DRAWINGSA. GENERAL PROVISIONS 1. THE WORK SHALL CONSIST OF FURNISHING LABOR, EQUIPMENT, ANI) MATERIALS TO PROVIDE THE COMPLETE INTEGRATED AND PROPER FUNCTION'G-SYSTEA:S At 8.'i0Nv.0t, Tit_DRAWING6. 2. ALL WORK SHALL BE DONE IN CONF3RMAIiCE WITH T, -EE LAMS3 6DIT.ONL OF TAE NATIONAL ELECTRICAL CODE, ALL APPLICABLE FEDERAL, STATE AND LOCAL REGU!ATION5 AND'9XDIIgWE%_. --- 3. ALL EQUIPMENT AND MATERIALS SHALL BE NEW OR EXISTING IN CONFORMANCE WITH APPLICABLE PROVISIONS OF NEMA, ANSI, UL ETC... 4. THE ELECTRICAL CONTRACTOR SHALL COORDINATE HIS WORK WITH THAT OF OTHER TRADES SO AS TO AVOID INTERFERENCES. 5. THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL LAYOUT OF ELECTRICAL SYSTEMS. FIELD VERIFICATIONS OF DIMENSIONS IS DIRECTED. 6. SECURE PERMITS AND INSPECTIONS REQUIRED BY STATE AND LOCAL LAWS AND ORDINANCES. 7. UPON COMPLETION OF THE WORK, FURNISH TO THE OWNER CERTIFICATES OF FINAL INSPECTIONS AND APPROVALS FROM AUTHORITIES HAVING JURISDICTION. & ALL WORKS SHALL BE GUARANTEED FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE OWNER. FROM AUTHORITIES HAVING JURISDICTION. 9. CIRCUITS ON THE PLANS ARE TO DETERMINE LOAD AND PANEL SIZE. THE CONTRACTOR SHALL PROVIDE CIRCUITS AND ROUTING TO SUIT JOB CONDITIONS, AND BALANCE THE CONNECTED LOAD. 10. FURNISH AND INSTALL LIGHTING FIXTURES AND LAMPS AS CALLED FOR ON THESE PLANS. FIXTURES SHALL NOT BE SUPPORTED BY THE CEILING GRID BUT BY GUY WIRES FROM ABOVE. 11. CHECK EQUIPMENT FOR PROPER VOLTAGE, PHASE, AND AMP RATING BEFORE CONNECTION TO CIRCUITS. 12. THE ELECTRICAL SYSTEM SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED AS REQUIRED IN ARTICLE 250 OF THE NEC. ALL RACEWAYS TO HAVE EQUIPMENT GROUND CONDUCTOR, AND WHEN CROSSING BUILDING EXPANSION JOINTS, EXPANSION FITTING WITH BONDING JUMPERS SHALL BE USED. B: RACEi(y9Y� 1. ALL WIRING SHALL BE INSTALLED IN APPROVED RACEWAYS. HOSPITAL GRADE ARMORED CABLE PROVIDING REDUNDANT GROUND IS ALLOWED. 2. MINIMUM CONDUIT SIZE SHALL BE 1/2' TRADE SIZE. 3. USE FLEXIBLE CONDUIT FOR SHORT FINAL CONNECTIONS TO VIBRATION EQUIPMENT SUCH AS MOTORS AND TRANSFORMERS. LIQUID -TIGHT FLEXIBLE CONDUIT SHALL BE USED IN DAMP AND WET LOCATIONS. 4. EXPOSED CONDUIT SHALL BE RUN PARALLEL TO BUILDING LINES. 5. DO NOT INSTALL CONDUITS LARGER THAN 1/3 THE SLAB THICKNESS IN CONCRETE SLABS. 6. PROVIDE APPROVED FIRE STOPPING MATERIALS AT ALL PENETRATIONS THROUGH FIRE RATED FLOOR AND WALLS TO PREVENT THE PASSAGE OF SMOKE. FIRE, TOXIC GAS OR WATER THROUGH THE PENETRATION EITHER BEFORE, DURING OR AFTER A FIRE. AS REQUIRED BY ARTICLE 300-21 OF THE N.E.C. 7. PROVIDE CABLE SUPPORTS IN ACCORDANCE WITH ARTICLE 300 OF THE N.E.C. 8. PROVIDE EXPANSION FITTINGS IN CONDUIT RUNS CROSSING STRUCTURAL EXPANSION JOINTS. 9. PANEL BOARDS SHALL BE CIRCUIT BREAKER TYPE. VERIFY NUMBER AND SIZES OF BREAKERS. C. CONDUCTORS 1. ALL WIRING SHALL BE COPPER. 2. CONDUCTORS SHALL BE RATED 60OV. WITH TYPE THHN INSULATION. 3. WIRES SIZES #10 AWG AND SMALLER SHALL BE SOLID CONDUCTOR WITH TYPE THHN INSULATION. WIRES SIZES STRANDED WITH TYPE THHN INSULATION. CONTRACTOR TO USE HIS BEST DISCRETION IN THE INSTALLATION, LOCAL CODES SUPERSEDE. 4. MINIMUM CONDUCTOR SIZE SHALL BE #12. CONTROL. WIRING MAY BE SMALLER. D. FIGHTING PANELS 1. PROVIDE LIGHTING AND RECEPTACLE PANE_ AS INDICATED ON THE PLANS AND AS SPECIFIED HEREN. ALL PANES SHALL BE DEAD FRONT,BOLT-ON CIRCUIT BREAKERS TYPE. PANE LBOARDS AND SHALL BEAR THE U.L LABEL AS WELL AS MEET ALL APPLICABLE NEMA REQUIREMENTS. 2. UNLESS OTHERWISE NOTED, TOP OF PANELS SHALL BE MOUNTED AT 6'A.F.F. TO TOP. 3. ALL PANES SHALL HAVE TYPEWRITTEN CIRCUIT DIRECTORIES MOUNTED INSIDE OF DOOR. 4. PANES SHALL BE SUITABLE FOR THE SERVICE RATING AND THE A.I.C. RATING INDICATED ON THE PANELS SCHEDULES. LABS_ AS WELL AS MEET ALL APPLICABLE NEMA REQUIREMENTS. 5. ALL BREAKERS SHALL BE FULL SPACE, INDIVIDUAL FRAME TYPE. NO -PINY-BACK-OR TANDEM BREAKERS WILL BE PERMITTED. E. SAFETY SWITCHES 1. ALL NEW SAFETY SWITCHES SHALL BE HEAVY DUTY TYPE -HD-, FUSIBLE OR NON -FUSIBLE WITH POLES, AMPERE AND SERVICE RATINGS AS INDICATED ON THE PLANS. LUGS SHALL BE U.L LISTED FOR CU. -AL 2. ENCLOSURES FOR SAFETY SWITCHES SHALL BE NEMA 1, EXCEPT FOR SWITCHES MARKED "WP- (WEATHERPROOF) SHALL BE NEMA 3R. F: FUS 1. ALL NEW FUSES SHALL HAVE A 200,000 AMP RMS SYMMETRICAL INTERRUPTING RATING UNLESS OTHERWISE NOTED. LOWER RATING MAY BE USED ONLY UPON POWER COMPANY ISSUING A LETTER WITH FAULT CURRENT ANALYSIS JUSTIFYING LOWER RATING. A COPY OF A LETTER MUST BE FORWARDED TO THE ARCHITECT OF RECORD. 2. NEW FUSES RATED 0 TO 600 AMPS SHALL BE AS FOLLOW: G) CIRCUIT BREAKER PANEL PROTECTION - U.L CLASS RK -1, DUAL ELEMENT (BUSSMANN 'LOW PEAK' OR EQUAL) b) MOTOR CIRCUIT PROTECTION -U.L CLASS RK -5, DUAL ELEMENT (BUSSUANN 'FUSETRON' OR EQUAL) 3. NEW FUSES RATED 601 AMPS OR LARGER SHALL BE U.L CLASS L TIME DELAY (BUSMANN "HI -CAP" OR EQUAL). 0 EMPTY CONDUIT FOR DATA MTS DUPLEX RECEPTACLE AT 18" A.F.F. U.O.N. BUS DUPLEX RECEPTACLE SPLIT CIRCUIT DESCRIPTION OR AS INDICATED ON PLAN N❑ QUAD RECEPTACLE AT 18" A.F.F. U.O.N. ®- 240/208 RECEPTACLE 30 AMP OR LARGER �- 240/208V RECEPTACLE 20 AMP e- SINGLE RECEPTACLE 20 AMP rFLOOR FLUSH MOUNTED DUPLEX RECEPTACLE -�- SWITCH A THREE WAY SWITCH -]A. VD DIMMER SWITCH BZ BUZZER W/ TRANSFORMER F<] FLOOR MOUNTED DATA/PHONE RECEPTACLE #6-1" DATA/PHONE RECEPTACLE AT 18" AFF U.O.N. 2 4 FAN MOTOR Eh DISCONNECT SWITCH P.O.S. POINT OF SERVICE 0 EMPTY CONDUIT FOR DATA MTS DISCONNECT SWITCH BUS IN CEILING WIRELESS ACCESS POINT DESCRIPTION GENERATOR RECEPTACLE N❑ TV LOCATION (POWER & DATA) R RELOCATED DEVICE KeoTEs EXACT POSITION TO BE CONSULTED WITH TENANT IN FIELD PRIOR TO INSTALL EXISTING LO TER "A" RATED VOLTAGE 120/208V,3PH.4W LOCATION:x �'1S5 __SkE_2LAN. . RATED AMPS: 200 AMPS MOUNTING:111s IST MAIN: MLO (CU BUSS) FEEDER CO S.... BRANCH POLES: 42 FEEDER CONDUIT�s`�Xt:3�� h` INTERRUPTING RATE: 10 K A.I.C. RER BUS KVA DESCRIPTION BRK WIRE/ COND. CKT NO. CKT NO. WIRE/ COND. BRK DESCRIPTION BUS KVA A B I C TRP PLS TRP/PLS A B C 5.1 5.1 U) AHU-1 60/2 #6-1" 1 3 2 4 #8-1" 50/2 CU -1 - - ,f 117% 5.1 5.1 MU -2 O 5 7 6 8 #8-1" 50/2 CU -1 - LJL - 2.6 2.6 EWH 30/2 #10-3/ 9 11 10 12 #10-3/4 30/2 WASHER/ DRYER 2.5 2.5 •9 GENERAL RECPT. 20/1 12-1 2 13 14 12-1/2 20/1 APPLIANCE 1.5 1.0 1 1 15 16 1 1 REFRIGERATOR 1.5 1.0 17 18 APPLIANCE 1.5 1.0 19 20 U.C. REF. 1.0 1.3 121 22 MICROWAVE 0.8 1.3 23 24 FAX/ PRINTER 0.4 1.0 25 26 LOUNGE RECEPT 0.9 1.1 1 27 28 GEN. RECPT. 0.7 .9 29 30 COFFEE 1.5 .7 31 32 LIGHTING 0.2 •4 SCANNER/ PRINTER 33 34 COPIER 1.5 .4 PHONE/ DATA 35 36 LIGHTING " - r 1-5 1.3 LIGHTING 37 38 GEN. RECPT. =0.7 r = - - 1.5 1 139 40 1 SPACE - 0.8 41 142 #12-1/2 20/1 GEN. RECPT. 15.1 13.0 12.11 TOTAL TOTAL 4.3 TOTAL BUS KVA A: 19.4 KVA TOTAL CONNECTED LOAD: 59.7 KVA =165.8 AMPS B: 20.0 KVA C: 20.3 KVA = = NON-CONCURRANT LOADS LCAAA 003432 Architecture, Inc. 1975 Sansbury's Way Suite 108 West Palm Beach, FL 33411 Phone: (561) 493-4787 Fax: (561) 493-4786 REVISIONS / DATE PROJ. NO. 16181 DESIGNED BY LAC DRAWN BY LC DATE 07/18/16 SCALE AS SHOWN ELECTRICAL _- 'L -AN =TOTES SHEET E.1 0 Oo L a) �+ W a) U) O ■ U_ L. 4-1 _0 U _> �CyU, W ,f 117% '�'^^t V, U O - - �W cn 0 O LJL o O C- ■ , 00 N PROJ. NO. 16181 DESIGNED BY LAC DRAWN BY LC DATE 07/18/16 SCALE AS SHOWN ELECTRICAL _- 'L -AN =TOTES SHEET E.1 KEY NOTES: (A CONNECT NEW SANITARY PIPE INTO EXISTING 4" SANITARY SYSTEM FIELD VERIFY EXACT (D LOCATfON CONNECT TO EXISTING COLD/ HOT WATER UNE AS SHOWN O RE -CIRCULATING PUMP O PIPING RUNS UNDER FLOOR SLAB. 0 PIPING RUNS ABOVE CEILING 0 REUSE EXIST. P&T LINE, NEW PAN AND DRAIN TO MOP SINK BELOW O FOR NEW SINK: USE EXISTING J" COLD WATER LINE. INSTALL NEW HOT WATER LINE AS SHOWN. FOR EXISTING SINK: REUSE COLD WATER, REPLACE HOT WATER LINE AS SHOWN PLUMBING FIXTURE SCHEDULE .NAM F XTURE MODEi._� ACCESSORIES SK -1 SMALL SINK ELKAY BCR -15-2 SPEAKMAN COMMANDER FAUCET SC-3084—LD, FLEXIBLE SUPPLY PIPES, ADJUSTABLE CHROME PLATED TRAP, AND MCGUIRE ANGLE STOPS. FIXTURE NATER PIPE SIZE NOMINAL SAN, SIZE MAXIMUM FLOW RATES SINK 1/201 1 1/2- 2.0 GPM STAINLESS STEEL COVER SCREWED TO THREADED C.O. PLUG FACE OF WALL WALL TYPE CLEANOUT N.T.S. HANGER ROD LOCKING NUT HANGER ROD -------,SUPPORT NUT SUPPORT NUT - �— HEAVY DUTY CLEVIS HEAVY DUTY CLEVI HANGER HANGER VAPOR BARRIER PIPE INSULATION 16 GAUGE ZINC COATED SHEET STEEL SADDLE AT LEAST 8" LONG CLEVIS HANGER CLEVIS HANGER SINGLE HORIZONTAL RUNS SINGLE HORIZONTAL RUNS NO VAPOR BARRIER INSULATION WITH VAPOR BARRIER INSULATION WELDS WW MEMOM ONE ANGLE ON EACH NMS NUT SIDE OF VO QRS ODTMM 011M STEEL Boff SCRAP 1 1/1 J0151S BEIwEEN PMEL LEST OF AN OM V . FOM SRE FOR I= w= ong �' STEEL JOIST STEEL BEAM BEAM NOTE: ALL TRAPS TO. $F 1 1/2' -UC -4. N. fi41N_. SLOPE OF DRAINAGE PIPING SHALL BE 1/4" PER 1 FT. PLUMBING FIXTURES 841 -IX -C OMPL'f WiTH FEC PLUMBING AND ACCE=SS1EILITY--= NOTE: CONTRACTOR TO COORDINATE ALL HEIGHTS AND EXACT LOCATIONS OF ALL UTILITIES WITH TENANT'S EQUIPMENT SUPPLIER PROVIDE BALL TYPE SHUT-OFF VALVES FOR FIXTURE SUPPLY LINES. PLACE VALVES ABOVE CEILING BEFORE LINES ENTER PARTITION CAVITY. SIZE SHALL MATCH PIPE SIZE. PLUMBING SYMBOLS + ABBREVIATIONS �___— _____S HOT WATER PIPE HW �_ _ �� COLD WATER PIPE CW HOT WATER RECIRCULAING HWR CHECK VALVE CV f --S BALL VALVE (SHUT—OFF VALVE) SOV 5S—i STORM DRAINAGE PIPE SD s SANITARY LINE SAN 5 CD CONDENSATE LINE CD VENT LINE .j PRESSURE RELIEF P&T 5 D DRAIN PAN DP HOSE BIBB W/ VACUUM BREAKER & HB + SHUT—OFF VALVE CU WATER HAMMER ARRESTOR WMA WATER CLOSET WC 0 VENT THRU ROOF VTR C' E LAVATORY LAV JANITOR'S SINK JS M (1) FLOOR SINK FS ■ r FLOOR DRAIN FD .p URINAL UR m SHOWER SH o ELECTRIC WATER COOLER EWC DRINKING FOUNTAIN DF C: ELECTRIC WATER HEATER EWH ABOVE FINISH FLOOR AFF BELOW FINISH FLOOR BFF FLOOR CLEANOUT FCO CLEANOUT TO GRADE CTG WALL CLEANOUT WCO ROOF DRAIN RD U-7 MOP SINK MS SINK SK NOTE: NOTE: NOT ALL SYMBOLS & ABBREVIATIONS APPLY I. o. n ' a < ` < s� n1� ,1 Hof 5 Ks � / \ SK. OfH G• I i .� CONNcof TG NEGT i v GO(� 2" WATER RISER DIAGRAM SCALE: N.T.S. I L\ � 1 Nw2 Rei NOTE: WATER LINES ARE 3/4" U.O.N. MATERIAL: HARD DRAWN SEAMLESS COPPER v GIRD• � AGE POMP I f� REP UNIT SANITARY RISER_DIA -RA]V_1 NTS J" 3" V CNT ASID BERG#0 FI �G1 LO p E� Ij ATER/SEWER PLAN kLE. 1/4"=l' -O" 3/4" C.W. HOT WATER t—(110) RETURN HW 3/4" H.W. OUT 1 /2" II II LCAAA 003432 Architecture, Inc. 1975 Sansbury's Way Suite 108 West Palm Beach, FL 33411 Phone: (561) 493-4787 Fax: (561) 493-4786 REVISIONS / DATE 1 7/28/2016 REVISION 1 LESLAW A. CZACZYK AIA \--z �-r.1 tj� -Lu rum j AR 00015391 y WATER HEATER PROD. NO. 16181 120 VOLT POWER AN g SET AT 110 DEG. DISCONNECT SWITCH DESIGNED BY LAC CIRCULATION PUMP-- DRAWN BY LC TACO-006—BC4 OR EQUAL 115V DATE 07/18/16 3/4' EXPANSION 3 4" RELIEF COPPER SCALE AS SHOWN TANK 3/4" CPUC DRAIN PLUMBINGEXPANSION TO EXISTING COLLECTION LINE VALVE /� WATTS #530C PLAN REPLACE DRAIN PAN NOTES 20 GAL. EWH v v DIAGRAMS WATER HEATER PIPING DIAG-RAI1-ri _ DETAILS SCALE: N.T.S. �SHEET P.1 0 0 00 4. N a) .j E o vJ .U_ (D Cl)__ CU 0 n' 0 4-a U) C' E C'U a 00 '0 M (1) C: >' ■ r _ / O .p 0 U m o C: C— 00 N 0 U) U-7 r ; ' LESLAW A. CZACZYK AIA \--z �-r.1 tj� -Lu rum j AR 00015391 y WATER HEATER PROD. NO. 16181 120 VOLT POWER AN g SET AT 110 DEG. DISCONNECT SWITCH DESIGNED BY LAC CIRCULATION PUMP-- DRAWN BY LC TACO-006—BC4 OR EQUAL 115V DATE 07/18/16 3/4' EXPANSION 3 4" RELIEF COPPER SCALE AS SHOWN TANK 3/4" CPUC DRAIN PLUMBINGEXPANSION TO EXISTING COLLECTION LINE VALVE /� WATTS #530C PLAN REPLACE DRAIN PAN NOTES 20 GAL. EWH v v DIAGRAMS WATER HEATER PIPING DIAG-RAI1-ri _ DETAILS SCALE: N.T.S. �SHEET P.1 SPECIFICATIONS GENERAL WORKMANSHIP 1) All manufacturer's recommended installation instructions and specifications are incorporated by reference for all materials installed. This includes U. S. Gypsum manuals for drywall, Armstrong specifications for the acoustical ceiling system, UL specifications for rated wall assemblies, Sherwin Williams specifications for paint, and HVAC, electrical and plumbing equipment manufacturers' specifications. 2) All materials, products, components and equipment shall be installed in a professional manner, and complying with applicable manufacturers' instructions and specifications. The construction, including all materials and labor, shall conform to all applicable city, county, and national building codes. INTERIOR PARTITIONS 1) Unless otherwise specified on the Drawings, all new interior partitions shall be constructed with 20GA galv. metal studs placed ® 24" o.c. max. and 5/8" gypsum wall board. Demising partitions shall be constructed strictly per UL #U465 2) Existing fire rated separation walls (if any) may need to be modified and completed to meet UL and local building codes. All existing unsealed penetrations must be properly sealed with UL approved materials. All existing ductwork designated to remain and penetrating fire rated assemblies shall be supplied with fire dampers. 3) All existing walls within the construction areas that are to remain and that are presently covered with wall covering must be stripped and skim coated to provide a smooth, even, and level surface. After skim coating, walls must be reprimed and recovered with finish per client's finish schedule. 4) Existing walls, which are not demolished per plans (if any), must be refinished if they do not meet specifications of new walls. This requires at minimum: a Any holes to be patched b Any damaged gypsum board to be removed and replaced; C) Any walls previously abutted bydemolished walls shall be refinished by laminating with new layer of gypsum board from corner to comer- as required to obtain a smooth and straight finish without bulges or patch marks. Remove and replace drywall where feasible. Application of a one coat plaster system is an acceptable alternative to laminating or removing and replacing drywall. ACOUSTICAL CEILINGS Ceiling tile: Exact specifications per interior designer unless specified in finish schedule. Ceiling tile cuts must be clean, straight, and tiles shall fit snuggly into grid. Tiles with visible gaps or frayed finished sides will not be accepted. All wall angles must be sealed where meeting drywall. All lights to be secured to ceiling grid with four screws. Grid to have hangers spaced 4'-0" in each direction. No partial tiles less than 12" in the smallest dimension allowed unless approved by architect. FINISHES—GENERAL NOTES (REFER TO OWNERS FINISH SCHEDULE FOR EXACT SPECIFICATIONS) 1) Wall paint shall be water based satin latex, one primer coat and two finish coats, Sherwin Williams or approved equal. Color and placement per finish schedule and/or Owners instructions. 2) Walls to receive VWC (if any) shall be primed with an oil base primer that makes paper strippoble. 3) All paint grade wood shall receive Sherwin Williams oil base enamel semi gloss paint (primer and two coats.) 4) Vinyl Base to be continuous (4' pieces not accepted.) No splices shorter than 4 ft. 5) All new materials and/or patchwork shall be provided to match existing materials and/or adjoining work. 6) All interior walls shall receive gypsum board of thickness as specified on plans and details. 7) All toilet rooms (if any) shall receive 5/8" moisture resistant gypsum board on all walls. 8) All gypsum board walls shall receive finish per finish schedule or Owner's/Tenant instructions as applicable. 9) All gypsum board walls and ceilings shall be taped, troweled and polished. 10) All outside corners at partitions shall have corner beads or "L" beads as applicable. 11) Provide samples for all wood indicated to have transparent, or stain finish. 12) All doors shall be pre—finished STAINED as specified on plans. 13) All doors, windows and rough openings shall be verified with manufacturer's specifications for proper installation. 14) Concrete slabs, new or patches to existing, shall be troweled smooth and level. 15) Provide floor preparation to receive new floor finish. This shall include flush patching and leveling at doorways perimeters and similar areas which might be obvious to the tenant. 16) Provide finishes per Interior Designer/ Tenant. Otherwise conform to building standards. 17) All wood in contact with concrete or masonry shall be pressure treated. 18) Contractor shall coordinate with cabinet sub—contractor and shall supply all necessary supports and blocking required, ready to receive cabinets and/or subsequent finishes. S: A) GENERAL RESPONSIBILITIES 1) Each contractor and subcontractor sholl Visit the site and examine exist. conditions to determine the extent of the work. It shall be the responsibility of each contractor to thoroughly examine and verify existing conditions and to make allowances for them prior to bidding. 2) General contractor and subcontractors shall review drawings prior to bidding and construction and report any discrepancies -to the architect before submitting a bid. 3) General contractor shall verify all dimensions and report any discrepancies to the architect. 4) This project shall conform to the latest edition of the governing building code, and all other Federal, State, County, and local codes, ordinances, rules, and regulations in effect. All those codes and regulations shall take precedence over drawings. 5) Dimensions as indicated on the drawings shall take precedence over scaling of the drawings. 6) These drawings DO NOT show every minor detail of construction. The contractor shall furnish and install all items required for a complete, properly functioning building system, and shall fulfill all requirements for all equipment to be placed in proper working order. Contractor's bid shall include all items and work to assure compliance with most stringent requirements of governing building codes and regulations. 7) Each contractor and subcontractor shall be responsible for the safety and well—being of his employees and shall strictly follow all construction safety regulations, including OSHA. 8) All contractors and subcontractors sholl be currently licensed in the State of Florida, County having jurisdiction, and local cities as required. Provide copies of licenses to Owner prior to commencement of work. 9) All contractors and subcontractors shall carry the minimum workman's compensation, liability, and automobile insurance required by the State of Florida and higher limits if required by the Owner. -Provide insurance certificates to Owner before commencement of work. 10) Should the scope of work, for any reason not be fully indicated on the Drawings, the contractor shall immediately contact architect for clarifications. 11) The Work shall be limited to the scope indicated in the Drawings and specifications. If any additional work is performed without Owner's approval, it shall be at the sole expense of the Contractor. 12) Contractor shall pay for and obtain all permits and secure all certificates of inspections and certificates of occupancy that are required by governing jurisdiction. 13) Any deviation and/or substitution from the information and instructions provided herein shall be submitted to the architect for his approval prior to the performance of the work. ..14) The Contractor shall coordinate all Tenant or Owner supplied items, and V V incorporate it into Contractor's work schedule. Verify scope of such items prior _ ro bid submittal. Tenant Improvement for South Florida Gastroenterology Boynton Beach Medical Pavilion 2800 S. Seacrest Boulevard, Suite 240 BOYNTON BEACH, FLORIDA. KEY PLAN - SECOND FLOOR T.S. NOTE: COMMON AREA PLUMBING FACILITIES TO BE UTILIZED MEET THE CODE REQUIREMENTS AT THE TIME THEY WERE CONSTRUCTED 2 15) The Contractor shall include into bid and provide all temporary utilities required for the Work completion. 16) Each contractor shall protect its own work and work of other contractors. All conflict to be resolved by the General Contractor. The general Contractor shall be responsible for full coordination of work of all trades. Any damages resulting from lack of coordination, lack of work protection shall be sole responsibility of the General Contractor, that includes all damages from weather, water, and dust. 17) The contractor shall expedite and schedule the delivery of long lead items to conform with the work schedule. 18) The Contractor shall warrant and guarantee all work, all component performance, and all materials for one year from the date shown on the certificate of occupancy. B) SCHEDULES, ORGANIZATION AND COORDINATION 1) Contractor shall be responsible for scheduling and implementing all work so as not to disrupt or inconvenience adjacent property users. C) CLEANING REQUIREMENT 1) The job site shall be maintained in a safe and neat condition at all times. Broom cleaning shall be performed as needed to avoid debris build up. 2) All building materials shall be stored in a safe and organized manner so as not to interfere with the work of other trades. 3) At project completion, the job site shall be fully cleaned and turned over to occupant ready for them to move in and begin operating without any additional work or cleaning. This requires all surfaces to be cleaned with appropriate cleaning solutions, vacuumed, and waxed/sealed as appropriate. All mirrors, windows, hardware, cabinetry, walls finished and fixtures shall be cleaned. All filters to be replaced. D) ROOF PENETRATIONS 1) Any roof penetrations such as vents, chimneys equipment curbs and syklights required shall be flashed and sealed to be water tight. If roof is under warranty or bonded, the general contractor shall hire the warranting roofing or bonding company to perform all roof modification work. E) CODE NOTES 1) Provide U.L. — rated fire extinguishers (min. rating of 10 LB. ABC) located within 75 ft. max. travel diserce from_nny Toint n the tenant space. Obtain Fire Marshal approval of locctions.- P1 a mir-imurrt provide- two extinguishers; one located near front exit Li an--obMuc-Iocat;drt and ttye �se and located near the rear or secondary exit in an obvious locditiah." Ali extinguishers to have updated inspection labels. 2) All penetrations in- fire rated astemnlie:F� Oa, be. -sealed with materials approved by governing agencies maetir4 UL to( equdl) specifications including installation system. All ducts penetrating fire rated assemblies shall receive fire dampers. m 3) All exit doors shall have hardware per N.F.P.A. standards. All exit door locks shall have thumb latches requiring less than an 180 degree turn. Entry lacks shall not require key operation in direction of exit. 4) Adhere to building standards for work affecting common areas 5) All doors in rated walls to be U.L. labeled, both door and jamb, with U.L. closers. 6) Fire resistive standard for interior finishes shall be as required per NFPA 101. Documentation shall be provided to the Architect prior to final inspection. 7) All new walls, ceiling grids, lights, conduits, pipes, ducts and wires, whether new or existing, to be braced, strapped, and/or supported per code, and shall meet U.L., and manufacturer specifications. 8) All fixtures and hardware shall comply with ADA and FBC—Accessibility. 9) Testing for the presence of the hazardous materials shall be the Owners responsibility. 10) All glass in doors and within 4'-0" of doors shall be tempered. F) SHOP DRAWINGS 1) Provide shop drawings for cabinetry and as noted in drawings. G) CLOSE OUT REQUIREMENTS—CONTRACTOR SHALL PROVIDE FOLLOWING DOCUMENTATION IN COMPLIANCE WITH FBC CHAPTER 13 1) As—built drawings 2) 0 & M manuals, Installed Options Information and Equipment Rating Information 3) Training 4) Warranties 5) Excess materials 6) Name and Address of at least one Service Agency. Electrical Power --Drawings: Construction documents shall require that within 30 days after the date of system acceptance, record drawings of the actual installation shall be provided to the building owner, including: 1) A single—line diagram of the building electrical distribution system and 2) Floor plans indicating location and area served for all distribution. Manuals: Construction documents shall require that an operating monual and maintenance manual be provided to the building owner. The manuals shall include,.. at c min mum, the -following: 1) Submittal data stating equipment rating and selectee oppnn ror--each piece �of aquip�nent requiring maintenance. 2) Operation manuals and maintenance manuals for each piece of equipment requiring maintenance. Required routine maintenance actions shall be clearly identified. 3) Names and addresses of at least one qualified aer_A agency. N LOCATION MAP N.T.S. VERIFICA TPON OF EXISTING CONDITIONS REQUIRED CONTRACTOR` SHALL FIELD VERIFY ALL EXISTING CONDITIONS, AND DETERMINE WHAT ITEMS SHALL BE REUSED AND WHAT MUST BE REPLACED. ALSO, ALL ITEMS SHOWN ON DRAWINGS AS EXISTING SHALL BE FIELD VERIFIED FOR CONDITION, PROPER SIZE, FUNCTIONALITY, LOCATION AND CODE COMPLIANCE. ALL DISCREPANCIES SHALL BE REPORTED TO THE ARCHITECT PRIOR TO SUBMITTING A BID. THE BID SHALL INCLUDE ALL ITEMS REQUIRED FOR COMPLETE, PROPERLY FUNCTIONING BUILDING SYSTEMS. BEFORE CUTTING CONCRETE SLAB, CONTRACTOR SHALL VERIFY UNDER SLAB CONDITIONS WITH GROUND PENETRATING RADAR, TO AVOID IMPACTING UNDERGROUND BUILDING SERVICES AND STRUCTURES. PROJECT DESCRIPTION THIS IS A MINOR RENOVATION TO EXISTING SUITE. ALL FINISHES ARE REPLACED, ALL MILLWORK IS REPLACED ONE DOOR IS REPLACED, MINOR ELECTRICAL DEVICE RELOCATION, ADDITION OF SINKS. NO HVAC WORK NO CEILING WORK EXCEPT WAITING ROOM LIGHTS REPLACED ONE FOR ONE WITH LED. WALLS ARE NOT MOVED OR REMOVED OR CHANGED. PROJECT DATA DRAWING LIST CODES7ULES T.1 TITLE SHEET FLORIDA BUILDING CODE, 5th EDITION, 2014 FLORIDA BUILDING CODE—EXISTING, 5th EDITION, 2014 A.0 DEMOLITION PLAN NATIONAL ELECTRICAL CODE 2011 (NFPA 70) A.1 FLOOR PLAN, NOTES, SCHED FLORIDA FIRE PREVENTION CODE, 5TH EDITION W/AMENDMENTS A,2 DETAILS LIFE SAFETY CODE, NFPA 101 — 2012 FIRE CODE, NFPA 1 — 2012 EA ELECTRICAL PLAN, NOTES, DIAGRAMS EXISTING BUILDING: TYPE VB, TWO STORY, SPRINKLED P.1 PLUMBING PLAN, NOTES, DIAGRAMS OCCUPANCY OCCUPANCY GROUP: B (NEPA 101 NEW BUSINESS PER CHAPTER 38) OCUPANCY COUNT. 25 AREAS TOTAL UNDER CONSTRUCTION (NET): 2,589 SF ALTERATION LEVEL: 2 HAZARD OF CONTENT: ORDINARY SPRINKLER NOTES 1) Fre Sprinkler System shall be installed by an approved automatic fire sprinkler contractor who must submit complete specifications, drawings and calculations signed and sealed by Florida registered professional Engineer. The system shall comply with NFPA sections 13,14,20 and all applicable codes and ordinances in effect. 2) Sprinkler head style shall be concealed and match existing building standard. 1 FIRE ALARM NOTES V - - --= 1) Fire Alarm System shall be installed by an approved fire alarm contractor who must submit complete specifications, drawings and calculations signed and sealed by Florida registered professicrcl Epgineer. The--systeixi shflll:comply with NFPA and all applicable codes and ordinances a effect. _ - - - - - - - - 2) Contractor shall verify exist. building fire alarm system and its capacity to accommodate new devices BEFORE BID.. Fire alarm system for this project shall be fully integrated with building fire alarm system _and ipcfudp all req&ed modifications. LCAAA 003432 Architecture, Inc. 1975 Sainsbury's Way Suite 108 West Palm Beach, FL 33411 Phone: (561) 493-4787 Fax: (561) 493-4786 REVISIONS / DATE 1 7/28/2016 REVISION 1 Z2\ 8/23/2016 REVI PROD. NO. 16181 DESIGNED BY LAC DRAWN BY LC DATE 07/18/16 SCALE AS SHOWN TITLE SHEET SHEET T.1 0 0 00 ( N -F-+ E 0 U .U_ n> F -C C/) > 0 c 0 CU CO a) 1. (D -, 4Cn m E (U N " C) C: 0 .0 M ..- W 0 .0 0 U) 0 C- 00 N 0 U) PROD. NO. 16181 DESIGNED BY LAC DRAWN BY LC DATE 07/18/16 SCALE AS SHOWN TITLE SHEET SHEET T.1 SPECIFICATIONS GENERAL WORKMANSHIP 1) All manufacturer's recommended installation instructions and specifications are incorporated by reference for all materials installed. This includes U. S. Gypsum manuals for drywall, Armstrong specifications for the acoustical ceiling system, UL specifications for rated wall assemblies, Sherwin Williams specifications for paint, and HVAC, electrical and plumbing equipment manufacturers' specifications. 2) All materials, products, components and equipment shall be installed in a professional manner, and complying with applicable manufacturers' instructions and specifications. The construction, including all materials and labor, shall conform to all applicable city, county, and national building codes. INTERIOR PARTITIONS 1) Unless otherwise specified on the Drawings, all new interior partitions shall be constructed with 20GA gals. metal studs placed ® 24" o.c. max. and 5/8" gypsum wall board. Demising partitions shall be constructed strictly per UL #0465 2) Existing fire rated separation walls (if any) may need to be modified and completed to meet UL and local building codes. All existing unsealed penetrations must be properly sealed with UL approved materials. All existing ductwork designated to remain and penetrating fire rated assemblies shall be supplied with fire dampers. 3) All existing walls within the construction areas that are to remain and that are presently covered with wall covering must be stripped and skim coated to provide a smooth, even, and level surface. After skim coating, walls must be reprimed and recovered with finish per client's finish schedule. 4) Existing walls, which are not demolished per plans (if any), must be refinished if they do not meet specifications of new walls. This requires at minimum: a Any holes to be patched b Any damaged gypsum board to be removed and replaced; c Any walls previously abutted by demolished walls shall be refinished by laminating with new layer of gypsum board from corner to comer- as required to obtain a smooth and straight finish without bulges or patch marks. Remove and replace drywall where feasible. Application of a one coat plaster system is an acceptable alternative to laminating or removing and replacing drywall. ACOUSTICAL CEILINGS Ceiling tile: Exact specifications per interior designer unless specified in finish schedule. Ceiling tile cuts must be clean, straight, and tiles shall fit snuggly into grid. Tiles with visible gaps or frayed finished sides will not be accepted. All wall angles must be sealed where meeting drywall. All lights to be secured to ceiling grid with four screws. Grid to have hangers spaced 4'-0" in each direction. No partial tiles less than 12" in the smallest dimension allowed unless approved by architect. FINISHES -GENERAL NOTES (REFER TO OWNERS FINISH SCHEDULE FOR EXACT SPECIFICATIONS) 1) Wall paint shall be water based satin latex, one primer coat and two finish coats, Sherwin Williams or approved equal. Color and placement per finish schedule and/or Owner's instructions. 2) Walls to receive VWC (if any) shall be primed with an oil base primer that makes paper strippable. 3) All paint grade wood shall receive Sherwin Williams oil base enamel semi gloss paint (primer and two coats.) 4) Vinyl Base to be continuous (4' pieces not accepted.) No splices shorter than 4 ft. 5) All new materials and/or patchwork shall be provided to match existing materials and/or adjoining work. 6) All interior walls shall receive gypsum board of thickness as specified on plans and details. 7) All toilet rooms (if any) shall receive 5/8" moisture resistant gypsum board on all walls. 8) All gypsum board walls shall receive finish per finish schedule or Owner's/Tenant instructions as applicable. 9) All gypsum board walls and ceilings shall be taped, troweled and polished. 10) All outside corners at partitions shall have corner beads or "L" beads as applicable. 11) Provide samples for all wood indicated to have transparent, or stain finish. 12) All doors shall be pre -finished STAINED as specified on plans. 13) All doors, windows and rough openings shall be verified with manufacturer's specifications for proper installation. 14) Concrete slabs, new or patches to existing, shall be troweled smooth and level. 15) Provide floor preparation to receive new floor finish. This shall include flush patching and leveling at doorways perimeters and similar areas which might be obvious to the tenant. 16) Provide finishes per Interior Designer/ Tenant. Otherwise conform to building standards. 17) All wood in contact with concrete or masonry shall be pressure treated. 18) Contractor shall coordinate with cabinet sub -contractor and shall supply all necessary supports and blocking required, ready to receive cabinets and/or subsequent finishes. GENERAL NOTE : A) GENERAL RESPONSIBILITIES 1) Each contractor and subcontractor shall visit the site and examine exist. conditions to determine the extent of the work. It shall be the responsibility of each contractor to thoroughly examine and verify existing conditions and to make allowances for them prior to bidding. 2) General contractor and subcontractors shall review drawings prior to bidding and construction and report any discrepancies to the architect before submitting a bid. 3) General contractor shall verify all dimensions and report any discrepancies to the architect. 4) This project shall conform to the latest edition of the governing building code, and all other Federal, State, County, and local codes, ordinances, rules, and regulations in effect. All those codes and regulations shall take precedence over drawings. 5) Dimensions as indicated on the drawings shall take precedence over scaling of the drawings. 6) These drawings DO NOT show every minor detail of construction. The contractor shall furnish and install all items required for a complete, properly functioning building system, and shall fulfill all requirements for all equipment to be placed in proper working order. Contractor's bid shall include all items and work to assure compliance with most stringent requirements of governing building codes and regulations. 7) Each contractor and subcontractor shall be responsible for the safety and well-being of his employees and shall strictly follow all construction safety regulations, including OSHA. 8) All contractors and subcontractors shall be currently licensed in the State of Florida, County having jurisdiction, and local cities as required. Provide copies of licenses to Owner prior to commencement of work. 9) All contractors and subcontractors shall carry the minimum workman's compensation, liability, and automobile insurance required by the State of Florida and higher limits if required by the Owner. Provide insurance certificates to Owner before commencement of work. 10) Should the scope of work, for any reasonnot be fully indicated on the Drawings, the contractor shall immediately contact architect for clarifications. 11) The Work shall be limited to the scope indicated in the Drawings and specifications. If any additional work is performed without Owner's approval, it shall be at the sole expense of the Contractor. 12) Contractor shall pay for and obtain all permits and secure all certificates of inspections and certificates of occupancy that are required by governing jurisdiction. 13) Any deviation and/or substitution from the information and instructions provided herein shall be submitted to the architect for his approval prior to the performance of the work. 14) The Contractor shall coordinate all Tenant or Owner supplied items, and v - incorporate it into Contractor's work schedule. Verify scope of such items prior to bid submittal. v - - - - v - V Tenant Improvement for South Florida Gastroenterology Boynton Beach Medical Pavilion 2800 S. Seacrest Boulevard, Suite 240 BOYNTON BEACH, FLORIDA. 15) The Contractor shall include into bid and provide all temporary required for the Work completion. 16) Each contractor shall protect its own work and work of other All conflict to be resolved by the General Contractor. The general shall be responsible for full coordination of work of all trades. An) resulting from lack of coordination, lack of work protection shall responsibility of the General Contractor, that includes all damages water, and dust. 17) The contractor shall expedite and schedule the delivery of Ion( with the work schedule. 18) The Contractor shall warrant and guarantee all work, all comp performance, and all materials for one year from the date showr the certificate of occupancy. B) SCHEDULES, ORGANIZATION AND COORDINATION 1) Contractor shall be responsible for scheduling and implementing all work so as not to disrupt or inconvenience adjacent property users. Z KEY PLAN - $ O FLOOR N.T.S. r C) CLEANING REQUIREMENT 1) The job site shall be maintained in a safe and neat condition at all times. Broom cleaning shall be performed as needed to avoid debris build up. 2) All building materials shall be stored in a safe and organized manner so as not to interfere with the work of other trades. 3) At project completion, the job site shall be fully cleaned and turned over to occupant ready for them to move in and begin operating without any additional work or cleaning. This requires all surfaces to be cleaned with appropriate cleaning solutions, vacuumed, and waxed/sealed as appropriate. All mirrors, windows, hardware, cabinetry, walls finished and fixtures shall be cleaned. All filters to be replaced. D) ROOF PENETRATIONS 1) Any roof penetrations such as vents, chimneys equipment curbs and syklights required shall be flashed and sealed to be water tight. If roof is under warranty or bonded, the general contractor shall hire the warranting roofing or bonding company to perform all roof modification work. E) CODE NOTES 1) Provide U.L. - rated fire extinguishers (min. rating of 10 LB. ABC) located within 75 ft. max. travel distance from any point in the tenant space. Obtain Fire Marshal approval of Iccations„ At -e minimum provide two extinguishers; one located near front exit Lh an--obvitiuz lgcaticrn and tf:e second located near the rear or secondary e=xit it ori ?)byi ris 19iAtior'. A"" extinguishers to have updated inspection labels. - - 2) All penetrations iav fire Yated jssem»lies shah b6 sealed with materials approved by governing- agc;ncics : rm6etir,g K l nr equal) specifications including installation system. -Ai duets penetcatiq fire -raie6 assemblies shall receive fire dampers. 3) All exit doo shall haveJre per N.F.P A. standards. All exit door locks shat! have umb latcng less than an 180 degree tum. Entry locks shall not re ' e key in direction of exit. 4) Adhere to building standards for work affecting common areas 5) All doors in rated walls to be U.L. labeled, both door and jamb, with U.L. closers. 6) Fire resistive standard for interior finishes shall be as required per NFPA 101. Documentation shall be provided to the Architect prior to final inspection. 7) All new walls, ceiling grids, lights, conduits, pipes, ducts and wires, whether new or existing, to be braced, strapped, and/or supported per code, and shall meet U.L., and manufacturer specifications. 8) All fixtures and hardware shall comply with ADA and FBC-Accessibility. 9) Testing for the presence of the hazardous materials shall be the Owners responsibility. 10) All glass in doors and within 4'-0" of doors shall be tempered. F) SHOP DRAWINGS 1) Provide shop drawings for cabinetry and as noted in drawings. G) CLOSE OUT REQUIREMENTS -CONTRACTOR SHAH PROVIDE FOLLOWING DOCUMENTATION IN COMPLIANCE WITH FBC CHAPTER 13 1) As -built drawings 2) 0 & M manuals, Installed Options Information and Equipment Rating Information 3) Training 4) Warranties 5) Excess materials 6) Name and Address of at least one Service Agency. Electrical Power --Drawings: Construction documents shall require that within 30 days after the date of system acceptance, record drawings of the actual installation shall be provided to the building owner, including: 1) A single -line diagram of the building electrical distribution system and 2) Floor plans indicating location and area served for all distribution. Manuals: Construction documents shall require that an operating manual and maintenance manual be provided to the building owner. The manuals shall include, at a minimum, the following: 1) Submittal data stating equipment rating and selected options for each piece of equipment requiring maintenance. --- --2)2) Operation manuals and maintenance manuals for each piece 6f zqr ipm&it rouir-ng maintenance. Required routine maintenance actions ,,qholl be-c;eaJv-ideatified._ = _ 3) Names and addresses of at least one qualified service agency. FIRE DEF 1. NV I ItUt: SEPARATE PERMITS FIRE SPRINKLER SYSTEMS/STANDPIPES/FIRE PUMPS; FIRE ALARM SYSTEMS; FIRE SUPPRESSION SYSTEMS; TYPE I GREASE HOODS/FIRE SUPPRESSION SYSTEMS; PAINT SPRAY BOOTHS/FIRE SUPPRESSION SYSTEMS; RACKS OVER 8 FEET; CLEAN AGENT SYSTEMS N (1)LOCATION MAP N.T.S. VERIFICATION OF EXISTING CONDITIONS REQUIRED c� CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS, AND DETERMINE WHAT ITEMS SHALL BE REUSED AND WHAT MUST BE REPLACED. ALSO, ALL ITEMS SHOWN ON DRAWINGS AS EXISTING SHALL BE FIELD VERIFIED FOR CONDITION, PROPER SIZE, FUNCTIONALITY, LOCATION, AND CODE COMPLIANCE. ALL DISCREPANCIES SHALL BE REPORTED TO THE ARCHITECT PRIOR TO SUBMITTING A BID. THE BID SHALL INCLUDE ALL ITEMS REQUIRED FOR COMPLETE, PROPERLY FUNCTIONING BUILDING SYSTEMS. BEFORE CUTTING CONCRETE SLAB, CONTRACTOR SHALL VERIFY UNDER SLAB CONDITIONS WITH GROUND PENETRATING RADAR, TO AVOID IMPACTING UNDERGROUND BUILDING SERVICES AND STRUCTURES. PROJECT DESCRIPTION THIS IS A MINOR RENOVATION TO EXISTING SUITE. ALL FINISHES ARE REPLACED, ALL MILLWORK IS REPLACED ONE DOOR IS REPLACED, MINOR ELECTRICAL DEVICE RELOCATION, ADDITION OF SINKS. NO HVAC WORK NO CEILING WORK EXCEPT WAITING ROOM LIGHTS REPLACED ONE FOR ONE WITH LED. WALLS ARE NOT MOVED OR REMOVED OR CHANGED. PROJECT DATA DRAWING LIST CODES FLORIDA BUILDING CODE, 5th EDITION, 2014 T.1 TITLE SHEET FLORIDA BUILDING CODE -EXISTING, 5th EDITION, 2014 A.1 FLOOR PLAN, NOTES, SCHEDULES NATIONAL ELECTRICAL CODE 2011 (NFPA 70) A,2 DETAILS FLORIDA FIRE PREVENTION CODE, 5TH EDITION W/AMENDMENTS LIFE SAFETY CODE, NEPA 101 - 2012 E.1 ELECTRICAL PLAN, NOTES, DIAGRAMS FIRE CODE, NFPA 1 - 2012 P.1 PLUMBING PLAN, NOTES, DIAGRAMS EXISTING BUILDING: TYPE VB, TWO STORY, SPRINKLED OCCUPANCY GROUP: B (NFPA 101 NEW BUSINESS PER CHAPTER 38) OCUPANCY COUNT: 25 AREAS TOTAL UNDER CONSTRUCTION (NET): 2,589 SF ALTERATION LEVEL: 2 HAZARD OF CONTENT: ORDINARY SPRINKLER NOTES 1) Fire Sprinkler System shall be installed by an approved automatic fire sprinkler contractor who must submit complete specifications, drawings and calculations signed and sealed by Florida registered professional Engineer. The system shall comply with NFPA sections 13,14,20 and all applicable codes and ordinances in effect. 2) Sprinkler head style shall be concealed and match existing building standard. FIRE ALARM NOTES f, 1) Fire Alarm System shall be installed by an approve -o drawings and calculations signed and sealed by Florida regisu�, and all applicable codes and ordinances in effect. 2) Contractor shall verify exist. building fire alarm system and its alarm system for this project shall be fully integrated with building itractor _who''rn�is! tulimit-ombete; spe,-ifications, ^ssional-- Enplesr_- The- sy.-tern thalr comply with NEPA ,V -to --occomi iod&t-.- new -devises BEFORE BID.. Fire .ATT system-,iod nclu&-all �e�uired modifications. LCAAA 003432 Architecture, Inc. 1975 Sansbury's Way Suite 108 West Palm Beach, FL 33411 Phone: (561) 493-4787 Fax: (561) 493-4786 REVISIONS / DATE # DATES„+.�� J 0 0 0 0 42, d' N C+C. 4-0 E o Cn . U. 0 > C/)— 0° (0 0 CU (D �Wm CZ CU a) (-) C:E A --a �O M a C: �. W 0 .00(6m 0 C co N 0 VJ PROJ. NO. 16181 DESIGNED BY LAC DRAWN BY LC DATE 07/18/16 SCALE AS SHOWN TITLE SHEET SHEET T.1 FIELD VERIFICATION OF EXISTING CONDITIONS REQUIRED CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS, AND DETERMINE WHAT ITEMS SHALL BE REUSED AND WHAT MUST BE REPLACED. ALSO, ALL ITEMS SHOWN ON DRAWINGS AS EXISTING SHALL BE FIELD VERIFIED FOR CONDITION, PROPER SIZE, FUNCTIONALITY, LOCATION AND CODE COMPLIANCE. ALL DISCREPANCIES SHALL BE REPORTED TO THE ARCHITECT PRIOR TO SUBMITTING A BID. THE BID SHALL INCLUDE ALL ITEMS REQUIRED FOR COMPLETE, PROPERLY FUNCTIONING BUILDING SYSTEMS. KEYNOTES �f REMOVE EXISTING CABINETRY AND COUNTERTOPS. �2 REMOVE EXISTING WALL BASE AND FLOORING. �3 REMOVE EXISTING SINK. O REMOVE EXISTING CABINETS AND SALVAGE FOR REUSE OEXISTING CABINETS TO REMAIN. �6 REMOVE EXISTING DOOR AND FRAME �7 REMOVE EXISTING HIGH HATS FOR REPLACEMENT. REFER TO ELECTR. PLAN. DEMOLITION LEGEND SOLID LINES INDICATE EXISTING ITEMS TO REMAIN. T_- - DASHED LINES INDICATE EXISTING ITEMS TO BE DEMOLISHED. DEMOLITION NOTES 1. PROVIDE NOTICE TO, AND ACQUIRE ALL NECESSARY PERMITS FROM AGENCIES HAVING JURISDICTION OVER DEMOLITION. 2. EXISITNG PARTITIONS TO REMAIN 3. EXISTING ELECTRICAL PANEL TO REMAIN 4. EXISTING CEILINGS TO REMAIN 5. EXISTING HVAC TO REMAIN 6. EXISTING PLUMBING TO REMAIN UNLESS NOTED OTHERWISE 7• REMOVE ALL FLOOR & WALL FINISHES AND ALL CABINETS 8. PRIOR TO DEMOLITION VERIFY THAT ALL APPROPRIATE UTILITIES HAVE BEEN DISCONNECTED AND MADE SAFE. 9. CONTROL AS MUCH AS PRACTICABLE THE SPREAD OF DUST AND DIRT. OBSERVE ENVIRONMENTAL PROTECTION REGULATIONS. 10. PROMPTLY DISPOSE OF MATERIALS RESULTING FROM DEMOLITION OPERATIONS. DO NOT ALLOW MATERIALS TO ACCUMULATE ON SITE. 11. TRANSPORT MATERIALS RESULTING FROM DEMOLITION OPERATIONS AND LEGALLY DISPOSE OFF-SITE. 12. UPON COMPLETION OF DEMOLITION OPERATIONS, REMOVE ALL TOOLS AND EQUIPMENT AND DISPOSE OFF-SITE ALL REMAINING DEBRIS. 13. LEAVE ALL AREAS (INCLUDING EXTERIOR) NOT AFFECTED BY DEMOLITION, FREE OF DEBRIS. 14. RETURN STRUCTURES AND SURFACES TO REMAIN TO CONDITION EXISTING PRIOR TO COMMENCEMENT OF DEMOLITION. 15. PATCH AND FIX ALL EXISTING DAMAGED FLOOR AND WALL SURFACES. PREPARE WALL AND FLOOR SURFACES TO RECEIVE NEW FINISHES. 16. COORDINATE WITH BUILDING OWNER/MANAGER ROUTES FOR WORKMEN, LOCATION OF DUMPSTERS, PARKING FOR WORKMEN, AND TIMES OF ANY UTILITY DISRUPTIONS. DEMOLITION PLAN SCALE: 1/4"=1'-0" II LCAAA 003432 Architecture, Inc. 1975 Sansbury's Way Suite 108 West Palm Beach, FL 33411 Phone: (561) 493-4787 Fax: (561) 493-4786 REVISIONS / DATE DATE in+i„n LESLAW A. CZACZYK All vv J 1 � 201 AR 00015391 PROD. NO. 16181 DESIGNED BY LAC DRAWN BY LC DATE 07/18/16 SCALE AS SHOWN DEMO PLAN NOTES SHEET A.O O 0 00 Lf.. (1) N 4.j C. .F -J C-'~ a) a tt:�3 E0ILL VJ a) -�-+U Cco CO O CCS a) 0 -U+ CL E CU (D U C- 0 4_j (� a) > W0 .0 0m v J 0 4-400 C� C- N 4-+ _ O U) LESLAW A. CZACZYK All vv J 1 � 201 AR 00015391 PROD. NO. 16181 DESIGNED BY LAC DRAWN BY LC DATE 07/18/16 SCALE AS SHOWN DEMO PLAN NOTES SHEET A.O PLAN LEGEND EXISTING CMU EXTERIOR WALL. SEE STRUCTURAL DRAWINGS. EXISTING 1 -HR FIRE RATED WALL EXISTING PARTITION - — — — — — - KNEE WALL 1 A.5 DENOTES DETAIL P1 DENOTES WALL TYPE, SEE DETAIL SHEET 1 WALL SECTION/ SHEET NUMBER A.5 1 BUILDING SECTION/ A.5 SHEET NUMBER DENOTES INTERIOR ELEVATIONS (00 DOOR MARK/NUMBER FE WALL HUNG FIRE ROOM NAME EXTINGUISHER FEC SEMI RECESSED FIRE �Q EXTINGUISHER CABINET PLAN NOTES 1) ALL FURNITURE IS NOT IN CONTRACT. (N.I.C.) U.O.N. 2) PROVIDE 2" BUILDING STANDARD WINDOW BLINDS FOR ALL WINDOWS. 3) ALL SLABS CORING AND PENETRATION PROTECTIONS SHALL BE INCLUDED 4) CONTRACTOR TO PREP FLOOR TO ACCEPT FINISH AND TO VISIT SITE TO DETERMINE FLOOR LEVELNESS PRIOR TO BID. 5) ALL PLUMBING AND ELECTRICAL LINES ARE TO BE CONCEALED UNLESS OTHERWISE SPECIFIED. 6) ALL INTERIOR FINISHES SHALL COMPLY WITH NFPA 101 AND FBC. 7) WALL THICKNESS ARE SHOWN AS NOMINAL. ALLOW FOR ACTUAL THICKNESS DURING LAYOUT. RESTROOM DIMENSIONS ARE MINIMUM CLEAR. 8) PROVIDE S.S. SURFACE MOUNTED BRADLEY PAPER TOWEL DISPENSER NEXT TO EACH SINK. 9) ALL CLOSET SHELVING TO BE MADE OF WHITE MELAMINE. (1) 24" DEEP. SHELF @ 24" A.F.F. (WHERE SPACE PERMITS) AND (4) 16" DEEP SHELVES 14" O.C. VERTICALLY, UNLESS OTHERWISE REQUESTED BY CLIENT. 10) ALL WALL HUNG LAVATORIES SHALL HAVE CHAIR CARRIERS. N.I.C. - NOT IN CONTRACT - ITEMS TO BE PURCHASED BY CLIENT. CONTRACTOR TO PREPARE SITE AND UTILITIES AS SHOWN. ALL BLOCKING/REINFORCING FOR N.I.C. ITEMS TO BE INCLUDED IN BID. PLAN KEYNOTES 01 RELOCATED WALL CABINETS FROM THE OFFICE ROOM #118. PROVIDE BACKING O COUNTER @ 30" A.F.F. �3 EXISTING RESTROOM TO REMAIN O INSTALL WOOD WALL BASE AND PORCELAIN TILE FLOORING. SEE FINISH SCHEDULE. O GRANITE COUNTERTOP. SEE FINISH NOTES. OLAMINATED COUNTERTOP O7 WIRE GROMMET TYP. Q8 NEW EXAM ROOM CABINETS, SEE TYPICAL ELEVATION O9 EXISTING CABINETS TO REMAIN EXISTING CABINETS TO REMAIN PLAN ABBREVIATIONS: FF FILE, FILE BBF DRAWER BOX, DRAWER BOX, FILE BFF DRAWER BOX, FILE, FILE CONTRACTOR SHALL EXAMINE PROVIDED EQUIPMENT SPECIFICATIONS AGAINST PROVIDED PLANS AND ISSUE REQUESTS FOR CLARIFICATION PRIOR TO BID. IF NO REQUEST IS ISSUED & RESPONDED TO FOR A GIVEN ITEM EQUIPMENT SPECIFICATION WILL GOVERN THESE PLANS. LCA'A 003432 Architecture, Inc. 1975 Sansbury's Way Suite 108 West Palm Beach, FL 33411 Phone: (561) 493-4787 Fax: (561) 493-4786 REVISIONS / DATE # DATE Descri tion 0 DOOR AND ROOM FINISH SCHEDULE Number ROOM NAME FLOOR BASE MATERIAL FINISH WALLS CEILING NOTES N S E W MATL 100 OFFICE PT VINYL STAIN PAINT :PAINT PAINT PAINT ACC -1 -- 101 EXAM PT VINYL STAIN PAINT PAINT PAINT PAINT ACC -1 -- 102 EXAM PT VINYL STAIN PAINT PAINT PAINT PAINT ACC -1 -- 103 EXAM PT VINYL STAIN PAINT PAINT PAINT PAINT ACC -1 -- 104 EXAM PT VINYL STAIN PAINT PAINT PAINT PAINT ACC -1 -- 105 OFFICE PT VINYL` STAIN PAINT PAINT PAINT PAINT ACC -1 -- 106 HALL 4 PT VINYL STAIN PAINT PAINT PAINT PAINT ACC -1 -- 107 HALL 3 PT VINYL STAIN PAINT PAINT PAINT PAINT ACC -1 -- 108 STOG. PT VINYL STAIN PAINT PAINT PAINT PAINT ACC -1 -- 109 OFFICE PT VINYL STAIN PAINT PAINT PAINT PAINT ACC -1 -- 110 NURSE PT VINYL STAIN PAINT PAINT 1PAINT I PAINT ACC -1 -- 111 HALL 2 PT VINYL STAIN PAINT PAINT PAINT I PAINT ACG -1 -- 112 SP. PROC. PT VINYL STAIN PAINT PAINT PAINT I PAINT ACC -1 -- 113 OFFICE PT VINYL STAIN PAINT PAINT PAINT I PAINT ACC -1 -- 114 RESTROOM EXIST. EXIST. E(IST. PAINT PAINT PAINT I PAINT ACC -1 -- 115 EXAM PT VINYL STAIN PAINT PAINT PAINT PAINT ACC -1 -- 116 PHONE PT VINYL STAIN PAINT PAINT PAINT PAINT ACC -1 -- 117 HALL 1 PT VINYL STAIN PAINT PAINT PAINT PAINT ACC -1 -- 118 1OFFICE PT VINYL STAIN PAINT PAINT I PAINT PAINT ACC -1 -- 119 BREAK PT VINYL STAIN PAINT PAINT I PAINT PAINT ACC -1 -- 120 BUSINESS PT VINYL STAIN PAINT PAINT PAINT PAINT ACC -1 -- 121 WAITING PT VINYL STAIN PAINT PAINT PAINT PAINT ACC -1 -- 122 UTILITY PT VINYL STAIN PAINT PAINT PAINT PAINT ACC -1 FINISH NOTES CONTRACTOR SHALL VERIFY ALL SELECTIONS WITH CLIENT PRIOR TO INSTALLAN. Al PORCELAIN TILE: FLORIDATILE PT. 6"x24" - BERKSHIRE - HICKORY FT1255356X24 *PROVIDE ACTUAL GROUT SAMPLES FOR APPROVAL VINYL: SCULPTURED WALL BASE: MANNINGTON COMMERCIAL, ETCHED, COLOR TO BE DETERMINED PAINT: TO BE DETERMINED, QUOTE 3 COLORS, BASE COLOR, SOFFIT WHITE AND ACCENT COLOR - ONE WALL IN EACH EXAM/ OFFICE LAMINATE: PLAM-1: TO BE DETERMINED, STANDARD LAMINATES GRANITE: MARBLE OF THE WORLD ACC -1: EXISTING TILES REPLACE GNT: MADURA GOLD DAMAGED ONLY FINISH REQUIREMENTS ALL WALL AND CEILING FINISHES IN PASSAGEWAYS SHALL CONFORM TO CLASS B REQUIREMENTS OF FBC. ALL WALL AND CEILING FINISHES IN ROOMS AND ENCLOSED SPACES SHALL CONFORM TO CLASS C REQUIREMENTS OF FBG. ALL FLOOR FINISHES SHALL CONFORM TO CLASS II REQUIREMENTS OF FBC. LCA'A 003432 Architecture, Inc. 1975 Sansbury's Way Suite 108 West Palm Beach, FL 33411 Phone: (561) 493-4787 Fax: (561) 493-4786 REVISIONS / DATE # DATE Descri tion 0 DOOR AND FRAME SCHEDULE GENERAL DOOR NOTES � C- CL) DOOR FRAME FIRE HARDW. 0 U) U. > SIZE -a > 1) NEW DOORS TO HAVE WALL MOUNTED OR FLOOR MARK STYLE MATERIAL FINISH RATING NOTES MOUNTED DOORSTOPS AS APPLICABLE. M Lc: E CQ a) U WD HGT THK MATERIAL FINISH LABEL SET KEY 2) ALL METAL FRAME DOORS TO HAVE SILENCERS Cn O .0 0 U) m 3) ALL DOOR HARDWARE TO COMPLY WITH NFPA 101 AND FBC, AND SHALL NOT REQUIRE KEY OPERATION IN DIRECTION OF EXIT. 100 Al 3'- 0 7 r--07 1 3 4 WOOD I STAIN METAL PAINT I NONE 1 01 NO -- DOOR TYPES 4) ALL DOOR HARDWARE SHALL BE ACCESSIBLE PER 0 ADA AND FBC-ACCESSIBILITY. U) 5) SUGGESTED HARDWARE: SCHLAGE "AL" SERIES, VERIFY MATCH EXISTING DOOR AND FRAME AND MATCH EXISTING PRIOR TO ORDERING 6) DOORS SHALL COMPLY WITH FBC OPENING FORCE. 7) WOOD DOORS: MARSHFIELD DSP SERIES, ROTARY WHITE BIRCH VENEER, FACTORY DESIGNER STAIN. 8) HOLLOW METAL FRAMES: STEELCRAFT F SERIES, 16 GAUGE COLD ROLLED STEEL, FACTORY PRIME COAT, FACE WELDED. Al SINGLE SWING FLUSH LCA'A 003432 Architecture, Inc. 1975 Sansbury's Way Suite 108 West Palm Beach, FL 33411 Phone: (561) 493-4787 Fax: (561) 493-4786 REVISIONS / DATE # DATE Descri tion 0 00 � N � C- CL) C: �= 0 U) U. > C/) -a > -C 0 Cts °° a) '.� ) M Lc: E CQ a) U O '0 a Sr. Cn O .0 0 U) m LJL c) c) 00C N 0 U) LESLAW A. PROD. NO. 16181 DESIGNED BY LAC DRAWN BY LC DATE 07/18/16 SCALE AS SHOWN FLOOR PLAN NOTES SHEET A. 1 w ZO N M- N U m (Al ti cr g o:O QgN O JV Z z O DO0zw mwiZ QWw i<(n U¢F-m Zg mJ LLJa U �Q aU0�aodO�aoZ? oho ¢ ow3v¢ wujLL 3 w�w �i3�I¢ �= Q UO. W k-- z J l.� vi m a J~ J ZD N m O Q 0 \ F- \C) w O ¢ W'- w a ca vi o w °O- R X 3 O D' W X O N 0' ``'c�'mww C oaw=)Rz U JozOa 5� `''cam o O H a=z�Zm OER LL. n ;Q azwzw am --j a Q Na�aQ-! MF-ZQ < LLJ �' , �O O Z �Li J NQ OR CV L¢ mUN V M Z N S Z d'Q L6 o Q F- / l I\ U J c s� OD uZ-,L CID N „9-,Z „8-, L k 0-,2 rI- M Y � � >� > O W � jYUO: W E= W o fU N LLJ LL z d Z UJ Z t� 3 w w w / m W o�Qwa4� �ww<0 0 O Z co V - z U N o m It? 14 Qs. a cu O E `'' •• 07 g w co \ CD CL N W Z z � w w J C -) cn cn a CU n. U w W m LO Q - m to 0 I 0- a N V 00 a:: o J Q = Or \ / -f Li Z a. 3 v O I\ it N W R Q ) Q 0 O z w w N Z CL UO O in w ZO N M- N U m (Al ti cr g o:O QgN O JV Z z O DO0zw mwiZ QWw i<(n U¢F-m Zg mJ LLJa U �Q aU0�aodO�aoZ? oho ¢ ow3v¢ wujLL 3 w�w �i3�I¢ �= Q UO. W k-- z J l.� vi m a J~ J ZD N m O Q 0 \ F- \C) w O ¢ W'- w a ca vi o w °O- R X 3 O D' W X O N 0' ``'c�'mww C oaw=)Rz U JozOa 5� `''cam o O H a=z�Zm OER LL. n ;Q azwzw am --j a Q Na�aQ-! MF-ZQ < LLJ �' , �O O Z �Li J NQ OR CV L¢ mUN V M Z N S Z d'Q L6 o Q F- / l I\ U J c s� OD uZ-,L CID N „9-,Z „8-, L k 0-,2 rI- M OD OD uj xm Y >� > O W � jYUO: W E= W o fU N LLJ LL CY)M MG) d Z UJ Z t� m Z w w w / m W o�Qwa4� �ww<0 0 O Z co V - z U N o m It? 14 Qs. Q cu O E `'' •• 07 g w co \ CD CL N W Z 0) N H S r J C -) cn cn a CU n. U w W m LO Q - w ZO N M- N U m (Al ti cr g o:O QgN O JV Z z O DO0zw mwiZ QWw i<(n U¢F-m Zg mJ LLJa U �Q aU0�aodO�aoZ? oho ¢ ow3v¢ wujLL 3 w�w �i3�I¢ �= Q UO. W k-- z J l.� vi m a J~ J ZD N m O Q 0 \ F- \C) w O ¢ W'- w a ca vi o w °O- R X 3 O D' W X O N 0' ``'c�'mww C oaw=)Rz U JozOa 5� `''cam o O H a=z�Zm OER LL. n ;Q azwzw am --j a Q Na�aQ-! MF-ZQ < LLJ �' , �O O Z �Li J NQ OR CV L¢ mUN V M Z N S Z d'Q L6 o Q F- / l I\ U J c s� OD uZ-,L Q (n w „9-,Z „8-, L k 0-,2 3 �W N=U 7 � uj xm Y U O W � jYUO: W E= W LU w=� -59 C> LLJ w Q d Z UJ Z t� m Z w w w / m W o�Qwa4� �ww<0 0 O Z GTa ow z U N o U pp r 0 Z U 3 � N Z � a Q 07 g w co \ CD to 0 M W Z CD N H S V U a C -) cn '= a 0- V) w W m LO Q Q w ZO N M- N U m (Al ti cr g o:O QgN O JV Z z O DO0zw mwiZ QWw i<(n U¢F-m Zg mJ LLJa U �Q aU0�aodO�aoZ? oho ¢ ow3v¢ wujLL 3 w�w �i3�I¢ �= Q UO. W k-- z J l.� vi m a J~ J ZD N m O Q 0 \ F- \C) w O ¢ W'- w a ca vi o w °O- R X 3 O D' W X O N 0' ``'c�'mww C oaw=)Rz U JozOa 5� `''cam o O H a=z�Zm OER LL. n ;Q azwzw am --j a Q Na�aQ-! MF-ZQ < LLJ �' , �O O Z �Li J NQ OR CV L¢ mUN V M Z N S Z d'Q L6 o Q F- / l I\ „Z -,L k9 -,Z K 9-, L .0-,2 T� VeG9 uo;uAog ObZ apS ''PM81saaoeaS 'S OOSZ AbolojejueoilseE) ep!jol:j qjnoS JOI IUGWGAoidwl joijejul uZ-,L 0-7 Z w U J c s� OD uZ-,L Q (n w „9-,Z „8-, L k 0-,2 3 �W N=U 7 � uj xm Y U O W � jYUO: W E= W LU w=� -59 C> LLJ w Q d Z UJ Z t� m Z w w w / m W o�Qwa4� �ww<0 0 O Z GTa ow U Q U N o U pp r � Z U 3 � N Z � a Q ao O \ O g w co \ CD to 0 M LO Z CD N H S V U a C -) cn '= a 0- V) �i�J $ W m LO Q Q m to I � Q- 00 N V 00 a:: i J Q = Or \ / -f Li Z a. 3 v co I\ it R R C ) /I I\ w \ / „Z -,L k9 -,Z K 9-, L .0-,2 T� VeG9 uo;uAog ObZ apS ''PM81saaoeaS 'S OOSZ AbolojejueoilseE) ep!jol:j qjnoS JOI IUGWGAoidwl joijejul uZ-,L 0-7 Z w U J c s� OD uZ-,L Q (n w „9-,Z „8-, L k 0-,2 3 �W N=U 7 � uj xm Y U O W � jYUO: W E= W LU w=� -59 C> LLJ w Q d Z UJ Z t� m Z w w w / m W o�Qwa4� �ww<0 0 O Z GTa ow U Q U N o U pp r � Z U 3 � N Z � a Q ao O \ O g w co \ CD to 0 M LO Z CD N H S V U a C -) cn '= a V) �i�J $ J m N w Q Q ozm�zmm Q to �/ �� mLLJ Q- 00 N V 00 a:: aa J Q = cc -f Li Z a. 3 v R R C ) w \ / „Z -,L k9 -,Z K 9-, L .0-,2 T� VeG9 uo;uAog ObZ apS ''PM81saaoeaS 'S OOSZ AbolojejueoilseE) ep!jol:j qjnoS JOI IUGWGAoidwl joijejul uZ-,L 0-7 Z w U J c s� OD OHO mOFNF-- Q (n w N O�jUm Y 3 �W N=U 7 � uj xm Y U O W � jYUO: W E= W LU w=� -59 R r U J z OD 0%� Q N z Y z 7 � N N = w UN Q W E= W Q m C> LLJ w Q d Z UJ Z t� m Z w w w / m W o�Qwa4� �ww<0 0 O Z GTa ow U Q U N � U pp r � Z U 3 � N Z � a Q ao O \ O g w co \ CD to 0 M LO Z CD N H S V U a C -) cn '= V) �i�J $ J m N w Q Q ozm�zmm Q to R r U J J OD 0%� U a N z o z z ry0 N N = w UN Q W E= W Q m C> LLJ w Q d Z UJ Z t� m Z w w w / m W o�Qwa4� �ww<0 0 O Z Q ow U Q U Q N U= U pp m O ii W O ui= 0 a N z z a N N = w UN O z _<j 'o Q m C> LLJ w w _ ►- Z w w a w 0 O Z Q m N U Q U Q N U= U pp m � Z U 3 � N Z a a Q ao O \ O g w co \ CV U 0 to 0 M LO Z IR aZ N QYW J mw NOLVA313 L33S 46 iZ �o 0 ui= 0 a N s� tV � O W „Z/ N = w UN a _<j 'o „02 �.i C9 Z W N Q tV � w pOp U) 3 � w Ww H- 0 gwg OJ.. M II t\ „02 U z 0 r N a Q a Z W U) 0_ O w CL J Q m F- w a' Z R m MU J J X m N F— in a W 0 W q z_� m N r - -- U Z 2 Y O mEfw w 8W0m 3W'w N� 0 N W 4- _ Y =0 < D FLLJ - 5`YFStL� w O o � =5 Y O gwg (% m Z Z O� O O y3 U 0 J Z U N w =5z F- d U > V L� 0 m !n Z LL' Y O N H S V U a C -) I '= V) �i�J $ U m N w Q 0. ozm�zmm Q to 0 m Q- 00 N V 00 a:: aa J Q = cc -f Li Z � o �J 3 v U z 0 r N a Q a Z W U) 0_ O w CL J Q m F- w a' Z R m MU J J X m N F— in a W 0 W q z_� m N r - -- U Z 2 Y O mEfw w 8W0m 3W'w N� 0 N W 4- _ Y =0 < D FLLJ - 5`YFStL� w A GENERAL PROVISIONS 1. THE WORK SHALL CONSIST OF FURNISHING LABOR, EQUIPMENT, AND MATERIALS TO PROVIDE THE COMPLETE INTEGRATED AND PROPER FUNCTIONING SYSTEMS AS SHOW ON THE DRAWINGS. 2. ALL WORK SHALL BE DONE IN CONFORMANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, ALL APPLICABLE FEDERAL, STATE AND LOCAL REGULATIONS AND ORDINANCES. 3. ALL EQUIPMENT AND MATERIALS SHALL BE NEW OR EXISTING IN CONFORMANCE WITH APPLICABLE PROVISIONS OF NEMA, ANSI, UL ETC... 4. THE ELECTRICAL CONTRACTOR SHALL COORDINATE HIS WORK WITH THAT OF OTHER TRADES SO AS TO AVOID INTERFERENCES. 5. THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL LAYOUT OF ELECTRICAL SYSTEMS. FIELD VERIFICATIONS OF DIMENSIONS IS DIRECTED. 6. SECURE PERMITS AND INSPECTIONS REQUIRED BY STATE AND LOCAL LAWS AND ORDINANCES. 7. UPON COMPLETION OF THE WORK, FURNISH TO THE OWNER CERTIFICATES OF FINAL INSPECTION$ AND APPROVALS FROM AUTHORITIES HAVING JURISDICTION. 8. ALL WORKS SHALL BE GUARANTEED FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE OWNER. FROM AUTHORITIES HAVING JURISDICTION. 9. CIRCUITS ON THE PLANS ARE TO DETERMINE LOAD AND PANEL SIZE. THE CONTRACTOR SHALL PROVIDE CIRCUITS AND ROUTING TO SUIT JOB CONDITIONS, AND BALANCE THE CONNECTED LOAD. 10. FURNISH AND INSTALL LIGHTING FIXTURES AND LAMPS AS CALLED FOR ON THESE PLANS. FIXTURES SHALL NOT BE SUPPORTED BY THE CEILING GRID BUT BY GUY WARES FROM ABOVE. 11. CHECK EQUIPMENT FOR PROPER VOLTAGE, PHASE, AND AMP RATING BEFORE CONNECTION TO CIRCUITS. 12. THE ELECTRICAL SYSTEM SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED AS REQUIRED IN ARTICLE 250 OF THE NEC. ALL RACEWAYS TO HAVE EQUIPMENT GROUND CONDUCTOR, AND WHEN CROSSING BUILDING EXPANSION JOINTS, EXPANSION FITTING WITH BONDING JUMPERS SHALL BE USED. B• RACEWAYS 1. ALL WIRING SHALL BE INSTALLED IN APPROVED RACEWAYS. HOSPITAL GRADE ARMORED CABLE PROVIDING REDUNDANT GROUND IS ALLOWED. 2. MINIMUM CONDUIT SIZE SHALL BE 1/2" TRADE SIZE. 3. USE FLEXIBLE CONDUIT FOR SHORT FINAL CONNECTIONS TO VIBRATION EQUIPMENT SUCH AS MOTORS AND TRANSFORMERS. LIQUID -TIGHT FLEXIBLE CONDUIT SHALL BE USED IN DAMP AND WET LOCATIONS. 4. EXPOSED CONDUIT SHALL BE RUN PARALLEL TO BUILDING LINES. 5. DO NOT INSTALL CONDUITS LARGER THAN 1/3 THE SLAB THICKNESS IN CONCRETE SLABS. 6. PROVIDE APPROVED FIRE STOPPING MATERIALS AT ALL PENETRATIONS THROUGH FIRE RATED FLOOR AND WALLS TO PREVENT THE PASSAGE OF SMOKE, FIRE, TOXIC GAS OR WATER THROUGH THE PENETRATION EITHER BEFORE, DURING OR AFTER A FIRE, AS REQUIRED BY ARTICLE 300-21 OF THE N.E.C. 7. PROVIDE CABLE SUPPORTS IN ACCORDANCE WITH ARTICLE 300 OF THE N.E.C. 8. PROVIDE EXPANSION FITTINGS IN CONDUIT RUNS CROSSING STRUCTURAL EXPANSION JOINTS. 9. PANEL BOARDS SHALL BE CIRCUIT BREAKER TYPE. VERIFY NUMBER AND SIZES OF BREAKERS. C• CONDUCTORS 1. ALL WIRING SHALL BE COPPER. 2. CONDUCTORS SHALL BE RATED 60OV. WITH TYPE THHN INSULATION. 3. WIRES SIZES #10 AWG AND SMALLER SHALL BE SOLID CONDUCTOR WITH TYPE THHN INSULATION. WIRES SIZES STRANDED WITH TYPE THHN INSULATION. CONTRACTOR TO USE HIS BEST DISCRETION IN THE INSTALLATION, LOCAL CODES SUPERSEDE. 4. MINIMUM CONDUCTOR SIZE SHALL BE #12. CONTROL WIRING MAY BE SMALLER. D: LIGHTING PANELS 1. PROVIDE LIGHTING AND RECEPTACLE PANEL AS INDICATED ON THE PLANS AND AS SPECIFIED HEREIN. ALL PANELS SHALL BE DEAD FRONT,BOLT-ON CIRCUIT BREAKERS TYPE, PANELBOARDS AND SHALL BEAR THE U.L. LABEL AS WELL AS MEET ALL APPLICABLE NEMA REQUIREMENTS. 2. UNLESS OTHERWISE NOTED, TOP OF PANELS SHALL BE MOUNTED AT 6-A.F.F. TO TOP. 3. ALL PANELS SHALL HAVE TYPEWRITTEN CIRCUIT DIRECTORIES MOUNTED INSIDE OF DOOR. 4. PANELS SHALL BE SUITABLE FOR THE SERVICE RATING AND THE A.I.C. RATING INDICATED ON THE PANELS SCHEDULES. LABEL AS WELL AS MEET ALL APPLICABLE NEMA REQUIREMENTS. 5. ALL BREAKERS SHALL BE FULL SPACE, INDIVIDUAL FRAME TYPE. NO -PIGGY-BACK-OR TANDEM BREAKERS WILL BE PERMITTED. E: SAFETY SWITCHES 1. ALL NEW SAFETY SWITCHES SHALL BE HEAVY DUTY TYPE "HD", FUSIBLE OR NON -FUSIBLE WITH POLES, AMPERE AND SERVICE RATINGS AS INDICATED ON THE PLANS. LUGS SHALL BE U.L LISTED FOR CU. -AL 2. ENCLOSURES FOR SAFETY SWITCHES SHALL BE NEMA 1, EXCEPT FOR SWITCHES MARKED "WP" (WEATHERPROOF) SHALL BE NEMA 3R. F. FUSES 1. ALL NEW FUSES SHALL HAVE A 200,000 AMP RMS SYMMETRICAL INTERRUPTING RATING UNLESS OTHERWISE NOTED. LOWER RATING MAY BE USED ONLY UPON POWER COMPANY ISSUING A LETTER WITH FAULT CURRENT ANALYSIS JUSTIFYING LOWER RATING. A COPY OF A LEITER MUST BE FORWARDED TO THE ARCHITECT OF RECORD. 2. NEW FUSES RATED 0 TO 600 AMPS SHALL BE AS FOLLOW: a) CIRCUIT BREAKER PANEL PROTECTION - U,L. CLASS RK -1, DUAL ELEMENT (BUSSMANN "LOW PEAK" OR EQUAL) b) MOTOR CIRCUIT PROTECTION -U.L CLASS RK -5, DUAL ELEMENT (BUSSMANN "FUSETRON" OR EQUAL) 3. NEW FUSES RATED 601 AMPS OR LARGER SHALL RE U.L CLASS L TIME DELAY (BUSMANN -HI-CAP- OR EQUAL). O EMPTY CONDUIT FOR DATA MTS DUPLEX RECEPTACLE AT 18" A.F.F. U.O.N. OIN DUPLEX RECEPTACLE SPLIT CIRCUIT IST/ OR AS INDICATED ON PLAN TVa QUAD RECEPTACLE AT 18" A.F.F. U.O.N. ®- 240/208 RECEPTACLE 30 AMP OR LARGER ®- 240/208V RECEPTACLE 20 AMP e- SINGLE RECEPTACLE 20 AMP I = FLOOR FLUSH MOUNTED DUPLEX RECEPTACLE -qI- SWITCH -La THREE WAY SWITCH --D DIMMER SWITCH BZ BUZZER W/ TRANSFORMER FLOOR MOUNTED DATA/PHONE RECEPTACLE DATA/PHONE RECEPTACLE AT 18" AFF U.O.N. < FAN MOTOR Eh DISCONNECT SWITCH P.O.S. POINT OF SERVICE O EMPTY CONDUIT FOR DATA MTS DISCONNECT SWITCH OIN CEILING WIRELESS ACCESS POINT IST/ GENERATOR RECEPTACLE TVa TV LOCATION (POWER & DATA) R RELOCATED DEVICE GFI FOR PUMP. CKT A-14 (UNUSED WASHER CKT) ELECTRICAL PLAN SCALE: 11/4"=V-0" ALL NEW RECEPTACLES, SWITCHES AND WIRING IN PATIENT CARE AREAS SHALL BE HOSPITAL GRADE. ALL WIRING IN PATIENT CARE AREAS INCLUDING WIRING OF EQUIPMENT SHALL COMPLY WITH NEC (INSULATED REDUNDANT GROUND & GROUNDING RACEWAY) PROVIDE EQUIPMENT GROUNDING CONDUCTORS PER NEC SEE SHEET T.1 FOR PROJECT CLOSE-OUT NOTES DESIGN VALUES: SERVICE WIRES VOLTAGE DROP: 2% BRANCH CIRCUITS VOLTAGE DROP: 3% KEYNOTES O1 EXACT POSITION TO BE CONSULTED WITH TENANT IN FIELD PRIOR TO INSTALL O2 HEAVY DUTY 2 POLE 30A SWITCH FOR WATER HEATER (ABOVE CEILING) ORECEPTACLE FOR PORTABLE GENERATOR. SEE RISER DIAGRAM OREWIRE EXISTING RECEPTACLE AS SHWON. VERIFY LOCATION IN FIELD. IF NOT IN LOCATION SHOWN, INSTALL NEW RECEPTACLE O RECEPTACLE FOR CONDENSATE PUMP �6 RECEPTACLE FOR RECIRCULATING PUMP O7 CLOCK TYPE RECEPTACLE City of Boynton Beach All Electrical work shall comply with the 2011 National Electrical Code. This approval of the plans shall not prevent the Field Inspector from requiring the corrections of errors on such plans when in violation of the FBC or NEC in effect. LCA 'A 003432 Architecture, Inc. 1975 Sansbury`s Way Suite 108 West Palm Beach, FL 33411 Phone: (561) 493-4787 Fax: (561) 493-4786 REVISIONS / DATE PROD. NO. 16181 DESIGNED BY LAC DRAWN BY LC DATE 07/18/16 SCALE AS SHOWN ELECTRICAL PLAN NOTES SHEET E.1 0 0 00 E 0 1 I I..L� C M 0 cU�.�,,,, a) (D m �. E cu V -IF-+ C: U ■ 0 0 �^ vJ MM0 W � 0 N ♦J � 0 U) PROD. NO. 16181 DESIGNED BY LAC DRAWN BY LC DATE 07/18/16 SCALE AS SHOWN ELECTRICAL PLAN NOTES SHEET E.1 KEY NOTES: O CONNECT NEW SANITARY PIPE INTO EXISTING 4" SANITARY SYSTEM FIELD VERIFY EXACT LOCATION O CONNECT TO EXISTING COLD/ HOT WATER LINE AS SHOWN O RE -CIRCULATING PUMP O PIPING RUNS UNDER FLOOR SLAB. O PIPING RUNS ABOVE CEILING REUSE EXIST. P&T LINE, NEW PAN AND DRAIN TO MOP SINK BELOW O FOR NEW SINK: USE EXISTING I" COLD WATER LINE. INSTALL NEW HOT WATER LINE AS SHOWN. FOR EXISTING SINK: REUSE COLD WATER, REPLACE HOT WATER LINE AS SHOWN PLUMBING FIXTURE SCHEDULE NAME FIXTURE MODEL ACCESSORIES SK -1 SMALL SINK ELKAY BCR -15-2 SPEAKMAN COMMANDER FAUCET SC -3084 -LD, FLEXIBLE SUPPLY PIPES, ADJUSTABLE CHROME PLATED TRAP, AND MCGUIRE ANGLE STOPS. FIXTURE WATER PIPE SIZE NOMINAL SAN. SIZE MAXIMUM FLOW RATES SINK 1/2- 1 1/2" 2.0 GPM STAINLESS STEEL COVER SCREWED TO THREADED C.O. PLUG FACE OF WALL WALL TYPE CLEANOUT N.T.S. HANGER ROD LOCKING NUT HANGER ROD -----,SUPPORT NUT SUPPORT NUT-------"- HEAVY DUTY CLEVIS HEAVY DUTY CLEVI HANGER HANGER PIPE :.:. VAPOR BARRIER INSULATION 16 GAUGE ZINC COATED SHEET STEEL SADDLE AT LEAST 8" LONG CLEVIS HANGER CLEVIS HANGER SINGLE HORIZONTAL RUNS SINGLE HORIZONTAL RUNS NO VAPOR BARRIER INSULATION WITH VAPOR BARRIER INSULATION VYELDS WEB MEMBERS 01 AWE ON EACH FF HANGER NUT SIDE OF WEBMOAM Eff ON TW OF BOTTOM 04M Sfln BENT StRIIP 1 �/� � \ JOISTS BEIWEEM PANEL 3/160 OVER VERT. Ppm, WE FOR LOAD LM OF . AMGI.ES BOTTOM CHM OF JOffr STEEL JOIST W:s:aa-.1ff_1►T1 BEAM D NOTE: ALL TRAPS TO BE 1 1/2" U.O.N. MIN. SLOPE OF DRAINAGE PIPING SHALL BE 1/4" PER 1 FT. PLUMBING FIXTURES SHALL COMPLY WITH FBC PLUMBING AND ACCESSIBILITY NOTE: CONTRACTOR TO COORDINATE ALL HEIGHTS AND EXACT LOCATIONS OF ALL UTILITIES WITH TENANT'S EQUIPMENT SUPPLIER PROVIDE BALL TYPE SHUT-OFF VALVES FOR FIXTURE SUPPLY LINES. PLACE VALVES ABOVE CEILING BEFORE LINES ENTER PARTITION CAVITY. SIZE SHALL MATCH PIPE SIZE. PLUMBING SYMBOLS + ABBREVIATIONS NOTE: NOTE: NOT ALL SYMBOLS & ABBREVIATIONS APPLY 0 'o ° In / k RN HOT 51NK5 BOT� � CONN T TO / CON�EG I WATER RISER DIAGRAM SCALE: N.T.S. L \ NOTE: WATER LINES ARE 3/4" U.O.N. MATERIAL: HARD DRAWN SEAMLESS COPPM v= - GIRL• I AGE P��P I i� RE UGIT TU� �OEFf f II,p d PTip� i 1 FIE GT � 1Aj SANITARY RISER -DIAGRAM NTS WATER/SEWER PLAN SCALE: 1/4"=l' -O" HOT WATER t--(110) 1 3/4" C.W. RETURN HW 3/4" H.W. OUT Il 120 VOLT POWER AN WATER HEATER DISCONNECT SWITCH 8 SET AT 110 DEC. CIRCULATION PUMP----,-' TACO-006-BC4 OR EQUAL 115V 3/4' EXPANSION 3/4" RELIEF (COPPER) TANK 3/4" CPVC DRAIN EXPANSION TO MOP SINK BELOW VALVE WATTS #530C REPLACE bf,'AIN4- FAN -�� 20 GAL: EWH WAT E R H EAT E R__P 1 P! NG AG RAM SCALE: N.T.S. LCAAA 003432 Architecture, Inc. 1975 Sansbury's Way Suite 108 West Palm Beach, FL 33411 Phone: (561) 493-4787 Fax: (561) 493-4786 I REVISIONS / DATE HOT WATER PIPE HW COLD WATER PIPE CW HOT WATER RECIRCULAING HWR 0 CHECK VALVE CV 0 BALL VALVE (SHUT-OFF VALVE) SOV S--SD--S STORM DRAINAGE PIPE SD SANITARY LINE SAN —CD—, CONDENSATE LINE CD VENT LINE --P&T-i PRESSURE RELIEF P&T --DP-i DRAIN PAN DP o HOSE BIBB W/ VACUUM BREAKER & HB + SHUT-OFF VALVE -0 _ � WATER HAMMER ARRESTOR WHA WATER CLOSET WC CCS VENT THRU ROOF VTR LAVATORY LAV m JANITOR'S SINK JS 0 U FLOOR SINK FS FLOOR DRAIN FD URINAL UR W SHOWER SH o ELECTRIC WATER COOLER EWC' a�U DRINKING FOUNTAIN DF ELECTRIC WATER HEATER EWH ABOVE FINISH FLOOR AFF BELOW FINISH FLOOR BFF FLOOR CLEANOUT FCO CLEANOUT TO GRADE CTG WALL CLEANOUT WCO 0 ROOF DRAIN RD MOP SINK MS SINK SK NOTE: NOTE: NOT ALL SYMBOLS & ABBREVIATIONS APPLY 0 'o ° In / k RN HOT 51NK5 BOT� � CONN T TO / CON�EG I WATER RISER DIAGRAM SCALE: N.T.S. L \ NOTE: WATER LINES ARE 3/4" U.O.N. MATERIAL: HARD DRAWN SEAMLESS COPPM v= - GIRL• I AGE P��P I i� RE UGIT TU� �OEFf f II,p d PTip� i 1 FIE GT � 1Aj SANITARY RISER -DIAGRAM NTS WATER/SEWER PLAN SCALE: 1/4"=l' -O" HOT WATER t--(110) 1 3/4" C.W. RETURN HW 3/4" H.W. OUT Il 120 VOLT POWER AN WATER HEATER DISCONNECT SWITCH 8 SET AT 110 DEC. CIRCULATION PUMP----,-' TACO-006-BC4 OR EQUAL 115V 3/4' EXPANSION 3/4" RELIEF (COPPER) TANK 3/4" CPVC DRAIN EXPANSION TO MOP SINK BELOW VALVE WATTS #530C REPLACE bf,'AIN4- FAN -�� 20 GAL: EWH WAT E R H EAT E R__P 1 P! NG AG RAM SCALE: N.T.S. LCAAA 003432 Architecture, Inc. 1975 Sansbury's Way Suite 108 West Palm Beach, FL 33411 Phone: (561) 493-4787 Fax: (561) 493-4786 I REVISIONS / DATE PROJ. NO. 16181 DESIGNED BY LAC DRAWN BY LC DATE 07/18/16 SCALE AS SHOWN PLUMBING PLAN NOTES DIAGRAMS DETAILS SHEET P.1 0 0 00 N E o vJ .,�� -0 _ � cf) 0 CCS (D (n m CU 0 U C: 0 C: W 0 o ._ o � CO a�U C)o C 00 N 0 U) PROJ. NO. 16181 DESIGNED BY LAC DRAWN BY LC DATE 07/18/16 SCALE AS SHOWN PLUMBING PLAN NOTES DIAGRAMS DETAILS SHEET P.1