PERMIT DOCUMENTS A-I CONSULTING ENGINEERS, INC
ROOF STRUCTURES CONSULTING UPLIFT TEST EXPERTS
LAB.CERTIFICATION No.01-1224-5
4383 SW 70 CT 119 LA%H.FL 33155
TEL: 305-740-9550 sFAX: 305-740-9550
August 22, 2017
City of Boynton Beach
Building and zoning Department
100 E. Boynton Beach Blvd.
Boynton Beach, FL 33425
CONTRACT: Al Pro Service Corp.
JOB SITE: 301 SE 12(11 Ave Boynton Beach, FL
PERMIT No: 1700002287
INSPECTION REPORT
After a visual inspection performed at the above referenced location, and photo provided by
roofing contractor we hereby certify that:
Flat Roof •
Slope= 1/8" / 12 pitch/ 10 ft mean hr.
5/8" PLYWOOD DECK (renail (@ 6" field and 4" corner)
Base Sheet= 1 Base #75 1 1/4 RS nails 5/8 tin cap,
FIELD 9 OC @ LAP 2 ROWS @ 9 OC _
PERIMETER 6 OC @ LAP 4 ROWS @ 6 OC
CONER 6 CC @ LAP 4 ROWS @ 6 CC
2 PLY IV Hop mop with 18" side lap
. 1 Ply Mineral Surfaced Cap Sheet Hop mop'with 3" side lap and 6" end lap.
Product used= G.A.F Material Corp NOA 13-1022.15
To the best of my knowledge, belief and professional opinion, it was found that the roof
installation complies with the minimum requirements of the Florida Building 2014 Codes 5ta
. Edition and approved Permit package.
Please do not hesitate to contact my office if you have questions regarding this inspection.
Sincerely,