DRAWINGS14' I I 11n
11„ 4
1 R,
14-
lit
( I I
IIff I
o lit
- c_ i
i
RES OOM STOR.
108 R = ( -
'-2l 11-101 3'-711 0---4-3l-T/
4
3'-7„4 4 11n
14
i 1n O
I � I
R (TEST RO ( R�
� � I 107! { I I _
n
1HAL-- .I
( 1 i
12
i�
�14„ — 4 --4'-- rr 11n
_ _ 4 r
N .�
R j TOk. — M
SOU OM I R 108 ; `
106 lt�___� _ - E R
i
ESTI OOiM °° i
105
it
�14 11n 1 �,i—
i
41 —
-
i I I 1„9 I
' LI
i
LAB/ EAI f R
�—
TO
04 i R
I
1„
if i
ifl
SSU I TE 102 i
( m
i
, i e
I ( i
I R i I R 1
i t
iI `�
A Ilit
PLU
IREC PTI N ►�
�-I-----,-
21
I
FIRE PLAN SUITE 102 4�
PIPE DETAIL
SCALE: N.T.S.
MAXIMUM DISTANCE BETWEEN HANGER
SIZE NOMINAL PIPE
EXISTING TY -FRB BRASS UPRIGHT ON 1" x 2'-0" SPRIG UP
O PLUG
(2) REMOVE UPRIGHT AND SPRIG UP AND PLUG EXISTING 1" OUTLET
QR
(16) REMOVE UPRGHT AND INSTALL NEW TY -FRB CHROME PENDENT, Q.R. 155 DEGREE, 1/2',5.6K
QTY.
NEW WALL
Q
TYCO TY -FRB -323
EXISTING PIPE
155
NEW PIPE
(INCHES)
3/4”
1"
1 %"
1 %"211
g
2%"3"
jurisdiction. Failure to do so may impair
3%"
4"
5"
6"
8"
STEEL PIPE(EXCEPT)
ordinary hazard, commercial occupan-
cies such as banks, hotels, and shop-
The owner is responsible for maintain -
ping malls.
ing their fire protection system and
devices in proper operating condition.
THREAD LIGHTWALL
N/A
12'-0"
12'-0"
15'-0"
15'-0"
16-0"
15'-0"
15'-0"
15'-0"
15'-0"
15'-0"
15'-0"
STEEL PIPE
THREAD LIGHTWALL
N/A
12'-0"
12'-0"
12'-0"
12'-0"
12'-0"
12'-0"
N/A
N/A
N/A
N/A
N/A
CPVC PIPE
5'-6"
6'-0"
6'-0"
6'-6"
7'-0"
8'-0"
9'4"
10'-0"
N/A
N/A
N/A
N/A
GENERAL NOTES
1. ALL MATERIAL AND LABOR TO BE IN ACCORDANCE W/ NFPA-13(07) AND THE LOCAL A.H.J.
2. THIS ENTIRE PROJECT IS TO BE DESIGNED AND SPACED PER NFPA-13(07) LIGHT HAZARD
OCCUPANCY WITH A MAX SPACING OF 225 SQ.FT.
4. NEW PIPING TO BE "XL" OR APPROVED EQUAL.
5. NEW FITTINGS TO BE CAST IRON
6. ALL PIPE LENGTHS ARE TO BE "CUT LENGTH"
7. ALL HANGERS TO BE IN ACCORDANCE W/ NFPA-13(07) TABLES 9.2.2.
8. ALL EXISTING WATER CONTROL VALVES TO BE MONITORED. (BY OTHERS)
9. EXISTING FIRE PROTECTION AND FIRE ALARM SYSTEMS ARE TO REMAIN. THESE SYSTEMS
WERE INSTALLED UNDER A SEPARATE PERMIT. NO WORK TO BE DONE IN ANY OTHER AREAS
THAN SHOWN ON THIS PLAN.
SCOPE OF WORK
J&J FIRE PROTECTION SHALL PLUG (2) EXISTING SPRIG UP OUTLETS & REMOVE (16) EXISTING
UPRIGHTS FROM 1" OUTLETS AND INSTALL PENDENT HEADS FOR NEW CEILING LAYOUT.
SPRINKLER LEGEND
O
EXISTING TY -FRB BRASS UPRIGHT ON 1" x 2'-0" SPRIG UP
O PLUG
(2) REMOVE UPRIGHT AND SPRIG UP AND PLUG EXISTING 1" OUTLET
QR
(16) REMOVE UPRGHT AND INSTALL NEW TY -FRB CHROME PENDENT, Q.R. 155 DEGREE, 1/2',5.6K
QTY.
NEW WALL
Q
TYCO TY -FRB -323
EXISTING PIPE
155
NEW PIPE
NOTE:
633.21 DEFINITIONS. --AS USED IN THIS CHAPTER
THE DEFINITIONS IN THIS SUBSECTION MUST NOT
BE CONSTRUED TO INCLUDE FIRE PROTECTION
ENGINEERS OR ARCHITECTS AND DO NOT LIMIT
OR PROHIBIT A LICENSED FIRE PROTECTION
ENGINEER OR ARCHITECT FROM DESIGNING ANY
TYPE OF FIRE PROTECTION SYSTEM. HOWEVER,
PERSONS CERTIFIED AS A CONTRACTOR 1,
CONTRACTOR II, OR CONTRACTOR IV UNDER
THIS CHAPTER MAY DESIGN FIRE PROTECTION
SYSTEMS OF 49 OR FEWER HEADS, AND MAY
DESIGN THE ALTERATION OF AN EXISTING FIRE
SPRINKLER SYSTEM IF THE ALTERATION
CONSISTS OF THE RELOCATION, ADDITION, OR
DELETION OF NOT MORE THAN 49 HEADS,
NOTWITHSTANDING THE SIZE OF THE EXISTING
FIRE SPRINKLER SYSTEM. SUCH PLANS MAY NOT
BE REQUIRED BY ANY LOCAL PERMITTING
AUTHORITY TO BE SEALED BY A REGISTERED
PROFESSIONAL.
NOTE:
DECK -17'-0" A.F.F
BRANCH LINE HEIGHT - 14'-6" A.F.F.
CEILING HEIGHT - 9'-0" A.F.F.
16.2.1.6 Modifications that cannot be isolated, such as relo-
cated drops, shall not require testing in excess of system
working pressure.
NEW SPRINKLER SCHEDULE
SYMBOL
MANUFACTURER MODEL #
RESPONCE
TEMP
K -FACTOR
ORIFICE
QTY.
REMARKS
Q
TYCO TY -FRB -323
Q.R.
155
5.6K
1/2"
16
CHR. PEND.
Worldwide www.tyco-fire.com
Contacts
Series TY -FRB, 5.6 K -factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
cenerat
UM
B.C.
Description
The eSeries TY -FRB Sprinklers
described herein must be installed and
L.D.
DATE
maintained in compliance with this doc-
01-19-2015
The TYCO Series TY -FRB, 5.6 K -factor,
ument, as well as with the applicable
1/4"-1'-0"
Upright (TY313) and Pendent (TY323)
Sprinklers described in this data sheet
are quick response, standard coverage,
standards of the National Fire Protec-
tion Association, in addition to the stan-
dards of any other authorities having
SHEET
g
decorative 3 mm glass bulb -type spray
jurisdiction. Failure to do so may impair
OF 1 SHEETS
sprinklers designed for use in light or
the performance of these devices.
ordinary hazard, commercial occupan-
cies such as banks, hotels, and shop-
The owner is responsible for maintain -
ping malls.
ing their fire protection system and
devices in proper operating condition.
The recessed version of the Series TY-
The installing contractor or sprinkler
FRB Pendent Sprinkler, where applica-
manufacturer should be contacted with
ble, is intended for use in areas with a
any questions.
finished ceiling. This recessed pendent
sprinkler uses one of the following:
Sprinkler
• A two-piece Style 15 Recessed`f
Escutcheon with recessed adjust-
Identification`
ment up to 5/8 inch (15,9 mm) from
v
the flush pendent position.
�+ `.
Number ((Slap)
• A two-piece Style 20 Recessed
Escutcheon with recessed adjust-
TY313 ....... Upright 5.6K, 1/2" NPT
ment up to 1/2 inch (12,7 mm) from
TY323 ...... Pendent 5.6K, 1/2' NPT
,
the flush pendent position.
The adjustment provided by the
Technical
Recessed Escutcheon reduces the
accuracy to which the fixed drops
Data
Finishes
Sprinkler: Natural
pipe
to the sprinklers must be cut.
Brass, Chrome
Plated, Pure White (RAL 9010) and
Intermediate level versions of Series
Approvals
Signal White (RAL 9003).
TY -FRB Sprinklers are described in
UL and C -UL Listed
Recessed Escutcheon: White Coated,
Technical Data Sheet TFP367. Sprin-
FM and VdS Approved
Chrome Plated, or Brass Plated
kier guards and shields are described
CE Certified
Physical Characteristics
in Technical Data Sheet TFP780.
Maximum Working Pressure
Frame ................... Bronze
175 psi (12.1 bar)
Button .............. Brass/Copper
250 psi (17.2 bar)`
Sealing Assembly ......... Stainless
The maximum working pressure of 250 psi
Steel w/TEFLON
Bulb
(17.2 bar) only applies to the listing by Un-
• • • ............ • .... , .Glass
derwriters Laboratories, Inc. (UL).
Compression Screw........ Bronze
IMPORTANTDischarge
Coefficient
Deflector ................. Bronze
Always refer to Technical Data
K=5.6 GPM/psi}/2 (80,6 LPM/bar7/2)
Sheet TFP700 for the `INSTALLER
Temperature Rating
WARNING" that provides cautions
135°F (57°C)
with respect to handling and
155°F (68°C)
installation of sprinkler systems and
175°F (79°C)
components. Improper handling and
200°F (93°C)
installation can permanently damage
286°F (141°C)
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.
Page 1 of 4
DRQ PrIr II nrATTARI.
JANUARY 2013
i 'ill No.
P .',7
TFP172
KEY PLAN
SCAT F- N T q
4628 N. Hiatus Rd
Sunrise, FL 33351
Telephone 954.747.4941
Facsimile 954.747.0553
REVISIONS
LICENSE NO.
SEAL
BY
FIRE
SPRINKLER
PROTECTION
PLAN
SHEET TITLE
DRAWN
B.C.
CHECKED
L.D.
DATE
01-19-2015
SCALE
1/4"-1'-0"
JOB. NO.
SHEET
FPml
OF 1 SHEETS