REMOVE EX. HEAD AND/OR
BUSHING. INSTALL NEW NEW I" ELL
I" x 0'-2" NIPPLE
NEW i" ARMOVER
EXISTING BRANCH LINE
NEW I" ELL
EXISTING I" OUTLET
NEW I" x y" R.C.
NEW FIRE SPRINKLER HEAD
(SEE LEGEND FOR TYPE) NEW CEILING
(SEE PLAN)
TYPICAL ARMOVER DETAIL
ILLS
STEEL BAR JOIST
ALL—THREAD ROD SIZES
FOR PIPE UP TO 4"
3/8" ROD TO BE USED
FIRE SPRINKLER PIPE
(SEE PLAN FOR SIZE)
%" TOP BEAM CLAMP
%" ALL -THREAD ROD
(LENGTHS VARY)
SWIVEL HANGER RING
(SEE PLAN FOR SIZE)
TYPICAL HANGER DETAIL
NA&
TYPICAL HANGER LOCATION DETAIL
PIPE SIZE
A
B*
C
1"
3'-0" MAX.
12'-0" MAX.
3" MIN.
1 1/4"
4'-0" MAX.
12'-0" MAX.
3" MIN.
1 1/2" - 8"
5'-0" MAX.
15'-0" MAX.
3" MIN.
14"
4'-6" TO LESS THAN 5'-0"
HANGER RING
AB4HEAD
11 L STEEL PIPE
a- FIRE SPRINKLE
* MAXIMUM HANGER SPACING FOR THREADED LIGHTWALL
STEEL PIPE IS 12'-0" FOR ALL PIPE SIZES
GENERAL NOTES:
I. ALL NEW FIRE SPRINKLERS TO BE INSTALLED PER N.F.P.A #13 (2010).
2. ALL NEW FIRE SPRINKLERS TO BE AS INDICATED ON FIRE SPRINKLER LEGEND.
3. ALL MATERIAL TO COMPLY WITH N.F.P.A. #13 (2010) AND BE UL LISTED AND APPROVED.
4. ALL NEW PIPE 2" AND SMALLER TO BE THREADABLE THINWALL.
5. ALL PIPE 2%" AND LARGER TO BE SCHEDULE 10 THIN WALL PIPE.
6. ALL NEW HANGERS TO CONSIST OF:
6.1. $" TOP BEAM CLAMP
6.2. 32" ALL THREAD ROD
6.3. SWIVEL HANGER RING
7. + - INDICATES CENTERLINE OF PIPE ABOVE FINISHED FLOOR.
8. (� - INDICATES CENTERLINE OF PIPE BELOW CONCRETE DECK.
9. ALL PIPE LENGTHS ARE "CENTER -CENTER" DIMENSION UNLESS NOTED OTHERWISE.
10. ALL ELECTRICAL WORK TO BE DONE BY OTHERS.
DESIGN CRITERIA:
1, FIRE SPRINKLER SYSTEM TO BE HYDRAULICALLY DESIGNED FOR:
LIGHT HAZARD.
2. DESIGN DENSITY OF .IOGPM/900SQ. FT.
3. Q - INDICATES HYDRAULIC REFERENCE POINT.
POSITIONING OF FIRE SPRINKLERS TO OBSTRUCEM
CEILING
FIRE SPRINKLER HEAD
m
A
OBSTRUCTION
DISTANCE FROM SPRINKLER TO SIDE OF
OBSTRUCTION (A)
MAXIMUM ALLOWABLE DISTANCE OF
DEFLECTOR ABOVE BOTTOM OF
OBSTRUCTION (IN.) (B)
LESS THAN 1'-0"
0"
1'-0" TO LESS THAN 1'-6"
2 %"
1'-6" TO LESS THAN 2'-0"
3 %"
2'-0" TO LESS THAN 2'-6"
5 12"
2'-6" TO LESS THAN 3'-0"
7 %"
3'-0" TO LESS THAN 3'-6"
9 %.'
3'-6" TO LESS THAN 4'-0"
12"
4'-0" TO LESS THAN 4'-6"
14"
4'-6" TO LESS THAN 5'-0"
16 %"
5'-0" AND GREATER
18"
TO FIRE SPRINKLER SYSTEM
6" ELECTRIC BELL
(WIRED BY OTHERS)
2" TESTANDRAIN VA.
W/ 175Ps1 RELIEF VA.
0
,,, r
N
N
LO
o FINISHED GRADE —�
I
0
4" GROOVED COUPLING
� o
r
L'F—Y4" GAUGE KIT
WATER FLOW SW.
(WIRED BY OTHERS)
- � 6 HEAD SPRINKLER CABINET
N
r
4" GROOVED BUTTERFLY VA. W/ TAMPER
o (WIRED BY OTHERS)
4" GROOVED FLANGE ADAPTER
r (POINT OF SERVICE FOR S.F.P.)
FROM CITY SUPPLY
(SEE CIVIL SHEET WS -1)
02 FIRE SPRINKLER RISER DETAIL
O.S. & Y TAMPER SW.
(WIRED BY OTHERS)
FINISHED GRADE
ST
FROM CITY SUPPLY
SCALE: %" = 1'-0"
lsll�v
4" x 22" x 2%" 90° F.D.C.
- 4" AMES 3000SS
BACKFLOW PREVENTOR
4" x 0'-4" THRD. x GRVD.
NIPPLE
4" GRVD. CHECK VA.
BFO
11
L
/ 4" GATE VA.
TO FIRE SPRINKLER SYSTEM
03 DOUBLE DECTECTOR CHECK VALVE DETAIL
SCALE: %" = 1'-0"
FIRE SPRINKLER HEAD
(SEE LEGEND)
I" x %" SCREWED ELL I" SCREWED ELL
I" SPRIG -UP
(SEE PLAN FOR LENGTH)
V4" X V4" x I" SCREWED TEE
0
V4" BRANCH LINE
04 SPRIG UP DETAIL
SCALE: 112" = 1'-0"
ABBREVIATIONS
WATER SUPPLY
FLOW TEST
LOCATION
FIRE PUMP
DATE OF TEST:
4/20/16
RATED CAPACITY:
TIME OF TEST:
2:00
RATED PRESSURE:
STATIC PRESSURE:
45
PUMP TYPE:
RESIDUAL PRESSURE:
29
WELL PUMP
GALLONS FLOWING:
1210
GPM AVAILABLE:
TESTED BY: BOYNTON BEACH FIRE
PSI AVAILABLE:
TO FIRE SPRINKLER SYSTEM
6" ELECTRIC BELL
(WIRED BY OTHERS)
2" TESTANDRAIN VA.
W/ 175Ps1 RELIEF VA.
0
,,, r
N
N
LO
o FINISHED GRADE —�
I
0
4" GROOVED COUPLING
� o
r
L'F—Y4" GAUGE KIT
WATER FLOW SW.
(WIRED BY OTHERS)
- � 6 HEAD SPRINKLER CABINET
N
r
4" GROOVED BUTTERFLY VA. W/ TAMPER
o (WIRED BY OTHERS)
4" GROOVED FLANGE ADAPTER
r (POINT OF SERVICE FOR S.F.P.)
FROM CITY SUPPLY
(SEE CIVIL SHEET WS -1)
02 FIRE SPRINKLER RISER DETAIL
O.S. & Y TAMPER SW.
(WIRED BY OTHERS)
FINISHED GRADE
ST
FROM CITY SUPPLY
SCALE: %" = 1'-0"
lsll�v
4" x 22" x 2%" 90° F.D.C.
- 4" AMES 3000SS
BACKFLOW PREVENTOR
4" x 0'-4" THRD. x GRVD.
NIPPLE
4" GRVD. CHECK VA.
BFO
11
L
/ 4" GATE VA.
TO FIRE SPRINKLER SYSTEM
03 DOUBLE DECTECTOR CHECK VALVE DETAIL
SCALE: %" = 1'-0"
FIRE SPRINKLER HEAD
(SEE LEGEND)
I" x %" SCREWED ELL I" SCREWED ELL
I" SPRIG -UP
(SEE PLAN FOR LENGTH)
V4" X V4" x I" SCREWED TEE
0
V4" BRANCH LINE
04 SPRIG UP DETAIL
SCALE: 112" = 1'-0"
ABBREVIATIONS
HYDRAULICALLY DESIGNED SYSTEM
MATERIAL TYPES
LOCATION
DESIGN CRITERIA
CL = CENTERLINE
SIZE
MATERIAL
TYPE SYSTEM NO.
1 2
+ = ELEVATION
1" - 2"
BRANCH LINES
XL PIPE HAZARD
LIGHT
TOS = TOP OF STEEL
2 1/2" - 6"
RISER & MAINS
SCH. 10 SPACING
169
G = GROOVED PIPE END
ALL
SCREWED FITTING
K FACTOR
5.6
T = THREADED PIPE END
ALL
GROOVED FITTINGS
INSIDE HOSE
0
F = FLANGED PIPE END
OUTSIDE DOSE
100
C -C = CENTER TO CENTES
RACK (PM
N/A
TYPES OF SPRINKLERS
SYMBOLS I NPT I TEMP. I MAKE & MODEL I TYPE I FINISH
a
O
0 TOTAL NUMBER OF SPRINKLERS ON THIS SHEET
01 FIRE SPRINKLER UNDERGROUND PLAN
SCALE : I" = 20'-0"
REVISIONS THOMAS J. TWOMEY, P.E.
ESC. K -FACT. NO. DATE DESCRIPTION BY
4/23/16 100% COMPLETE (PERMIT SET) BT
A 6/1.5/161 PER FIRE PLAN REVIEW COMMENTS BT
LIC#25626 I STATE LIC#:42031800011994
2831-A EXCHANGE COURT
WEST PALM BEACH, FL. 33409
Phone: 561-688-2844 Fax: 561-686-6852
STATE LIC #: 46428800012004 HOME AWAY FROM HOME D`r. CARE.Fri:
`l =;4791 N. CONGRESS AV
e EC
"BOYNTON BEACH, FL ter.
DRAWN BY: B. TOUCHET a DATE: AAIL 3, 2016
TOTAL SPRKS. ON JOB: 86 SCAL 3116- = 1'70"
A.H.J: CITY OF BOYNTON
200 BUSINESSPAR KWAY,SUITE F DRAWING NAME: 16-0071
ROYAL PALM BEACH, FL. 33411
Phone* 561-792-9690 Fam 561-792-3023 CONTRACT NO. 16-007
SHEET NQ FP -1 OF 2
HYDRAULICALLY DESIGNED SYSTEM
3
LOCATION
AREA #1 AREA #2 AREA #3
NO. OF SPRINKLERS
6
DENSITY
.10
DESIGN AREA
900
GPM DISCHARGE
205.596
RESIDUAL PSI AT
31.124
TYPES OF SPRINKLERS
SYMBOLS I NPT I TEMP. I MAKE & MODEL I TYPE I FINISH
a
O
0 TOTAL NUMBER OF SPRINKLERS ON THIS SHEET
01 FIRE SPRINKLER UNDERGROUND PLAN
SCALE : I" = 20'-0"
REVISIONS THOMAS J. TWOMEY, P.E.
ESC. K -FACT. NO. DATE DESCRIPTION BY
4/23/16 100% COMPLETE (PERMIT SET) BT
A 6/1.5/161 PER FIRE PLAN REVIEW COMMENTS BT
LIC#25626 I STATE LIC#:42031800011994
2831-A EXCHANGE COURT
WEST PALM BEACH, FL. 33409
Phone: 561-688-2844 Fax: 561-686-6852
STATE LIC #: 46428800012004 HOME AWAY FROM HOME D`r. CARE.Fri:
`l =;4791 N. CONGRESS AV
e EC
"BOYNTON BEACH, FL ter.
DRAWN BY: B. TOUCHET a DATE: AAIL 3, 2016
TOTAL SPRKS. ON JOB: 86 SCAL 3116- = 1'70"
A.H.J: CITY OF BOYNTON
200 BUSINESSPAR KWAY,SUITE F DRAWING NAME: 16-0071
ROYAL PALM BEACH, FL. 33411
Phone* 561-792-9690 Fam 561-792-3023 CONTRACT NO. 16-007
SHEET NQ FP -1 OF 2
NOTE:
ARMOVERS GREATER THAN 24"
IN LENGTH SHALL BE
SUPPORTED BY A HANGER
REMOVE EX. HEAD AND/OR
BUSHING. INSTALL NEW NEW I" ELL
I" x 0'-2" NIPPLE
NEW I" ARMOVER
EXISTING BRANCH LINE
NEW I" ELL
EXISTING I" OUTLET J
NEW I" x%" R.C.
NEW FIRE SPRINKLER HEAD
(SEE LEGEND FOR TYPE) NEW CEILING
(SEE PLAN)
TYPICAL ARMOVER DETAIL
KL&
STEEL BAR JOIST
FIRE SPRINKLER PIPE
(SEE PLAN FOR SIZE)
%" TOP BEAM CLAMP
8" ALL -THREAD ROD
(LENGTHS VARY)
SWIVEL HANGER RING
(SEE PLAN FOR SIZE)
TYPICAL HANGER DETAIL
KTS
TYPICAL HANGER LOCATION DETAIL
PIPE SIZE
A
B*
C
1"
3'-0" MAX.
12'-0" MAX.
3" MIN.
1 1/4"
4'-0" MAX.
12'-0" MAX.
3" MIN.
1 1/2" - 8"
5'-0" MAX.
15'-0" MAX.
3" MIN.
14"
4'-6" TO LESS THAN 5'-0"
HANGER RING
A B4HEAD
5'-0" AND GREATER
STEEL PIPE
GROOVED FITTINGS
INSIDE HOSE
FIRE SPRINKLE
* MAXIMUM HANGERSPACINGFOR THREADED LIGHTWALL
STEEL PIPE IS 12'-0" FOR ALL PIPE SIZES
GENERAL NOTES:
I. ALL NEW FIRE SPRINKLERS TO BE INSTALLED PER N.F.P.A #13 (2010).
2. ALL NEW FIRE SPRINKLERS TO BE AS INDICATED ON FIRE SPRINKLER LEGEND.
3. ALL MATERIAL TO COMPLY WITH N.F.P.A. #13 (2010) AND BE UL LISTED AND APPROVED.
4. ALL NEW PIPE 2" AND SMALLER TO BE THREADABLE THINWALL.
5. ALL PIPE 2'/" AND LARGER TO BE SCHEDULE 10 THIN WALL PIPE.
6. ALL NEW HANGERS TO CONSIST OF:
6.1. %" TOP BEAM CLAMP
6.2. $" ALL THREAD ROD
6.3. SWIVEL HANGER RING
7. + - INDICATES CENTERLINE OF PIPE ABOVE FINISHED FLOOR.
8. � - INDICATES CENTERLINE OF PIPE BELOW CONCRETE DECK.
9. ALL PIPE LENGTHS ARE "CENTER -CENTER" DIMENSION UNLESS NOTED OTHERWISE.
10. ALL ELECTRICAL WORK TO BE DONE BY OTHERS.
DESIGN CRITERIA:
I. FIRE SPRINKLER SYSTEM TO BE HYDRAULICALLY DESIGNED FOR:
LIGHT HAZARD.
2. DESIGN DENSITY OF .10GPM/900SQ. FT.
3.0 - INDICATES HYDRAULIC REFERENCE POINT.
FIRE SPRINKLER HEAD
m
A
OBSTRUCTION
DISTANCE FROM SPRINKLER TO SIDE OF
OBSTRUCTION (A)
MAXIMUM ALLOWABLE DISTANCE OF
DEFLECTOR ABOVE BOTTOM OF
OBSTRUCTION (I N.) (B)
LESS THAN 1'-0"
0"
1'-0" TO LESS THAN 1'-6"
2/2"
1'-6" TO LESS THAN 2'-0"
3 %"
2'-0" TO LESS THAN 2'-6"
5 Iz"
2'-6" TO LESS THAN 3'-0"
7 %"
3'-0" TO LESS THAN 3'-6"
9 y°
3'-6" TO LESS THAN 4'-0"
12"
4'-0" TO LESS THAN 4'-6"
14"
4'-6" TO LESS THAN 5'-0"
16 %"
5'-0" AND GREATER
18"
TESTED BY. BOYNTON BEACH FIRE IPSI AVAILABLE:
TO FIRE SPRINKLER SYSTEM � TR
6" ELECTRIC BELL
(WIRED BY OTHERS)
2" TESTANDRAIN VA.
W/ 175PS1 RELIEF VA.
0
N
-N N
N
i u')
�o
o FINISHED GRADE —�
4" GROOVED COUPLING
� o
r%4" GAUGE KIT
WATER FLOW SW.
(WIRED BY OTHERS)
- � 6 HEAD SPRINKLER CABINET
N
7- 4" GROOVED BUTTERFLY VA. W/ TAMPER
o (WIRED BY OTHERS)
rn
4" GROOVED FLANGE ADAPTER
(POINT OF SERVICE FOR S.F.P.)
FROM CITY SUPPLY
(SEE CIVIL SHEET WS -1)
02 FIRE SPRINKLER RISER DETAIL
SCALE: %" = 1'-0"
4" x 2Y2" x 2Y2" 90° F.D.C.
O.S. 8& Y TAMPER SW. 4" AMES 3000SS
(WIRED BY OTHERS) BACKFLOW PREVENTOR
4" x 0'-4" THRD. x GRVD.
NIPPLE
4" GRVD. CHECK VA.
BFI BFO
d
X
Q
N
FINISHED GRADE
N
10
m
z
F
S� M 4" GATE VA.
FROM CITY SUPPLY TO FIRE SPRINKL�SSYSTTEMMM
03 DOUBLE DECTECTOR CHECK VALVE DETAIL
SCALE: %" = 1'-0"
FIRE SPRINKLER HEAD
(SEE LEGEND)
I" X/2" SCREWED ELL I" SCREWED ELL
I" SPRIG -UP
(SEE PLAN FOR LENGTH)
V4" x V4" x I" SCREWED TEE
0
V4" BRANCH LINE
04 SPRIG UP DETAIL
SCALE: 1 %" = 1'-0"
ABBREVIATIONS
CL = CENTERLINE
WATER SUPPLY
FLOW TEST
TYPE SYSTEM NO.
FIRE PUMP
DATE OF TEST'
4/20/16
RATED CAPACITY -
TIME OF TEST:
2:00
RATED PRESSURE:
STATIC PRESSURE:
45
PUMP TYPE:
RESIDUAL PRESSURE:
29
WELL PUMP
GALLONS FLOWING:
1210
GPM AVAILABLE:
TESTED BY. BOYNTON BEACH FIRE IPSI AVAILABLE:
TO FIRE SPRINKLER SYSTEM � TR
6" ELECTRIC BELL
(WIRED BY OTHERS)
2" TESTANDRAIN VA.
W/ 175PS1 RELIEF VA.
0
N
-N N
N
i u')
�o
o FINISHED GRADE —�
4" GROOVED COUPLING
� o
r%4" GAUGE KIT
WATER FLOW SW.
(WIRED BY OTHERS)
- � 6 HEAD SPRINKLER CABINET
N
7- 4" GROOVED BUTTERFLY VA. W/ TAMPER
o (WIRED BY OTHERS)
rn
4" GROOVED FLANGE ADAPTER
(POINT OF SERVICE FOR S.F.P.)
FROM CITY SUPPLY
(SEE CIVIL SHEET WS -1)
02 FIRE SPRINKLER RISER DETAIL
SCALE: %" = 1'-0"
4" x 2Y2" x 2Y2" 90° F.D.C.
O.S. 8& Y TAMPER SW. 4" AMES 3000SS
(WIRED BY OTHERS) BACKFLOW PREVENTOR
4" x 0'-4" THRD. x GRVD.
NIPPLE
4" GRVD. CHECK VA.
BFI BFO
d
X
Q
N
FINISHED GRADE
N
10
m
z
F
S� M 4" GATE VA.
FROM CITY SUPPLY TO FIRE SPRINKL�SSYSTTEMMM
03 DOUBLE DECTECTOR CHECK VALVE DETAIL
SCALE: %" = 1'-0"
FIRE SPRINKLER HEAD
(SEE LEGEND)
I" X/2" SCREWED ELL I" SCREWED ELL
I" SPRIG -UP
(SEE PLAN FOR LENGTH)
V4" x V4" x I" SCREWED TEE
0
V4" BRANCH LINE
04 SPRIG UP DETAIL
SCALE: 1 %" = 1'-0"
ABBREVIATIONS
CL = CENTERLINE
SIZE
MATERIAL TYPES
MATERIAL
TYPE SYSTEM NO.
DESIGN CRITERIA
1 2
+ = ELEVATION
1" — 2"
BRANCH LINES
XL PIPE HAZARD
LIGHT
TOS = TOP OF STEEL
2 1/2" — 6"
RISER & MAINS
SCH. 10 SPACING
169
G = GROOVED PIPE END
ALL
SCREWED FITTING
K FACTOR
5.6
T = THREADED PIPE END
ALL
GROOVED FITTINGS
INSIDE HOSE
0
F = FLANGED PIPE END
K ` SZ
Z'S Pte. _ M r-
" H
OUTSIDE HOSE
100
C—C = CENTER TO CENTER
ESC. K—FACT. NO. DATE DESCRIPTION BY
RACK GPM
N/A
� � A T OF ° t :
e
FIPJ
so
BOYNTON BEACH, FL.
4/23/16 100% COMPLETE (PERMIT SET) BT
TYPES OF SPRINKLERS
SYMBOLS NPT TEMP. MAKE & MODEL TYPE FINISH
0
Q
0 I TOTAL NUMBER OF SPRINKLERS ON THIS SHEET
01 FIRE SPRINKLER UNDERGROUND PLAN
SCALE : I" = 20'-0"
By—
__;2
BEACH §c SEPT,
HYDRAULICALLY DESIGNED SYSTEM
3
LOCATION
AREA #1 AREA #2 AREA #3
NO. OF SPRINKLERS
6
DENSITY
.10
DESIGN AREA
900
GPM DISCHARGE
205.596
RESIDUAL PSI AT
TEST
31.124
TYPES OF SPRINKLERS
SYMBOLS NPT TEMP. MAKE & MODEL TYPE FINISH
0
Q
0 I TOTAL NUMBER OF SPRINKLERS ON THIS SHEET
01 FIRE SPRINKLER UNDERGROUND PLAN
SCALE : I" = 20'-0"
By—
__;2
BEACH §c SEPT,
REVISIONSr
K ` SZ
Z'S Pte. _ M r-
" H
"LIC#25626
STATE LIC #:42031800011984 STATE LIC 46428800012004
HOME AWAY FROM HOME DAY CARE
4791 N. CONGRESS AVE.
ESC. K—FACT. NO. DATE DESCRIPTION BY
� � A T OF ° t :
e
FIPJ
so
BOYNTON BEACH, FL.
4/23/16 100% COMPLETE (PERMIT SET) BT
1Q 6/15/16 PER FIRE PLAN REVIEW COMMENTS BT'
DRAWN BY. B. TOUCHET
DATE: APRIL 3, 2016
TOTAL SPRKS. ON JOB: 86
SCALE: 3/16" = 1'-0"
FIRE PROTECTION
A.H.J: CITY OF BOYNTON BEACH FIRE RESCUE
2831-AEXCHA ECOURT
200 BUSINESS PARKWAY, SUITE
DRAWING NAME: 16-007(MedowsSquareDarecare).dwg
EST PALM BEACH, FL. 33409
ROYAL PALM BEACH, FL. 33411
CONTRACT NO. 16-007
SHEET NO. FP -1 OF 2
Phone 561-688-2844Fax:561-686-6852
Phone: 561-792-9690 Fax:561-792-3023
EL. +16'-0"
JOIST BEARING
%" x 4'-0" A.T.R.
1:
I!
is
I'
N
35'-10,V2"
ei o
3 5'— 5,V2"
28'-8"
10' — I y4" 25' —3 4"
DESIGN AREA #1
LIGHT HAZARD
.IOGPM / 900SQ.FT.
EL. +16'---0,
SG� _ JOIST BEARING _
9'-9' � ____ L -------J 9;'' 9 L._ �.1 _ __5'-1' 2'-1012" __ �� 9'-6" ._.._!1_ ►Z' -z" i L'_� 14--'UU�_ f
°T
I
-Ile
I
0
_I
EL. +15,_6"
JOIST BEARING
o
ml
SPRINKLER
SCALE :
1
STATE LIC #:42031600011994
DESIGN CRITERIA
FLOW TEST
�O
N
CL = CENTERLINE
SIZE
N
TYPE SYSTEM NO.
001
li
4/20/16
RATED CAPACITY:
+ = ELEVATION
1" — 2"
BRANCH LINES
XL PIPE HAZARD
1
TIME OF TEST:
2:00
RATED PRESSURE:
141
11/4n
N
35'-10,V2"
ei o
3 5'— 5,V2"
28'-8"
10' — I y4" 25' —3 4"
DESIGN AREA #1
LIGHT HAZARD
.IOGPM / 900SQ.FT.
EL. +16'---0,
SG� _ JOIST BEARING _
9'-9' � ____ L -------J 9;'' 9 L._ �.1 _ __5'-1' 2'-1012" __ �� 9'-6" ._.._!1_ ►Z' -z" i L'_� 14--'UU�_ f
°T
I
-Ile
I
0
_I
EL. +15,_6"
JOIST BEARING
� j
FOR UNDERGROUND CONTINUATION
SEE CIVIL DRAWINGS (SHEET WS -0
L.X i I
}
}
I E
29 GRD =N: 26 GRD: _ _. I _ 2e3°' R®
I
_ GRID:
E :
t:o?—L
01
in _ o -
= 1 _
4" V4" 4 V4 V4 V4 V4 4 4 V4 V l
�4 V4"
8'-0"!, 9 t 8 0 q - 'q'- 5 �2 2 10� I �22'-IQ`'
3
f VARIES
I _ 1 + 12'-0" I
31
V)
I
/ry ,.
0.+J
... F I
col � — If
(%4" UP TO TOWER ABOVE
_ �, (SEE 02 TOWER PLAN FOR LAYOUT)
1 i� i�I ill I�/ „ ) ' �' [ V4.1
"' ..' II "
V4 V4 4 4
�4 ' ` �4 _ i Vh 9 4 V4 f t
10' , 4'-10'-2" _ 9' 5'-; 2'_7" 9-0 V" I
V V.'
' 2'-10Y2"
-
10
V4 4 (/4 , j V4IL
_ 14' 14'-0" 5"
8' 7' I '-0" _- d I'- „ 8'-7"
��,F I ' "GRD l
. GRD. } ' - � ARD_ _
: F
„FV
4 W. KV4' I -- �4„ 1 V4.. V4 , 1 4 V4 i V4
1 if
2'-0' 10'-3" �" 9'-10��1'_2'� 4'-10" 121 11'_0"� 5'-81� 5'-10" 0 0'-0" = I & 5" 21.
I
€ j = _ I
t N 3 N} i
x ILIo _ } j
' 12'..0"` 9'
" V4 V4 �4w V4 V41 A V4 V4" N 3
' = t - p
I �2
�" �-
12, 12'-0"` i_ $'-112 7'-2 4'-10"_ 0" 3'-2"
—6
1
i .
i
s _
,
1 I i
" ' 11/4" V4 ; - ✓4 ✓4 ! 1�4 V44" 1 I
17Fr ,
V
c
'Fl
2'-2" 112'-0"} 8'-� T.-2 _ 4'-10 1112'-0" I 4'-8" 4'. V" I L4.
-� BR 2 I 2 , _
12'-0" _ _I 14'-0"
1 TR € 1/2
' I
4
F .2'
— I ;
li'-7_21'-0"I
13 _
EL. +14'-4" 4" x 2/" GRVD. REDUCING COUPLING s -
EL. +14 —4
JOIST BEARING 4" FIRE SPRINKLER RISER JOIST BEARING
(SEE DETAIL 01 ON FP -I)
BFO
BFI ST
WATER SUPPLY
ABBREVIATIONS
SPRINKLER
SCALE :
�o
STATE LIC #:42031600011994
� j
FOR UNDERGROUND CONTINUATION
SEE CIVIL DRAWINGS (SHEET WS -0
L.X i I
}
}
I E
29 GRD =N: 26 GRD: _ _. I _ 2e3°' R®
I
_ GRID:
E :
t:o?—L
01
in _ o -
= 1 _
4" V4" 4 V4 V4 V4 V4 4 4 V4 V l
�4 V4"
8'-0"!, 9 t 8 0 q - 'q'- 5 �2 2 10� I �22'-IQ`'
3
f VARIES
I _ 1 + 12'-0" I
31
V)
I
/ry ,.
0.+J
... F I
col � — If
(%4" UP TO TOWER ABOVE
_ �, (SEE 02 TOWER PLAN FOR LAYOUT)
1 i� i�I ill I�/ „ ) ' �' [ V4.1
"' ..' II "
V4 V4 4 4
�4 ' ` �4 _ i Vh 9 4 V4 f t
10' , 4'-10'-2" _ 9' 5'-; 2'_7" 9-0 V" I
V V.'
' 2'-10Y2"
-
10
V4 4 (/4 , j V4IL
_ 14' 14'-0" 5"
8' 7' I '-0" _- d I'- „ 8'-7"
��,F I ' "GRD l
. GRD. } ' - � ARD_ _
: F
„FV
4 W. KV4' I -- �4„ 1 V4.. V4 , 1 4 V4 i V4
1 if
2'-0' 10'-3" �" 9'-10��1'_2'� 4'-10" 121 11'_0"� 5'-81� 5'-10" 0 0'-0" = I & 5" 21.
I
€ j = _ I
t N 3 N} i
x ILIo _ } j
' 12'..0"` 9'
" V4 V4 �4w V4 V41 A V4 V4" N 3
' = t - p
I �2
�" �-
12, 12'-0"` i_ $'-112 7'-2 4'-10"_ 0" 3'-2"
—6
1
i .
i
s _
,
1 I i
" ' 11/4" V4 ; - ✓4 ✓4 ! 1�4 V44" 1 I
17Fr ,
V
c
'Fl
2'-2" 112'-0"} 8'-� T.-2 _ 4'-10 1112'-0" I 4'-8" 4'. V" I L4.
-� BR 2 I 2 , _
12'-0" _ _I 14'-0"
1 TR € 1/2
' I
4
F .2'
— I ;
li'-7_21'-0"I
13 _
EL. +14'-4" 4" x 2/" GRVD. REDUCING COUPLING s -
EL. +14 —4
JOIST BEARING 4" FIRE SPRINKLER RISER JOIST BEARING
(SEE DETAIL 01 ON FP -I)
BFO
BFI ST
02 TOWER FIRE SPRINKLER PLAN
SCALE : 3/16" = 1'-0"
WATER SUPPLY
ABBREVIATIONS
SPRINKLER
SCALE :
MATERIAL TYPES
STATE LIC #:42031600011994
DESIGN CRITERIA
FLOW TEST
FIRE PUMP
CL = CENTERLINE
SIZE
MATERIAL
TYPE SYSTEM NO.
1 2
.DATE OF TEST-
4/20/16
RATED CAPACITY:
+ = ELEVATION
1" — 2"
BRANCH LINES
XL PIPE HAZARD
LIGHT
TIME OF TEST:
2:00
RATED PRESSURE:
TOS = TOP OF STEEL
2 1/2" — 6"
RISER & MAINS
SCH. 10 SPACING
169
STATIC PRESSURE:
45
PUMP TYPE:
G = GROOVED PIPE END
ALL
SCREWED FITTING
K FACTOR
5.6
RESIDUAL PRESSURE:
29
WELL PUMP
T = THREADED PIPE END
ALL
GROOVED FITTINGS
INSIDE HOSE
0
GALLONS FLOWING:
1210
GPM AVAILABLE:
F = FLANGED PIPE END
OUTSIDE HOSE
100
TESTED BY: BOYNTON BEACH FIRE
PSI AVAILABLE:
C—C = CENTER TO CENTE4
I
RACK GPM I
N/A
02 TOWER FIRE SPRINKLER PLAN
SCALE : 3/16" = 1'-0"
OI
FIRE
SPRINKLER
SCALE :
PLAN ll
3/16" = 1'-0"
STATE LIC #:42031600011994
HYDRAULICALLY DESIGNED SYSTEM
TYPES OF SPRINKLERS
3
LOCATION
AREA #1
AREA #2 AREA #3 QUAN. SYMBOLS NPT
TEMP. MAKE & MODEL TYPE FINISH ESC. K—FACT. NO. DATE
{
NO. OF SPRINKLERS
6
82 OO 1/2"
155' TYCO TY323 QR PENDENT CHROME RECESSED 5.6 4/23/16
DENSITY
.10
FIRE PROTECTION
4 O 1/2"
286' TYCO TY313 QR UPRIGHT BRASS NONE 5.6
1- CHANG OURT
DESIGN AREA
900
Q
ROYAL PALM BEACH, FL. 33411
Phone: 561-792-9690
GPM DISCHARGE
205.596
O
RESIDUAL PSI AT
TEST
31.124
O
86 TOTAL NUMBER OF SPRINKLERS ON THIS SHEET
02 TOWER FIRE SPRINKLER PLAN
SCALE : 3/16" = 1'-0"
STATE LIC #: 46428800012004 HOME AWAY FROM HOME DAY CARE
4791 N. CONGRESS AVE.
BOYNTON BEACH, FL.
DRAWN BY: B. TOUCHET DATE: APRIL 3, 2016
TOTAL SPRKS. ON JOB: 86 SCALE: 3/16" = 1'-0"
A.H.J: CITY OF BOYNTON BEACH FIRE RESCUE
DRAWING NAME: 16-007(MedowsSquareDarecare).dwg
Fax 561-792-3023 CONTRACT NO. 16-007 1 SHEET NO. FP -2 OF 2
q tx
REVISIONS
THOMASI TWO R #25626
STATE LIC #:42031600011994
_LIC
F
DESCRIPTION BY
100% COMPLETE (PERMIT SET) BT
{
OVFIPJ
`
FIRE PROTECTION
1- CHANG OURT
200 BUSINESS PARKWAY, SUITE F
P LM BEACH, FL. 33409
Phone: 61-688-2844Fax:561-686-6852
ROYAL PALM BEACH, FL. 33411
Phone: 561-792-9690
STATE LIC #: 46428800012004 HOME AWAY FROM HOME DAY CARE
4791 N. CONGRESS AVE.
BOYNTON BEACH, FL.
DRAWN BY: B. TOUCHET DATE: APRIL 3, 2016
TOTAL SPRKS. ON JOB: 86 SCALE: 3/16" = 1'-0"
A.H.J: CITY OF BOYNTON BEACH FIRE RESCUE
DRAWING NAME: 16-007(MedowsSquareDarecare).dwg
Fax 561-792-3023 CONTRACT NO. 16-007 1 SHEET NO. FP -2 OF 2
G
G
a
0
.0
N
r`
N
N
..__....._.tel -'1 ......... ........ ...
FOR UNDERGROUND CONTINUATION
SEE CIVIL DRAWINGS (SHEET WS -1)
35'-10,V2"
35'-5)/2" 28'-8°
E
WATER SUPPLY
ABBREVIATIONS
SPRINKLER
MATERIAL TYPES
IDESIGN
CRITERIA
FLOW TEST
FIRE PUMP
CL = CENTERLINE
SIZE
MATERIAL
TYPE SYSTEMNO.
1 2
DATE OF TEST:
4/20/16
RATED CAPACITY:
+ = ELEVATION
1" - 2"
BRANCH LINES
XL PIPE HAZARD
LIGHT
TIME OF TEST:
2:00
RATED PRESSURE:
TOS = TOP OF STEEL
2 1/2" - 6"
RISER & MAINS
SCH. 10 SPACING
169
STATIC PRESSURE:
45
PUMP TYPE:
G = GROOVED PIPE END
ALL
SCREWED FITTING
K FACTOR
5.6
RESIDUAL PRESSURE:
GALLONS FLOWING:
29
1210
WELL PUMP
GPM AVAILABLE:
T = THREADED PIPE END
F = FLANGED PIPE END
ALL
GROOVED FITTINGS
INSIDE HOSE
OUTSIDE HOSE
0
100
TESTED BY. BOYNTON BEACH FIRE
PSI AVAILABLE:
C -C = CENTER TO CENTEF
RACK GPM
N/A
00
FIRE
SPRINKLER
PLAN
SCALE :
3/16" = I'-0"
HYDRAULICALLY DESIGNED SYSTEM
TYPES OF SPRINKLERS REVISIONS
THOMAS J. TWOMEY, P.E. LIC#25626
STATE LIC #: 42031800011994 STATE LIC #:46428800012004'
3
LOCATION
AREA #1
AREA #2 AREA #3 QUAN. SYMBOLS NPT
TEMP. MAKE & MODEL TYPE FINISH ESC. K -FACT. NO. DATE DESCRIPTION
BY
HOME AWAY FROM HOME DAY CARE k`
NO. OF SPRINKLERS
6
82 OO 1/2"
155' TYCO TY323 QR PENDENT CHROME RECESSED 5.6 4/23/16 100% COMPLETE (PERMIT SET)
BT
4791 N. CONGRESS AVE.
BOYNTON
DENSITY
.10
4 Q 1/2"
286' TYCO TY313 QR UPRIGHT BRASS NONE 5.6
Lv
BEACH, FL.
DESIGN AREA
900
a
bo
DRAWN BY: B. TOUCHET DATE: APRIL 3, 2016 <;
GPM DISCHARGE
205.596
�I�
TOTAL SPRKS. ON JOB: 86 SCALE: 3/16" = 1'-O" ,;
�
A.H.J: CITY OF BOYNTON BEACH FIRE RESCUE
RESIDUAL PSI AT
TEST
31.124
O
2831-A EXCHANGE COURT
WEST PALM BEACH, FL. 33409
200 BUSINESS PARKWAY, SUITE
ROYAL PALM BEACH, FL. 33411
DRAWING NAME: 16-007(MedowsSquareDarecare).dwg
86 TOTAL NUMBER OF SPRINKLERS ON THIS SHEET
Phone: 561-688-2844Fax:561-686-6852
Phone: 561-792-9690 Fax: 561-792-3023
CONTRACT N0. 16-007 SHEET N0. FP -2 ';.OF 2